installation instructions - lennox...occklwise) om backseated position.-4- when finished using port,...
TRANSCRIPT
3DJH �
£
PRODUCT LITERATURE
¤1994 Lennox Industries Inc.
Dallas, Texas
HS23 CONDENSING UNIT
HS23 condensing units are designed for expansion
valve (TXV) and RFC systems. Refer to Lennox engi-
neeringhandbook for expansion valve kitswhichmust
be ordered separately.
SHIPPING AND PACKING LIST
1-- Assembled HS23 condensing unit
1-- Thermometer well (field installed)
1-- Filter/dryer (field installed)
Check unit for shipping damage. Consult last carrier
immediately if damage is found.
GENERAL INFORMATION
These instructions are intended as a general guide
and do not supersede national or local codes in any
way. Authorities having jurisdiction should be con-
sulted before installation.
IMPORTANT
The Clean Air Act of 1990 bans the intentionalventing of refrigerant (CFC�s and HCFC�s) as ofJuly 1, 1992. Approved methods of recovery, re-cycling or reclaiming must be followed. Finesand/or incarcerationmay be levied for non--com-pliance.
INSTALLATION
INSTRUCTIONS
+6�� 6(5,(6 81,76
&21'(16,1* 81,76
� WKURXJK � WRQ�������0����
6XSHUVHGHV ����
TABLE OF CONTENTS
HS23 CONDENSING UNIT 1. . . . . . . . . . . . . . . . . . . . . . . . .
SHIPPING AND PACKING LIST 1. . . . . . . . . . . . . . . . . . . . . .
GENERAL INFORMATION 1. . . . . . . . . . . . . . . . . . . . . . . . . .
HS23 UNIT DIMENSIONS 2. . . . . . . . . . . . . . . . . . . . . . . . . .
HS23 CHECK POINTS 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SETTING THE UNIT 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRICAL 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLUMBING 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
REFRIGERANT METERING DEVICE 4. . . . . . . . . . . . . . . . . .
MANIFOLD GAUGE SET 5. . . . . . . . . . . . . . . . . . . . . . . . . . .
LIQUID & SUCTION LINE SERVICE VALVES 5. . . . . . . . . .
LEAK TESTING 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EVACUATION 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
START--UP 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CHARGING CONSIDERATIONS 8. . . . . . . . . . . . . . . . . . . . .
CHARGING FOR RFC SYSTEMS 8. . . . . . . . . . . . . . . . . . . .
CHARGING FOR TXV SYSTEMS 9. . . . . . . . . . . . . . . . . . . .
SYSTEM OPERATION 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MAINTENANCE 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RETAIN THESE INSTRUCTIONS
FOR FUTURE REFERENCE
WARNING
Product contains fiberglass wool.
Disturbing the insulation in this product duringinstallation, maintenance, or repair will exposeyou to fiberglass wool. Breathing this may causelung cancer. (Fiberglass wool is known to theState of California to cause cancer.)
Fiberglass woolmay also cause respiratory, skin,and eye irritation.
To reduce exposure to this substance or for fur-ther information, consult material safety datasheets available from address shown below, orcontact your supervisor.
