information to users - tspace.library.utoronto.ca · likewise digital time-domain simulations using...

113
INFORMATION TO USERS This manuruipt his ben mpmdwd hom the miadihn mastri. UMI films th text di-y from a# ofigi~l or copy suknitW. Thur, some thesis and dissertation copies are in typmdter face, whiie men may be hm any typa of wmputrr printer. Th. qurlïty of this npmductkn is deprndrnt upon th. quality d ai. copy rubmitted. Bmken or indistinct print, cdomd or poor qwlity illurtnoans and photographr, print bbdthrwgh, substandard rnarghs, and improprr alignment can advemely aikt reproduction. In the unlikely evmt ntt th author did not rcmd UMI a complette m~uscript and them are missing pnges, these will be Wed. Aso. if unauthorued copyright material hid to k mmoved, a nota Ml indiCate the dekakn. Ovenue materials (0.9.~ mgr, dnwingr, chrrts) am npmducsd by sectiming the original, beghin~ at aH, upper M-hand mi and continuing fm left to right in qwl sections with smai overlapo. Photognphs induded in the original manuwipt have ôeen reproduoed werographically in this copy. Higher gurlity 6' x W blrck and nihite photographie prints are availabb for ury photognphs or illustntionr a m r i n g in this wpy for an aâdioonal charge. Contact UMI dimtly to order. Bell & HOU Information and Learning 300 Norai Zeeô RU, Ann Arbor, MI 481-1346 USA 800-521-0600

Upload: truongkiet

Post on 26-Aug-2018

237 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

INFORMATION TO USERS

This manuruipt his ben mpmdwd hom the miadihn mastri. UMI films

th text di-y from a# of ig i~ l or copy suknitW. Thur, some thesis and

dissertation copies are in typmdter face, whiie men may be h m any typa of

wmputrr printer.

Th. qurlïty of this npmductkn is deprndrnt upon th. quality d ai.

copy rubmitted. Bmken or indistinct print, cdomd or poor qwlity illurtnoans

and photographr, print bbdthrwgh, substandard rnarghs, and improprr alignment can advemely a i k t reproduction.

In the unlikely evmt n t t th author did not rcmd UMI a complette m~uscript

and them are missing pnges, these will be Wed. Aso. if unauthorued

copyright material hid to k mmoved, a nota Ml indiCate the dekakn.

Ovenue materials (0.9.~ mgr, dnwingr, chrrts) am npmducsd by

sectiming the original, begh in~ at aH, upper M-hand mi and continuing

fm left to right in qwl sections with smai overlapo.

Photognphs induded in the original manuwipt have ôeen reproduœd

werographically in this copy. Higher gurlity 6' x W blrck and nihite

photographie prints are availabb for ury photognphs or illustntionr a m r i n g

in this wpy for an aâdioonal charge. Contact UMI dimtly to order.

Bell & H O U Information and Learning 300 Norai Zeeô R U , Ann Arbor, MI 481-1346 USA

800-521-0600

Page 2: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 3: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

NOTE TO USERS

This reproduction is the best copy available.

UMI

Page 4: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 5: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Application of Static Transfer Switch

for Induction Motor Load Transfer

Yuri Pavlyuk

A thesis subrnitted in confonnity with the nquirements

for the de- of Master of Applied Science

Graduate Depammnt of Electricd and Computer Engineering

University of Toronto

0 Copyright by Yuri Pavlyuk 1997

Page 6: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

National Library Bibliathequû nationale du Canada

Acquisitions and Acquisitions et Biblioglsphic Services seMces bibliographiques 385 W W n g W Stroet 395, NO Wdlington 0ti.waON K l A W ûttawa ON K 1 A W CMldr canada

The author has granted a non- L'auteur a accordé une licence non exclusive licence allowing the exclusive pemettant a la National Library of Canada to Bibliothèque nationale du Canada de reproduce, loan, distribute or seU reproduire, prêter, distribuer ou copies of this thesis in microfonn, vendre des copies de cette thèse sous paper or electronic formats. la forme de rnicrofiche/film, de

reproduction sur papier ou sur format électronique.

The author retains ownership of the L'auteur conserve la propriété du copyright in this thesis. Neither the droit d'auteur qui protège cette thèse. thesis nor substantial extracts fiom it Ni la thèse ni des extraits substantiels may be printed or othewise de celle-ci ne doivent être imprimés reproduced without the author's ou autrement reproduits sans son permission. autorisation.

Page 7: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Application of Static Transfer Switch for Induction Motor

Load Transfer

by

Yuri Pavlyuk

A thesis subrnitted in conformity with the rcquircments

for the degree of Mater of Applied Science

Graduate Department of Electrical and Computer Engineering

University of Toronto 1997

Abstract The most cost-effective way to provide a large power user with unintemptible power is

to supply the consumer's facility with two feeders and to install automatic transfer equipment

to switch over to an altemate fecder if the primary supply fails. The given work is concemed

with such a type of load transfer. For the purpose of a transfer process study, a laboratory

prototype of an automatic transfer switch was built. The control algorithm of the switch

operation was developed and implcmentcd on the controller board utilizing a TMS320C40

digital signal processor. Transfer tests wcre perfomcd on various types of common industrial

Ioads under differcnt disturbances, although the siudy of an induction motor transfer was of

primary importance. Likewise digital time-domain simulations using PSCAD/EMTDC

software was made and comparison with laboratory tests provided. Results and observations -.

found in the studies are pnsented in this thesis.

Page 8: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Table of Contents

Abstract

CHAPTER 1 Introduction

1.1 Typical Application of Automatic Transfer Switches

1.2 Thesis Objective

1.3 Thesis Outline

CHAPTER 2 Static Trader Switch (STS)

2.1 Main Power Circuit Configuration

2.2 STS Performance During Undervoltage and Overvoltage Conditions

2.2.1 Mode 1 Operation

2.2.2 Mode 2 Operation

2.3 Required Feanires of Automatic Static Transfer Switches with Dual Feeders

2.4 Conclusions

CHAPTER 3 Dynamic Behavior of Induction Motor during Transfer between Two

Sources

3.1 The General Nature of the Problem of Motor Load Transfer 20

3.2 Transfer of a Group of Induction Moton 24

3.3 Criteria for Safe Transfer of an Induction Motor 26

3.4 Industrial schemes for Conventional Motor Load Transfer 28

3.4.1 Fast Transfer 28

3.4.2 Paralle 1 (Hot) Transfer 28

3.4.3 Dclayed In-Phase Transfer 29

3.4.4 Delayd Residuai Voltage Transfer 30

3.4.5 Slow Transfer 3 1

3.5 Conc 1 usions 33

CHAP'ïEk 4 Deveiopmnt of a Laboratory prototype d the Staüc Trrasler Switch

4.1 Functiond Characteristics of the Dcveloped Laboraîory Prototype of STS 34

4.2 Powtr Circuit 35

Ili

Page 9: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

4.3 STS Controller 36

4.4 Sensing and Gating Circuits 39

4.5 UndervoltagdOvervoltage Deteciion Mcthod 41

4.6 Load Transfer Strategy 5 1

4.7 Conclusions 55

CHAPTER 5 Testhg and Evaluation of Static Tmnster System

5.1 Results of Experimental Tests of the Dcveloped Laboratory Prototype of STS 56

5.1.1 Resistive Load Transfer 56

S. 1.2 R-L Load Transfer 58

5.1.3 R-C Load Transfer 40

5.1.4 Inductive Load Transfer 62

5.1.5 Motor Load Transfer 64

5.2 Results of Digital Time-Domaan Simulation of Induction Motor Transfer 7 1

5.2.1 Undervoltage and Loss of Power Supply Simulation 73

5.2.2 Short Circuit Faults Simulation 76

5.3 Conclusions 79

CHAPTER 6 Conelusions and Proposais for Future Studies

6.1 ConcIusions 80

6.2 Proposais for Future Studies 81 +

REFERENCES

APPENDIX A Program for Static Transfer Switch Control

APPENDIX B Magnitude .ad Phase Rcsponse of the Implemented MgiW Filter

APPENDIX C ALTERA MAX+plusIl Graphk Design File

APPENDIX D Panmeters d the ExperimcnW Iaductioa Motor

APPENDIX E PSCAD/EMTDC Graphic Design File

APPENDIX F PSCADIEMTDC Data Fik . -.-

Page 10: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

List of Figures

FIGURE 1. Double-ended substation

FIGURE 2. Spot network (with network protectors, i.e. circuit breakers with reverse power

protection)

FIGURE 3. Transfer switch (manual or automaiic operation)

FIGURE 4. Typical design goals of powersonscious computer manu fac turers ( from IEEE

S td. 446)

FIGURE 5. Typical power plant auxiliary system

FIGURE 6. Static Transfer Switch with Dual Service Topology

FIGURE 7. Static Transfer Switch with Bus Tie Topology

FIGURE 8. Diode Bridge STS

FIGURE 9. Inductive Load Voltage and Cunent Waveforms

FIGURE 10. Mode 1 Operation

FIGURE 11. Mode 2 Qperation

FIGURE 12. Three Phase Static Transfer Switch

FIGURE 13. Supply and Motor Voltage Phasors

FIGURE 14. Results of Simulation of a IO-kW Induction Motor Transfer [4]. Power Supply

is Resumed at t=255 ms aftet interruption

FIGURE 15. Rcsults of Simulation of a IO-kW Induction Motor Transfer (41. Power Supply

is Resumed at t=286 ms after Intemption

FIGURE 16. Power Interruption for a Group of Two Induction MotorsMotor 1 (7.3 MW)

with Nominal Load, Motor 2 (2.5 MW) Unloaded. - Specd, - Torque [SI.

FIGURE 17. Typical Curve of Motor Bus Voltage Magnitude Versus Anplar Difference

Between Motor Bus Voltage and hcoming Source Voltage

FIGURE 18. Rcsidual Voltage Phase Angle for 3500 HP Induction Motor [8]; H - inertia

. constant (a), L - torque (P.u.).

FIGURE 19. Types of Motor Lod Tmsfer Depending on the Phase Difference and Resid-

ud Voltage

Page 11: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FIGURE 20. Universal High-Performance Conmmllcr UHP-U)

FIGURE 21. Sensing and Gating Circuits

FIGURE 22. Cwrdinate Transformation

FIGURE 23. Cornponcnts , and Amplitude of Voltage Sprc Phasor in Balanced (a) and

Unbalanced (b) Thme-Phase Sy\tcm

FIGURE 24. Undervoltage/Overvolisge Deteciion Method B;rïcd on Equation (EQ 5)

FIGURE 25. Waveforms Obtained Applying t EQ 5) io r Thme-Phase System during Bal-

anced (a) and Unbaluiccd (b) Opration

FIGURE 26. Undervoltage/Overvoltage Detcction Method Using (EQ 6)

FIGURE 27. Integration-Reset Methcxî

FIGURE 2û. Characteristic of Uoder- and Ovcrvoltage Detection System

FIGURE 29. Thyristor Voltage and Cunent Woveforms during Tum-Off

FIGURE JO. Failure to Ensure Thyristor's Turn-off State results in a Subcycle Overlap

FIGURE 31. Control Diagram of the Laboratory Prototype of STS

FIGURE 32. Resistive Load Transfer

FIGURE 33. R-L Load Transfer

FIGURE 34. R-C Load Transfcr

FIGURE 35. Inductive Load Transfer

FIGURE 36.

FIGURE 37.

FIGURE 38.

FIGURE 39.

FIGURE 40,

FIGURE 41.

FIGURE: 42.

FIGURE 43.

FIGURE 44.

Induction Motor Transfer Due to Voltage Sag in Phase A

Induction Motor Transfer Due to Loss of Phase B

Induction Motor Transfer Due to Loss of Preferred Source

Induction Motor Behavior during Transfer to Altemate Source

Simulation of the Induction Motor Transfer Due to a Voltage Sag In One

Phase

Simulation of the Induction Motor Transfer Due to Loss of the Referred

Source

Maximum Stator Peak Cumnt as a Function of Fault Instant

Simulation of the Induction Motor Transfer Due to a h - P h a s e Short Circuit

Maximum Stator Peak Cumnt as a Function of Fault Instant

Page 12: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

CHAPTER 1

Introduction

1.1 Typical Application of Automatic Transfer Switches

Automatic transfer switches have ken used for years to provide altemate sources of ac

power for critical loads in the event of disturbance or loss of the normal or preferred sources.

The critical equipment served by these switches has varied in scope from the whole industrial

uni& using many rnegawatts of power served by dual utility feeden from different

substations to hctional kilowatt engine generators switched in to restore domestic lighting

during a blackout. This switching has been accomplished traditionally by electromechanical

means. At low c u m t ratings interlocked or double-throw contactors have been used with

either mechanical or electrical latching. In the larger sizes, "double-ended substations" with

a norrnally open tic circuit breaker configuration as shown in Figure 1, or "spot networks"

using "network pmtectors", as shown in Figure 2 have been used [14]. Tôe later case

disconnects paralleled fctders rather than transfers between them. Similar configurations

have k e n used at medium voltage (5 and 15 kV class) using circuit breakers or other power-

operatecl electromechanical switchgear for automatic operations.

The spot network has ken used successfully by utilities to protect customers from loss

of power to traditional loads. However, they can actually be a detriment when applied to

cntical loads, for example computers, for two reasons. First, the operating time to disco~ect

h m faulted fecder (several cycles) is too long to be effective for computers. Second, by

paralleling feeders, the incidence of feeder faults is significantly increased since momentary

faults on al1 connectai fdm appear at the load. Again this is no problem for naditional

loads but is disastrous for sensitive loaâs. For this reasons, it is more appropriate to transfer

feeders as shown in Figure 1 or 3 rather than use a spot network when serving such critical

equipment 11 41.

Page 13: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Utility Feeder

FIGURE 1. Double-ended substation

Utility Feeder

FiOlJRE 2. Spot nehvork (with network protectors, i.8. circuit breakers with reverse powei protection)

Page 14: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Utility

I; Utility Feeder

_1. 'T

FIGURE 3. Transfer switch (manual or automatic operation)

For many applications the characteristics of automatic rlectrornechanical transfer

switches are very satisfactory. This is particularly tme whcn used in combination with

emergency engine generators for bachp power because the time involved to suu i the engine

is fa; grrater than the operating time of the transfer switches. However, there are two

catcgories of loads for which the sensing and a s f e r tirnes of several cycles create problems.

One problem area is dual-utility source feeding equiprnent that cannot tolerate the

resultant momentary loss of voltage. Cornputers, process controls and communication

equipment generally fa11 into this category, with a typical inteiniption tolcrance of IR cycle

(Figure 4) (141. Also, metal vapor lighting systems extinp:ish after 112 cycle of power

intcmption i d cannot k rcstarted for several minutes. When this type of quipment is used

in cri tical applications in which domitirne cannot be accepted, :inother solution is necessary.

nie second problem a m is feeding active equipment, i!iat is, equipment with energy

stomge, sÜch as fmresonant transfonmrs or motors, even if inomentary intemiption can be

tolcrated.

Page 15: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Typicrl Application of Automatic Tnirmtu Switchas

. -- ." - COMPUTER VOLTAGE r TOLERANCE ENVELOPE '

m

87% ACK OF STORE0 ENER OME MANUFACTURER'S QUIPMENT

r 1 1 1 1 0 1 0.01 . 0.1 0.51.0 6 1 0 30 100 1000

TlME IN CYCLES (60 Hz) 2%

FIGURE 4. Typical design goals of power-conscious cornputer manufacturen

(from IEEE Std. 446) (141

Figure 5 shows typicai power plant auxiliary systcm which serves a large number of elecvic

motoa [SI. These moton an typically induction machines and drive loads such as pumps. fans.

cornpressors, pulverizea and conveyors. In order to provide continuity of proccss, the auxiliary

systern is supplied from two sources of power. Start-up and shutdown power is provided from one

source through the Start-up Transformer whcn the main gencrator is off-line. Once the unit has

been tied to the systern, the station srnice load is transfemd to the unit Auxiliary Transformer or --- normal source. This transfer operation can also bc done on emergency basis when t h e ~ is an

unplanned unit trip or a sudden loss of the normal power source.

