installation operation maintenance '1 … • operation • maintenance 1; ... is a...

16
. OC\ I.L. 41-334.1A INSTALLATION OPERATION MAINTENANCE 1; . INSTRUCTIONS * - - --------- - - ------ - --- - - --- - - TYPE CA-4 PERCENTAGE DIFFERENTIAL RELAY CAUTION Before putting protective relays into service, remove all blocking which may have been inserted for the purpose of securing the pts dur- ing shipment, make se that all moving parts oper- ate freely, inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings and electrical connections. APPLICATION The type CA-4 percentage differential relay is designed for the differential protection of three- winding transformers, and has three restraining coils - one for each winding of the transformer. is a current-operated induction disc relay designed so that the operating coil current required to close the contacts varies in proportion to the current through the restraining windings. This feature pre- vents tripping on through faults, because of unbal- anced current transformer characteristics or loading, and allows the relay to be set for sensitive protec- tion. The relay has three percentage taps of 15, 25 and 40%. The choice of a particular tap is based on the performance of the main current transformers under heavy through faults and the severity of the magnetizing crent inrush when the protected trans- former is energized. When this magnetizing inrush current is large enough in magnitude and long enough in duration to cause the Type CA-4 relay to trip when the trans- former is energized, it is necessary to provide aux- iliary time-delay feates to restrain the action of the Type CA-4 until the magnetizing current has diminished below the pick-up value of the relay. The time-delay relay used for this purpose is the Type TSI Magnetizing Inrush Tripping Suppressor Relay described in I. L. 41-346.1. External current balancing auto transformers are required where the main current transformers do not provide equal secondary currents with the correct phase relation for the Type CA-4 restraining wind- SUPERSEDES I.L. 41-334.1 *Denotes change from superseded issue. ings. Figures 8 and 9 show the auxiliary auto- transformers and Type CA-4 relay external connec- tions for typical installations. The power transformer connections as shown in Figs. 8 and 9 have been made on the assumption that the delta winding is the low voltage side of the transformer, and in conformance with the ASA Stand- ard that the voltages on the HV side lead the volt- ages on the LV side by 30 " · In following the relay connections it will be simpler to illustrate the prin- ciples involved by using a two-winding transformer application. The method illustrated may then be applied to any transformer bank, whether in con- formance with the standard or not. When applied to a three winding bank, each delta winding is checked separately against the star winding. F'ig. 6 shows a two winding transformer protected by three differential relays. In order to establish the proper connections to the relays, first assume a set of reference currents, A, B and C flowing into the wye side of the traformer. The currents flowing out of the delta side of the transformer will by A-C, B-A, and C-B, as shown in F'ig. 6, by virtue of the way this particular bank is connected. On the delta side of the power transformer the crent transformers will be connected in star. The con- nections to the relays must be such as to have the same currents entering and leaving the relay through the restraining windings, for the condition illustrated of primary current flowing through the bank. Con- sidering the top relay, for example, it is seen that A-C current delivered to the right hand restraining coil from the a-phase cuent transformer on the delta side of the bank is passed right on through the other restraining coil of the relay to satisfy the re- quirements of the A- and c- phase current trans- formers on the w ye side of the bank. This keeps the current out of the operating coil, which is proper for the through load condition illustrated by the primary current direction arrows. An improper con- nection in the diagram will show up in this analysis EFFECTIVE SEPTEMBER 1957 www . ElectricalPartManuals . com

Upload: halien

Post on 18-Mar-2018

234 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

�.1-l Ci /Y OC\ I.L. 41-334.1A

INSTALLATION • OPERATION • MAINTENANCE

1;\g/ ... '1 INSTRUCTIONS � * � /----------------------------------------------------------------------------------------------------------------------------------------------------

r--

TYPE CA-4 PERCENTAGE DIFFERENTIAL RELAY

CAUTION Before putting protective relays into

service, remove all blocking which may have been

inserted for the purpose of securing the parts dur­

ing shipment, make sure that all moving parts oper­

ate freely, inspect the contacts to see that they are

clean and close properly, and operate the relay to

check the settings and electrical connections.

APPLICATION

The type CA-4 percentage differential relay is

designed for the differential protection of three­

winding transformers, and has three restraining

coils - one for each winding of the transformer. It is a current-operated induction disc relay designed

so that the operating coil current required to close

the contacts varies in proportion to the current

through the restraining windings. This feature pre­

vents tripping on through faults, because of unbal­

anced current transformer characteristics or loading,

and allows the relay to be set for sensitive protec­

tion. The relay has three percentage taps of 15, 25

and 40%. The choice of a particular tap is based

on the performance of the main current transformers

under heavy through faults and the severity of the

magnetizing current inrush when the protected trans­

former is energized.

When this magnetizing inrush current is large

enough in magnitude and long enough in duration to

cause the Type CA-4 relay to trip when the trans­

former is energized, it is necessary to provide aux­

iliary time-delay features to restrain the action of

the Type CA-4 until the magnetizing current has

diminished below the pick-up value of the relay.

