Installation Guidelineof FirePro Aerosol units for Kardex Remstar
KIT-05-Shuttle XP - Sigma XT
Version 1, 19-06-2012
Installation guideline of
FirePro aerosol generators
for Kardex remstar Filing
System
MANUAL
Version 1, 19-06-2012
“Shuttle XP”
KIT-05-Shuttle XP - Sigma XT
FirePro Systems Ltd 6 Koumandarias & Spyrou Araouzou Street
Tonia Court No. 2, 6th Floor, CY-3036 Limassol
P O Box 54080, CY-3720 Limassol, CYPRUS
Tel: +357 25 379 999, Fax: +357 25 354 432
Web: www.firepro.info, email: [email protected]
An ISO 9001:2008 & 14001:2004 registered company
Installation Guideline of Aerosol Generators to Kardex remstar Filing System
“Shuttle XP - Sigma XT”
For the kit installation and system commission please find here below the following guidelines.
Step 1: Identify the Kit components as indicated in schematic drawing on figure 1.
Step 2: Identify the locations of each component for installation as indicated in the schematic drawing on figure 2.
Step 3: Identify the route of both Linear Heat Detector Cables that must be followed for the protection of the various sections of the machine, as indicated in the schematic drawing on figure 3.
Step 4: Identify the wire connections of various accessories like detectors, warning devices, sequential activators, aerosol generators, testing lamps that must be interconnected to the panel terminals, as indicated in the schematic drawing on figure 4 and 5.
Step 5: The installation of the various aerosol generators and Linear Heat Detector Cables in various sections of the machine, are indicated in the schematic drawing on figure 6.
Step by step process, on cable connections to aerosol generators, is indicated on page 9 and 10.
Step 6: For the commissioning of the system please follow the guidelines indicated in the attached logbook.
Step 7: For more information regarding the extinguishing panel, please see the attached panel operation and Maintenance manual.
Kit Components (KIT-05-Shuttle XP - Sigma XT)
No Description/Details Model Quantity
1 FIREPRO KENTEC FIRE EXTINGUISHANT PANEL SIGMA XT
XT FP K11031M2
1
2 BACK UP BATTERY 7Ah 12V 24-107F 2
3 SEQUENTIAL ACTIVATOR GEN3.0 3
4 FIREPRO AEROSOL GENERATOR FP-200S 2
5 FIREPRO AEROSOL GENERATOR FP-100S 1
6 FIREPRO AEROSOL GENERATOR FP-40S 2
7 FIREPRO AEROSOL GENERATOR FP-20SE 1
8 LINEAR HEAT SENSOR CABLE TH105N 35
9 LINEAR HEAT SENSOR CABLE TH88N 35
10 FIRE RESISTANCE CABLE RAMCRO-F3 2 X1.5mm 45
11 FIRE RESISTANCE CABLE RAMCRO-F3 4 X1.5mm 3
12 SELF ADHESIVE ALUMINIUM ACLIP6mm 200
13 ABORT BUTTON RP-BS-11 RP-BS-11 1
14 BELL 24VDC MBM246 1
15 SIRENE FS24 1
16 GAS RELEASE SIGN FL24 1
17 TEST LAMPS 24V (MES 1.2W) 6
18 PLASTIC CABLE GLANDS 20mm G11 12
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 3
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
Shuttle XP - Sigma XT
2 4
6
5
7
1
3
8
9
FP-200S FP-200S FP-100S FP-40S FP-40S
S.A. 1 S.A. 2 S.A. 3
FP-20S
FirePro ®Sequential
Activator
Fault
FirePro ®Sequential
Activator
Fault
FirePro ®Sequential
Activator
Fault
(1) Extinguishing Panel(2) 1st Stage Sounder(3) 2nd Stage Sounder& Strobe(4) Extinguishing Indication(5) Zone 1, Linear Heat Det. TH88(6) Zone 2, Linear Heat Det. TH105(7) Isolation / Abort Button(8) Sequential Activators(9) Aerosol Generators
Figure 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Shuttle XP - Sigma XT