Page 16: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Typicrl Applicrtlorr of Automrtic Tnnrkr Swltch.8

Ld+ Unit Aullimias Tranitormar

Station Sarvice - Stui-up Sourco Souno - SM-up Brorkar

Motor Bus T

I

Omar L o d

Station Sewkr Source: The power source tor the power planrs auxiliary systern. typically taken from the generator bus through the unit euxiliaries tmnsfomef and auxiliiry b rea km.

Start-up Source: Source wbkh provides power to operatr the plant's auxiliaiy systern while a gmemtor h rhut down or king started.

Motor 8ur: An auxiiiary systrm bus that pflrnailly feeds power to a plant's large moton.

RGURE 5. Typical power plant auxiliary system

The use of conventional elcctromechanical transfer switches usually rcsulu in power

interruption time of several cycles [1.2]. As it will be shown in Chapter 3, a several cycle transfer

interval can mate an out-of-phase condition between the ultimate source and the load upon

transfer to that source. This rnay rcsult in damage to the equipment. such as motors, or extendcd

loss of operation due to the neccssity to stop and then attcmpt to restart (perhaps sequentially

when multiple loads arc involved, to keep inrush within the source rating).

In order to avoid the above mentioncd negative phenornena, the spced of transfer must be as . --

high as possible. This can be accomplished using a solid-state transfer switch.

Page 17: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

1.2 Thesis Objective

In the ment years Static Tnuufe Switchci (STSs) ha! . been widely used to pmvide

unintemptible power supply for voltage sensitive equipmci t (electronic instruments and

cornputers) and in continuous proceu planis [ I I . 1 2, 1 3. 14 1. Since little has ken reponed on the performance of'a S O during the m s f e r of high

inertia motor ioads, the objective of ihis work is it) rlevelop 3~ 1 teSI the laboratory prototype

of a STS for this particulai application.

The presented work consists of two pans:

development of a laboratory prototype of a STS:

experirnental study of the STS performance during moior I lad transfer.

The development of STS includcs:

rating of semiconductors and equipment in order to implen lent the irans fer of a 5- 1 O hp

AC motot;

control algorithm development and implementation in 3 m srocontroller board;

identification of undervoltage/overvoltage detection mahod which can provide desirable

sensitivi ty and speed of operation;

building laboratory senip for motor load transfer implemer tation.

The developed prototype is used to:

study the STS perfomnce under different fault and distur3ance conditions;

identiQ the maximum motor inrush current during transfe: transients.

Finally, the experimental results are compared with simulation results in order to

valiàate the computer model. nie computer model is used to study the motor load ûansfcr

whm the experimmtal setup becomes impractical in tems of rost and equipment.

Page 18: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

1.3 Thesis Outline

This thesis is composed of six chapters. The first cliapter attempts to clarify the

motivation of this thesis and covers introductory material.

Chapter 2 introduces static trans fer switch détails: main power circuit configuration

and principle of operation. Switch performance dunng RL load tmsfer is analysed and

maximum tmsfer time for two different transîer co;itrol s:ratcgic?s is identifid.

Chapter 3 reviews dynarnic behavior of iriduction motor d u h g power supply

interruption. Analysis of physical processes in large inenia induction motor during power

intemption is given. Problems of motor load transfcr and possible solutions are discussed.

Chapter 4 covers development of laboratory prototype of STS: power circuit,

undervoltagdovervoltage detection method. control algorithm implementation using digital

signal pmcessing board.

Chapter 5 discusses obtained expenrnental results. The cornparison between the

expriment and simulation is provided.

Chapter 6 provides conclusions about the feasibiliiy of the STS implementation for

moior ioad tmnsfer and some recornrnenâations for iùnire work.

Page 19: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

CHAPTER 2

Static Transfer Switch

2.1 Main power circuit configuration

Figure 6 displays a single-line diagram of a systeni in which S, and S, are two solid

state switches. One is connected between the normal (preierred) source V I and the load and

the other one is connected between the altemate source Y, and the load. Such a configuration

fonns Static Transfer Switc h (STS) [ 141.

Preferred Source Y, I

Akernate Source V2 I

critical Load

Nomlly Closed I

FIGURE 6 Static Transfer Switch with Dual Sewice Topology

During normal operation only one pair of thyristors is nimed on in each phase -. comspondingly. P r e f d and altemate source voltages are continuously monitod by

conml logic. Wôen the p n f d source &as a proper voltage, control logic uns on .

thyristors on the prferred soum side. If a deviation of the p r e f d source voltage h m the

S~

I Ir

I

Page 20: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

pre-specified limits is detecteâ, transfer to the altemate source is initiated by removing gating

pulses from the thyristors of the preferred source switch and firing thyristors on the altemate

source side. Transfer to an altemate source is prevented if the alternate source voltage is not

present. Upon restoration of the preferred source voltage within the preset limits. a transfer

back to the preferred source is initiated.

Figure 7 shows another widely used configurarion for a Static Transfer Switch. The

power system in service in this figure serves pan of the load from Source A and the other part

of the load fiom Source B. For a disturbance on Source A. switch SI opens, the bus tie switch

S3 closes and the entire load is then served from Source B.

A diode bridge and a thyristor can be used to perfon the same hinction as two

antiparallel thyristors (Figure 8) [14]. Although the drawbitck of this circuit is that it has less

overload capability because a thyristor conducts on both half-cycles and has higher losses

due to the additional voltage drop in two senes conducting diodes.

Usually thyristors or GTOs are used as semicmductor devices in STS applications.

Since a thyristor is nimed off at zero crossing of the clrrrenr, its tumsff tirne can be as long as

half period of the power source. On the other band, 3 GTO breaks current within about 20

rnicroseconds, since it has self-tum-off capability. Although the GTO has supior tumsff

time characteristics, it bas some disadvantages as cornpwed with the thyristor, such that the

GTO itself is still expensive, steady-state dissipation !s large and gating and snubber circuits

are large [iZ].

Page 21: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Source A Source B

Bus Tie Switch

1 1 Critical Loads 1 1

FIGURE 7. Static Transfer Switch with Bus Tie Topology

#' - - - - O

- - - #

+

current flow uring 1 R cycle

ÇlWRE 8. Static Transfer Switch with Diode Bridge

Page 22: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

2.2 STS Performance During Undervoltage/Overvoltage

Conditions

To illustrate the STS performance under vMous opcrating conditions a simple single-phase

circuit diagram can be used.

According to the inductive load voltage and currents wavefoms of Figure 9, there are four

typical regions of operation in one cycle:

Region 1: v o > O . i , < O ;

Region 3: v o < O , i , > O ;

Region 4: v, < O . i , < O .

The circuit operates in exactly the same way in Region 1 and 3 and in Region 2 and 4.

There are, therefore, two modes of operation. In Mode 1, the load voltage and current have

opposite signs (Region I and 3) and in Mode 2 they have the same sign (Region 2 and 4).

Two methods can be used to trigger the thyristor switches:

conventional gating;

selective gating. .

In the first case both thyristors of one switch are tumed on immediately after the control circuit

removes gating sigoals from the other switch. In the second method only the desired

thyristor is tumed on immediately while its antiparallel counterpart is tumed on only after the

current zero crossing.

2.2.1Mode 1 Operation.

In Region 1. thyristor SI, conducts and al1 other thyristors are off (Figure 1 Oa).

If then is a voltage drop on the prefemd source side V,, , the control logic will initiate a transfer . -..

from source VI, to V2, by blocking the gating signals of thyristors SI, and SI, , and providing

gating signais for SZp and S2,. Because of the load cumnt direction, thyristor S2. should k

Page 23: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FIGURE 9. Inductive Load Voltage and Current Wavefoms

conducting the load current. At this instant. however. since v, is srnaller than v,, thyristor S2,

is reverse biased and can not be turned on. Thyristor SZp however is fonvard biased and tums on

instantaneously. This results in paraileling preferred and altemate source with maximum overlap

tirne n. During the overlap timc there is a current flow from the altemate source to the preferred

source. If the voltage drop is caused by a shon cirquit on the prrfemd source side, such an

overlap may lead to an increase in fault cumnt. By the use of selective gating during the transfer.

so that only the desired alternate source thyristor conducts initially. the overlap is prevented

(Figure lob). Maximum transfer time in this case is equal to the load power factor angle cp . If an overvoltage occurs on the pnferred soum side (VI, > V2, ), thyristor S2,, is forward

biased and ~ r n s -. on instantaneously. This rrsults in commutation bctween S,, and S2,, in such a

manner that the cuncnt through S,, declines and increases through Sin (Figure WC).

Page 24: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

a) Load Transfer Due to Voltage Drop on the Preferred Source Side with Overlap

b) Selective Gating Prevents Overlap at Transfer under Conditions a)

-.. Ivld > 1vz.l

c) hstantaneous Load Tramfer Due to Overvoltage on the Prcferred Source Side

FlGURE 10. Mode 1 Operation

Page 25: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

2.2.2 Mode 2 Operation.

In region 2, thyristor SI,, conducts positive load cumnt. When the voltage VI, rises above

a tolerable level, the transfer process is initiatcd. The control logic blocks gating pulses for

thyristors SI,, and SI,, and provides gating pulses for SzP and S2,. Because of the load current

direction. thyristor SZp should be conducting. Since the load voltage v , in this case is higher than

the second source voltage VZa, thyristor S2, is reverse biased and cannot be turned on

instantaneously. However. thyristor SZn is forward biased and tums on instantaneously. When

both thyristors SI, and S2, are conducting rt the same time. the two sources VI, and V2. are

paralleled for a maximum interval I. During the overlap interval line current flows from the

prefemd to the altemate source (Figure I 1 a). The magnitude of this current is determined by

voltage difference V I , - V2, and the impedances of the supply system and line. If the line and

supply system impedances are small in cornparison to the load irnpedance the overlap may result

in considerable overcumnts leading to switch and associated equipment damage. This can be

avoided by the use of selective gating in which thyristor Slp is gated irnrnediately after the

overvoltage is detected. but Sln is gated only after the cumnt through the thynstor S l p declines

to zero (Figure 1 1 b). Maximum transfer dclay in this case is x - cp . In the case of an undervoltage on the pnferred source side, thyristor Sb is fomard biased

and tums on imrnediately. This results in commutation between thyristors Slp and S Z p . The

transfer is completed when the cumnt through Slp declines to zero and S2,, takes on the full load

. current. This is illustrated in Figure 1 lc.

The nsulu of a qualitative analysis of static transfer switch khavior in differcnt modes of

operation are summarized in Table 1.

The conCcpt of a singlephase static transfer switch can k extended to a thrce-phase

application (Figure 12a). The gating signais for thyristors and cumnt through TI are shown in

Figure 12b.

Page 26: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

a) Load Trmsfer Due to Overvoltage on the Prefemd Source Side with Overlap

b) Selective Gating Prevenu Overlap ai Transfer under Conditions of a)

lvld 1vz.l

c ) instantaneous Load Transfer Due CO Undervoltage on the Prefcrnd Source Side

-. FIGURE 11. Mode 2 Operation

Page 27: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

STS Perlorminco During Onâewolt~wnroItrgo Condition8

Disturbance

r

Undervoltage

Overvoltage

TABLE 1.

1 ( Maximum 1 Maximum Type of Gating Region of Operation I Delay

Gating 1 Quadrants 2&4 ( O I O

Selective Gating

Conven tional

Gating

Quadrants 1&3

Quadrants 2&4

Selective Gating

Quadrants 1&3

Quadrants 2&4

-

cP

O

Quadrants 1&3

Quadrants 2&4

- --

O

O

O

O

--

O

72

O

x-CP

O

O

Page 28: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

a) Circuit

b) Waveforms for Resistive Load -"

FiGURE 12. l'hree Phase Static Transfer Switch

Page 29: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

2.3 Required Features of Automatic Static Transfer Switches with Dual Feeders A properly designed static tnnsfcr rwitch intiiates tnnsfcr to the alternate source due to

over- or undervoltage conditions. such a! might uccur owing io o feeder fault. power factor

correcting capacitor switching, or motor styiing on ihc preferrcd source [ 1 1.12. 13. 141. It should

do this within the transient tolerance lirnits of the vrved critic~l equipment while ignoring less

severe transients. Such a switch should also be designed to automatically retum to the preferred

source once that source has returned to normal voltage. It should transfer to the altemate source

and remain in that position until manually reset in ihc event of a dixontinuity of the normal path

for the power flow frorn the prefemd source. such as loss of thyristor gating signal. A

synchronizing check should be built into the switch logic. which prevents transfer in either

direction if the two sources are not within 10 electrical degrees of phase with respect to each other

to prevent excess circulation of cumnt between sources during the transfer process [14].

Static transfer switches should include self-contained protection for transient surges that

rnight occur on either source. which would otherwise turn on a thyristor intended to be off and /or

damage the switch. This cm be achieved, for example. by using switching devices with forward

and reverse voltage ratings of at lest twice the maximum peak line voltage plus a tolerance

margin to account for reverse phase condition. Built-in surge suppressors, such as MOVs (metal

oxide variston) with breakdown voltage above the rated line voltage but below twice line

voltage, should ôe included on both sources with sufficicnt energy-absorbing capacity to handle

the worst expected voltage surges 1141. Provisions should be included to prevent false t u m a for

the fastest rising voltage wavefonn expected on either source. Typically this is achieved by the

use of dvldt snubbers across each thyristor pair 1141.

Page 30: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

2.4 Conclusions

A Static Transfer Switch is a very efficient means of providing an unintemptible power

supply to criticd loads which cannot tolcnte a mornentûnly loss of power. It can transfer loads to

an altemate power supply in less than a cycle of the supply voltage.

The main power circuit configuration of a Static Transfer Switch can generally be divided

into two categories:

Dual Service Topology ;

Bus Tie Topology.

Operation of the STS is deterrnined by the type of disturbance. and the polarity of the

voltage and current. There are therefore two modes of STS operation which are mirror images of

each other:

Mode 1: voltage and cumnt have the same polarity;

a Mode 2: voltage and cumnt have opposite polarity.

Selective gating of thynston in a STS entirely eliminates cross-cunents between preferred

and altemate sources during a transfer.

Page 31: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

CHAPTER 3

Dynamic Behavior of the Induction Motor during

Transfer between Two Sources

3.1 The General Nature of the Problem of Motor Load

Transfer

Figure 13 shows the supply and motor voltage phasors before and after the motor is

disconnected from the power supply [2] . Phasor V, in Figure 13 represents the supply voltge.

Phasor V, represents the motor voltage. 8 is the phase angle between the supply and the motor

voltage.

Prior to disconnection, the supply voltage phasor V, is roiaiing at synchronous speed while

forcing the motor voltage V, to follow in synchronism but at an angle 8 behind it corresponding

to the load-torque angle.

When the motor is disconnected from the supply bus, the supply bus voltage V, continues

as it did when connected to the motor. without varying in amplitude and frequency. However, the

motor terminal voltage V, does change after the disconnection. The total rotating inertia acts as a

prime mover and delivers energy to the xrved load. While üiis energy is transfemd from the

rotating mass to the load, deceleration in the rotating mass results. Such a deceleration coupled

with decaying trapped air-gap flux in the motor produces a decaying voltage whose frequency is

alw continually dropping. nie rotor of a disconncctcd motor immcdiatcly star& to decelerate at a

rate determincd by the rotating inertia and the load chuacteristics; the frequency of the motor

voltage starts decreasing [ I l . Further, the motor residual voltage s t u i s decreasing and the relative

phase angle bétween the motor voltage and the supply voltage starts incnasing. After a certain

time the motor has slowed down such that the motor rcsidual voltage is out of phase with respect

Page 32: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

to the supply bus voltage by an angle Q, which is greater than . This situation is illustrated in

Figure 13b.

