Installation & Maintenance ManualDigital Pressure SwitchSeries ZSE30/ISE30
Model Indication Method Names and Functions of Individual Parts
The Digital Pressure Switch and this manual contain essentialinformation for the protection of users and others from possibleinjury and property damage and to ensure correct handling.Please check that you fully understand the definition of the followingmessages (signs) before going on to read the text, and alwaysfollow the instructions.
Read this manual and follow its instructions. Signal words suchas WARNING and NOTE, will be followed by important safetyinformation that must be carefully reviewed.
Do not disassemble, modify (including change of printedcircuit board) or repair.An injury or failure can result.
Do not operate outside of the specification range.Fire, malfunction or switch damage can result.
Do not operate in atmosphere of inflammable, anexplosive or corrosive gas.Fire, an explosion and corrosion can result.This pressure switch is not an explosion-proof type.
Do not use this product in a place where static electricityis a problem.Otherwise It can cause failure or malfunction of the system.
IMPORTANT MESSAGES
Indicates a potentially hazardous situationwhich could result in death or serious injuryif you do not follow instructions.
Gives you helpful information.
NOTEFollow the instructions given below when handling the pressureswitch.Otherwise, the switch may be damaged or may fail, therebyresulting in malfunction.• Do not drop, bring into collision with other objects or applyexcessive shock to the unit (100m/s2 or more).
• Do not pull the lead wire with force or lift the main unit by holdingthe lead wire. (Pulling strength less than 35N)
• Do not insert wire or other articles into the pressure port.• Connect wires and cables correctly.• Do not perform wiring while power is on.• Do not wire with power cable or high-voltage cable in the same wireroute.
• Connect Terminal FG to ground when using a switching regulatorobtained on the commercial market.
For one-touch fitting type:• Do not apply unnecessary forces such as twisting, pulling, momentloads, etc. on fitting or tubing.
• When using a brand of tubing other than SMC, be careful of thetolerance of the tube’s O.D.1) Nylon tube ±0.1mm2) Soft nylon tube ±0.1m3) Polyurethane tube +0.15mm, -0.2mm
30- - -
25
65
26
28
ISE
ZSE
A
D
B
M
01
T1
C4H
C6H
C4L
C6L
N7L
N7H
-100kPa 0 100kPa 500kPa
1MPa
ZSE30
ISE300 1MPa
-100kPa (-0.1MPa)
1MPa
-100kPa 100kPa
-101kPa 101kPa
Set pressure range and Rated pressure rangeSet the sensor pressure with the rated pressure range"Set pressure range " means the pressure range that can be set."Rated pressure range" means pressure range that satisfies the productspecifications (accuracy, linearity, etc.)Setting outside of the Rated pressure range could be set if the setting is within theWithstand pressure range, but the specified performance is not always realized.
ZS-27-A
ZS-27-B
ZS-27-C
ZS-27-D
ZS-27-01
L
A
B
D
--
Use the following product codes when optional items are needed asseparate products.
Main UnitIndication Light : Displays switch operation condition.(Green Light)LCD Display : Displays the current status of pressure, setting mode,
selected indication unit and error code. Four displaymodes can be selected: display always in red or greenonly, or changing from green to red linked to output.
Button : Selects the mode or increases ON/OFF set value.Press this button to change to the peak display mode.
Button : Selects the mode or decreases ON/OFF set value.Press this button to change to the bottom display mode.
Button : Press this button to change to either mode and to set aset value.
Safety Instructions
Safety Instructions (continue)
• Insert a noise filter (line noise filter, ferrite element or other element)between the switching regulator and pressure switch when analogoutput is used.
• Do not use with a corrosive or inflammable gas or liquid.• Do not press the setting buttons with a sharp pointed object.• Turn power on for 20 to 30 minutes before detecting fine pressure.Initial drift of about ±1% occurs immediately after turning the power on.
• The direct-current power supply to combine should be a ULauthorization class 2 power supply based on UL1310, or a powersupply using a transformer which is class 2 based on UL1585.