The time-delay relay used for this purpose is the

Type TSI Magnetizing Inrush Tripping Suppressor

Relay described in I. L. 4 1-346. 1.

External current balancing auto transformers are

required where the main current transformers do not

provide equal secondary currents with the correct

phase relation for the Type CA-4 restraining wind-

SUPERSEDES I.L. 41-334.1 *Denotes change from superseded issue.

ings. Figures 8 and 9 show the auxiliary auto­

transformers and Type CA-4 relay external connec­

tions for typical installations.

The power transformer connections as shown in

Figs. 8 and 9 have been made on the assumption

that the delta winding is the low voltage side of the

transformer, and in conformance with the ASA Stand­

ard that the voltages on the HV side lead the volt­

ages on the LV side by 30"

· In following the relay

connections it will be simpler to illustrate the prin­

ciples involved by using a two-winding transformer

application. The method illustrated may then be

applied to any transformer bank, whether in con­

formance with the standard or not. When applied

to a three winding bank, each delta winding is

checked separately against the star winding.

F'ig. 6 shows a two winding transformer protected

by three differential relays. In order to establish

the proper connections to the relays, first assume a

set of reference currents, A, B and C flowing into

the wye side of the transformer. The currents

flowing out of the delta side of the transformer will

by A-C, B-A, and C-B, as shown in F'ig. 6, by virtue

of the way this particular bank is connected. On

the delta side of the power transformer the current

transformers will be connected in star. The con­

nections to the relays must be such as to have the

same currents entering and leaving the relay through

the restraining windings, for the condition illustrated

of primary current flowing through the bank. Con­

sidering the top relay, for example, it is seen that

A-C current delivered to the right hand restraining

coil from the a-phase current transformer on the

delta side of the bank is passed right on through the

other restraining coil of the relay to satisfy the re­

quirements of the A- and c- phase current trans­

formers on the wye side of the bank. This keeps

the current out of the operating coil, which is proper

for the through load condition illustrated by the

primary current direction arrows. An improper con­

nection in the diagram will show up in this analysis

EFFECTIVE SEPTEMBER 1957 www . El

ectric

alPar

tMan

uals

. com

Page 2: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPECA-4RELAY ____________________________________ ______________________ __

INDICATIIIG CONT.I.CTORSWITCH

IIOTE:

li�To3h�·J�P�RED H RElAY CASE

INTERNAL SCHEMATIC

182A'730

Fig. 1. Internal Schematic of the Type CA-4 Relay In the Type FT3l Case,

through involving the op0rating coil of one or more

relays in the return circuit for the currents, or

through not having the same current entering and

leaving the restraining coils for the same relay.

J:<'ig. 7 is similar to Fig. 6 except that the delta

connected windings are the high voltage windings,

necessitating a rearrangemel'l.t of connections to

satisfy the requirement that the high side voltages

lead the low side voltages by 30 •. This changes

the currents to the relays to A-B, B-C, and C-A

instead of the A-C, B-A, and C-B currents of Fig. 6.

CONSTRUCTION AND OPERATION

DIFFERENTIAL UNIT

The type CA-4 relay operates on the induction

disc principle and consists of four electromagnets

operating ·on two discs which are fastened to the

same shaft. Three of the electromagnets are re­

straining elements and are connected to receive the

secondary currents from the various current trans­

formers. The fourth electromagnet element is con­

nected to receive the differential or unbalance cur­

rent. The operating winding is tapped so that the

relay will just operate on 15, 25, or 40 percent un­

balance. An extra connector block screw is pro·

vided so that taps on the relay can be changed with­

out opening the current differential circuit.

The currents in the three restraining elements

produce contact opening torque proportional to the

currents in the various windings of the protected

2

transformer. The current in the difference or opera­

ting element produces a contact closing torque pro­

portional to the difference of the three restraining

currents when these currents are flowing through the

power transformer. The necessary quadrature flux

to produce torque is supplied by the upper pole coil

of the electromagnet. These coils are excited by

transformer windings on the main poles of the vari­

electromagnets.

Because of the restraint which exists in the

relay during through faults when the current is

heavy, the current transformer characteristics need

not be accurately matched, since there is a restrain­

ing torque on the relay disc that permits a certain

discrepancy of current transformer ratio character­

istics without resulting in faulty tripping. This is

illustrated in figure 2 which shows typical operating

characteristics for a through fault. f!'igs. 3 and 4

show typical time current curves for the type CA-4

relay.

INDICATING CONT ACTOR SWITCH UNIT (ICS)

The d-e indicating contactor switch is a small

clapper type device. A magnetic armatur,�. to which

leaf-spring mounted contacts are attached, is at­

tracted to the magnetic core upon energization of the

switch. When the switch closes, the moving contacts

bridge two stationary contacts, completing the trip

circuit. Also during this operation two fingers on

the armature deflect a spring located on the front of

the switch, which allows the operation indicator

target to drop. The target is reset from the outside

of the case by a push rod located at the bottom of

the cover.

