Electromagnetic Flowmeters

MagMasterTM

Instruction Manual –BOOK 3 Electrical InstallationIM/MM/BK3_6

Page 2: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

ABB

The Company

We are an established world force in the design and manufacture of instrumentation forindustrial process control, flow measurement, gas and liquid analysis and environmentalapplications.

As a part of ABB, a world leader in process automation technology, we offer customersapplication expertise, service and support worldwide.

We are committed to teamwork, high quality manufacturing, advanced technology andunrivalled service and support.

The quality, accuracy and performance of the Company’s products result from over 100 yearsexperience, combined with a continuous program of innovative design and development toincorporate the latest technology.

The UKAS Calibration Laboratory No. 0255 is just one of the ten flow calibration plantsoperated by the Company and is indicative of our dedication to quality and accuracy.

Use of Instructions

Warning.An instruction that draws attention to the risk of injury ordeath.

Caution.An instruction that draws attention to the risk of damage tothe product, process or surroundings.

Note.Clarification of an instruction or additional information.

Information.Further reference for more detailed information ortechnical details.

Although Warning hazards are related to personal injury, and Caution hazards are associated with equipment or property damage,it must be understood that operation of damaged equipment could, under certain operational conditions, result in degradedprocess system performance leading to personal injury or death. Therefore, comply fully with all Warning and Caution notices.

Information in this manual is intended only to assist our customers in the efficient operation of our equipment. Use of this manualfor any other purpose is specifically prohibited and its contents are not to be reproduced in full or part without prior approval of theMarketing Communications Department.

Health and SafetyTo ensure that our products are safe and without risk to health, the following points must be noted:

1. The relevant sections of these instructions must be read carefully before proceeding.

2. Warning labels on containers and packages must be observed.

3. Installation, operation, maintenance and servicing must only be carried out by suitably trained personnel and in accordance with theinformation given.

4. Normal safety precautions must be taken to avoid the possibility of an accident occurring when operating in conditions of high pressureand/or temperature.

5. Chemicals must be stored away from heat, protected from temperature extremes and powders kept dry. Normal safe handling proceduresmust be used.

6. When disposing of chemicals ensure that no two chemicals are mixed.

Safety advice concerning the use of the equipment described in this manual or any relevant hazard data sheets (where applicable) may beobtained from the Company address on the back cover, together with servicing and spares information.

EN ISO 9001:2000

Cert. No. Q 05907

REGISTERE

D

EN 29001 (ISO 9001)

Lenno, Italy – Cert. No. 9/90A

0255

Stonehouse, U.K.

Page 3: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

1

3.5 Transmitter Sensor Cable Connections(Remote Transmitter) ....................................... 8

3.6 Cable Glands and Conduit Fixings.............................. 93.6.1 Cable Glands .................................................... 93.6.2 Conduit Adapters (N. American - 0.5") ...........103.6.3 Cable Glands (N. American - 0.5") ................ 10

3.7 Input/Output Connections .......................................... 113.7.1 Frequency Outputs ......................................... 113.7.2 PLC Interface ................................................. 123.7.3 Alarm Outputs ................................................133.7.4 Contact Input ..................................................143.7.5 Current Output ................................................153.7.6 Computer Connection ....................................173.7.7 Power Supply Connections ...........................18

APPENDIX A – ENVIRONMENTAL PROTECTION 19APPENDIX B – MAGMASTER BLOCK DIAGRAM 20

Section PageBOOK 3 ELECTRICAL INSTALLATION

Section PageSAFETY MEASURES ......................................................... 11 INTRODUCTION ........................................................ 1

2 GROUNDING ............................................................. 22.1 Full Bore Sensors ............................................ 22.2 Insertion Probe Sensors ................................. 3

3 INSTALLATION .......................................................... 43.1 Connection Requirements .............................. 4

3.1.1 Sensors ................................................ 43.1.2 Transmitters ......................................... 5

3.2 Cable Identification .......................................... 63.3 Cable Preparation ........................................... 63.4 Sensor Terminal Box Connections

(Remote System) ............................................ 7

CONTENTS

Note. Not all versions referred to are available as approved. This book covers general aspects for hazardous andgeneral approved products.

SAFETY MEASURES

Warning.• EXPLOSION HAZARD.

SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.

• EXPLOSION HAZARD.DO NOT REMOVE FUSE OR DISCONNECT POWER LEADS WHILE CIRCUIT IS LIVE.