• Only a pressure switch with UL mark on the body is UL approved.• This pressure sensor is for use with air only. Please contact SMC ifthe switch is to be used with other fluids.
ZSE30(Vacuum, Low Pressure)SeriesRated Pressure RangeSet Pressure RangeWithstand PressureMinimum Display UnitApplicable FluidTemperature Characteristic
Env
ironm
enta
lRes
isita
nce
AmbientTemperature Range
ISE30(Positive Pressure)-100.0 to 100.0kPa 0.000 to 1.000MPa-101.0 to 101.0kPa -0.100 to 1.000MPa
500kPa 1.5MPa0.2kPa 0.001MPa
Air, inert gases and Non-flammable gases±2%F.S. or less (25ÞC reference)
Enclosure IP40 (IEC60529)Operation: 0 to 50ÞC, Storage:-10 to 60ÞC
(No condensation or freezing)Ambient HumidityRange
Operation·and Storage:35 to 85%RH(No condensation)
Withstand Voltage1000VAC ,1 minute
(between live parts and case)InsulationResistance
50M or more (at 500VDC M)(between live parts and case)
Vibration proof10 to 150Hz, 1.5mm or 20m/s2 double amplitude,
2 hours each indirections of X, Y and Z
Impact proof100m/s2, 3 times each in directions of
X, Y and Z respectively
Standards CE Marked, UL/CSA(E216656)
01Piping Type
Port Size
One-touch FittingStrait TypeOne-touch FittingElbow Type
R1/8M5 0.8
-
-
Material for FluidContact
Pressure sensing part: silicon, Piping port: C3602(Electroless nickel plated)Oring:HNBR
Wei
ght Including lead wire
with connector (2m)Excluding lead wire
with connector
O ring: NBR O ring: NBR, Fitting Part: PBT
76g
38g
78g
40g
81g
43g
T1NPT1/8
M5 0.8
-
-
C4H
-
4mm5/32inch
-
C6H
-
6mm
-
N7H
-
1/4inch
-
C4L
-
-
4mm5/32inch
C6L
-
-
6mm
N7L
-
-
1/4inch NOTE 1:Analog output cannot be selected when switch output is selected.NOTE 2:Both switch output and current output cannot be selected simultaneously when
voltage output is selected.NOTE 3:Both switch output and voltage output cannot be selected simultaneously when
current output is selected.
ZSE30
Power Supply Voltage
Repeatability
AnalogOutput
VoltageOutput(See NOTE 2)
CurrentOutput(See NOTE 3)
Hyste-resis
Hysteresis ModeWindow Comparator Mode
ISE3012 to 24VDC, ripple (p-p) 10% or less(Protected against inverse connection)
30V (During NPN output)1V or less (at 80mA load current)
2.5ms or less (anti-chatter function working: 20, 160,640 or 1280ms selectable)
Provided±0.2%F.S. ±1 digit or less±0.2%F.S. ±2 digits or less
Output Voltage:1 to 5V ±2.5%F.S. or less(within rated pressure range)Linearity:±1.0%F.S. or less
Output impedance: about 1kOutput Current: 4 to 20mA ±2.5%F.S. or less
(within rated pressure range)Linearity:±1.0%F.S. or less
Maximum Load Impedance: 300 at power supplyvoltage of 12V, 600 at 24V
Minimum Load Impedance: 50
Variable(From 0)
Maximum Load Current 80mAMaximum Impressed VoltageResidual Voltage
Response Time
Short Circuit Protection
Switch Output (See NOTE 1) NPN or PNP open collector output. 1 outputCurrent Consumption 45mA or less (With no load)
Display Method3.5 digits 7-segment display, dual-color display
(red/green) Sampling rate: 5 times/ 1sDisplay Accuracy (at 25oC) ±2%F.S. ±2 digits ±2%F.S. ±1 digitIndication Light Lit when ON (Green)
SpecificationZISE##-TFI48GB-A
For Positive Pressure
For Vacuum or Low Pressure
Pressure Range
Piping Specification
Output Specification
Option 1
Option 2
Units Specification
R1/8 (M5 female thread)
NPT1/8 (M5 female thread)
One-touch fitting Ø4mm,Ø5/32inch
One-touch fitting Ø6mm
One-touch fitting Ø1/4inch
One-touch fitting Ø4mm, Ø5/32inch
One-touch fitting Ø6mm
One-touch fitting Ø1/4inch
Straight Type
Elbow Type
NPN Output
PNP Output
1-5V Output
4-20mA Output
Rated Pressure Range of a SwitchSet Pressure Range of a Switch
Forvacuum orLowPressure
For PositivePressure
Switch Pressure Range
SI Units Only (Note 1)
With Unit Selection Function (Note 2)No Symbol
No
Symbol
Note 1) Fixed Unit For Vacuum, Low Pressure: kPa
For Positive Pressure: MPa
Note 2) Product with unit selection function cannot be
used in Japan due to new Measure Law issued.
