Information about IE2, IE3 and NEMA motor changeover for blowers and side channel blowers Including list of all affected Side Channel Blowers

Upload: lyhanh

Post on 17-Dec-2018

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

Information about IE2, IE3 and NEMA motor changeover for blowers and side channel blowers

Including list of all affected Side Channel Blowers

Page 2: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

New standards and legal requirements

The new standard and its scope

With the aim of reducing energy consumption and therefore CO2 emissions worldwide, the International Elec-trotechnical Commission (IEC) has developed a new standard. The „IEC 60034-30-2008“ rates 50 and 60 Hz asynchronous motors with a power range from 0.75 kW to 375 kW in terms of their degree or class of effi ciency, thereby taking the place of the earlier re-gulations which varied between different countries in Europe. It also defi nes which motors are affected in different parts of the world, and what exceptions apply. In all member countries of the European Union, EU Regulation 640/2009 is defi ni-tive for application of the new standard

In North America the EISA (Energy Inde-pendence Security Act) comes into force in December 2010, and specifi es mini-mum effi ciency requirements for NEMA motors (60 Hz).

The new energy effi ciency classes

The standard IEC 60034-30 defi nes the new effi ci-ency classes (IE = International Effi ciency):

• IE1 (Standard Effi ciency)• IE2 (High Effi ciency) (comparable to NEMA Energy Effi cient)

• IE3 (Premium Effi ciency) (comparable to NEMA Premium)

Coming into force of the legal regulations (Europe and USA)*

*further countries see following page

2 Elektror IE2 / IE3

16.06.2011, EuropeIE2 for all motors from 0,75 kW to 375 kW

01.01.2015, EuropeIE3 for all motors from 7,5 kW to 375 kW (or IE2 with frequency converter)

01.01.2017, EuropeIE3 for all motors from 0,75 kW to 375 kW (or IE2 with frequency converter)

19.12.2010, USANEMA Premium (IE3) for all fl ange motors with foot from 1 HP to 200 HP(without foot NEMA Energy Effi cient (IE2) is suffi cient)

Page 3: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

Elektror IE2 / IE3 3

Global requirements in detail

CountryVoltage/

Frequency

Power

range

No.

of

Poles

Law/

Regulation

Regulation

of minimum

effi ciency

Outlook

Europe 400 V+/- 10%; 50 Hz

0.75 kW-375 kW

2-6 EC No. 640/2009

IE2 compulso-ry 16.6.2011

1.1.2015: IE3 from 7.5 to 375 kW or IE2 motor + frequency converter1.1.2017: IE3 from 0.75 to 375 kW or IE2 motor + frequency converter

Russia up to 690 V 1 kW-400 kW

all GOST R 51677-2000

No

Switzerland 400 V+/- 10%; 50 Hz

0.75 kW-375 kW

2-6 EnV IE2 compulso-ry 1.7.2011

From January 2010: IE1From July 2010: IE2, for extension of regulati-ons in 2015 and 2017, Swiss energy act will be revised in time

Turkey 400 V+/-10%; 50 Hz

0.75 kW-375 kW

2-6 EC No. 640/2009

IE1 No decision yet. Will probably follow the EU timeline

USA 480 V+/- 10%; 60 Hz

1 HP-200 HP

2-6 Nema EPAct EISA 2007

IE3 compulso-ry 19.12.2010

Until 18.12.2010: NEMA EPAct - IE2From 19.12.2010: EISA - IE3

Canada 480 V/575 V+/- 10%; 60 Hz

1 HP-200 HP

2-6 CSA C390 IE3 compulso-ry 1.1.2011

Until 31.12.2010: NEMA EPAct - IE2From 1.1.2011: EISA - IE3

Mexico 460 V+/- 10%; 60 Hz

1 HP-200 HP

2-6 Nema EPAct EISA 2007

IE3 expected Expected to follow USA timeline

Brazil 220 V/380 V/440 V/ 460 V/480 V+/- 10%; 60 Hz

0.75 kW-250 kW

2-8 NBR 17094-1Regulation 553

IE2 compulso-ry 8.12.2009

Chile 380 V/400 V/420 V/ 440 V/460 V/690 V+/- 10%; 50 Hz

0.75 kW-7.5 kW

2-6 NCH 3086 IE2 compulso-ry 4.1.2011

China 380 V+/- 10%;50 Hz

0.55 kW-315 kW

2-6 GB 18613-2006 IE2 compulso-ry 1.7.2011

Scope ot motor output will be changed to 0.75 kW - 375 kW in near future.