Page 4
Electric motor
POINT X5
Aerosol Generator
FP-200S
POINT X1
Fire Protection Controller
Electronic boards and
power supply
Figure 2POINT X3
Aerosol Generator
2 X FP-40S
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
POINT X6
Aerosol Generator
FP-200S
Electric motor
POINT X2
Aerosol Generator
1 X FP-100S
POINT X4
Aerosol Generator
1 X FP-20S
Electronic boards
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 5
5K
1
POINT X1
Sigma XT panel
E.O.L. resistance
6.8 KΩ
Linear Heat detector TH88
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
2-3cm
POINT X6
2-3cm
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
Shuttle XP - Sigma XT
5K
1
Linear Heat detector TH105
POINT X3POINT X4
POINT X2 POINT X5
Figure 3
Page 6
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Shuttle XP - Sigma XT
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
+ ROVAUX
24V
SIL AL FLT RSTREMOTE
CONTROL
+ - + -DATA POWER
STATUS UNITS
+ - + - + - + - + - + -S1 S2 ZONE1 ZONE2 ZONE3 2ND
SOUNDER
NC C NO1ST
STAGE
NC C NO2ST
STAGE
+ -MODE
SELECT
+ -MAN
RELEASE
+ -HOLD
+ -REL.
PRESS
SWITCH
+ -
EXTING.
+ -LOW.
PRES.
SWITCH
NC C
EXTRACT FAULT
RELAY
LOCAL
FIRE
NC C NOFIRE
RELAY
NC C NO NC C NO+ E -
Sigma XT PCB
10K
10K
1st Stage
Sounders
6K
8
10K
2nd
Stage
Sounders
Periph
era
l
Dete
cto
rs
To
Status
Units
Sto
p A
ir
Con
ditio
nin
g
Shut D
ow
n
Pow
er
470R
6K
8
Rem
ote
Auto
/Manual
Sele
ct S
witch
Rem
ote
Manual
Activation
Sw
itch
470R
6K
8R
em
ote
Hold
Sw
itch
Extr
act F
an
Pow
er
Auxiliary Signaling
Relays
Remote
Control
Inputs
470R
6K
8E
xtinguis
hant R
ele
ase P
ressure
Sw
itch
470R
6K
8E
xtinguis
hant Low
Pre
ssure
Sw
itch
To S
equential A
ctivato
r (A
ero
sol G
enera
tors
)
1st Stage
Sounders
6K
8
24VDC from AUX
Kentec Panel
COM
COM
NC
NC
NO
NO
6K
8
6K
8
Fire
Pro
®
Se
qu
en
tial A
ctiv
ato
r
Fa
ult
Fire
Pro
®
Se
qu
en
tial A
ctiv
ato
r
Fa
ult
Bell
Siren &
Strobe Light
Warning
Strobe LightAbort Button
Extinguishing LineExtinguishing Line
Extinguishing Line
24VDC from Panel(AUX)
24VDC from Panel(AUX)
Test Lamps
Sequential activator 1
Fire
Pro
®
Se
qu
en
tial A
ctiv
ato
r
Fa
ult
Sequential activator 2
Sequential activator 3
Linear Heat Detector (TH 88)
Linear Heat Detector (TH 105)
Figure 4
Page 7
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Shuttle XP - Sigma XT
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
10K
1st Stage
Sounders
Bell -+
6K8
Panel End of Line Resistance
+
-S1
Bell wires terminal
Panel wires
terminal S1
Typical arrangement of 1st stage sounders
10K
2nd
Stage
Sounders
-+
6K8
Panel End of Line Resistance
+
-
2ND
SOUNDER
Siren & Strobe Light
wires terminal
Panel wires
terminal 2ND
SOUNDER
Typical arrangement of 2nd
stage sounders
-+
Warning Strobe
Light wires terminal
Siren &
Strobe Light
Warning
Strobe Light
B-
B+
A-
A+
+ -
OUT
24V
+ -
OUT
EXT
+ -
IN
EXT
+ -
IN
24V
B-
B+
A-
A+
+ -
OUT
24V
+ -
OUT
EXT
+ -
IN
EXT
+ -
IN
24V
B-
B+
A-
A+
+ -
OUT
24V
+ -
OUT
EXT
+ -
IN
EXT
+ -
IN
24V
S.A. 1 S.A. 2 S.A. 3
FP-200S FP-200SFP-100S
FP-40S FP-40S FP-20S
Extinguishing Line
24VDC from
Panel(AUX)
Insert End Of Line Diode jumper link
Figure 5
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 8
Shuttle XP - Sigma XT
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
Two L.H.D. Cables (Linear
Heat Detector)
Example: Aerosol Generator installation.