Lead Wire with Connector
Bracket
Panel Mount Adapter
Panel mount Adapter + Front Protection Cover
Front Protection Cover
Length: 2m
Mounting Screw (M3x5L, 2 pcs)
M3x8L, 2 pcs attached
M3x8L, 2 pcs attached
No Lead Wire
Lead Wire withConnector(Length: 2m)
No Symbol None
Bracket
Panel Mount Adapter
Panel Mount Adapter + Front Protection Cover
LCD Display
Indication Light
Button
Button
Button
Connection• Make connection after turning the power off.• Install the lead wire separately from the route for power cable orhigh-voltage cable. Otherwise, malfunction may potentially resultdue to noise.
• Be sure to ground Terminal FG when using a switching regulatorobtained on the commercial market. If the analog output isconnected to a switching regulator obtained on the market, switchingnoise will be superimposed and product specification can no longerbe met. This can be prevented by inserting a noise filter, such as aline noise filter and a ferrite element, between the switching regulatorand the pressure switch, or by using a seriespower supply instead ofa switching regulator.
Pipe Connection (One-touch Fitting Type)1.Cut the tube perpendicularly.2.Hold the tube, slowly push it into the one-touch fitting until it
comes to a stop.
Connector Connecting/Disconnecting• When connecting the connector, insert it straight onto the pins andlock the connector into the square groove in the housing unitconnector clicks.
• When disconnecting the connector, press the connector lever todisengage the lever claw from the square groove. Then pull theconnector straight out.
-25NPN Open Collector OutputMax. 30V, 80mAResidual Voltage not exceeding1V
-26Analog Output Type1 to 5V (±2.5% F.S.)Load Impedance : Approx. 1k
-28Analog Output Type4 to 20mA (±2.5% F.S.)Maximum Load Impedance :300 at 12V power supply voltage600 at 24V power supply voltageMinimum Load Impedance : 50
-65PNP Open CollectorMax. 80mA
+
-
+
-
+
-
+
-
When the Lead wire with connector provided by SMCCORPORATION is used, the colors of wire (Brown, Black, Blue) willapply as shown on circuit diagram.
Output Specification
Internal Circuit and Wiring
25 8 9.53.6
01:R1/8T1:NPT1/8 M5 0.8
2-M3 0.520 0.1
1.5
3010
200.
1
Dimensions of Main Unit
Details of Pipe Fitting PartRefer to the abovepipe fitting part
Refer to the abovepipe fitting part
Refer to the following diagrams for pipe fitting part.
14.4
11.2
C4H
18
20
10.4
C4L
14.4
11.2
N7H
20.5
22.8
13.2
N7L
14.4
11.2
C6H20
22.4
12.8
C6L
01 Type
R1/8
T1 Type
NPT/8
Outline with Dimensions (in mm)
4.2
22
401510
35
42.5
30
451.
8 30
3
20
20
34.5 17.87.231 0
8 9.5 -0.4
8.75
Mounting hardware
Panel mount adapter
Bracket
Panel mount adapter and Front protection cover
1134.542.4 17.8 8 9.5
Outline with Dimensions (continue)
310 -0
.4
31 n+3.5 ( n-1)
31 0-0.4
31n
+3.