FIGURE 13. Supply and Motor Voltage Phasors

If the motor were to be rwlosed to the bus voltage at phase angle Bi , shown in Figure

13b. the intemal voltage drop in the motor would be extremely large as indicated in the figure.

However, if the angle between the supply voltage and motor voltage phasors reaches 180

electrical degrees. and the amplitude V, does not reduce appreciably, the phasor sum of V,

and V, would be almost twice the normal line voltage. Upon reconnection, the statting inrush

cumnt could be two tirnes the normal starting innish cumnt of the motor, which is about 6 to 10

times the rated full load cumnt of the motor [l-31. Since the force to which the motor is

subjected is proportional to the square of the cumnt, it should be obvious why out of phase

switching of a motor can bc a problcm. Such forces could loosen the stator coils. loosen the rotor

bars of the induction motors, twist a shaft or even rip the machine from its basc plate. The

cumulative abnonal magnetic stresses andlor mechanical shock in the motor windings and to

the shaft and couplings could ultimatcly lcad to prematun motor failure due to fatigue.

~xtensive studies have bem done regarding the transient khavior of an induction machine

during a transfer ktween two power sources [l-71. Fipns 15 and 16 show rcsults of a digital

simulation of a 10 kW induction rnotor transfer nported in (41, where VS2 - stator terminai

Page 33: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

nia Ormnl Natut. of !ha Problrm of Motor Lord tnnrfw

voltage, Is2 - stator cunenl M - torque and s - slip. î h e powcr supply is reconnecied at t = 255

ms after the interruption.

RGURE 14. Results of Simulation of a 10-kW Induction Motor Transfer [4]. Power

Supply is Resumed at 1-255 ms after Interruption

Page 34: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

th. Chnoml Natun of tha Probkm of Motar Lord Tnnrkr

which resulu in 8 = 180" phase difference between the supply and motor terminal voltage.

The maximum stator current reaches a value of 10.7 times the rated stator current amplitude and

the torque reaches a value of 5 times the rated torque. Howevcr. the same simulation approach

shows that the worst mm on instant in terms of torque does not nccessarily occur at O = 180" .

In the case of the machine under study, the biggest torque occun at At = 286ms. which

corresponds to a phase diffennce 8 = 205" (Figure 16). It naches value of 6.3 times the nted

torque.

FIGURE 15. Results of Simulation of a 1 0-kW Induction Motor 1 ransfer [4]. Power

Supply is Resumed at b286 ms after Interruption

Page 35: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

3.2 Transfer of a Group of Induction Motors

Special attention should k p i d to the cau when the trinsferred load is composed of a

group of different induction motors. Sevenl p;ym have k e n written to explain transients

during motor group tnnsfer (5. 7). To mdyzc the transient bchavior of a group of different

induction moton a parallel connection of iwo machines cm be considered. becruse this

configuration aireaciy exhibits ail the essentid fcaiurcs of r multi-motor group. In addition. a

group of induction moton can be rcduccd to r iwo-machine cquivalent in many cases.

The voltages, induced in stator windings of two panIlcl connected induction rnotors,

are functions of rotor speeds. rotor iime constants and load characteristics (51. If the induced

voltages have different amplitudes or phase angles during the voltage interruption period. a

circulating cumnt between the two parallei connected machines will flow. This cumnt

contributes to a balancing torque in the machines if there is an angular difference between the

rotor fluxes. The torques have the srme amplitude but opposite directions. The machine with

leading rotor flux phasor develops a braking torque and acts as a generator. while the machine

with a lagging rotor flux phasor develops accelerating torque and acts as a motor.

In the beginning of the transieni. rotor fluxes of both machines are in synchronism with

respect to each other. Developed electromechanical torques are equal to driven load torques.

Therefore. the initial speed reduction in both machines is almost the same. Later, per contra.

the speed diffennce between the machines grows in such a way chat the machine acting as a

generator. develops a higher spced than the machine acting as a motor. As the flux

magnitudes of both machines rcduce, the speed difference bctween the machines increases.

Simultaneously the angular diffmnce ktween fluxes grows. When the anplar difference

naches a value of 90'. the torque balance cm no longer be maintained. and the machines faIl

out of synchronism with respect to cadi 0th.

Besides the above discussed electromechanical transients. then are electromagnetic

transients btween two machines so long as they are in synchronism. Figure 16 illustrates the

simulation of power interruption for a grwp of two induction motors.

Page 36: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FIGURE 16. Power Interruption for a Group of Two Induction Motors. Motor 1 (7.3 MW)

with Nominal Load, Motor 2 (2.5 MW) Un1oaded.n - Speed, dm - Torque (51.

Page 37: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

-- -

3.3 Criteria for Safe Transfer of Induction Motor

In order to transfer an induction rnotor without damage. motor designers have

established a rule of thurnb. giving conxrvative rcsults in most cases. which indicates that

reclosing or transfer of induction motors should be avoided when the phasor difference

between the residual voltage and the incorning voltage exceeds about 125% to 135% of the

rated voltage of the moior [Z]. The American National Standards institute (ANSI) standard

(30.41-77 (Polyphase Induction Motors for Power Generating Stations) and a proposed

National Electric Manufacturing Association (NEMA) standard would permit a maximum

voltage of 1.33 per unit for out-of-phase transfer or reclosing [2] . With 1.0 p.u. residual

voltage at the rnotor temiinals. the reclosing should occur when the phase difference brtween

the voltages is less than 83 electrical degrees. With the voltage phase difference of 180". for

the reclosing to occur. the residual voltage at the motor terminais should be less than 0.33 p.u.

As stated in Section 3.1, the rate at which the residual voltage decays is dependent upon the

tirne constant of the motor. and the frequency of the residual voltage decays at a rate equal to

the decay in motor speed depending on the type of the load. It is necessary to minimize speed

reduction and voltage drop in order to maintain process continuity. By lirniting the load

which must be reaccelerated. the voltage &op can be reduced. Al1 unessential loads should be

intentionally disconnected from the line and sequentially nstarted after the disturbance.

A typical curve of induction motor bus voltage magnitude versus angular difference

bctween motor bus voltage and incorning system voltage is shown in Fipre 17 [2]. When the

typical decay of motor bus voltage as a function of timc is supcrposed as in Figure 17, for the

group of induction machines that the curve repmscnts. it can k seen that the reclosing or

transfer must be pnvented ktween 0.25-0.4 seconds aftcr the power interruption. If the

residual voltage is ailowed to decay to 33% or less of the rated voltage. any nclosing angle

will. of course, k acceptable. Anothcr helphil guidcline for induction m o t m rhat can be

observed from Fipre 17 is that. from the standpoint of motor damage, it is generally safe to

ieston power immediately after the disconnection so long as the nsidual voltage has fallen

less than 80' bchind the incoming system voltage.

Page 38: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Angular Diffennce between Motor Residual Voltage and Incoming System Voltage

0.2 -

FIGURE 17. Typical Cuwe of Motor Bus Voltage Magnitude Versus Angular

Difference Between Motor Bus Voltage and lncoming Source Voltage

Safe for nclosing

90° 180" 270" 360" 450" 540" 630" 720" 1 1 I 1 1 I 1

Page 39: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

3.4 Industrial Schemes for Conventional Motor Load

Transfer

To guard ûgainst excessive reclosing innish currents and torques, the following five

general transfer schemes are used [2 .8 .9] :

3.4.1 Fast Transfer

The basic philosophy behind the fast trmsfer is to transfer the rnotor as fast as possible.

keeping the dead time (time of disconnection from both sources of power) to a minimum.

This is to minimize the decay in the bus residual voltage and phase angle before the transfer

is completed. Fast transfer is often made possible kcause the induction motor is designed to

withstand a reasonable number of transfers at a closing angle less than 80' without a

significant loss in the life expectancy. This transfcr approach provides increased assurances

that the bus has been disconnected from the normal source prior to the altemate source

breaker closing. Bus dead times of 5 to 10 cycles can usually be obtained (using conventional

switchgear) [2, 8, 91. However. failure of the normal source breaker to open will result in

paralleling two sources and may result in equipment damage. This transfer method is widely

used to provide continuous power supply for power plant auxiliary systems and has the

following advantages:

1. Speed of transfer minirnizes the interruption of power supply to the motor bus;

2. Provides the minimum ltvtl of motor stresses of al1 methods available;

3. A safe method to maintain operation of the motors and the most diable rheme;

4. Avoids paralleling of the prefcrnd and altemate sources;

5. Simplescheme to implement.

This transfer method also has the following disadvantages:

1 . Interruption of power supply during the transfer;

2. if the @ansfer occurs fnquently, significant transient torques contributing to fatigue fail-

ures will be prrsent.

Page 40: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

3.4.2 Parallel (Hot) Transfer

A common form of planned bus transfer is the parallel bus transfer scheme in w hich the

prefemd and altemate sources are connected in panllel for a short period of time during the

transfer of the motor bus between sources. Prior to paralleling the sources it is ensured that they

are approximately in phase to minimize electrical and mechanical transients that can damage the

assuciated equipmcnr. This method has gnined wide acceptmce bcc;iusc. assuming two sources

are in phase. the transient on the motor bus is eliminated. However. the bus system designed for

this transfer will usually violate the intempt rating for the switchgear and the shon ierm

withstand rating for the transfomen. The advantages of the parallel transfer are:

Continuous power to the motor bus permits an orderly shut-down of units by eliminating

bumps and avoiding motor overstress;

Ease of application and operator understanding.

The limitations of the parallel transfer are as follows:

During parallel operation, the increase in available fault current to the rnotor bus caused by

paralleling the sources requins equipment with much higher fault duty ratings or minimized

paralleling time;

Will not work when steady state differences of voltage and/or voltage angle are too large to

allow safe transfcr.

Cannot be used to transfer when the source to the rnotor bus is lost due to an electrical fault

or abnormal condition.

3.4.3 Delayed In-Phase Transfer In-phase transfer is a scherne designed to monitor the relative phase angle of the motor bus

nsidual voltage with respect to the source voltage and connect the bus to a new source when the

angle is ncar zero. This definition implies that the bus has k e n dixonnected from its primary

source and the motor residual voltage is asynchmnous with the new soum voltage. In order to

connect the bus to the new source, the In-Phase Transfer system must know the time required for

the switch to close and prcdict when to initiate closing. Although. due to variations in the bus

Page 41: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Indu8ttiil Sehamas for Convontlonril Motot Loid T rinater

loading in the time of transfer the residual voltage angle ch;ir;ictenstics may Vary. widely as

shown in Figure 18. This may result in large mgulîr mors on closure [8].

Modem relays chat rneasurc the phase mgle decay charûcteristics use the fint and

second denvatives to predict when CO close the brerker. This minimizes errors due to

variations of residual voltage angle chuacteristics caused by bus loading [2,8].

O 6 12 18 24 30 Xme (Cycles)

FIGURE 18. Residual Voltage Phase Angle for 3500 HP Induction Motor [8]; H - inertia constant (sec), L - torque (pu.).

It should k crnphasized that the in-phase transfer technique is generally suggested for

emergency transfen and not for routine transfers. It provides a diable method of transfer in

instances when the two sources of power are not initially in synchronism [8]. This could be

due to a system design that results in a significant phase angle betwecn two power sources.

3.4.4 Delayed Residual Voltage Transfer W . .

This method involves waiting until the motor residual voltage drops bclow a

predetcrmined level kfon connecting to an alternate source. By waiting until the nsidual

voltage is low such as 25 to 35% of the normal beforc completing the transfer, the rcsultant

Page 42: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

lndudrid Sc)Hmaa for Convmtionrl Motor Lord Tnnmfw

voltage at the instant of reconnection to the ultimate source is reduced to a maximum of 1.25

to 1.35 p.u. However. in most bus systems by the timc the voltage drops to this level. the

motor loads would have decelerated to a point. when a portion of this loads may have to be

disconnected because sirnultaneous reacceleration of d l motors is noi possible. Such load

shedding funher complicates the trans fer scheme and requins the operators to mrnuall y

restart the motors that have been taken out of service,

The nsidual voltage transfer wiil always subject the motor to a larger value of open-

circuit voltage than the proper choice of either fast or in-phase transfer. Also the residual

voltage transfer introduces a significantly longer tirne delay than either fast or in-phase

transfer. Therefore the residual voltage transfer should be used only as a backup and either

fast or in-phase trmsfer should be used to provide the minimum transfer transient on the

motor bus.

Advantages of the residual voltage transfer include:

1. Relay and conuol equipment to implement the transfer scheme is relatively uncompli-

cated with an accompany ing high dependabili ty of correct operation.

2. Most auxiliary systems can be successfully transfemd using a sid du al voltage scheme.

3. There is minimal chance of inadvertently paralleling the normal and rltemate sources

due to equipment malfunction.

The disadvantage of nsidual voltage transfer is the following:

The longer time rquircd to transfer to the alternate supply, as compared to a fast

transfer scheme, increases the possibility of low voltage motor starting problems andor the

necessity of shedding loads pnor to transfer.

3.45 Slow Transfer Slow ttansfer is a transfer schemè designed to wait for a predetcrmined time (usually

greater then 20 cycles) after the motor bus power source is removed before connecting this

bus to another source. Voltage rclays do not supervise the transfer. -..

The practice of slow transfer is not widcly used and has no advantage in cornparison to

other schemes.

Page 43: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

- -

InduWîrl Sc)nma for Conwntlonrl Motor Lord Tnnatw

The disadvantages of this schemc arc:

1. This scheme takes too long to transfer key motor loads;

2. Gencrally requires some motor loûds to k shed to reduce inrush.

Figure 19 illustrates the three zones for the tnnsfer using the typical voltage and phase

curves as a function of time. Fast iransfer requires that the ultimate source is reconnected

before the phase angle moves outside of Zone 1 . Zone 2 of Figure 19 repnsents the in-phase

transfer when the ultimate source is reconnected when the motor residual voltage is in phase

with this source. When the motor residud voltage drops below a predetermined level (such as

33% of the rated voltage) the ultimate source c m be reconnected with any phase difference.

This is represented in Zone 3 of Figure 19.

Zone 1 2d \ \

ase Di fference \ \

Timc -. -

FIGURE 19. Types of Motor Load Transfer Dependhg on the Phase Diff erence and

Residual Voltage (2)

Page 44: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

3.5 Conclusions Transfer of an induction motor between two sources is a senous and challenging

problem, because immediately after the disconnection the motor will not become free of

c k n t s and fluxes. On the contrary, the flux linked with rotor circuit will decay in a iransient

process controlled by the circuit parameten of the rotor (its L/R ratio). This flux will induce

a voltage in the open stator circuit as long as the rotor kecps rotating. However. after

disconnection the rotor stans to slow down at a rate dctermined by its moment of inertia and

the characteristics of the driva load. The nsulting angular difference between supply and

motor residual voltage may lead to significant overcumnts and torque pulses at the moment

of reconnection.

According to [4] the wont case for motor reconnection from the siandpoint of torque

pulse does not necessarily occur when the angular difference between the supply and the

motor residual voltage is 180' . To guard against excessive inrush currents and torques dunng induction motor transfer,

reconnection should be avoided between 0.25-0.4 sec after power interruption.

If the motor residual voltage is allowed to decay below 33% any reclosing angle is

permissible. Although. by the time voltage drops to this level, motor spad reduces such that

continuity of some critical process may be lost.

The ideal solution to the pmblcm of motor load tramfer is to do this operation as fast as

possible. Application of a Static Transfer Switch is very advantageous for this purpose.

Page 45: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

CHAPTER 4

Development of Laboratory Prototype of

the Static Transfer Switch

4.1 Functional Characteristics of the Developed

Laboratory Prototype of Static Transfer System

To study the operation of a static transfer system. a laboratory prototype of such system

was developed. It consists of two pairs of thyristors per phase where each pair is connected in

inverse parallel. One set of thyristors is connected to the prefemd power source. while the

other set of thyristors is connected to the alternate source. The outputs of two sets of thyrisors

are connected together and fumish power to a critical load (dual service configuration. as

shown in Figure 6). Thyristors are nanirally commutated.