Lennox Industries Inc.P.O. Box 799900Dallas, TX 75379--9900
/LWKR 8�6�$�
3DJH �
HS23 UNIT DIMENSIONS--INCHES (MM)
Model No. A B C
HS23-141, HS23-211,
HS23-26126-3/8 26-3/8 16-7/8
HS23-311, HS23-411-413 26-3/8 30-3/8 16-7/8
HS23-461-463,
HS23-511-513,
HS23-651-653
31-5/16 34-3/8 21-3/16
&+(&. 32,17667$57� �83 $1' 3(5)250$1&( &+(&. /,67
-RE 1DPH
-RE /RFDWLRQ
,QVWDOOHU
8QLW 0RGHO 1R�
1DPHSODWH 9ROWDJH
0LQLPXP &LUFXLW $PSDFLW\
0D[LPXP 2YHUFXUUHQW 3URWHFWLRQ 6L]H
5HIULJHUDQW /LQHV�
6HUYLFH 9DOYHV %DFNVHDWHG"
&RQGHQVHU )DQ &KHFNHG"
-RE 1R�
&LW\
&LW\
6HULDO 1R�
'DWH
6WDWH
6WDWH
6HUYLFHPDQ
$PSV�
6XSSO\ &RQGHQVHU )DQ
&RPSUHVVRU
,QGRRU )LOWHU &OHDQ" ,QGRRU %ORZHU &)0(OHFWULFDO &RQQHFWLRQV 7LJKW"
6XSSO\ 9ROWDJH �8QLW 2II� 6�3� 'URS 2YHU (YDSRUDWRU �'U\�
&RQGHQVHU (QWHULQJ $LU 7HPSHUDWXUH
'LVFKDUJH 3UHVVXUH 6XFWLRQ 3UHVVXUH
&22/,1* 6(&7,21
7+(50267$7
5HIULJHUDQW &KDUJH &KHFNHG"
&DOLEUDWHG" 3URSHUO\ 6HW" /HYHO"
3URSHUO\ ,QVXODWHG"
6HUYLFH 9DOYH &DSV 7LJKW"
9ROWDJH :LWK &RPSUHVVRU 2SHUDWLQJ
/HDN &KHFNHG"
B
2-3/8
2-1/2
4-3/4
1
3-1/8
TOP VIEW
SIDE VIEWFRONT VIEW
CC
INLET AIR
INLET
AIR
INLET
AIR
INLET AIR
FAN GUARD
AA
SUCTION LINE
CONNECTION
AND VALVE
LIQUID LINE
CONNECTION
AND VALVE
DISCHARGE AIR
COMPRESSOR
ELECTRICAL
CONNECTIONS
BOTTOM OF
CONTROL BOX
CONTROL
BOX
4-3/44-3/44-3/44-3/4
3DJH �
SETTING THE UNIT
Refer to unit dimensions on page 2 for sizing mount-
ing slab, platforms or supports. Refer to figure 1 for
installation clearances.
INSTALLATION CLEARANCES
FIGURE 1
36
(914 mm)
*36
(914 mm)
36
(914 mm)
NOTE�48 inch clearance required on top of unit.
*NOTE�One side must be 36 inches. Two of the remainingthree sides may be 12 inches.
*36
(914 mm)
Slab Mounting
When installing unit at grade level, install on a level
slab high enough above grade to allow adequate
drainage of water. Top of slab should be located so
run--off water from higher ground will not collect
around unit.
Roof Mounting
Install unit at a minimum of 4 inches above the sur-
face of the roof. Care must be taken to ensure weight
of unit is properly distributed over roof joists and raf-
ters. Either redwood or steel supports are recom-
mended.
ELECTRICAL
Wiring must conform to current standards of the Na-
tional Electric Code (NEC), Canadian Electrical Code
(CEC) and local codes. Refer to the furnace or blower
coil installation instructions for additional wiring ap-
plication diagrams and refer to unit rating plate for
minimum circuit ampacity and maximum overcur-
rent protection size.
WARNING
Unit must be grounded in accordance with na-tional and local codes. Electric Shock Hazard.Can cause injury or death.
Line Voltage
To facilitate conduit, a hole is provided in bottom of
the control box. Connect conduit to hole in control
box with proper conduit fitting.
127(� �8QLWV DUH DSSURYHG IRU XVH ZLWK FRSSHU FRQGXF�
WRUV RQO\�
24V, Class II Circuit
24V, Class II Circuit connections are made up in the
low voltage junction box. Refer to figure 2 for field
wiring diagram.
