BILL OF MATERIALS Sl.No. Description 1 3 x 1010 KVA DG SYNCHRONIZING PANEL : INCOMING 3 nos. 250A Neutral Contractor 1 Set of Control MCB for Control Circuit a) AMF Start/Stop b) Synchronization and Load Management Automatic base load c) Automatic Start/Stop Sequencing 1 lot 1600A TPN EC grade Al.Bus Bar Protection Relays: 1 No. Master Trip Relay 1 No. Reverse Power Reley Supply of3 Phase and Neutral 415V 4 wire free standing dloor mounted DG panel made out of 2mm thick CRCA sheet for main frame and 1.6mm thick partition after seven tank process abd painting with powder coating. The Panel shall consist of suitable rating TPN Al.Bus Bar ( at the rating of 0.8A/Sqmm supported with DMC/SMC barriers and colour coaded with Heat shrinkable PVC sleeves. All meter shall be 96x96 mm. Panel shall be mounted on U-channels including supply and mounting the same. 3 Nos. 1600A, 3P, 50KA, EDO ACB with built in OC,SC, EF release Digital Indicating Instruments Frequency Meter, MDM, KWH Meter with sealing facility 1 set LED Indicating Lamps for 3Ph, Trip, Load on DG, DG running, DG off, DC On etc 1 set Push buttons for Engine start/stop, Emergency Stop, Ack & Reset 1 set of 20A/24V DC Microprocessor based Baterry Charger with built in protection & DC Voltmeter & Ammeter Generator Controller & Monitering Relay - 1 no.AMF, Auto Synchronizing & Auto-Load Sharing Relay With built in complete engine, generator and mains Protection and controller into one unit d) Over/Under Voltage, over/under Frequency, overload /Reverse Power, over current, load imbalance Protection with can bus communication

Upload: vandang

Post on 27-May-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

BILL OF MATERIALS

Sl.No. Description Unit Qty1 3 x 1010 KVA DG SYNCHRONIZING PANEL : No. 1

INCOMING

3 nos. 250A Neutral Contractor

1 Set of Control MCB for Control Circuit

a) AMF Start/Stop

c) Automatic Start/Stop Sequencing

1 lot 1600A TPN EC grade Al.Bus BarProtection Relays:1 No. Master Trip Relay1 No. Reverse Power Reley

Supply of3 Phase and Neutral 415V 4 wire free standing dloor mounted DG panel made out of 2mm thick CRCA sheet for main frame and 1.6mm thick partition after seven tank process abd painting with powder coating. The Panel shall consist of suitable rating TPN Al.Bus Bar ( at the rating of 0.8A/Sqmm supported with DMC/SMC barriers and colour coaded with Heat shrinkable PVC sleeves. All meter shall be 96x96 mm. Panel shall be mounted on U-channels including supply and mounting the same.

3 Nos. 1600A, 3P, 50KA, EDO ACB with built in OC,SC, EF release

Digital Indicating Instruments Frequency Meter, MDM, KWH Meter with sealing facility

1 set LED Indicating Lamps for 3Ph, Trip, Load on DG, DG running, DG off, DC On etc

1 set Push buttons for Engine start/stop, Emergency Stop, Ack & Reset1 set of 20A/24V DC Microprocessor based Baterry Charger with built in protection & DC Voltmeter & Ammeter

Generator Controller & Monitering Relay - 1 no.AMF, Auto Synchronizing & Auto-Load Sharing Relay With built in complete engine, generator and mains Protection and controller into one unit

b) Synchronization and Load Management Automatic base load

d) Over/Under Voltage, over/under Frequency, overload /Reverse Power, over current, load imbalance Protection with can bus communication

1 No. Restricted Earth Fault Relay1 No. Earth Leakage Relay with CBCT1600/5 CL-1, 15VA Tape wound ring type CTs for metering

As soon as the mains supply goes off, the DG set Should Auto Start and take the full load prescribed Within 15 seconds including LDSSMonitoring and data logging the all DG parameters,

OUTGOING

Digital Indicating Instruments Frequency Meter, MDM1 set LED Indicating Lamps for 3Ph ACB On/Off/Trip1 Set of Control MCB for Control CircuitAuto / Manual selector switch CAM type1600/5 CL-1, 15VA Tape wound ring type CTs for metering5000A common Al.Bus BarBUS DUCT

Mtr 100

2 11 KV DG DISTRIBUTION PANEL No. 1

INCOMER - 3 Nos.