The front spring, in addition to holding the tar­

get, provides restraint for the armature and thus

controls the pickup value of the switch.

CHA RACTERISTICS

The type CA-4 relay has three percentage taps,

15%, 25% and 40% on the operating coil. These

values represent the percentage unbalance current

required to operate the relay on a through to external

fault as shown by Fig. 5.

Typical time curves are shown in l<'igs. 3 and 4.

TRIP CIRCUIT

The main contacts will safely close 30 amperes

at 250 volts d-e and the seal-in contacts of the indi­

cating contactor switch will safely carry this current

www . El

ectric

alPar

tMan

uals

. com

Page 3: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4 RELAy -- ---------------------------�-1-_L_. _41_-3_3�4-.lA

:::! RELAY CoNTACTS (LOS£ /J!IEN t'tiRROVTS � 50 PLOTTED ARE ABOVE CURVE. ++++++++++-++++

·. r 1::::1::1-:-1;:: 11:.:. 1:;.: 1.,:111.1111 :lr -;-+ � . •_: DASH LINE- 3 RESTRAIN/Ntj ELEMENTS lNERGI.ZEDH-+++-f-H-1:: ':�:SOLID LINE- 2 REST/i'AIN/Ntj ELEMENTS ENEI?t;IZED � 40�-�+++-++++"�;�;r·� · '_:�•� .. �·�·�::�r�:+-;·�'++-"�·rl·�·+r·•Ht�·+r�-�+++�++

<:::5 :t :g <:::1 � 30

� ..... � Q,;: � 20���-++r�+-���+-�++-H-++-�+-���++-�4++

'-J

Curve 235381

0��--_.�----------.. �-w�������� 0 2 0 40 60 80 100 AMPERES ltJTAL SHORT C!RCt/IT CURRENT THROI/uH RELAY. THIS Is TH£ GREATER OF THE 70TAL /Nt:0/'1/NG OR TOTAL OUTGOING CIIRRE/VTS As MEASURED Br' llt£ CURI?E.IYT lRA!vSF0R(-J£R:::.

Fig. 2. Typical Operatln!i Characteristic lor an External Fault.

0 0 20 40 60 80 100 120 Curve 165270 AMPERES

Fig. 3. Typical Time-Current Curves with Current in One Restraint Coil.

/40

3 www . El

ectric

alPar

tMan

uals

. com

Page 4: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPECA -4RELAY __________________________________________________________ __

.6 -ttl+ H

.5

Q. .4

� R: � "l .3 �

8 �

.2

+ 1' _ _;_

h H + r++�+n �-t-1+ 20 40 60 80 100 /20 /40

AMPERFS Curve 165271

Fig. 4. Typical Time-Current Curves of the Type CA-4 Relay· One Third of Operating Coil Current In Each Restraint Coil.

long enough to trip a circuit breaker.

The indicating contactor switch has two taps

that provide a pickup setting of 0.2 or 2 amperes.

To change taps requires connecting the lead located in front of the tap block to the desired setting by

means of a screw connection.

TRIP CIRCUIT CONSTANT

Indicating Contactor Switch (ICS)

0.2 ampere tap 6. 5 ohms d-e resistance

2.0 ampere tap 0.15 ohms d-e resistance

INSTALLATION

The relays should be mounted on switchboard

panels or their equivalent in a location free from

dirt, moisture, excessive vibration, and heat. Mount

the relay vertically by means of the four mounting

holes on the flange for semi-flush mounting or by

means of the rear mounting stud or studs for pro­

jection mounting. Either a mounting stud or the

mounting screws may be utilized for grounding the

relay. The electrical connections may be made

directly to the terminals by means of screws for

steel panel mounting or to the terminal studs fur-

4

nished with the relay for thick panel mounting. The

terminal studs may be easily removed or inserted

by lecking two nuts on the stud and then turning the

proper nut with a wrench.

For detaHed FT case information refer to I.L.

41-076.

SETTINGS

U�FFERENTIAL UNIT

Select the desired percent slope tap - - 15, 25 or

40. The 25% slope tap is recommended for trans­

formers with no load taps. Where the transformers

have tap changing under load mechanisms, the 40%

tap is recommended.

�DICATING CONTACTOR SWITCH (ICS)

No setting is required on the ICS unit except the

selection of the current tap - 0.2 or 2.0 amperes.

This selection is made by connecting the lead lo­

cated in front of the tap block to the desired setting

by means of the connecting screw. Where the CA-4

.., relay energizes a 125 or 250 volt d-e Type WL relay

switch, or its equivalent, the 0.2 ampere tap is

recommended.

www . El

ectric

alPar

tMan

uals

. com

Page 5: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

\

TYPE CA-4 RELAY ___________________________________________________________ I_.L_._4 1_-3_3_4 . __ 1A

LAMP

} 120 YOLTS ----+-4-----i-- 60 CYCLES

-----------� } 125 �.D.C.