127(� �$ FRPSOHWH XQLW ZLULQJ GLDJUDP LV ORFDWHG LQVLGH
WKH XQLW FRQWURO ER[ FRYHU�
TO
COOLING
SPEED
TO
HEATING
SPEED
Y1 RCWG RH
CONDENSING UNITTYPICAL INDOOR UNIT
ROOM THERMOSTAT
POWER
GROUND
PER NATIONAL
AND LOCAL
CODES
24v
TRANSFORMER
24V
CLASS II
JUNCTION
BOX
TO
HEATING
CONTROLS
TO 24V CLASS II POWER SOURCE
-- 20 VA MINIMUM
K3 INDOOR BLOWER RELAY
NOTE--IF INDOOR UNIT IS NOT EQUIPPED WITH
BLOWER RELAY, IT MUST BE FIELD PROVIDED
AND INSTALLED (P--8--3251 OR EQUIVALENT)
NOTE--SEE UNIT WIRING DIAGRAM
FOR POWER SUPPLY CONNECTIONS.24V CLASS II INSTALLED AT FACTORY
24V CLASS II FIELD INSTALLED
FIGURE 2
Y1
C
C
T1
R
W1
G
C
W2
HS23 TYPICAL FIELD WIRING DIAGRAM
3DJH �
PLUMBING
Field refrigerant piping consists of liquid and suction
lines from the condensingunit (sweat connections) to
the indoor evaporator coil (flare or sweat connec-
tions). Use Lennox L10 series line sets as shown in
table 1 or use field--fabricated refrigerant lines. Refer
to unit information manual piping section for proper
size, type and application of field--fabricated lines.
Sweat Connection Procedure
1-- Ends of refrigerant lines must be cut square, free
from nicks or dents, deburred. Pipe must remain
round, do not pinch end of line.
2-- The thermometer well (packaged separately)
should be installed in the liquid line close to the
HS23unit as shown in figure3. Connect thermome-
terwellmale end to female endof liquid valve. Take
care to install thermometer well so that the ther-
mometer can be inserted and read easily. Wrap a
wet clotharound the liquid linevalvebodyand cop-
per tube stub to protect from heat damage during
brazing.Wrapanotherwet clothunderneath the liq-
uid valve to protect the base paint.
FIGURE 3
THERMOMETER WELL
(Field Installed)
PROTECT LIQUID LINE
VALVE WITH WET RAG
DURING BRAZING
THERMOMETER WELL
INSTALL THERMOMETER WELL SO THAT THERMOMETER
CAN BE INSERTED AND READ EASILY
LIQUID
LINE
VALVE
3-- Quench the joints with a wet cloth to prevent pos-
sible heat damage to the valve core and opening
port.
4-- The filter dryer is shipped with the unit and
shouldbe field installed as closeaspossible to the
expansion device.
REFRIGERANT METERING DEVICE
HS23 units are applicable to either RFC (II or IV) or an
expansion valve system. See indoor coil installation
instructions and the Lennox engineering handbook
for approved RFC and TXV match--ups and applica-
tion information.
RFC Systems
HS23 units are shipped with either an RFCII or RFCIV
metering device. Installation of the RFCII orifice is
shown in figure 4. Table 1 lists HS23 unit and corre-
sponding RFCII number. RFCIV bullet is installed as
shown in figure 5. Take care not to twist cap tubes
when loosening seal nut fromorifice body. In cases of
non--traditional applications, RFCIV bullet shipped
may not be appropriate. Refer to the indoor coil
installation instructions and the engineering hand-
book for specific orifice information.
72,1'225&2,/
),*85( �
5)&,, ,167$//$7,21
/,48,'/,1(
5)&,, 25,),&(�127( )/2: ',5(&7,21�
)/$5(),77,1*6
)/$5(),77,1*6
TABLE 1REFRIGERANT LINE KITS
UNITLIQUID
LINE
SUCTION
LINE
L10
LINE SETS
HS23--261
HS23--311
HS23--410
HS23--460
3/8 in
(10 mm)
3/4 in.
(19 mm)
L10--41
20 ft. -- 50 ft.
(6 m -- 15 m)
HS23--211 5/16 in*
(8 mm)
3/8 in
(10 mm)
L10--65
30 ft. -- 50 ft.
(9 m -- 15 m)
L10--21
20 ft. -- 50 ft.
(6 m -- 15 m)
5/8 in
(16 mm)
7/8 in.
(22 mm)
RFCII
ORIFICE
97H3301
27H9301
76A9001
P--8--11320
P--8--11323
HS23--141 ------1/4�
(6mm)
1/2�
(12mm)
FIELD
FABRICATED
HS23--510 47F6001
3/8 in
(10 mm)
1--1/8 in.
(29 mm)
FIELD
FABRICATEDHS23--650 47F6201
*Use reducer supplied in bag assembly.
