inrush presentation

Upload: wexki

Post on 03-Jun-2018

266 views

Category:

Documents


4 download

TRANSCRIPT

  • 8/12/2019 Inrush Presentation

    1/35

    Fundamentals of TransformerInrush

    Suhag Patel, P.E.GE Digital Energy

    Placentia, CA

    Texas A&M Protective Relay Conference

    College Station, TX April 13, 2010

  • 8/12/2019 Inrush Presentation

    2/35

    Objective Understand why transformer inrush

    occurs

    Understand the characteristics of aninrush waveform

    Understand the impact transformer

    inrush can have on differential relays Discuss various methods to reliably

    restrain differential relay operation

  • 8/12/2019 Inrush Presentation

    3/35

    Basics of Differential Relays Very Simple

    Sum of Allcurrents shouldbe zero.

    Must Compensatefor Phase Shift andMagnitudeDifference

  • 8/12/2019 Inrush Presentation

    4/35

    Problems with Transformer

    Differential Relays

  • 8/12/2019 Inrush Presentation

    5/35

    Inrush Current Impact on

    Differential Relay

  • 8/12/2019 Inrush Presentation

    6/35

    What is Inrush Current

    All transformers must establish flux in the transformer core This flux causes a current to flow known as the

    magnetizing current Magnetizing current appears as differential current

  • 8/12/2019 Inrush Presentation

    7/35

    Steady State Magnetization

    Current

    Non-Linearity of the core results in a non-linearmagnetizing current waveform

    Notice flux lags excitation voltage by 90 degrees Steady State Magnetizing current is in the range of 1-3% of

    XFMR FLA

  • 8/12/2019 Inrush Presentation

    8/35

    Magnetizing Current Under

    Non-Steady State Conditions

    When an abrupt change in excitation voltage occurs, alarge magnetizing current can flow.

    The Magnetizing Inrush Current is dependant on severalfactors, which will be discussed on the following slides

  • 8/12/2019 Inrush Presentation

    9/35

    Impact of Switching Point

    Highest magnitude inrush occurs when excitation voltage isapplied at zero crossing.

    Lowest magnitude inrush occurs when excitation voltage is

    applied at 90 degrees.

    Time

    e

    tar t of event

    Time

    e

    tar t of event

  • 8/12/2019 Inrush Presentation

    10/35

    Impact of Remnant Flux

    Remnant Flux can be positive or negative

    This can lead to increased or decreased magnetizing

    inrush current

  • 8/12/2019 Inrush Presentation

    11/35

    Impact of Power System

    Impedance

    The peak magnitude of the inrush current isdictated by the strength of the power systemsource

    The duration of an inrush event is dictated by the

    resistive losses in the circuit

  • 8/12/2019 Inrush Presentation

    12/35

    Impact of Transformer Design Electrical steel has remained fairly

    constant over the years

    Laminated core designs lead to lowerreluctance cores

    Lower reluctance cores are more

    efficient leading to lower magnetizingcurrent

  • 8/12/2019 Inrush Presentation

    13/35

    Transformer Inrush Waveform

    No CT Errors Time Domain

  • 8/12/2019 Inrush Presentation

    14/35

    Transformer Inrush Waveform

    No CT Error Freq Domain

  • 8/12/2019 Inrush Presentation

    15/35

    Transformer Inrush Waveformwith CT Sat Time Domain

  • 8/12/2019 Inrush Presentation

    16/35

    Transformer Inrush Waveformwith CT Sat Freq Domain

  • 8/12/2019 Inrush Presentation

    17/35

    When Does Inrush Occur?

    During Transformer Energization: Typically the most severe case, because excitation voltage is going

    from zero to maximum value

    During Post Fault Voltage Recovery: During a fault the system voltage is depressed, and then returns to

    full value Not typically as sever as Energization because Flux wont be fully

    offset from excitation voltage

    Sympathetic Inrush:

  • 8/12/2019 Inrush Presentation

    18/35

    Inrush Restraint Methods

    As shown earlier, high levels of inrushcurrent can cause differential relay

    misoperation

    We need to identify this condition and stopthe differential relay from operating while

    inrush condition is present

    Many methods exist, all rely on thecharacteristics of the inrush waveform

  • 8/12/2019 Inrush Presentation

    19/35

    Percentage of Total Harmonic

    This method utilizes the fact the inrushwaveform is rich in harmonics.

