INTRODUCTION
Central Cables Berhad (CCB) was incorporated in Malaysia as a private limited com-
pany on 6 June 1967 under the name of Syarikat Central Cables Sendirian Berhad. It was
subsequently converted to a Public Limited Company on 25th September 1980 under the
present name “Central Cable Berhad”. The factory is situated in Batu Berendam, Melaka,
Malaysia, with a land area of 2.7 hectares.
We specializes in the manufacture of power cables of copper and aluminium from 500V to
33kV.
Central Cables Berhad
Content Page
II
III-V
6-14
15-16
30-39
40-55
56-58
59-70
71-72
73-84
85-96
97-99
100-105
106
Central Cables Berhad (CCB) Introduction
XLPE Introduction
XLPE Insulated Unarmoured Sheathed Cable For Voltages 1kV IEC 60502-1
XLPE Insulated Unarmoured Sheathed Cable With Cu Tape Screened For Voltages 1kV IEC 60502-1
XLPE Insulated Armoured Sheathed Cable For Voltages 1kV and 3.3kV to BS 5467
Single Core - XLPE Insulated Unarmoured Sheathed Cable For Voltages 6.6kV up toAnd Including 33kV to IEC 60502-2
Single Core - XLPE Insulated Unarmoured Double Sheathed Cable For Voltages 11kV and 22kV to IEC 60502-2
Three Core - XLPE Insulated Unarmoured Sheathed Cable For Voltages 6.6kV up to And Including 33kV to IEC 60502-2
Three Core - XLPE Insulated Unarmoured Double Sheathed Cable For Voltages 11kV to IEC 60502-2
Single Core - XLPE Insulated Armoured Sheathed Cable For Voltages 6.6kV up to And Including 33kV to IEC 60502-2
Three Core - XLPE Insulated Armoured Sheathed Cable For Voltages 6.6kV up to And Including 33kV to IEC 60502-2
Technical Data - Short Circuit And Earth Fault Current Rating
Technical Data - Current Rating Informations - Current Rating Correction Factors - XLPE Cable Installation Guide
Publications Referred To
WHAT IS XLPE?
Structure of PE and XLPE
XLPE is an abbreviated designation of “cross-linked polyethylene”. Polyethylene has a linear molecular
structure as shown in A. Molecules of polyethylene not chemically bonded as shown in B are easily
deformed at high temperature, while XLPE molecules bonded in a three dimensional network as shown in
C and D, have strong resistance to deformation even at high temperatures.
Cross linked polyethylene is produced from polyethylene under high pressure with organic peroxides
as additives. The application of heat and pressure is used to effect the cross linking. This causes the
individual molecular chains to link with one another which in turn causes the material to change from a
thermoplastic to an elastic material.
An important advantage of XLPE as insulation for medium and high voltage cables is their low dielectric
loss. The dielectric loss factor is about one decimal power lower than that of paper insulated cables and
about two decimal powers lower than that of PVC-insulated cables. Since the dielectric constant is also
more favourable, the mutual capacitance of XLPE cables is also lower, thus reducing the charging currents
and earth-leakage currents in networks without the rigid star-point earthing.
Polyethylene
Crosslinked Polyethylene
III
Central Cables Berhad
XLPE Insulation Advantages
1. Outstanding physical and mechanical toughness
2. Extremely low moisture absorption
3. Excellent ozone resistance
4. Strong resistance to chemicals fumes and gases
5. Low SIC and power factor
6. High impulse strength
7. High insulation resistance and dielectric strength
8. Capability of carrying and terminating
9. Easy to splice and terminate
IV
Central Cables Berhad
EXCELLENT XLPE INSULATION QUALITY
In order to obtain excellent high quality and stable cable insulation, Central Cables have selected
Nokia CDCC (completely dry curing and cooling) to produce the most important part in high voltage
cable insulation. The curing and cooling is done using dry Nitrogen Gas, heat transfer is by radiation
and convection. This method provides the cable insulation in:
1. Minimizing the water content
2. Minimizing the number of microvoids
3. Reduces mechanical stress in the insulation
4. Avoid mechanical stress, treeing and electrochemical treeing
5. Reduces the insulation shrink back phenomenon
120
110
100
90
80
70
60
50
40
30
20
10
For A.C
Bre
ak D
own
Vol
tage
(kv
/mm
)
For Impulse
A.C. and Impulse Voltage Break Down Characteristic
DryCuring
DryCuring
SteamCuring
SteamCuring
V
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHEDCABLE FOR VOLTAGES 1kV IEC 60502-1
DESCRIPTION
Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, extruded outer sheath made
from MDPE or HDPE or PVC.
CONSTRUCTION
Conductor
Plain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228.
Insulation
An extruded layer of cross-linked polyethylene(XLPE) compound rated at 90oC
Single Core-natural (black on request)
Two Core-red, black
Three Core-red, yellow, and blue
Four Core-red, yellow, blue and black
Lay Up Cores
material compatible with the insulation and covered with of PVC or MDPE or HDPE inner sheath which may be an
Non-conductive binder tape
Applied when requested by purchaser for single core.
A layer of non-conductive tape helically wrap with overlap laid over lay up cores.
Outer sheath
Extruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent or
different outer sheath colour are available upon request.
Shaped Conductor
XLPE Insulation
Binder Tape
PVC Sheath
Non-hygroscopicFiller
6
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.**Note : Single Phase Voltage Drop. #Note : Three Phase Voltage Drop.
SINGLE CORE - CU / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthNominal thickness of PVC
sheathApproximate overall
diameter
mm2 mm mm mm mm m/drum
1.52.54610162535507095120150185240300400500630
1.62.02.63.14.04.75.97.08.19.711.512.914.316.018.420.623.326.329.9
0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
5.8 6.2 6.8 7.3 8.2 8.9 10.5 11.6 12.9 14.7 16.5 18.1 19.9 22.0 24.6 27.0 30.1 33.5 37.5
5000 5000 5000 5000 4500 3500 2500 2000 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
SINGLE CORE - CU / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried direct in
ground
In single-way PEduct inground
In tray in air (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum CapacitanceMinimumchargingcurrent
Maximumvoltage drop
mm2 A A ATrefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400500630
3546597397125161192227278333379425480556626709799894
36476177102131169203241297358409462525613695794901
1017
2635465980
105142175213271336393453526628726848983
1135
30.859**18.899**11.759**7.858**4.672**2.940**1.865**1.170#0.870#0.612#0.452#0.386#0.310#0.262#0.218#0.193#0.173#0.159#0.149#
0.04150.04950.05980.07060.08650.10040.09860.11400.11880.12860.14930.15340.14650.14380.15420.16230.16500.16920.1759
0.220 0.263 0.317 0.375 0.459 0.533 0.523 0.605 0.630 0.682 0.792 0.814 0.777 0.763 0.818 0.861 0.876 0.898 0.933
0.145 0.135 0.125 0.117 0.109 0.104 0.100 0.096 0.090 0.087 0.084 0.081 0.081 0.080 0.078 0.077 0.076 0.075 0.074
7
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.**Note : Single Phase Voltage Drop. #Note : Three Phase Voltage Drop.
SINGLE CORE - AL / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthApproximate overall
diameter
mm2 mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0 2.2 2.4
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4
8.9 10.6 11.6 13.0 14.8 16.6 18.2 20.0 22.2 24.7 27.1 30.3 33.7 37.7
3500 2500 2000 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
SINGLE CORE - AL / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried direct in
ground
In single-way PEduct inground
In tray in air (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum CapacitanceMinimumchargingcurrent
Maximumvoltage drop
mm2 A A ATrefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
500630
97125149
176216259
295330375
435492563
643731
101131158
187231278
318359410
480546631
726834
82110136
166211261
306352411
493571674
793930
4.902**3.084**1.935#
1.432#1.996#0.726#
0.481#0.480#0.392#
0.311#0.262#0.221#
0.192#0.171#
0.10120.09920.1147
0.19960.12960.1503
0.15460.14740.1448
0.11520.16320.1662
0.17060.1771
0.537 0.524 0.609 0.634 0.688 0.797 0.820 0.782 0.768 0.823 0.866 0.882 0.905 0.940
0.104 0.100 0.095 0.090 0.087 0.084 0.081 0.081 0.080 0.078 0.077 0.076 0.075 0.074
Nominal thickness ofPVC sheath
8
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
TWO CORE - CU/XLPE/PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthNominal thickness of PVC
sheathApproximate overall
diameter
mm2 mm mm mm mm m/drum
1.52.54610162535507095120150185240300400
1.62.02.63.14.04.7
4.3 x 8.25.1 x 9.76.0 x 11.47.2 x 13.78.5 x 16.29.6 x 18.310.7 x 20.211.9 x 22.613.7 x 26.015.3 x 29.117.3 x 32.9
0.7 0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.9
9.7 10.5 11.6 12.8 14.4 15.9 15.9 17.5 19.8 22.6 25.3 27.9 31.3 34.8 39.0 42.8 48.0
3000 2500 2000 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
TWO CORE - CU/XLPE/PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum1 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400
273545567394119142168206247281316358415468531
273647587799127153182225272312353403437536614
2939526589
116136177215273337392453519616710822
30.86018.90011.7617.8614.6762.9461.8711.3591.0610.7210.5410.4480.3860.3360.2650.2630.244
0.01980.02140.02320.02460.02630.02740.03610.03860.03930.04060.04310.04420.04280.04250.04370.04510.0455
0.105 0.114 0.123 0.131 0.140 0.146 0.191 0.205 0.209 0.215 0.228 0.235 0.227 0.226 0.232 0.239 0.242
0.177 0.168 0.159 0.152 0.145 0.140 0.126 0.121 0.120 0.114 0.111 0.108 0.109 0.109 0.088 0.105 0.105
9
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
TWO CORE - AL / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthApproximate overall
diameter
mm2 mm mm mm mm m/drum
162535
507095
120150185
240300400
4.74.3 x 8.25.1 x 9.7
6.0 x 11.47.2 x 13.78.5 x 16.2
9.6 x 18.310.7 x 20.211.9 x 22.6
13.7 x 26.018.9 x 29.117.3 x 32.9
0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.9
9.1 16.0 17.5 20.1 22.9 25.7 28.4 31.9 35.4 39.7 43.6 49.0
2000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
TWO CORE - AL / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum1 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
7392110
131160192
219246279
325368422
7699
119
142175212
243275315
370422489
91112135
168213263
307351407
485561656
4.9063.0872.239
1.6611.1590.851
0.6860.5730.476
0.3880.3350.293
0.02750.03620.0387
0.3870.04020.0424
0.04270.04190.0417
0.04260.04330.0437
0.146 0.192 0.205 0.206 0.213 0.225 0.227 0.227 0.221 0.226 0.230 0.232
0.140 0.123 0.121 0.118 0.114 0.111 0.109 0.110 0.110 0.108 0.107 0.106
Nominal thicknessof PVC sheath
10
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthNominal thickness of PVC
sheathApproximate overall
diameter
mm2 mm mm mm mm m/drum
1.52.546162535507095120150185240300400
1.62.02.63.14.7
5.2 x 8.16.1 x 9.57.2 x 11.2 8.7 x 13.510.2 x 15.911.5 x 17.912.8 x 19.814.3 x 22.216.4 x 25.518.4 x 28.520.8 x 32.3
0.7 0.7 0.7 0.7 0.7 0.9 0.9 1 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.7 3.0
10.2 11.1 12.2 13.5 16.9 18.0 19.8 22.5 26.0 29.3 32.4 36.3 40.3 45.3 49.8 55.5
2500 2000 2000 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500 500
THREE CORE - CU / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400
253343537191158189225276330376422478554625708
3242556292117166199237291349398448509591668758
2736476082
108137168206262323377435506603696808
26.72516.36710.1846.8064.0482.5501.6191.1750.8770.6230.4680.3870.3340.2910.2520.2300.213
0.04150.04950.05980.07060.08650.10040.09860.11400.11800.12860.14630.15460.14650.14380.15420.16320.1662
0.220 0.263 0.317 0.375 0.459 0.533 0.523 0.605 0.630 0.682 0.792 0.820 0.777 0.763 0.818 0.866 0.882
0.152 0.145 0.140 0.135 0.131 0.128 0.119 0.116 0.113 0.112 0.110 0.108 0.109 0.109 0.108 0.107 0.106
11
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthApproximate overall
diameter
mm2 mm mm mm mm m/drum
162535
507095
120150185
240300400
4.75.2 x 8.16.1 x 9.5
7.2 x 11.28.7 x 13.510.2 x 15.9
11.5 x 17.912.8 x 19.814.3 x 22.2
16.4 x 25.518.4 x 28.520.8 x 32.3
0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.3 2.4 2.6 2.7 3.0
9.5 18.2 20.1 23.0 23.2 30.0 33.3 37.2 41.4 46.5 51.2 57.6
1000 1000 1000 1000 1000 1000 1000 500 500 500 500 500
THREE CORE - AL / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
86123147
175215258
294330376
436494565
89129155
184227272
311350399
464526604
83107131
161205253
296341399
477553650
2.1561.7821.565
1.4411.0070.741
0.5990.5030.497
0.3370.2930.257
0.10120.09920.1147
0.11960.07780.1503
0.15460.14740.1448
0.15520.15160.1662
0.537 0.526 0.061 0.634 0.413 0.797 0.820 0.939 0.768 0.823 0.804 0.882
0.144 0.119 0.130 0.129 0.124 0.121 0.119 0.120 0.111 0.109 0.109 0.109
Nominal thicknessof PVC sheath
12
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
FOUR CORE - CU / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthNominal thickness
of PVC sheathApproximate overall
diameter
mm2 mm mm mm mm m/drum
2.54610162535507095120150185240300
2.02.63.14.04.7
5.7 x 7.76.8 x 9.17.9 x 10.69.5 x 12.711.2 x 15.012.6 x 16.914.0 x 18.715.6 x 21.017.9 x 24.120.1 x 27.0
0.7 0.7 0.7 0.7 0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 2.0 2.1 2.3 2.4 2.6 2.8 3.0
12.0 13.3 14.6 16.7 18.4 20.1 22.2 25.3 29.5 33.3 37.0 41.2 46.0 51.7 57.0
2000 1500 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500 500 250
FOUR CORE - CU / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300
26.72516.36710.1856.8074.0492.5511.6211.1780.8810.6280.4740.3950.3430.3010.2640.242
0.04150.04950.05980.07060.08650.10040.09860.11400.11880.36270.14930.15460.14650.14380.15420.1632
0.220 0.263 0.317 0.375 0.459 0.533 0.523 0.605 0.630 0.682 0.792 0.820 0.777 0.118 0.818 0.866
0.159 0.152 0.147 0.142 0.138 0.136 0.128 0.125 0.122 0.120 0.118 0.117 0.118 0.763 0.117 0.116
253343537191158189225276330376422478554625
3242556290
117166189237291349398448509591668
2736476082
108137168206262323377435506603696
13
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
FOUR CORE - AL / XLPE / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness Standard packing lengthApproximate overall
diameter
mm2 mm mm mm mm m/drum
162535
507095
120150185
240300400
4.75.7 x 7.76.8 x 9.1
7.9 x 10.69.5 x 12.711.2 x 15.0
12.6 x 16.914.0 x 18.715.6 x 21.0
17.9 x 24.120.1 x 27.022.8 x 30.5
0.7 0.9 0.9 1.0 1.1 1.1 1.2 1.4 1.6 1.7 1.8 2.0
1.8 1.8 1.8 1.8 2.0 2.1 2.3 2.4 2.6 2.8 3.0 3.3
18.4 20.4 22.6 25.8 30.1 34.0 37.9 42.2 47.2 53.0 58.6 65.8
1000 1000 1000 1000 1000 1000 1000 1000 500 500 500 500
FOUR CORE - AL / XLPE / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
0.10040.09920.1147
0.11960.12960.1503
0.15460.14740.1448
0.15520.15530.1747
0.533 0.526 0.609 0.634 0.688 0.797 0.820 0.782 0.768 0.823 0.824 0.927
0.136 0.128 0.126 0.125 0.121 0.120 0.118 0.119 0.119 0.118 0.118 0.117
Nominal thicknessof PVC sheath
86123147
175215258
294330376
436494565
89129153
184227272
311350399
464526604
83107131
161205253
296341399
464526650
4.2482.6741.940
1.4021.0060.741
0.5990.5030.420
0.3460.3030.268
14
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE WITH CU TAPE SCREENED FOR VOLTAGES 1kV IEC 60502-1
DESCRIPTION
Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, extruded outer sheath
CONSTRUCTION
Conductor
Aluminium(AL) conductor conform to class 2 in IEC 60228.
Insulation
An extruded layer of cross-linked polyethylene(XLPE) compound rated at 90ºC
Four Core-red, yellow, blue and black
Lay Up Cores
compatible with the insulation
Non-conductive binder tape
A layer of non-conductive tape helically wrap with overlap laid over lay up cores.
Inner Sheath
Extruded layer made from black MDPE compound.
Metallic Screening
Two layers of copper tape (CTS) helically wrap with overlap laid over inner sheath.
Separator Binder Tape
A layer of non-conductive tape helically wrap with overlap laid over metallic screen when necessary.
Outer sheath
Extruded layer made from black MDPE compound. Additive like Anti-termite repellent, anti-rodent or different
outer sheath colour are available upon request.
Conductor
XLPE Insulation
Binder Tape
Copper Tape Screen
MDPE Inner Sheath
MDPE Outer Sheath
Non-hygroscopicFiller
15
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE WITH CU TAPE SCREENED 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
FOUR CORE - AL / XLPE / MDPE / CTS / MDPE SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominalinsulationthickness
Metallic screeningNominal thicknessof copper
tape
Nominal thicknessof MDPE inner sheath
Nominal thicknessof MDPE sheath
Standardpackinglength
Approximateoverall
diameter
mm2 mm mm mm mm x n mm mm m/drum
5.7 x 7.76.8 x 9.1
7.9 x 10.69.5 x 12.711.2 x 15.0
12.6 x 16.914.0 x 18.715.6 x 21.0
17.9 x 24.120.1 x 27.022.8 x 30.5
0.90.9
1.01.11.1
1.21.41.6
1.71.82.0
1.0 1.0 1.0 1.2 1.2 1.4 1.4 1.4 1.6 1.6 1.8
0.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.6 2.9 3.0 3.3
10001000
100010001000
100010001000
10001000500
23.826.5
29.634.038.2
42.246.651.4
57.963.270.9
FOUR CORE - AL / XLPE / MDPE / CTS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per Conductor*
Maximum ReactanceMaximum CapacitanceMinimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
126151
179219263
299337383
445503577
132158
188232278
317357407
474538618
112138
169216266
311359420
502581684
2.6741.940
1.4021.0060.741
0.5990.5030.420
0.3460.3030.268
0.09920.1147
0.11960.12960.1503
0.15460.14740.1448
0.15520.15530.1747
0.526 0.609 0.634 0.688 0.797 0.820 0.782 0.768 0.823 0.824 0.927
0.128 0.126 0.125 0.121 0.120 0.118 0.119 0.119 0.118 0.118 0.117
25#
35
5070#
95
120#
150185#
240300#
400
25#
35
5070#
95
120#
150185#
240300#
400
16
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLEFOR VOLTAGES 1kV AND 3.3kV TO IEC 60502-1
DESCRIPTION Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, covered with extruded inner sheath, armoured, extruded outer sheath made from MDPE or HDPE or PVC. CONSTRUCTION
ConductorPlain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228.
InsulationAn extruded layer of cross-linked polyethylene(XLPE) compound rated at 90oC
Single Core-natural (black on request)Two Core-red, blackThree Core-red, yellow, and blueFour Core-red, yellow, blue and black
Lay Up Cores
compatible with the insulation and covered with of PVC or MDPE or HDPE inner sheath which may be an integral part of
Non-conductive binder tapeApplied when necessaryA layer of non-conductive tape helically wrap with overlap laid over lay up cores.
