Inspection Report Happy Chicago Bungalow Owner Property Address: Focal Point Home Inspection Ltd. Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Chicago Bungalow Owner Focal Point Home Inspection Ltd. Page 1 of 31

Upload: others

Post on 29-Aug-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

Inspection Report

Happy Chicago Bungalow Owner

Property Address:

Focal Point Home Inspection Ltd.

Joseph Poelsterl 450.0102206334 W. Grace st

Chicago Illinois 606341-773-454-6700

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 1 of 31

Page 2: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

Table of Contents

Cover Page

Table of Contents

Intro Page

General Summary

1 Roofing

2 Exterior

3 Garage

4 Interiors

5 Structural Components

6 Plumbing System

7 Electrical System

8 Heating / Central Air Conditioning

9 Insulation and Ventilation

10 Built-In Kitchen Appliances

Invoice

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 2 of 31

Page 3: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

Date: 2/23/2013 Time: Report ID:

Property: Customer:Happy Chicago Bungalow Owner

Real Estate Professional:Gloria ReeColdwell Banker

Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. All comments by the inspector should beconsidered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a secondopinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair orreplacement of item, component or unit should be considered before you purchase the property.

Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to befunctioning as intended allowing for normal wear and tear.

Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it wasfunctioning as intended and will state a reason for not inspecting.

Not Present (NP) = This item, component or unit is not in this home or building.

Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by aqualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Standards of Practice:INACHI National Association of CertifiedHome Inspectors, Illinois

In Attendance:Customer and their agent

Type of building:Single Family (1 story)

Style of Home:Bungalow

Approximate age of building:85

Home Faces:South

Temperature:27

Weather:Cloudy, Snow

Ground/Soil surface condition:Frozen

Rain in last 3 days:No

Radon Test:No

Water Test:No

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 3 of 31

Page 4: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

General Summary

Focal Point Home Inspection Ltd.

6334 W. Grace stChicago Illinois 60634

1-773-454-6700

CustomerHappy Chicago Bungalow Owner

Address

The following items or discoveries indicate that these systems or components do not function as intended or adverselyaffects the habitability of the dwelling; or warrants further investigation by a specialist, or requires subsequentobservation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it inproper functioning condition or recommendations to upgrade or enhance the function or efficiency of the home. ThisSummary is not the entire report. The complete report may include additional information of concern to the customer. It isrecommended that the customer read the complete report.

2. Exterior

2.0 WALL CLADDING FLASHING AND TRIM

Inspected, Repair or Replace

Inspector recommends covering exposed sheathing where old electrical meter was mounted.(Picture 1)

Inspector recommends covering exposed sheathing where old porch railings attached to structure.(Picture 2)

2.1 DOORS (Exterior)

Inspected, Repair or Replace

Exterior door on North elevation should be sealed shut to prevent accidental falls.(Picture 1) (Picture 2)

2.6 MASONRY

Inspected, Repair or Replace

Tuckpointing needed on stairway wing walls.(Picture 1) (Picture 2)(Picture 3)(Picture 4)(Picture 5)(Picture 6)(Picture7)(Picture 8)(Picture 9)

Tuckpointing needed Bottom of East elevation.(Picture 10)

3. Garage

3.4 OCCUPANT DOOR FROM GARAGE TO INSIDE HOME

Inspected, Repair or Replace

Entry door has been split and damaged.(Picture 1)

3.5 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with resistance)

Inspected, Repair or Replace

(1) Garage door does not reverse when held in resistance. Adjustments can be made here.(Picture 1)

(2) The sensors are in place for garage door(s) and will reverse the door.