COMMECTIOMS FOR CHECKING SPRING TENSION ADJUSTMENT

CA-'1 RELAY (FRONT YIEW)

LAMP

} 120 YOLTS ----+---------+- 60 CYCLES

-----------......_ }12!> �.D.C.

CONNECTIONS FOR CHECKING THE OPERATING CHARACTERISTICS

l83Al33 Fig. 5. Diagram of Test Connections.

ADJUSTMENTS AND MAINTENANCE

The proper adjustments to insure correct opera­

tion of this relay have been made at the i.•x:tory and

should not be disturbed after receipt by the customer.

If the adjustments have been changed, the relay

taken apart for repairs, or if it is desired to check

the adjustments at regular maintenance periods, the

instructions below should be followed.

The top bearing screw should have approximately

.002" clearance between it and the shaft. Adjust

the stationary contact so that 1/4 inch contact

separation is obtained when the moving contact is

held open against its stop.

The tension of the spiral spring should be ad­

justed so that the contacts just close bet"oeen 3. 9 to 4.1 amperes 60 cycles gradually increasing cur­

rent thru the operating coil on the 40% tap. On the

25% tap these values are 2.1 to 2.6 amperes and on

the 15% tap, 1. 2 to 1.4 amperes. This current should

be passed thru the operating coil only as shown in

the left half of figure 5.

The relay operating characteristics of figure 2

may be checked by connecting the relay as shown in

the right half of figure 5.

With 80 amperes through the operating coil and

one of the restraining coils, the relay should close

the contacts properly with little chattering. If it

does not, look for incorrect location of the disc in

the air gap.

INDICATING CONTACTOR SWITCH (ICS)

Close the main relay contacts and pass suffi­

cient d-e current through the trip circuit to close

the contacts of the ICS. This value of current

should not be greater than the particular ICS tap

setting being used. The indicator target should

drop freely.

ENERGY REQUIREMENTS

The burden of the type CA-4 restraining wind­

ings with 5 amperes flowing is . 75 volt-amperes

per element. lvith 5 amperes flowing through the

operating winding its burden is as follows:

15% Tap

25%

40%

24.0 volt amperes

8.5 " 3.3 II

58" Lag 53"

45°

II

5 www . El

ectric

alPar

tMan

uals

. com

Page 6: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4 RELAY

A _A_

TYPE CA RELAYSL_-

•-o LV �

�r ,---s l__

B-A � ,. C-B

"L

C_c_ --

_A-C

---------

_c-e Jrn_ _ �--___ _

�" I_

b

Fig. 6. Current and Voltage Relatioaships for Wye- Delta Transf-:rmer Differential Protection - WYe Volt· ages Lead Delta Voltages by 30",

87 5 87 T

TRANS FORMER BANK

IL IC

fi� EF-=-

a b c

=c lr _A-B c ---=:.- j -n-----L+--- --"�� --- . I

TYPE C4 �ELA.Y$-1 --- . , B-C ' B-C I I --.. -- - ,�--�-��J-t--

------ -- �--J =

Fig. 7. Current and Voltage Relationships for Wye - Delta Transformer Differential Protection D.,lta Voltages Lead Wye Voltages by 30".

p��- __ ,.:..;.;..;.;;;;;_=­NEil.

u Lti-, I

I

--� p �CURRENT BALANCE AUTO TRANSFORMERS

87 T +

��ICS 1 � �w86

PH. 1

NEG. OR -----------------

POS.

DEi ICE MUMaER CHART 87 - PERCENTAGE DIF FEREMTIAL RELAY

TYPE CA-<

87R - RESTRAINIMu COIL OF THE TYPE C A-q RELAY

870P - OPERATING COl L OF THE TYPE

CA-q RELAY

ICS - IHOICATIHu CONTACTOR SWITCH 86- AUXILIARY TRIPPING RELAY

PM. l TYPE WL

PM. J

288B�8o Fig. 8. External Schematic of the Type CA-4 Relay for Wye - Delta -Delta Transform er Protection.

6 www . El

ectric

alPar

tMan

uals

. com

Page 7: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4 RELAY ----------------------------___:•:::·L::.·.:;_4.:_1·:::.:33:::4.:.:.1-=...A

TIIANSFOKMER BANK

B A

POS. D.C. TRIP BUS OR --.-------

'----- CURRENT BAL AHCE AUTO TRANSFORMER

NEG.

NEG. OR

POS.

DEVICE NUMBER CHARTS

87 • PERCENTAGE DIFFERENTIA� REUY TYPE CA-�

87R • RESTRA I M I NG CO I� OF THE TYPE CA-� RE�AY

870P • OPERATINii COl� OF THE TYPE CA-� RE�AY

ICS - INDICATING CONTACTOR SWITCH

86 - AUXILIARY TRIPPINil RELAY TYPE WL

288B581 Fig. 9. External Schematic of the Type CA-4 Relay for Wye - Delta - Wye Transformer Protect/on.