Inner SheathExtruded layer made from black PVC or MDPE or HDPE compound.
ArmourSingle Core-Aluminium wires shall be applied helically over the inner sheathMutli Core-Galvanized Steel wires shall be applied helically over the inner sheath.
Non-conductive binder tapeA layer of non-conductive tape helically wrap with overlap laid over armour when necessary.
Outer sheathExtruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent or different outer sheath colour are available upon request.
Conductor
XLPE Insulation
Binder Tape
PVC Bedding
Gal. SteelWire Armour
PVC Sheath
Non-hygroscopicFiller
17
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54610162535507095120150185240300400500630
1.62.02.63.14.04.75.97.08.19.711.512.914.316.018.420.623.326.329.9
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.02.22.4
1.01.01.01.01.01.01.01.01.01.01.01.01.01.01.01.01.21.21.2
0.90.90.90.90.90.90.90.9
1.251.251.251.61.61.61.61.62.02.02.0
1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.9 1.9 2.1 2.2 2.3
10.4 10.8 11.4 11.9 12.8 13.5 15.1 16.2 18.2 20.0 21.8 24.5 26.3 28.4 31.2 33.6 38.3 41.9 46.1
100010001000100010001000100010001000100010001000100010001000100010001000500
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B. **Note : Single Phase Voltage Drop. #Note : Three Phase Voltage Drop.
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE DIMENSION
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum voltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400500630
36476175100127164195232283339387433489567639727822924
38496479
105135174209249307369424478542632717825939
1065
3242546892
120159193237298365428489564670771904
10451204
30.860**18.900**11.761**7.860**4.675**2.944**1.870**1.175#0.877#0.621#0.462#0.382#0.324#0.277#0.234#0.209#0.192#0.177#0.167#
0.04150.04950.05980.07060.08650.10040.09860.11400.11880.12860.14630.15340.14650.14380.15420.16230.16500.16920.1759
0.220 0.263 0.317 0.375 0.457 0.533 0.523 0.605 0.630 0.682 0.792 0.814 0.777 0.763 0.818 0.861 0.876 0.898 0.933
0.182 0.169 0.158 0.148 0.137 0.130 0.123 0.117 0.112 0.106 0.101 0.101 0.099 0.096 0.093 0.091 0.091 0.089 0.087
18
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / PVC / AWA / PVC DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
0.70.90.9
1.01.11.1
1.21.41.6
1.71.82.0
2.22.4
1.01.01.0
1.01.01.0
1.01.01.0
1.01.01.2
1.21.2
0.90.90.9
1.251.251.25
1.61.61.6
1.61.62.0
2.02.0
1.4 1.4 1.4 1.5 1.6 1.7 1.7 1.7 1.8 1.9 1.9 2.1 2.2 2.3
13.5 15.2 16.2 18.3 20.1 21.9 24.6 26.4 28.6 31.3 33.7 38.5 42.2 46.4
100010001000
100010001000
100010001000
100010001000
10001000
SINGLE CORE - AL / XLPE / PVC / AWA / PVC ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
500630
99127152
180220263
301336381
442500574
656747
104135162
193238286
330371423
494561651
750861
93123150
184232284
333380440
523604715
835975
4.2482.6731.938
1.4381.0010.733
0.5890.4890.402
0.3230.2740.236
0.2080.187
0.10120.09920.1147
0.11960.12960.1503
0.15460.14740.1448
0.15520.16320.1702
0.17060.1771
0.537 0.526 0.609 0.634 0.688 0.797 0.820 0.782 0.768 0.823 0.865 0.903 0.905 0.937
0.1279 0.1224 0.1163 0.1143 0.1060 0.1010 0.1002 0.0983 0.0960 0.0920 0.0904 0.0908 0.0888 0.0865
19
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
TWO CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54610162535507095120150185240300400
1.62.02.63.14.04.7
4.3 x 8.25.1 x 9.76.0 x 11.47.2 x 13.78.3 x 15.78.5 x 16.210.7 x 20.211.9 x 22.613.7 x 26.015.3 x 29.1017.3 x 32.9
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
1.01.01.01.01.01.01.01.01.01.01.21.21.21.41.41.61.6
0.90.90.90.9
1.251.251.61.61.61.62.02.02.02.52.52.52.5
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.7 2.9 3.1
13.5 14.3 15.4 16.6 18.9 20.4 21.6 23.1 25.6 28.6 32.5 35.2 38.6 43.9 48.0 52.4 57.5
10001000100010001000100010001000100010001000100010001000500500500
TWO CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum1 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400
283646577696123146174212255289324368425479542
2938496181
104134161191235286326367421490556634
303951658891
150183220276343396450522616707814
30.86018.90111.7627.8624.6782.9491.8811.3701.0230.7310.5540.4620.4010.3540.3090.2630.228
0.04150.04950.05980.07060.08650.10040.08130.09860.11960.12960.15030.15460.14740.14480.15520.16320.1662
0.220 0.263 0.317 0.375 0.459 0.533 0.435 0.523 0.634 0.688 0.797 0.820 0.782 0.768 0.823 0.866 0.882
0.198 0.187 0.177 0.169 0.162 0.156 0.159 0.149 0.133 0.128 0.126 0.123 0.122 0.123 0.120 0.118 0.116
20
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
TWO CORE - AL / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
16
25
35
50
70
95
120
150
185
240
300
400
4.7
4.3 x 8.2
5.1 x 9.7
6.0 x 11.4
7.2 x 13.7
8.5 x 16.2
9.6 x 18.3
10.7 x 20.2
11.9 x 22.6
13.7 x 26.0
18.9 x 29.1
17.3 x 32.9
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.25
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5
1.8
1.8
1.8
1.9
2.0
2.1
2.2
2.4
2.5
2.7
2.9
3.1
20.5
21.6
23.2
25.9
28.9
32.9
38.5
39.1
44.5
48.8
53.3
58.5
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
TWO CORE - AL / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum1 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
16
25
35
50
70
95
120
150
185
240
300
400
87
104
125
148
183
222
254
286
329
385
438
504
80
116
141
171
215
267
309
351
409
484
556
647
4.250
2.677
1.943
1.443
1.009
0.744
0.602
0.505
0.424
0.349
0.305
0.268
0.1012
0.0986
0.1147
0.1196
0.1296
0.1503
0.1545
0.1474
0.1448
0.1552
0.1516
0.1662
0.537
0.523
0.609
0.634
0.688
0.797
0.820
0.782
0.768
0.823
0.804
0.882
0.156
0.145
0.139
0.136
0.129
0.127
0.124
0.123
0.128
0.121
0.119
0.117
75
95
114
135
165
196
225
252
287
334
376
430
21
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.546
101625
355070
95120150185
240300400
1.62.02.63.1
4.04.7
5.2 x 8.1
6.1 x 9.57.2 x 11.28.7 x 13.5
10.2 x 15.911.5 x 17.912.8 x 19.814.3 x 22.2
16.4 x 25.518.4 x 28.520.8 x 32.3
0.70.70.70.7
0.70.70.9
0.91.01.1
1.11.21.41.6
1.71.82.0
1.01.01.01.0
1.01.01.0
1.01.01.2
1.21.21.41.4
1.61.61.6
0.90.90.90.9
1.251.251.6
1.61.62.0
2.02.02.52.5
2.52.52.5
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.1 2.2 2.3 2.5 2.6 2.8 3.0 3.3
14.0 14.9 16.0 17.3 19.8 21.4 23.6 25.4 28.4 33.3 36.5 39.6 45.3 49.4 54.7 59.4 65.1
1000100010001000
100010001000
100010001000
10001000500500
500250250
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400
26.72516.36710.1846.8064.0482.5501.6191.1750.8770.6230.4680.3890.3340.2910.2520.2300.214
0.04150.04920.05980.07060.08650.10040.09860.11400.11800.12860.14930.15340.15570.14380.15420.16230.1650
0.220 0.263 0.317 0.375 0.459 0.533 0.523 0.065 0.630 0.682 0.792 0.814 0.826 0.763 0.820 0.861 0.876
0.152 0.145 0.140 0.135 0.131 0.125 0.119 0.116 0.113 0.112 0.110 0.108 0.109 0.109 0.108 0.107 0.106
253241516786125149176217259294331373431485546
3542556992
119137164194243293335380431503570646
3138506391
114146178216274335388447515604689787
22
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
16
25
35
50
70
95
120
150
185
240
300
400
4.7
5.2 x 8.1
6.1 x 9.5
7.2 x 11.2
8.7 x 13.5
10.2 x 15.9
11.5 x 17.9
12.8 x 19.8
14.3 x 22.2
16.4 x 25.5
18.4 x 28.5
20.8 x 32.3
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.4
1.4
1.6
1.6
1.6
1.25
1.6
1.6
1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
1.8
1.8
1.8
1.9
2.1
2.2
2.3
2.5
2.6
2.8
3.0
3.3
22.7
23.6
25.7
28.9
33.9
37.2
40.5
46.3
50.4
56.0
60.8
67.2
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
500
THREE CORE - AL / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
16
25
35
50
70
95
120
150
185
240
300
400
66
151
178
207
248
291
326
359
400
454
503
560
92
129
155
184
226
271
310
348
395
457
515
587
89
114
139
169
215
262
305
351
407
481
551
641
4.248
2.673
1.938
1.437
1.003
0.737
0.594
0.497
0.413
0.337
0.293
0.257
0.0744
0.0992
0.1147
0.1196
0.1414
0.1503
0.1535
0.1474
0.1448
0.1552
0.1632
0.1662
0.395
0.526
0.609
0.634
0.750
0.797
0.814
0.782
0.768
0.823
0.869
0.882
0.134
0.119
0.117
0.114
0.113
0.111
0.110
0.110
0.115
0.109
0.109
0.109
23
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
FOUR CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
“Armouring wire
diameter”
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54610162535507095120150185240300400
1.62.02.63.14.04.7
5.7 x 7.76.8 x 9.17.9 x 12.79.5 x 12.7111.2 x 15.012.6 x 16.914.0 x 18.715.6 x 21.018.0 x 24.120.1 x 27.022.8 x 30.5
0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
1.01.01.01.01.01.01.01.01.01.21.21.41.41.41.61.61.8
0.90.90.9
1.251.251.61.61.62.02.02.02.52.52.52.52.53.2
1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.9 2.0 2.2 2.3 2.5 2.7 2.8 3.0 3.2 3.6
14.4 15.8 17.1 19.1 21.2 24.1 25.7 28.0 32.1 36.7 40.5 46.4 50.5 55.1 61.1 66.5 75.0
10001000100010001000100010001000100010001000500500500250250250
FOUR CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.54610162535507095120150185240300400
253241516786125149176217259294331373431485546
3542556992
119137164194243293335380431503570646
3138506391
114146178216274335388447515604689787
26.72516.36710.1856.8074.0492.5511.6211.1780.8820.6280.4740.3950.3430.3010.2640.2430.228
0.04150.04950.05980.07060.08650.10040.09860.11400.11880.12860.14730.15340.14650.14380.15420.16230.1650
0.220 0.263 0.317 0.375 0.046 0.533 0.523 0.605 0.630 0.682 0.792 0.814 0.777 0.763 0.188 0.861 0.876
0.159 0.152 0.147 0.142 0.138 0.136 0.128 0.125 0.124 0.120 0.118 0.117 0.118 0.118 0.117 0.116 0.116
24
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
FOUR CORE - AL / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
16
25
35
50
70
95
120
150
185
240
300
400
4.7
5.7 x 7.7
6.8 x 9.1
7.9 x 10.6
9.5 x 12.7
11.2 x 15.0
12.6 x 16.9
14.0 x 18.7
15.6 x 21.0
17.9 x 24.1
20.1 x 27.0
22.8 x 30.5
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.4
1.6
1.6
1.8
1.6
1.6
1.6
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
3.15
1.8
1.8
1.9
2.0
2.2
2.3
2.5
2.7
2.8
3.0
3.2
3.6
25.6
26.0
28.4
32.6
37.4
41.2
46.9
51.4
56.2
62.5
68.0
77.2
1000
1000
1000
1000
1000
1000
500
500
500
500
500
500
FOUR CORE - AL / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
16
25
35
50
70
95
120
150
185
240
300
400
66
151
178
207
248
291
326
359
400
454
503
560
92
129
155
184
226
271
310
348
395
457
515
587
89
114
139
169
215
262
305
351
407
481
551
641
4.249
2.674
1.940
1.440
1.006
0.741
0.599
0.503
0.420
0.346
0.303
0.268
0.0744
0.0992
0.1147
0.1196
0.1296
0.1503
0.1564
0.1474
0.1448
0.1552
0.1632
0.1662
0.395
0.526
0.061
0.634
0.688
0.797
0.820
0.782
0.768
0.823
0.866
0.882
0.141
0.128
0.126
0.123
0.121
0.120
0.118
0.119
0.119
0.118
0.118
0.117
25
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 1.9/3.3(3.6)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
16
25
35
50
70
95
120
150
185
240
300
8.1
9.7
11.5
12.9
14.3
16.0
18.4
20.6
23.3
26.3
29.9
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
2.4
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.25
1.25
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
1.5
1.6
1.7
1.7
1.8
1.8
1.9
2.0
2.1
2.2
2.3
20.2
21.8
24.3
26.1
27.5
29.3
31.8
33.7
38.3
41.9
46.1
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
50
70
95
120
150
185
240
300
400
500
630
231
282
339
385
432
488
566
637
724
815
925
249
306
371
423
477
541
632
716
822
931
1066
241
301
373
431
491
564
671
770
901
1037
1205
1.017
0.720
0.539
0.444
0.377
0.322
0.271
0.241
0.222
0.206
0.192
0.3591
0.4185
0.4817
0.5331
0.5842
0.6460
0.7309
0.8928
0.9078
0.9308
0.9674
0.349
0.404
0.465
0.514
0.564
0.623
0.705
0.861
0.876
0.898
0.933
0.121
0.112
0.108
0.104
0.101
0.098
0.094
0.091
0.091
0.089
0.087
26
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 1.9/3.3 (3.6)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / PVC / AWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
50
70
95
120
150
185
240
300
400
500
630
8.17
9.83
11.6
13.0
14.4
16.2
18.5
20.7
23.5
26.5
30.1
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
2.4
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.2
1.2
1.2
1.25
1.25
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
1.5
1.6
1.7
1.7
1.8
1.8
1.9
1.9
2.1
2.2
2.3
20.27
21.93
24.4
26.2
27.6
29.4
31.9
33.8
38.5
42.2
46.4
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
SINGLE CORE - AL / XLPE / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
50
70
95
120
150
185
240
300
400
500
630
180
220
339
385
432
488
566
637
725
816
926
194
239
371
424
477
542
633
716
823
933
1067
187
235
373
432
491
566
672
771
902
1040
1208
1.438
1.003
0.469
0.386
0.328
0.280
0.236
0.209
0.192
0.208
0.187
0.2080
0.2428
0.2790
0.3090
0.3384
0.3746
0.4235
0.5168
0.5264
0.5403
0.5608
0.349
0.407
0.467
0.518
0.567
0.628
0.710
0.866
0.882
0.905
0.940
0.118
0.111
0.108
0.104
0.101
0.098
0.094
0.091
0.091
0.089
0.087
27
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 1.9/3.3 (3.6)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
162535
507095
120150185
240300400
4.75.9
6.1 x 9.5
7.2 x 11.28.7 x 13.510.2 x 24.7
11.5 x 24.712.8 x 24.714.3 x 24.7
16.4 x 24.718.4 x 28.520.8 x 32.3
2.02.02.0
2.02.02.0
2.02.02.0
2.02.02.0
1.01.01.0
1.01.01.0
1.21.21.2
1.41.41.6
1.61.61.6
2.02.02.0
2.52.52.5
2.52.52.5
1.81.81.8
1.92.02.2
2.22.32.4
2.62.73.0
28.1 30.7 25.7 29.5 33.1 36.5 41.6 41.6 49.6 55.1 59.9 66.5
100010001000
100010001000
10001000500
500250250
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
82103156
188235287
332380438
517591677
125160200
239293351
399448507
583654734
127165178
219276337
394451520
612699800
2.5461.6151.166
0.8660.6070.446
0.3620.3020.253
0.2080.1810.161
0.23380.27890.5708
0.65320.77100.8966
1.00691.10071.2239
1.39331.56051.7593
0.2260.2690.551
0.6300.7440.865
0.9711.0621.181
1.3441.5051.697
0.10240.09620.0796
0.07480.07260.0710
0.06910.06840.0675
0.06620.06550.0648
Maximum current rating per conductor*
28
Central Cables Berhad
XLPE INSULATED ARMOURE SHEATHED CABLE 1.9/3.3 (3.6)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / PVC / SWA / PVC DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
162535
507095
120150185
240300400
4.75.9
6.1 x 9.5
7.2 x 11.28.7 x 13.510.2 x 24.7
11.5 x 24.712.8 x 24.714.3 x 24.7
16.4 x 24.718.4 x 28.520.8 x 32.3
2.02.02.0
2.02.02.0
2.02.02.0
1.71.82.0
1.01.01.0
1.01.01.0
1.21.21.2
1.61.61.6
1.61.61.6
2.02.02.0
2.52.52.5
2.52.52.5
1.81.81.8
1.81.92.0
2.22.32.4
2.62.83.0
28.1 30.7 25.7 29.5 33.1 36.5 41.6 45.4 49.6 56.0 60.8 66.5
100010001000
100010001000
1000500500
500500500
THREE CORE - AL / XLPE / PVC / AWA / PVC ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
66151178
207248291
326359400
454503560
92129155
184226271
310348395
457515587
89114139
169215262
305351407
481551641
4.2482.6731.938
1.4371.0030.737
0.5940.4970.413
0.3370.2930.257
0.07440.09920.1147
0.11960.14140.1503
0.15350.14740.1448
0.15520.16320.1662
0.3950.5260.609
0.6340.7500.797
0.8140.7820.768
0.8230.8690.882
0.1340.1190.117
0.1140.1130.111
0.1100.1100.115
0.1090.1090.109
Maximum current rating per conductor*
29
Conductor
XLPE Insulation
Binder Tape
PVC Bedding
Gal. SteelWire Armour
PVC Sheath
Non-hygroscopicFiller
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE FOR VOLTAGES 1kV AND 3.3kV TO BS 5467
DESCRIPTION Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, covered with extruded inner sheath,armoured, extruded outer sheath made from PVC.
CONSTRUCTION Conductor Plain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228. Insulation An extruded layer of cross-linked polyethylene(XLPE) compound at rated 90 C Colours for core identification Single Core-natural (black on request) Two Core-red, black Three Core-red, yellow, and blue Four Core-red, yellow, blue and black Five Core-red, yellow, blue, black, and green/yellowSix Core and above-numbering on white core Lay Up Cores Two, three, four or five insulated conductors are laid up together, if necessary filled with non-hygroscopic material compatible with the insulation and covered with of PVC inner sheath which may be an integral part of the filling. Non-conductive binder tape Applied when necessary A layer of non-conductive tape helically wrap with overlap laid over lay up cores. Inner Sheath Extruded layer made from black PVC compound. Additive like Anti-termite repellent, anti-rodent or different separation sheath colour are available upon request. Armour Single Core cables-Aluminium wires shall be applied helically over the inner sheath Mutli Core cables-Galvanized Steel wires shall be applied helically over the inner sheath. Non-conductive binder tape A layer of non-conductive tape helically wrap with overlap laid over armour when necessary. Outer sheath Extruded layer made from black PVC compound. Additive like Anti-termite repellent, anti-rodent or different outer sheath colour are available upon request.