• THE LOCAL TERMINAL MUST NOT BE USED WHEN THERE IS AN EXPLOSION RISK.

Warning.• Installation and maintenance must only be carried out by suitably trained personnel.

• HAZARDOUS AREA DESIGNATION ON THE EQUIPMENT LABEL MUST BE SUITABLE FOR THE INTENDED DUTYAND LOCATION.

• All relevant sections of this manual must be read before selecting a location.

• Safety requirements of this equipment, any associated equipment, and the local environment must be taken intoconsideration.

• The installation and use of this equipment must be in accordance with relevant national and local standards.

This book describes the electrical installation of theMagMaster Transmitter with full bore and insertion typeelectromagnetic flowmeters.

Attention to the installation procedures, safety measures andgeneral precautions will ensure trouble free operation of thesystem.

1 INTRODUCTION

Page 4: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

2

Fig. 2.1 Metal Pipelines

Sensors with internal grounding electrodes Sensors without grounding electrodes

Fig. 2.2 Plastic Pipelines

2

Supplied Bonding Cables

GroundingRings

Insulating Sleeveand Washer(not provided)

Common Ground(Plant bonding)

>4mm (<10 AWG)Copper Wire

Insulated connecting wire(not included). Must beadequately rated to carrycathodic currents

Gasket Gasket

Grounding Ring

Fig. 2.3 Pipelines with Cathodic Protection

Supplied Bonding Cables

2>4mm (<10 AWG)Copper Wire

Wafer Type Sensors

Common Ground(Plant bonding)

2 GROUNDING

2>4mm (<10 AWG)(Copper Wire)

Common Ground(Plant Bonding)

2

FLOW

Supplied Bonding Cable Grounding RingUpstream FlangePreferably

Common Ground(Plant Bonding)

>4mm (<10 AWG)Copper Wire

2.1 Full Bore Sensors

Caution.• Do NOT rely on the flange bolts or studs for electrical connection.• All earth bonding (grounding) must be in accordance with relevant national and local safety standards.

Page 5: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

3

Fig. 2.4 Ground connection to the Probe Sensor

4mm (<10 AWG)Copper Wireto Common Ground(Plant Bonding)

2

…2 GROUNDING

2.2 Insertion Probe Sensors

Page 6: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

4

3 INSTALLATION

Fig. 3.1 Connection Requirements

Power

Input/Output

Sensor

Probe Head Connections(usually potted)

Power

Input/Output

Sensor ConnectionsSensors are usually supplied with an integral cable and potted head connections. The transmitter end of the cable, the powersupply and any output cables must be prepared and connected as detailed in the relevant parts of this book. If the sensor hasbeen supplied unpotted, connections must also be made to the full-bore sensor terminal box or probe head (Fig. 3.1) and thenpotted on completion – see ENVIRONMENTAL PROTECTION.

3.1 Connection Requirements

3.1.1 Sensors

Caution.• Each connection MUST be insulated from all others; in particular, NO connections must be made to screens or drain

wires except as shown.

• All cable entries must be properly sealed.

• Glands must be appropriate for sealing on the cable size in use.

• Unused cable entries must be plugged.

• Electrical installation and earthing must be in accordance with relevant national and local standards.

• The transmitter and sensor are supplied as a matched system. Check serial numbers to ensure matched pair.

Page 7: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

5

3 INSTALLATION…

Power Supply

Sensor(Remote Only)

N

+

L

ALA

RM

1F

OU

T A

ALA

RM

2F

OU

T B

PLS

OV

PLS

OV

EX

T I/

P+

EX

T I/

P-

TX

- S

IGR

X-

SIG

TX

+ S

IGR

X+

SIG

OV

CIC

2

IC

+C

D1

IC-

CD

2

SIG

GN

D

DS

1

SIG

1

SIG

2

DS

2

Frequency Outputs,Alarm Outputs and

Contact Inputs

Analogue andComputer Outputt

Fig. 3.3 Cable/Conduit Entries

Transmitter Connections

3.1.2 Transmitter

Caution. Unused cable entries must be blanked with the permanent blanking plugs supplied.

Fig. 3.2 Connection Terminal Access

2

2...andSlide Off

1 SlideDown

4

SlackenCaptiveScrews

RemoveProtectionCover

3 Hygienic transmitter

SEAL

Pull Out Slightly...