RFCIV INSTALLATION
DISTRIBUTOR
�BULLET�
ORIFICE
ORIFICE
BODY
SEAL
NUT
FIGURE 5
SWEAT
CONNECTION
Expansion Valve Systems
Expansion valves equipped with either �Chatliff� or
flare type fittings are available from Lennox. Refer to
the indoor coil installation instructions or the engi-
neering handbook for applicable expansion valves
for use with specific match--ups.
3DJH �
If an expansion valve application is desired with in-
door coil product shipped with an RFCIV orifice, the
RFCIV restrictormust be removed before installing the
expansion valve.
IMPORTANT
Failure to remove RFCIV when installing an ex-pansion valve to the indoor coil will result in im-proper operation and damage to the system.
0$1,)2/' *$8*( 6(7
Amanifold gauge set equippedwith�low loss�hoses
should be used when checking unit charge. A man-
ifold gauge set with anything other than �low loss�
hose should not be used.
/,48,' 68&7,21 /,1( 6(59,&( 9$/9(6
The liquid line and suction line service valves and
gauge ports are accessible by removing the compres-
sor access cover. Full service liquid and suction line
valves are used. See figures 6and 7. The service ports
are used for leak testing, evacuating, charging and
checking charge.
Liquid Line Service Valve ( Figure 6)
The valve is equipped with a service port. There is no
schrader valve installed in the liquid line service port. A
service port cap is supplied to seal off the port.
The liquid line service valve is a front and back seating
valve. When the valve is backseated the service port is
not pressurized. The service port cap can be removed
and gauge connections can be made.
To Access Service Port:
1-- Remove the stem cap. Use a service wrench to
make sure the service valve is backseated (turn
counterclockwise).
CAUTION
The service port cap is used to seal the liquidline service valve. A schrader valve is notprovided. Access to service port requiresbackseating the service valve to isolate theservice port from the system. Failure to do sowill cause refrigerant leakage.
KNIFE EDGE SEAL
STEM CAP
VALVEBACKSEATED
INLET(FROM OUTDOOR COIL)
OUTLET(TO INDOOR COIL)
SERVICE PORTCLOSED TO LINE SET
AND UNIT(NO PRESSURE)
SERVICE PORT CAP
TO OUTDOOR UNIT(COIL)
TO LINE SET
STEM CAP
KNIFE EDGESEAL
VALVE FRONTSEATED
TO LINE SET
SERVICE PORT OPENTO LINE SETAND CLOSEDTO UNIT
TO OUTDOORUNIT (COIL)
LIQUID LINE SERVICE VALVE
IMPORTANT
A schrader valve is not provided on the liquid line service port.Valve must be backseated to turn off pressure to service port.
VALVE STEMUSE SERVICEWRENCH
VALVE STEMUSE SERVICE WRENCH
FIGURE 6
2-- Remove service port cap and connect high pres-
sure gauge to service port.
3-- Using service wrench, open valve stem (one turn
clockwise) from backseated position.
4-- When finished using port, backseat stem with ser-
vice wrench. Tighten firmly.
5-- Replace service port and stem cap. Tighten finger
tight, then tighten an additional 1/6 turn.
To Close Off Service Port:
1-- Using service wrench, backseat valve by turning
stem counterclockwise. Tighten firmly.
3DJH �
To Open Liquid Line Service Valve:
1-- Remove the stem cap with an adjustable wrench.
2-- Using service wrench, backseat valve by turning
stem counterclockwise until backseated. Tighten
firmly.
3-- Replace stem cap, finger tighten then tighten an
additional 1/6 turn.
To Close Liquid Line Service Valve:
1-- Remove the stem cap with an adjustable wrench.
2-- Turn the stem in clockwisewith a servicewrench to
front seat the valve. Tighten firmly.
3-- Replace stem cap, finger tighten then tighten an
additional 1/6 turn.
Suction Line Service Valve ( Figure 7)
The valve is equipped with a service port. A schrader
valve is factory installed. A service port cap is supplied
to protect the schrader valve from contamination and
assure a leak free seal.