5(n
-1)
Panel mounting of adjacent switches
Horizontal
n : The number of switches
Vertical
Mount the bracket on the main unit using the two mounting screwsM3 5L and install onthe facility usinghexagon socket headcap screws.
•Mounting with BracketCaution :Tighten the pipe port to a torque of 7 to 9N·m.
Fasten the bracket mounting screws to a torque of 0.5to 0.7N·m.
•Mounting with Panel Mount Adapter
Panel mountadapter can berotated 90 degreesto be attached.
Installation
Installation(continue)
Notice when removing the switch• The Digital pressure switch with panel mount adaptercan be removed from panel by releasing the hooks atthe switch sidesas illustrated.Pressure switchand Panel mountadapter may bedamaged if notreleased correctly.
•Mounting with Panel Mount Adapter and FrontProtection Cover
ZISE##-TFI48GB-A
Lead wire withconnector Depth 4
Pipe Port
Pipe Port
Ø4. Ø5/32[inch]One-touch fitting
Ø4. Ø5/32[inch]One-touch fittingelbow type
Ø6One-touch fitting
Ø6One-touch fittingelbow type
Ø1/4[inch]One-touch fitting
Ø1/4[inch]One-touch fittingelbow type
Type Type
Type Type
Type Type
View from Top
Panel Cut Dimensions forPanel Mounting
Panel Thickness0.5 to 6mm
Panel Thickness: 0.5 to 6 mm Panel Mount Adapter(Article No. ZS-27-C)
Bracket(Article No. ZS-27-B)
M3x5L
M3x5L
more than 24
mor
eth
an24
Front Protection Cover(ZS-27-01)
Panel
Panel Mount Adapter plus Front Protection Cover(Article No.ZS-27-D)
Hook
One-touch Fitting
Tube
Housing
Square GroovePin
LeverDC Polarity Mark
Lead Wire (Brown)
Lead Wire (Blue)Connector
Mai
nC
ircui
tM
ain
Circ
uit
Mai
nC
ircui
tM
ain
Circ
uit
Load
Load
Load
Load
12to
24VDC
12to
24VDC
12to
24VDC
12to
24VDC
Brown DC (+)
Black OUT
Blue DC (-)
Brown DC (+)
Black OUT
Blue DC (-)
Brown DC (+)
Black OUT(Analog Output)
Blue DC (-)
Brown DC (+)
Black OUT(Analog Output)
Blue DC (-)
Setting Procedures
Measurement Mode
InitializeSet output mode, response time and display color change.
Pressure SettingInput a set value for pressure to perform switch output.
Measurement ModeDetects pressure, displays values and performs switching.
Other functions such as zero clear can also be set if necessary.
Initialize
Press and hold the button for more than twoseconds. The display shown at the lower right willallow the setting of the display color.When the units specification of model indication is -M, the SI units will be fixed. If no symbol is supplied,see “Selecting Indication Unit”.
1.Display Color SettingSelect a color for the LCD display.When changing the display color, press the or
button to select a display color.Sor (Red/ON) SoG (Green/ON) rEd (Red) Grn (Green)
Press thebutton to set the desired display color and to move on to setting adesired operation mode.If the mode is set to analog output, press the or button,to select a desired display color from“Grn” (Green) “rEd” (Red), then press the button to set.The display will move to operation mode setting.
2.Operation Mode SettingThe desired switch operation mode can be selected.The operation mode currently selected will be displayed. Selectthe desired operation mode by pressing the or button.
HyS(Hysteresis)
wnd(Window Comparator)
Hysteresis Mode Window Comparator Mode
P1 n1 P1 P2 n1 n2
Press the button to set and move to output mode setting.
3.Output Mode SettingThe desired output mode can be set for switch output.The output mode currently selected will be displayed.Press the or button to switch to normal output “no” orreverse output “nC”.
Press the button to set and move to response time setting.
no(Normally open)
nC(Normally closed)
4.Response Time SettingThe response time for switch output can be set.Setting of the response time prevents chattering ofthe output.The response time currently set will be displayed. Select thedesired response time by pressing the or button.