O
30
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
507095
120150185
240300400
500630
210255302
342382426
483543600
701783
193236283
321360407
472531603
681766
240300367
424483555
657754872
10051152
0.8750.6190.461
0.3780.3240.277
0.2340.2080.192
0.1770.167
0.1190.1290.149
0.1530.1470.144
0.1540.1620.165
0.1690.176
0.63010.68200.7922
0.81400.77720.7627
0.81790.86120.8756
0.89780.9332
0.1056 0.1031 0.0988 0.0954 0.0980 0.0962 0.0926 0.0905 0.0907 0.0877 0.0866
SINGLE CORE - CU / XLPE / PVC / AWA / PVC DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
507095
120150185
240300400
500630
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
1.01.11.1
1.21.41.6
1.71.82
2.22.4
0.80.80.8
0.81.01.0
1.01.01.2
1.21.2
0.91.251.25
1.251.61.6
1.61.62.0
2.02.0
1.5 1.5 1.6 1.6 1.7 1.8 1.8 1.9 2.0 2.1 2.2
16.5 19.0 21.0 22.6 26.1 28.4 31.0 33.6 38.1 41.7 45.9
100010001000
100010001000
100010001000
1000500
Armouring wire
diameter
31
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
TWO CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.546
10162535507095
120150185240300400
1.62.02.63.14.04.7
4.3 x 8.25.1 x 9.7
6.0 x 11.47.2 x 13.78.5 x 16.29.6 x 18.3
10.7 x 20.211.9 x 22.613.7 x 26.015.3 x 29.117.3 x 32.9
0.60.70.70.70.70.70.90.91
1.11.11.21.41.61.71.82
0.80.80.80.80.80.80.81.01.01.01.21.21.21.41.41.61.6
0.90.90.90.90.91.251.251.61.61.62.02.02.02.52.52.52.5
1.31.41.41.41.51.51.61.71.81.92.02.12.22.42.62.62.8
11.713.114.215.417.219.419.622.925.428.432.335.038.243.747.651.856.9
10001000100010001000100010001000100010001000100010001000500500500
TWO CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum1 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.546
10162535507095
120150185240300400
283646577698
157195235294366422479555657749859
2937496182106138165195238285323362409474534606
3242577199131239199244305372429488560662759878
30.85818.89811.7587.8574.0442.5441.6121.3461.0000.7010.5160.3620.3510.2950.2450.2150.191
0.0470.0500.0600.0710.0870.1000.0990.1140.1190.1290.1490.1550.1470.1440.1540.1630.166
0.24700.26280.31740.37470.45880.53270.52320.60460.63010.68020.95060.82040.77720.76270.81790.86580.8819
0.09500.09290.08720.08300.07870.07610.07640.07410.07480.07380.79220.07080.07140.07160.07080.07020.0696
32
Central Cables Berhad
XLPE INSULATED ARMOURE SHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.546
10162535507095
120150185240300400
1.62.02.63.14.04.7
5.2 x 8.16.1 x 9.5
7.2 x 11.28.7 x 13.5
10.2 x 15.911.5 x 17.912.8 x 19.814.3 x 22.216.4 x 25.518.4 x 28.520.8 x 32.3
0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0
0.80.80.80.80.80.81.01.01.01.01.21.21.41.41.41.61.6
0.90.90.90.91.251.251.61.61.61.62.02.02.52.52.52.52.5
1.3 1.4 1.4 1.4 1.5 1.6 1.7 1.8 1.8 1.9 2.1 2.2 2.3 2.4 2.6 2.7 2.9
12.1 13.7 14.8 16.1 18.8 20.6 23.4 25.4 28.2 31.7 36.3 39.4 44.9 49.0 53.9 58.8 64.3
100010001000100010001000100010001000100010001000500500500250250
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum1 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.546
10162535507095
120150185240300400
273342536987
131190212256304344379423479535682
3343567094119167166196239286325364411476536607
2938506488114146206247308375432491564666763881
26.72416.36610.1836.8044.0442.5441.6121.1660.8660.6070.4460.3620.3040.2560.2100.1850.167
0.04360.04950.05980.07060.08650.10040.09860.14400.11180.12860.14930.15460.14650.14380.19340.16320.1662
0.2312 0.2628 0.3174 0.3747 0.4588 0.5327 0.5232 0.6046 0.6301 0.6820 0.7922 0.8204 0.7772 0.7627 1.0258 0.8658 0.8819
0.1015 0.0969 0.0912 0.0870 0.0827 0.0801 0.0804 0.0782 0.0748 0.7380 0.0720 0.0708 0.0714 0.0716 0.0682 0.0698 0.0696
Armouring wire
diameter
33
Central Cables Berhad
XLPE INSULATED ARMOUREDSHEATHED CABLE 0.6/1 (1.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
FOUR CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Single Cable Single Cable
Single Cable
mV/A/m A/km μF/km ohm/km
1.52.546
10162535507095
120150185240300400
273342536987
131190212256304344379423479535682
3343567094119167166196239286325364411476536607
2938506488114146206247308375432491564666763881
26.723916.366210.18277.85674.0442.5441.6121.6600.8660.6070.4460.3620.3040.2560.2110.1850.166
0.04660.04950.05980.07060.08650.1000.0990.1140.1190.5730.1490.1550.1470.1440.1540.1630.166
0.2470 0.2628 0.3808 0.3747 0.4588 0.5327 0.5232 0.6046 0.6301 0.6820 0.7922 0.8204 0.7772 0.7627 0.8179 0.8658 0.8819
0.0991 0.0969 0.0912 0.0870 0.0827 0.0801 0.0804 0.0782 0.0748 0.0738 0.0720 0.0708 0.0714 0.0716 0.0704 0.0698 0.0696
FOUR CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.546
10162535507095
120150185240300400
1.62.02.63.14.04.7
5.7 x 7.76.8 x 9.1
7.9 x 10.69.5 x 12.7
11.2 x 15.012.6 x 16.914.0 x 18.715.6 x 21.017.9 x 24.120.1 x 27.022.8 x 30.5
0.60.70.70.70.70.70.90.91
1.11.11.21.41.61.71.82.0
0.80.80.80.80.80.81.01.01.01.21.21.41.41.41.61.61.8
0.90.90.91.251.251.251.61.61.62.02.02.52.52.52.52.53.15
1.3 1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.1 2.2 2.3 2.4 2.6 2.7 2.9 3.2
12.9 14.6 15.9 18.1 20.2 22.1 25.5 27.8 31.1 36.7 40.3 45.6 49.9 54.7 60.5 65.9 74.6
10001000100010001000100010001000100010001000500500500250250250
34
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
FIVE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
61016
253550
70
1.62.02.6
3.14.04.7
5.97.08.1
9.7
0.60.70.7
0.70.70.7
0.90.91.0
1.1
0.80.80.8
0.80.81.0
1.01.01.2
1.2
0.90.90.9
1.251.251.6
1.61.62.0
2.0
1.4 1.4 1.5 1.5 1.6 1.7 1.8 1.9 2.0 2.2
13.9 15.5 17.2 19.4 21.9 25.6 30.2 33.2 38.6 43.9
100010001000
100010001000
100010001000
1000
SEVEN CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
1.62.02.6
0.60.70.7
0.80.80.8
0.90.91.25
1.4 1.4 1.5
14.7 16.5 19.1
100010001000
TWELVE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
1.62.02.6
0.60.70.7
0.80.81.0
1.251.251.6
1.5 1.6 1.6
18.8 21.6 25.4
100010001000
Armouring wire
diameter
Armouring wire
diameter
35
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
NINETEEN CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
1.62.02.6
0.60.70.7
0.81.01.0
1.251.61.6
1.6 1.7 1.7
21.4 26.2 28.9
100010001000
TWENTY SEVEN CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
1.62.02.6
0.60.70.7
1.01.01.0
1.61.61.6
1.7 1.8 1.9
26.3 30.3 33.9
100010001000
THIRTY SEVEN CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
1.62.02.6
0.60.70.7
1.01.01.2
1.61.62.0
1.7 1.8 2.0
28.7 33.2 38.6
100010001000
36
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 0.6/1 (1.2)kV
FOURTY EIGHT CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
1.52.54
1.62.02.6
0.60.70.7
1.01.01.2
1.61.62.0
1.7 1.8 2.0
32.1 38.7 43.4
100010001000
Armouring wire
diameter
37
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 1.9/3.3 (3.6)kV
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
507095
120150185
240300400
500630
8.19.7
11.5
12.914.316.0
18.420.623.3
26.329.9
2.02.02.0
2.02.02.0
2.02.02.0
2.22.4
0.80.80.8
1.01.01.0
1.01.01.2
1.21.2
1.251.251.25
1.61.61.6
1.61.62.0
2.02.0
1.6 1.6 1.6 1.7 1.7 1.8 1.8 1.9 2.0 2.1 2.2
19.4 21.0 22.8 25.9 27.3 29.2 31.6 34.0 38.1 41.7 45.9
100010001000
100010001000
100010001000
1000500
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per cable*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
507095
120150185
240300400
500630
203248297
336377425
491553626
706792
198242290
328368415
480540612
690776
252314382
439498570
672769888
10211171
0.8780.6220.464
0.3840.3260.279
0.2350.2100.192
0.1770.167
0.35910.41850.4817
0.53310.58420.6460
0.73090.81030.9078
0.93080.9674
0.3464 0.4037 0.4646 0.5142 0.5635 0.6231 0.7050 0.7816 0.8756 0.8978 0.9332
0.1158 0.1093 0.1040 0.1040 0.1008 0.0979 0.0938 0.0913 0.0907 0.0887 0.0866
38
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 1.9/3.3 (3.6)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Buried directin ground
In single-way PEduct inground
In tray inair (indoor)
Maximum current rating per conductor*
Maximum ReactanceMaximum Capacitance
Minimum charging current
Maximum3 phasevoltage
drop
mm2 A AA
Trefoil Trefoil Trefoil
mV/A/m A/km μF/km ohm/km
162535
507095
120150185
240300400
113144172
203248297
336377425
491553626
106136163
198242290
328368415
480540612
123161196
252314382
439498570
672769888
2.5461.6151.169
0.8660.6070.446
0.3630.3020.253
0.2080.1810.161
0.2340.2790.318
0.6530.7710.897
0.8281.1011.224
1.3931.5611.759
0.2256 0.2691 0.3062 0.6301 0.7437 0.8648 0.7990 1.0617 1.1806 1.3439 1.5052 1.6970
0.1024 0.0962 0.0922 0.0748 0.0727 0.0710 0.0711 0.0684 0.0675 0.0662 0.0655 0.0648
THREE CORE - CU / XLPE / PVC / SWA / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominaldiameter ofconductor
Nominalinsulationthickness
Nominalthicknessof innersheath
Armouring wire
diameter
Standardpackinglength
Nominal thickness of PVC outer sheath
Approximate overalldiameter
mm2 mm mm mmmm mm mm m/drum
162535
507095
120150185
240300400
4.75.9
6.1 x 9.5
7.2 x 11.28.7 x 13.5
10.2 x 15.9
11.5 x 17.912.8 x 19.814.3 x 22.2
16.4 x 25.518.4 x 28.520.8 x 32.3
2.02.02.0
2.02.02.0
2.02.02.0
2.02.02.0
1.01.01.0
1.21.21.2
1.41.41.4
1.61.61.6
1.61.61.6
2.02.02.0
2.52.52.5
2.52.52.5
1.8 1.8 1.9 2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.9
28.1 30.7 30.4 34.0 37.1 40.2 44.6 47.5 50.6 55.3 59.2 64.3
100010001000
100010001000
1000500500
500250250
39
Central Cables Berhad
SINGLE CORE - XLPE INSULATED UNARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
DESCRIPTION Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, with copper tape or copper wire or aluminium wire screen and extruded outer sheath made from MDPE or HDPE or PVC. CONSTRUCTION Conductor Plain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228. Conductor wrapping Applied when cable voltage rated at 19/33kV and aluminium conductor size reach 400mm² or above A layer of helically wrap semi-conductive tape with overlap laid over stranded conductor. Conductor screen An extruded thin layer of semi-conductive compound as a 1st layer by triple extrusion process. Insulation An extruded layer of cross-linked polyethylene(XLPE) compound as a 2nd layer by triple extrusion process. Insulation screen An extruded thin layer of semi-conductive compound as a 3rd layer by triple extrusion process. Semi-conductive tape Applied under copper wire screen or aluminium wire screen when requested by purchaser A layer of helically wrap semi-conductive water blocking tape with overlap laid over insulation screen. Metallic screen 1 or 2 layer(s) of Copper tape(CTS) helically wrap with overlap laid over insulation screen or numbers of copper wires(CWS) or numbers of aluminium wires(AWS) laid over semi-conductive tape. An equalizing copper tape with open helically wrap and metallic screen construction base on customer’s earth fault current requirement are available upon request. Binder tape Applied when necessary A layer of non-conductive or semi-conductive tape helically wrap with overlap laid over metallic screen. Outer sheath Extruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent or different outer sheath colour are available upon request.
Conductor
Insulation Screen
Conductor ScreenXLPE Insulation
Semi-ConductiveTapeCopper Wire Screen
Binder Tape
PVC Sheath
40
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
Approximate overall diameter
Standard packing length
mm m/drum
1.5 1.5 1.5 1.6 1.6 1.7 1.7 1.8 1.8 1.9 2.0 2.1 2.2 2.3
15.7 16.9 18.0 19.3 20.9 22.9 24.3 25.9 27.6 30.4 33.2 36.5 40.1 43.9
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
mm2 mm mm mm mm
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
2.52.52.5
2.52.52.5
2.52.52.5
2.62.83.0
3.23.2
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.51.51.5
1.61.61.7
1.71.81.8
1.92.02.1
2.22.3
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE
duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
107137164
193236283
321360407
472533605
684770
162535
507095
120150185
240300400
500630
113144172
203248296
336377425
491552623
694783
123161196
236296362
419478550
652751870
10041151
2.5501.6201.180
0.8780.6220.464
0.3810.3240.275
0.2320.2080.188
0.1740.169
0.17680.20500.2298
0.25640.29410.3342
0.36670.39880.4378
0.48020.50600.5394
0.57600.6400
mm² A A A mV/A/m A/km ohm/km ohm/km
41
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
2.52.52.5
2.52.52.5
2.52.52.5
2.62.83
3.23.2
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.5 1.5 1.5 1.6 1.6 1.7 1.7 1.8 1.8 1.9 2.0 2.1 2.2 2.3
15.7 17.0 18.0 19.4 21.0 23.0 24.4 26.0 27.8 30.5 33.3 36.7 40.1 44.1
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
82106126
149183219
249279316
368416477
545622
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
87120144
169207247
281314356
412465531
603686
95126153
183230282
326372429
511589691
777940
4.2482.6741.935
0.2471.0850.734
0.5890.4890.401
0.3210.2730.233
0.2040.183
0.17680.20600.2309
0.25780.05480.3360
0.36920.40110.4407
0.48300.50850.5430
0.57900.6488
1.9485 + j0.1391 1.2243 + j0.1294 0.8856 + j0.1230 0.0675 + j0.1152 0.4521 + j0.2640 0.3270 + j0.1041 0.2588 + j0.0997 0.2111 + j0.0972 0.1685 + j0.0942 0.1292 + j0.0911 0.1042 + j0.0896 0.0822 + j0.0878 0.0654 + j0.0862 0.0526 + j0.0837
8.3931 + j0.0805 7.0912 + j0.0721 6.3286 + j0.0665 5.1139 + j0.0589 5.0201 + j0.2089 4.4833 + j0.0493 4.1233 + j0.0456 3.8301 + j0.0433 3.5528 + j0.0410 3.1585 + j0.0384 2.8619 + j0.0372 2.5679 + j0.0359 2.3218 + j0.0347 2.0875 + j0.0327
mm² A A A mV/A/m A/km ohm/km ohm/km
42
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal cross
sectionalarea
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
2.52.52.5
2.52.52.5
2.52.52.5
2.62.83
3.23.2
16.016.016.0
16.016.016.0
16.025.025.0
25.025.035.0
35.035.0
1.5 1.5 1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.2 2.3 2.4
19.8 21.0 22.2 23.4 25.2 26.9 28.6 30.0 31.9 34.4 37.2 40.7 44.4 48.2
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
79101120
142173207
235263296
342385440
477556
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
96123147
173211252
286320361
417470536
590691
94123148
177222270
312353406
480552642
723866
4.2502.6761.942
1.4411.0060.738
0.5940.4940.407
0.3280.2800.241
0.2120.190
0.03130.03670.0414
0.04640.05350.0610
0.06720.07320.0806
0.08810.09210.0978
0.10390.1164
1.9485 + j0.1535 1.2243 + j0.1429 0.8856 + j0.1363 0.6541 + j0.1272 0.4522 + j0.1203 0.3269 + j0.1143 0.2587 + j0.1098 0.2109 + j0.1064 0.1683 + j0.1031 0.1290 + j0.0990 0.1039 + j0.0968 0.0818 + j0.0946 0.0650 + j0.0923 0.0521 + j0.0895
2.8582 + j0.0937 2.1284 + j0.0841 1.7850 + j0.0777 1.5483 + j0.0694 1.3390 + j0.0632 1.2061 + j0.0581 1.1317 + j0.0538 0.7990 + j0.0511 0.7530 + j0.0481 0.7085 + j0.0449 0.6787 + j0.0432 0.5007 + j0.0412 0.4799 + j0.0395 0.4630 + j0.0371
mm² A A A mV/A/m A/km ohm/km ohm/km
43
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
mm2 mm mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
3.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.5 1.6 1.6 1.6 1.7 1.7 1.8 1.8 1.9 2.0 2.0 2.2 2.2 2.4
17.5 18.9 20.0 21.1 22.9 24.7 26.3 27.7 29.6 32.2 34.4 37.5 40.5 44.5
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500
108138165
194238284
323362409
474534606
685770
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
114145174
205250299
339379428
494555628
705788
120157191
229286350
404460529
627719832
9591099
2.5531.6231.179
0.8810.6250.467
0.3850.3270.280
0.2370.2100.190
0.1750.164
0.25550.29550.3292
0.36540.41660.4708
0.51470.55810.6106
0.68240.74950.8317
0.92371.0331
1.7270 + j0.1463 0.7414 + j0.1367 0.5345 + j0.1299 0.3949 + j0.1211 0.2738 + j0.1148 0.1976 + j0.1090 0.1571 + j0.1049 0.1278 + j0.1017 0.1029 + j0.0958 0.0794 + j0.0949 0.0640 + j0.0920 0.0522 + j0.0896 0.0427 + j0.0868 0.0356 + j0.0847
4.6132 + j0.0894 3.9088 + j0.0801 3.4993 + j0.0740 3.1672 + j0.0659 2.8105 + j0.0600 2.5232 + j0.0551 2.3348 + j0.0511 2.1761 + j0.0454 2.1033 + j0.0457 1.8279 + j0.0422 1.6843 + j0.0399 1.5375 + j0.0376 1.4012 + j0.0354 1.2684 + j0.0334
mm² A A A mV/A/m A/km ohm/km ohm/km
44
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
3.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.5 1.6 1.6 1.6 1.7 1.7 1.8 1.8 1.9 2.0 2.0 2.2 2.2 2.4
17.5 19.0 20.0 21.2 23.0 24.8 26.4 27.8 29.8 32.3 34.5 37.7 40.5 44.7
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
83107127
150184220
315280318
369417478
545622
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
87112134
158193230
250293331
384453494
562638
93122148
178223272
262358413
490564660
768896
4.2492.6751.941
1.4391.0040.736
0.5920.4920.404
0.3240.2760.235
0.2050.184
0.15410.29680.3308
0.36730.41940.4732
0.51810.56120.6145
0.68640.75320.8371
0.92371.0398