    EM relays applied this per phase. Problems

    More efficient core designs produce less harmoniccontent

    CT Saturation essentially creates a setting floor

  • 8/12/2019 Inrush Presentation

    20/35

    CT Saturation Waveform

    Note that a saturated CT waveform ishighly non-linear

  • 8/12/2019 Inrush Presentation

    21/35

    CT Saturation Spectrum

    Note the high 2nd

    harmonic component

  • 8/12/2019 Inrush Presentation

    22/35

    Typical 2nd Harmonic Ratios

    Typical values of 2nd

    harmonic tofundamental ratios in

    the range of 10%-60% Can be much lower as

    shown

    Microprocessor relayshave introducedmethods to deal withthis problem

  • 8/12/2019 Inrush Presentation

    23/35

    Percentage of 2nd Harmonic

    This method utilizes the fact the inrushwaveform has a dominant second

    harmonic component. EM relays applied this per phase. CT Saturation still a problem

  • 8/12/2019 Inrush Presentation

    24/35

    Percentage of 4th Harmonic

    This method utilizes the fact the inrushwaveform is not symmetric, leading to evenharmonics

    Used in some microprocessor relays CT Saturation still a problem No significant benefit over 2nd harmonic

    methods

  • 8/12/2019 Inrush Presentation

    25/35

    Waveshape Based Method

    Relies on flat spotsnear zero value

    CT saturation cancompromisesecurity anddependability

    Were used widelyin solid-staterelays

  • 8/12/2019 Inrush Presentation

    26/35

    Adaptive 2nd Harmonic Method

    Method utilizes 2nd

    HarmonicMagnitude and

    Angle Dynamically

    restrains over amaximum of 6cycles

    May slowoperation by a fewcycles if 2nd

    harmonic current

    is present

  • 8/12/2019 Inrush Presentation

    27/35

    How to Apply VariousMethods?

    EM relays typically used either % totalharmonic or % 2nd harmonic methods

    EM relays applied them on a per-phasebasis Microprocessor relays can apply many

    methods on a per-phase, 1 out of 3

    (cross blocking), 2 out of 3, or averagebasis Pros and Cons to each

  • 8/12/2019 Inrush Presentation

    28/35

    Considerations When ApplyingHarmonic Restraint

    Reliability Ability for the differentialrelay to operate on all internal faults

    Security Ability for the differential relayto restrain for all transformer inrushevents

    Speed How quickly internal faults are

    cleared No method is best, depends on user

    requirements

  • 8/12/2019 Inrush Presentation

    29/35

    Considerations When ApplyingHarmonic Restraint

    1 out of 3 (Cross Blocking) Very secure,but can reduce reliability or speed: Consider fault during energization

    Per Phase Less secure, very reliable: Consider low 2nd harmonic inrush

    2 out of 3 More secure then Per Phase,

    potentially less reliable Averaging Method More secure then

    Per Phase or 2 out of 3, no compromiseon reliability

  • 8/12/2019 Inrush Presentation

    30/35

    Transformer Inrush Impact onGenerator Differential

    High DC component of Inrush may saturateGen CTs.

    Using harmonic restraint is not a good

    solution, adds too much delay

    87G

  • 8/12/2019 Inrush Presentation

    31/35

    Transformer Inrush Impact onGenerator Differential

    Flux balanced CT configuration can be used onsmaller Generators

  • 8/12/2019 Inrush Presentation

    32/35

    Transformer Inrush Impact onGenerator Differential

    For problem installations, transformer CB closecan be used to delay 87G

    87G

    Transformer Close CB Command

    Delays 87G Relay

  • 8/12/2019 Inrush Presentation

    33/35

    Importance of GoodWaveform Capture

    Depending on specific system conditions and transformerdesign, varying levels of 2nd harmonic content may bepresent

    It is in the users best interest to capture inrushwaveforms whenever possible

    If a fairly complete library of actual waveform data isavailable, this can be used to fine tune settings andevaluate new methods

  • 8/12/2019 Inrush Presentation

    34/35

    Conclusion

    Transformer Inrush will occur anytime a change tothe transformer excitation voltage occurs

    Transformer Inrush appears as differential current to

    the transformer differential relay 2nd harmonic based methods should not be set lower

    then 15% otherwise dependability is put at risk

    Many blocking methods exist, however, they pose

    various compromises to security, reliability, andspeed.

    The right choice of blocking method depends on theindividual user

    Generator Differential relays can also be impacted by

    transformer inrush

  • 8/12/2019 Inrush Presentation

    35/35

    Thank You

    Suhag Patel

    [email protected]

    562-233-1371