1600/5 CL-5P 10, 15VA Tape wound ring type CTs for Protection24V DC Micro PLC & SCADA System PLC Control System:

MMI-graphical display of DG Set status, A, KW, RPM, TEMP & all alarms etc.,

3 Nos. 1600A, 4P, 50KA, EDO ACB with built in OC,SC, EF release

Supply & fabrication of following 415V 1600A TPN non phase seggregated Bus duct made out of 1.6/2mm thick MS sheet with painting after Seven tank process and consisting of 1600A TPN Aluminium Busbars (@0.8A/sq.mm) including flexible braided connections at the ends to facilitate connections and running 2runs of 50x6mm hot dip galvanised GI strip along the Bus duct complete as required. App

Design, manufacturing, testing at works, supply and delivery, installation, testing & commissioning of Relay,Metering and Control panel.

800 A, 3P Vacuum circuit breaker of (350 MVA) 26.2 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation horizontal drawout type having double isolation ferruling top.

15 VA burden for protection (class 5P 10).15 VA burden for instrumentation (accuracy class 1.0).

Following protection shall be provided:

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthyR,Y,B - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter / Voltmeter / Frequency Meter.

HT Danger Plate.(as per IS specification)

Manually and motor operated, spring charged ( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indication

800 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 100/5A - 3 Nos.

Voltage Transformer with 3 numbers 1 phase, 3 limbs connected in star, dual class, 11KV/√3 /110V/√3 with drawable type with automatic shutters 100 VA burden on bus side and line side with primary & secondary fuses and isolating plugs. (Confirming to relevant standards)

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., 51,51N Restricted Earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay (95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Digital Energy Meter & Multi Data Meter (EM 6400 or equivalent)Necessary D.C. supply healthy indication lamp (White Colour), switch with alarm.Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.Terminal boxes with single gland trifucating cable box suitable (Raychem make) for 11 KV Aluminium XLPE (E) cable of size 3 x 300 Sq. mm. for incoming breaker.

OUTGOING - 1 No.

15 VA burden for protection (class 5P 10).15 VA burden for instrumentation (accuracy class 1.0).Following protection shall be provided:

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthyR,Y,B - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter

1 Run of 50 X 6 mm earth bus of tinned copper shall be provided for the full length of the panel.

800 A, 3P Vacuum circuit breaker of (350 MVA) 18.4 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation ferruling top

Manually and motor operated, spring charged( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indica

800 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 200/5-5A (seperate core for metering and separate core for protection).

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., (NI41) of ABB or 51,51N approved equivalent,Hi set) Restricted earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay ( 95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.

HT Danger Plate.(as per IS specification)

3 11 KV DG CHANGE OVER PANEL No. 1INCOMER - 2 Nos.

15 VA burden for protection (class 5P 10).

Following protection shall be provided:

Terminal boxes with single gland trifucating cable box suitable (Raychem make) for 11 KV Aluminium XLPE (E) cable of size 3 x 400 Sq. mm. for outgoing breaker.

1 Run of 50 X 6 mm earth bus shall be provided for the full length of the panel.HT Panel switchboard complete with all interconnections, labels, wiring etc, complete as described above in A , B , & C items and as per specifications & SLD.

2 NOS 800 A, 3P Vacuum circuit breaker of (350 MVA) 26.2 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation ferruling top

Manually and motor operated, spring charged ( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indication

630 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 200/5-5A (seperate core for metering and separate core for protection).

15 VA burden for instrumentation (accuracy class 1.0).Voltage Transformer with 3 numbers 1 phase, 3 limbs connected in star, dual class, 11KV/√3 /110V/√3 with drawable type with automatic shutters 100 VA burden on bus side and line side with primary & secondary fuses and isolating plugs. (Confirming to relevant standards)

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., (NI41) of ABB or 51,51N approved equivalent,Hi set) Restricted Earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay (95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthywhite - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter / VoltmeterMulti Data Meter EM 6400 or equivalent

HT Danger Plate.(as per IS specification)

OUTGOING- 1 No.

15 VA burden for protection (class 5P 10).15 VA burden for instrumentation (accuracy class 1.0).Following protection shall be provided:

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Necessary D.C. supply healthy indication lamp (White Colour), switch with alarm.Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.Terminal boxes with single gland trifucating cable box suitable for 11 KV Aluminium XLPE (E) cable of size 3 x 400 Sq. mm. for incoming breaker.

1 Run of 50 X 6 mm ALUMINIUM earth bus shall be provided for the full length of the panel.800 amp air insulated but encapsulated,PVC insulated copper bus bars.