1.9485 + j0.1459 1.2243 + j0.1364 0.8856 + j0.1296 0.6541 + j0.1208 0.4523 + j0.1144 0.3269 + j0.1088 0.2588 + j0.1054 0.2110 + j0.1023 0.1684 + j0.0993 0.1291 + j0.0947 0.1041 + j0.0918 0.0821 + j0.0894 0.0653 + j0.0868 0.0526 + j0.0845
7.5756 + j0.0891 6.4059 + j0.0799 5.7337 + j0.0738 5.1857 + j0.0657 4.5936 + j0.0597 4.1272 + j0.0549 3.1836 + j0.0509 3.5571 + j0.0483 3.2869 + j0.0455 2.9850 + j0.0506 2.7521 + j0.0398 2.5074 + j0.0374 2.2823 + j0.0353 2.0669 + j0.0333
mm² A A A mV/A/m A/km ohm/km ohm/km
45
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
3.43.4
16.016.016.0
16.016.016.0
16.025.025.0
25.025.035.0
35.035.0
1.5 1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.1 2.2 2.3 2.4
21.6 23.0 24.0 25.4 27.0 28.9 30.4 32.0 33.7 35.8 38.6 41.5 44.4 48.6
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
79102121
143174208
236263297
344387435
492557
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
96123147
173211252
286319361
417470533
605685
96125151
181225274
315357410
485556644
748867
4.2512.6771.943
1.4421.0080.740
0.5960.4970.410
0.3300.2830.242
0.2120.191
0.02650.03080.0344
0.03800.04400.0498
0.05460.05930.0651
0.07280.08010.0892
0.09930.1112
1.9485 + j0.1590 1.2243 + j0.1468 0.8856 + j0.1412 0.6541 + j0.1323 0.4522 + j0.1247 0.3269 + j0.1188 0.2587 + j0.1136 0.2109 + j0.1104 0.1683 + j0.1066 0.1289 + j0.1015 0.1038 + j0.0991 0.0818 + j0.0958 0.0650 + j0.0923 0.0521 + j0.0900
2.8500 + j0.1007 2.1203 + j0.0906 1.7770 + j0.0839 1.5403 + j0.0752 1.3313 + j0.0685 1.1985 + j0.0630 1.1241 + j0.0585 0.7956 + j0.0554 0.7496 + j0.0522 0.7056 + j0.0482 0.6762 + j0.0455 0.5000 + j0.0462 0.4795 + j0.0401 0.4626 + j0.0377
mm² A A A mV/A/m A/km ohm/km ohm/km
46
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE /CTS / PVC SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
1625355070
95120150
185240300
400500630
4.745.927.08.19.7
11.512.914.3
16.018.420.6
23.326.329.9
4.54.54.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
0.10.10.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.4
19.9 21.1 22.4 23.5 25.3 27.1 28.7 30.1 32.0 34.5 36.8 39.7 42.9 46.7
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
108139166
227293286
325364411
476537609
687773
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
113144172
203248297
336377425
491552625
703786
128168204
244305372
429488560
662759878
10111160
2.5541.6251.182
0.8830.6300.471
0.3890.3320.289
0.2420.2160.195
0.1800.176
0.30770.35360.3917
0.43240.48990.5504
0.59950.64790.7063
0.78630.86090.9521
1.05421.1756
1.1727 + j0.1545 0.7414 + j0.1436 0.5345 + j0.1370 0.3949 + j0.1278 0.2738 + j0.1210 0.1975 + j0.1149 0.1570 + j0.1104 0.1277 + j0.1105 0.1027 + j0.1069
0.0792 + j0.0994 0.0643 + j0.0962 0.0519 + j0.0932 0.0424 + j0.0904 0.0427 + j0.0877
4.1430 + j0.0987 3.5122 + j0.0885 3.1490 + j0.0819 2.8586 + j0.0734 2.5496 + j0.0668 2.3020 + j0.0614 2.1396 + j0.0570 2.0024 + j0.0576 1.8613 + j0.0509
1.6996 + j0.0470 1.5736 + j0.0443 1.4437 + j0.0417 1.3223 + j0.0392 1.2108 + j0.0368
mm2 A A A mV/A/m A/km ohm/km ohm/km
47
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
4.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.6 1.6 1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.1 2.1 2.2 2.3 2.4
19.9 21.2 22.4 23.6 25.4 27.2 28.8 30.2 32.2 34.7 36.9 39.9 42.9 46.9
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
84107128
151185221
252282320
371419480
548624
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
87112134
158193230
262293331
384433495
563639
95124151
181226276
319362417
49456864
771900
4.2502.6771.942
1.4411.0060.738
0.5940.4940.407
0.3280.2800.239
0.2100.188
0.30980.35510.3935
0.43460.49300.5532
0.60320.65130.7108
0.79070.86490.9582
1.05421.1830
1.9485 + j0.1540 1.2243 + j0.1433 0.8856 + j0.1367 0.6541 + j0.1275 0.4552 + j0.1207 0.3269 + j0.1146 0.2587 + j0.1101 0.2109 + j0.1067 0.1683 + j0.1034 0.1290 + j0.0992 0.1039 + j0.0960 0.0819 + j0.0930 0.0651 + j0.0904 0.0523 + j0.0875
6.8203 + j0.0981 5.7585 + j0.0882 5.1624 + j0.0816 4.2433 + j0.0731 4.1695 + j0.0665 3.7670 + j0.0612 3.4964 + j0.0568 3.2746 + j0.0538 3.0400 + j0.0507 2.7765 + j0.0468 2.5718 + j0.0442 2.3553 + j0.0415 2.1544 + j0.0390 1.9607 + j0.0367
mm2 A A A mV/A/m A/km ohm/km ohm/km
48
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE DIMENSION
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of MDPE sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm2 mm mm m/drum
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.330.1
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
4.54.5
16.016.016.0
16.016.016.0
16.025.025.0
25.025.035.0
35.035.0
1.61.71.7
1.71.81.8
1.92.02.1
2.12.22.3
2.42.5
24.025.426.4
27.629.4 31.1
32.834.4 36.1
38.641.0 43.9
47.251.0
100010001000
100010001000
100010001000
100010001000
500500
80103122
144176209
238265299
346389437
495660
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
162535
507095
120150185
240300400
500630
96123146
172211251
286319360
417470533
606730
98128154
184229277
320362415
490562651
755841
4.2512.6781.945
1.4441.0100.743
0.5990.4500.413
0.3340.2870.246
0.2170.195
0.02280.02620.0206
0.03230.03680.0414
0.04520.04980.0535
0.05690.06530.0725
0.08050.9060
1.9485 + j0.1656 1.2243 + j0.1549 0.8856 + j0.1475 0.6541 + j0.1375 0.4522 + j0.1300 0.3269 + j0.1234 0.2586 + j0.1184 0.2108 + j0.1149 0.1682 + j0.1109 0.1288 + j0.1062 0.1037 + j0.1029 0.0816 + j0.0994 0.0647 + j0.0962 0.0518 + j0.0932
2.8403 + j0.1083 2.1106 + j0.0978 1.7676 + j0.0912 1.5308 + j0.0816 1.3219 + j0.0744 1.1894 + j0.0685 1.1151 + j0.0637 0.7914 + j0.0604 0.7455 + j0.0569 0.7016 + j0.0526 0.6722 + j0.0469 0.4978 + j0.0464 0.4774 + j0.0436 0.4662 + j0.0410
mm2 A A A mV/A/m A/km ohm/km ohm/km
49
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 12.7/22 (24)kV
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
35
507095
120150185
240300400
500630
7.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
5.5
5.55.55.5
5.55.55.5
5.55.55.5
5.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.7 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5
24.4 25.7 27.3 29.3 30.7 32.3 34.0 36.6 39.0 41.9 45.1 48.9
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
167
197240288
326366413
478538610
689775
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
35
507095
120150185
240300400
500630
174
205254298
339379428
494556629
708792
206
247308375
432491564
666763881
10151164
1.184
0.8860.6310.475
0.3930.3360.289
0.2460.2210.200
0.1840.172
0.5167
0.56810.64040.7164
0.77790.83850.9117
1.01161.10471.2184
1.34571.4969
0.5345 + j0.1424 0.3949 + j0.1335 0.2737 + j0.1258 0.1975 + j0.1198 0.1569 + j0.1146 0.1276 + j0.1113 0.1026 + j0.1075 0.0791 + j0.1030 0.0641 + j0.0998 0.0516 + j0.0966 0.0421 + j0.0936 0.0348 + j0.0906
2.8954 + j0.0883 2.6321 + j0.0794 2.3550 + j0.0724 2.1345 + j0.0660 1.9902 + j0.0619 1.8683 + j0.0587 1.7427 + j0.0553 1.5984 + j0.0511 1.4853 + j0.0481 1.3682 + j0.0452 1.2580 + j0.0424 1.1491 + j0.0398
mm2 A A A mV/A/m A/km ohm/km ohm/km
50
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
128
151186222
253283322
373421482
550626
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
35
507095
120150185
240300400
500630
134
158193230
262293331
384433495
563640
152
183228278
321365420
497570666
775905
1.943
1.4421.0080.741
0.5960.4970.410
0.3320.2830.243
0.2130.191
0.5190
0.57050.64430.7692
0.78270.84280.9172
1.01711.10971.2260
1.35541.5061
0.0886 + j0.1420 0.6541 + j0.1331 0.4522 + j0.1254 0.3269 + j0.1195 0.2687 + j0.1143 0.2109 + j0.1111 0.1683 + j0.1072 0.1289 + j0.1027 0.1038 + j0.0997 0.0818 + j0.0964 0.0649 + j0.0934 0.0520 + j0.0904
4.7486 + j0.0880 4.3135 + j0.0791 3.8528 + j0.0721 3.4940 + j0.0664 3.2535 + j0.0617 3.0562 + j0.0585 2.8473 + j0.0551 2.6118 + j0.0509 2.4281 + j0.0480 2.2326 + j0.0450 2.0503 + j0.0422 1.8734 + j0.0396
mm2 A A A mV/A/m A/km ohm/km ohm/km
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 12.7/22 (24)kV
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Metallic screening
Nominal thickness of PVC sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
35
507095
120150185
240300400
500630
7.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
5.5
5.55.55.5
5.55.55.5
5.55.55.5
5.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.7 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.3 2.4 2.5
24.4 25.8 27.4 29.4 30.8 32.4 34.2 36.7 30.1 42.1 45.3 49.1
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
51
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 12.7/22 (24)kV
1625355070
95120150
185240300
400500630
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
SINGLE CORE - AL / XLPE / CWS / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal cross-
sectional area
Metallic screening
Nominal thickness of MDPE sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm2 mm mm m/drum
4.75.927.08.19.7
11.512.914.3
16.018.420.6
23.326.330.1
5.55.55.55.55.5
5.55.55.5
5.55.55.5
5.55.55.5
16.016.016.016.016.0
16.016.025.0
25.025.025.0
35.035.035.0
1.7 1.7 1.8 1.8 1.9 1.9 2.0 2.0 2.1 2.2 2.2 2.3 2.4 2.5
26.2 27.4 28.6 29.8 31.6 33.3 35.0 36.4 38.3 40.8 43.0 45.9 49.2 53.0
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
162535
507095
120150185
240300400
500630
*Note : Electrical properties are calculated base on conditions in appendix B.
80103123
145176210
239266300
347391439
498731
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
95123146
172210251
285318360
417469533
606663
99129156
186231281
323365419
494566655
759847
4.2522.6791.946
1.4451.0110.745
0.6010.5020.416
0.3380.2900.249
0.2200.198
0.02060.02350.026
0.02870.03240.0363
0.03960.04270.0465
0.05170.05650.0625
0.06920.0702
1.9485 + j0.1711 1.2243 + j0.1596 0.8856 + j0.1522 0.6541 + j0.1423 0.4522 + j0.1345 0.3268 + j0.1277 0.2586 + j0.1224 0.2108 + j0.1185 0.1682 + j0.1146 0.1287 + j0.1096 0.1036 + j0.1059 0.0815 + j0.1021 0.0646 + j0.0987 0.0516 + j0.0954
2.8315 + j0.1145 2.1020 + j0.1036 1.7589 + j0.0962 1.5224 + j0.0869 1.3136 + j0.0794 1.1812 + j0.0732 1.1070 + j0.0681 0.7877 + j0.0646 0.7418 + j0.0609 0.6978 + j0.0563 0.6686 + j0.0530 0.4959 + j0.0496 0.4755 + j0.0466 0.4662 + j0.0409
mm2 A A A mV/A/m A/km ohm/km ohm/km
52
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 19/33 (36)kV
507095
120150185
240300400
500630
SINGLE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal cross-
sectional area
Metallic screening
Nominal thickness of MDPE sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
8.08.08.0
8.08.08.0
8.08.08.0
8.08.0
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7
31.1 32.7 34.7 36.1 37.7 39.4 42.0 44.4 47.3 50.5 54.3
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
507095
120150185
240300400
500630
199243291
330370417
482543615
694779
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
204250298
338379427
494556630
710796
241300365
419476545
642734848
9751118
0.8910.6380.483
0.4020.3460.299
0.2570.2310.211
0.1950.183
0.69990.78140.8667
0.93531.00281.084
1.19461.29751.3889
1.56301.7291
0.3949 + j0.1454 0.2737 + j0.1371 0.1974 + j0.1304 0.1568 + j0.1248 0.1275 + j0.1210 0.1024 + j0.1167 0.0788 + j0.1116 0.0638 + j0.1080 0.5012 + j0.1042 0.0415 + j0.1007 0.0342 + j0.0972
mm2 A A A mV/A/m A/km ohm/km ohm/km
2.2141 + j0.0924 1.9884 + j0.0846 1.8130 + j0.0780 1.6996 + j0.0728 1.6041 + j0.0690 1.5061 + j0.0651 1.3930 + j0.0602 1.3039 + j0.0567 1.2109 + j0.031 1.1225 + j0.0498 1.0340 + j0.0466
53
507095
120150185
240300400
500630
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 19/33 (36)kV
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal cross-
sectional area
Metallic screening
Nominal thickness of MDPE sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm mm mm m/drum
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
8.08.08.0
8.08.08.0
8.08.08.0
8.08.0
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7
31.2 32.8 34.8 36.2 37.8 30.6 42.1 44.5 47.5 50.7 54.5
1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500
SINGLE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
507095
120150185
240300400
500630
154188225
256286324
376424485
553630
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
158193230
262293331
384433495
372641
188233283
326370425
502575670
779905
1.1461.0120.746
0.6020.5040.417
0.3390.2920.252
0.2220.201
0.70300.78590.8705
0.94061.00761.0901
1.20071.30311.4313
1.57361.7392
3.6312 + j0.0921 3.2258 + j0.0842 2.9698 + j0.0778 2.7805 + j0.0725 2.6258 + j0.0688 2.4623 + j0.0648 2.2775 + j0.0600 2.1325 + j0.0565 1.9770 + j0.0529 1.8304 + j0.0496 1.6864 + j0.0464
mm2 A A A mV/A/m A/km ohm/km ohm/km
0.6541 + j0.1451 0.4522 + j0.1367 0.3268 + j0.1301 0.2568 + j0.1245 0.2108 + j0.1208 0.1682 + j0.1164 0.1287 + j0.1114 0.1036 + j0.1078 0.0815 + j0.1040 0.0645 + j0.1004 0.0515 + j0.0970
54
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 19/33 (36)kV
*Note : Electrical properties are calculated base on conditions in appendix B. #Note-630TNB : Refer to the TNB specification, earth fault rating 25kA in 3 second.
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE DIMENSION
Nominal cross-
sectional area of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal cross-
sectional area
Metallic screening
Nominal thickness of MDPE sheath
Approximate overall diameter
Standard packing length
mm2 mm mm mm2 mm mm m/drum
4.75.926.978.19.7
11.512.914.3
16.018.420.6
23.326.330.130.1
8.08.08.08.08.0
8.08.08.0
8.08.08.0
8.08.08.09.0
16.016.016.016.016.0
16.016.025.0
25.025.025.0
35.035.035.0312.0
1.9 1.9 1.9 2.0 2.0 2.1 2.1 2.2 2.2 2.3 2.4 2.5 2.6 2.7 5.0
32.2 33.4 34.4 35.8 37.4 39.3 40.8 42.4 44.1 46.6 49.0 51.9 55.2 59.0 69.4
1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 500 500 500
SINGLE CORE - AL / XLPE / CWS / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
82105124147179213
242269304
309395445
504671502
Nominal cross-
sectional area of
conductor
Maximum current rating per cable*
Buried direct in ground
Trefoil Trefoil Trefoil
In single-way PE duct in ground
In tray in air (indoor)
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence
impedance at 25°C*
Zero sequence impedance at 25°C*
95122146172210251
285318360
416469533
607733614
103133161192238288
331373428
503575666
771858827
4.2542.6821.9481.4481.1020.750
0.6070.5090.423
0.3460.2990.259
0.2300.2080.222
0.01680.01890.02070.02260.02530.0281
0.03040.03250.0352
0.03880.03600.0464
0.05100.06120.0610
1.9485 + j0.1841 1.2243 + j0.1720 0.8856 + j0.1637 0.6541 + j0.1538 0.4522 + j0.1457 0.3268 + j0.1380 0.2586 + j0.1321 0.2107 + j0.1281 0.1681 + j0.1234 0.1286 + j0.1180 0.1034 + j0.1141 0.0813 + j0.1098 0.0643 + j0.1060 0.0512 + j0.1021 0.0508 + j0.1112
2.8079 + j0.1292 2.0787 + j0.1176 1.7358 + j0.1096 1.4997 + j0.0998 1.2912 + j0.0915 1.1591 + j0.0846 1.0852 + j0.0790 0.7775 + j0.0751 0.7317 + j0.0708 0.6880 + j0.0656 0.6589 + j0.0618 0.4906 + j0.0579 0.4703 + j0.0543 0.4703 + j0.0507 0.1046 + j0.0572
mm2 A A A mV/A/m A/km ohm/km ohm/km
1625355070
95120150
185240300
400500630
630TNB#
162535507095
120150185
240300400
500630
630TNB#
55
Central Cables Berhad
SINGLE CORE - XLPE INSULATED UNARMOURED DOUBLE SHEATHED CABLE FOR VOLTAGES 11kV AND 22kV TO IEC 60502-2
DESCRIPTION Circular compacted stranded aluminium conductor, cross-linked polyethylene, with copper tape or copper wire or aluminium wire screen and extruded outer sheath made from MDPE. Complies with Tenaga Nasional Berhad (TNB) specification. CONSTRUCTION Conductor Aluminium(AL) conductor conform to class 2 in IEC 60228.
Conductor wrapping Applied when cable voltage rated at 19/33kV and aluminium conductor size reach 400mm² or above A layer of helically wrap semi-conductive tape with overlap laid over stranded conductor. Conductor screen An extruded thin layer of semi-conductive compound as a 1st layer by triple extrusion process. Insulation An extruded layer of cross-linked polyethylene(XLPE) compound as a 2nd layer by triple extrusion process. Insulation screen An extruded thin layer of semi-conductive compound as a 3rd layer by triple extrusion process. Metallic screen Two layers of copper tape(CTS) helically wrap with overlap laid over insulation screen. Non-conductive binder tape Applied when necessary. A layer of non-conductive tape helically wrap with overlap laid over metallic screen. Inner Sheath Extruded layer made from black MDPE compound. Non-conductive binder tape A layer of non-conductive tape helically wrap with overlap laid over inner sheath. Outer sheath Extruded layer made from MDPE compound. Additive like Anti-termite repellent, anti-rodent or different outer sheath colour are available upon request.