3.7 Electrical system in garage.

Inspected, Repair or Replace

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 4 of 31

Page 5: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

3. Garage

Receptacle in garage must be changed to a GFCI type.(Picture 1)

3.8 Windows

Inspected, Repair or Replace

Windows (3) do not have trim installed.(Picture 1)

4. Interiors

4.1 WALLS

Inspected, Repair or Replace

Wall and trim has not been completed inside basement doorway.(Picture 1)

Basement kitchen area not complete.(Picture 2)

4.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS

Inspected, Repair or Replace

Railing is missing for stairway to 2nd floor.(Picture 1)

Hand rail at top of basement stairs is loose. Repairs needed.(Picture 2)

5. Structural Components

5.1 WALLS (Structural)

Inspected, Repair or Replace

Old basement and attic stair well have not been sealed and braced properly. Inspector recommends evaluation bylicensed structural engineer for recommends repairs.(Picture 1)(Picture 2)(Picture 3)

6. Plumbing System

6.3 MAIN WATER SHUT-OFF DEVICE (Describe location)

Inspected, Repair or Replace

Water main valve is located on South wall of basement near gas meter.(Picture 1)

Main copper water line has been cut to drain down plumbing system in building.(Picture 2)

7. Electrical System

7.0 SERVICE ENTRANCE CONDUCTORS

Inspected, Repair or Replace

Inspector recommends removal of birds nest on top of electrical service entrance.(Picture 1)

7.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIRAMPERAGE AND VOLTAGE

Inspected, Repair or Replace

Inspector observed bx cable still connected in breaker panel exiting old dry vent and laying exposed on groundunder back porch. Removal suggested.(Picture 1)(Picture 2)(Picture 3)

Romex cable is not legal to use in the city of Chicago.(Picture 4)

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 5 of 31

Page 6: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

7. Electrical System

7.3 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of ceiling fans,lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exteriorwalls)

Inspected, Repair or Replace

(1) Exterior receptacle on South elevation must be changed to a GFCI type.(Picture 1)

Light Fixture for front porch ceiling is missing cover and bulbs.(Picture 2)

Only 2 electrical receptacles are installed on the 2nd floor. Code requires 1 every eight foot of wall.(Picture 3)

Light switch incomplete for basement stairway light.(Picture 4)

(2) At least Two at the Sunroom is a "two-prong" receptacle, and is not a "three-prong" GFCI outlet with exteriorcover. This is a safety issue that needs to be corrected. A qualified licensed electrical contractor should performrepairs that involve wiring.(Picture 3)(Picture 4)

(3) At least two "three-prong" outlets are not working in the bedroom. Further inspection is needed by a qualifiedlicensed electrical contractor. A qualified licensed electrical contractor should correct as needed.(Picture 6)(Picture7)

9. Insulation and Ventilation

9.4 VENTING SYSTEMS (Kitchens, baths and laundry)

Inspected, Repair or Replace

Dryer vent is missing exterior vent damper.(East elevation).(Picture 1)

This dryer vent is not being used at time of inspection.(Picture 2)

Bathroom exhaust fan on main floor needs cleaning.(Picture 3)

10. Built-In Kitchen Appliances

10.1 RANGES/OVENS/COOKTOPS

Inspected, Repair or Replace

Cooking range must have anti tip device installed as per manufactures instructions.(Picture 1)

Home inspectors are not required to report on the following: Life expectancy of any component or system; The causes of theneed for a repair; The methods, materials, and costs of corrections; The suitability of the property for any specialized use;Compliance or non-compliance with codes, ordinances, statutes, regulatory requirements or restrictions; The market value ofthe property or its marketability; The advisability or inadvisability of purchase of the property; Any component or system thatwas not observed; The presence or absence of pests such as wood damaging organisms, rodents, or insects; or Cosmeticitems, underground items, or items not permanently installed. Home inspectors are not required to: Offer warranties orguarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter any area orperform any procedure that may damage the property or its components or be dangerous to the home inspector or otherpersons; Operate any system or component that is shut down or otherwise inoperable; Operate any system or componentthat does not respond to normal operating controls; Disturb insulation, move personal items, panels, furniture, equipment,plant life, soil, snow, ice, or debris that obstructs access or visibility; Determine the presence or absence of any suspectedadverse environmental condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise,contaminants in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or removesuspected hazardous substances; Predict future condition, including but not limited to failure of components; Since this reportis provided for the specific benefit of the customer(s), secondary readers of this information should hire a licensed inspectorto perform an inspection to meet their specific needs and to obtain current information concerning this property.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 6 of 31

