INVESTIGATING THE ROW SHEAR FAILURE OF BOLTED
CONNECTION IN SELANGAN BATU WOOD
MUHAMMAD AIMAN BIN MAT GHANI
Bachelor of Engineering with Honours
(Civil Engineering)
2017
UNIVERSITI MALAYSIA SARAWAK
Grade _____
Please tick (J)
Final Year Project Report ~
Ivlasters D PhD D
DECLAILTIO~ OF ORIGINAL WORK
This declaration is made on the 7 day oc 3y 2017
Students Declaratinn
I MUHAMMAD AlMAN BIN MAT GHANI (42379) from FACULTY OF ENGINEERING hereby declale that the work entitled IoNESTIGATING ROW SHEAR FAILURE OF BOLTED CONlECTION TN SELANGAN BATU rOOD is my oritill ai wotlL 1 have not copied from any other students work or from any other SOUlCCS except wheTe due refer ence or acknowledgement is made egtlllicitly in the tt nOT has any p mi been written for me by another person
l~ -- y ~ fUHAMMAP ArMAN BTN MAT GHA -r (4 2379) Date submitted Name of the student (Matrie No )
Supervi sors Declaration
I DR ABDUL RAZ-K ABDUL KARIM hereby certifies thaI the work enti tJed INVESTIGATrO~ ROW SHEAR FAILURE OF BOLTED CONNECTIOJli IN SELANGA BAlU WOOD was prepared ur the above named studen t and was submitted to the FACULTY as a paJllallfullk
fulfillment foJ the coruerment of DEGREE OF BACHELOR OF ENGINEERING (RONS) (CIVU ENGINEERING) and the aforementioned work to the best of Ill kn owledge is the said studenLs work
Received for examination by DR ABDUL RAz1K ABDUL MRLr Oame of the supervisor)
1 declare that ProjectJThesis is classified as (please tick h))
D CONFIDENTL~ (Contains confidential information under the Official Secret Act 1972) D RESTRICTED (ConLallls Jestricted information as by the organization whece
research was done) []] OPEN ACCESS
Validarion of Projectllhesis
1 therefole duly offirmed with free consen t and willingness declare that this said Projectrrhesis shall be placed officially in the Centre for Academic Information Services with the ahiding interest and l~gh ts as follows
bull This Projectrrhesis is the sale legal property of Universiti Malaysia Sarawak (UNlMAS) bull The Centre fo r Acadcmic Information Services has th e lawful right to make copies for th e
purpo of eademic and research only an d not for other purpose bull The Cenie for Academic Information Services has the lawful right La digltalise the
content for the Local Content Database bull Th e Centre for Academic Irrformation Services has the lawful right to make copies of the
Pro]ectrrhesis for academic exchange between Higher Learning Institute bull No disp Lt te or any claim shall arise from the student itself neitber thlrd patty on this
Projectrfhesis once it becomes the sale property of UNIMAS bull This PrnjectJrhesis 01middot any material data and information related to it 8h1l not be
distributed pu bJihed 01 (hsclosed to any party by the stuMnt except with lDltIMAS j)CJlDisSiOIl
Supervisor signature
CUrIent Address Lot 46-13 Jalan Kubur 17500 Tanah Merah Kclanlan Darul ~aim
~()te8 If the ProiectlThesis is CO NFIDENTLlL or RESTR lCTED plca5e attach together as annenlre a letter from the organisation ith the period and re asons of confidentiali ty and restriction
[rne instlument is duly prepaJed by Tne Centre for Academic Infonnfltioll S~rvices]
INVESTIGATING THE ROW SHEAR FAILURE OF BOLTED CONNECTION IN
SELANGAN BATU WOOD
MUHAMMAD AIMAN BIN MAT GHANI
This project is submitted in partial fulfillment of the requirement for the degree of
Bachelor of Engineering with Honors
(Civil Engineering)
Faculty of Engineering
Universiti Malaysia Sarawak
2017
This thesis is dedicated to my beloved parents for the support and unconditional love
i
ACKNOWLEDGEMENT
Alhamdullilah thank and praise to Allah SWT the Almighty and His Messenger for His
blessing for successfully complete this study ldquoInvestigating The Row Shear Failure of Bolted
Connection of Selangan Batu Woodrdquo
I would like to express my gratitude and appreciation to my supervisor Dr Abdul Razak
Abdul Karim for his guidance and excellent advice through the entire time during completing
this project There are a lot of advised and ideas that I received from him along the completing
this project Without his help guidance time and advised this project cannot be successfully
done