Hong Kong 380 V+/- 10%; 50 Hz

0.75 kW-375 kW

2-6 Mandatory Buildings Energy Effi ciency Bill

IE2 Introduc-tion stage sin-ce Dec 2009

Effi ciency bill will follow the model of the EU (see Europe)

India 415 V/690 V+/- 10%; 50 Hz

0.37 kW-315 kW

2-8 IS:4889/IS:12615-2004

IE2 expected 2013

IE1/IE2-based regulations assumed 2013

Israel 400 V+/- 10%; 50 Hz

0.75 kW-185 kW

2-8 SI 5289 IE2 compulso-ry 1.2.2008

Review of IS 5289 at the end of 2010 and chan-ging it in line with European law

Japan 200/220/400/440 V+/- 10%; 50/60 Hz

0.2 kW-160 kW

2-6 JIS C 4210JIS C 4212

IE2 expected No law, effi ciency per JIS standard IEC 60034-30 will be integrated into JIS in 2010

Korea Bis 600 V+/-10%; 60 Hz

0.75 kW-200 kW

2-6 KS C 4202 IE2 compulso-ry 1.7.2008

1.7.2010: IE2 from 0.75 kW to 200 kW

Singapore 415 V+/- 10%; 50 Hz

1.1 kW-90 kW

2-4 SS530:2006 IE2 Only government projects compulsory in IE2

Taiwan <600 V+/- 10%; 60 Hz

0.37 kW-200 kW

2-8 CNS 14400 IE2 No plan to adapt IEC 60034-30 right now. IE2 motors can be certifi ed acc. to CNS 14400 as high-effi ciency motors

United ArabEmirates

400 V+/- 10%; 50 Hz

0.75 kW-375 kW

2-6 EC Nr. 640/2009 IE2 from 16.6.2011 as recommenda-tion

No local standards/demands on this effi ciency levels, just following EU (see Europe)

SaudiArabia

380 V/460 V+/- 5%; 60 Hz

all all no regulation No

Republic of South Africa

400 V/525 V+/- 10%; 50 Hz

0.75 kW-375 kW

2-6 IEC 60034-30 IE1 IE2 is being recommended. Implementa-tion of the IEC standard is probably not foreseen before 2016

Australia/ New Zealand

415 V/690 V+ 10%/- 6%; 50 Hz

0.73 kW-186 kW

2-8 AS/NZS 1359.5-2004

IE2 1.4.2006IE3 expected

IE3 is planned for the near future

Errors and omissions excepted.

Page 4: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

4 Elektror IE2 / IE3

= red font or fi elds with red background mark a change of external dimensions of IE2/NEMA motor compared to current IE1 motor

* = dimensions of 60 Hz motors

** = due to design B3 (fl ange mounted motor with foot) for this type of blower it is neccessary to use a NEMA Premium motor (instead of NEMA Energy Effi cient motor). The column „NEMA Energy Effi cient“ here shows the dimensions of the NEMA Premium motor.

Which Elektror devices are affected?

X

D

IE1 motors (50 Hz and 60 Hz)

IE2 motors (50 Hz and 60 Hz)

NEMA Energy Effi cient (60 Hz)

Motor size X [mm] D [mm] Motor size X [mm] D [mm] Motor size X [mm] D [mm]