800 A, 3P Vacuum circuit breaker of (350 MVA) 26.2 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation ferruling top

Manually and motor operated, spring charged( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indica

800 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 80/5-5A (seperate core for metering and separate core for protection).

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthywhite - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter

HT Danger Plate.(as per IS specification)

4 Mains HT VCB Panel No. 1INCOMER - 1 No.

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., approved Hi set Restricted earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay ( 95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.Terminal boxes with single gland trifucating cable box suitable (Raychem make) for 11 KV Aluminium XLPE (E) cable of size 3 x 400 Sq. mm. for outgoing breaker.

1 Run of 50 X 6 mm earth bus shall be provided for the full length of the panel.HT Panel switchboard complete with all interconnections, labels, wiring etc, complete as described above in A , B , & C items and as per specifications and Single Line Diagram VKC/KDG/1.

800 A, 3P Vacuum circuit breaker of (350 MVA) 26.2 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation ferruling top

Manually and motor operated, spring charged ( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indication

15 VA burden for protection (class 5P 10).

Following protection shall be provided:

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthywhite - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter / VoltmeterDigital Energy Monitor type EM 6400 or equivalent

Sub Trivector Meter - 3 Ph, 4 W TVM 110 V, 5 A, CL-0.5, BM

HT Danger Plate.(as per IS specification)

800 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 200/5-5A (seperate core for metering and separate core for protection).

15 VA burden for instrumentation (accuracy class 0.5).Voltage Transformer with 3 numbers 1 phase, 3 limbs connected in star, dual class, 11KV/√3 /110V/√3 with drawable type with automatic shutters 100 VA burden on bus side and line side with primary & secondary fuses and isolating plugs. (Confirming to relevant standards)

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., (NI41) of ABB or 51,51N approved equivalent,Hi set) Restricted Earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay (95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Necessary D.C. supply healthy indication lamp (White Colour), switch with alarm.Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.Terminal boxes with single gland trifucating cable box suitable for 11 KV Aluminium XLPE (E) cable of size 3 x 400 Sq. mm. for incoming breaker.

OUTGOING FEEDERS - 2 Nos.

15 VA burden for protection (class 5P 10).15 VA burden for instrumentation (accuracy class 1.0).Following protection shall be provided:

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthywhite - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter

1 Run of 50 X 6 mm ALUMINIUM earth bus shall be provided for the full length of the panel.800 amp air insulated but encapsulated,PVC insulated copper bus bars.

800 A, 3P Vacuum circuit breaker of (350 MVA) 26.2 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation ferruling top

Manually and motor operated, spring charged( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indica

800 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 200/5-5A (seperate core for metering and separate core for protection).

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., approved Hi set Restricted earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay ( 95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.

HT Danger Plate.(as per IS specification)

5 HT BESCOM METERING CUBICAL (3000 KVA) No. 1INCOMER - 1 No.

15 VA burden for protection (class 5P 10).

Following protection shall be provided:

Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.

1 Run of 50 X 6 mm earth bus shall be provided for the full length of the panel.HT Panel switchboard complete with all interconnections, labels, wiring etc, complete as described above in A , B , & C items and as per specifications and Single Line Diagram VKC/KDG/1.

800 A, 3P Vacuum circuit breaker of (350 MVA) 26.2 KA ruputuring capacity at 11 KV rated, totally enclosed,air insulated metal clad housing, floor mounting, horizantal isolation,vermin proof,fully interlocked horizontal drawout type having double isolation ferruling top

Manually and motor operated, spring charged ( release closing mechanism) trip free type,triple pole truck mounted draw out, vacuum circuit breaker, incorporating mechanical as well as electrical ON/OFF indication. Spring charge/discharge mechanical indication

800 amp air insulated but encapsulated,PVC insulated copper bus bars.C.T. chamber with double wound, C.T.'s 200/5-5A (seperate core for metering and separate core for protection).

15 VA burden for instrumentation (accuracy class 0.5).Voltage Transformer with 3 numbers 1 phase, 3 limbs connected in star, dual class, 11KV/√3 /110V/√3 with drawable type with automatic shutters 100 VA burden on bus side and line side with primary & secondary fuses and isolating plugs. (Confirming to relevant standards)

3 nos.outer elements for over current and 1no. middle earth-fault element with IDMT self power Relay with shunt trip on 30/24 Volts, D.C., (NI41) of ABB or 51,51N approved equivalent,Hi set) Restricted Earth fault relay.

Anti pumping relay (94) Master trip relay (86), Trip ckt supervision relay (95)All wiring necessary for the above including inter-connections. The size of the conductor should not be less than 2.5 sq. mm. Copper wire where required.

