Page 1: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

17 Sept 2015

Integrated Architecture Builder,

SLC-to-CompactLogix / ControlLogix

Migration

Hands-On Lab

For support or to comment, send e-mail to [email protected]

Page 2: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save
Page 3: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

3 of 37

Integrated Architecture Builder,

SLC-to-CompactLogix / ControlLogix Migration

Contents

Before you begin ......................................................................................................................................... 4

About This Hands-On Lab............................................................................................................................. 4

Lab Materials ................................................................................................................................................. 4

Document Conventions ................................................................................................................................. 4

1: Open a New IAB Project (Workspace) .................................................................................................. 5

2: Migrate and Retain SLC 500 I/O ............................................................................................................. 9

2.1 Retain SLC 500 I/O with CompactLogix ................................................................................................. 9

2.2 Retain SLC 500 I/O with ControlLogix .................................................................................................. 14

2.3 Retain Remote SLC 500 I/O ................................................................................................................. 18

3: Migrate and Replace SLC I/O ............................................................................................................... 24

3.1 Replace SLC 500 I/O with CompactLogix............................................................................................. 24

Chassis 1:.................................................................................................................................................... 24

Chassis 2 :................................................................................................................................................... 28

2.1 Replace SLC 500 Remote I/O with CompactLogix ............................................................................... 30

Chassis 3:.................................................................................................................................................... 30

Page 4: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

4 of 37

Before you begin

About This Hands-On Lab

IAB includes a wizard that enables you to help a customer migrate an existing SLC configuration to a

CompactLogix / ControlLogix controller-based configuration. You specify the SLC configuration

graphically by placing SLC modules in SLC chassis. IAB automatically selects equivalent CompactLogix /

ControlLogix controllers and I/O modules to duplicate the original configuration. You will have options for

chassis size and whether to retain or replace the SLC I/O modules with CompactLogix / ControlLogix.

This lab shows how to use the IAB SLC Migration functionality.

Lab Materials

You need IAB v 9.3 or higher to complete this lab exercise.

Document Conventions

Throughout this manual, we use the following conventions to guide you through the lab materials:

Style or Symbol Indicates

Words in Bold Italics An item or button that you must click on or a menu name from which you must choose an option or command. This will be the actual name of an item that you see on your screen or in an example.

Words or phrases ‘in italics and single

quotes’

An item that you must type in the specified field. This information must be supplied based on the application (e.g., a variable). Note: When you type the text in the field, remember that you only need to type the word(s) within the quotes.

Supplemental information appears in gray boxes. These items are not required to complete the lab exercises, but they may help you gain a better understanding of how IAB works & how to efficiently use it.

Note: If the mouse button is not specified in the text, use the left button.

Text in a gray box

Page 5: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

5 of 37

1: Open a New IAB Project (Workspace)

1. If IAB is already running, skip to step 2.

If IAB is not already running, double click on the Integrated Architecture Builder icon on the

computer desktop to launch IAB.

The IAB opening dialog appears. Click New project then skip to step 3.

Page 6: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

6 of 37

2. If IAB is already running, save your work if a project is open, then click the New button.

The Create a New Workspace dialog appears.

3. In the Create a New Workspace dialog, under Migration Workspaces, click SLC 500 Migration

Wizard. Type the name ‘SLC Migration Wizard’ in the Workspace Name text box and click OK.

Page 7: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

7 of 37

IAB creates a new project workspace and opens the SLC Migration Chassis Selection dialog.

4. Click the Add Chassis button. IAB opens the Add Chassis dialog. Name this chassis

‘SLC_With_CompactLogix’.and click OK.

Page 8: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

8 of 37

5. IAB opens the SLC Migration Module Selection dialog, in which you will make the conversion

selections for this chassis. Notice the different areas of this window.

Page 9: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

9 of 37

2: Migrate and Retain SLC 500 I/O

For this exercise, we will migrate a SLC 500 configuration that has three chassis:

Chassis 1 – 2 banks

o Bank 1 – 4-slot chassis with 1747-L531 processor, 1746-P3

o Bank 2 - 7-slot chassis with 1746-P2, three 1746-IA8, two 1746-IB16

Chassis 2 – 7-slot chassis, 1746-P6 power supply, 1747-L543 processor, two 1746-OV32,

three 1746-OB32, one 1746-OBP16

Chassis 3 – 7-slot chassis with 1746-P3 power supply, 1746-ACN15 adapter, two 1746-IB16,

one 1746-IV32, one 1746-OB32E

2.1 Retain SLC 500 I/O with CompactLogix

Chassis 1:

6. We will choose the Retain With CompactLogix option for SLC I/O in this example. Select the

chassis size as 4 and choose the 1746-P3 Power Supply

7. Check the bank 2 checkbox, set the bank 2 chassis size to 7, and select 1746-P2 as the Power

Supply.

Page 10: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

10 of 37

The wizard adds one additional bank to the SLC chassis.

8. From the module list, drag a 1747-L531 processor module to slot 1 of the Bank 1 chassis.

Page 11: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

11 of 37

9. The SLC Migration Conflict Resolution Dialog appears. A conflict resolution dialog appears when you

must make a decision about the migration. The information in the dialog is specific to the action you

are performing.