I also would like to thank to the Universiti Malaysia Sarawak for giving the opportunity to do
this project with their financial and technical support Special thanks to the assistant engineer of
the Civil Engineering Laboratory(Mr Adha and Mr Zaidi) Chemical Engineering
Laboratory(Mr Abang) and Mechanical Engineering Laboratory(Mr Sabariman) for their help
and guidance during the experimental process Endless thanks to my teammates Abu Rashid bin
Abu Bakar Norsyathirah bin Shoib Vikki Diane Anak Sampai Angela Ramas Anak Tembak
and my fellow friends for encouragement and support along completing this project
Last and not least an endless thank and love to my beloved family (Mat Ghani bin Mahmud
and Siti Hajar binti Majid) for giving the blessing concern support and encouragement during
the progressing on this project with their best wishes May Allah bless all of you
Thank you
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
UNIVERSITI MALAYSIA SARAWAK
Grade _____
Please tick (J)
Final Year Project Report ~
Ivlasters D PhD D
DECLAILTIO~ OF ORIGINAL WORK
This declaration is made on the 7 day oc 3y 2017
Students Declaratinn
I MUHAMMAD AlMAN BIN MAT GHANI (42379) from FACULTY OF ENGINEERING hereby declale that the work entitled IoNESTIGATING ROW SHEAR FAILURE OF BOLTED CONlECTION TN SELANGAN BATU rOOD is my oritill ai wotlL 1 have not copied from any other students work or from any other SOUlCCS except wheTe due refer ence or acknowledgement is made egtlllicitly in the tt nOT has any p mi been written for me by another person
l~ -- y ~ fUHAMMAP ArMAN BTN MAT GHA -r (4 2379) Date submitted Name of the student (Matrie No )
Supervi sors Declaration
I DR ABDUL RAZ-K ABDUL KARIM hereby certifies thaI the work enti tJed INVESTIGATrO~ ROW SHEAR FAILURE OF BOLTED CONNECTIOJli IN SELANGA BAlU WOOD was prepared ur the above named studen t and was submitted to the FACULTY as a paJllallfullk
fulfillment foJ the coruerment of DEGREE OF BACHELOR OF ENGINEERING (RONS) (CIVU ENGINEERING) and the aforementioned work to the best of Ill kn owledge is the said studenLs work
Received for examination by DR ABDUL RAz1K ABDUL MRLr Oame of the supervisor)
1 declare that ProjectJThesis is classified as (please tick h))
D CONFIDENTL~ (Contains confidential information under the Official Secret Act 1972) D RESTRICTED (ConLallls Jestricted information as by the organization whece
research was done) []] OPEN ACCESS
Validarion of Projectllhesis
1 therefole duly offirmed with free consen t and willingness declare that this said Projectrrhesis shall be placed officially in the Centre for Academic Information Services with the ahiding interest and l~gh ts as follows
bull This Projectrrhesis is the sale legal property of Universiti Malaysia Sarawak (UNlMAS) bull The Centre fo r Acadcmic Information Services has th e lawful right to make copies for th e
purpo of eademic and research only an d not for other purpose bull The Cenie for Academic Information Services has the lawful right La digltalise the
content for the Local Content Database bull Th e Centre for Academic Irrformation Services has the lawful right to make copies of the
Pro]ectrrhesis for academic exchange between Higher Learning Institute bull No disp Lt te or any claim shall arise from the student itself neitber thlrd patty on this
Projectrfhesis once it becomes the sale property of UNIMAS bull This PrnjectJrhesis 01middot any material data and information related to it 8h1l not be
distributed pu bJihed 01 (hsclosed to any party by the stuMnt except with lDltIMAS j)CJlDisSiOIl
Supervisor signature
CUrIent Address Lot 46-13 Jalan Kubur 17500 Tanah Merah Kclanlan Darul ~aim
~()te8 If the ProiectlThesis is CO NFIDENTLlL or RESTR lCTED plca5e attach together as annenlre a letter from the organisation ith the period and re asons of confidentiali ty and restriction
[rne instlument is duly prepaJed by Tne Centre for Academic Infonnfltioll S~rvices]
INVESTIGATING THE ROW SHEAR FAILURE OF BOLTED CONNECTION IN
SELANGAN BATU WOOD
MUHAMMAD AIMAN BIN MAT GHANI
This project is submitted in partial fulfillment of the requirement for the degree of
Bachelor of Engineering with Honors
(Civil Engineering)