SUCTION LINE SERVICE VALVE (VALVE OPEN)
FIGURE 7
SCHRADER VALVE
SERVICE PORT
SERVICE PORTCAP
STEM CAP
SNAP RINGINSERT HEXWRENCH HERE
SUCTION LINE SERVICE VALVE (VALVE CLOSED)
INLET(FROM INDOOR COIL)
OUTLET (TOCOMPRESSOR)
KNIFE EDGESEAL
SCHRADER VALVE OPENTO LINE SET WHENVALVE IS CLOSED(FRONT SEATED)
SERVICE PORT
SERVICE PORTCAP
(VALVE FRONTSEATED)
SNAP RING
STEMCAP
OUTLET(TO COMPRESSOR)
KNIFE EDGE SEAL
INLET(FROM INDOOR COIL)
INSERT HEXWRENCH HERE
To Access Schrader Port:
1-- Remove service port cap with an adjustablewrench.
2-- Connect gauge to the service port.
3-- When testing is completed, replace service portcap. Tighten finger tight, then anadditional 1/6 turn.
To Open Suction Line Service Valve:
1-- Remove stem cap with an adjustable wrench.
2-- Using service wrench and 5/16� hex head exten-sion back the stem out counterclockwise until thevalve stem just touches the retaining ring.
Do not attempt to backseat this valve. Attempts tobackseat this valve will cause snap ring to explodefrom valve body under pressure of refrigerant.Personal injury and unit damage will result.
'$1*(5
3-- Replace stem cap tighten firmly. Tighten fingertight, then tighten an additional 1/6 turn.
To Close Suction Line Service Valve:
1-- Remove stem cap with an adjustable wrench.
2-- Using service wrench and 5/16� hex head exten-sion, turn stem clockwise to seat the valve. Tight-en firmly.
3-- Replace stem cap. Tighten finger tight, then tightenan additional 1/6 turn.
/($. 7(67,1*
After the line set has been connected to the indoor
and outdoor units, the line set connections and in-
door unit must be checked for leaks.
WARNING
Neveruseoxygen topressurize refrigerationor airconditioning system.Oxygenwill explodeon con-tact with oil and could cause personal injury.When using high pressure gas such as nitrogen orCO2 for this purpose, be sure to use a regulatorthat can control the pressure down to 1 or 2 psig.
Using an Electronic Leak Detector or Halide
1-- Connect a cylinder of nitrogen with a pressure reg-
ulating valve to the center port of the manifold
gauge set.
2-- Connect the high pressure hose of the manifold
gauge set to the service port of the suction valve.
(Normally, the high pressure hose is connected to
the liquid line port, however, connecting it to the
suction port better protects the manifold gauge
set from high pressure damage.)
3-- With bothmanifold valves closed, open the valve
on the R22 bottle (vapor only).
3DJH �
4-- Open the high pressure side of themanifold to al-
low R22 into the line set and indoor unit. Weigh in
a trace amount of R22. (A trace amount is a maxi-
mum of 2 ounces or 3 pounds pressure.) Close
the valve on the R22 bottle and the valve on the
high pressure side of themanifold gauge set. Dis-
connect R22 bottle.
5-- Adjust nitrogen pressure to 150 psig. Open the
valve on the high side of the manifold gauge set
which will pressurize line set and indoor unit.
6-- After a short period of time, open a refrigerant
port to make sure the refrigerant added is ade-
quate to be detected. (Amounts of refrigerant will
vary with line lengths.) Check all joints for leaks.
Purge nitrogen and R22 mixture. Correct any
leaks and recheck.
(9$&8$7,1*
Evacuating the system of non--condensables is criti-
cal for proper operation of the unit. Non--condens-
ables are defined as any gas that will not condense
under temperatures and pressures present during
operation of an air conditioning system. Non--con-
densables such as water vapor, combine with refrig-
erant to produce substances that corrode copper pip-
ing and compressor parts.
1-- Connect manifold gauge set to the service valve
ports as follows: low pressure gauge to suction
line service valve; high pressure gauge to liquid
line service valve.
2-- Connect the vacuum pump (with vacuum gauge)
to the center port of the manifold gauge set.
3-- Open both manifold valves and start vacuum
pump.
4-- Evacuate the line set and indoor unit to an abso-
lute pressure of 23mm of mercury or approxi-
mately 1 inch of mercury. During the early stages
of evacuation, it is desirable to close themanifold
gauge valve at least once to determine if there is a
rapid rise in absolute pressure. A rapid rise in
pressure indicates a relatively large leak. If this oc-
curs, the leak testingproceduremust be repeated.