Power is provided from two synchronized power sources. The steady state voltage is

assumed to be sinusoidal with a maximum Total Harrnonic Distortion (THD) of 5%. The

waveform has no single hamonic component with a magnitude gnater than 3% of the

magnitude of fundamental. Cumnt distottion is expected to be higher. but it should not cause

voltage distortions grcater than the above specified.

The transfer system provides unintemptible power supply for a critical load in the

event of any disturbance:

undervoltage or overvoltage conditions in al1 three phases;

voltage sag in only one phase which results in a total undervoltage of 10%;

short circuit conditions;

loss of one or two phases of the prefemd source;

complete loss of prefemd source. -. (

At the same time the rransfer switch does not rcspond to short term abnomal conditions so

long as significant disturbances do not appear at the served Ioaâ.

Page 46: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

- -

Although synchronized sources are assumed, a phase difference between both power

sources is checked and. if any diffennce is found. it is identified as unit malhinction and

transfer is prevented.

The served load is a three phase symmetrical static load or induction motor load. If the

load is an induction motor. it may backfeed the energy stored in spinning shafts into the faulty

system. Therefore. the transfer operation should be accomplished without

faulty system.

4.2 Power Circuit

Since the primary goal of this work is to drvelop of a static trmsfer

induction motor, the ratings of power circuit components should satisfy

regeneration to the

system for 5- 10 hp

requirements for a

safe steady state operation as well as expected worst case overvoltages and overcunents. The

rating of the main components of such a system is specified in this section.

Power Supply: I 15V AC thm-phase three-wire system.

Power Rating: 12.5kVA.

Powcr Factor: the static transfer system is able to power loads with a power factor ranging

from 0.5 (lagging) to unity.

Maximum Continuous Steady State Current: 63A mis.

Overcument Protection: 50-A extemal fuses are placed in the prefemd and altemate side

of the static transfer system.

dV/dt Protection: a snubbcr circuit is placed across each STS thyristor (R = 15 Q.

C = 0.22 pF).

Semiconductor Devices: naturally commutatcd thyristors are u r d as switching devices in

the STS.

Page 47: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

4.3 STS Controller

The control of the static transfer sysiem i s ptovided by r Universal High Performance

Controller Platform (L'HP-40) dcvelopd ri thc Pnwer Gmup of the Department of Electrical

and Computer Engineering at the Univcrsiiy of Toronto 11 5). A short description of the

controller and sorne peripheral devices i s given in ihis seciion.

The UHP-40 controller piaiforni i s bûsed un the tloaitng point digital signal pmcessor

TMS320C40 from Texas Instruments (Figure ?O). It ha^ r Harvard architecture with two

separate buses which are called a local and a global bus. The intemal structure of the UHP-40

is 32 bits for al1 address and data paths.

Two static RAM modules (Bank I and Bank 2) with standard sizes can be connected via

SIMM-sockets to the local bus. Bank I is usually populated to provide a minimum amount of

R A M space. A third RAM module (Bank 3) is connected in a similar way to the global bus.

RAM modules are fast enough to operate at a frequency of 40 MHz.

The global bus can be considercd as the peripheral bus on the board since it serves

besides the RAM module also additional hardware. A Dual-Port-RAM with a data bus width

of 32 bits can be accessed directly in order to provide a fast communication with the VME bus

circuit controllcd by the MC68030. The global bus is connected to the FPGA from Altera

which is used to generate gating pattern signais depending on the application. The 9 bit pons

for input and output arc also accessible via the global bus. The output port (Global Control

Register, GCR) provides signals to control several functions on the board whereas the input

port (CornPort Input Register, CPIR) can k used to read status signals on the four CornPort

soc kets . The communication ports provide eight bit asynchronous data paths with handshake

mechanism. Communication ports O to 2 an token owners after rcset. This means that they are

set as output ports whereas communication ports 3 to 5 are set as input ports. Four connectors

on the board provide acccss to the communication ports 1. 2. 4 and S. Thcy are mainly used

for communication with A/D converter bards, but c m also be connected to other üHP-40s in

a multi-DSP rtup. The rcmaining communication ports O and 3 can dso k dimtly accessed

through the connecter on the front panel. They am used for cornrnunicating with a personal

Page 48: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

STS Contralkr

cornputer. This interface uses communication pon O for output and communication port 3 for

input data. The second function of cornmunicriion port 3 is io nceive data coming from the

MC68030 in order to download programs.

The circuit around the Motorola CPU MC68030 consists of another 32-bit wide bus. It

accesses a fourth SRAM module (Bank 4) ihat has io k populated in order to provide RAM

for the CPU. Besides Bank 4 an in-circuit programmable Flash-PROM is also connected to the

bus. It uses only 8 data lines but can be directly rcessed by the CPU using its capability of

dynamic bus sizing. A dual asynchronous recciver/transmitter (DUART) with 8 bit bus

interface provides a serial RS-232 interf'ace.

The SCV64 chip 1s connected to the MC6830 and consists of a complete VME bus

interface. It can prform all common types of VME bus transfer cycles and therefore

guarantees full VME bus compatibility of UHP40. Most of the VME bus signals have to be

buffered using bidirectional bus drivers. The SCV64 provides control signals to set the

direction of the fast TTL drivers.

Communication with a cornputer is provided through a serial transmission line

"Hotlink". The Hotlink operates at a speed of 20 MHz w hich corresponds to a data transfer

rate of 20 MBytedsec. It consists of one set of receiving and transmitting lines with associated

circuity and provides most of the functionality mcessary to develop a powerful interface for a

reliable and electrically decoupled data transmission to and from the PC.

The integral part of the DSP system is a quad channel malog to digital converter board.

The board provides high speed data conversion (20 MBytedsec) and maximum use of the

UHP-40 arc hi tecturt . The DSP board can execute user programs for a vat range of industrial control

algorithms. These prognuns arc written in C pmgiamming language using the TMS320

Aoating Point C Compiler. User programs typically requin differcnt signals to be monitored

and puameters/command valucs to be set. This is done through the DSP-Monitor program

which manages data transmission between the U H P 4 and PC. The program emulates

functionality of an oscilloscope and provides data npnscntation in a graphicd form.

Page 49: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

SRAM Bank 4 I I P l

F m PROM

V M E b interface scv64 N M d g e J

PZ

FPGA Aîien

FIGURE 20. Universal High-Performance Controller (UHP-40)

Page 50: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

4.4 Sensing and Gating Circuits. The static transfer system requires continuous voltage and current monitoring for its

operation. Since the UHP-40 controller board cannot process line voltages and cumnts directly,

special sensing equipment is necessary. It provides a safe level of electrical isolation from the

main power circuit and fumishes distortionless data signals for reliable DSP operation. In the

laboratory setup this is accomplished using voltage and cumnt sensors. Voltages and currenis are

measured at the inputs of the solid state switches on prefemd and altemate source sides. Since

the system is powered from a thne-phase thm-wire supply system and serves only symmetncal

load with dlowable unbalance limits not more than 5%. only two phase-to-phase voltages c m be

monitored. If, for example, voltages VAB and VBC are rneasured directly, the third voltage

VCA can be obtained as follows:

whercas phase voltages can be obtained from the following relations:

The gating signals are developcd by the UHP-40 and amplified by a gate pulse amplifier.

The schematic diagram of the static transfer switch with the controller, and the equipment

which generates the sensing and gating pulses is shown in Figure 2 1.

The frequency spectra of signals for samplc-data systems must be limited to avoid the

aliasing effect. Usually this is achicvcd by the use of an antialiasing filter 1161. Since the

sampling frequency in the actuai setup is rclatively high (5.28 kHz), no aliasing effect was

obsewed and no antialiasing filter was used. Instcad, noise caused by EMI in power electronics

systerns rcsults in signals distortion. To d u c e the influence of this noir on the accuracy of

measurcments, a fourthsrder FIR digital filter was impkmented in the control program. The

filter coefficients were calculated using MATLAB Signal Rocessing Toolbox. The Harnming

window function technique [16] was employed in the filer design. Since no filter specifications

werc initially assumcd, a triai and enor mcthod was used until the desircd rcsults were achieved.

The filter coefficients am givm in Appndix A. Amplihi& and phase chancteristics of the filter

are ploned in Appendix B. Cdculated grwp L l a y of the filter is two sampling periods.

Page 51: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 52: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

4.5 UndervoltagelOvervoltage Detection Method Since thyristors are uscd as switches in the developed static transfer system. the tum off

time can be as long as half the cycle of the source period. as described in Section 2.2. Therefore,

the method of sensing an undervoltage/overvoltage condition is a key for realizing high-speed

operation. Generally an AC voltage drop can be sensed through cornparison of the refennce

voltage with a DC signal that is obtained by ACDC conversion 111, 12). Voltage dips. however.

do not always occur in three phases at the sarne time. If the sampled voltage is converted into DC

through the-phase rectification, a voltage drop in only one phase-to-phase voltage may not be

detected. Moreover. the signal obtained by AC/DC conversion contains not only a pure DC

component. but some ripples as well. Therefore, an RC filter must be used to eliminate these

ripples. However. this arrangement introduces detection time delay.

To avoid the above drawbacks. the properties of the thne-phase system can be utilized. If

such a system is balanced and supplies power for a balanced load the d-q-O transformation can be

applied to obtain ripple free DC quantitics:

cos(8 - 2n/3) cos(@ + 2n/3) sin(e) sin@ - 2n/3) sin (8 + 2+/3) 1

when 8 = or + cp in particular.

Equation (3) shows that when the lhrre source voltages are balanccd, the Y, component is

zero. Furthennorc, the value of cp can be choscn such that the q-component becomes zero.

Thenfore. the transformation will nsult in a pure DC d-component which is proportional to the

source voltage and can be cornparcd with a refennce voltage.

The d-q-O transformation is a very usehl rnethod to redize DC conversion. but requires - --+

very accurate syncluonization with the thm-phase system. Thercfore, it is difficult to

Page 53: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

implement in a practical setup. As an rltcrnativc IO the d g 4 innsformation the a - P - O

trmsfomiation can be used. Thc a - B Irame ih no longer synchronized with the system but

fixed in a certain position with respect io it as show in Figure 3. I t can be seen that a and

p components are not constant vducs. Y in the case of the Park's transforrnation but

J-i functions, of ut. However. the value of a + is constant. It yields the amplitude of the

+ line voltage phasor Vs in a symmctricd thrcc-phsu system. and can be used for overvoltage/

undervoltage detection.

If the a - frame is positioned with respect to the three phase-system as shown in

Figure 22b. the following transformation matrix rpplies:

The elements of the transformation matrix (EQ 4) are no longer trigonometrical functions

of ut + rp as in the case of d-q4 transformation but fixed numben. Furthemore, the a - P - O

transformation does not requin synchronization with the supply system. Hence. it is easy to

implement with less computational effon.

The space phasor obtaincd by transformation (EQ 4) is composed of each component VA.

Vg and V, of the thme-phase system. nius, if undervoltage/overvoltage occun in al1 three

phases simultaneously. it can be effcctivtly dttccted using (EQ 4). However, if a voltage

disturbance occurs in one phase only. it may not be detected. Moreover. if a disturbance results

in topologicai changes in the system. such as loss of phase. then an unbalanced operation of the -.

system happens. In this case transformation (EQ 4) does not yield a DC value. Figure 23a

shows the rcsults of the transformation (EQ 4) implementation on the acnial laboratory setup

for a balanced t h e - p h w system. It can k secn that this transfomation yields a DC signal

Page 54: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FIGURE 22. Coordinat8 Transformation

Page 55: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

time (sec)

FIOURE 23. Cornponents va , va and Amplitude Jmi of Voltage Space Phasor in

Balanced (a) and Unbalancd (b) Three-P hase System

Page 56: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

V, which cm be compared to the reference V, in order to detemine an overvoltagel

undervoltage condition. Fipre 23b shows results of the same method but for the case when

phase A of the supply system is lost. The signal V, is no longer pure DC value md cannot be

used (without incorporating additional logic into the control algorithm) for disturbance

detection since this may lead to enoneous operation of the transfer system.

Reference [ I l ] describes an oventoltagelundervoltage method in which each phase

voltage (or line voltage) is squared and added as shown by the following relation:

In order to detect undervoltage/overvoltage in each phase separately, equation (5) was

adopted for a real static transfer switch as shown in Figure 24. Although, the control algorithm

shown in Figure 24 allows one to detect an abnormal condition in each phase separately it has

the same drawback as the two previously discusscd methods: equation (5) holds only for a

balanced three-phase system. Results of tcsting this method on the laboratory setup are shown

in Figure 25a for a balanced operation and in Figure 25b for the case when phase A of the

supply system is lost.

In [12] a dctcction methd is introduced which effcctively eliminates deficiencies of the

above approaches. It is descrikd by the following set of equations:

Page 57: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 58: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

tirne (sec)

0.005 0.01 0.01 5 0.02 time (sec)

flaURE U-vWaveforms Obtained Appîying (EQ 5) to a Three-Phase System during

Balanced (a) and Unbalanced (b) Operation

Page 59: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Block diagram of the system concsponding to 46) is shown in Figure 26. It nalizes ACDC

conversion theontically without ripplcs and dlows disturbûnce detection in each phase

separate l y.

FIGURE 26. UndervoHage/Ovewoltage Detection Method Using (EQ 6)

To incorporate this system in the laboratory prototype of ihe static transfer switch, the

realization of a -90' phase shifting is needed. In the DSP board this can be achieved by

impkmenting an all-pass digital filter with a 90" phase delay i.e. Hilbert transformer. An attempt

to implement such a filter in the actual xtup nsulted in a significant nduciion in the sample rate

because of the high order of the filter. Thercfore an alternative approach was sought.

One way to detcct an abnormal condition in each phase separately is to calculate in the DSP

the amplitude or mis value of the supply voltage directly at each sampling instant as follows:

Vi = si/ sino>ti (EQ 7)

where si is the sarnpled value at instant ti .The dnwback of this approach i s that the function

sinot yields zero at each zero crossing of the sampled signal. Then are also numerical problems

close to the zero crossing since the denominator in (EQ 7) approaches zero. Thenfore. to

implement this'detcction method, a "window" must be established in which rcliable results cm k

obtained. In the vicinity of zero mssing it cannot be used.

Page 60: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Another way is to integrate the sampled signal over hrlf a period. calculate the average

value and compare it with the teference value. Detcction time in this case is half a cycle of the

supply voltage. although it may be reduced to a quuier of cycle using the following property of

a sine function:

According to (8) a sampled signal is integrated over each qumer of a cycle. After thüt the

average value of the signal is calculated and compared with the reference value. The integrating

block is reset and a new integration period stms (Figure 27).

Thus. the calculated average voltage is compared with the reference voltage four times over a

cycle at the instants: r/2, +. 3x/2. 2ir. Also. to satisfy the requirements of the CBMA curve

(Figure 4), an additional block for instantaneous detection is built in. It performs ABC to apO

transformation and calculates the magnitude of the line voltage space phasor. If it is more chan

100% or less than 50% with respect to the reference value. command to transfer is issued

immediately . The operational characteristic of the detection system is plotted in Figure 28. The solid

line indicates the "best" case of detection in which a disturbance is detected within a quarter of

a cycle. The dashed line repiesents the "worst" case of detection which is half a cycle. This

happens when a disturbance begins somewhere within the integration period such that it does

not result in sufficient enor obtaincd during this pcriod. Hence. it can be detected only after the

next quarter of cycle

The integration-reset mehod is the most robust among ail considered and involves

minimum computaiiond efforts using the trapemidal rule of intcgration with a step equal to the

sampling period. -. In addition it allows one to distinpish between abnomai conditions and

momcntary voltage spikcs or short-term transients. Abnomal condition can be detected in each

phase sepamtely. Thenfore. the integrationiesct rncthod was findly implemented for

ovcrvoltagdun&rvoltagc detection in the actual setup.