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Copper Tape Screen
MDPE Inner Sheath
Separation Tape
MDPE Outer Sheath
56
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / MDPE / MDPE SHEATHED CABLE DIMENSION
162535
50 70#
95
120150185
240300400
500#
630
4.75.97.0
8.19.711.5
13.014.416.2
18.520.723.5
26.530.1
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
3.43.4
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 2
2.22.22.2
2.22.22.2
2.22.22.2
2.22.22.2
2.22.2
1.51.61.6
1.71.71.8
1.81.91.9
2.02.12.2
2.32.4
22.523.924.9
26.328.029.9
31.332.934.7
37.239.642.6
45.949.7
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Nominal thickness of MDPE inner sheath
Nominal thickness of MDPE inner sheath
Nominal thickness of MDPE inner sheath
Metallic screening
mm2 mm mm mm mm mmmm x n
SINGLE CORE - AL / XLPE / CTS / MDPE / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
50 70#
95
120150185
240300400
500#
630
87111133
157191229
260290328
380428457
553626
84108128
151185221
251281317
367413470
532599
96125152
181226275
318360414
489561653
758877
4.9082.6781.944
1.4431.0080.741
0.5970.4980.411
0.3320.2840.244
0.2140.192
0.28020.32550.3184
0.40590.46530.5268
0.57810.62740.6886
0.77100.84760.9439
1.05130.1112
1.9485 + j0.16151.2243 + j0.15090.8856 + j0.1426
0.6541 + j0.13440.4522 + j0.12660.3269 + j0.1206
0.2587 + j0.11540.2109 + j0.11210.1683 + j0.1081
0.1289 + j0.10360.1038 + j0.10050.0817 + j0.0972
0.0649 + j0.09410.0520 + j0.0911
29.0001 + j0.090326.1738 + j0.081024.2571 + j0.0748
22.5249 + j0.066720.4678 + j0.060718.0558 + j0.0558
17.4763 + j0.051716.4303 + j0.049015.2975 + j0.0462
13.9988 + j0.042712.9752 + j0.040411.8824 + j0.0380
10.8628 + j0.0358 9.8741 + j0.0337
57
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 12.7/22 (24)kV
SINGLE CORE - AL / XLPE / CTS / MDPE / MDPE SHEATHED CABLE DIMENSION
162535
50 70#
95120
150#
185 240#
300
400 500#
630
4.76.07.0
8.29.8
11.613.014.4
16.218.520.7
23.526.530.1
5.55.55.5
5.55.5
5.55.55.5
5.55.55.5
5.55.55.5
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
2.22.22.2
2.22.2
2.22.22.2
2.22.22.2
2.22.22.2
1.71.71.8
1.81.9
1.92.02.0
2.12.22.2
2.32.42.5
27.128.329.5
30.732.6
34.335.937.3
39.341.844.0
47.050.354.1
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Nominal thickness of MDPE inner sheath
Nominal thickness of MDPE inner sheath
Approximate overall diameter
Metallic screening
mm2 mm mm mm mm mmmm x n
SINGLE CORE - AL / XLPE / CTS / MDPE / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
50 70#
95
120 150#
185
240#
300400
500#
630
87112133
157192229
260290328
380428488
554626
85109130
153187223
253283320
370415472
534601
98128155
185230280
322365419
494565657
762821
4.2522.6801.946
1.4451.0120.746
0.6020.5810.417
0.3390.2910.251
0.2040.200
0.43510.49740.5502
0.60660.68670.7692
0.83770.90340.9848
1.09411.19551.3229
1.46471.6300
1.9485 + j0.17321.2243 + j0.16160.8856 + j0.1540
0.6541 + j0.14410.4522 + j0.13620.3268 + j0.1293
0.2586 + j0.12400.2108 + j0.11990.1682 + j0.1160
0.1287 + j0.11090.1036 + j0.10710.0815 + j0.1033
0.0654 + j0.08620.0516 + j0.0964
22.9179 + j0.106320.9080 + j0.095919.5739 + j0.0889
18.3703 + j0.080016.9312 + j0.072915.6878 + j0.0671
14.7930 + j0.062314.0274 + j0.059113.1857 + j0.0557
12.2030 + j0.051411.4140 + j0.048510.5567 + j0.0455
9.7420 + j0.04278.9378 + j0.0400
*Note : Electrical properties are calculated base on conditions in appendix B.
58
Central Cables Berhad
THREE CORE - XLPE INSULATED UNARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
DESCRIPTION
Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, with copper tape or copper wire or aluminium wire screen and extruded outer sheath made from MDPE or HDPE or PVC.
CONSTRUCTION
ConductorPlain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228.
Conductor wrappingApplied when cable voltage rated at 19/33kV and aluminium conductor size reach 400mm² or aboveA layer of helically wrap semi-conductive tape with overlap laid over stranded conductor.
Conductor screenAn extruded thin layer of semi-conductive compound as a 1st layer by triple extrusion process.
Insulation An extruded layer of cross-linked polyethylene(XLPE) compound as a 2nd layer by triple extrusion process. Insulation screen An extruded thin layer of semi-conductive compound as a 3rd layer by triple extrusion process.
Colour of core Identification Red, yellow and blue shall be applied over insulation screen.
Semi-conductive tape Applied under copper wire screen or aluminium wire screen when requested by purchaser A layer of helically wrap semi-conductive water blocking tape with overlap laid over insulation screen.
Metallic screen 1 or 2 layer(s) of Copper tape(CTS) helically wrap with overlap laid over insulation screen or numbers of copper wires(CWS) or numbers of aluminium wires(AWS) laid over semi-conductive tape. An equalizing copper tape with open helically wrap and metallic screen construction base on customer’s earth fault current requirement are available upon request.
Lay Up Cores Three screened core are laid up together with non hygroscopic material
PVC Outer Sheath
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Copper Tape Screen
Non-HygroscopicFilter
Binder Tope
59
Central Cables Berhad
THREE CORE - XLPE INSULATED UNARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
Binder tape Applied when necessaryA layer of non-conductive or semi-conductive tape helically wrap with overlap. Outer sheath Extruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent ordifferent outer sheath colour are available upon request.
60
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
2.52.52.5
2.52.52.5
2.52.52.5
2.62.83.0
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.51.51.5
1.61.61.7
1.71.81.8
1.92.02.1
15.716.918.0
19.320.922.9
24.325.927.6
30.433.236.7
100010001000
100010001000
10001000500
500500250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
507095
120150185
240300400
119144182
203261309
349395425
505562628
107116140
193203283
275304351
456456514
113148179
236263320
364414470
588626707
2.5491.6181.173
0.8770.6160.457
0.3740.3150.266
0.2230.1970.177
0.17680.20500.2298
0.5050.29410.3342
0.36670.39880.4378
0.48020.50600.5394
1.7271 + j0.12410.7415 + j0.11580.5346 + j0.1103
0.4000 + j0.11200.2740 + j0.09740.1979 + j0.0930
0.1375 + j0.08940.1283 + j0.08700.1035 + j0.0847
0.0802 + j0.08210.0654 + j0.08090.0532 + j0.0796
2.4824 + j0.08051.9373 + j0.07231.6444 + j0.0667
3.2300 + j0.05701.2067 + j0.05381.0455 + j0.0495
0.9462 + j0.04580.8661 + j0.04350.7874 + j0.0411
0.6969 + j0.03850.6257 + j0.03730.5580 + j0.0360
61
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
2.52.52.5
2.52.52.5
2.52.52.5
2.52.52.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
2.02.12.1
2.22.42.5
2.62.72.8
3.03.23.4
31.134.036.3
38.941.946.8
50.253.557.5
63.469.476.6
100010001000
100010001000
1000500500
500500250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
507095
120150185
240300400
94119141
165202243
274305348
399447506
7191
109
128157190
216242276
321362415
90116139
164205251
287323376
439498572
4.2472.6731.937
1.4350.9990.730
0.5840.4830.394
0.3140.2660.225
0.17680.20600.2309
0.25180.29620.3360
0.36920.40110.4407
0.48300.50850.5430
1.9486 + j0.12411.2234 + j0.11560.8857 + j0.1100
0.6542 + j0.10250.4524 + j0.09710.3271 + j0.0929
0.2590 + j0.08920.2113 + j0.08690.1688 + j0.0845
0.1296 + j0.08190.0828 + j0.07940.0828 + j0.0794
4.0967 + j0.08053.1799 + j0.07212.6999 + j0.0665
2.3365 + j0.05891.9748 + j0.05361.7122 + j0.0493
1.5467 + j0.04561.4171 + j0.04331.2861 + j0.0410
1.1383 + j0.03841.0225 + j0.03720.9096 + j0.0359
62
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
2.12.22.3
2.42.52.6
2.72.82.9
3.13.33.5
35.138.040.4
43.146.850.8
54.057.461.3
66.771.978.1
100010001000
100010001000
10001000500
500500250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
507095
120150185
240300400
119152182
213260311
352390610
504564628
92119142
167205246
279313352
408460516
116151180
215249325
373417473
553640721
2.5501.6201.175
0.8760.6190.461
0.3770.3190.271
0.2260.2000.179
0.25550.29550.2955
0.36540.41660.4708
0.51470.55810.6106
0.68240.74950.8317
1.1727 + j0.13300.7415 + j0.12370.5346 + j0.1176
0.3950 + j0.10950.2739 + j0.10360.1978 + j0.0987
0.1573 + j0.09470.1281 + j0.09200.1033 + j0.0893
0.0799 + j0.08580.0652 + j0.08350.0530 + j0.0811
2.3195 + j0.08941.7972 + j0.08011.5227 + j0.0740
1.3190 + j0.06591.1192 + j0.06000.9726 + j0.0551
0.0826 + j0.05110.8101 + j0.04840.7390 + j0.0457
0.6613 + j0.04220.6032 + j0.03990.5456 + j0.0376
63
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
2.12.22.3
2.42.52.6
2.72.82.9
3.13.33.5
35.238.040.4
43.247.050.9
54.257.661.6
67.072.178.5
100010001000
100010001000
100010001000
500500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
507095
120150185
240300400
92118140
166202241
273307345
402449506
7292
110
130159191
216245278
324365415
90117140
167208252
288330375
446503574
4.2482.6741.938
1.4361.0000.732
0.5860.4860.397
0.3170.2680.226
0.25690.29680.3308
0.36730.41940.4732
0.51810.56120.6145
0.68640.75320.8371
1.9485 + j0.13261.2243 + j0.12340.8857 + j0.1173
0.6542 + j0.10920.4523 + j0.10330.3230 + j0.0985
0.2589 + j0.09440.2112 +j0.09180.1687 + j0.0861
0.1294 + j0.08560.1045 + j0.08330.0826 + j0.0810
3.8242 + j0.09812.9514 + j0.07992.5016 + j0.0738
2.1646 + j0.06571.8326 + j0.05971.5935 + j0.0549
1.4435 + j0.05091.3261 + j0.04831.2075 + j0.0455
1.0804 + j0.04210.9859 + j0.03980.8894 + j0.0374
64
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
2.32.42.5
2.62.72.8
2.93.03.1
3.33.43.7
40.443.145.5
48.251.955.9
59.262.566.4
71.976.783.3
100010001000
100010001000
1000500500
500500250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
507095
120150185
240300400
119153182
214260310
352391440
505561628
9496
144
170208249
283317358
411460515
118152185
219270327
379423432
554623722
2.5521.6221.178
0.8790.6230.465
0.3820.3240.276
0.2320.2050.184
0.30770.35360.3917
0.43240.48990.5504
0.59950.64790.7063
0.78630.86090.9459
1.7270 + j0.14220.7415 + j0.13210.5345 + j0.1255
0.3950 + j0.11660.2738 + j0.11040.1977 + j0.1050
0.1572 + j0.10060.1279 + j0.09760.1030 + j0.0945
0.0796 + j0.09060.0648 + j0.08790.0526 + j0.0852
2.1628 + j0.09871.6650 + j0.08851.4060 + j0.0819
1.2161 + j0.07341.0322 + j0.06680.8988 + j0.0614
0.8175 + j0.05700.7522 + j0.05400.6883 + j0.0509
0.6185 + j0.04700.5663 + j0.04430.5143 + j0.0417
65
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
4.76.07.0
8.29.811.6
13.014.416.0
18.420.623.3
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
2.32.42.5
2.62.72.8
2.93.03.1
3.33.43.7
40.443.245.7
48.452.156.1
59.462.866.7
72.277.183.6
100010001000
100010001000
10001000500
500500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
507095
120150185
240300400
93118141
166203241
275306343
393440496
7294
112
132162194
221247323
323363413
92119143
170211255
295330442
442500569
4.2492.6751.940
1.4381.0030.734
0.5890.4890.401
0.3210.2720.230
0.30980.35510.3935
0.43460.49300.5532
0.60320.61140.7108
0.79070.86490.9582
1.9485 + j0.14171.2243 + j0.13180.8856 + j0.1252
0.6541 + j0.11660.4523 + j0.11010.3270 + j0.1048
0.2588 + j0.10030.2111 + j0.09740.1685 + j0.0943
0.1292 + j0.09040.1043 + j0.08760.0824 + j0.0850
3.5725 + j0.09812.7357 + j0.08822.3112 + j0.0816
1.9969 + j0.07311.6912 + j0.06651.4735 + j0.0612
1.3377 + j0.05681.2319 + j0.05071.1252 + j0.0507
1.0110 + j0.04680.9258 + j0.04420.8387 + j0.0415
66
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 12.7/22 (24)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
355070
95120150
185240300
400
7.08.19.7
11.512.914.3
16.018.420.6
23.3
5.55.55.5
5.55.55.5
5.55.55.5
5.5
0.10.10.1
0.10.10.1
0.10.10.1
0.1
2.62.72.8
2.93.03.1
3.33.43.6
3.8
50.152.756.5
60.463.767.0
71.176.481.5
87.8
100010001000
10001000500
500500250
250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
355070
95120150
185240300
400
181214260
310352393
438165560
624
146172210
251286321
361416464
520
186222274
330379430
435563636
716
1.1800.8810.626
0.4680.3860.328
0.2800.2360.210
0.189
0.51670.56810.6406
0.71640.77790.8385
0.91171.01161.1047
1.2184
0.5345 + j0.13190.3949 + j0.12300.2738 + j0.1157
0.1976 + j0.11020.1571 + j0.10550.1278 + j0.1022
0.1029 + j0.09890.0794 + j0.09460.0646 + j0.0917
0.0522 + j0.0887
1.3214 + j0.08831.1406 + j0.07940.9674 + j0.0724
0.8430 + j0.06660.7678 + j0.06190.7075 + j0.0587
0.6488 + j0.05520.5847 + j0.05110.5368 + j0.0481
0.4891 + j0.0452
67
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 12.7/22 (24)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
35
507095
120150185
240300400
7.0
8.29.811.6
13.014.416.2
18.520.723.5
5.5
5.55.55.5
5.55.55.5
5.55.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
2.6
2.72.82.9
3.03.13.3
3.43.63.8
50.2
52.956.670.4
63.967.371.4
76.981.888.2
1000
100010001000
1000500500
500500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
35
507095
120150185
240300400
141
166203242
301304345
402448505
116
134164196
252248283
330370424
145
173213258
310330379
450505575
1.941
1.9391.0040.470
0.5920.4920.404
0.3240.2750.234
0.5190
0.57080.64430.7164
0.78270.84280.9172
1.01711.10971.2260
0.8856 + j0.1316
0.8868 + j0.12270.4522 + j0.11570.1977 + j0.1102
0.2588 + j0.10520.2110 + j0.10200.1648 + j0.0986
0.1291 + j0.09440.1041 + j0.09150.0822 + j0.0885
2.1733 + j0.0880
12.1054 + j0.07911.5857 + j0.07211.2564 + j0.0666
1.2568 + j0.06171.1591 + j0.05851.0610 + j0.0551
0.9560 + j0.05090.8779 + j0.04800.7978 + j0.0450
68
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 19/33 (36)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
507095
120150185
240300400
8.19.711.5
12.914.316.0
18.420.623.3
8.08.08.0
8.08.08.0
8.08.08.0
0.10.10.1
0.10.10.1
0.10.10.1
3.13.23.3
3.43.53.6
3.83.94.2
64.368.072.0
75.278.682.5
88.092.999.3
100010001000
500500500
500250250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - CU / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km507095
120150185
240300400
214259264
351393438
502560627
176216257
291327366
421474530
225279335
383433485
564643726
0.8870.6330.476
0.3950.3380.291
0.2480.2220.201
0.69990.78140.8667
0.93531.00281.0840
1.19461.29751.4299
0.3949 + j0.13600.2737 + j0.12820.1975 + j0.1216
0.1569 + j0.11630.1276 + j0.11260.1026 + j0.1088
0.0790 + j0.10420.0641 + j0.10070.0516 + j0.0971
1.0012 + j0.09240.8452 + j0.08460.7358 + j0.0780
0.6709 + j0.07280.6194 + j0.06900.5699 + j0.0651
0.5163 + j0.06060.4764 + j0.05710.4376 + j0.0536
69
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 19/33 (36)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE DIMENSION
507095
120150185
240300400
8.29.811.6
13.014.416.2
18.520.723.5
8.08.08.0
8.08.08.0
8.08.08.0
0.10.10.1
0.10.10.1
0.10.10.1
3.13.23.3
3.43.53.6
3.83.94.2
64.468.272.2
75.578.882.8
88.393.299.7
10001000500
500500500
500250250
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm
THREE CORE - AL / XLPE / CTS / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCable
SingleCable
SingleCable
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
507095
120150185
240300400
167202241
274307344
396447502
138167200
227255287
333376
426.0
177215260
298338381
445509575
1.4431.0090.742
0.5970.4980.411
0.3320.2840.244
0.70300.78560.8705
0.94061.00761.0901
1.20071.30311.4313
0.6541 + j0.13560.4522 + j0.12860.3269 + j0.1213
0.2587 + j0.11600.2109 + j0.11230.1683 + j0.1048
0.1289 + j0.10350.1038 + j0.10010.1020 + j0.0965
1.6464 + j0.09211.3750 + j0.08051.2077 + j0.0778
1.0991 + j0.07251.0156 + j0.06880.9326 + j0.0648
0.8446 + j0.06000.7794 + j0.05650.7331 + j0.0529
70
Central Cables Berhad
THREE CORE - XLPE INSULATED UNARMOURED DOUBLE SHEATHED CABLE FOR VOLTAGES 11kV TO IEC 60502-2
DESCRIPTION
Circular compacted stranded aluminium conductor, cross-linked polyethylene, copper tape screened,lay up core together non-hygroscopic polypropylene fillers, extruded with MDPE sheath and extrudedouter sheath made from MDPE. Complies with Tenaga Nasional Berhad (TNB) specification.
CONSTRUCTION
ConductorAluminium(AL) conductor conform to class 2 in IEC 60228.
Conductor screenAn extruded thin layer of semi-conductive compound as a 1st layer by triple extrusion process.
InsulationAn extruded layer of cross-linked polyethylene(XLPE) compound as a 2nd layer by triple extrusion process.
Insulation screenAn extruded thin layer of semi-conductive compound as a 3rd layer by triple extrusion process.
Metallic screenTwo layers of copper tape(CTS) helically wrap with overlap laid over insulation screen.
Colour of core IdentificationRed, yellow and blue shall be applied over insulation screen.
Lay Up CoresThree screened core are laid up together , if necessary filled with non hygroscopic material compatible with insulationand covered with a layer of inner sheath.
Inner SheathExtruded layer made from black MDPE compound.
Non-Conductor Binder TapeA layer of non-conductive tape helically wrap with overlap laid over inner sheath.