NOTE -- The term absolute pressuremeans the to-
tal actual pressure within a given volume or sys-
tem, above the absolute zero of pressure. Abso-
lute pressure in a vacuum is equal to atmospheric
pressure minus vacuum pressure.
5-- When the absolute pressure reaches 23mm of
mercury, close the manifold gauge valves, turn
off the vacuum pump and disconnect the man-
ifold gauge center port hose from vacuumpump.
Attach themanifold center port hose to anitrogen
cylinder with pressure regulator set to 150 psig
and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and in-
door unit. Close the manifold gauge valves.
&$87,21
Danger of Equipment Damage.Avoid deep vacuum operation. Do not use com-pressors to evacuate a system.Extremely low vacuums can cause internal arc-ing and compressor failure.Damage caused by deep vacuum operation willvoid warranty.
6-- Shut off the nitrogen cylinder and remove the
manifold gauge hose from the cylinder. Open the
manifold gauge valves to release the nitrogen
from the line set and indoor unit.
7-- Reconnect the manifold gauge to the vacuum
pump, turn thepumponandcontinue toevacuate
the line set and indoor unit until theabsolutepres-
sure does not rise above5mmofmercurywithin a
20 minute period after shutting off the vacuum
pump and closing the manifold gauge valves.
8-- Depending on the equipment used to determine
the vacuum level, the following units are equiva-
lent to absolute pressure of 5mm of mercury:
5000 microns; 754 millimeters of mercury vacu-
um pressure; or 29.7 inches of mercury vacuum
pressure.
9-- When the absolute pressure requirement above
has been met, disconnect the manifold hose from
the vacuum pump and connect it to an upright
bottle of R22 refrigerant. Open themanifold gauge
valves to break the vacuum in the line set and in-
door unit. Close manifold gauge valves and shut
off R22 bottle and remove manifold gauge set.
67$57��83
IMPORTANT
Crankcase heater should be energized 24 hoursbefore unit start--up to prevent compressor dam-age as a result of slugging.
1-- Rotate fan to check for frozenbearings or binding.
2-- Inspect all factory and field--installed wiring for
loose connections.
3-- After evacuation is complete, open liquid line and
suction line service valves to release refrigerant
charge (contained in condensing unit) into the
system.
3DJH �
4-- Replace stem caps and secure finger tight, then
tighten an additional (1/6) one--sixth of a turn.
127(� �:KHQ WLJKWHQLQJ� WKH WRUTXH ZLOO LQFUHDVH�
WKHQ GURS RII DV WKH IUDQJLEOH SOXJ VKHDUV�
5-- Check voltage supply at the disconnect switch.
The voltage must be within the range listed on
unit nameplate. If not, do not start the equipment
until the power company has been consulted and
the voltage condition corrected.
6-- Set the thermostat for cooling demand, turn on
power to evaporator blower and close condens-
ing unit disconnect switch to start unit.
7-- Recheck voltage with unit running. Power must
be within range shown on nameplate. Check am-
perage draw of unit. Refer to unit nameplate for
correct running amps.
&+$5*,1* &216,'(5$7,216
Units are factory charged with the amount of R22 re-
frigerant indicated on the unit rating plate. This charge
is based on a matching indoor coil and outdoor coil
with 20 ft. (6096 mm) line set. For varying lengths of
line set, refer to table 2 for refrigerant charge adjust-
ment. A blank space is provided on the rating plate to
list the actual field charge.
Liquid LineSet Diameter
Ozs. per 5 ft. (ml per mm) adjust
from 20 ft. (6096 mm) line set*
1/4 in.(6mm)
1 ounce per 5 ft.(30ml per 1524 mm)
3/8 in.(10mm)
5/16 in.(8mm)
2 ounce per 5 ft.(60ml per 1524 mm)
3 ounce per 5 ft.(90ml per 1524 mm)
*If line length is greater than 20 feet (6096 mm), add thisamount. If line length is less than 20 feet (6096 mm), subtractthis amount.