Page 61: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FIGURE 27. Integrationdeset Method

0.24 0.5 0.73 1.0 1.25

time in cycles

FIGURE 28. Characteristic of Under- and bveivoitage Detection Systern

Page 62: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

4.6 Load Transfer Strategy

The main automatic transfer techniques for major rotating machinery loads summarized in

Section 3.3 are Fast. Slow, Parallel, Residual Voltage and In-Phase methods. Although each

method has its advantages and disadvantages the universal solution is to transfer ;is fast as

possible. This ensures power supply continuity for essential Ioads and minimizes transients on the

ioad bus during the transfer. However. it is also important that a fault on one source does not

disturb loads of the other source. In this case no overlap of the supply systems is allowed. Al! of

these requirements can be met by gating thynston pmperly.

Generally, STS thyristor gating methods faIl in two categories, as outlined in Section 2.2:

conventional gating;

selective gating.

The first method may result in subcycle overlap depending on the disturbance type and operating

point while the other one always provides nonoverlapping transfer. Therefore, in order to prevent

fault back-feed from one source to another. selective gating was used to implement loûd transfer

on the laboratory prototype of STS.

According to the selective gnting method, only that thyristor of the incoming source switch

is gated immediately after a disturbance is detected. which can prevent supply systems from

overlapping or comrnutate with cumntly conducting thyristor of the other switch. Its antiparallel

counterpart is turned on only after the load is isolated from the previous source. In the STS

control algorithm this is done by checking the polarity of the current during the transfer. If the

line cumnt is positive. then the thyristor which conducts during the positive half-cycle of the

incoming source is gated immediately. If the line cumnt is negative, the thyristor which conducts

during the negative half-cycle of the incoming source is gated immediately.

To guarantee a nonoverl.apping transfer, the mans should bc provided to detect thyristor

tum-off. In the actual senip this is done by monitoring the line cumnt. if the cumnt drops below

a holding level, which is 250 mA for the givcn device, then the thyristor loses its cumnt latching

capability. This condition solely docs not ensun the tum-off state of the device since a certain

amount of time ton is rcquind to remove excess carriers and then dlow the device to .kcovcr its

Page 63: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

fonvard blocking capability as shown in Figure 29. If a fonvard bias voltage i s reapplied to a . thyristor, which is being tumed off, ai the moment t c ta,,--. it will be turned on again. This

results in subcycle overlap of two supply sources as illustnied in Figure 30. For the actual

thyristors the tum-off time toj, is specified to be 100 p. Thercfore, since the sampling period

T,,,, in the control program is 189.3939 p S. ihen one sampling period delay after the current

in the device drops below holding level would be long enough to ensure the thyristor's tum-off

state. But due to the implemented digital filier the sampled signal is delged by 2 sampling

periods. Hence, the tum-off state is reached when the filiered current is less then the holding

current because the necessary delay is already introduced by the filter. At this instant the load

is completely isolated from the previous source.

If an abnormal condition and operational point of the STS results in commutation

between thyristors on each source side, the served load undergoes an almost "seamless"

transfer. However, in the opposite case there will be sorne "dead" time caused by power

interruption. This is because of the necessity to prevent overlap and due to the imprecision in

thyristor mm-off state detection. Since the sampling process is not synchronized with the

signal the "dead" tirne can be as long as 3 sarnpling pends which is 0.568 ms in the worst

case. This is the limit. obtained by a trial and error method, providing non-overlapping transfer

in the actual laboratory setup. To =duce the dead time, more sophisticated instrumentation is .

required. But this makes the system bulky and costly. The control system implemented in the

laboratory prototype of STS incorporating intcgration-met fault detection method and

selective gating of thyristors during the &ansfer is illustrated in Figure 3 1.

Page 64: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

1 1 Turn off timc t,,, 1 I fl '!

FIGURE 29. Thyristor Voltage and Current Wavefoms during Tum-Off

Load Transfsr Due to Undsniobge with ûwriap

FIGURE 30. Failure to Ensure Thyristor's Tum-off State results in a Suôcycte Overîap

Page 65: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Lord Trrnrfu Stntogy

' I I I

Page 66: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

4.7 Conclusions

This chapter outlined important aspects of the laboratory prototype of Static Transfer

System development. The functional characteristic of the systcm and the rating of the main

components are provided. Principal features of the STS controller as well as gating and

sensing equipment are introduced.

The method of undervoitage/overvoîtage detection is crucial for reûl izing high speed of

sw itch operation, therefore it is addressed in panicular. Several methods for undervol tagel

overvoltage. among them those implernented in real static tnnsfer switches are described in

Section 4.5. Each of them has its advantages and disadvantages. Considering the available

control and instrumentation hardware, the integration-reset method was finally selecied

because of its robustness and reliability.

Page 67: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Rarultm of Lwpdnnritil hat8 of th . bvalopoâ C.bamtoy Prototype of Strtic Tnndw Sylam.

CHAPTER 5

Testing and Evaluation of Static Transfer System

5.1 Results of Experimental Tests of the Developed

Laboratory Prototype of Static Transfer System.

The developed prototype of a static transfer system was subjected to a number of

experimental tests involving various loads and abnormal conditions which caused a transfer. The

purpose of these experiments was to study the performance of the static transfer system during

load transfer. to determine the maximum transient on the served load and to identify the potential

problems and methods of their elimination. Two categories of load were used in the studies:

passive (resistive, inductive) load;

induction motor.

Specific tests were selected to provide a complete picture of the static transfer system

performance. This chapter presents the selected tests and follow-up evaluaiions.

5.1.1 Resistive Load Transfer Resistive load transfer was the fint full-scale test perfonned on the laboratory prototype to

check the propemess of systern operation under practical abnormal conditions. The sets of

obtained results are plotted in Figure 32.

Figure 32a illustrates the resistive load R = 12 SL transfer to the altemate source due to an

undervoltage which was implernented by reducing the prefemd source voltage with a laboratory

transfomer below 0.9 p.u. The plotted data npresent thrcc line currcnts and phase A voltages of

the prefemd and altemate sources respeaively. An abnormal condition was detected and transfer

initiated at t = 0.018 sec on the cumnt plot. Because of the load cumnt direction and type of

disturbance, transfer prmess is completed instantaneously as a result of commutation between

thyristors in each phase.

Figure 32b illustrates an opposite case to the previous one. The transfer process is initiated

due to an overvoltagc on the prefemd source which was implemcnted by incrcasing the supply

voltage with the laboratory transfomm above 1.1 p.u., although, it is not accomplished '

instantancousi y.

Page 68: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

- 2 .s 1 I O 0 . 0 0 5 0 . 0 1 0 . 0 1 S 0 . 0 2 0 . 0 2 s 0 . 0 3 O . O 3 5 0 . 0 4

tirna ( s o c )

FîGURE 32. Resistive Load Transfer

Page 69: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Reaulta of ErprlnmW T ~ B of th. ûovdopd Libontory Prototype of S W c Tnnakr Syatm.

Because of the load cumnt direction md type of disturbance. there is no commutation between

thyristors. Hence. each phase is transferred sepantcly after the cumnt zero crossing. The transfer

process is completed after 0.005 sec from the moment of its commencement.

To test the sensitivity of the static transfer system to disturbances in one phase only. a

voltage sag was caused by inserting a series resisior 10 Q in phase A. Voltage dips to 0.7 p u . at

r = 0.01 sec in phase A. as seen in Figure 32c. although it is detected at t = 0.01 5 sec. For this

particular case the transfer process is instantaneous. Upon completion of transfer. the voltage of

the faulted phase is restored because there is no cunent flow.

Another common type of asymmetrical fault is loss of one phase of a power source. The

behavior of the transfer system dunng this fault was studied by subjecting it to a loss of phase B

of the prefemd source. Obtained results are plotted in Figure 32d. Phase loss occurs ai

t = 0.0 17 sec. It is detected at t = 0.02 sec. Again. the transfer process is instantaneous.

Figures 32a-d illustrate idealized cases of transfer. As the served load is pure resistance. it is

transferred "seamlessly". No transients wen obsewed during and after the iransfer.

5.1.2 R-L Load Trader

Since the majority of industrial loads are resistive-inductive in nature, the second set of

tests was performed on this particular type of load. It consists of a resistor R = 12 Ci, and an .

inductor . L = 25.3 mH. Thus. the cumnt is lagging behind the voltage with an angle 38' . This

is a typical case of a passive R-L load with a power factor coscp n 0.8. The performance of the

static transfer system is similar to that with a pure rcsistive load. In case of an undervoltage on the

prefemd source. the load is transferrcd with commutation between thyristors in phases B and C,

as shown in Figure 33a If an overvoltage mon than 1.1 peu. occurs on the prefemd source. the

load is transfemd to the altemate source phase-by-phase after the zero crossing of the prefemd

source's cumnt (Figure 33b). Because of the selectivc p i n g of thyristors in semiconductor

switches. then'is no overlap of the systems and no overcunents. Abnomal condition on the

prefemd source does not disturb loads suppliexi from the ditmate soua.

Fipm 33c illustrates the R-L load tramfer to the alternate source due to voltage dip to 0.6

peu. in phase A of the pnfcned source.

Page 70: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FIGURE 33. R-L Load Transfer

Page 71: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

While the transfer in phases A and C is instantancous. in phase B it occurs only after a zero

crossing of the prefemd source's cumni.'lhe tnnrfer process is completed after At s 0.6 ms

from the moment of its commencement.

One of the most disturbing load abnonnd conditions is r complete loss of a power source.

Performance of the system for this case is illustnicd in Figure 33d. The preferred source is lost

just before the zero crossing of the phase B currcnt. Sincc ii cumnt through an inductor cannot

change instantaneously, phaxs A and C yc si i i i conducting the load current. The fault is

detected with a delay At = 3 ms. which is approximately 65 electrical degrees. This is well

within the "ride through" limiü of major sensitive clcctronic equipment.

5.1.3 R-C Load Transfer

To study static transfer system performance during the transfer of loads with leading

power factor, a number of experiments was performed on an R-C load. In the example of Figure

34. the load consists of a resistor R = 6 fi in series with a battery of capacitors C = 250 pF.

Thus. the cumnt leads the voltage at an angle 60'. If an undervoltage occurs on the preferred

source, the load is transferred instantaneously as a result of commutation between thyristors. as

shown in Figure 34a. However, in case of an overvoltage. the load is not transferred to the

altemate source until zero crossing of the prefemd source current, as shown in Figure 34b.

Therefon, the transfer pmcess takes At = 15 ms from the moment of its commencement.

Fiprc 34b shows. that during the transfer interval the served load may draw cumnt from both

power sources (phases A and B). Although, due to selective gating, current flow from one

source to another is effectively blocked. This minimizes transients during the load transfer.

Figure 34c illustrates the load transfer due to voltage sag to 0.7 p.u. in phase A. An abnormal

condition occurs at t, = 17 rns. It is detccted at t = 21 ms. Phases B and C of the load are

transferred instantamously, while phase C is uansferred only after the current zero crossing.

Again, there is no considerable disturbances to the load during ihc transfer.

Figure -34d illustrates the transfer system performance when the prefemd source is

completely lost. A fault is detccted after At = 3 ms. However. in the beginning of the transfer,

the thyristor of phase B does not turn on because it is reverse biased. It tums on only at

t = 25 ms with a momentary cumnt overshwt.

Page 72: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

. v ..... ....... ; ........ .W. . ;'?evf. .. :. ..... ;. ..... .:. .:. .... i

0 O .O O S O . O 1 0 . 0 1 S O . O 2 0 . 0 2 5 O .O 3 0 . 0 3 1 O . O 4 I i m o ( r o c )

FIGURE 34. R-C Load Tmnsfer

Page 73: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Peak cucrent reaches almost twice the steady state value. But the transicnt decays very fast.

Already at t = 28 ms. the normal power supply for the load is restored.

5.1.4 Inductive Load Transfer.

This test is unique in a sense that it gives an insight into the static transfer system

behavior during transfer of an almost purely inductive load. The served load is an inductor

L = 35.1 mH. Its resistuice is negligible in cornparison to its inductance. Due ro an iilniost

90 degrees phase shift between currcnt and voltage transfer conditions in each phase differ

fmm those in the case of an R- or R-L load. as shown in figures 38 a, b. In addition this

particular load is poorly damped, and it takes a much longer time. before steady state

operation is attained. Experimental results showed. that the transient penod may last for

about 7 cycles.

The conducted tests demonstrated, that the developed prototype of a static tnnsfer

switch has proved to be a very effective means of maintaining power for different types of

passive loads. They also verified proper operation of the implemented control algorithm. The

served load is transferred to the altemate source in the event of any disturbance on the

pnferred source within tolerable time limits. The transients during load transfer are

minimized.

Page 74: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

a) Imbdvm Lord Tmnder Due to Undrrvdirgo on the P d e m Soum

! . . . ....... O

b) IncbcUva Lord Tmndar Due to Ovewdtigs on tha P r o k m Source

- c) Inducihm L W Tmihr Dur to Vo)tige Sig in P h r e A

1 1

t . a . . . . ....... !

O O . O O 5 0 . 0 1 O . O 1 5 O . O 2 O .O 2 s O . O 3 O . O 3 5 O . O 4

flOURE 35, Inductive Load Transfer

Page 75: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

5.1.5 Motor Load Transfer

The performance of the laboratory prototype of a static transfer system during transfer of

active (i.e. energy storage) loads was studicd using a 5-hp (3.725-kV) I IO-V three-phase

induction motor. Parameters of the equivalent circuit of expcrimental machine are given in

Appendix D. The system was subjected to the s m e type of the disturbances as in the previous

cases. The experimental induction motor operated under rûted conditions. A separately excited

DC motor was used as a loading machine to provide constant load torque. Selectzd tests results

are illustrated in Figures 36-39. where experimental data is represented in per unit values for

greater convenience.

Figure 36 shows the induction motor transfer due to a voltage sag in phase A. Momeniary

voltage sag to 0.8 peu. was rnodeled by inserting 1 R series resistor in phase A of the preferred

source circuit. The fault occun at t = 0.1014 sec. as seen in the figure. The undervoltagel

overvoltage detection logic recognized the abnormal condition at t = 0.1044 sec or 65

electrical degrees later. The transfer process occurs alrnost instantaneously. The initiai peak

cumnt in each phase does not exceed 1.5 times the rated cument.

Figure 37 shows the induction motor transfer caused by loss of phase B of the preferred

source. Phase loss occurs at time t = 0.05 sec. It is detected at t = 0.0522 sec or 47 electrical

degree later. Load transfer in al1 t h e phases is accomplished with commutation between

thyristors of the pnfemd and altemate source. The overall detection and transfer time is 1.1

msec. Again, peak current aftcr the transfer does no< exceed 1.5 times the rated current.

Figure 38 illustrates an example of an induction motor transfer due to the complete loss

of the prefemd source. A fault occua at t = 0.0536 sec according to the voltage plot. It is

detected instantaneously. Transfer in phases A and C is accomplished as a nsult of

commutation between thyristors, while in phase B transfer does not happen until the prefemd

source current falls to zero. Although the induction motor under test was subjected to a very

severe disturbance, fault detcction and transfer occurs so fast that the phenomena described in

Chapter 3 not observed. The transfer process is accomplished without significant

overcumnts. This can be bctter obsemd in Figun 39, where amplitudes of the stator cumnt

space vector as well as pnfemd and Plternate source voltages are plotted versus time.

Page 76: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

O - 1 2 O . I 4 0 . 1 1 O - 1 8 O - 2 O - 2 2 Hm, sec

FIGURE 36. Induction Motoi Transfer Due to Voltage Sag in Phase A

Page 77: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

- t . s 1 O O . O 5 O . I O . l 5 O . 2

Hm, sec

FlGURE 37. Induction Motor Transfer Due to Loss of Phase 6

Page 78: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

FiGURE 98. Induction Motor Transter Due to Loss of Prefened Source

Page 79: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Space vectors of the measured values are obtrined in the stator fixed frame using (EQ 4).