Faculty of Engineering
Universiti Malaysia Sarawak
2017
This thesis is dedicated to my beloved parents for the support and unconditional love
i
ACKNOWLEDGEMENT
Alhamdullilah thank and praise to Allah SWT the Almighty and His Messenger for His
blessing for successfully complete this study ldquoInvestigating The Row Shear Failure of Bolted
Connection of Selangan Batu Woodrdquo
I would like to express my gratitude and appreciation to my supervisor Dr Abdul Razak
Abdul Karim for his guidance and excellent advice through the entire time during completing
this project There are a lot of advised and ideas that I received from him along the completing
this project Without his help guidance time and advised this project cannot be successfully
done
I also would like to thank to the Universiti Malaysia Sarawak for giving the opportunity to do
this project with their financial and technical support Special thanks to the assistant engineer of
the Civil Engineering Laboratory(Mr Adha and Mr Zaidi) Chemical Engineering
Laboratory(Mr Abang) and Mechanical Engineering Laboratory(Mr Sabariman) for their help
and guidance during the experimental process Endless thanks to my teammates Abu Rashid bin
Abu Bakar Norsyathirah bin Shoib Vikki Diane Anak Sampai Angela Ramas Anak Tembak
and my fellow friends for encouragement and support along completing this project
Last and not least an endless thank and love to my beloved family (Mat Ghani bin Mahmud
and Siti Hajar binti Majid) for giving the blessing concern support and encouragement during
the progressing on this project with their best wishes May Allah bless all of you
Thank you
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
1 declare that ProjectJThesis is classified as (please tick h))
D CONFIDENTL~ (Contains confidential information under the Official Secret Act 1972) D RESTRICTED (ConLallls Jestricted information as by the organization whece
research was done) []] OPEN ACCESS
Validarion of Projectllhesis
1 therefole duly offirmed with free consen t and willingness declare that this said Projectrrhesis shall be placed officially in the Centre for Academic Information Services with the ahiding interest and l~gh ts as follows
bull This Projectrrhesis is the sale legal property of Universiti Malaysia Sarawak (UNlMAS) bull The Centre fo r Acadcmic Information Services has th e lawful right to make copies for th e
purpo of eademic and research only an d not for other purpose bull The Cenie for Academic Information Services has the lawful right La digltalise the
content for the Local Content Database bull Th e Centre for Academic Irrformation Services has the lawful right to make copies of the
Pro]ectrrhesis for academic exchange between Higher Learning Institute bull No disp Lt te or any claim shall arise from the student itself neitber thlrd patty on this
Projectrfhesis once it becomes the sale property of UNIMAS bull This PrnjectJrhesis 01middot any material data and information related to it 8h1l not be
distributed pu bJihed 01 (hsclosed to any party by the stuMnt except with lDltIMAS j)CJlDisSiOIl
Supervisor signature
CUrIent Address Lot 46-13 Jalan Kubur 17500 Tanah Merah Kclanlan Darul ~aim
~()te8 If the ProiectlThesis is CO NFIDENTLlL or RESTR lCTED plca5e attach together as annenlre a letter from the organisation ith the period and re asons of confidentiali ty and restriction
[rne instlument is duly prepaJed by Tne Centre for Academic Infonnfltioll S~rvices]
INVESTIGATING THE ROW SHEAR FAILURE OF BOLTED CONNECTION IN
SELANGAN BATU WOOD
MUHAMMAD AIMAN BIN MAT GHANI
This project is submitted in partial fulfillment of the requirement for the degree of
Bachelor of Engineering with Honors
(Civil Engineering)
Faculty of Engineering
Universiti Malaysia Sarawak
2017
This thesis is dedicated to my beloved parents for the support and unconditional love
i
ACKNOWLEDGEMENT
Alhamdullilah thank and praise to Allah SWT the Almighty and His Messenger for His
blessing for successfully complete this study ldquoInvestigating The Row Shear Failure of Bolted
Connection of Selangan Batu Woodrdquo
I would like to express my gratitude and appreciation to my supervisor Dr Abdul Razak