2.5 20 160 640 1280
If the operating mode is set to Hysteresis, press button to setand move on to setting Auto Preset mode.If the operating mode is set to Window comparator, pressbutton to set and return to Measurement mode.
For Vacuum and Low Pressure
For Positive Pressure
Selecting Indication UnitIf the unit specification of the model indicationis without “-M”The indication unit can be selected freely.Pressing the or button will change the unit and willautomatically convert set values.The units will change in the following order :PA GF bAr PSi inH mmH
Pa kgf/cm2 bar psi inchHg mmHg
MPa kgf/cm2 bar psi
Press the button to set and to move on to setting thedisplay color.
5.Auto Preset SettingThis function is used to memorise a measurementpressure as a reference value when Auto Preset input is set.The settings currently set will be displayed. Press the orbutton to set to Auto Preset mode.
Press the button to set and return to Measurement mode.
mAn(Manual Setting)
AUt(Auto Preset)
If set to Manual Setting
Press the SET button while in Measurement mode to display setvalues. “P_1” or “n_1” and the current set value will displayalternately. Press the button to move to the next set value, orPress the or button to enter into the Value Change mode.(See “Value Setting” )
Hysteresis mode setting
If set to Normally Open Mode If set to Normally Closed Mode
When the Hysteresis is set at less than or equal to 2 digits, theswitch output may chatter if input pressure fluctuates near theset point.
P1 n1
Window comparator mode setting
If the Window comparator mode is set, “P2” or “n2” and the currentset value will be displayed alternately (after the setting for “P1” or“n1”). Press the button to move to the next set value.(Hysteresis : H)
Press the or button to enter into the Value Change mode.(See “Value Setting” )Next, “H” and the set value of Hysteresis will be displayedalternately. Press the button to return to the normalMeasurement mode, or Press the or button to enter into theValue Change mode. (See “Value Setting” )
If the initialize setting is Normally Open mode, “P_1” will bedisplayed. “n_1” will be displayed if it is Normally Closed mode.The set pressure value can be checked without holding or stoppingswitch output operation.
If set to Normally Open Mode If set to Normally Closed Mode
P2P1 n2n1
flicker
flashing
flashing
flashing
Setting Pressure Setting
Fine Adjustment Mode(Fine Adjustment Function of Display Value)Press the button and buttonssimultaneously for longer than two seconds while inMeasurement mode. “FSt” and the current pressureMeasurement value will be displayed. Press the orbutton to change the set value. If no operation is made forlonger than two seconds or the button is pressed, thedisplay will return to the current pressure Measurement valuewhich will then display alternately with “FSt”.Press the button to display the adjusted amount(percentage), which will then display flicker alternately with“FSC”.Press the button to set and return to the Measurementmode.
Pressure Setting (continue)
Auto Preset Mode settingPress the button while in Measurement mode toselect the Auto Preset mode. “AP1” will be displayed. Prepare aswitch unit for which pressure is to be set. Press the andbuttons simultaneously while “AP1” is displayed to return to theMeasurement mode.To execute Auto Preset, press the button and “A1L” will bedisplayed. Perform adsorption and desorption operations.Detection will be made and a set value will be stored in the memoryautomatically. Press the button while “A1L” is displayed tofinish setting and to return to the normal Measurement mode.
Value SettingTo input a value for pressure setting or otherpurposes:1. Press the or button to enter the Set Value
Change mode. The first digit will flash.2. Press the or button to set the desired
value.(No operation within ten seconds after the SetValue Change mode was selected results inautomatic setting of the value appearing in thedisplay window and in charging of the mode to SetValue Change mode to Set Value Indication mode.)
3. Press the button to make the next digit flash.(If the highest digit is zero, “ ” or “ ” will flash.“ ” means “+zero”, “ ” means “-zero”.)(When the button is pressed at the third digit, the firstdigit will flash).