Page 8: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

6

…3 INSTALLATION

6 5 4 Inches 3 2 1

0

0

50Millimetres100150

Overjacket Armour

Sheath

Ground wire sleeved,to earth post.

(Safety Ground)

Red (CD1)

Yellow (CD2)

Pink (SIG2)

White

Grey

Screen (DS2)

Screen (DS1)Blue (SIG1)

Violet (SIG GND)

Fig. 3.5 Cable Preparation

Fig. 3.4 Cable Identification

3.2 Cable Identification (Fig. 3.4)

3.3 Cable Preparation (Fig. 3.5)

Filler

Red wire (CD1)

Optional Steel Wire Armourand submersible overjacket

Yellow wire (CD2)

Violet wire (SIG GND)

Grey Coaxial Core (SIG2)

Inner Conductor (SIG2)Inner Insulation (Pink)Conductive Layer (Black)Primary Screen (DS2)Insulation (Grey)Foil Secondary Screen

White Coaxial Core (Sig1)

Inner Conductor (Sig 1)Inner Insulation (Blue)Conductive Layer (Black)Primary Screen (DS1)Insulation (White)Foil Secondary Screen

Ground Wire (ESCREEN)

Overall Foil Screen

Page 9: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

7

3 INSTALLATION…

Fig. 3.6 Terminal Box Connections

ESCRNCD1

CD2

SIG GND

DS1

SIG1

SIG2

DS2

Red

Yellow

Screen

Pink

Blue

Screen

Violet

WhiteCoaxial

GreyCoaxial

Ground Wire(sleeved)

3.4 Sensor Terminal Box Connections (Remote System) – Fig. 3.6

Caution.• Remove any exposed black conductive layer from under coaxial screens.• Make connections only as shown.• Sleeve all bare wiring.• Twist RED and YELLOW cores lightly together.• Twist WHITE and GREY coaxial cables lightly together.• Maintain Environmental Protection at all times.• Conduit connections must provide cable entry sealing.

Information.• Refer to ENVIRONMENTAL PROTECTION (APPENDIX A).• Internal appearance of Terminal Box may vary from that shown.• Hazardous area approved flowmeters – see BOOK 1.

Page 10: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

8

Fig. 3.7 Sensor Cable Connections

…3 INSTALLATION

DS

2

IC 2

CD

1

CD

2

SIG

GN

D

DS

1

SIG

1

Grey CoaxPink Inner (SIG 2)Screen (DS 2)

Red(CD 1)

Yellow(CD 2) White Coax

Blue Inner (SIG 1)Screen (DS 1)

DriveConnections

Ground Wire(Safety Earth)

Violet

SignalConnections

3.5 Transmitter Sensor Cable Connections (Remote Transmitter) Fig. 3.7

Caution.• Remove any exposed black conductive layer from the inner insulation of both coaxial cables.• Substitute sensor cable of any kind is not acceptable.• Do not make connections except as shown.• Twist cable pairs together as shown.• Sleeve ALL bare wires.• Sensor cable may only be joined using company supplied junction box - available separately.

Information.• Environmental protection – See APPENDIX• Hazardous area approved flowmeters– See Book 1

Page 11: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

9

B – Gland for other Field Connections C – Gland for Armoured Cables (Transmitter or Sensor)

Fig. 3.8 Cable Glands (IEC Installation Practice)

A – Gland for Sensor Cable (Transmitter or Sensor)

3 INSTALLATION…

'O'-Ring

3.6 Cable Glands and Conduit Fixings

3.6.1 Cable Glands (IEC – 20mm)

'O'-Ring

Page 12: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

10

Fig. 3.9 Conduit Adaptors Fig. 3.10 Cable Glands

…3 INSTALLATION

3.6.2 Conduit Adaptors (N. American – 0.5") – Fig. 3.9

Warning.• Rigid conduit must NOT be fitted to the transmitter.• Transmitter adaptors must incorporate a face seal.• Sensor adaptors must incorporate cable/conduit sealing.• Cable/conduit sealing is advisable on transmitter

adaptors.• Torque settings for the hubs and outer nuts on the

specified adaptors is 20ft. lbs minimum, 25ft. lbs.maximum.

Information.• Suitable adaptors for transmitter (mandatory for FM

installations):APPLETONST-50 PLUS STG-50 or STB-50 PLUS STG-50.Reusable ONLY with replacement ferrule STF-50.O.Z. GEDNEY4Q-50, 4Q50T or 4Q-50TG.