7 www . El

ectric

alPar

tMan

uals

. com

Page 8: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE C�4 RELAY ________________________________________________________ __

190·32 SCRE.W

SPACER FOR TH\t-.1 P"NE.LS

.5 -I Q ':.CREW IG (F"OR \\-\IC� �\JEL IJSE � -16 ':>IUD) \10

,I90-3Z. SCREW (FOR \HICK. """"W'EL use:

. 1 9 0 -32. 5\UD)

T�RMINAL ANt> MOUNTIN<I DE1AIL'O

_!__ DIA. 4-1-\0LES f"OR 4.190-32. MTG. 'OCR£W�

PANEL CUTCllT $ DRILLIWGr FOR. SEMI-FLUC:.H MT�.

I \3z.

PA.NEL CRILL\� OR. CUTOUT 'PROJ&:C.T\ON MTGr.

( FRO\.tT \J\EW)

3 -eR.

TERMINAL NUMeER.

57-D-7902

Fig. JO. Outline ana Drilling Plan for the Type CA-4 Relay In the FT31 Case.

WESTINGHOUSE ELECTRIC CORPORATION METER DIVISION • N,EWARK, N.J.

Printed in U. S. A. www . El

ectric

alPar

tMan

uals

. com

Page 9: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

t(G I.L. 41-334. 1A �0 INSTALLATION • OPERATION • MAINTENANCE

���El-J_I_ N_S_T_R_U_C_T_I _O_N_S_ .. * ..

,.....-

TYPE CA-4 PERCENTAGE DIFFERENTIAL RELAY

CAUTION Before putting protective relays into

service, remove all blocking which may have been

inserted for the purpose of securing the parts dur­

ing shipment, make sure that all moving parts oper­

ate freely, inspect the contacts to see that they are

clean and close properly, and operate the relay to

check the settings and electrical connections.

APPLICATION

The type CA-4 percentage differential relay is

designed for the differential protection of three­

winding transformers, and has three restraining

coils - one for each winding of the transformer. It is a current-operated induction disc relay designed

so that the operating coil current required to close

the contacts varies in proportion to the current

through the restraining windings. This feature pre­

vents tripping on through faults, because of unbal­

anced current transformer characteristics or loading,

and allows the relay to be set for sensitive protec­

tion. The relay has three percentage taps of 15, 25

and 40%. The choice of a particular tap is based

on the performance of the main current transformers

under heavy through faults and the severity of the

magnetizing ct.UTent inrush when the protected trans­

former is energized.

When this magnetizing inrush current is large

enough in magnitude and long enough in duration to

cause the Type CA-4 relay to trip when the trans­

former is energized, it is necessary to provide aux­

iliary time-delay features to restrain the action of

the Type CA-4 until the magnetizing current has

diminished below the pick-up value of the relay.

The time-delay relay used for this purpose is the

Type TSI Magnetizing Inrush Tripping Suppressor

Relay described in I. L. 41-346.1.

External current balancing auto transformers are

required where the main current transformers do not

provide equal secondary currents with the correct

phase relation for the Type CA-4 restraining wind-

SUPERSEDES I.L. 41-334.1 *Denotes change from superseded issue.

ings. Figures 8 and 9 show the auxiliary auto­

transformers and Type CA-4 relay external connec­

tions for typical installations.

The power transformer connections as shown in

Figs. 8 and 9 have been made on the assumption

that the delta winding is the low voltage side of the

transformer, and in conformance with the ASA Stand­

ard that the voltages on the HV side lead the volt­

ages on the LV side by 30"

· In following the relay

connections it will be simpler to illustrate the prin­

ciples involved by using a two-winding transformer

application. The method illustrated may then be

applied to any transformer bank, whether in con­

formance with the standard or not. When applied

to a three winding bank, each delta winding is

checked separately against the star winding.

Fig. 6 shows a two winding transformer protected

by three differential relays. In order to establish

the proper connections to tbe relays, first assume a

set of reference currents, A, B and C flowing into

the wye side of the transformer. The currents

flowing out of the delta side of the transformer will

by A-C, B-A, and C-B, as shown in Fig. 6, by virtue

of the way this particular bank is connected. On

the delta side of the power transformer the ctnTent

transformers will be connected in star. The con­

nections to the relays must be such as to have the

same currents entering and leaving the relay through

the restraining windings, for the condition illustrated

of primary current flowing through the bank. Con­

sidering the top relay, for example, it is seen that

A-C current delivered to the right hand restraining

coil from the a-phase current transformer on the

delta side of the bank is passed right on through the

other restraining coil of the relay to satisfy the re­

quirements of the A- and c- phase current trans­

formers on the wye side of the bank. This keeps

the current out of the operating coil, which is proper

for the through load condition illustrated by the

primary current direction arrows. An improper con­

nection in the diagram will show up in this analysis

EFFECTIVE SEPTEMBER 1957 www . El

ectric

alPar

tMan

uals

. com

Page 10: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4 RELAY ________________________________________________________ __

IIIT£RMAL SCHEMATIC

MOTE:

!�To3l:·��P�REO FRONT VIEW ATIElAYCASE

BOTTOM FRONT (F.V.)