Outer sheathExtruded layer made from black MDPE compound. Additive like Anti-termite repellent, anti-rodent or differentouter sheath colour are available upon request.
MDPE Inner Sheath
MDPE Outer Sheath
Seperation Tape
ConductorConductor Screen
XLPE Insulation
Insulation ScreenCopper Tape Screen
Non-Hygroscopic Filter
Binder Tope
71
Central Cables Berhad
XLPE INSULATED UNARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
THREE CORE - AL / XLPE / CTS / MDPE /MDPE SHEATHED CABLE DIMENSION
162535
5070
95#
120 150#
185 240#
300
400
4.76.07.0
8.29.8
11.613.014.4
16.218.520.7
23.5
3.43.43.4
3.43.4
3.43.43.4
3.43.43.4
3.4
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 20.1 x 20.1 x 2
0.1 x 2
2.22.22.2
2.22.2
2.22.22.2
2.22.22.2
2.2
2.22.22.3
2.42.5
2.72.82.9
3.03.23.3
3.5
41.343.946.4
49.152.9
57.060.363.8
67.573.277.9
84.2
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper
tape
Nominal thickness of MDPE inner sheath
Nominal thickness of MDPE sheath
Approximate overall diameter
Metallic screening
mm2 mm mm mm mm mmmm x n
THREE CORE - AL / XLPE / CTS / MDPE / MDPE SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
SingleCore
SingleCore
SingleCore
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per conductor*
mm2 A A A mV/A/m A/km ohm/km ohm/km
162535
5070
95#
120 150#
185
240#
300400
86116138
162196236
270300339
389433486
7093
111
131161191
219244277
319357404
80111132
157198234
271305352
408461525
4.2482.6731.953
1.4351.0000.732
0.5840.4860.398
0.3180.2680.227
0.28020.32550.3184
0.40590.46530.5268
0.58660.62740.6886
0.77100.84760.9439
1.9485 + j0.13391.2243 + j0.12460.8857 + j0.1184
0.6542 + j0.11030.4524 + j0.10420.3270 + j0.0944
0.2589 + j0.09530.2113 + j0.65440.1686 + j0.0898
0.1294 + j0.08630.1044 + j0.08390.0829 + j0.0781
10.9657 + j0.55809.5408 + j0.57328.6761 + j0.5856
7.9443 + j0.59817.1240 + j0.61486.4567 + j0.6307
5.9977 + j0.05175.6171 + j0.65445.2110 + j0.0462
4.7517 + j0.68394.3936 + j0.69804.0144 + j0.7143
72
Central Cables Berhad
SINGLE CORE - XLPE INSULATED ARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
DESCRIPTION
Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, with copper tapeor copper wire or aluminium wire screen, covered with extruded separation sheath, armored and extruded outer sheath made from MDPE or HDPE or PVC.
CONSTRUCTION
ConductorPlain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228.
Conductor wrappingApplied when cable voltage rated at 19/33kV and aluminium conductor size reach 400mm² or aboveA layer of helically wrap semi-conductive tape with overlap laid over stranded conductor.
Conductor screenAn extruded thin layer of semi-conductive compound as a 1st layer by triple extrusion process.
InsulationAn extruded layer of cross-linked polyethylene(XLPE) compound as a 2nd layer by triple extrusion process.
Insulation screenAn extruded thin layer of semi-conductive compound as a 3rd layer by triple extrusion process.
Semi-conductive tapeApplied under copper wire screen or aluminium wire screen when requested by purchaserA layer of helically wrap semi-conductive water blocking tape with overlap laid over insulation screen.
Metallic screen1 or 2 layer(s) of Copper tape(CTS) helically wrap with overlap laid over insulation screen or numbers of copperwires(CWS) or numbers of aluminium wires(AWS) laid over semi-conductive tape. An equalizing copper tape withopen helically wrap and metallic screen construction base on customer’s earth fault current requirement are availableupon request.
Binder tapeApplied when necessaryA layer of non-conductive or semi-conductive tape helically wrap with overlap laid over metallic screen.
Separation SheathExtruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent ordifferent separation sheath colour are available upon request.
PVC Outer Sheath
Conductor
Conductor Screen
XLPE Insulation
Insulation Screen
Copper Tape Screen
PVC Separation Sheath
Aluminium Wire
73
Central Cables Berhad
SINGLE CORE - XLPE INSULATED ARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
ArmourAluminium Wires shall be applied helically over the separation sheath
Non-conductive binder tapeA layer of non-conductive tape helically wrap with overlap laid over armour when necessary.
Outer sheathExtruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent or different outer sheath colour are available upon request.
74
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.811.5
13.014.416.2
18.520.723.5
26.530.1
2.52.52.5
2.52.52.5
2.52.52.5
2.62.83.0
3.23.2
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.81.81.8
1.81.81.9
1.92.02.1
2.12.22.3
2.52.6
22.323.524.6
25.827.429.4
30.832.435.0
37.740.543.9
49.053.0
100010001000
100010001000
100010001000
100010001000
10001000
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.21.2
1.21.21.2
1.21.21.2
1.31.4
1.61.61.6
1.61.61.6
1.61.62.0
2.02.02.0
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
507095
120150185
240300400
500630
96123146
172210251
284318360
416469534
607687
88113134
159194231
263294334
387436496
565637
104135163
195243295
340385447
527605702
823951
4.2512.6781.944
1.4431.0080.741
0.5970.4970.411
0.3330.2860.246
0.2190.198
0.17680.20600.2309
0.25780.29620.3360
0.32920.40110.4407
0.48300.50930.5430
0.58030.6488
1.9485 + j0.16121.2243 + j0.15010.8856 + j0.1426
0.6541 + j0.13590.4522 + j0.12550.3269 + j0.1196
0.2587 + j0.11430.2109 + j0.11110.1682 + j0.1090
0.1288 + j0.10450.1033 + j0.10190.0816 + j0.0991
0.0646 + j0.09820.0517 + j0.0951
8.3900 + j0.08057.0912 + j0.07216.3286 + j0.0665
5.7014 + j0.06175.0201 + j0.05364.4833 + j0.0493
4.1233 + j0.04563.8301 + j0.04333.5228 + j0.0410
3.1585 + j0.03842.8619 + j0.03722.5679 + j0.0359
2.3072 + j0.03462.0875 + j0.0327
75
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
2.52.52.5
2.52.52.5
2.52.52.5
2.52.52.5
2.52.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.81.81.8
1.81.81.9
1.92.02.1
2.12.22.3
2.52.6
22.323.524.6
25.727.429.3
30.732.335.0
37.640.843.7
48.752.7
100010001000
100010001000
100010001000
100010001000
500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.21.2
1.21.21.2
1.21.21.2
1.31.4
1.61.61.6
1.61.61.6
1.61.62.0
2.02.02.0
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
507095
120150185
240300400
500630
123158188
222270322
365408461
531596672
755841
113145173
204249297
337377426
491551620
696773
134174210
251312380
436495571
672769885
10221164
2.5551.6271.184
0.8860.6310.475
0.3930.3360.291
0.2480.2240.204
0.1920.180
0.17740.20500.2298
0.25640.29410.3342
0.36670.39880.4378
0.48020.48550.5394
0.57600.6446
1.1727 + j0.16110.7414 + j0.15050.5345 + j0.1429
0.3949 + j0.13350.2737 + j0.12590.1975 + j0.1198
0.1569 + j0.11470.1276 + j0.11130.1026 + j0.1093
0.0790 + j0.10470.0640 + j0.10270.0515 + j0.0993
0.0417 + j0.09840.0344 + j0.0953
5.1147 + j0.08034.3290 + j0.07233.8644 + j0.0667
3.4839 + j0.05913.0731 + j0.05382.7421 + j0.0495
2.5256 + j0.04582.3440 + j0.04352.1586 + j0.0411
1.9347 + j0.03851.7287 + j0.03821.5748 + j0.0360
1.4166 + j0.03471.2811 + j0.0328
76
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
3.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.81.81.8
1.81.91.9
2.02.12.1
2.22.32.4
2.52.6
24.225.426.4
27.629.531.2
33.635.237.0
39.541.946.1
49.453.4
100010001000
100010001000
100010001000
100010001000
10001000
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.21.2
1.21.21.2
1.21.21.3
1.31.4
1.61.61.6
1.61.61.6
2.02.02.0
2.02.02.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
507095
120150185
240300400
500630
95122146
172210250
285318360
416468535
607687
88113135
159195232
265296335
388436498
565637
105137165
197245298
346392449
530606771
823951
4.2572.6781.945
1.4431.0100.743
0.6000.5010.419
0.3440.2880.249
0.2200.199
0.26590.29680.3308
0.36730.41940.4732
0.51810.56120.6145
0.51360.84760.8371
0.93071.0398
1.9485 + j0.16611.2243 + j0.15480.8856 + j0.1470
0.6541 + j0.13740.4522 + j0.12990.3269 + j0.1233
0.2586 + j0.11980.2108 + j0.11630.1682 + j0.1122
0.1286 + j0.11590.1037 + j0.10410.0815 + j0.1021
0.0646 + j0.09870.0516 + j0.0956
7.5756 + j0.08916.4059 + j0.07995.7337 + j0.0738
5.1857 + j0.06574.5936 + j0.05974.1272 + j0.0549
3.1836 + j0.05093.5571 + j0.04833.2869 + j0.0455
2.9850 + j0.05062.7521 + j0.03982.5074 + j0.0374
2.2823 + j0.03532.0669 + j0.0333
77
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 6.35/11 (12)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
3.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.81.81.8
1.81.91.9
2.02.12.1
2.22.32.4
2.52.6
24.125.326.4
27.529.431.1
33.535.136.8
39.441.845.9
49.153.1
100010001000
100010001000
100010001000
100010001000
500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.21.2
1.21.21.2
1.21.21.3
1.31.4
1.61.61.6
1.61.61.6
2.02.02.0
2.02.02.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
507095
120150185
240300400
500630
123158188
221270322
365409460
531595673
754841
113146174
205250298
339379427
492551622
696773
134176211
254315383
444503575
675771891
10231165
2.5561.6281.185
0.8870.6340.478
0.3980.3420.295
0.2520.2260.208
0.1920.180
0.2560.2960.329
0.3650.4170.471
0.5150.5520.611
0.6820.7500.832
0.9291.033
1.1727 + j0.16650.7414 + j0.15510.5345 + j0.1474
0.3949 + j0.13770.2737 + j0.13030.1975 + j0.1236
0.1569 + j0.12010.1276 + j0.11660.1025 + j0.1125
0.0789 + j0.10760.0639 + j0.10420.0513 + j0.1024
0.0417 + j0.09900.0343 + j0.0958
4.6132 + j0.08943.9088 + j0.08013.4493 + j0.0740
3.1672 + j0.06592.8105 + j0.06002.5232 + j0.0551
2.3348 + j0.05112.1761 + j0.04842.0133 + j0.0457
1.8279 + j0.04221.6843 + j0.03991.5375 + j0.0376
1.4012 + j0.03541.2684 + j0.0334
78
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
500630
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
4.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.81.81.9
1.92.02.0
2.12.12.2
2.32.32.5
2.62.7
26.427.628.8
30.031.934.4
36.037.439.4
41.944.148.5
52.055.8
100010001000
100010001000
100010001000
100010001000
10001000
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.21.2
1.21.21.2
1.21.21.3
1.41.4
1.61.61.6
1.61.62.0
2.02.02.0
2.02.02.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
507095
120150185
240300400
500630
95138146
172210251
285318359
416468534
607686
88114136
160195234
266297336
389437499
565638
106122167
199248303
348394452
533609713
825954
4.2522.6791.946
0.5281.0110.746
0.6020.0530.417
0.3390.2910.253
0.2240.202
0.30980.35510.3935
0.43460.493
0.5532
0.60290.65130.7108
0.79070.86490.9582
1.06191.1830
1.9485 + j0.17151.2243 + j0.16000.8856 + j0.1525
0.2147 + j0.14270.4522 + j0.13480.3268 + j0.1294
0.2586 + j0.12410.2108 + j0.12010.1682 + j0.1161
0.1278 + j0.11110.1036 + j0.10730.0814 + j0.1053
0.0644 + j0.10190.0514 + j0.0984
6.8203 + j0.09815.7585 + j0.08825.1624 + j0.0816
4.2433 + j0.07314.1695 + j0.06653.7670 + j0.0612
3.4964 + j0.05683.2746 + j0.05383.0400 + j0.0507
2.7765 + j0.04682.5718 + j0.04422.3553 + j0.0415
2.1544 + j0.03901.9607 + j0.0367
79
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
162535
507095
120150185
240300400
500630
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
4.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.81.81.9
1.92.02.0
2.12.12.2
2.32.32.5
2.62.7
26.327.528.8
29.931.834.3
35.937.339.2
41.844.048.3
51.755.5
100010001000
100010001000
100010001000
100010001000
500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.21.2
1.21.21.2
1.21.21.3
1.41.4
1.61.61.6
1.61.62.0
2.02.02.0
2.02.02.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km162535
507095
120150185
240300400
500630
123157188
221270323
365409460
530595673
755841
114146175
206251300
340380428
493552623
696750
137178215
256318389
447506578
679775897
10261169
2.5571.6301.187
0.8900.6370.483
0.4020.3450.299
0.2570.2310.213
0.1970.185
0.30830.35360.3197
0.43240.48990.5504
0.59950.64790.7063
0.78630.86090.9521
1.05421.1756
1.1727 + j0.17200.7414 + j0.16030.5345 + j0.5128
0.3949 + j0.14300.2737 + j0.15320.1974 + j0.1297
0.1568 + j0.12450.1275 + j0.12040.1024 + j0.1164
0.0788 + j0.11130.0638 + j0.10750.0511 + j0.1056
0.0414 + j0.10220.0341 + j0.0986
4.1503 + j0.09853.5122 + j0.08853.1490 + j0.0819
2.8586 + j0.07342.5496 + j0.06682.3020 + j0.0614
2.1396 + j0.05702.0024 + j0.05401.8613 + j0.0509
1.6996 + j0.04701.5763 + j0.04431.4437 + j0.0417
1.3223 + j0.03921.2029 + j0.0368
80
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 12.7/22 (24)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
35
507095
120150185
240300400
500630
7.0
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
5.5
5.55.55.5
5.55.55.5
5.55.55.5
5.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.9
2.02.12.1
2.22.22.3
2.32.52.6
2.72.8
30.8
32.234.936.6
38.239.641.6
43.947.750.7
54.258.2
1000
100010001000
100010001000
100010001000
10001000
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.2
1.21.21.2
1.21.21.2
1.21.31.3
1.41.5
1.6
1.62.02.0
2.02.02.0
2.02.52.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km
35
507095
120150185
240300400
500630
145
171210250
284318359
415468534
606638
136
160197235
238298337
389439500
566686
168
201251305
350396454
534615714
827955
1.947
1.4461.0140.748
0.0650.5060.420
0.3420.2970.257
0.2280.206
0.5190
0.57080.64430.7199
0.78270.84280.9172
1.01711.10971.2260
1.35541.6300
0.8856 + j0.1567
0.6541 + j0.14710.4522 + j0.14050.3268 + j0.1333
0.2586 + j0.12790.2108 + j0.12370.1681 + j0.1195
0.1287 + j0.11400.1035 + j0.11220.0813 + j0.1081
0.0643 + j0.10450.0513 + j0.1010
4.7486 + j0.0880
4.3135 + j0.07913.8528 + j0.07213.4940 + j0.0664
3.2535 + j0.06173.0562 + j0.05852.8473 + j0.0551
2.6118 + j0.05092.4281 + j0.04802.2326 + j0.0450
2.0503 + j0.04221.1621 + j0.0396
81
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 12.7/22 (24)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
35
507095
120150185
240300400
500630
7.0
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
5.5
5.55.55.5
5.55.55.5
5.55.55.5
5.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
1.9
2.02.12.1
2.22.22.3
2.32.52.6
2.72.8
30.8
32.134.836.5
38.139.541.4
43.847.650.5
53.957.9
1000
100010001000
100010001000
100010001000
500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.2
1.21.21.2
1.21.21.2
1.21.31.3
1.41.5
1.6
1.62.02.0
2.02.02.0
2.02.52.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km
35
507095
120150185
240300400
500630
187
221270322
365408459
530596672
754841
175
206253301
341381429
493554623
696773
217
258323392
449509581
682783899
10291172
1.189
0.8920.6470.486
0.4050.3490.303
0.2600.2380.217
0.2010.189
0.5167
0.56810.64040.7164
0.77790.83850.9117
1.01161.10471.2184
1.34571.4969
0.5345 + j0.1571
0.3949 + j0.14750.2737 + j0.14090.1974 + j0.1336
0.1568 + j0.12820.1275 + j0.12400.1024 + j0.1199
0.0787 + j0.11430.0636 + j0.11240.0510 + j0.1084
0.0413 + j0.10480.0339 + j0.1012
2.8954 + j0.0883
2.6321 + j0.07942.3550 + j0.07242.1345 + j0.0666
1.9902 + j0.06191.8683 + j0.05781.7427 + j0.0553
1.4853 + j0.04811.4835 + j0.04811.3682 + j0.0452
1.2580 + j0.04241.1491 + j0.0398
82
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 19/33 (36)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
507095
120150185
240300400
500630
8.29.811.6
13.014.416.2
18.520.723.5
26.530.1
8.08.08.0
8.08.08.0
8.08.08.0
8.08.0
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
2.22.22.3
2.32.42.5
2.62.52.7
2.83.0
38.440.142.0
43.446.248.2
50.753.156.1
59.663.8
100010001000
100010001000
100010001000
1000500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.31.3
1.31.41.4
1.51.6
2.02.02.0
2.02.52.5
2.52.52.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - AL / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km
507095
120150185
240300400
500630
171209250
284318359
415467533
606685
162198236
268301340
392441501
568638
205254308
354402461
542618717
831956
1.4511.0170.752
0.6100.5130.428
0.3510.3040.265
0.2360.215
0.70300.78590.8705
0.98411.00761.0901
1.20071.30311.4313
1.57361.7392
0.6541 + j0.16090.4522 + j0.14920.3268 + j0.1420
0.2585 + j0.13590.2107 + j0.13340.1680 + j0.1288
0.1285 + j0.12310.1033 + j0.11890.0812 + j0.1145
0.0641 + j0.11050.0510 + j0.1068
3.6312 + j0.09493.2258 + j0.08422.9698 + j0.0778
2.7805 + j0.07252.6258 + j0.06882.4623 + j0.0648
2.2775 + j0.06002.1325 + j0.05651.9770 + j0.0529
1.8304 + j0.04961.6864 + j0.0464
83
Central Cables Berhad
XLPE INSULATED ARMOURED SHEATHED CABLE 19/33 (36)kV
*Note : Electrical properties are calculated base on conditions in appendix B.