Example: L.H.D. Linear Heat Detector
Example: Clips
Figure 6
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 9
Step 1
Pass the prepared cable through the
Unit 1 = Cable gland fixing component
Unit 2 = Cable gland & Activator Cable
housing
Step 3
Pull back the cable.
Activator cable housing
PART 1
Activator cable housing
PART 2
Connector Connector
Pull back the cable until
the edge of the cable
shield just shown
Cable gland fixing component
UNIT 1
Cable gland & activator cable housing
UNIT 2
Activator cables
Activator cables
Step 2
Connect the cable wires, positive ( + )
& negative ( - ), with aerosol unit
connector with any of the 2 non
polarized activator cables.
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
Shuttle XP - Sigma XT
D
C
B
A
4 3 2 1
D
C
B
A
4 3 2 1
Page 10
Step 4
Hold the cable avoiding the turning of
the connector within housing while
turning by hand the activator cable
housing (part 1) with activator cable
housing (part 2).
Step 5
By using two spanner keys Connect
Unit 1 (cable gland fixing component)
with Unit 2 (Cable gland & activator
cable).
Activator cable housing
PART 1
Activator cable housing
PART 2
Spanner key # 22
Cable gland fixing
component
UNIT 1
Cable gland & activator
cable housing
UNIT 2
Spanner key # 22
REV. BYDATEDESCRIPTION
1.0 Shuttle XP – Sigma XT 19/06/2012 Michaelides Loucas
Shuttle XP - Sigma XT
PART LIST
Pos
ition
Qua
ntity
Denomination Type /
1 C20TOCSTOP OUTLET COVER PLATE123
1 CABLE HOUSING
4C20HTSHOUSING TUBE1
1 C20BOCSBOTTOM OUTLET COVER PLATE
DWG. Number
2 1
3
4
Top View Iso View (Top)
Front View Side View
Bottom View
Iso View(Bottom)
55.0
Installation Options
Fixing Drills
Condenced aerosol generator FP-20ESDRAWING NUMBER: ID-20ESDATE: 15/04/10
TITLE:INSTALLATION DRAWING
Isometric View of Bracket
C204080CH
205
5 1 BRACKET C20BR
5
102
1
3 2
4
5
Top View Iso View (Top)
Front View Side View
Bottom View
Iso View(Bottom)
76.0
Installation Options
Fixing Drills
DRAWING NUMBER: ID-80SDATE: 15/04/10
TITLE:INSTALLATION DRAWING
Isometric View of Bracket
224.
