infection prevention and control (ipc) cdc ......programme emergencies bibliography •world health...
TRANSCRIPT
HEALTH
programmeEMERGENCIES
INFECTION PREVENTION AND CONTROL (IPC)
CDC/WHO GLOBAL WEBINAR SERIES
SEVERE ACUTE RESPIRATORY INFECTION (SARI)
TREATMENT FACILITY
VENTILATION SYSTEMS AND MINIMUM REQUIREMENTS
Luca Fontana
environmental toxicologist – epidemiologist
World Health Organization – Emergency Program
Health & Technical team– WHO/WHE/OSL
PRACTICAL IPC CONSIDERATIONS IN THE FIGHT AGAINST COVID-19
23rd July 2020
HEALTH
programmeEMERGENCIES
Objectives
By the end of this lecture, you will be able to:
• Understand the environment and engineering controls measures within a SARI treatment center
• Explain the ventilation systems and minimum requirements
• Describe Pro and cons of different ventilation systems
Nothing to disclose: I have no financial relationships with commercial entities
producing healthcare-related products and/or services
Crabb, J., Ramage, J., Smith, D.,. IFHE Ventilation Team. Computational Fluid Dynamic
Simulation for Accra COVID’19 Field Hospital. WHO
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Controlling exposures to
hazards is the fundamental
method of protecting
workers, patients and visitors
Most effective
Less effective
Physically remove the hazard
Replace the hazard
Isolate people from the hazard
Change the way people work
Protect the worker with Personal Protective Equipment
CDC, Centers for Disease Control and Prevention. Hierarchy of controls.
Retrieved July 16, 2020, from https://www.cdc.gov/
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Most effective
Less effective
Physically remove the hazard
Replace the hazard
Isolate people from the hazard
Change the way people work
Protect the worker with Personal Protective Equipment
CDC, Centers for Disease Control and Prevention. Hierarchy of controls.
Retrieved July 16, 2020, from https://www.cdc.gov/
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Areas distribution
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Proper staff and patient’s flows
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Finishing and furniture
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Katwa Ebola Treatmente Center, DRC, 2018. Used with permission. Dr Ian Crozier
Technical solution, transparent surfaces
HEALTH
programmeEMERGENCIES
SARI treatment center & IPC
Technical solution, transparent surfaces & glove box
Sampling box. Time of India
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
The purpose of ventilation
is to provide healthy air for
breathing by both diluting
the pollutants originating in
the building and removing
the pollutants from it.
Silenzi, A., WHO. 2020
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
Building ventilation has three basic elements:
✓ Ventilation rate — the amount of outdoor air that is provided
into the space, and the quality of the outdoor air;
✓ Airflow direction — the overall airflow direction in a building,
which should be from clean zones to less-clean zones; and
✓ Air distribution or airflow pattern — the air should be
delivered to each part of the space in an efficient manner and
the airborne pollutants generated in each part of the space
should also be removed in an efficient manner.
Crabb, J., Ramage, J., Smith, D.,. IFHE Ventilation Team. Computational Fluid Dynamic
Simulation for Accra COVID’19 Field Hospital.
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
There are three methods that may be used to ventilate a building:
Atkinson, J., Chartier, Y., Pessoa-silva, C. L., Jensen, P. & Li, Y. Natural Ventilation for
Infection Control in Health-Care Settings Edited by : WHO Publ. (2009).
Natural ventilation
Natural forces (e.g. winds) drive
outdoor air through the building
openings such as windows, doors,
solar chimneys, wind towers and
trickle ventilators.
Mechanical ventilation
Mechanical fans drive mechanical
ventilation. Fans can either be
installed directly in windows or
walls, or installed in air ducts for
supplying air into, or exhausting
air from, a room.
Hybrid ventilation
Hybrid (mixed-mode) ventilation
relies on natural driving forces to
provide the desired (design) flow
rate. It uses mechanical
ventilation when the natural
ventilation flow rate is too low.