Side Channel Blowers

SD 12-SD 2n Not affected by the changeover because power of motor < 0,75 kW

SD 4n 80S(80L*) 233 156 80L 233 156 80L 233 156

SD 42 80L(90S*) 233 (250*) 156 (176*) 90S 250 176 90S 250 176

SD 5 80L 233 156 80L 233 156 80L 233 156

SD 52 90S 250 176 90S 250 176 90S 250 176

SD 54 90L 275 176 90LL 275 176 90LL 275 176

SD 6 90L 275 176 90LL 275 176 90LL 275 176

SD 62 100L 305 194 100LL 305 194 100LL 305 194

SD 64 112M 323 218 112L 323 218 112L 323 218

SD 7 100L 305 194 100LL 305 194 100LL 305 194

SD 72 112M 323 218 112L 323 218 112L 323 218

SD 80 112M 323 218 112L 323 218 112L 323 218

SD 8 112L 323 218 132SX 370 258 132SX 370 258

SD 82 132SX 370 258 132SL 405 258 132SL 405 258

SD 90 132S 370 258 132SX 370 258 132SX 370 258

SD 9 132SX 370 258 132SL 405 258 132SL 405 258

SD 92 132M 405 258 132M 405 258 132M 405 258

SD 120 132M 405 258 132M 405 258 132M 405 258

SD 140 160L 478 314 160L 478 314 160L 478 314

SD 3 Not affected by the changeover because power of motor < 0,75 kW

SD 400 90S 250 176 90S 250 176 90S 250 176

SD 420 90L 275 176 90LL 275 176 90LL 275 176

SD 540 90L 275 176 90LL 275 176 90LL 275 176

SD 600 90L 275 176 90LL 275 176 90LL 275 176

SD 740 112L 323 218 112L 323 218 112L 323 218

SD 800 132SX 370 258 132SX 370 258 132SX 370 258

SD 820 132M 405 258 132SL 405 258 132SL 405 258

SD 900 132M 405 258 132M 405 258 132M 405 258

SD 5200 100L 305 194 100LL 305 194 100LL 305 194

SD 5400 112M 323 218 112L 323 218 112L 323 218

SD 6100 New device (50 and 60 Hz available) 112L 323 218 112L 323 218

SD 6200 112L 323 218 132SX 370 258 132SX 370 258

SD 6400 132SX 370 258 132SL 405 258 132SL 405 258

Conveying Blowers

RD 14 F Not affected by the changeover because power of motor < 0,75 kW

RD 74 F 112L 323 218 132SX 370 258 132SX 370 258

For RD 4 F, RD 5 F, RD 6 F, RD 62 F, RD 64 F, RD 82 F** no change of motor size to IE2/NEMA.

Page 5: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

Which Elektror devices are affected?

Elektror IE2 / IE3 5

IE1 motors (50 Hz and 60 Hz) IE2 motors (50 Hz and 60 Hz) NEMA Energy Effi cient (60 Hz)

Motor size X [mm] D [mm] Motor size X [mm] D [mm] Motor size X [mm] D [mm]

Low Pressure Blowers

D 03 - D 052 andD 060 (50 Hz) Not affected by the changeover because power of motor < 0,75 kW