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE DIMENSION
507095
120150185
240300400
500630
8.19.711.5
12.914.316.0
18.420.623.3
26.329.9
8.08.08.0
8.08.08.0
8.08.08.0
8.08.0
0.10.10.1
0.10.10.1
0.10.10.1
0.10.1
2.22.22.3
2.32.42.5
2.62.62.7
2.83.0
38.340.041.9
43.346.148.0
50.653.055.9
59.363.5
100010001000
100010001000
10001000500
500500
Nominalcross-
sectionalarea of
conductor
Nominal diameter of conductor
Nominal insulation thickness
Nominal thickness of copper tape
Nominal thicknessof PVC outer
sheath
Approximate overall diameter
Standardpacking length
Metallic screening
mm2 mm mm mm mm m/drummm mm mm
1.21.21.2
1.21.31.3
1.31.41.4
1.51.6
2.02.02.0
2.02.52.5
2.52.52.5
2.52.5
Armouringwire
diameter
Nominal thickness
of separation
sheath
SINGLE CORE - CU / XLPE / CTS / PVC / AWA / PVC SHEATHED CABLE ELECTRICAL PROPERTIES
Nominalcross-
sectionalarea of
conductor
Buried direct in ground
In single-way PE duct in ground
In tray in air (indoor)
TrefoilTrefoilTrefoil
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance
at 25°C*
Zero sequence impedance at 25°C*
Maximum current rating per cable*
mm2 A A A mV/A/m A/km ohm/km ohm/km
507095
120150185
240300400
500630
221269321
364498460
530595671
754841
209254303
343385432
497555624
697773
264327396
454517590
691787904
10331177
0.8980.6470.493
0.4130.3600.314
0.2720.2470.226
0.2100.198
0.69990.78140.8667
0.93531.00281.0804
1.19461.29751.4429
1.56301.7291
0.3949 + j0.15850.2736 + j0.14970.1973 + j0.1423
0.1567 + j0.13630.1274 + j0.13370.1022 + j0.1921
0.0785 + j0.12840.0634 + j0.11920.0507 + j0.1148
0.0409 + j0.11080.0334 + j0.1070
2.2141 + j0.09241.9884 + j0.08461.8130 + j0.0780
1.6996 + j0.07281.6041 + j0.06901.5024 + j0.0653
1.3930 + j0.06021.3039 + j0.05671.2109 + j0.0531
1.1225 + j0.04981.0340 + j0.0466
84
Central Cables Berhad
THREE CORE - XLPE INSULATED ARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
DESCRIPTION
Circular compacted stranded copper or aluminium conductor, cross-linked polyethylene, with copper tape or copper wire or aluminium wire screened, laid up cores together with non-hygroscopic fillers, covered with extruded separation sheath, armored and extruded outer sheath made from MDPE or HDPE or PVC.
CONSTRUCTION
ConductorPlain circular compacted stranded copper(CU) or aluminium(AL) conductor conform to class 2 in IEC 60228.
Conductor wrappingApplied when cable voltage rated at 19/33kV and aluminium conductor size reach 400mm² or aboveA layer of helically wrap semi-conductive tape with overlap laid over stranded conductor.
Conductor screenAn extruded thin layer of semi-conductive compound as a 1st layer by triple extrusion process.
Insulation An extruded layer of cross-linked polyethylene(XLPE) compound as a 2nd layer by triple extrusion process. Insulation screen An extruded thin layer of semi-conductive compound as a 3rd layer by triple extrusion process.
Colour of core Identification Red, yellow and blue shall be applied over insulation screen.
Semi-conductive tape Applied under copper wire screen or aluminium wire screen when requested by purchaser A layer of helically wrap semi-conductive water blocking tape with overlap laid over insulation screen.
Metallic screen 1 or 2 layer(s) of Copper tape(CTS) helically wrap with overlap laid over insulation screen or numbers of copper wires(CWS) or numbers of aluminium wires(AWS) laid over semi-conductive tape. An equalizing copper tape with open helically wrap and metallic screen construction base on customer’s earth fault current requirement are available upon request.
Lay Up Cores Three screened core are laid up together with non hygroscopic material.
ConductorConductor ScreenXLPE InsulationInsulation ScreenCopper Tape ScreenNon-hygroscopicFillerBinder Tape
PVC SeparationSheath
Gal. Steel Wire Armour
PVC Outer Sheath
85
Central Cables Berhad
THREE CORE - XLPE INSULATED ARMOURED SHEATHED CABLE FOR VOLTAGES 6.6kV UP TO AND INCLUDING 33kV TO IEC 60502-2
Non-conductive binder tape A layer of non-conductive tape helically wrap with overlap laid over lay up cores Separation Sheath Extruded layer made from black PVC or MDPE or HDPE compound.
Armour Galvanized Steel Wires shall be applied helically over the separation sheath Non-conductive binder tape A layer of non-conductive tape helically wrap with overlap laid over armour when necessary. Outer sheath Extruded layer made from black PVC or MDPE or HDPE compound. Additive like Anti-termite repellent, anti-rodent or different outer sheath colour are available upon request.
86
Central Cables Berhad
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
162535
507095
120150185
240300400
162535
507095
120150185
240300400
93118140
164201240
271297342
392436491
7798117
138169203
231255294
339380386
96124150
177221269
306345399
464524601
4.2472.6731.937
1.4350.9990.730
0.5840.4830.394
0.3140.2660.225
0.1768 0.2060 0.2309
0.2578 0.2962 0.3360
0.3692 0.4011 0.4407
0.4830 0.5850 0.5430
1.9486 + j0.1241 1.2234 + j0.1156 0.8857 + j0.1100 0.6542 + j0.1025 0.4524 + j0.0971 0.3271 + j0.0929 0.2590 + j0.0892 0.2113 + j0.0869 0.1688 + j0.0845 0.1296 + j0.0819 0.1046 + j0.0808 0.0828 + j0.0794
4.0967 + j0.0805 3.1799 + j0.0721 2.6999 + j0.0665 2.3365 + j0.0589 1.9748 + j0.0536 1.7122 + j0.0493 0.5461 + j0.0456 1.4171 + j0.0433 1.2861 + j0.0410 1.1383 + j0.0384 1.0225 + j0.0372 0.9096 + j0.0359
4.76.07.0
8.29.811.6
13.014.416.2
18.520.723.5
2.52.52.5
2.52.52.5
2.52.52.5
2.62.83.0
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.21.21.3
1.31.41.4
1.51.61.6
1.71.82.0
2.02.02.5
2.52.52.5
2.52.52.5
2.53.153.15
2.2 2.3 2.4
2.5 2.6 2.7
2.9 3.0 3.1
3.3 3.5 3.8
38.4 41.2 45.3
48.0 52.0 55.9
59.6 63.2 67.1
73.2 80.7 88.5
100010001000
100010001000
500500500
500500250
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
87
Central Cables Berhad
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 3.8/6.6 (7.2)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
162535
507095
120150185
240300400
162535
507095
120150185
240300400
111140167
196236284
319353403
459506708
98126151
178217260
294328372
426474527
119151185
160265327
317414486
562632559
2.5491.6181.173
0.8740.6160.457
0.3740.3150.266
0.2230.1970.177
0.1758 0.2050 0.2298 0.2564 0.2941 0.3342 0.3667 0.3988 0.4378 0.4802 0.5060 0.5394
1.1727 + j0.1244 0.7415 + j0.1158 0.5346 + j0.1103 0.3951 + j0.1027 0.2740 + j0.0974 0.1979 + j0.0930 0.1575 + j0.0894 0.1283 + j0.0870 0.1035 + j0.0847 0.0802 + j0.0821 0.0654 + j0.0809 0.0532 + j0.0796
2.4867 + j0.0809 1.9373 + j0.0723 1.6444 + j0.0667 1.4245 + j0.0591 1.2067 + j0.0538 1.0455 + j0.0495 0.9462 + j0.0458 0.8661 + j0.0435 0.7874 + j0.0410 0.6909 + j0.0385 0.6257 + j0.0373 0.5580 + j0.0360
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
2.52.52.5
2.52.52.5
2.52.52.5
2.52.52.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.21.31.3
1.31.41.5
1.51.61.6
1.71.82.0
2.02.02.5
2.52.52.5
2.52.52.5
2.53.153.15
2.2 2.3 2.4 2.5 2.6 2.7 2.9 3.0 3.1 3.3 3.5 3.8
38.3 41.1 45.2 47.8 51.8 55.7 59.4 63.0 66.8 72.9 80.4 88.1
100010001000
1000500500
500500500
250250250
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
88
Central Cables Berhad
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 6.35/11 (12)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
162535
507095
120150185
240300400
162535
507095
120150185
240300400
93117140
164200239
269303340
393438491
7899118
139171204
231261294
342383431
98124150
179221269
328350397
471530603
4.2482.6351.938
1.4361.0000.732
0.5870.4860.398
0.3170.2680.226
0.2802 0.2968 0.3308 0.3673 0.4149 0.4732 0.5181 0.5612 0.6145 0.6864 0.7532 0.8371
1.9485 + j0.1326 1.2243 + j0.1234 0.8857 + j0.1173 0.6542 + j0.1092 0.4523 + j0.1033 0.3230 + j0.0985 0.2589 + j0.0953 0.2112 + j0.0926 0.1687 + j0.0899 0.1294 + j0.0856 0.1045 + j0.6833 0.0826 + j0.0810
3.8242 + j0.0981 2.9514 + j0.0799 2.5016 + j0.0738 2.1646 + j0.0657 1.8326 + j0.0597 1.5935 + j0.0549 1.4435 + j0.0517 1.3261 + j0.0491 1.2075 + j0.0463 1.0804 + j0.0421 0.9859 + j0.0398 0.8894 + j0.0374
4.76.07.0
8.29.811.6
13.014.016.2
18.520.723.5
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.21.31.3
1.41.51.5
1.61.61.7
1.81.92.0
2.02.52.5
2.52.52.5
2.52.52.5
3.153.153.15
2.3 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.4 3.6 3.8
42.4 47.0 49.5 52.5 56.4 60.4 63.9 67.2 71.4 78.4 83.7 90.2
100010001000
10001000500
500500500
500500250
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
89
Central Cables Berhad
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 6.35/11 (12)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
162535
507095
120150185
240300400
162535
507095
120150185
240300400
112140168
197238284
320359400
453507560
99127152
179219261
296332372
424475528
122154187
223272331
375428482
555636771
2.5501.6201.175
0.8760.6190.464
0.3770.3200.271
0.2260.2000.179
0.2555 0.2955 0.3292 0.3654 0.4166 0.4708 0.5147 0.5581 0.6106 0.6824 0.7495 0.8317
1.1727 + j0.1330 0.7415 + j0.1237 0.5346 + j0.1176 0.3950 + j0.1095 0.2736 + j0.1036 0.1978 + j0.0987 0.1573 + j0.0947 0.1281 + j0.0920 0.1033 + j0.0893 0.0799 + j0.0858 0.0652 + j0.0835 0.0530 + j0.0811
2.3195 + j0.0894 1.7972 + j0.0801 1.5227 + j0.0740 1.3190 + j0.0659 1.1192 + j0.600 0.9276 + j0.0551 0.8826 + j0.0511 0.8101 + j0.4840 0.7390 + j0.0457 0.6613 + j0.0422 0.6032 + j0.0399 0.5456 + j0.0376
4.75.97.0
8.19.711.6
12.914.316.0
18.420.623.3
3.43.43.4
3.43.43.4
3.43.43.4
3.43.43.4
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.21.31.3
1.41.51.5
1.61.61.7
1.81.92.0
2.02.52.5
2.52.52.5
2.52.52.5
3.153.153.15
2.3 2.5 2.6 2.7 2.8 2.9 3.0 3.1 3.2 3.4 3.6 3.8
42.4 47.0 49.5 52.3 56.2 60.2 63.7 67.0 71.1 78.1 83.4 89.8
100010001000
1000500500
500500500
250250250
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
90
Central Cables Berhad
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
162535
507095
120150185
240300400
162535
507095
120150185
240300400
94117140
165201238
271301337
390433493
80100120
141173206
235262295
342382435
101126153
181223270
312350395
467523611
4.2492.6751.940
1.4381.0030.734
0.7100.6270.558
0.3210.2720.230
0.3098 0.3551 0.3935 0.4346 0.4930 0.5532 0.6032 0.6513 0.7108 0.7907 0.8649 0.7519
1.9485 + j0.1417 1.2243 + j0.1318 0.8856 + j0.1252 0.6541 + j0.1166 0.4523 + j0.1101 0.3270 + j0.1048 0.2588 + j0.2496 0.2111 + j0.2467 0.1685 + j0.2436 0.1292 + j0.0904 0.1043 + j0.0878 0.0824 + j0.0850
3.5725 + j0.0981 2.7357 + j0.0882 2.3112 + j0.0816 1.9969 + j0.0731 1.6912 + j0.0665 1.4735 + j0.0612 1.3377 + j0.2061 1.2319 + j0.2031 1.1252 + j0.2000 1.0110 + j0.0468 0.9258 + j0.0441 0.8387 + j0.0415
4.76.07.0
8.29.811.6
13.014.416.0
18.420.623.3
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.31.41.4
1.51.51.6
1.71.71.8
1.92.02.1
2.52.52.5
2.52.52.5
2.53.153.15
3.153.153.15
2.6 2.6 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.8 4.0
49.5 52.2 54.7 57.6 61.4 65.7 69.2 73.9 78.0 83.7 89.0 95.6
100010001000
1000500500
500500500
500250250
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
91
Central Cables Berhad
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 8.7/15 (17.5)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
162535
507095
120150185
240300400
162535
507095
120150185
240300400
113141491
197240283
321356396
454627719
101129154
182221264
300332375
427473526
125156189
224278332
382427480
563627719
2.5521.6221.178
0.8790.3920.465
0.3820.3240.276
0.2320.2050.184
0.3083 0.3536 0.3917 0.4324 0.4899 0.5504 0.5995 0.6479 0.7063 0.7863 0.8609 0.9521
2.1652 + j0.0985 1.6650 + j0.0885 1.4060 + j0.0819 1.2161 + j0.0734 0.9523 + j0.0668 0.8988 + j0.0614 0.8175 + j0.0570 0.7552 + j0.0540 0.6833 + j0.0509 0.6185 + j0.0470 0.5645 + j0.0446 0.5143 + j0.0417
4.75.97.0
8.19.711.5
12.914.316.0
18.420.623.3
4.54.54.5
4.54.54.5
4.54.54.5
4.54.54.5
0.10.10.1
0.10.10.1
0.10.10.1
0.10.10.1
1.31.41.4
1.51.51.6
1.71.71.8
1.92.02.1
2.52.52.5
2.52.52.5
2.53.153.15
3.153.153.15
2.6 2.6 2.7 2.8 2.9 3.1 3.2 3.3 3.4 3.6 3.8 4.0
49.3 52.1 54.6 57.0 61.2 65.5 69.0 73.7 77.8 83.4 88.8 95.2
100010001000
1000500500
500500250
250250250
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
1.1727 + j0.1421 0.7415 + j0.1321 0.5345 + j0.1255 0.3950 + j0.1169 0.1941 + j0.1104 0.1977 + j0.1050 0.1572 + j0.1006 0.1279 + j0.0976 0.1030 + j0.0945 0.0796 + j0.0906 0.0648 + j0.0879 0.0526 + j0.0852
92
Central Cables Berhad
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 12.7/22 (24)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
35
507095
120150185
240300400
35
507095
120150185
240300400
139
165206237
270299339
386435487
120
142174207
236263298
341385433
152
183225270
313349401
460417602
1.941
1.4401.0040.736
0.7150.4920.404
0.3240.2750.234
0.5190 0.5708 0.6443 0.7363 0.7827 0.8428 0.9172 1.0171 1.1097 1.2260
0.8856 + j0.1316 0.6541 + j0.1227 0.4522 + j0.1157 0.3269 + j0.1099 0.2588 + j0.2545 0.2110 + j0.1020 0.1648 + j0.0986 0.1291 + j0.0944 0.1041 + j0.0915 0.0822 + j0.0885
2.1733 + j0.0880 1.8738 + j0.0791 1.5857 + j0.0721 1.3825 + j0.0664 1.2568 + j0.2110 1.1591 + j0.0585 1.0610 + j0.0551 0.9560 + j0.0509 0.8779 + j0.0480 0.7978 + j0.0450
7.0
8.29.811.6
13.014.416.2
18.520.723.5
5.5
5.55.55.5
5.55.55.5
5.55.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
1.5
1.61.61.7
1.81.81.9
2.02.12.2
2.5
2.52.52.5
3.153.153.15
3.153.153.15
2.9 3.0 3.1 3.2 3.4 3.5 3.6 3.8 3.9 4.2
59.6
63.066.370.4
75.478.183.0
88.693.7100.5
1000
500500500
500500250
250250250
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
93
Central Cables Berhad
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 12.7/22 (24)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
35
507095
120150185
240300400
35
507095
120150185
240300400
167
197238283
319353397
449502553
155
183222265
300335374
426472523
188
226277333
382425485
555634707
1.18
0.8810.6530.468
0.3860.3280.280
0.2360.2100.189
0.5167 0.5681 0.6404 0.7164 0.7779 0.8385 0.9117 1.0116 1.1047 1.2148
1.3214 + j0.0883 1.1406 + j0.0794 0.9764 + j0.0724 0.8430 + j0.0666 0.7678 + j0.0619 0.7075 + j0.0587 0.6488 + j0.0553 0.5847 + j0.0511 0.5368 + j0.0481 0.4891 + j0.0452
7.0
8.19.711.5
12.914.316.0
18.420.623.3
5.5
5.55.55.5
5.55.55.5
5.55.55.5
0.1
0.10.10.1
0.10.10.1
0.10.10.1
1.5
1.61.61.7
1.81.81.9
2.02.12.2
2.5
2.52.52.5
3.153.153.15
3.153.153.15
59.5
62.466.170.2
75.278.682.7
88.393.5100.1
1000
500500500
500500250
250250250
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
2.9 3.0 3.1 3.2 3.4 3.5 3.6 3.8 3.9 4.2
0.5345 + j0.1319 0.3949 + j0.1230 0.2738 + j0.1160 0.1976 + j0.1102 0.1571 + j0.1055 0.1278 + j0.1022 0.1029 + j0.0989 0.0794 + j0.0946 0.0646 + j0.0917 0.0522 + j0.0887
94
Central Cables Berhad
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 19/33 (36)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
507095
120150185
240300
507095
120150185
240300
201239282
317353392
446495
183223264
298331372
427473
237282337
383432482
557629
0.8870.6330.476
0.3950.3382.903
0.2470.221
0.6999 0.7814 0.8667 0.9353 1.0028 1.084 1.1946 1.2975
0.3949 + j0.1360 0.2737 + j0.1282 0.1975 + j0.1216 0.1569 + j0.1163 0.1276 + j0.1126 0.1026 + j0.1086 0.0790 + j0.1037 0.0641 + j0.1002
1.0012 + j0.0924 0.0852 + j0.0846 0.7358 + j0.0780 0.6709 + j0.0728 0.6194 + j0.0690 0.5699 + j0.0651 0.5163 + j0.0662 0.4764 + j0.0562
8.19.711.5
12.914.316.0
18.420.6
8.08.08.0
8.08.08.0
8.08.0
0.10.10.1
0.10.10.1
0.10.1
1.81.81.9
2.02.02.1
2.22.3
3.153.153.15
3.153.153.15
3.153.15
3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.3
75.779.483.7
87.290.694.7
100.3105.5
500500500
250250250
250250
THREE CORE - CU / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
95
Central Cables Berhad
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLE DIMENSION
XLPE INSULATED ARMOURED SHEATHED CABLE 19/33 (36)kV
Nominal cross-
sectional area of
conductor
Nominal cross-
sectional area of
conductor
Maximum 3 phase voltage
drop
Minimum charging current
Positive & negative sequence impedance at
25°C*
Zero sequence impedance at 25°C*Buried direct
in ground
In single-way PE duct in ground
In tray in air (indoor)
Single Cable SingleCable
SingleCable
Maximum current rating per conductor*
Nominal thickness
of separation
sheath
Nominal diameter of conductor
Nominal insulation thickness
Armouringwire
diameter
Standard packing length
Nominal thickness of PVC outer sheath
Approximate overall diameter
Metallic screening
Nominal thickness of copper
tape
mm2
mm2 A A A mV/A/m A/km ohm/km ohm/km
mm mm mm mm mm mm mm m/drum
507095
120150185
240300
507095
120150185
240300
165199237
267301335
385432
145176210
237267299
344386
185226273
309356398
464530
1.4431.0090.742
0.5970.4980.411
0.3320.284
0.7030 0.7793 0.8705 0.9406 1.0076 1.0901 1.2007 1.3031
1.6464 + j0.0921 1.4445 + j0.0808 1.2077 + j0.0778 1.0991 + j0.0725 1.0156 + j0.0688 0.9326 + j0.0648 0.8446 + j0.0600 0.7794 + j0.0565
8.29.811.6
13.014.416.2
18.520.7
8.08.08.0
8.08.08.0
8.08.0
0.10.10.1
0.10.10.1
0.10.1
1.81.81.9
2.02.02.1
2.22.3
3.153.153.15
3.153.153.15
3.153.15
3.4 3.5 3.7 3.8 3.9 4.0 4.2 4.3
75.879.683.9
87.490.894.9
100.6105.7
500500500
250250250
250250
THREE CORE - AL / XLPE / CTS / PVC / SWA / PVC SHEATHED CABLEELECTRICAL PROPERTIES
*Note : Electrical properties are calculated base on conditions in appendix B.