This figure illustrates another example of motor transfcr when the preferred source is lost

completely. The initial peak current in this case is 1 .S times the rated current. and the

transient process lasts 22 mec.

time, (sec)

flGURE 39. Induction Motor Behavior dunng Transfer to the Altemate

Results of the experimental tests an summarired in Table 2 .

Source

Page 80: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

TABLE 2.

LOSS of One 1 0,003 1 Phase

Overvol tage l Voltage Sag in ( O,m5 ~ One Phase

Transfer Timeqsce

0.0006

0.005

ferred Source Loss Of 1

Total Time, sec

-

*

Disturbmce

Undervoltage

Overvol tage

Fil!urr

32a I

32b

L

Voltage Sag in 1 One Phase

Detection Ti

-

-

I

C-

h d L

Resistive Load

Loss of Pn- 1 *,W*, ferreci Source

Voltage Sag in OnePhlse 32c

I

~ o l t a ~ e Sag in1 Ont Phase

, I

7-

s s O 1 1 fernd Source

Page 81: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

TABLE 2.

*

Load I

Motor Load

Fipre

36

37

38

Disturbance

Voltage Sag in One Phase

Loss of One Phase

Loss of Pm- femd Source

Detec tion Tirne,

0.003

Transfer Time, sec

0.006

0.008

0.0037

Total Time, sec

0.009

0.0 102

0.0039 1

Page 82: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

5.2 Digital Tirne-Domain Simulation of Induction Motor

Transfer Although the developed laboratory prototype of the static transfer system proved to bc a

very useful tool for studying the ôehavior of a real static transfer switch dunng transfer of power

to major practical loads, it has the following limitations:

disturbances cannot be üpplied at a certain. prcdetennined time by the user;

short circuit tests cannot be conducted since they might affect other loads. connected to the

sarne power supply line and because of safety considerations.

Therefore, further studies were performed by computer simulation of the developed system. The

need for computer simulation was dictated also by the impossibility io make conjecture about the

worst case scenario for the transfer and to reproduce it in al1 details on the laboratory prototype.

Among al1 of the commercially available power system simulation software packages

PSCAD/EMTDC [18] was chosen. This package provides a very flexible graphical interface to

electrornagnetic transients simulation program, a built-in library of power system component

models and procedures as well as plotting and analysis tools for convenient representation of data

generated by simulation. Thus, it is a very suitable software to handle problems studied in this

thesis.

PSCADIE- library provides components which allow one to build various practical

analog control systems. However. in the STS laboratory prototype digital control was used. It

rnight seern, that this fact requircs developrnent of a customized rnodcl of the irnplernented

digital control to make expcrimcnt and the simulation results compatible and comparable. On the

other han& any analog component is npresentcrl in EMïDC by its digital indel. Therefore it is

truc to say that if the tirne step of the digital simulation of a continuous time system is equal to the

sampling period of a real m p l e d data system performing the sarne control algorithm.

comparison ktween thcm can be made. This is of course tnie if sarnpling period is small enough.

so that the simulation timc step of the s u m value will not cause numerical problems. Since the

sampling priod used in the UHP-40 to pcrfomi control of the STS labontory prototype is as low

as 189.394 p, the above assumption is justifiai. Thus, the simulation time step was chosen to k

equal to the sampling pend and EMTDC libiary components w m used as building blocks to

Page 83: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

60 80 time, sec

Page 84: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

O ICI 0 ta

Figure 41. Simulation of the Induction Motor Tnnsfer Due

Page 85: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

create the simulation mode1 of the STS control system. With exception of the digital filter the

implemented control system was accurately modeled. Since thete is no such phenomenon as EMI

noise in cornputer simulation. there is no need to filter out measured signûls. Though, to account

for time delay introduced by the filter, i first-order delay bloc k from EMTDC library was used.

Figures 40 and 4 1 provide simulation results of the induction motor transfer under the same

conditions as those illustrated in figures 36 and 38. As seen. simulation results are very close but

not exxtly the same as in the experiment. The differenccs c m be explaincd by the impossibility

to reproduce in simulation the exact real situation because in the laboratory prototype of the STS.

line voltages, sampling and fault events are asynchronous with respect to each other, whereas in

the simulation everything is synchronized with the time step. Although. without loss of generality

simulation can be used to study performance of the laboratory prototype of STS during induction

motor transfer.

5.2.1 Results of Undervoltage and Loss of Power Supply Simulation This simulation was performed to study the relation between maximum transient current in

the motor and the instant at which the abnorrnal condition occurs. This allows one to identify the

worst case condition for the motor to be transferred. The absolute value of the induction motor

s p r e phasor current was chosen as a criterion determinhg the severity of the transient. Since

supply voltages and currents are priodic signals it is enough to limit the snidy interval to one

pend of the supply voltage or 0.0167 sec. The transfer system will operate in the same way

anywhen beyond this time interval. Also, to guarantee a systematic simulation approach, the

system was subjected to disturbances at equidistant moments of time (At = 570 psec) on this

interval. In the viccinity of extrema this time resolution was increased to find the maximum or

minimum values. ksults of the simulation are pnsented in the fonn of plots in Figure 42. Circles

on these plots denote the absolute value of space phasor of the initial stator peak cumnt caused

by a transfer to the altemate source if the fault occurs on prefemd source at time t. One period of

phase A voltage was arbitrarily iaken as the interval of study, i. e. v,, = O at t, = O . Prior to

transfer the motor was operating at rated conditions.

As seen fiom the plots. the simulation results do not reveal any discrepancy as compared to

those obtained in the experiment. The initial peak stator cumnt varies between 1.4 and 2.2 p. u.

Page 86: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

and two phases-to gmund shon circuits. According to actual simulation results. the initial

stator peak cumnt reaches up to five times the rated cumnt.

Loss of Phase A

O 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018

Loss of Phases A and B

Loss of Prcfemd Source

Page 87: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

depending on the type of disturbance and the moment of its occurrence. Although intuitively one

would expect higher transients in the case of a complete loss of power supply. in fact they are

lower as compared to those in the case of one or iwo phases k i n g lost. This is because the

implemented control logic detects a supply source loss mon quicker. Another interesting

phenornenon which can be observed from this figure is the periodicity of the results. In the case

of a symmetrical fault such as the loss of a supply source. this period tends to be 116 times the

voltage period, which is explicable for a three-phase system.

5.3.1 Results of Short Circuit Fault Simulations

Similar io the studies described in the previous section, the simulation of short circuit faults

was performed and the behavior of the static transfer system was investigated. This simulation is

of particular importance since no such tests were performed on the laboratory prototype of STS.

The results of short circuit fault simulations revealed different STS performance as compared to

that in the previous section. Figure 43 illustrates the example of an induction motor transfer due

to a three-phase shon circuit on the preferred source. As seen in the figure, the difference in the

system behavior is caused by induction motor currents changing their direction immediately after

the fault. This is due to the fact that mechanical energy stored in the spinning shaft of the motor

does not dissipate instantaneously but acts as a prime mover thus turning the induction motor into

a generator which delivers substaniial amounts of power to the fault. Thus, if in one of the phases

a change in the instantaneous current polarity was expected shortly k f o n the fault. this would

not happen. On the contrary. cumnt starts to rise again prcserving its sign, as can be observed

from the plots of phase B and C cumnts shown in the figure. As a consequence. one cumnt zero

crossing is missed. Comspondingly, if die transfer in this phase is accomplished after a cumnt

zero crossing, it is delayed. During this delay significant fault cumnt flows. The worst situation

aises when fault occurs just beforc a cumnt zero crossing. in this case transfer is delayed by

almost half a cycle.

Dependence of stator pcak cumnt from the type of fault and instant at which it occurs is

plotted in ~ i g u k 44. It can be observed. that the most severc types of faults are three-phase and

two phases-to ground short circuits. According to actual simulation rcsults, the initial stator peak

cumnt naches up to five times the ratcd cumnt.

Page 88: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

a VC1 0 ICI A I c 2

Figure 4 1. Simulath of the Induction Motoi Tmfcr Duc

to aTbiise-Phase Short Circuit

Page 89: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

6 Phases A and B to Ground Fault

I I 1 1 1 I 1 I ,

Fault Between Phases A and B

Phase A to Ground Fault

- 0 0.002 0.001 0.0080.008 0.01 0.012 0.014 0.016 0.018

-. Fault Occurrence Instant, (sec)

FIGURE 44. Maximum Stator Peak Current as a Function of FauR Instant

Page 90: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

5.3 Conclusions Experimental tests conducted on the labontory prototype of the Static Transfer Switch

as well as computer simulations dcmonstrated quite satisfacrory system performance during

transfer of common industrial loads due to typical disturbances.

Motor load transfer due to under- and overvoltages or loss of power supply occurs so

Fast that transient are minimized. Negative phenornena descnbed in Chapter 3 were not

observed. The highest value of overcumnts cruscd by a transfer is ûpproximately 2 times the

rated fùll load cumnt. In fact. system behavior during transfer of the experimental motor

does no< Vary considerably from that during transfer of a passive inductive load.

In the case of short circuit faults and an induction motor load, a different STS

performance was observed. Immediately after the fault. the stator cumnt changes its

direction providing additional power to the fault spot. This may lead to the omission of a

cumnt zero crossing in one of the phases. As a consequence. transfer in this phase will be

delayed until the next cumnt crossing or until commutation between thyristors is possible.

Maximum delay in one phase can be almost half a cycle. However. the overall transfer time is

still less then a cycle.

Page 91: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

CHAPTER 6

Conclusions and Proposals for Future Studies

6.1 Conclusions

The study conducted in this thesis dernonstnted that one of the most cost effective ways

to pmvide unintemptible power to critical industrial loads is to use a Static Transfer Switch

(STS). Its performance dunng the transfer of viuious static loads and particularly an induction

motor load was investigated on the developed laboratory prototype and with the help of digital

computer simulations. The following observations were made during the studies:

Load transfer by STS is accomplished either as a result of commutation between thyristors

or with temporary overlap of the prefemd and altemate sources. In the f i n t case smooth

transfer is usually achieved. However, in the second case significant overcurrents may

arise depending on the type of fault and the system's parameten. To avoid these overcur-

nnts, transfer shouid not start until a cumnt zero crossing is detected.

Selective gating of thyristors in the STS dunng the trmsfer prevents overlapping of the

sources while preserving high spced of the operation. Thenfore, loads supplied from the

sound source are not disturbcd by faults on the other source.

An integration-Reset fault detection method implemented in the laboratory prototype and

in the computer simulation proved to be very robust and diable.

Experimental tests and simulation ~ s u l t s of the 5 hp induction motor transfer during

under- and ovcrvoltages, unbalanctd conditions and loss of power supply dcmonstrated

that the process is accompished in reasonable time so that associated transients are Mn-

imizcd.

Transfer due to short circuit faults was found to be the most scvere for the induction

motor. m e uansfet process is delayed in this case by almost half a cycle. resulting in an

initial stator pcak cumnt of up to 5 times the ratcd cumnt. This is comparable to inrush

cumnt values dunng start-up and therefoie still within tolerablc limits. Duc to good .

damping, the transient current decays very quickly.

Page 92: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

6.2 Proposals for Future Studies

The scope of the cumnt work included the study of the Static Transfer Switch operating

principles. the development of the STS laboratory prototype. expcrimental tests of the static

and induction motor load transfen and the computer simulations of the induction motor

transfer and its verifkation. Complete answers were obtained on the behavior of the STS

during transfer of a single induction rnotor in ternis of the speed of operation and maximum

transients. although, the studied single-machine case is somewhat idealized. Most of the

practical systems include transfomers which like the electric machines represent an active or

energy storage load. if there is residual magnetism in the core of a transformer at the instant of

voltage reapplication and this residual flux possesses an opposite polarity to the normal flux

which the transformer would rather have. then significant innish current will flow. Therefore.

to make the study case more redistic. the transformer should be taken into consideration.

' Most of the real motor loads are not homogeneous. i. e. they do not consist of one or a

group of the same machines. but rather a group of different machines or even a mix of motors

and static loads. Although interaction between different motors in the group is not expected

due to the high specd of transfer. static loads may mitigate transients cauxd by short circuit

faults absorbing a part of the energy supplied by the motor to the fault.

A more elaboratc picturc of the Static Transfer Switch performance can only be

obtained by studying a reai system, e. g. power plant auxiliary system. This can be effectively

done by computer simulation since the simulation results reportcd in the work wcll agree with

experiments.

Page 93: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

References

1. J. D. Jill. "Transfer of Motor Loads Between Out-of-Phase Sources".

EEE Trans. on Industry Applications. Vol. 1 A. 15, #4. JulylAugust 1979,

pp. 376-38 1.

2. S. S. Mulukutla. E. M. Gulachcnski. "A Critical Survcy of Considerations

in Maintaining Process Continuity During Voltage Dips while Protecting

Moton with Reclosing and Bus Transfer Practices", IEEE Trans. on

Power Systems, Vol. 7. #3. August 1992. pp 1299- 1305.

3. J. Reynaud. P. Pillay. "Reclosing Transients in Induction Machines

Including the Effects of Saturation of Magnetizing Branch and a Practical

Case Study", IEEE Trans. on Energy Conversion, Vol. 9, # 4. Iune 1994.

pp 383-389.

4. R. Probst, "Übergangsverhalten von Asynchronmotoren bei Netzum-

schaltung unter Berücksic hiigung der S tromverdrangung in den Laü fer-

staben". ETZ Archiv, Vol. 94 (1973) H.9, pp 5 15-520.

5. M. Abbe, bTransientes Verhaiten von Asynchronmotonng~ppen bei

Spannungsunterbrechungen", ET2 Archiv. 1979 H.3. pp 83-86.

6. M. Abbe. "Digitde Simulation von Asynchronmotorengruppen bei Net-

zumschaltungen", Archiv fUr Elektrotechnik, 62 ( 1980).

7. S. Sriharan, L.H. Tan, H.M. Ting, "Reduced Transient Model of a Group

of Induction Motoa", IEEE Trans. on Energy Conversion, Vol. 8. # 4,

Dcccmber 1993, pp 769J77.

8. R. D. Pettigrew, P. ~owell, "Motor Bus Transfer", . IEEE Trans. on Power

- . Delivery, Vol. 8. # 4, October 1993, pp 1747- 1758.

Page 94: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

9. A. Higgins. P. L. Young, W. L. Snider. H. J. Holley, "Report on Bus

Transfer. Part 1-3. IEEE Trans. on Energy Conversion. Vol. 5. # 3. Sep-

tember 1990. pp 462-484.

10. S. Mazumdar, M. Chiramal, "Bus Transfer Practices at Nuclear Plants",

IEEE Transactions on Power Delivery. Vol. 6, #4. October 1991. pp

1448- 1443.

1 1. T. Masaki, Y. Kataoka. M. Ono, Y. Yokoi, "Development of Static Trans-

fer Switch Equipment for Different Distribution Systems". IPEC Yoko-

hama 95, pp 1588- 1593.

12. K. Matsushita, Y. Kataoka. M. Ono. "High Speed Switchgear Protecting

Power Generating Facilities against Voltage Dip and Interruption". E E E

Catalogue U95TH8025. 1995, pp 726-73 1.

13. W. Schartzenberg, R. W. De Doncker, " 15 kV Medium Voltage Static

Transfer Switch", EEE Industry Application Society. 30th Annual Meet-

ing, 1995, pp 25 15-2520.

14. D. C. Griffith, "Unintemptible Power Supplies", Marcel Dekker, 1989.

15. .S. Krebs, "UHP-40 User's Manud", University of Toronto, Power Group,

1995.

16. A. Oppenheim, "Digital Signal hocessing". Prentice-Hall. 1975.

17. N. Mohan, T. M. Undeland, W. R. Robbins, "Power Electronics", John

Wilcy & Sons, 1995.