• When fitting conduit adaptor hubs to the transmitter, startwith an outer adaptor and also temporarily fit an adaptorhub at the opposite end, to aid location of the transmittergland plate. Fit and tighten hubs consecutively from initialhub.

3.6.3 Cable Glands (N. American – 0.5") – Fig. 3.10

Warning.• Transmitter glands must be fitted with a face seal.• Torque settings (hubs only) – 20ft. lbs minimum, 25ft.

lbs. maximum.• Outer nuts – hand tight plus a half turn only.

Information.• Suitable Cable Glands:

(mandatory for FM installations):O.Z. GEDNEYSR-50-375 or SR-504APPLETONCG 3150 or CG-3150S (and STG-50 sealing ring).THOMAS & BETTS2521.

• When fitting cable glands to the transmitter, start with anouter gland and also temporarily fit a gland at theopposite end, to aid location of the transmitter glandplate. Fit and tighten glands consecutively from initialgland.

Ferrule

Outer Nut

Seal(Present in O.Z.Gedney Fittings)

AlternativeFace Seal

FaceSeal

Hub

Fittings varyslightly fordifferent makes

Outer Nut

AlternativeFace Seal

FaceSeal

Hub

Illustrationtypical forO.Z.Gedney

Page 13: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

11

Fig. 3.11 Frequency Output Connections

Electromechanical Connections

3 INSTALLATION…

3.7 Input/Output Connections

Caution.• Refer to SPECIFICATION SHEET for Input/Output ratings.• Inductive loads must be suppressed or clamped to limit voltage swings• Capacitive loads must be inrush current limited.• Hazardous area requirements are not considered in the following pages.

3.7.1 Frequency Outputs – Fig. 3.11

Telemetry, Electronic Counters etc.

F O

UT

A

F O

UT

B

PLS

0V

and/or

Reverse FlowCounter/Totaliser

Forward FlowCounter/Totaliser

1 2 3 4 5 6

1 2 3 4 5 6+–

+–

–ve+ve+ve

Screen

F O

UT

A

F O

UT

B

PLS

0V

and/or Reverse FlowCounter/Totaliser

+–

1 2 3 4 5 6

Forward FlowCounter/Totaliser

1 2 3 4 5 6d.c. supply

–ve+ve+ve

Screen

Page 14: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

12

Fig. 3.12 Frequency Output Connections

3.7.2 PLC Interface – Fig. 3.12

Information.Frequency Output illustrated. The same interfacing applies to the alarm outputs.

PLC – Common +ve

PLC – Common -ve

…3 INSTALLATION

F O

UT

A

F O

UT

B

PLS

0V +

–ve+ve+ve

Typically1kΩ 1W

Fwd +

Rev +

PLC

d.c. common

d.c. supply

Screen

F O

UT

A

F O

UT

B

PLS

0V

–ve+ve+ve +

Fwd

Rev

PLC

d.c supplyScreen

Page 15: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

13

Relay and Timers

Fig. 3.13 Alarm Output Connections

Alarms

3 INSTALLATION…

3.7.3 Alarm Outputs – Fig. 3.13

Information.• Inductive loads may be suppressed by diodes (D) – 1N4004 or similar.• Inrush currents are limited to 1 Amp by resistor R – e.g. 27Ω 1W for 24V systems.• Operation of outputs is programmable – see Configuration Manual for details.• Frequency and Alarm outputs share a common return with contact input.• External isolators not normally required, as the pulse, alarm and contact circuits are electrically separated from all other

Magmaster connections.

Information. Bell and Horn shown for example only. Use any suitable alarm device, e.g. lamp, siren, buzzer etc.

Information. Relay and Timer Switch shown for example only. Connect as required.

ALA

RM

1

ALA

RM

2

PLS

0V

–ve+ve+ve

and/orAlarm 2

+–

Alarm 1

d.c.. supply

Relay

Timer Switch

R

Screen

ALA

RM

1

and/or

ALA

RM

2

PLS

0V

Alarm 2

+–d.c. supply

Horn

–ve+ve+ve

Alarm 1

Bell

Screen

Page 16: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

14

Fig. 3.14 Contact Input Connections

Volt-free Contact Voltage Signal or Logic Signal

Open Collector (or Grounded Contact) Using an Alarm for Automatic Range Change

…3 INSTALLATION

3.7.4 Contact Input – Fig. 3.14

EX

T I/

P –

EX

T I/

P +

Switch

Screen

EX

T I/

P –

PLS

0V

Switch

+ 5V

d.c. supply

+ve–ve

Screen

PLS

0V

EX

T I/

P –

EX

T I/

P +

+

Controller withOpen Collector Outpuu

50.047.5

+ve–ve

Screen

EX

T I/

P –

EX

T I/

P +

ALA

RM

2

Page 17: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

15

Information. For MULTIDROP HART installations, remove 'HART Link' and connect HART systems directly to IC2:this allows the analog output function to be retained.