TABLE 2
If the system is void of refrigerant, the recommended
andmost accuratemethodof charging is toweigh the
refrigerant into the unit according to the total amount
shown on the unit nameplate. This may be done after
any leaks havebeen repaired. Ifweighing facilities are
not available or if unit is just lowon charge, use oneof
the procedures outlined.
Charging a condensing unit is recommended during
warm weather. However, applications arise in which
charging must occur in the colder months. The way
the unit is charged depends on the unit�s refrigerant
metering device and the outdoor ambient tempera-
ture.
For RFC systems,weighing in the charge and Subcool-
ing are two acceptablemeans of charging under certain
conditions. For installations of anRFC systemwhere the
outdoor ambient is less than 60EF, weighing in the
charge is the best method. However, in installations
where the outdoor ambient is 60EF or above, subcool-
ing is the best method.
The �weighing in the charge� and the Approach
methods are the two recommended procedures for
charging the HS23 using an expansion valve system
for refrigerant metering. The difference between the
two involves the outdoor ambient temperature. For
expansion valve systems where the outdoor ambient
temperature is 60EF or above, the Approach method
must be used. For expansion valve systems where
the outdoor ambient temperature is below 60EF,
weighing in the charge will suffice.
Before charging the unit, follow the procedure below
to determine: the liquid line temperature and the out-
door ambient temperature.
1-- Connectmanifoldgaugeset to servicevalves: low
pressure gauge to suction valve service port; high
pressure gauge to liquid valve service port. Con-
nect the centermanifold hose to an upright bottle
of R22. Close manifold gauge set valves.
2-- Set the room thermostat to call for heat. This will
create the necessary load for properly charging
the system in the cooling cycle.
3-- Fill the thermometer well with mineral oil.
4-- Record the outdoor ambient temperature. For
greater accuracy, use the same thermometer to
measure liquid temperature.
5-- When thermostat demand has been satisfied,
switch to cooling mode with a set point of 68EF.
When pressures have stabilized, place the ther-
mometer in thermometer well and record the liq-
uid line temperature.
6-- The outdoor temperature will determine which
charging method to use. Proceed with the ap-
propriate charging procedure below.
&+$5*,1* )25 5)& 6<67(06
Weighing in the Charge Method
RFC Systems, < 60EF Outdoor Temp
1-- Recover the refrigerant from the unit.
2-- Conduct a leak check, then evacuateas previously
outlined.
3-- Weigh in the factory charge as shown on the out-
door unit�s rating plate.
3DJH �
The Subcooling Method
RFC Systems, > 60EF Outdoor Temp
1-- With the manifold gauge hose still on the liquid
service port and the unit operating stably, record
the liquid line temperature.
2-- At the same time, record the liquid line pressure
reading.
3-- Using a temperature/pressure chart for R22, de-
termine the saturation temperature for the liquid
line pressure reading.
4-- Subtract the liquid line temperature from the sat-
uration temperature (according to the chart) to
determine subcooling. (Liquid line temperature --
Saturation temperature = Subcooling)
5-- Compare the subcooling valuewith those in table
3. If subcooling is greater than shown, some re-
frigerant must be recovered. If subcooling is less
than shown, some refrigerant must be added.
--650
OUTDOOR
TEMP. (EF)
LIQUID SUBCOOLING (+ 1EF)
60
65
70
75
80
85
90
95
100
105
110
115
--211 --261 --311 --411 --461
9
8
7
7
6
6
5
4
4
3
3
2
14
14
13
13
12
12
11
11
10
10
9
8
17
16
15
14
13
12
11
10
8
7
6
4
15
15
14
14
13
13
12
11
11
10
10
9
17
16
16
15
15
14
14
13
13
12
11
10
TABLE 3SUBCOOLING FOR RFC SYSTEMS
--141 --510
11
11
10
10
9
9
8
8
7
6
6
5
15
14
14
14
13
13
11
10
8
6
4
3
20
19
19
18
18
17
17
16
15
15
14
13
--463
18
17
17
17
15
15
14
14
13
12
10
9
--413
15
14
13
12
11
10
9
8
6
5
4
2
&+$5*,1* )25 7;9 6<67(06
Weighing in the Charge Method
TXV Systems, < 60EF Outdoor Temp
1-- Recover the refrigerant from the unit.