18. PSCAD/EMTDC, Manuals, Manitoba HVD<J Rescarch Centre, 1993:

Page 95: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 96: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

r i u n r d lonq d a t ~ l . d a t ~ 2 . a L l t . r p . .Ut-. 4 d J t r m p . a L 4 t . q ~ static i n t coun tg* - 0. c o u o t ~ J c - 0 , c o w i t ~ - c a 0 ; r t a t i c i n t c o u n t . b - 0, c o u n c ~ c - O, c o u n t ~ c a - O ; n t a t i c i n t p-to-a - 0, ~ t 0 - p - O , narm = 1. a8aorm - 0: n t r t i c f l o a t v l - a b ~ ~ e v - f - 0.0, v l 4 c g t e v - f = 0.0, vl-cwrmv-f - 0.0; 8 t a t i c f lait ~ 2 - 4 b ~ r . v - f 0 .o. ~2-bcgr .v-f 0 0 . O , v ~ , c w ~ w , ~ o. O ; r t a t i c f lomt e p i i l o n = 0.0, c o r r g - a b = 0.0. c o r r g g c - 0.0. c o r r g s r = O . O ,

corr- ab - 0.0. corr-a-bc - O . O , c o r r - ~ c a 0. O I s t a t i c f l o a t i l - w r e v i l - (0.0, 0 .0, 0.0. 0.0. 0.01: r t r t i c f l o r t i l J~ ,p revI l - IO.0, 0 .0, 0.0, 0 .0, 0.01; r t a t i c f l o a t i l - c g r m v l l - (0.0, 0.0. 0.0. 0.0, 0.01; n t a t i c f l o a t i l ~ r * v [ ] - ( 0 . 0 , 0.0, 0.0, 0.0. 0.01; a t a t i c f l o a t i 2 , p g r e v l l - (0 .0 , 0.0. 0.0, 0.0, 0.011 r t a t i c f l o a t i2 ,cgrevlI - 10.0, 0.0, 0.0. 0.0, 0 ,O); u t a t i c f l o a t vl ,abgrev[l - [O.O. 0.0, 0.0, 0.0, 0.01; r t a t i c f l o a t v l J ~ g r i v [ l = 10.0. 0 .0. 0.0. 0.0, 0.01; i t a c i c Cloa t v l - c w r e v i l - (0.0. 0 . 0 , 0.0, 0.0. 0.011 r t a t i c t l o a t v 2 - a b g r e v [ l - I0.0, 0 . 0 , 0.0, 0.0, 0.01; r t a t i c f l o a t v 2 ~ c g r e v ( l - (0.0, 0 .0 , 0.0, 0.0, 0 .01; r t a t i c f l o a t v 7 , c ~ r e v l l = (0.0, 0 .0 , 0.0, 0.0, 0.01; n t a t i c f l o a c bI1 - 10.0, 0.0746, 0.2344, 0.46l21, 0.7344, O.O746l; /*diqtcal f i l t e r c o e f f . * / r t a t i c f l o a t vl,trap& - 0.0, v1,trrpJc * 0.0. vl,trrp,cr - 0.0: r t a t i c f l o a t v2,trap-~b = 0.0. v2,trapJc - 0.0, v2,tr.p-cr - 0.0; i a t i ;

/ * A/D & t a acquisition * / data-1 - f r l r o r d l l l t d a t a - i r c u o r d (1 : a L l t . a i 9 = ( ( d a t u i OxOOOOffff) ** 161 i Oxffff0000; r u t - - I (data-1 r Owffff0000) 1 ; 4 U t m m p = ( ( d a t k 2 i Ox0000ffff) << 16) i OxfLttOOOOr .tut- ' ( ( d a t a i O x f f f f 0 0 0 0 ~ ) ; A u ( f h ~ t l adJtUUQt r u - ( f l o a t l rL1taaig; r L 3 - t f l o a t l acl3t.mg: a L 4 - ( f l a a t ) rtL4tmnp;

/ a p r e f e r r e d r o u r c e l i n o - t o - l i n e v o l t r g d r * / vl-ab œ 5 .O ad-1 / ( IriTJ(AiCFL0AT) : vlJc - 5.0 a u / I I K F ~ M A T I ; v L c a = . (vl-ab + v l h c ) ;

/ a a l t e r n a t . s o u r c e I f n i - t a - l i n * v o l c r g e r ./ v L a b - 5.0 a L 3 / t I N T ' s L O A T ) : v 2 h c - 5.0 - a c l ( / i I N T W L O A T I ; v2,ca - - Iv2,ib - v 2 A c ) ;

/ * A/D 6*t4 a c q u i s i t i o n * / d a t c l - i r l v o r d ( 2 1 I d a t u 0 &-rd (2) 1 adJtaup - î ( d a t k l L Ox0000ffff i << 16) L Oxffff0000; a L 2 t . m ~ ' ((data-1 r O x f f f f 0 0 0 0 1 ~ t a L 3 t a p - ( ( d a r d r Ox0000ffff l <c 16) 6 Oxff ffOOOO t acL4ta rg = ((d4t.J r Oxffff000011; .CL1 = (fl0.t) rdJtIIPg1 .La - (fl0.C) ad.Jt8mp; ad-3 r ( f l o a t l aL3t-; a L 4 - ( f l o a t ) rC4tmmpr

/ * p r e f a r r e d i o u r c a l i n @ cur rmnt r * / i L a 5.0 . .Li/ [IHT3NUU)AT) ; i l b - 5.0 0 r u / tIHFJAXJ'LOAT1 ; i l s = 5.0 . a & 3 / ( I H F m L O A T ) t

/ * A/D a c q u i r i t i o n * / d a t ~ l - i i l u o r d ( 5 1 I d i t e = i ~ w r d ( 5 ) t rL1tmmp - ( ( â a t ~ l r Ox0000fLff 1 16) 6 Oxf t f fOOOO; .ut- = t ( d a t u i Oxf f f t 0 0 0 0 ) 1 ; rd-3~- = ( ( d a t u L OrOO00f f f f 1 *< 16) 4 OxffffOOOOt rd - l t . .~ - ( ( d m 0 r O x f f f f 0 0 0 0 ~ ~ 1 4d-l (fl0.t) ad-lt-I r d 3 - c f l o r t l r43t.rsp: ad-3 - ( f l a a t l a L 3 t r m p t rd-4 - ( f l o a t l aL4trsi0t

/ * a l t e r n a t e r o u r c 8 lin. c u r r 8 n t a + / iL. - 5.0 a m / (XWUNU&ûAT) ; i 2 - b 1 5 .O a u / iXHPlUL?LûAT) ; i L c - 5.0 0 rU/(Xm-TI I

/ * p r e f a t m d nourc8 c u r r a n t s f i l t a r i n g * / i L ~ t a o - i L a b 111 ; f o r (i = 1; i <- 41 i++l i l ~ t a m p - i-tu i U r w [ i I b [ i + l l ; i l cf i â - 8 - t q t / * phare A currrnt f i l c i r a d */ 1-3- - tu b t l l r f o r (i - 18 i <= 4; i+*) i-trq = f a t u + i - rwt i l b i i * l l ; iLbf = i l L t i 9 t / * phare 8 curroat f i l t o n b ./ ii,c,t- - il& b i l1 t

Page 97: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

t r l b [ i + l l r f o r t i = 1; i <= 4r i*+) if-c-tump = il-c-tamp i l - cg rev il-c,f il-c,cemp;/* phare C cu r r en t f i l t e rmâ * /

/ * r l t e r n a t e rource cu r r en t r f i l t e r i n g * / i 2 , ~ t a q = il-8 b t l l ; f o r (i = I r i a= 4: i++) i 2 , ~ t i m g = i l - ~ t r a ~ - i2,rgrev i&J = i l , a ~ . a g ; / * phaim A current f i l t e r e d * / i2J-t.r0 = il2 bill; fo r (i = l r i *- 4 1 i+*i i2-b-cemp - i2A-tailp i 2 J g r e v il&-€ - i7-b-craip:/. phare 0 current f i l t e r e d il-c,t.ig - il-c b [ l l ; f o r I i - I r r <= 4; i*+) il-c-cril~ = i2,c-r.ag + i 2 , c g r ~ v [ i l . b [ i * l l r 12-c-f = i7-c,tmpt/* phare C current f i l t e r d * /

/ * p r e f r r r e à source voltaqer f i l t e r i n g * / vl,.b,tamp = vl-ab b l l l ; f o r ( i = 1: i <= 4; i++) vl,a.b,tmp = v l B - r u n g + vl,abgrevti l bIbtr-11 ; vl,ab-f r vl,&b,canigr v U c - t w = v l h c b I l l : fo r [i - Ir <- 41 i++) v l , b c , c ~ vlJc,cuap v l J c g r e v [ r l b [ i * l l : v 1Ac-f = v l b c - t u g t v L c d = . (vl-ab-f vlJc-f 1 ;

/ * a l t e r n a t e source vo l t rqa s f i l t a r i n q * / vl,&-temp = vl-ab b i l l J

f o r ( i = I r i 4; i++) v2-lb-ttag = v2,ab,temp v7-abgrev v 2 ~ b - f = v 2 , ~ ~ c t l ~ g r v lbc- teap = v2Ac b I l l : fo r ( i - 1; i <= 4 ; i**) vlJx,cemp = v2Ac,trmp * v 2 A c g r e v v23c-f - vaAc-camg : vl-CL€ - - (v2-ab,f + va-bc-f :

/ * prefer red rource l i n s - t o - n u e t r a l volcrqer * / vl& = ( v l - c ~ f - vl-ab,f)/3: v1g-f = (vl-ab-f - vlJc,f)/3t vl-c-f = ( ~ 1 - b ~ - f - v l - c ~ f ) / 3 r

/ * a l t e r n a t e source l i n o - t o - n u a t r a l vo l t rqe r * / v L ~ f = ivl-ca-f - v2,rb-f / 3 t v a 4 3 (vl-ab-f - V~JC-c 1 / 3 ; v2-c-f = ~ V ~ J C - f - V ~ , C L ~ 1 / 3 ;

/ * voltage zero crorminq de t ec t i on * / i f ((VI-abgrev,f vl-ab,f 0.0) CC (countg-ab > 5 1 1 councg-ab > 441) 1

counw-ab O:/* countar r e r e t * / vl-ab-trap = 0.0; / * in teqracor r e r e t * / ep r i l on r .vl-ab-f/vl,absrev-f: c o r r u = r p i r l o n . t g - / (1 + epmilon) r rf (corrg,a.b r t-rmp) c o r r a - a b = t -srmgt/* correc t lnq f ac to r * /

1 / * i n r eg ra to r output over O t o p i / 2 * /

if ( c o u n t a ~ b -= 27) 1

ca r rg -ab = vl-ab-f corrg,.b; vl-ab-ave =(vl-ib-trmp - c o r r ~ A ) / (27 U-1 i f ( v l - ab jve 4 0.01 v l 3 - a v m - .vLabIzbavet/* average voltage * / vl-8b-trap = 0.0 ; /* i n t eg ra to r remet * /

1 / * i n t ep ra to r output over p i / 2 t o p i * /

i f (countq-ab =- 41) t

vl,.b,rve = ( v u - t t r p + c o r r s A ) / ( 7 2 u.n01; i f ivl,.b,ave < 0.0) v l a b ~ v e = -vl,lb,.ver/* averiqm voltrqm * / vL.b,crap - 0.0;/* i n t e g r a t o r m e e t * /

1 / * vol tage zero croa i inq detmction a,'

i f ( ( v U c g r e v - f v U c - f <- 0.0) 66 ( c o u n W c + 5 1 1 c o u a w & c 441 I

v14c - t r rp - O,Ot/* i n t eq r8 to r remet * / COUAW-~C = O ; / * counter remet * / epa i lon = - vlgc-f / v l g c g r e v - f t corr-pJc = s p i i l o n t juip/ {l + e p i i l o n ) r i f ( c o r r s J c > t ~ . a p ) c o r r 3 - b ~ = uw;/* c o r n c t i n g f a c t o r */

1 / * i n t eg ra to r output over O t o p i / l * /

i f ( coun lpJc 72) t

c o r r ~ A c = vue-f corr-pJict v l ~ c , r v a = i v l b ~ c r i p - c o r r s J c 1 / (32 U-1 r i f (vl4c-ave < 0.0 1 vlgc-rve = -vlJc,rve; / * avoragr vol tage * / v u e - t r a p = 0.0;/* incoqra tor n i e t * /

1 / * intmqrator output ovmr p i / l t o p i * /

i f t c o u n t g A c -= 4 1 ) (

v U u v m - (v l4c , t r ao + corn-) / (22 Ln-1 r

Page 98: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

i f (v1Jc-ave < 0.0) v lhc-ave = - v l ~ c ~ v e r / * avaragm voltage * / v lgc - t r ap - 0.0; / * i n t w r a t o r n i e t */

I / * voltage zaro cror r ing da t ac t i on ./

i f ((vl-clprev-f * v l - cc f <= 0.0) 66 (couow-ca > 5 1 1 countg,c& 4 4 ) ) 1

v l - c ~ t r a p - O . o r / * intmqrator r e i e t * / C O U I l t q , C I = O ; / * countmr remet * / ap r i l on - ~ v l ~ c ~ f / v l , c 4 p r e v ~ f 1 co r rg , ca - api i lon u.aip/ 11 - *** 1 lonl r i f tcorrg,c& s t - 8 ~ ) co r rg , ca - t,a.mp;/* corrictLng fac tor * /

I / * i n t aq ra to r output over O t o p i / 2 * /

i f icounw-ca =- 12) (

c o r r g , c i 0 v l - c ~ f co r rg , ca t v l - c ~ a v a = ( v l - c ~ c r r p - co r rg , ca i / (22 t ~ u n p l t i f ( v l - c ~ a v e c 0.01 v l - ccave = - V I - c ~ a v e r / * averaqe voltage * / v f - c ~ t r a p = 0.0;/* i n t a q r a t o r rmiet * /

1 / * i n t aq ra to r output over p i / l CO p i * /

i f (countg-ca == 41) (

vl-ccave = ( v l - c ~ t r a p r c o r r g , c a ) / (32 t - ~ m p l ; i f (vl,c&ave * 0 . O ) v l - c ~ a v e = .vl,crcave; / * averagm voltage * / vl,c&,trap = O . O t / * i n t e q r a t o r r eae t * /

1 / * voltage zero cror r inq de t ec t i on * /

i f ((v2-abgrev,f - v2-rb-L c- 0.0) 6& ( c o u n t u . 5 1 1 count- ab > 441 1 I

cowit-a-& - O z / * counter r e i e t * / v2-&b,trap = 0.0; / * i n t a g r a t o r r e i a t * / ep r i l on = - v 2 , a b - f / v 2 ~ b ~ r e v , f r c o r r ~ b = apailon tdraip/(l + a p r i l o a ) : i f .icorr-a-ab > t j r m p ) corr-r,ab u u a g : / * co r r r c t i nq t ac to r * /

1 / * i n t eq ra to r output ovat O t o p i / 2 * /

i f (counr,La.b == 27) (

corr -cab - v2-ab,f - corr-&-ab; v2-ab-ave - tv2-ab-crap - corr,cL.bJ/ t 22 t - rw ; i f (v2-ab,ave c 0. O } v2-ab-rve = -v2,ab,avei / * avetaqe voltage * / v 2 A t r . p = O . O r / * i n t a g r a t o r r e i e t * /

1 / * i n t aq ra to r output ov8r p i /2 t o p i * /

rf (c0unt-a-a.b == 41) [ .

va>-ave = (va&-trap - c o r r - U ) / (22 9 t ~ u n p ) r i f (v2,rb,rve * 0.0) v23b-ave = -vl,ab-nvmt / * rveraqe vol t rqe * / vl,.b,trap = 0.01/* f n t o q r i t o r r e i a t * /