Page 7: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Joseph Poelsterl

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 7 of 31

Page 8: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

1. Roofing

The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and Signs of' leaks orabnormal condensation on building components. The home inspector shall: Describe the type of roof covering materials; and Report the methods used toobserve the roofing. The home inspector is not required to: Walk on the roofing; or Observe attached accessories including but not limited to solar systems,antennae, and lightning arrestors.

IN NI NP RR

1.0 ROOF COVERINGS •

1.1 FLASHINGS •

1.2 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS •

1.3 ROOF DRAINAGE SYSTEMS •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsRoof Covering:

3-Tab fiberglassAsphalt/Fiberglass

Viewed roof covering from:GroundBinoculars

Sky Light(s):None

Chimney (exterior):Brick

Comments:

1.0 The roof covering is old, and the life of covering has expired. The covering does need to be replaced. While it could last ayear or so, some areas may need patching with tar as leaks develop.

Shingles are beginning to lift.Plan to replace roof covering.(Picture 1)(Picture 2)

1.0 Item 1(Picture) Shingles are beginning tolift.Plan to replace roof covering.

1.0 Item 2(Picture)

1.3 The gutters appear intact but due to the lack of recent rain, I am unable to determine if gutters leak at seams or spillswater.

The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, someareas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes anattempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 8 of 31

Page 9: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

2. Exterior

The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage door operators;Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation, grading, drainage, driveways, patios,walkways, and retaining walls with respect to their effect on the condition of the building. The home inspector shall: Describe wall cladding materials; Operateall entryway doors and a representative number of windows; Operate garage doors manually or by using permanently installed controls for any garage dooroperator; Report whether or not any garage door operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probeexterior wood components where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening,shutters, awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote controltransmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playgroundequipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures; or Presence or condition of buried fuel storage tanks.The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, snow, ice or debris that obstructs access or visibility.

IN NI NP RR

2.0 WALL CLADDING FLASHING AND TRIM • •

2.1 DOORS (Exterior) • •

2.2 WINDOWS •

2.3DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES, PATIO/COVER AND APPLICABLE RAILINGS

2.4VEGETATION, GRADING, DRAINAGE, DRIVEWAYS, PATIO FLOOR, WALKWAYSAND RETAINING WALLS (With respect to their effect on the condition of thebuilding)

2.5 EAVES, SOFFITS AND FASCIAS •

2.6 MASONRY • •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsSiding Style:

DropSiding Material:

Aluminum 8"Exterior Entry Doors:

WoodAppurtenance:

Deck with stepsPorchSidewalk

Driveway:Street Parking

Comments:

2.0 Inspector recommends covering exposed sheathing where old electrical meter was mounted.(Picture 1)

Inspector recommends covering exposed sheathing where old porch railings attached to structure.(Picture 2)

2.0 Item 1(Picture) Inspector recommendscovering exposed sheathing where old electricalmeter was mounted.

2.0 Item 2(Picture) Inspectorrecommends covering exposedsheathing where old porch railingsattached to structure.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 9 of 31

Page 10: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

2.1 Exterior door on North elevation should be sealed shut to prevent accidental falls.(Picture 1) (Picture 2)

2.1 Item 1(Picture) Exterior door onNorth elevation should be sealed shutto prevent accidental falls.

2.1 Item 2(Picture)

2.4 Inspector could not inspect concrete walks for damage due to snow cover.(Picture 1)

2.4 Item 1(Picture) Inspector could not inspectconcrete walks for damage due to snow cover.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 10 of 31

Page 11: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

2.6 Tuckpointing needed on stairway wing walls.(Picture 1) (Picture 2)(Picture 3)(Picture 4)(Picture 5)(Picture 6)(Picture 7)(Picture 8)(Picture 9)