3 INSTALLATION…

3.7.5 Current Output – Fig. 3.15 and 3.16

Information.• Output is fully programmable – see Configuration Manual.• Output is electrically separated from all other MagMaster connections.• External isolators are not normally required and may significantly limit accuracy if used.

IC +

IC –

IC2

–ve

+ve

HART connectionswhere applicable

Alternative

IC-IC+

IC-IC2

Common

+veNormal

HARTLink

Screen

HART

Fig. 3.15 Current Output Connections: Standard

Page 18: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

16

…3 INSTALLATION

…3.7.5 Current Output

IC +

IC –

IC2

–ve+ve

+ve

HART connections(where applicable)

IC-

IC2

Receiver No. 1 - Forward

Receiver No. 2 - Reverse

CommonForward +ve

Reverse +ve + HART

Information. HART option: MULTIDROP Mode cannot be used with this configuration

Fig. 3.16 Current Output Connections: Dual Current Option

Page 19: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

17

Fig. 3.17 RS 422 Connections (Balanced)

3 INSTALLATION…

CO

NN

EC

T T

O

TX -

SIG

TX +

SIG

0VC

RX

- S

IG

RX

+ S

IG

Optional 0VConnection

MagMasterTERMINALS

RS422 ConnectionNAME

APPLE Connector(8 Pin MCC)

TX -SIG RX DATA – 5Tx + SIG RX DATA + 8RX -SIG TX DATA – 3

RX + SIG TX DATA + 60VC SIGNAL GROUND 4

– DCD 7– DTR 1– DSR 2

Linktogether

Linktogether

MagMasterTERMINALS

RS232Name

9 PINPC

Connector

25 PINPC

Connector

Hygienic AdaptorCable

TX-SIG RXD 2 3 RedTX+SIG – – – –RX–SIG TXD 3 2 BlueRX+SIG GND 5 7 Yellow

0VC (Linked) (Linked) (Linked) Green– DTR 4 20 –– DSR 6 6 –– RTS 7 4 –– CTS 8 5 –

CO

NN

EC

T T

O

Linktogether

Linktogether

Linktogether

Linktogether

Linktogether

Linktogether

TX

- S

IG

TX

+ S

IG

0VC

RX

- S

IG

RX

+ S

IG

Link

Fig. 3.18 RS 423 Connections (Single Ended or RS 232)

3.7.6 Computer Connection – Fig. 3.17 and 3.18

Information.• RS422/423 option is electrically isolated from all other MagMaster connections.

Page 20: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

18

Fig. 3.20 Power Supply Connections (D.C. Version Transmitter)

Fig. 3.19 Power Supply Connections (A.C. Version Transmitter)

…3 INSTALLATION

3.7.7 Power Supply Connections – Figs. 3.19 and 3.20

Warning.• DISCONNECT THE SUPPLY FROM ANY CABLES BEING TERMINATED ON THE TRANSMITTER.• Electrical installation and earthing must be in accordance with relevant national and local standards.

Transmitter LabelSUPPLY 95V – 240V ac

=

Kent-Taylor

N L

A.C power via a suitableisolator and fuse

>4mm2

(<10 A.W.G.)Copper

Wire

ExternalInternalNeutral (N/L2) to N

Line (L/L1) to L

Kent-Taylor

– +

D.C. Supply

Transmitter LabelSUPPLY 11 V – 40V dc (Max)

=

>4mm2

(<10 A.W.G.)Copper

Wire

ExternalInternalNegative to –

Positive to +

Page 21: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

19

Warning.• Potting materials are toxic – use suitable safety precautions.

• Read the manufacturers instructions carefully before preparing the potting material.

• The remote sensor terminal box connections must be potted immediately on completion to prevent the ingress ofmoisture. For hazardous area versions – see HAZARDOUS AREA APPROVALS.

• Check all connections before potting – see ELECTRICAL INSTALLATION.