BOTTOMREAR(F.Y.)

CHASSIS OPERATED --1----t---r-SIIORTING SWITCH

REDIIAIIDLE TEST SWITCH CURRENT TEST .JACK

TEII�INAL

182A730

Fig. J. Internal Schematic of the Type C A-4 Relay In the Type FT31 Case.

through involving the operating coil of one or more

relays in the return circuit for the currents, or

through not having the same current entering and

leaving the restraining coils for the same relay.

l<,ig. 7 is similar to Fig. 6 except that the delta

connected windings are the high voltage windings,

necessitating a rearrangemel'lt of connections to

satisfy the requirement that the high side voltages

lead the low side voltages by 30°

. This changes

the currents to the relays to A-B, B-C, and C-A

instead of the A-C, B-A, and C-B currents of Fig. 6.

CONST RUCTION AND OPERATION

DIFFERENTIAL UNIT

The type CA-4 relay operates on the induction

disc principle and consists of four electromagnets

operating · on two discs which are fastened to the

same shaft. Three of the electromagnets are re­

straining elements and are connected to receive the

secondary currents from the various current trans­

formers. The fourth electromagnet element is con­

nected to receive the differential or unbalance cur­

rent. The operating winding is tapped so that the

relay will just operate on 15, 25, or 40 percent un­

balance. An extra connector block screw is pro­

vided so that taps on the relay can be changed with­

out opening the current differential circuit.

The currents in the three restraining elements

produce contact opening torque proportional to the

currents in the various windings of the protected

2

transformer. The current in the difference or opera­

ting element produces a contact closing torque pro­

portional to the difference of the three restraining

currents when these currents are flowing through the

power transformer. The necessary quadrature flux

to produce torque is supplied by the upper pole coil

of the electromagnet. These coils are excited by

transformer windings on the main poles of the vari­

electromagnets.

Because of the restraint which exists in the

relay during through faults when the current is

heavy, the current transformer characteristics need

not be accurately matched, since there is a restrain­

ing torque on the relay disc that permits a certain

discrepancy of current transformer ratio character­

istics without resulting in faulty tripping. This is

illustrated in figure 2 which shows typical operating

characteristics for a through fault. F'igs. 3 and 4

show typical time current curves for the type CA-4

relay.

INDICATING CONTACTOR SWITCH UNIT (ICS)

The d-e indicating contactor switch is a small

clapper type device. A magnetic armature, to which

leaf-spring mounted contacts are attached, is at­

tracted to the magnetic core upon energization of the

switch. When the switch closes, the moving contacts

bridge two stationary contacts, completing the trip

circuit. Also during this operation two fingers on

the armature deflect a spring located on the front of

the switch, which allows the operation indicator

target to drop. The target is reset from the outside

of the case by a push rod located at the bottom of the cover.

The front spring, in addition to holding the tar­

get, provides restraint for the armature and thus

controls the pickup value of tbe switch.

CHA RACTERISTICS

The type CA-4 relay has three percentage taps,

15%, 25% and 40% on the operating coil. These

values represent the percentage unbalance current

required to operate the relay on a through to external

fault as shown by Fig. 5.

Typical time curves are shown in l<,igs. 3 and 4.

TRIP CIRCUIT

The main contacts will safely close 30 amperes

at 250 volts d-e and the seal-in contacts of the indi­

cating contactor switch will safely carry this current

www . El

ectric

alPar

tMan

uals

. com

Page 11: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4 RELAY _________________________________________________________________________________________________________ I . L_._ 4_1-_33_4_.1_A

::;! lij RELAY CONTACTS (LOSE �£/HEN t'tJRR£NTS ,a 50 ��� PLOTTEO ARc ABOVE CURVE. : rr TT HTl+-LI::uuW-ll I I WI r I� -III-I I �H.I-W U++-� � [�· . DASH LINE 3 RESTJf'AIN/N(j Ei.£MENTS CNERGIZED .::: c-;SOLIO LIN£- 2 RESTHAININ(j ELEMENTS ENEIUiiZEO � 4o 1

+ r-F ' H-� . . . . � tt 1; •l -.

<;:::) �- t ::):. � f � 30 � I

1

Curve 235381

Fig. 2. Typical Operating Characteristic lor an External Fault •

. 5 C'ONTACT 7/i>A VEL t

.I

0 0 20 Curve 165270

40 60 80 AMPERES

100 120

Fig. 3. Typical Time-Current Curves with Current In One Restraint Coli.