Tuckpointing needed Bottom of East elevation.(Picture 10)

2.6 Item 1(Picture) Tuckpointingneeded on stairway wing walls.

2.6 Item 2(Picture)

2.6 Item 3(Picture) 2.6 Item 4(Picture)

2.6 Item 5(Picture) 2.6 Item 6(Picture)

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 11 of 31

Page 12: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

2.6 Item 7(Picture) 2.6 Item 8(Picture)

2.6 Item 9(Picture) 2.6 Item 10(Picture) Tuckpointing needed Bottomof East elevation.

The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, someareas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be consideredbefore purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in thisinspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 12 of 31

Page 13: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

3. Garage

IN NI NP RR

3.0 GARAGE CEILINGS •

3.1 GARAGE WALLS (INCLUDING FIREWALL SEPARATION) •

3.2 GARAGE FLOOR •

3.3 GARAGE DOOR (S) •

3.4 OCCUPANT DOOR FROM GARAGE TO INSIDE HOME • •

3.5GARAGE DOOR OPERATORS (Report whether or not doors will reverse when metwith resistance)

• •

3.6 ROOF •

3.7 Electrical system in garage. • •

3.8 Windows • •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsGarage Door Type:

One automaticGarage Door Material:

InsulatedMetal

Auto-opener Manufacturer:LIFT-MASTER1/2 HORSEPOWER

Comments:

3.4 Entry door has been split and damaged.(Picture 1)

3.4 Item 1(Picture) Entry door hasbeen split and damaged.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 13 of 31

Page 14: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

3.5 (1) Garage door does not reverse when held in resistance. Adjustments can be made here.(Picture 1)

3.5 Item 1(Picture) Garage door does not reversewhen held in resistance. Adjustments can be madehere.

(2) The sensors are in place for garage door(s) and will reverse the door.

3.7 Receptacle in garage must be changed to a GFCI type.(Picture 1)

3.7 Item 1(Picture) Receptacle in garage must bechanged to a GFCI type.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 14 of 31

Page 15: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

3.8 Windows (3) do not have trim installed.(Picture 1)

3.8 Item 1(Picture) Windows (3) donot have trim installed.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 15 of 31

Page 16: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

4. Interiors

The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a representative number of installedcabinets; and A representative number of doors and windows. The home inspector shall: Operate a representative number of windows and interior doors;and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The homeinspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, orother window treatments.

IN NI NP RR

4.0 CEILINGS •

4.1 WALLS • •

4.2 FLOORS •

4.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS • •

4.4 COUNTERS AND A REPRESENTATIVE NUMBER OF CABINETS •

4.5 DOORS (REPRESENTATIVE NUMBER) •

4.6 WINDOWS (REPRESENTATIVE NUMBER) •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsCeiling Materials:

Gypsum BoardPlaster

Wall Material:Gypsum BoardPlaster

Floor Covering(s):CarpetHardwood T&GVinyl

Interior Doors:Wood

Window Types:AGEDSingle paneStorm windows

Window Manufacturer:UNKNOWN

Cabinetry:Wood

Countertop:Granite

Comments:

4.1 Wall and trim has not been completed inside basement doorway.(Picture 1)

Basement kitchen area not complete.(Picture 2)

4.1 Item 1(Picture) Wall and trim hasnot been completed inside basementdoorway.

4.1 Item 2(Picture) Basement kitchen area notcomplete.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 16 of 31

Page 17: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

4.3 Railing is missing for stairway to 2nd floor.(Picture 1)

Hand rail at top of basement stairs is loose. Repairs needed.(Picture 2)

4.3 Item 1(Picture) Railing is missing for stairwayto 2nd floor.

4.3 Item 2(Picture) Hand rail at top of basementstairs is loose. Repairs needed.

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, someareas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please beaware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommendedthat qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 17 of 31

Page 18: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

5. Structural Components

The Home Inspector shall observe structural components including foundations, floors, walls, columns or piers, ceilings and roof. The home inspector shalldescribe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector shall: Probe structuralcomponents where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except when access is obstructed, when entrycould damage the property, or when dangerous or adverse situations are suspected; Report the methods used to observe under floor crawl spaces andattics; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components.The home inspector is not required to: Enter any area or perform any procedure that may damage the property or its components or be dangerous to oradversely effect the health of the home inspector or other persons.