In this case, you must select the CompactLogix processor that you wish to use in this migration.

Scroll in the processor window to see the options. Notice that for SLC 500 migration, IAB

recommends CompactLogix L3 processors. Select the 1769-L33ER CompactLogix 5370 processor

and click OK.

AB adds processors to both the SLC chassis, the replacement CompactLogix chassis, and it adds a

1747-AENTR EtherNet/IP adapter to the migrated SLC chassis.

Page 12: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

12 of 37

10. Next, drag three 1746-IA8 Digital I/O modules to the SLC chassis. Because we are retaining the

SLC I/O, IAB duplicates these modules in the migrated chassis.

Page 13: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

13 of 37

11. Finish by adding the two 1746-IB16 modules to the Bank 2 chassis. There are no empty slots in the

first bank, so the modules are placed in the second bank. Again IAB duplicates the modules in the

migrated chassis. Use the scroll bars to view all the banks in the SLC chassis.

Click OK to finish configuring this chassis. IAB closes the Module Selection window and returns to

Chassis Selection window.

Page 14: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

14 of 37

2.2 Retain SLC 500 I/O with ControlLogix

Chassis 2 :

12. Click the Add Chassis button. Name this second chassis ‘SLC_With_ControlLogix’.and click OK.

13. Now we will choose the Retain With ControlLogix option for SLC I/O in this example, select the

chassis size as 7 and choose the 1746-P6 Power Supply,

.

Page 15: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

15 of 37

Notice the ControlLogix Chassis in the migration area.

14. From the module list, drag a 1747-L543 processor module to slot 1 of the SLC chassis.

Page 16: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

16 of 37

15. The SLC Migration Conflict Resolution Dialog appears. A conflict resolution dialog appears when you

must make a decision about the migration. The information in the dialog is specific to the action you

are performing.

In this case, you must select the ControlLogix processor that you wish to use in this migration and a

ControlLogix Ethernet adapter for communicating the migration chassis. Scroll in the Ethernet

adapter window to see the options. Notice that IAB recommends ControlLogix L7 processors as the

nearest equivalents to SLC 500 processors. Select the 1756-L74 processor and the1756-EN2T

adapter and click OK.

IAB adds processors to both the SLC chassis and the replacement ControlLogix chassis, and adds a

EtherNet/IP adapter 1747-AENTR to the migrated SLC and 1756-EN2T to the replacement

ControlLogix chassis.

Page 17: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

17 of 37

16. Next, drag two 1746-OV32, three 1746-OB32 and one 1746-OBP16 I/O modules to the SLC

chassis. Because we are retaining the SLC I/O, IAB duplicates these modules in the migrated

chassis.

Click OK to finish configuring this chassis. IAB closes the Module Selection window and returns to

the Chassis Selection window.

Page 18: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

18 of 37

2.3 Retain Remote SLC 500 I/O

Chassis 3:

17. In the Chassis Selection dialog click the Add Chassis button. Name this chassis

‘SLC_Remote’.and click OK.

18. Select the chassis size as 7 and a 1746-P3 power supply. We will also choose Retain with

CompactLogix for SLC I/O.

Page 19: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

19 of 37

19. Drag a 1747-ACN15 adapter module to slot 0 of the SLC chassis. Note that IAB replaces the 1747-

ACN15 adapter with a 1747-AENTR EtherNet/IP adapter in the migrated SLC remote I/O chassis.

Page 20: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

20 of 37

20. Drag the following Digital I/O modules to the SLC chassis: two 1746-IB16, one 1746-IV32 and one

1746-OB32E. IAB duplicates the modules in the migrated chassis. Click OK.

Page 21: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

21 of 37

21. In the SLC Migration Chassis Selection dialog, click the Generate Hardware button to close the

migration wizard and create the wizard-defined CompactLogix and ControlLogix configuration in IAB.

Click on the Hardware tab and click on the SLC_with_CompactLogix chassis to see the hardware.

You can move your cursor over each module in the chassis to display the catalog number in the tool

tip that appears.

Note that this chassis contains all the SLC I/O from the local rack that we replaced. A 1747-AENTR

module has been added to connect this I/O remotely over EtherNet/IP to the CompactLogix

controller that is replacing the SLC processor.

Page 22: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

22 of 37

22. In the hardware tree, click the SLC_Migration.1_ SLC_with_CompactLogix.CMX chassis. This

CompactLogix chassis contains the CompactLogix 5370 L33ER processor that is the replacement

for the SLC processor.

23. In the hardware tree, click the SLC_Migration.1_SLC_Remote chassis. This is the SLC remote I/O

chassis. Notice that the1747-ACN15 ControlNet module in the original configuration has been

replaced with a 1747-AENTR EtherNet/IP module.

In the same way, you can click the other migrated chassis with ControlLogix to see how it has been

created.

Page 23: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

23 of 37

24. Click the Project BOM button to view the bill of materials for this project. Click Yes when asked if

you want to save changes to the project. In the BOM, notice that only newly required hardware is

listed. Existing chassis and modules that have been retained are not listed in the BOM. Close the

BOM.