140

3 www . El

ectric

alPar

tMan

uals

. com

Page 12: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4RELAY ____________________________________________________ __ __

.6

.5

It .4

Ci: I' � "' .3 � 8 �

.2

.I

r

+- H-' ' 2S% TAP -" ll_] ' IS" "l'o TAP

+-+-+-<++-+-++ 1H T •++++ + , 1 , , T Jti J4 ltvcH CotvTA,cT TRAVEL ' W--1---1----l-+---1+-it '

+-H-'-=1 i -

T t

+

-+--++-: +-+++

+�

' -+--'

i

' H- -

' '

-i-+ t-l-H

'

0 4() 60 80 /00 120 /40 AMPERES Curve 165271

Fig. 4. Typical Time-Current Curv .. of the Type CA-4 Relay. One Third ol Operating Coil Current In Each Restraint Col/.

long enough to trip a circuit breaker.

The indicating contactor switch has two taps

that provide a pickup setting of 0.2 or 2 amperes.

To change taps requires connecting the lead located

in front of the tap block to the desired setting by

means of a screw connection.

TRIP CIRCUIT CONSTANT

Indicating Contactor Switch (ICS)

0.2 ampere tap 6.5 ohms d-e resistance

2.0 ampere tap 0.15 ohms d-e resistance

INSTALLATION

The relays should be mounted on switchboard

panels or their equivalent in a location free from

dirt, moisture, excessive vibration, and heat. Mount

the relay vertically by means of the four mounting

holes on the flange for semi-flush mounting or by

means of the rear mounting stud or studs for pro­

jection mounting. Either a mounting stud or the

mounting screws may be utilized for grounding the

relay. The electrical connections may be made

directly to the terminals by means of screws for

steel panel mounting or to the terminal studs fur-

4

nished with the relay for thick panel mounting. The

terminal studs may be easily removed or inserted

by lecking two nuts on the stud and then turning the

proper nut with a wrench.

For detaHed FT case information refer to I.L.

41-076.

SETTINIGS

DIFFERENTIAL UNIT

Select the desired percent slope tap -- 15, 25 or

40. The 25% slope tap is recommended for trans­

formers with no load taps. Where the transformers

have tap changing under load mechanisms, the 40%

tap is recommended.

llroiCATING CONTACTOR SWITCH (ICS)

No setting is required on the ICS unit except the

selection of the current tap - 0.2 or 2.0 amperes.

This selection is made by connecting the lead lo­

cated in front of the tap block to the desired setting

by means of the connecting screw. Where the CA-4

... relay energizes a 125 or 250 volt d-e Type WL relay

switch, or its equivalent, the 0.2 ampere tap is

recommended.

www . El

ectric

alPar

tMan

uals

. com

Page 13: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4RELAY _________________________________________________ ___________ I

._L_.4_1_-3_u_. __ 1A

CA•" RELAY (FRONT VIEW)

11 = TOTAL RESTRAINING COIL CURRENT

10 = OPERATING COIL CURRENT

LAICP

} 120 VOLTS ----+-.... -----� 60 CYCLES

-----------� } 125 �.o.c.

CO .. ECTIOIS FOR CHECKING SPRING TEISIOM AD�USTMENT

LAICP

} 120 VOLTS ----+---,._ ___ _,_ 60 CYCLES

___________ _..._} 125 v.o.c.

CONNECTIONS FOR CHECKING THE OPERATING CHARACTERISTIC�

183Al33

Fig. 5. Diagram ol Test Connections.

ADJUSTMENTS AND MAINTENANCE

The proper adjustments to insure correct opera­

tion of this relay have been made at the factory and

should not be disturbed after receipt by the customer.

If the adjustments have been changed, the relay

taken apart for repairs, or if it is desired to check

the adjustments at regular maintenance periods, the

instructions below should be followed.

DIFFERENTIAL UNIT

The top bearing screw should have approximately

.002" clearance between it and the shaft. Adjust

the stationary contact so that 1) 4 inch contact

separation is obtained when the moving contact is

held open against its stop.

The tension of the spiral spring should be ad­

justed so that the contacts just close between 3. 9

to 4.1 amperes 60 cycles gradually increasing cur­

rent thru the operating coil on the 40% tap. On the

25% tap these values are 2.1 to 2.6 amperes and on

the 15% tap, 1.2 to 1.4 amperes. This current should be passed thru the operating coil only as shown in

the left half of figure 5.

The relay operating characteristics of figure 2

may be checked by connecting the relay as shown in

the right half of figure 5.

With 80 amperes through the operating coil and

one of the restraining coils, the relay should close

the contacts properly with little chattering. If it

does not, look for incorrect location of the disc in

the air gap.

INDICATING CONTACTOR SWITCH (ICS)

Close the main relay contacts and pass suffi­

cient d-e current through the trip circuit to close

the contacts of the ICS. This value of current

should not be greater than the particular ICS tap

setting being used. The indicator target should

drop freely.