D 060 (60 Hz) 71L 212 138 80S 233 156 80S 233 156

D 064 80L 233 156 80L 233 156 80L 233 156

D 066 90S 250 176 90S 250 176 90S 250 176

D 07 90L 275 176 90LL 275 176 90LL 275 176

D 072 100L 305 194 100LL 305 194 100LL 305 194

D 08 100L 305 194 90LL 275 176 90LL 275 176

D 082 100L 305 194 100LL 305 194 100LL 305 194

D 09** 132S 370 258 132SX 370 258 132SX 370 258

D 092** 132SX 370 258 132SL 405 258 132SL 405 258

2D 04 - 2D 052 Not affected by the changeover because power of motor < 0,75 kW

2D 060 90S 250 176 90S 250 176 90S 250 176

2D 064 90L 275 176 90LL 275 176 90LL 275 176

2D 066 112M 323 218 112L 323 218 112L 323 218

2D 07 112L 323 218 112L 323 218 112L 323 218

2D 08 112L 323 218 112L 323 218 112L 323 218

Medium Pressure Blowers

RD 0 - RD 5 Not affected by the changeover because power of motor < 0,75 kW

RD 6 80S 233 156 80S 233 156 80S 233 156

RD 62 80L 233 156 80L 233 156 80L 233 156

RD 64 90S 250 176 90S 250 176 90S 250 176

RD 65 90L 275 176 90LL 275 176 90LL 275 176

RD 7 90L 275 176 90LL 275 176 90LL 275 176

RD 72 100L 305 194 100LL 305 194 100LL 305 194

RD 74 112M 323 218 112L 323 218 112L 323 218

RD 8** 132S 370 258 132SX 370 258 132SX 370 258

RD 82** 132SX 370 258 132SL 405 258 132SL 405 258

RD 84** 132M 405 258 132M 405 258 132M 405 258

RD 92** 160M 478 314 160M 478 314 160M 478 314

RD 94** 160L (V) 518 314 160L (V) 518 314 160L (V) 518 314

High Pressure Blowers

HRD 1/2T -HRD 1/3T

Not affected by the changeover because power of motor < 0,75 kW

HRD 1/4T 80S 233 156 80S 233 156 80S 233 156

HRD 1/5T 80L 233 156 80L 233 156 80L 233 156

HRD 14/2T 80L 233 156 80L 233 156 80L 233 156

HRD 14/3T 80L 233 156 80L 233 156 80L 233 156

HRD 14/4T 90S 250 176 90S 250 176 90S 250 176

HRD 14/5T 90L 275 176 90LL 275 176 90LL 275 176

HRD 2/3T 90S 250 176 90S 250 176 90S 250 176

HRD 2/4T 100L 305 194 100LL 305 194 100LL 305 194

HRD 2/5T 100L 305 194 100LL 305 194 100LL 305 194

HRD 60/3** 100L 305 194 100LL 305 194 100LL 305 194

HRD 60/4** 112M 323 218 112L 323 218 112L 323 218

HRD 60/5** 112L 323 218 132SX 370 258 132SX 370 258

HRD 60/7** 132SX 370 258 132SL 405 258 132SL 405 258

HRD 65/2** 90L 275 176 90LL 275 176 90LL 275 176

HRD 65/4** 112M 323 218 112L 323 218 112L 323 218

HRD 65/5** 112L 323 218 132SX 370 258 132SX 370 258

HRD 65/7** 132SX 370 258 132SL 405 258 132SL 405 258

HRD 7/12** 132M 405 258 132M 405 258 132M 405 258

HRD 7/17** 160L 478 314 160L 478 314 160L 478 314

HRD 7/23** 160L (V) 518 314 160L (V) 518 314 160L (V) 518 314

Page 6: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

3

1. Who is affected?After 16.06.2011 only blowers/side channel blowers with IE2 or IE3 motors will be approved within the Europe-an Economic Area (EEA). This regulation affects manufacturers as well as plant designers/operators. Direct export of blowers/side channel blowers with IE1 motors (or equipment/machinery incorporating such blowers as components) to countries outside the EEA will continue to be allowed. Details of the regulations in individual countries can be found on page 3.

2. Which devices are affected?All blowers/side channel blowers equipped with a 50 or 60 Hz low-voltage three-phase motor with a power ran-ge from 0.75 kW to 375 kW must by law be converted to IE2 or IE3 motors. This affects the following devices in particular:• ND Low Pressure Blowers: D 060 (60 Hz), D 064 to D 092 and 2D 060 to 2D 08• RD Medium Pressure Blowers: RD 6 to RD 94• HRD High Pressure Blowers: HRD 1/4T to HRD 7/23• RDF Conveying Blowers: RD 4 F to RD 82 F• SD Side Channel Blowers: SD 4n to SD 6400 (exception: SD 3)A detailed list of all the affected devices can be found on pages 4/5.

3. Are blowers/side channel blowers with multi-voltage motors affected?Yes! From 16.06.2011 onward blowers/side channel blowers with multi-voltage motors will no longer be sup-plied. By that date at the latest your existing multi-voltage devices will be confi gured with the best possible settings for your application.NOTE: To make this conversion as easy as possible both for yourselves and for us please get in touch with us in good time

4. Which devices are NOT affected?This standard does not affect the following:• Blowers/side channel blowers with motors < 0.75 kW and > 375 kW (i.e. specifi cally: D 03 to D 060 (50 Hz), 2D 04 to 2D 052, RD 0 to RD 5, HRD 1/2T and HRD 1/3T, SD 12 to SD 2n, SD 3, RD 14 F)• Pole changing devices• Single-phase devices

The standard treats the following as exceptions:• Devices equipped with a frequency converter (except 50 and 60 Hz)• ATEX blowers

5. What changes need to be made to blowers/side channel blowers?We have made the following changes to the motors on the affected blowers and side channel blowers in order to bring them in line with effi ciency class IE2:• Higher-quality sheet metal• More active material (in certain cases the external dimensions of the motor are altered*)• More effi cient motor cooling system• Slot-fi ll factor increased by using more copper• Rating plate modifi ed (stating effi ciency rating etc.)