I / * vol tage zero crorainq de t ec t i on * /

i f ( (vl-bcgrev-f vl3rc-f <= 0.0) i r t c o u n U c r 5 1 1 coun-c . 44 J (

v24c-trap = 0.0:/* i n t o g r r t o r teret ./ count ,cPc = Ot/* counter r e i e t */ e p i i l o n - . v 2 b ~ f l v 2 A c j r . v , f ; corr-mJc - epi i lon c a m p / (1 - mgailon) t i f i c o r r - O c ~ a m p ) c o r r d = U m p t / * corrac t ing f ac to r * /

1 / * i n t ag ra to r output over O t o p i / 2 * /

i f (CouaLLbc 0- 22) I

c o r r - U c = v l h c f 9 c o r r a c ; v09c-rve =(vlgc,trap - c o r r - U c I l ( l 2 9 LJamp) : i f ( v 2 J c ~ v e < 0.0) v 2 A c ~ v i - - v l A ~ v e t / * averagm voltage */ v24c-trap = O . o r / * i n tmqr i t o r r o r a t */

1 / * i n t eq ra to r output over p i / 2 t o p i * /

i f t c o u n ~ a - b c == 41) [

- - v2Jcdve - (v2Jc-trrp - c o r r a c ) / (22 u.sp) r i f iv2Jc-rve c 0.0) v2gc-rve = -v2hc-avmi/* rvmrrqm voltage * / v U c - t r a p = O.or/* in tmqrr tor -mat */

1 / * vo l t rge zero c ro r i i ng de t ac t i on ./

i f ((v2,cwr.v-f v 2 , c e <O 0." - " '---r?*&ca + 5 I t c o w u c r > 44) 1 (

v 2 , c ~ t r a p - O.or/* i n t a g r a t o r n i a t */ c o u a t - ~ c a - O;/* couatmr rmaat * / opailon - - v U & f / v L c q p r . v 3 t

Page 99: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

c o r r - ~ c a = a p i i l o n t,samp/(l + e p r r l o n l t i f ( c a r + - ~ c a , c-aungl c o r r - ~ c a = t-8-r / * c o r t a c t r n g t r c r o r * /

1 / * i n t e g r i t o r outpuc over O to p i / 2 * /

i f ( c o u n t - ~ c r -= 22) L

corr-ccc* = v l - c ~ f c o r r - i c r t v 2 , c ~ a v e = (v2,ca-t t r p - corr-r-ra i / (22 c,iumi : i f (v2,c&~vm < 0.0) v 2 - c ~ r v a - -v2,c&-ivar / * rvoraqm voLt4ai * / v a - c ~ t r a p - O.or/* i n t a g r a t o r r i r e t * /

1 / * i n t e q r r t o r outpuc o v e r p i / 2 t o p i * /

i f ( c o u n t - ~ c a == 41) L

v 2 - c ~ a v e - t v 2 - c ~ t r r p + corr-cc.) / l22 c,aupl a rf ( v a - c ~ r v a c 0.0) v 2 - c ~ a v e - - v 2 , c ~ b v a r / * a v a r i q a vo l tage ./ va-ca-crrp - O . O r / * i n c e p r a t o r ris8t * I

1 / * i n t a q r a t i o n ur rng t r i p e r o i d a 1 r u l e * /

vl-ab-trap vl-&,trip + ( v l - a b j r a v - f + vl-ab,f 1 / 2 t-8-r vl_bc,trap = vlJc-trrp + ( v l b c g r a v - f + v1Jc-f 1 12 c,r.sipr vl-ca-trap = v l - c ~ t r a p + (VI-cwriv,f vl,cr,f)/2 t-rmp: v 2 A - t rap = v2,ab-t r r p + (v2-abgrrv,f + v2-ab-f 1 / 2 t - 8 ~ t v2Jc-trrp v 2 A c - t r i p + ( v 2 q c g r a v - f + v2Ac-f 1 /2 t-irop; v 2 , c ~ c r a p v 2 - c ~ t r a g + (v2,c.grsv-f + v 2 - c ~ f 1 /2 t-m.nip;

/ * vol taqa d a v i a t i o n from r a f a r e n c i v i l u a * / vl-ab-err - tvl-ab-i&va - v-ref 1 / v - r d r v U c - a r r t v l h c - a v s - v-ref 1 /v-ref r v l s ~ a r r = ( v l - c u v e . v d e f 1 /v,rmf; v2-ab-err - (v2,&-avi - v3.t ) /v,ref r vLbc,err m (v2Jc-ave - v,taf) /v-rmf r v a - c ~ a r r = (va-c-vi - v-ref l /v,ref;

/ * phare d i f f e r e n c s batween rourcar * / phare-diff = countg-ab - cowit- ab; rf ( a b n o m =- 0)

1 / * tr&nafonQation CO a l p h i - b u t a frame * / v-al = 2 (vl-ab-f . 0.5 vl-bc-f - 0.5 v l - c ~ f 1 /3: vJam - 2 (e0.866 v1Jc-f * n 0 6 6 v l , c ~ f ) / 3 ~ v-ilbe - i q r t (v-al v-al + vJe vJel i / * rpace v e c t o r aba. v i l u r * / i f (v-alba c 3.0)

I / * a l t e r n a t a i o u r c v o l t a g a O.K. * / i f ( (~2-&-ar t * 0.1 r r -v2&-err < 0.1)

cr (v2,bc-err c 0.1 r r .vlAc,arr c 0.11 a6 ( v 2 , c ~ e r r c 0.1 Cc - v J , c ~ e r r * 0.111

i * p r f ~ o u r c . g t r - 0x000000001 / * p r f . arc. t h y r i i t o r r qa t rnq blocked * / p-to-• - I r / * t r m i f a r to a l te rna t . r o u r c e enable*/ a b n o m l z / e a b n o m 1 condi t ion d a t a c t a d * /

1 1

i f ( ALT-ON ( 1 (vl-ab-irr 0 .1 I I vl-ab-arr < -0.1) I I (vlJc,err r 0.1 I I v 1 4 c - e r r < .0.1) I I ( v l - c c a r r 0.1 I l v l - c l a r r c -0.11)

t / * ~ ~ 4 1 t r u a r f e r to a l t e r n a t a r o u r c r * / i f ( ( v 2 A - e r r < 0.1 CL -vl&-arr c 0.11

LL (v2Jc-arr < 0.1 66 -v7Jc,err * 0.11 CL ( v 7 , c ~ a r r * O. 1 r r - v l , c ~ e r r O - 1 1

[ * p r f , r o u r c e g t r = 0x00000000;/* p r f . rrc. t h y r i i c o r r q i t i n q b1ock.d * / L t 0 - a ' 1; abnom - 1;

1 t

1 / * check f o r n o m l o p a r a t i n g c o n d i t i o a i rmr tora t ion * /

i f ( n o m =- 0) i

i f (!ALT-ON CL (vL-ab-arr < 0.1 &C -vl-ab-err < 0.11 CL tvl-bc-err c 0.1 CL - v l _ b ~ e r r c 0.1)

-- c i ( v L - c ~ a t r c 0.1 r i - v l - c ~ e r r < 0.1) 1 (

* r l u o u r c i g t r = 0 x 0 0 0 0 ~ ~ ~ ~ ' ; ~ - a l t . a r c . t h y r i s t o r 8 qa t ing blocked * / ~ t o g - 1 ; / . t r u i r f e r back t o p re fmrr rd r o u r c a e n a b l e * / n o m = l t / * r m r t o r a t i o n of n o m l c o a d i t i o n bcmcted * /

1 I

/ * t r m r f e r t o a l t r n m t a r o u r c e * / i f (p-to-a -- 1)

1 i f (il-a < -0.11

( / * curmat ir n.qativ0 */

Page 100: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

d-y - dwmy 1 OxOOOlOOOOt *altaourclgtr = d u n n y ~ / ~ qatinq riqnal to IFGA * /

1 elma if il^ > 0.1)

( / * current ii poiitive * / dunily - duinay 1 OxOOO0OOOOt * a l U o u r c w t r - duaray;/* qating iiqnaL to FPGA * /

1 if (ii1-a-f c= 0.03) LL (-il-L€ a= 0.03))

( / * currmnt zero crorrinq detectad * / duiry 0 duisy 1 0x00090000;

*alt-8ourc.gtr - duaisiy;/* qating aiqnrl ta FPGA ./ 1

if (il& -0.1) ( / * currmnc ii neqative * /

dumy - dunry 1 0x00020000; alt,iourcrgtr = dunimyr/* qatrng s ~ q n r l to FPGA * /

1 elre if ( i l 2 + 0.1)

i/* currrnt ir poritivm * / dusiy - dunmiy 1 Ox00100000r

* a l t ~ o u r c w t r - & u m y ; ; - qacrnq irqnal ta PPCA * / i

if ((119-f <- 0.031 && (-ilJ,f <= 0.03)) ( / * current zero croaiing delscted * / duaimy * duiany 1 OxOOl2OOOOt *alt,iourc.gtr = dumiiyr/* qrtinq riqnrl CO PPGA * /

1 if (il-c < -0.1)

( / * current ir neqative * / d w - dwny ( 0x000~00001 * a l t ~ o u t c ~ t r = dumiiyt/* qatinq signal ta FPGA * /

1 elre if (il-c r 0.11

( / * current ii poiitive * / duniy = dwmy 1 0x002000001 *alt-aourcagtr = duarny;/* qat~nq iignal to PPGA * /

t If ((il-c,f c= 0.03) &a (-il-c,f e- 0.03))

I / * current zero crorrinq detected * / d m 0 du- 1 0~00240000~ *altjourcagtr duaii~y;/* gatlnq iiqnrl CO ?PGA * /

1 if (dumy =- 0xO03tOOOO)

i O-to-a = O; / * tranifer cogletmd * / dwmy - 0x000000001 n o m = Or/* check for n o A l condition rarcoration mnable * /

I 1

/ * trmrfer back to prefrrrrd source * / if i ~ t o g -= 1)

f if (13,. -0.1)

f / - cutrent ir neqative O'

dunmiy - 4- 1 O ~ O O O ~ O O O O ~ *alt~ourc.gtr = duaiy;/* qattng rima1 to ?PGA * /

I elre i f (13-8 . 0.1)

I / * current ir poiitive * / dusry - dumy 1 0x000~0000; *aluourc.gtr - dumyt / * qatfnq rigaal to PFGA * /

1 if ( ( 1 2 ~ f <= 0.031 rr ( - i 2 ~ f <= 0.03))

( / O current zero crorrinq detected * / duary = dirrry 1 0x00090000~ *prf~ourcegtr dunay;/* qrtiaq riqnal ta ??GA * /

1 if ( 1 2 4 c -0.1)

f / * current ir neqative */ d u r r y l dirary 1 0x00020000~ *aluourc.gtr duaiytl* qatinq signal ta CPQA * /

else if ( 1 2 4 . 0.1) ( / * currant ii poiicivm */

d u r y = duiiy I 0x00100000; *rltJourc.qtr = d m ; / * g8tiog iiqnrl CO PPGA * /

I if ((i2.J-f 0.03) 64 ( - 5 - 3 0.03))

{ / * cur~rnt taro croiring &t.ctmâ */ d i u y * d\Piy 1 OrOOlJOOOO t

Page 101: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

*prf,aourc.gtr = d m ; / * qa t inq i imrl to IIU *, I

i f (il-c c -0.11 I / * c u r r e n t i r noqative * /

dumy - du~rny 1 0x00040000; *a l t , iourc .g t r = duiinyr/* qacanq rrgnal C O t)CI O !

1 a l a e i f (i2-c > 0.1)

( / * c u r r a n t i r pos i t i ve * / duiimy = duniy 1 O~OOI00000r * r l u o u r c e g t r = d u r i y ~ / ~ q r t t n q i r q i u l CO P W ' 1

I I I ((i2-c,f *- 0.03) && (-iI-cJ 0 . 3 1 i )

( / * c u r r r n t zero croa i inq do t ec t i d * f

dunray = duaiaiy 1 0xO0240000r a p r f d o u r c w t r = duiaiiyr -ar nu i r q m l t o tW I

1

vl-abgrev-f = vl-ab-f r v U c g r e v - f = vlJc-f ; v l c w r e v - f V L C L ~ 1 va-abgrrv-f - v 7 A - f : v2Jcgrev-f - v2-b~-f i v2,cwrev-f = v 2 , c ~ f :

/ * counti,nq @ / COulltg*+* ; C O U ~ ~ J C + + ; COUll~t-Oc.++ ; ~ 0 U n ~ a b + + : count,a-bc*+ r COullt~LCa++ ;

t / * end of u i e r funct ion * /

/ * i n i t i a l i r r t i o n t unc t ion * / void ur8r-init (void) f

r u p l i n q g e r i o d - 189.3939 t * p r f - s o u r c a p t r OxOO3?OOOO r / * p t8 fe r r . d raurcr rwitch t u m d on * / * a l t - s o u r c e g t r - 0x00000000;/* rLterri.to rource iwitcb turnd o f f O /

duaray = 0x00000000; / * d w va r i ab l a f o r t.rporary &ta i t o r aqe * / vl-ab-ave - 2 .SU; v1Jc-rve = 2.50: Vl-CLbV8 2 .Sv? v u - a v o = 2.58; vlJx,rvo 2.58 : v 2 - c u v e 2.50; v j e f 12 .58 ; -

vl,rb,.rr 9 1.0; v U c - e r r = 1.0 : v l c c 8 r r = 1.0 t v-err = 0.0; u iar - in ter rupt = STS r

1

Page 102: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Phase (pegrees) 1 1

Page 103: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

APPENDIX C File STS.CDF

ALTERA MAX+plusII Grpk Design File Implemented in FPCA EPF8820GC 192

Page 104: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 105: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

Parameters of Experimental Induction Motor

Name-plate data of the induction motor used in experimcnts are as given below:

Rateci Voltage: 1 10 V (line-line, mis);

Rated Frequency: 60 Hz;

RatedCurrent:26A;

Rated Power: 5 hp (3.725 kW);

Number of Poles: 4:

Rated Speed: 1730 r.p.m. (full load).

Selected Base Values:

Voltage: VB = f i V,,,,,, (line-to-neutral) = 89.8 1 Y;

Frequency: oB = 2nf,led = 376.99 rud/sec.

kr ived Base Values:

Impcdance: 2, = V B / I , = 2.43351;

Power: SB = 3 / 2 V B l B = 4953JW;

Time: tg = 1 /mg = 0.00265 sec;

O Inductance: Lg = Vg/(18 4) = 6.48mH;

Flux: yB = V B / a B ;

Mechanical Speed: nB = CU,/ P p = 1 88.49 rdsec, P p - number of pole pairs;

Measured parameters of the induction motor in per unit system: -.

Stator Resistance: R, = 0.034 peu. ;

0 LeaLage Inductance: L, = 0.26 p.u.;

Page 106: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

- Rotor Resistance: R, = 0.04 p.u.;

COR-Loss Resistancc: R, = 208.35 p. u.;

Con-Las Inductance: Lm = 2.66 peu.;

Measureâ magnetizing characteristic of the experimental motor is shown in Figure C 1

FIGURE Cl. Magnetizing Characteristic of the Experimental Induction Motor

Page 107: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

APPENDIX E

Graphic Design FUe for PSCADIEMTDC Simulation

Page 108: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 109: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 110: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 111: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic
Page 112: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

APPENDIX F

Data File for PSCADIEMTDC Simulation

Page 113: INFORMATION TO USERS - tspace.library.utoronto.ca · Likewise digital time-domain simulations using PSCAD/EMTDC ... CHAPTER 1 Introduction ... 3. Transfer switch (manual or automaiic

0 0 0 c 3 0 . : 3 0 0 0 0 ? 0 0 0 0 0 0 0 0 0 0 0 0 I I 0 0 0 0 . . . . . . . c o o . > ' i .L . , adou . d d d d d d o o o ~ o o ~ o o o o