• Do not overfill the terminal box or allow the potting material to come into contact with the ‘O’ ring or groove.

• Do not let potting material enter conduit, if used.

APPENDIX A – ENVIRONMENTAL PROTECTION

Page 22: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

20

Fig

. B1

Mag

Mas

ter

Blo

ck D

iag

ram

APPENDIX B – MAGMASTER BLOCK DIAGRAM

DS

1S

IG1

SIG

2D

S2

SIG

GN

D

CD

1

CD

2

Sen

sor

Tran

smitt

er

DS

1S

IG1

SIG

2D

S2

SIG

GN

D

CD

1C

D2

GN

D

Mea

surin

gS

yste

m

Coi

l Driv

er

Dis

play

Sys

tem

Opt

ioo

Mic

ro-

proc

esso

r

Loca

lP

rogr

amm

ing

Con

nect

or

95 to

240

V a

.c.

or11

to 4

0V d

.c. m

ax.

Ver

sion

IC+

IC–

IC2

4mA

I Out

+ – + –

Dua

l Ana

logu

eO

utpu

t Opt

ion

Ala

rm 2

Ala

rm 1

F O

UT

A

F O

UT

B

PLS

0V

PLS

0V

+5V

EX

T I/

P+

EX

T I/

P–

RS

422

/423

Opt

ion

TX

+ S

IG

TX

– S

IG

RX

+ S

IG

RX

– S

IG

0VC

GN

D

Scr

een

Blu

eP

ink

Scr

een

Vio

let

Red

Yello

w

Pla

in

+

Com

monm

A

mA

++ – –H

art

Opt

ion

+ve

Pla

nt

Page 23: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

PRODUCTS & CUSTOMER SUPPORT

ProductsAutomation Systems

• for the following industries:– Chemical & Pharmaceutical– Food & Beverage– Manufacturing– Metals and Minerals– Oil, Gas & Petrochemical– Pulp and Paper

Drives and Motors• AC and DC Drives, AC and DC Machines, AC motors to 1kV• Drive systems• Force Measurement• Servo Drives

Controllers & Recorders• Single and Multi-loop Controllers• Circular Chart , Strip Chart and Paperless Recorders• Paperless Recorders• Process Indicators

Flexible Automation• Industrial Robots and Robot Systems

Flow Measurement• Electromagnetic Flowmeters• Mass Flow Meters• Turbine Flowmeters• Flow Elements

Marine Systems & Turbochargers• Electrical Systems• Marine Equipment• Offshore Retrofit and Refurbishment

Process Analytics• Process Gas Analysis• Systems Integration

Transmitters• Pressure• Temperature• Level• Interface Modules

Valves, Actuators and Positioners• Control Valves• Actuators• Positioners

Water, Gas & Industrial Analytics Instrumentation• pH, conductivity, and dissolved oxygen transmitters and

sensors• ammonia, nitrate, phosphate, silica, sodium, chloride,

fluoride, dissolved oxygen and hydrazine analyzers.• Zirconia oxygen analyzers, katharometers, hydrogen purity

and purge-gas monitors, thermal conductivity.

Customer Support

We provide a comprehensive after sales service via aWorldwide Service Organization. Contact one of the followingoffices for details on your nearest Service and Repair Centre.

United KingdomABB LimitedTel: +44 (0)1453 826661Fax: +44 (0)1453 829671

United States of AmericaABB Inc.Tel: +1 (0) 755 883 4366Fax: +1 (0) 755 883 4373

Client Warranty

Prior to installation, the equipment referred to in this manualmust be stored in a clean, dry environment, in accordance withthe Company's published specification.

Periodic checks must be made on the equipment's condition. Inthe event of a failure under warranty, the followingdocumentation must be provided as substantiation:

1. A listing evidencing process operation and alarm logs at timeof failure.

2. Copies of all storage, installation, operating and maintenancerecords relating to the alleged faulty unit.

Page 24: Instruction Manual – Electromagnetic Flowmeters MagMaster · PDF fileSensors with internal grounding electrodes Sensors without grounding electrodes ... gland plate. Fit and tighten

IM/M

M/B

K3

Issu

e 6

ABB LimitedOldends Lane, StonehouseGloucestershireGL10 3TAUKTel: +44 (0)1453 826661Fax: +44 (0)1453 829671

ABB Inc.125 E. County Line RoadWarminsterPA 18974USATel: +1 215 674 6000Fax: +1 215 674 7183