IN NI NP RR

5.0FOUNDATIONS, BASEMENTS AND CRAWLSPACES (Report signs of abnormal orharmful water penetration into the building or signs of abnormal or harmfulcondensation on building components.)

5.1 WALLS (Structural) • •

5.2 COLUMNS OR PIERS •

5.3 FLOORS (Structural) •

5.4 CEILINGS (structural) •

5.5 ROOF STRUCTURE AND ATTIC •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsFoundation:

Poured concreteMethod used to observeBasement:

From entryWalked

Floor Structure:2 X 8

Wall Structure:MasonryBrick

Columns or Piers:Wood piers

Ceiling Structure:2X6Not visible

Roof Structure:Stick-builtCommon boardNot visible

Roof-Type:Hip

Method used to observeattic:

From entryWalked

Attic info:No Storage

Comments:

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 18 of 31

Page 19: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

5.1 Old basement and attic stair well have not been sealed and braced properly. Inspector recommends evaluation bylicensed structural engineer for recommends repairs.(Picture 1)(Picture 2)(Picture 3)

5.1 Item 1(Picture) 5.1 Item 2(Picture)

5.1 Item 3(Picture)

The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern,some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should beconsidered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments inthis inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 19 of 31

Page 20: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

6. Plumbing System

The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets;functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipeinsulation; leaks; and functional drainage; Hot water systems including: water heating equipment; normal operating controls; automatic safety controls; andchimneys, flues, and vents; Fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks; andSump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping materials; Water heatingequipment; and Location of main water supply shutoff device. The home inspector shall operate all plumbing fixtures, including their faucets and all exteriorfaucets attached to the house, except where the flow end of the faucet is connected to an appliance. The home inspector is not required to: State theeffectiveness of anti-siphon devices; Determine whether water supply and waste disposal systems are public or private; Operate automatic safety controls;Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; Fire and lawn sprinkler systems;On-site water supply quantity and quality; On-site waste disposal systems; Foundation irrigation systems; Spas, except as to functional flow and functionaldrainage; Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials.

IN NI NP RR

6.0 PLUMBING DRAIN, WASTE AND VENT SYSTEMS •

6.1 PLUMBING WATER SUPPLY AND DISTRIBUTION SYSTEMS AND FIXTURES •

6.2 HOT WATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND VENTS •

6.3 MAIN WATER SHUT-OFF DEVICE (Describe location) • •

6.4 MAIN FUEL SHUT OFF (Describe Location) •

6.5 EJECTION PUMP •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsWater Source:

PublicWater Filters:

NonePlumbing Water Supply(into home):

LEAD HOSEPlumbing WaterDistribution (inside home):

CopperWasher Drain Size:

Laundry tubPlumbing Waste:

PVCCast iron

Water Heater PowerSource:

Gas (quick recovery)Water Heater Capacity:

75 GallonManufacturer:

WEIL MCLAINWater Heater Location:

BasementUtility Room

Comments:

6.1 The plumbing has been winterized and water is off. I did not inspect condition of faucets, fixtures, plumbing, pressure orvolume. There is no additional charge for a separate trip to return and inspect plumbing.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 20 of 31

Page 21: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

6.3 Water main valve is located on South wall of basement near gas meter.(Picture 1)

Main copper water line has been cut to drain down plumbing system in building.(Picture 2)

6.3 Item 1(Picture) Water main valve is located onSouth wall of basement near gas meter.

6.3 Item 2(Picture) Main copper waterline has been cut to drain downplumbing system in building.

6.4 Gas meter and shut off valve located on South wall of basement.(Picture 1)

Gas meter and main water valve was concealed behind drywall. Access panel door should be installed.(Picture 2)