Abdul Karim for his guidance and excellent advice through the entire time during completing
this project There are a lot of advised and ideas that I received from him along the completing
this project Without his help guidance time and advised this project cannot be successfully
done
I also would like to thank to the Universiti Malaysia Sarawak for giving the opportunity to do
this project with their financial and technical support Special thanks to the assistant engineer of
the Civil Engineering Laboratory(Mr Adha and Mr Zaidi) Chemical Engineering
Laboratory(Mr Abang) and Mechanical Engineering Laboratory(Mr Sabariman) for their help
and guidance during the experimental process Endless thanks to my teammates Abu Rashid bin
Abu Bakar Norsyathirah bin Shoib Vikki Diane Anak Sampai Angela Ramas Anak Tembak
and my fellow friends for encouragement and support along completing this project
Last and not least an endless thank and love to my beloved family (Mat Ghani bin Mahmud
and Siti Hajar binti Majid) for giving the blessing concern support and encouragement during
the progressing on this project with their best wishes May Allah bless all of you
Thank you
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
INVESTIGATING THE ROW SHEAR FAILURE OF BOLTED CONNECTION IN
SELANGAN BATU WOOD
MUHAMMAD AIMAN BIN MAT GHANI
This project is submitted in partial fulfillment of the requirement for the degree of
Bachelor of Engineering with Honors
(Civil Engineering)
Faculty of Engineering
Universiti Malaysia Sarawak
2017
This thesis is dedicated to my beloved parents for the support and unconditional love
i
ACKNOWLEDGEMENT
Alhamdullilah thank and praise to Allah SWT the Almighty and His Messenger for His
blessing for successfully complete this study ldquoInvestigating The Row Shear Failure of Bolted
Connection of Selangan Batu Woodrdquo
I would like to express my gratitude and appreciation to my supervisor Dr Abdul Razak
Abdul Karim for his guidance and excellent advice through the entire time during completing
this project There are a lot of advised and ideas that I received from him along the completing
this project Without his help guidance time and advised this project cannot be successfully
done
I also would like to thank to the Universiti Malaysia Sarawak for giving the opportunity to do
this project with their financial and technical support Special thanks to the assistant engineer of
the Civil Engineering Laboratory(Mr Adha and Mr Zaidi) Chemical Engineering
Laboratory(Mr Abang) and Mechanical Engineering Laboratory(Mr Sabariman) for their help
and guidance during the experimental process Endless thanks to my teammates Abu Rashid bin
Abu Bakar Norsyathirah bin Shoib Vikki Diane Anak Sampai Angela Ramas Anak Tembak
and my fellow friends for encouragement and support along completing this project
Last and not least an endless thank and love to my beloved family (Mat Ghani bin Mahmud
and Siti Hajar binti Majid) for giving the blessing concern support and encouragement during
the progressing on this project with their best wishes May Allah bless all of you
Thank you
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
This thesis is dedicated to my beloved parents for the support and unconditional love
i
ACKNOWLEDGEMENT
Alhamdullilah thank and praise to Allah SWT the Almighty and His Messenger for His
blessing for successfully complete this study ldquoInvestigating The Row Shear Failure of Bolted
Connection of Selangan Batu Woodrdquo
I would like to express my gratitude and appreciation to my supervisor Dr Abdul Razak
Abdul Karim for his guidance and excellent advice through the entire time during completing
this project There are a lot of advised and ideas that I received from him along the completing
this project Without his help guidance time and advised this project cannot be successfully
done
I also would like to thank to the Universiti Malaysia Sarawak for giving the opportunity to do
this project with their financial and technical support Special thanks to the assistant engineer of
the Civil Engineering Laboratory(Mr Adha and Mr Zaidi) Chemical Engineering
Laboratory(Mr Abang) and Mechanical Engineering Laboratory(Mr Sabariman) for their help