5
PART LIST
1 1
Pos
ition
Qua
ntity
Denomination
THERMOCONECTOR
Type /
2 C80TOCPSTOP OUTLET COVER PLATE134
1 CABLE HOUSING
5C80HTSHOUSING TUBE1
1 C80BOCPSBOTTOM OUTLET COVER PLATE
C1-2-5THC
DWG. Number
C204080CH
6 17 1
BRACKET PART1 C4080BRS1BRACKET PART2 C4080BRS2
6
7
Ø6.0
96
Condenced aerosol generator FP-20ES
PART LIST
1 1
Pos
ition
Qua
ntity
Denomination
THERMOCONECTOR
Type /
2 C1-2-5IGNIGNITER1
3
4
1 ANGLE BRACKET SUPPORT
5
C1HTHOUSING TUBE1
1 C1HECHOUSING EXIT COVER
C1-2-5THC
DWG. Number
1
2
3
4
5
Top View Iso View (Top)
Front View Side View
Bottom View Iso View(Bottom)
Installation Options
Fixing Drills
21.5
Ø6.0
C1-2-5ABS
DRAWING NUMBER: ID-100SDATE: 15/04/10
TITLE:INSTALLATION DRAWING
26.0
Condenced aerosol generator FP-20ES
1
2
3
4
6
Top ViewIso View (Top)
Front View Side View
Bottom View Iso View(Bottom)
Installation Options
Fixing Drills
21.5
Ø6.0
DRAWING NUMBER: ID-200SDATE: 15/04/10
TITLE:INSTALLATION DRAWING
26.0
PART LIST
1 1
Pos
ition
Qua
ntity
Denomination
THERMOCONECTOR
Type /
2 CABLE HOUSING13
5
1 ANGLE BRACKET SUPPORT
611 C2HECHOUSING EXIT COVER
C1-2-5THC
DWG. Number
C1-2-5ABSC1-2-5CH
4C2HTHOUSING TUBE
1 ROUND BRACKET "A" C1-2-5RBR
7 1 M8BOLT & NUT8 1 M6BOLT & NUT
5
7
8
144
206
92.0
Condenced aerosol generator FP-20ES
Weight Gross 310gr Tolerance +/- 5%
Net
MODEL FP 20SE
Mass of Extinguishing material 20gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω(ohm) Resistance
Maximum 5mA
Self Activation Temp 300℃Classes of Fire A, B, C, F
Testing Electrical Current
20gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets Two Directions Outlet
Dimension 165mm x 32mm ( incl connector housing)
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 20SE
Weight
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω(ohm) Resistance
Maximum 5mA
Self Activation Temp 300
℃
Classes of Fire A, B, C, F
Testing Electrical Current
40gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets Two Direction Outlet
Dimension 140mm x 51mm ( incl connectors housing)
Gross 610gr Tolerance +/- 5%
Net
MODEL FP 40S
Mass of Extinguishing material 40gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
Thermally activated Thermocord at 172
℃
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 40S
Weight Gross 1370gr Tolerance +/- 5%
Net
MODEL FP 100S
Mass of Extinguishing material 100gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
Thermally activated Thermocord at 172
℃
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω (ohm) Resistance
Maximum 5mA
Self Activation Temp 300
℃
Classes of Fire A, B, C, F
Testing Electrical Current
100gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets One Direction Outlet
Dimension 120 mm x 84 mm ( plus connector housing)
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 100S
Weight
FirePro Systems Ltd is the manufacturer of the FirePro products
Activator Type Heating Element with 2.3Ω(ohm) Resistance
Maximum 5mA
Self Activation Temp 300
℃
Classes of Fire A, B, C, F
Testing Electrical Current
200gr
Operation (Discharge) Time 5 - 10 Seconds
Discharge Outlets One Direction Outlet
Dimension 150 mm x 84 mm (plus connector housing)
Gross 1840gr Tolerance +/- 5%
Net
MODEL FP 200S
Mass of Extinguishing material 200gr
Activation Mode/s Electrical 6-24VD/C, min. 0.8A for 3-4 sec
Thermally activated Thermocord at 172
℃
Fire Extinguishing Aerosol systems
Technical Data Sheet
FP 200S
FirePro Systems6 Koumandarias Street, PO Box 54080, CY-3720 Limassol, Cyprus - EU Tel.: +357 25 379999 | Fax: +357 25 354432 | Email: [email protected] www.firepro.com