6.4 Item 1(Picture) Gas meter and shut off valvelocated on South wall of basement.

6.4 Item 2(Picture) Gas meter andmain water valve was concealedbehind drywall. Access panel doorshould be installed.

The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern,some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle.Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. Ifthe water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the pipingsystem. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. Itis recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 21 of 31

Page 22: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

7. Electrical System

The home inspector shall observe: Service entrance conductors; Service equipment, grounding equipment, main over current device, and main anddistribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over current devices, and the compatibility of theirampacities and voltages; The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside thehouse, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior plumbing fixtures, and allreceptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and Smoke detectors. Thehome inspector shall describe: Service amperage and voltage; Service entry conductor materials; Service type as being overhead or underground; andLocation of main and distribution panels. The home inspector shall report any observed aluminum branch circuit wiring. The home inspector shall report onpresence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The homeinspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over current device except ground fault circuitinterrupters; Dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltagesystems; Security system devices, heat detectors, or carbon monoxide detectors; Telephone, security, cable TV, intercoms, or other ancillary wiring that isnot a part of the primary electrical distribution system; or Built-in vacuum equipment.

IN NI NP RR

7.0 SERVICE ENTRANCE CONDUCTORS • •

7.1 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAINAND DISTRIBUTION PANELS

7.2 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES ANDCOMPATIBILITY OF THEIR AMPERAGE AND VOLTAGE

• •

7.3CONNECTED DEVICES AND FIXTURES (Observed from a representative numberoperation of ceiling fans, lighting fixtures, switches and receptacles located inside thehouse, garage, and on the dwelling's exterior walls)

• •

7.4POLARITY AND GROUNDING OF RECEPTACLES WITHIN 6 FEET OF INTERIORPLUMBING FIXTURES, AND ALL RECEPTACLES IN GARAGE, CARPORT,EXTERIOR WALLS OF INSPECTED STRUCTURE

7.5 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS) •

7.6 LOCATION OF MAIN AND DISTRIBUTION PANELS •

7.7 SMOKE DETECTORS •

7.8 CARBON MONOXIDE DETECTORS •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsElectrical ServiceConductors:

Overhead service220 volts

Panel capacity:150 AMP

Panel Type:Circuit breakers

Electric PanelManufacturer:

SQUARE DBranch wire 15 and 20AMP:

CopperWiring Methods:

RomexConduitBX cable

Comments:

7.0 Inspector recommends removal of birds nest on top of electrical service entrance.(Picture 1)

7.0 Item 1(Picture) Inspector recommends removalof birds nest on top of electrical service entrance.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 22 of 31

Page 23: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

7.2 Inspector observed bx cable still connected in breaker panel exiting old dry vent and laying exposed on ground underback porch. Removal suggested.(Picture 1)(Picture 2)(Picture 3)

Romex cable is not legal to use in the city of Chicago.(Picture 4)

7.2 Item 1(Picture) Inspector observed bx cablestill connected in breaker panel exiting old dry ventand laying exposed on ground under back porch.Removal suggested.

7.2 Item 2(Picture)

7.2 Item 3(Picture)

7.2 Item 4(Picture) Romex cable is notlegal to use in the city of Chicago.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 23 of 31

Page 24: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

7.3 (1) Exterior receptacle on South elevation must be changed to a GFCI type.(Picture 1)

Light Fixture for front porch ceiling is missing cover and bulbs.(Picture 2)

Only 2 electrical receptacles are installed on the 2nd floor. Code requires 1 every eight foot of wall.(Picture 3)

Light switch incomplete for basement stairway light.(Picture 4)

7.3 Item 1(Picture) Exterior receptacle on Southelevation must be changed to a GFCI type.

7.3 Item 2(Picture) Light Fixture for front porchceiling is missing cover and bulbs.

7.3 Item 3(Picture) Only 2 electrical receptaclesare installed on the 2nd floor. Code requires 1every eight foot of wall.