0.6541 + j0.1356 0.4522 + j0.1278 0.3269 + j0.1213 0.2587 + j0.1160 0.2109 + j0.1123 0.1683 + j0.1048 0.1289 + j0.1035 0.1038 + j0.1001
96
Central Cables Berhad
(A) SHORT CIRCUIT AND EARTH FAULT CURRENT RATING
APPENDIX ATECHNICAL DATA
Nominal cross-
sectional area of
conductor or metallic
screen
Short Circuit Current Rating Earth Fault Current Rating
1 second 1 second1 second 1 second3 second 3 second3 second 3 second
Copper Conductor
K = 142.9
Initial temp. : 90°CFinal temp. : 250°C
Copper Screen
K = 148.4
Initial temp. : 80°CFinal temp. : 250°C
Aluminium Conductor
K = 94.5
Initial temp. : 90°CFinal temp. : 250°C
Aluminium Screen
K = 98.1
Initial temp. : 80°CFinal temp. : 250°C
mm2 kA kA kA kA
1.52.54
61016
253550
7095120
150185240
300400500
630
0.2140.3570.572
0.8571.432.29
3.575.007.15
10.013.617.1
21.426.434.3
42.957.271.5
90.0
---
--
1.51
2.363.314.73
6.628.9811.3
14.217.522.7
28.437.847.3
59.5
0.220.370.59
0.891.492.38
3.715.207.43
10.414.117.8
22.327.535.7
44.659.474.3
93.6
---
---
2.453.434.91
6.879.3211.8
14.718.223.5
29.439.249.1
61.8
0.1240.2060.330
0.4950.8251.32
2.062.894.13
5.787.849.90
12.415.319.8
24.833.041.3
52.0
---
--
0.873
1.361.912.73
3.825.186.55
8.1810.113.1
16.421.827.3
34.4
0.130.210.34
0.510.861.37
2.143.004.29
6.008.1510.3
12.915.920.6
25.734.342.9
54.0
---
---
1.421.982.83
3.975.386.80
8.5010.513.6
17.022.728.3
35.7
Formula :- I = K x A t I is the current rating in ampere (A) K is the constant value of the conductive material at reference temperature. A is the cross-sectional area of conductor (mm²) t is the short circuit duration in second. Example:- Given earth fault rating at 25kA in 3 second. Therefore, the screen area shall be at least:- For copper screen:- For aluminium screen:- 25 x 1000 x 3 = 291.79mm² 25 x 1000 x 3 = 441.40mm² 148.4 98.1
97
Central Cables Berhad
APPENDIX ATECHNICAL DATA
2..0mm 2
1.5mm 2
1000mm2
800mm2
630mm2
500mm2
400mm2
300mm2
240 mm2
150mm2
185mm2
120mm2
95mm2
70mm2
50mm2
35mm2
25mm 2
16mm2
10mm2
6.0mm 2
4.0mm 2
1000
100
10
10
1
10.1
0.1
Short circuit current ratings for Copper conductors
Duration of short circuit seconds
Max
. Con
duct
or S
hort
Cir
cuit
Cur
rent
in k
A 1000mm2
800mm2
600mm2
500mm2
400mm2
300mm2
240mm2
155mm2
150mm2
120mm2
95mm2
70mm2
50mm2
35mm2
25mm2
16mm2
10mm2
6.0mm2
4.0mm2
98
(A) SHORT CIRCUIT CURRENT RATINGS FOR COPPER CONDUCTORS
Central Cables Berhad
APPENDIX ATECHNICAL DATA
2..0mm 2
1.5mm 2
1000mm2
800mm2
630mm2
500mm2
400mm2
300mm2
240 mm2
150mm2
185mm2
120mm2
95mm2
70mm2
50mm2
35mm2
25mm 2
16mm2
10mm2
6.0mm 2
4.0mm 2
1000
100
10
10
1
1
0.1
0.1
Short circuit current ratings for Aluminium conductors
Duration of short circuit seconds
Max
. Con
duct
or S
hort
Cir
cuit
Cur
rent
in k
A
1000mm2
800mm2
600mm2
500mm2
400mm2
300mm2
240mm2
155mm2
150mm2
120mm2
95mm2
70mm2
50mm2
35mm2
25mm2
16mm2
10mm2
6.0mm2
4.0mm2
(A) SHORT CIRCUIT CURRENT RATINGS FOR ALUMINIUM CONDUCTORS
99
Central Cables Berhad
(B) CURRENT RATING INFORMATIONS. The Current rating of the cables given in the tables are based on the assumption shown below : 1) Maximum conductor temperature : ---------------------------------------------------- 90°C 2) Ambient temperature : Ground ------------------------------------------ 15°C Air ------------------------------------------------ 30°C 3) Soil thermal resistivity : ----------------------------------------------------- 1.2 K.m/W 4) Laying depth in ground : ----------------------------------------------------- 800mm 5) Screen bonding : Single core cables ---------------------------- Bonded at both ends Three core cables ---------------------------- Single point or Cross-bonded 6) Installation method : 1 core cables in ground 1 core cables in duct : 1 core cables in tray in air Multi-core cable in ground : Multi-core cable in duct Multi-core cable in tray in air All the ratings for cables install in duct in ground are assumed to be polyethylene(PE) duct type having an inside diameter of 1.5 times the outside diameter of the cable and a wall thickness equal to 6% of the duct inside diameter.
All the ratings for cables install in tray in air are calculated for indoor use only without any solar radiation taken into account. The cables are assumed to be spaced at least 0.5 times the cable diameter for single core cables and 0.3 times the cable diameter for three-core cables from any vertical surface such as wall and installed in non-magnetic cable tray.
conductor.
APPENDIX BTECHNICAL DATA
Trefoil
Trefoil
Trefoil
Single cable
Single cable Single cable
100
Central Cables Berhad
APPENDIX CTECHNICAL DATA
(C) CURRENT RATING CORRECTION FACTORS.
Table 1 Correction factors for ambient air temperatures.
Maximum conductortemperature °C
Ambient air temperature °C
9020
1.0825
1.0430
1.0035
0.9640
0.9145
0.8750
0.8255
0.76
Table 2 Correction factors for ambient ground temperatures.
Maximum conductortemperature °C
Ambient ground temperature °C
9010
1.0315
1.0020
0.9725
0.9330
0.8935
0.8640
0.8245
0.77
Table 4 Correction factors for depth laying for cables in duct in ground.
Depth layingm
Three-core cables
Single-core cablesNominal conductor size
mm²
0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00
1.04 1.02 1.00 0.98 0.96 0.95 0.94 0.93 0.91 0.90
1.05 1.03 1.00 0.97 0.95 0.93 0.92 0.91 0.89 0.88
1.03 1.02 1.00 0.99 0.97 0.96 0.95 0.94 0.93 0.92
Table 3 Correction factors for depth laying for direct buried cables.
Depth layingm
Three-core cables
Single-core cablesNominal conductor size
mm²
0.50 0.60 0.80 1.00 1.25 1.50 1.75 2.00 2.50 3.00
1.04 1.02 1.00 0.98 0.96 0.95 0.94 0.93 0.91 0.90
1.06 1.04 1.00 0.97 0.95 0.93 0.91 0.90 0.88 0.86
1.04 1.03 1.00 0.98 0.96 0.95 0.94 0.93 0.91 0.90
> 185 mm²
> 185 mm²
101
Central Cables Berhad
APPENDIX CTECHNICAL DATA
(C) CURRENT RATING CORRECTION FACTORS.
Table 5 Correction factors for soil thermal resistivities for direct buried single-core cables.
Nominalarea of
conductormm²
Values of soil thermal resistivity K.m/W
2535
507095
120150185
240300400
500630
1.231.241.24
1.251.251.25
1.261.261.26
1.261.271.27
1.271.27
1.171.181.18
1.181.191.19
1.191.191.19
1.201.201.20
1.201.20
1.121.121.12
1.131.131.13
1.131.131.13
1.131.141.14
1.141.14
1.071.071.07
1.081.081.08
1.081.081.08
1.081.081.09
1.091.09
1.001.001.00
1.001.001.00
1.001.001.00
1.001.001.00
1.001.00
0.910.910.91
0.910.910.91
0.910.910.90
0.900.900.90
0.900.90
0.800.800.80
0.800.800.79
0.790.790.79
0.790.790.79
0.790.79
0.730.730.72
0.720.720.72
0.720.710.71
0.710.710.71
0.710.71
0.670.670.66
0.660.660.66
0.660.660.65
0.650.650.65
0.650.65
0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0Moist Dry
Recommended value of soil thermal resistivities are as follows: Peat / Clay / Chalk soil 1.2 K.m/W Very dry soil 3.0 K.m/WVery stony soil 1.5 K.m/W Dry soil 2.0 K.m/WSandy soil 2.5 K.m/W Moist soil 1.0 K.m/WThe value for the all soils category may be reduced to 1.2 K.m/W if the soil is under impermeable cover such as asphalt or concrete.
Table 6 Correction factors for soil thermal resistivities single-core cables in buried ducts.
Nominalarea of
conductormm²
Values of soil thermal resistivity K.m/W
2535
507095
120150185
240300400
500630
1.141.151.15
1.161.161.16
1.171.171.17
1.171.181.18
1.181.18
1.101.111.11
1.111.121.12
1.121.121.12
1.131.131.13
1.131.13
1.081.081.08
1.081.081.08
1.081.081.08
1.081.091.09
1.091.09
1.041.041.04
1.051.051.05
1.051.051.05
1.051.051.06
1.061.06
1.001.001.00
1.001.001.00
1.001.001.00
1.001.001.00
1.001.00
0.920.920.92
0.920.920.92
0.920.920.91
0.910.910.91
0.910.91
0.820.820.82
0.820.820.81
0.810.810.81
0.810.810.81
0.810.81
0.760.760.75
0.750.750.75
0.750.740.74
0.740.740.74
0.740.74
0.700.700.69
0.690.690.69
0.690.690.68
0.680.680.68
0.680.68
0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0Moist Dry
102
Central Cables Berhad
APPENDIX CTECHNICAL DATA
(C) CURRENT RATING CORRECTION FACTORS.
Table 7 Correction factors for soil thermal resistivities for direct buried three-core cables.
Nominalarea of
conductormm²
Values of soil thermal resistivity K.m/W
2535
507095
120150185
240300400
500630
1.211.211.22
1.221.231.23
1.231.231.23
1.231.231.23
1.231.24
1.171.171.17
1.171.171.17
1.171.171.17
1.171.171.17
1.171.18
1.111.111.11
1.111.121.12
1.121.121.12
1.121.121.12
1.121.12
1.071.071.07
1.071.071.07
1.071.071.07
1.081.081.08
1.081.08
1.001.001.00
1.001.001.00
1.001.001.00
1.001.001.00
1.001.00
0.920.920.91
0.910.910.91
0.910.910.91
0.910.910.91
0.910.91
0.820.810.81
0.810.810.80
0.810.810.81
0.800.800.80
0.800.80
0.740.740.74
0.740.730.73
0.730.730.73
0.730.730.73
0.730.72
0.690.680.68
0.680.680.67
0.670.670.67
0.670.670.67
0.670.67
0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0Moist Dry
Recommended value of soil thermal resistivities are as follows: Peat / Clay / Chalk soil 1.2 K.m/W Very dry soil 3.0 K.m/WVery stony soil 1.5 K.m/W Dry soil 2.0 K.m/WSandy soil 2.5 K.m/W Moist soil 1.0 K.m/WThe value for the all soils category may be reduced to 1.2 K.m/W if the soil is under impermeable cover such as asphalt or concrete.
Table 8 Correction factors for soil thermal resistivities three-core cables in buried ducts.
Nominalarea of
conductormm²
Values of soil thermal resistivity K.m/W
2535
507095
120150185
240300400
500630
1.101.101.11
1.111.121.12
1.121.121.12
1.121.121.12
1.121.13
1.091.091.09
1.091.091.09
1.091.091.09
1.091.091.09
1.091.10
1.041.041.04
1.041.051.05
1.051.051.05
1.051.051.05
1.051.05
1.031.031.03
1.031.031.03
1.031.031.03
1.041.041.04
1.041.04
1.001.001.00
1.001.001.00
1.001.001.00
1.001.001.00
1.001.00
0.930.930.92
0.920.920.92
0.920.920.92
0.920.920.92
0.920.92
0.840.830.83
0.830.830.82
0.830.830.83
0.820.820.82
0.820.82
0.780.780.78
0.780.770.77
0.770.770.77
0.770.770.77
0.770.76
0.750.730.73
0.730.730.72
0.720.720.72
0.720.720.72
0.720.72
0.7 0.8 0.9 1.0 1.2 1.5 2.0 2.5 3.0Moist Dry
103
Central Cables Berhad
APPENDIX CTECHNICAL DATA
(C) CURRENT RATING CORRECTION FACTORS.
Table 9 Correction factors for groups of three-core cables in horizontal formation laid direct in ground.
Table 10 Correction factors for groups of three-phase circuits of single-core cables laid direct in the ground.
Table 11 Correction factors for groups of three-core cables in single way ducts in horizontal formation.
Table 12 Correction factors for groups of three-phase circuits of single-core cables in single-way ducts.
Number of circuits
Number of circuits
Number of circuits
Number of circuits
Spacing between cable centres(mm)
Spacing between cable centres(mm)
Spacing between cable centres(mm)
Spacing between cable centres(mm)
123
456
123
456
123
456
123
456
1.000.800.69
0.620.570.54
1.000.730.60
0.540.490.46
1.000.850.75
0.690.650.62
1.000.780.66
0.590.550.51
1.000.860.77
0.720.680.65
1.000.830.73
0.680.630.61
1.000.880.80
0.750.720.69
1.000.850.75
0.700.660.64
1.000.900.82
0.790.760.74
1.000.880.79
0.750.720.70
1.000.920.85
0.820.790.77
1.000.890.81
0.770.740.72
1.000.920.86
0.830.810.80
1.000.900.83
0.800.780.76
1.000.940.88
0.860.840.83
1.000.910.85
0.820.800.78
1.000.940.89
0.870.850.84
1.000.920.86
0.840.820.81
1.000.950.91
0.890.870.87
1.000.930.88
0.860.840.83
Touching
Touching
Touching
Touching
200
200
200
200
400
400
400
400
600
600
600
600
800
800
800
800
104
Central Cables Berhad
APPENDIX DTECHNICAL DATA
(D) XLPE CABLE INSTALLATION GUIDE
Table 13 XLPE cable minimum bending radius
Note : D is overall diameter of the cable. Table 14 Side wall pressure Permissible maximum side wall pressure to the cable at bending point during installation is 500 kgf/m. Side wall Pulling tension (kg) T pressure = = to cable Bending radius (m) R
FOR VOLTAGE 1 kV UP TO AND INCLUDING 3.3kV
Fixed installationDuring installation
Unarmoured cable
- Circular conductor
- Shaped conductor
Armoured cable
- Circular conductor
- Shaped conductor
Unarmoured cable
- Single core
- Three core
Armoured cable
- Single core
- Three core
6D
8D
6D
8D
20D
15D
15D
12D
6D
8D
6D
8D
15D
12D
12D
10D
FOR VOLTAGE 6.6 kV UP TO AND INCLUDING 33kV
Means of pulling
With pulling eye on
conductor
With pulling eye on
armour
With stocking grip*
Factor,
Cu conductor = 70 N/mm²
Al conductor = 50 N/mm²
Steel wire armour = 100 N/mm²
Al wire armour = 50 N/mm²
Type of cable
All type of cables
Armoured cables
Unarmoured cables
Formula
P = x A
P = 120D
Table 15 Permissible maximum pulling force
P = Permissable maximum pulling force in N A = Total cross sectional area in mm² of the conductor or armour D = Overall diameter of the cable
*Note : When P = 120D more than P = x A, than the permissible pulling force shall be refered to P = x A.
105
Central Cables Berhad
PUBLICATIONS REFERRED TO
IEC 60038 IEC Standard Voltages
IEC 60060 High Voltage Test Techniques
IEC 60183 Guide To The Selection Of High Voltage Cable
IEC 60228 Conductors Of Insulated Cable
IEC 60230 Impulse Test On Cables And Their Accessories
IEC 60287 Electric Cable - Calculation Of The Current Rating
IEC 60332 Test On Electric Cable Under Fire Conditions
IEC 60502 Power Cable With Extruded Insulation And Their Accessories For Rated Voltages
From 1 kV (Um = 1.2 kV) Up To 30 kV (Um = 36 kV)
IEC 60724 Short Circuit Temperature Limits Of Electric Cable With Rated Voltage Of 1 kV
(Um = 1.2 kV) And 3 kV (Um = 3.6 kV)
IEC 60811 Common Test Methods For Insulating And Sheathing Materials Of Electric Cables And Optical Cable.
IEC 60885 Electrical Test Methods For Electric Cable
IEC 60986 Short Circuit Temperature Limits Of Electric Cable With Rated Voltage From 6 kV
(Um = 7.2 kV) And 30 kV (Um = 36 kV)
BS 5467 Electric Cables - Thermosetting Insulated, Armoured Cables For Voltages Of
600/1000 V And 1900/3300 V.
106
107
Central Cables BerhadNotes
108
Central Cables BerhadNotes
109
Central Cables BerhadNotes
110
Central Cables BerhadNotes
111
Central Cables BerhadNotes
Customer details ( please type or print clearly )
Name Position in company..............................................................................................................................................................................
Company..............................................................................................................................................................................
Address..............................................................................................................................................................................
..............................................................................................................................................................................
..............................................................................................................................................................................
Post / Zip Code Country..............................................................................................................................................................................
Telephone Facsimile..............................................................................................................................................................................
e-mail @..............................................................................................................................................................................
Signed Date..............................................................................................................................................................................
Product Interested
Bare Cu / Al Conductor
XLPE INSULATED Cu / Al Power Armoured Cables (LV)
XLPE / PVC Cu / Al Cables (LV)
XLPE or PE Al Aerial Bundle Cables (LV&MV)
PVC Insulated Flexible Cords
PVC Insulated Cables (Non-Armoured)
For Electric Power and Lighting
PVC Insulated Cables (Armoured) For Electricity Supply
XLPE Insulated Power Cables (MV)
XLPE Insulated Armoured Cables (MV)
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Central Cables Berhad (7169-A)7862. Batu Berendam, 75350 Melaka, Malaysia.
P.O. Box 313, 75760 Melaka, Malaysia.
Fold this flap for sealing
Fold this flap for sealing
Fold this flap for sealing
Affix stamp
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Disclaimer :
Use the information in this book on the risk of users only.
Although we make every effort to publish information or material as accurately as possible, we do
not make any statement or warranty in respect of this book and not responsible for any loss, directly
or indirectly. We reserve the right to improve the content of this book from time to time without prior
notice.
Revision : O