ENERGY REQUIREMENTS

The burden of the type CA-4 restraining wind­

ings with 5 amperes flowing is . 75 volt-amperes

per element. With 5 amperes flowing through the

operating winding its burden is as follows:

15% Tap 25%

40%

24. 0 volt amperes 8.5 II II

3. 3 II

58" Lag

53°

45°

II

"

5 www . El

ectric

alPar

tMan

uals

. com

Page 14: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4 RELAY

TYPE CA RELAYS �--f----��

Fig. 6. Current and Voltage Relationships for Wye -Delta Transformer Dllferentlol Protection- WYe Volt· ages Lead Delta Voltages by 30".

TRAMSFGaMER BANK

� ;::r l)s IL � � 41---

3e IL

� L,O. ��� c

t�t �� � � � rP B. B � c 8 A 8�1 jZ 87 v+ 87�- 1 87 s * 87 v+ 87;t-I � � .r+ 87��

·v � d�( 87 3

¥ ,,-. 87�-2 87 ¥ v+ 8;{-2 � ¥_ ,,-. B;�v_l �

v � �-J � 87 �87RA J d7 5 � v •I+87;�

llj lv- � .r+87R·J �

• � LV HV

,---3 • L _1j �:• � ;J l

.1§ t!s c c � s J i§ ��c

_A-8 �h I TYPE CA RELAYS�

�� ��

a b c A-tl

��

;::;:::;..... � B-C I_

�' � C-A

L_ rYY--.. � L_

v�r �b 'bt)

Vc Vba

Fig. 7. Current and Voltage Relationships for Wye -Delta Transformer DIHerential Protection Delta Voltages Lead Wye Voltages by 30".

� ,---J ,_,

rv--. u

u

I ��

Lt.-,. �

1 87 2

"--.cuRRENT BAL AHCE RMERS AUTO TRANSFO

} '"·

' 8 87

1 '" '

I

P•·

J

NEG.

OR __ .,._. _____ _ POS.

DEVICE NUM8ER CHART 87 - PERCENTAGE DIFFERENTIAL RELAY

TYPE CA-'1 7R • RE STRAINING COIL OF THE TYPE

CA-'1 RELAY

OP - OPERATING COl L OF THE TYPE

CA-'1 RELAY

CS - INDICATING COHTACTOR SWITCH 86 - AUXILIARY TIIIPPI N G RELAY

TY P E WL

288B'S80 Fig. 8. External Schematic of the Type CA-4 Relay for Wye -Delta -Delta Transformer Protection.

6 www . El

ectric

alPar

tMan

uals

. com

Page 15: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPE CA-4RELAY _______________________________________________________ �J�.L�.4�1���34�·�1A

87 5 87

(

87 5

TUII$FOIIMER BANK POS. D.C. TRIP BU$

OR ----��----------NEG.

87 2

'\__ CURRENT BALANCE AUTO TRANSFORMER

} �. 3

NEG. OR ---41-----------..

POS.

DEVICE NUMBER CHART$

87 • PERCENTAGE DIFFERENTIAL RELAY TYPE CA-�

87R • RESTRAIIIING COIL OF THE TYPE CA·� RELAY

870P • OPERATING COl L OF THE TYPE CA·� RELAY

ICS • INDICATING CONTACTOR SWITCH

86 • AUXILIARY TRIPPING RELAY TYPE WL

288B581

Fig. 9. External Schematic of the Type CA-4 Relay for Wye -Delta - Wye Transformer Protection.

7 www . El

ectric

alPar

tMan

uals

. com

Page 16: INSTALLATION OPERATION MAINTENANCE '1 … • OPERATION • MAINTENANCE 1; ... is a current-operated induction disc relay designed ... The time-delay relay used for this purpose is

TYPEC�4RELAY--------------------------------------------------------

190·32. SCRE.W

SPACER FOR 1\-\IN P/\N·L�

_s -I Q SCREW II<> (FOR \�IC�

R'..\JE\... IJSE ..:i-IS '!)TUD) IE>

,I90-3Z. SCREW (FOR. \HICK. l"'�N'E\... US.E.

. 1 9 0 -.32. '5\UO)

T�RMINAL AWO MCUNTII'lCJ DEtAIL�

� DIA.. 4�0LES FOR .190-32. MTG. <;;,CREWS

PANEL C.UTO\lT t DRILLING­FoR 'SEM\-FLUC:.H MTQ-.

I I '5""t. '�

PANEL CRILL\� OR C.\JTO\JT f>ROJi:CT\ ON M'T'Or.

( FR�T \1\EW) 5'7-D-'7902

Fig. JO. Outline anJ Drilling Plan for the Type CA-4 Relay In the FTJJ Case.

WESTIN GHOUSE METER DIVISION

ELECTRIC •

CORPORATION NEWARK, N.J.

PriDtecl ill U. S. A. www . El

ectric

alPar

tMan

uals

. com