2-- Conduct a leak check, thenevacuate as previously
outlined.
3-- Weigh in the factory charge as shown on the out-
door unit�s rating plate.
The Approach Method
TXV Systems, > 60EF Outdoor Temp
Having taken the outdoor ambient and liquid line
temperature readings, subtract the outdoor ambient
temperature from the liquid line temperature to de-
termine the Approach temperature. (Liquid line EF --
Outdoor Ambient EF = Approach temperature) The
resulting difference (Approach temperature) should
agree with the values given in table 4. If not, add re-
frigerant to lower the approach temperature or recov-
er refrigerant from the system to increase the ap-
proach temperature.
TABLE 4APPROACH METHOD
HS23--211
HS23--261
HS23--311
HS23--413
HS23--461
5 + 1
5 + 1
8 + 1
10 + 1
9 + 1
HS23--141 2 + 1
HS23--510
HS23--650
5 + 1
10 + 1
Note--For best results, the same thermometer should be used tocheck both outdoor ambient and liquid temperatures.
MODEL NO.APPROACH TEMPERATURE
LIQUID LINE E F
-- OUTDOOR AMBIENT E F
HS23--411 9 + 1
HS23--463 8 + 1
6<67(0 23(5$7,21
Condensing unit and indoor blower cycle on demand
from room thermostat. When thermostat blower
switch is switched to ON position, indoor blower op-
erates continuously.
Crankcase Heater
Four and five ton units are equipped with internal
self--regulating crankcase heaters.
Compressor Start Kit
Three and one half, four and five ton single phase
units have internal start components and do not re-
quire field installation of a compressor start kit.
Timed Off Control
(International and Government Units ONLY)
Five ton units are factory equipped with a timed off
control which provides low voltage protection and
prevents compressor short cycling.
High and Low Pressure Switches
(International and Government Units ONLY)
The HS23 is factory--equipped with a manual reset
high pressure switch (see figure 8 for location) and an
auto--reset low pressure switch. Pressure switches
are mounted on valve cores in the line to allow for
easy replacement.
HS23 SERIES HIGH PRESSURE LIMIT RESET
FIGURE 8
RESET BUTTON
3DJH ��
0$,17(1$1&(
:$51,1*
(OHFWULF VKRFN KD]DUG� &DQ FDXVH LQ�MXU\ RU GHDWK� %HIRUH DWWHPSWLQJ WRSHUIRUP DQ\ VHUYLFH RU PDLQWHQDQFH�WXUQ WKH HOHFWULFDO SRZHU WR XQLW 2))DW GLVFRQQHFW VZLWFK�HV�� 8QLW PD\KDYH PXOWLSOH SRZHU VXSSOLHV�
At the beginning of each cooling season, the system
should be checked as follows:
1-- Clean and inspect condenser coil. Coil may be
flushed with a water hose.
2-- Visually inspect connecting lines and coils for evi-
dence of oil leaks.
3-- Check wiring for loose connections.
4-- Check for correct voltage at unit (unit operating).
5-- Check condenser fan motor amp--draw.
Unit nameplate _________ Actual ____________ .
127(� �,I RZQHU FRPSODLQV RI LQVXIILFLHQW FRROLQJ� WKH
XQLW VKRXOG EH JDXJHG DQG UHIULJHUDQW FKDUJH
FKHFNHG� 5HIHU WR VHFWLRQ RQ UHIULJHUDQW FKDUJLQJ LQ
WKLV LQVWUXFWLRQ�
Evaporator Coil
1-- Clean coil, if necessary.
2-- Check connecting lines and coils for evidence of
oil leaks.
3-- Check condensate line and clean, if necessary.
Indoor Unit
1-- Clean or change filters.
2-- Adjust blower speed for cooling. The pressure drop
over the coil should be measured to determine the
correct blower CFM. Refer to the unit information
servicemanual for pressure drop tables and proce-
dure.
3-- Belt Drive Blowers � Check belt for wear and
proper tension.
4-- Check all wiring for loose connections
5-- Check for correct voltage at unit (blower operat-
ing).
6-- Check amp--draw on blower motor
Unit nameplate_________ Actual ____________.