Page 24: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

24 of 37

3: Migrate and Replace SLC I/O

Suppose you would like to replace the original SLC I/O in the local SLC processor chassis instead of

retaining it. The SLC migration wizard can help select appropriate replacement modules.

For this exercise, we will replace above three original SLC I/O to CompactLogix and ControlLogix.

3.1 Replace SLC 500 I/O with CompactLogix

Chassis 1:

25. Click the Wizard View tab and double click the SLC_Migration.1 item under SLC Migration Wizard

in the tree. In the SLC Migration Chassis Selection dialog, select chassis

SLC_With_CompactLogix and click the Edit Chassis button.

Page 25: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

25 of 37

26. In the SLC Migration Module Selection dialog, select Replace with CompactLogix option in the

SLC I/O dropdown.

A Conflict Resolution dialog appears. Select the 1769-L33ER processor again and click OK.

IAB selects equivalent Compact I/O modules for the original SLC I/O and populates the

CompactLogix chassis. The original SLC chassis is no longer part of the migrated solution.

Page 26: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

26 of 37

27. Next, drag two 1746-IA4 modules to the SLC chassis. Both modules are added to the second bank.

IAB selects equivalent Compact I/O modules for the original SLC I/O and these modules are added

in the CompactLogix chassis.

Page 27: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

27 of 37

28. Finish by adding the two 1746-IM16 modules to the second bank of the SLC chassis. IAB places

four 1769-IM12 Compact I/O modules in the migrated chassis.

Click OK to finish configuring this chassis. IAB closes the Module Selection window and returns to

the Chassis Selection window.

Page 28: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

28 of 37

Chassis 2 :

29. Select SLC_With_ControlLogix and click Edit Chassis.

30. In the SLC Migration Module Selection dialog, select Replace with ControlLogix in the SLC I/O

dropdown.

Page 29: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

29 of 37

A Conflict Resolution dialog appears. Select the 1756-L74 processor again and click OK.

IAB selects equivalent ControlLogix I/O modules for the original SLC I/O and populates the

ControlLogix chassis. The original SLC chassis is no longer part of the migrated solution.

31. Click OK to finish configuring this chassis. IAB closes the Module Selection window and returns to

the Chassis Selection window.

Page 30: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

30 of 37

2.1 Replace SLC 500 Remote I/O with CompactLogix

Chassis 3:

32. Select SLC_Remote and click Edit Chassis.

33. Select Replace with CompactLogix in the SLC I/O dropdown.

IAB displays a message informing you that there is no exact replacement in 1769 Compact I/O for

the 1747-ACN15 module, and advising you to contact a Rockwell Automation representative for

assistance. Click OK.

Page 31: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

31 of 37

A similar message appears for the 1746-OB32E module. Click OK.;

IAB creates a CompactLogix chassis with replacement modules, except for the two modules for

which there was no exact replacement. Click OK to accept this migration.

If there is no exact replacement for an SLC I/O module, IAB displays a message to inform

you of the fact, but otherwise takes no action. You will have to proceed on your own to

migrate those modules for which an exact replacement is not available.

Page 32: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

32 of 37

34. Click the Generate Hardware button. IAB asks you to confirm that you want to regenerate the

hardware. Click Yes.

35. Click the Hardware tab and view the chassis the migration wizard has created.

SLC with CompactLogix controller

Page 33: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

33 of 37

SLC with ControlLogix Controller

SLC Remote Chassis

Page 34: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

34 of 37

36. One way you might deal with the modules in the second chassis is to move them into the controller

chassis. You can add empty slots to the controller chassis and move the modules from the second

chassis into the empty slots.

In the controller chassis view, right click on the power supply and select Configure 1769 Chassis.

In the second bank add two slots to the left side of the power supply and one slot to the right side.

Click OK to make the changes.

Page 35: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

35 of 37

37. In the Hardware tree, expand both chassis. Drag each module from the third chassis into an empty

slot in the second bank of first chassis.

Page 36: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015

36 of 37

When finished, you will have a single CompactLogix chassis with all the migrated I/O modules.

You can now delete the third chassis, which is now empty.

38. The SLC Migration Wizard does not automatically connect migrated chassis to any network. To

establish network connections, you will have to go to each migrated chassis and make the

connection through the right-click menu.

Right click on the processor in the CompactLogix chassis and select Connect to EtherNet/IP

network > Connect ‘Port 1’ to a new EtherNet/IP network > Standalone Device Level Ring.

Click OK four times to accept the network name, select copper media, accept the IP address, and

acknowledge the default processor for the network.

Page 37: Integrated Architecture Builder, SLC-to-CompactLogix ... · IAB Hands-On Lab – SLC-to CompactLogix / ControlLogix Migration 17 Sept 2015 6 of 37 2. If IAB is already running, save

IAB Hands-On Lab – SLC-to-CompactLogix / ControlLogix Migration 17 Sept 2015

37 of 37

IAB makes the network connection. Go to the Networks tab and see that the processor has been

connected to the new network.

39. Save the IAB project.

This concludes the SLC 500 to CompactLogix Migration Wizard lab exercise.