*The devices whose motor dimensions have changed are shown in the tables on pages 4/5.

6. Is there any change to the technical specifi cations of the blowers/side channel blowers with regard to airfl ow?Radial blowers: No!Side channel blowers: The characteristics of all curves stay the same, but in some cases the limit points change. For more information please ask your Elektror contact person.

Changes for blowers and side channel blowers

6 Elektror IE2 / IE3

Page 7: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

7. When will blowers with IE2 motors be available?All blowers/side channel blowers can already be supplied with an IE2 motor on request.

8. What factors should be considered for medium- to long-term projects?We generally recommend that the changeover to IE2 motors is done at the earliest opportunity. Since the dimensions of the motor can change in certain devices, system design changes may become necessary (after 16.06.2011, even if there are dimensional problems, the use of IE1 motors will no longer be allowed). Advance planning should also enable you to avoid any processing or supply bottlenecks.

If you export systems with blowers with foot motors (e.g. design B3) to the USA/Canada, please note that these may only be shipped with NEMA Premium (= IE3) motors from the earlier date of 19.12.2010. For side channel blowers and blowers with footless fl ange motor NEMA Energy Effi cient (=IE2) is suffi cient. We can also supply blowers/side channel blowers with NEMA motors.

9. Do I have to convert blowers/side channel blowers in existing systems to IE2? What happens in the event of a repair?Blowers/side channel blowers in existing systems that have already been commissioned do not need to be con-verted. With simple repairs such as replacement of bearings the existing motor does not have to be replaced (spare parts for IE1 motors will continue to be available). In cases where the complete motor needs to be replaced, the standard stipulates that the new motor must conform at least to IE2.

10. I am exporting systems/blowers/side channel blowers to countries outside the EU. What regulations are applicable there?An overview of national standards and legal requirements that are applicable around the world can be found on page 3.

11. Do the new motors result in higher purchase costs?Converting to the new motors leads to concrete additional costs (see point 5 for the reasons for this), and a cost adjustment is therefore unavoidable. This price adjustment falls into a different category from a general price increase.

12. What benefi ts will I gain from the new motors?• IE2/NEMA motors will reduce your operating costs (90% of a motor‘s total costs are operating costs, the majority of which are energy costs)• IE2/NEMA motors develop less waste heat• IE2/NEMA motors have a longer service life• IE2/NEMA motors are environmentally friendly

13. Where can I fi nd further information and help with converting my blowers/side channel blowers?Your Elektror sales representative and our Customer Support team are always ready and willing to assist you with questions on any aspect of converting your blowers and side channel blowers to IE2/NEMA. We are also happy to help you with advance planning to make your system or machine IE2/NEMA-compliant.

To contact Elektror Customer Support• Phone: +49 (0)711 31973-111• Fax: +49 (0)711 31973-116• E-mail: [email protected]

Changes for blowers and side channel blowers

Elektror IE2 / IE3 7

Page 8: Information about IE2, IE3 and NEMA motor changeover for ... for ENG_Infoflyer_IE2-IE3...2-8 NBR 17094-1 Regulation 553 IE2 compulso-ry 8.12.2009 ... 12615-2004 IE2 expected 2013 IE1/IE2-based

Elektror airsystem

s gm

bh

• Hellm

uth-Hirth-Str. 2 • D

-73760 Ostfi ldern • Phone: +

49 711 31973-0 • Fax: +49 711 31973-5000 • info@

elektror.com • w

ww

.elektror.com

Stand 03/2011

Glo

bal sco

pes o

f IE2 / IE3*

IE2

IE3 or NEM

A Energy Effi cient or

NEM

A Prem

ium

*For a list in detail please have a look at page 3