4. Press the button continuously for longer thanone second to return to displaying set values.
If the Hysteresis mode is set, “H” and the set value of Hysteresis will bedisplayed alternately (after the setting for “P1” or “n1”).Press the button to return to Measurement mode, orPress the or button to enter into the Value Change mode.(See “Value Setting” )
ZISE##-TFI48GB-A
ON
OFF
ON
OFF
ON
OFF
ON
OFF
(Whe the productis shipped)
(Reverse) (Whe the productis shipped)
(Reverse)
Set value of Hysteresis (H)
ON
OFF
Switch Output
High pressure
Set value of Hysteresis (H)
ON
OFF
Switch Output
High pressureSet value of Hysteresis (H)
ON
OFF
Switch Output
High pressure
Set value of Hysteresis (H)
ON
OFF
Switch Output
High pressure
Key Lock FunctionThis function prevents malfunction such as a set value beingchanged by mistake. Press and hold the button for longer thanfour seconds to display which of “Loc” or “UnL” is currently set.Select by pressing the or button and set by presing the
button. If button operation isnot desired, set to “Loc” to set the Lock mode. To release key lock,Press and hold the button for longer than four seconds todisplay the current setting and set to “UnL”.Zero Clear FunctionThe displayed value can be adjusted to zero when pressure to bemeasured is within ±70digits of the atmospheric pressure.(The range of ±10% F.S.setting is different depending on theindividual product difference)This function is useful because it enables the detection of pressurefluctuations larger than a certain value without being influenced byfluctuations of source pressure. Press continuously the and
buttons simultaneously to reset to “0” on the display. andreturn to the Measurement mode automatically.
This function displays error location and nature when a problem oran error occurs.
Error Name
OvercurrentError
ResidualPressureError
PressurizingError
SystemError
Error Nature TroubleshootingMethodError Display
A load current is flowig tothe switch output of 80mAor more.
Pressure more than ±0.071MPafor 1MPa or more than ±7.1kPafor vacuum compared with theatmospheric pressure is appliedduring zero clear operation.In three seconds, the mode willreset to the Measurement mode.±10% F.S. of the setting rangechanges with individual productdifferences.
Displayed in the case of aninternal data error.
Displayed in the case of aninternal data error.
Displayed in the case of aninternal data error.
Displayed in the case of aninternal data error.
Pressure outside of the highlimit of the set pressurerange is applied.
Pressure outside of the lowlimit of the set pressurerange is applied.
Turn the power off andremove the cause of theoutput oovercurrent.Then turn the power on.
Perform zero-clearoperation again afterrestoring the appliedpressure to anatmospheric pressurecondition.
Reset appliedpressure to a levelwithin the setpressure range.
Turn the power offand turn it on again.If resetting fails, aninvestigation by SMCCorporation will berequired.
Other Functions
Error Display Function
Peak and Bottom Hold Display FunctionMaximum and minimum values are always detected and updatedduring measurement. Displayed values can be held. For peak hold,Press and hold the button for longer than one second to hold themaximum pressure value. The display will flash.To reset holding, press and hold the button for more than onesecond. The display will return to measurement mode. For buttomhold, press and hold the button for longer than one second tohold the minimum pressure value. To display will flashTo reset holding, pressure and hold the button for more thanone second. The display will return to measurement mode.
ZISE##-TFI48GB-A
AUSTRIA (43) 2262 62280 NETHERLANDS (31) 20 531 8888BELGIUM (32) 3 355 1464 NORWAY (47) 67 12 90 20CZECH REP. (420) 541 424 611 POLAND (48) 22 211 9600DENMARK (45) 7025 2900 PORTUGAL (351) 21 471 1880FINLAND (358) 207 513513 SLOVAKIA (421) 2 444 56725FRANCE (33) 1 6476 1000 SLOVENIA (386) 73 885 412GERMANY (49) 6103 4020 SPAIN (34) 945 184 100GREECE (30) 210 271 7265 SWEDEN (46) 8 603 1200HUNGARY (36) 23 511 390 SWITZERLAND (41) 52 396 3131IRELAND (353) 1 403 9000 UNITED KINGDOM (44) 1908 563888ITALY (39) 02 92711