and guidance during the experimental process Endless thanks to my teammates Abu Rashid bin
Abu Bakar Norsyathirah bin Shoib Vikki Diane Anak Sampai Angela Ramas Anak Tembak
and my fellow friends for encouragement and support along completing this project
Last and not least an endless thank and love to my beloved family (Mat Ghani bin Mahmud
and Siti Hajar binti Majid) for giving the blessing concern support and encouragement during
the progressing on this project with their best wishes May Allah bless all of you
Thank you
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
i
ACKNOWLEDGEMENT
Alhamdullilah thank and praise to Allah SWT the Almighty and His Messenger for His
blessing for successfully complete this study ldquoInvestigating The Row Shear Failure of Bolted
Connection of Selangan Batu Woodrdquo
I would like to express my gratitude and appreciation to my supervisor Dr Abdul Razak
Abdul Karim for his guidance and excellent advice through the entire time during completing
this project There are a lot of advised and ideas that I received from him along the completing
this project Without his help guidance time and advised this project cannot be successfully
done
I also would like to thank to the Universiti Malaysia Sarawak for giving the opportunity to do
this project with their financial and technical support Special thanks to the assistant engineer of
the Civil Engineering Laboratory(Mr Adha and Mr Zaidi) Chemical Engineering
Laboratory(Mr Abang) and Mechanical Engineering Laboratory(Mr Sabariman) for their help
and guidance during the experimental process Endless thanks to my teammates Abu Rashid bin
Abu Bakar Norsyathirah bin Shoib Vikki Diane Anak Sampai Angela Ramas Anak Tembak
and my fellow friends for encouragement and support along completing this project
Last and not least an endless thank and love to my beloved family (Mat Ghani bin Mahmud
and Siti Hajar binti Majid) for giving the blessing concern support and encouragement during
the progressing on this project with their best wishes May Allah bless all of you
Thank you
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
ii
ABSTRACT
The main aim of this research study was to investigate the row shear failure of a bolted
connection particularly the connections between the masonry walls and timber floorroof
diaphragms in order to strengthen the unreinforced masonry buildings in Malaysia The reasons
for initiating this study because the occurrence of recent earthquake activities in Malaysia and
the similarity between Malaysia unreinforced masonry building characteristic compared to other
countries Similar building characteristics can obviously cause a major destruction to the
unreinforced masonry buildings that are well known to perform poorly during the earthquake
based on the past structural performance in previous earthquakes Another aim of this study was
to assess the strength of Selangan Batu wood bolted connection whereas the wood is commonly
used in the construction in Malaysia especially in Sarawak In the main bolted connection test
there are four groups of different connection arrangements of Selangan Batu wood which were
ten specimens in each group The current timber design equations that were used to calculate the
predicted values of the connection strength are Malaysia Standard European Yield Model and
Row Shear Model The results of the bolted connection test conducted were utilized to evaluate
the effectiveness of the Malaysian StandardEuropean Yield Model and Row Shear ModelThe
calibration factor was also determined for optimizing the connection design From the
comparison it is recommended to use European Yield Model and Row Shear Model to predict
the bolted connection strength in Selangan Batu wood because Malaysia Standard is too
conservative which can cause an uneconomical in designing the connection
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
iii
ABSTRAK
Tujuan utama kajian penyelidikan ini adalah untuk menyiasat kegagalan barisan ricih dalam
sambungan kayu diperketatkan terutamanya sambungan antara dinding batu dan diafragma
lantai kayubumbung bagi mengukuhkan bangunan batu tanpa tetulang di Malaysia Antara