7.3 Item 4(Picture) Light switchincomplete for basement stairwaylight.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 24 of 31

Page 25: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

(2) At least Two at the Sunroom is a "two-prong" receptacle, and is not a "three-prong" GFCI outlet with exterior cover. This isa safety issue that needs to be corrected. A qualified licensed electrical contractor should perform repairs that involve wiring.(Picture 3)(Picture 4)

7.3 Item 5(Picture) 7.3 Item 6(Picture)

(3) At least two "three-prong" outlets are not working in the bedroom. Further inspection is needed by a qualified licensedelectrical contractor. A qualified licensed electrical contractor should correct as needed.(Picture 6)(Picture 7)

7.3 Item 7(Picture) 7.3 Item 8(Picture)

7.4 2 receptacles on kitchen counter must be changed to GFCI type.(Picture 1)

7.4 Item 1(Picture) 2 receptacles on kitchencounter must be changed to GFCI type.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 25 of 31

Page 26: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

7.6 Electrical panel located on North wall of basement.

Square D Electrical Panel(Picture 1)

7.6 Item 1(Picture) Square DElectrical Panel

7.7 (1) The smoke detector should be tested at common hallway to bedrooms upon moving in to home.

(2) The smoke detector needs locating at least 4 inches from ceiling/wall junction and no further than 12 inches away.

Inspector recommends replacement of smoke detectors every five years.

7.8 There is no carbon monoxide detector found in home. It is recommended that one be installed according to themanufacturer's instructions.

The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas ofconcern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator forexample) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this reportshould be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to thecomments in this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 26 of 31

Page 27: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

8. Heating / Central Air Conditioning

The home inspector shall observe permanently installed heating and cooling systems including: Heating equipment; Cooling Equipment that is central tohome; Normal operating controls; Automatic safety controls; Chimneys, flues, and vents, where readily visible; Solid fuel heating devices; Heat distributionsystems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, convectors; and the presence of aninstalled heat source in each room. The home inspector shall describe: Energy source; and Heating equipment and distribution type. The home inspectorshall operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the manufacturer orinstaller for routine homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or othercircumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish solid fuel fires; or Observe: The interior of flues;Fireplace insert flue connections; Humidifiers; Electronic air filters; or The uniformity or adequacy of heat supply to the various rooms.

IN NI NP RR

8.0 HEATING EQUIPMENT •

8.1 NORMAL OPERATING CONTROLS •

8.2 AUTOMATIC SAFETY CONTROLS •

8.3DISTRIBUTION SYSTEMS (including fans, pumps, ducts and piping, with supports,insulation, air filters, registers, radiators, fan coil units and convectors)

8.4 PRESENCE OF INSTALLED HEAT SOURCE IN EACH ROOM •

8.5 CHIMNEYS, FLUES AND VENTS (for fireplaces, gas water heaters or heat systems) •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsHeat Type:

Circulating boilerElectric Base

Energy Source:GasElectric

Number of Heat Systems(excluding wood):

ThreeHeat System Brand:

WEIL MCLEANDuctwork:

N/AFilter Type:

N/AFilter Size:

N/ATypes of Fireplaces:

NoneOperable Fireplaces:

NoneNumber of Woodstoves:

None

Comments:

8.0 Heating unit has been shut off and winterized.Testing could not be performed.

8.4 Electric baseboard heater in 2nd floor.(Picture 1)

8.4 Item 1(Picture) Electric baseboard heater in2nd floor.

The heating and cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find allareas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal andinspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware thatthe inspector has your best interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended thatqualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 27 of 31

Page 28: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

9. Insulation and Ventilation

The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas; Kitchen, bathroom, andlaundry venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits, the operation of any readilyaccessible thermostatic control. The home inspector shall describe: Insulation in unfinished spaces; and Absence of insulation in unfinished space atconditioned surfaces. The home inspector shall: Move insulation where readily visible evidence indicates the need to do so; and Move insulation wherechimneys penetrate roofs, where plumbing drain/waste pipes penetrate floors, adjacent to earth filled stoops or porches, and at exterior doors. The homeinspector is not required to report on: Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.