Red - Breaker close (ON)Green - Breaker open (OFF)Amber - auto tripClear - trip circuit healthywhite - 3 nos. one per phaseBlue spring chargedThe following meters are to be provided :Digital Ammeter / VoltmeterTrivector Meter CL-0.5, 3Ph, 4W, 110V, BM

HT Danger Plate.(as per IS specification)

INTERNAL ELECTRIFICATION6

1.8.2) 25 mm Mtr 3001.8.3) 32 mm Mtr 50

7

2.5.3) 2.5 sqmm Mtr. 12002.5.4) 4 sqmm Mtr. 200.00

8

3.7.1) 6 Amps one way. Each 103.7.3) 6 Amps 3 way Socket. Each 33.7.9) 32 Amps DP switch. Each 4

Test terminal block, fuses/2A SPMCB , circuit labels,set of phase, indication lamps etc. as per standard practise as under.

Necessary D.C. supply healthy indication lamp (White Colour), switch with alarm.Control :- T-N-C (Trip, Neutral. Close) breaker control switch with indication arrangement.Terminal boxes with single gland trifucating cable box suitable for 11 KV Aluminium XLPE (E) cable of size 3 x 400 Sq. mm. for incoming breaker.

1 Run of 50 X 6 mm ALUMINIUM earth bus shall be provided for the full length of the panel.

Supplying and fixing of PVC casing and capping on the wall or ceiling using necessary materials like bends, screws at an interval of 300mm …. Etc as required.

Wiring for lighting/power circuit using one of FR PVC insulated 1100V grade, multistrand Copper conductor single core cable in open or concealed system of wiring with specified IS-694:1990 & confirming to the attached GTP of GROUP -A.

Supplying and fixing of modular switch/ Socket/stepped electronic fan regulator/ dimmer/telephone socket etc on existing modular switch plate as per IS 3854 and IS 1293

9

3.4.2) 4-5 Way Each 43.4.3) 6-8 Way Each 6

10

3.6.2) 4 Module. Each 43.6.3) 6 Module. Each 6

11

4.8.3 ) 2 x 4ft x 90 Watts Each 14

12

4.16.1) 250W Each 4

Supplying and surface/flush mounting unbreakable PVC modular box suitable for mounting modular switch plates. The box should be firmly surface/flush mounted after due groove cutting in Brick/C.C wall, fixing including necessary rawl plugs, Machine/NF screws etc., complete.

Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box.

Supplying industrial box type suitable for 90W T5 single / twin Lamp along with stove enameled white reflector & suspension mounted luminaire & optical reflector. Prewired with HF electronic Ballast, push fit type lamp holders & main connectors. Channel cover shall be made of CRCA MS Sheet and finishing is done with stove enameled white with end caps made of engineering plastic.

Supplying High pressure Sodium Vapour street light luminaire suitable for use with high pressure Sodium Vapour lamp with integrated control gear & gray color power coated. The fitting shall be non corrosive pressure die cast aluminium housing with high purity anodized aluminium reflector with EPDM Gaskets suitable for Outer Dia of pole 40mm - 60mm. Cable Entry through a cable gland with toggle clips. IP65 Protection for both optical & Electrical Compartment. Bottom cover may be with Poly carbonate/tempered/ toughened glass. Luminaire efficiency should be >60% & ambient temperature > 35 deg C. High Intensity Discharge Electro Magnetic Ballast with Copper winding of Orthocyclic winding coil. Class H insulated dual coated copper wire. Compliance to IEC 61347-2-9 Safety & IEC 60923 - Performance. Winding Temperate for HID Ballast tw = 130 deg C & temperature rise ∆T = 70 deg C. Luminaire shall be suitable to operate on 230/250 Volts finish including wiring, suitable to operate on 230/250 Volts 50 Hz AC supply including heavy duty copper ballast, ignitor, condenser. SS Toggles for opening front hingeable glass.

13

6.16.3 b) 8Way SP &N Each 1

14

6.15.1) 5 to 32 A SP Each 66.15.5) 5 to 32 A DP Each 1

15 All Statuatory Approvals including BESCOM LS 1Total

Supplying and fixing regular MCB distribution boards on wall / wood board / flush mounting using required clamps, bolts, nuts etc., with provision for fixing suitable type capacity MCB's single phase / 3 phase / single door with powder coated painting. Made out of 14 SWG MS enclosure.

Supplying and fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve , indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required.

Supply Rate

Erection Rate

Supply Amount

Erection Amount