sebab kajian ini dimulakan kerana berlakunya aktiviti gempa bumi di Malaysia pada baru-baru
ini dan persamaan antara ciri bangunan batu tanpa tetulang di Malaysia dengan negara-negara
lain Ciri-ciri binaan yang serupa jelas boleh menyebabkan kemusnahan besar kepada bangunan
batu tanpa tetulang yang terkenal dengan prestasi buruk semasa gempa bumi berdasarkan
prestasi struktur dalam gempa bumi sebelumnya Antara tujuan lain kajian ini adalah untuk
menilai kekuatan sambungan kayu Selangan Batu yang diperketatkan manakala kayu Selangan
Batu biasanya digunakan dalam pembinaan di Malaysia khususnya di Sarawak Dalam ujian
sambungan diperketatkan terdapat empat kumpulan sambungan yang berbeza jarak daripada
Selangan Batu kayu yang terkandung sepuluh specimen dalamnya Formular reka bentuk kayu
semasa yang digunakan untuk mengira ramalan nilai kekuatan sambungan adalah Malaysia
Standard European Yield Model dan Row Shear Model Keputusan ujian sambungan
diperketatkan juga digunakan bagi menilai keberkesanan Malaysian Standard European Yield
Model dan Row Shear Model Faktor penentukuran boleh ditentukan untuk mengoptimumkan
reka bentuk sambungan Dari perbandingan antara formular adalah disyorkan untuk
menggunakan European Yield Model dan Row Shear Model untuk meramalkan kekuatan
sambungan diperketatkan pada kayu Selangan Batu kerana Malaysia Standard adalah terlalu
konservatif dimana akan menyebabkan pengunaannya adalah tidak jimat dalam mereka
sambungan anatara kayu dengan bolt
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
iv
TABLE OF CONTENTS
ACKNOWLEDGEMENT i
ABSTRACT ii
ABSTRAK iii
TABLE OF CONTENTS iv
LIST OF FIGURES vii
LIST OF TABLES ix
NOMENCLATURE x
CHAPTER 1 1
INTRODUCTION 1
11 BACKGROUND 1
12 PROBLEM STATEMENTS 4
13 SCOPE OF STUDY 5
14 THESIS OUTLINE 5
Chapter 2 7
LITERATURE REVIEW 7
21 GENERAL 7
22 UNREINFORCED MASONRY BUILDING 7
23 CHARACTERISTICS OF UNREINFORCED MASONRY BUILDING 13
24 STATISTIC OF UNREINFORCED MASONRY BUILDING 15
25 POSSIBILITY OF EARTHQUAKE IN MALAYSIA 17
26 PERFORMANCE OF UNREINFORCED MASONRY BUILDING IN PAST
EARTHQUAKE 22
27 PREVIOUS STUDY ON WALL-DIAPHRAGM CONNECTION 26
28 CURRENT STANDARD 28
29 CURRENT EQUATION TO PREDICT THE STRENGTH CONNECTION 30
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
v
291 European Yield Model (EYM) 30
292 Brittle Failure Model 33
210 WHY SELANGAN BATU IS SELECTED 35
211 SUMMARY 36
Chapter 3 37
METHODOLOGY 37
31 GENERAL 37
32 PREPARATION OF TESTING RIGS 37
33 SELECTION OF TIMBER 40
34 TIMBER PROPERTIES TESTING 41
341 Moisture Content And Density 42
342 Embedding Strength Test 43
35 TIMBER BOLTED CONNECTION TESTING 44
351 Materials and Apparatus 45
352 Arrangement of Test Specimens 45
Chapter 4 48
RESULTS AND CONCLUSIONS 48
41 GENERAL 48
42 EMBEDDING STRENGTH TEST RESULT 48
43 MOISTURE CONTENT AND DENSITY RESULTS 49
44 BOLTED CONNECTION TEST RESULT 50
441 Failure Modes of Selangan Batu Hardwood 50
442 Ultimate Strength of connections 51
443 Calibration Factor 57
444 Experimental Results versus Prediction Results 57
45 SUMMARY OF RESULT AND ANALYSIS 60
Chapter 5 61
CONCLUSIONS AND RECOMMENDATIONS 61
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
vi
41 GENERAL 61
42 CONCLUSION 61
43 RECOMMENDATIONS FOR THE FUTURE RESEARCH 62
REFERENCES 63
APPENDIX A 68
APPENDIX B 72
APPENDIX C 78
APPENDIX D 85
APPENDIX E 87
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
vii
LIST OF FIGURES
Figure Page
Figure 11 Illustration of unreinforced masonry structure 2
Figure 21 St Micheal‟s All Angles Church at Sandakan Sabah (Balakrisnan
2015)
9
Figure 22 Kuala Lumpur Railway Station in the center of Kuala Lumpur (Al-
Syam amp Badarulzaman 2010)
9
Figure 23 India Street in Kuching Sarawak (The Borneo Post2016) 10
Figure 24 Square Tower Kuching (Unreinforced Masonry Building) 11
Figure 25 Unreinforced masonry building on India Street that‟s not well preserved 11
Figure 26 Unreinforced masonry building in front of WaterfrontKuching 12
Figure 27 Unreinforced masonry building that‟s become a commercial area on
India StreetKuching
12
Figure 28 Illustration of Unreinforced Masonry Building from FEMA (2009) 15
Figure 29 Locality of Unreinforced Masonry Buildings in Kuching area 17