IN NI NP RR

9.0 INSULATION IN ATTIC •

9.1 INSULATION UNDER FLOOR SYSTEM •

9.2 VAPOR RETARDERS (ON GROUND IN CRAWLSPACE OR BASEMENT) •

9.3 VENTILATION OF ATTIC AND FOUNDATION AREAS •

9.4 VENTING SYSTEMS (Kitchens, baths and laundry) • •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsAttic Insulation:

UnknownVentilation:

None foundExhaust Fans:

Fan with lightDryer Power Source:

Gas ConnectionDryer Vent:

Flexible MetalMetal

Floor System Insulation:NONE

Comments:

9.1 The floor system is not insulated. Heat loss can occur more on this home than one that is properly insulated.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 28 of 31

Page 29: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

9.4 Dryer vent is missing exterior vent damper.(East elevation).(Picture 1)

This dryer vent is not being used at time of inspection.(Picture 2)

Bathroom exhaust fan on main floor needs cleaning.(Picture 3)

9.4 Item 1(Picture) Dryer vent is missing exteriorvent damper.(East elevation).

9.4 Item 2(Picture) This dryer vent is not beingused at time of inspection.

9.4 Item 3(Picture) Bathroom exhaust fan on mainfloor needs cleaning.

The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areasof concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and bends or obstructions can occur withoutbeing accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was inspected. Please be aware that the inspector has your bestinterest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used inyour further inspection or repair issues as it relates to the comments in this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 29 of 31

Page 30: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

10. Built-In Kitchen Appliances

The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher, through its normalcycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or range hood; and Permanentlyinstalled microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning oven function, or thermostats for calibration orautomatic operation; Non built-in appliances; or Refrigeration units. The home inspector is not required to operate: Appliances in use; or Any appliance that isshut down or otherwise inoperable.

IN NI NP RR

10.0 DISHWASHER •

10.1 RANGES/OVENS/COOKTOPS • •

10.2 RANGE HOOD •

10.3 TRASH COMPACTOR •

10.4 FOOD WASTE DISPOSER •

10.5 MICROWAVE COOKING EQUIPMENT •

IN= Inspected, NI= Not Inspected, NP= Not Present, RR= Repair or Replace IN NI NP RR

Styles & MaterialsDishwasher Brand:

MAYTAGDisposer Brand:

NONEExhaust/Range hood:

RE-CIRCULATERange/Oven:

MAYTAGBuilt in Microwave:

MAYTAGTrash Compactors:

NONERefrigerator:

GENERAL ELECTRIC

Comments:

10.1 Cooking range must have anti tip device installed as per manufactures instructions.(Picture 1)

10.1 Item 1(Picture) Cooking rangemust have anti tip device installed asper manufactures instructions.

The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort to find all areas ofconcern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report shouldbe considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the commentsin this inspection report.

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 30 of 31

Page 31: Inspection Report · 2019. 11. 7. · 3. Garage Receptacle in garage must be changed to a GFCI type.(Picture 1) 3.8 Windows Inspected, Repair or Replace Windows (3) do not have trim

INVOICE

Focal Point Home Inspection Ltd.6334 W. Grace stChicago Illinois 606341-773-454-6700Inspected By: Joseph Poelsterl

Inspection Date: 2/23/2013Report ID:

Customer Info: Inspection Property:

Happy Chicago Bungalow Owner638 Sheridan Rd #1cHighwood Il 60040

Customer's Real Estate Professional:Gloria ReeColdwell Banker

Inspection Fee:

Service Price Amount Sub-Total

Tax $0.00

Total Price $0.00

Payment Method:Payment Status:Note:

Chicago Bungalow OwnerFocal Point Home Inspection Ltd.

Page 31 of 31