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
World Health Organization (WHO). (2020). Infection prevention and control during health care
when COVID-19 is suspected. Who, i, 1–5.
https://apps.who.int/iris/rest/bitstreams/1272420/retrieve
Area Natural Ventilation Mechanical Ventilation
AGPs are NOT performed Average 60 L/s/patient At least 6 air changes per hour (ACH)
AGPs are performed Average 160 L/s/patient Old building:At least 6 air changes per hour (ACH)
New building:At least 12 air changes per hour (ACH)
HEALTH
programmeEMERGENCIES
Pro and cons of different ventilation systems
Area Mechanical Ventilation Natural Ventilation Hybrid Ventilation
Advantages • Suitable for all climates and weather
• More controlled and comfortable environment
• Smaller range of control of environment by occupants
• Suitable for warm and temperate climates• Lower capital, operational and maintenance• Capable of achieving high ventilation rate• Large range of control of environment by occupants
• Suitable for most climates and weather
• Energy-saving• More flexible
Disadvantages • Expensive to install and maintain
• Reported failure rate in delivering the required outdoor ventilation rate
• Potential for noise from equipment
• Easily affected by outdoor climate and/or occupant’s behaviour
• More difficult to predict, analyse and design• Reduces comfort level of occupants when hot, humid or cold• Inability to establish negative pressure in isolation areas, but
may be provided by proper design; depends on situation• Potential for noise intrusion• High-tech natural ventilation shares some of the limitations
and disadvantages of mechanical ventilation
• May be expensive• May be more
difficult to design
Atkinson, J., Chartier, Y., Pessoa-silva, C. L., Jensen, P. & Li, Y. Natural Ventilation for
Infection Control in Health-Care Settings Edited by : WHO Publ. (2009).
HEALTH
programmeEMERGENCIESAtkinson, J., Chartier, Y., Pessoa-silva, C. L., Jensen, P. & Li, Y. Natural Ventilation for
Infection Control in Health-Care Settings Edited by : WHO Publ. (2009).
ACH or l/s
The ventilation flow rate can be referred to as either an absolute ventilation flow rate in l/s or m3/s, or an air-change rate relative to the volume of the space (ACH) .¹
ACH= [ventilation rate (l/s) × 3600 (s/hr)] × 0.001 (m3/s)]/[room volume (m3 )] or
Ventilation rate (l/s) = ACH× room volume (m3) × 1000 (l/m3 )/3600 (s/hr).¹
The steady-state concentration of a pollutant is determined by the pollutant generation rate and the ventilation rate (absolute ventilation flow rate), but not the air-change rate
Therefore, for the purpose of controlling long-term exposure to pollutants, the ventilation rate should be specified, not the air-change rate. ¹
Considering the situation of concentration decay without a constant pollutant source, the decay rate is governed by the air-change rate, not the ventilation rate.
Therefore, for the purpose of reducing the pollutant concentration in a short time after a sudden release of a pollutant, the air-change rate is the most appropriate. ¹
Ventilation systems and minimum requirements
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
Area Natural Ventilation Mechanical Ventilation
AGPs are performed Average 160 L/s/patient New building:At least 12 air changes per hour (ACH)
324
m3/h
576
m3/h
Some example: one patient, same room (3x3x3m), different ventilation system
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
Area Natural Ventilation Mechanical Ventilation
AGPs are performed Average 160 L/s/patient New building:At least 12 air changes per hour (ACH)
1.728
m3/h
Some example: three patients, same room (3x3x3m), different ventilation system
324
m3/h
HEALTH
programmeEMERGENCIES
Ventilation systems and minimum requirements
Area Natural Ventilation Mechanical Ventilation
AGPs are performed Average 160 L/s/patient New building:At least 12 air changes per hour (ACH)
324
m3/h
2.592
m3/h
Some example: one patient, different rooms (6x6x6m and 3x3x3m), same ventilation system
HEALTH
programmeEMERGENCIES
Thank you
19 July 2020
Luca Fontana
environmental toxicologist – epidemiologist
World Health Organization – Emergency Program
Health & Technical team– WHO/WHE/OSL
HEALTH
programmeEMERGENCIES
Bibliography
• World Health Organization (WHO). Infection prevention and control of epidemic- and pandemic-prone acute respiratory infections in health care. WHO
Guidel. 1–156 (2014).
• World Health Organization (WHO). (2020). Infection prevention and control during health care when COVID-19 is suspected. Who, i, 1–5.
https://apps.who.int/iris/rest/bitstreams/1272420/retrieve
• Atkinson, J., Chartier, Y., Pessoa-silva, C. L., Jensen, P. & Li, Y. Natural Ventilation for Infection Control in Health-Care Settings Edited by : WHO Publ.
(2009).
• World Health Organization (WHO). (2020). Severe Acute Respiratory Infections Treatment Centre. World Health Organization Publications, March,
120. World Health Organization
19 July 2020