Figure 210 Tectonic plate around Malaysia (Balendra 2001) 18
Figure 211 Damage caused by the tremor (The Borneo Post) 21
Figure 212 Example of In-Plane Failure of URM (Bruneau 1994) 24
Figure 213 Example of Out-of-Plane Failure of URM (Bruneau 1994) 24
Figure 214 Example of Combination Failure between In-plane and Out-of-plane
Failure of URM (Bruneau 1994)
25
Figure 215 Close up view of failure at the anchor plate connection (Cambell et al
2012)
25
Figure 216 Failure modes for timber bolted connection (a) net tension (b) group
tears out (c) row shear (d) bearing (e) splitting (Quenneville 2009)
33
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
viii
Figure 217 Example of Selangan Batu wood 35
Figure 31 Mild Steel Bolt and Nut specimen 38
Figure 32 Mild Steel Plate 39
Figure 33 Stainless steel rods and stainless steel testing rigs 39
Figure 34 Selangan Batu Balau use as the outdoor decking retrieve from
(Roudwood of Mayfield 2016)
40
Figure 35 Weighing the specimen for moisture content and density 42
Figure 36 Illustration of embedding strength test sample 43
Figure 37 Embeding Strength Test 44
Figure 38 Detailing of the Specimen with definition of the variable used 44
Figure 39 Drilling the specimen for preparation of bolted connection test 45
Figure 310 Specimen Configuration for Group 5 46
Figure 311 Specimen Configuration for Group 10 46
Figure 312 Specimen Configuration for Group 15 46
Figure 313 Specimen Configuration for Group 20 47
Figure 41 Typical load-displacement curves for Group 5 with 50 mm end distance 52
Figure 42 Tested specimen of Group 5J showing the row shear failure mode 52
Figure 43 Typical load-displacement curves for Group 10 with 50 mm end
distance and 100mm spacing between bolt
53
Figure 44 Tested specimen of Group 10G showing the splitting failure mode 53
Figure 45 Typical load-displacement curves for Group 15 with 50 mm end
distance and spacing
54
Figure 46 Tested specimen of Group 15J showing the splitting failure mode 54
Figure 47 Typical load-displacement curves for Group 20 with 50 mm end
distance and spacing between bolt
55
Figure 48 Tested specimen of Group 20C showing the row shear failure mode 55
Figure 49 Average predicted row shear strength values versus experimental values
for Group 5 1011121314151819 and 20
56
Figure 410 Prediction of 5th percentile against Experimental 5th percentile values
for Group 5 10 15 and 20
59
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
ix
LIST OF TABLES
Table Page
Table 21 Pilot Survey on the Conservation of Historical Buildings
in Malaysia
16
Table 22 Seismic record taken from the Malaysian Meteorological
Department fom January 2016 to May 2017
19
Table 23 Comparison of Ritcher Magnitude and Modified Mercalli
Intensity
20
Table 24 Details of earthquakes construction features and
damages that involve by unreinforced masonry building
22
Table 25 Previous research related witl timber bolted connection 27
Table 26 Basic working loads for a bolted joint system loaded
parallel to grain (Malaysia Standard 2001)
29
Table 27 Possible failure modes for single shear joint as per
European Yield Model
31
Table 28 Possible failure modes for double shear joint as per EYM 32
Table 31 Details of Equipment for testing timber bolted
connection strength (Samsudin 2016)
38
Table 32 Strength Groups of Timbers and Their Applications 41
Table 33 Detailing of specimen bolt connection arrangement 47
Table 41 Embedding test result of Selangan Batu hardwood 49
Table 42 Moisture and Density test result of Selangan Batu
hardwood
50
Table 43
Comparison and ratios between experimental and
prediction results
57
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
x
NOMENCLATURE
MC avg average moisture content
β ratio of the embedding strengths
Φ strength reduction factor
C1 average density
CF calibration factor
et timber end distance
k1 duration of load factor for strength
k11 bolt bearing stress factor
k12 factor for the design of bolted connections in green timber
k13 factor for the design of multiple-bolt connections
K17 factor for multiplied bolted joint given in table 15
K18 factor for member loaded surfaces (065 for side member 1 for
internal member)
t member thickness
t1 timber thickness or fastener penetration of member 1
t2 timber thickness or fastener penetration of member 2
tp thickness of steel plate
F basic working loads as derived in equation
d diameter of fastener
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
xi
My fastener yield moment
ρ5th
5
th percentile density
ρavg average density
R2 coefficient of determination
R5th
5th
percentile strength of the rest results
Ravg average experimental value
RSi min minimum (rs1 rs2hellip rsnr) in n
nr number of rows in the joint as per load component
RSi shear capacity along two shear plane fastener row ldquoirdquo in n
G 5th
percentile relative density of timber in the oven dry condition
nfi number of fasteners in a row ldquoirdquo
acri minimum of et and sb for row rdquoirdquo in mm
G relative density of timber for the oven dry condition
fv member shear strength
fyf fastener yield strength
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
1
CHAPTER 1
INTRODUCTION
11 BACKGROUND
Unreinforced masonry buildings still well preserved in Malaysia and often be the
historical places or become commercial buildings The unreinforced masonry buildings
have historical value that becomes attraction to the tourist and location of the unreinforced
masonry buildings that located at the center of town are suitable for commercial purposes
The design of the unreinforced masonry buildings in Malaysia was affluent from the
European colonial architecture that came to Malaysia from 1511 to 1957 There are three
European colonies that came to Malaya (Malaysia) and brought their architecture design to
adapt with a local design The first colony came to Malaya (Malaysia) is Portugese follow by
the Dutch and finally British (Endut 1993) The design of colonial buildings in Malaysia also
has combinations of local Malay traditional design and others culture designs such as Indian
and Chinese due to migrations (Chun et al 2005) A combination of local and foreign
architecture design produces a unique design that only can be found in Malaysia
In 1992 and 1993 inventory study has been conducted by the Heritage Trust of
Malaysia collaboration with the National Museum the Housing and Local Government
Ministry and Faculty of Built Environment University Technology Malaysia (UTM)
reported that around 39000 historic buildings are worth to be preserved and protected
(Kamal et al 2008) Remnants of the colony still can see until today that scattered around
big cities in Malaysia especially in Malacca and Pulau Pinang city From the author‟s
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
2
observation in Kuching city the unreinforced masonry buildings constructed from 1879 to
1954 can be found in the Waterfront India Street and Padungan areas According to Idid
(1995) there are around 1010 numbers of historic buildings in Sarawak and the number is
decreasing every year due to demolition for further city development
Since centuries ago unreinforced masonry buildings had been constructed by mankind
due to the characteristic of the masonry structure that had high durability fire resistance and
isolation properties (Barrantes 2012) Because of this characteristic masonry building still
well preserved and exist until nowadays worldwide Among the type of masonry buildings
that be constructed either it is new or old masonry buildings are unreinforced masonry
buildings and reinforced masonry buildings FEMA (2009) state that the unreinforced
masonry building consists of brick wall that contains no steel reinforcing in it As for the
masonry wall the brick hollow concrete block hollow clay tile and stone be used because
this material is strong enough to resist fire and to support the vertical load of the structure
From the author‟s observation in India streetit shows that most of the unreinforced masonry
buildings have no wall-diaphragm connection Figure 11 show the illustration of
unreinforced masonry buildings and there are no connections between masonry wall and
timber diaphragms Timber diaphragms only are slotted into the masonry wall and have high
risk to collapse if lateral force apply to these buildings
Figure 11 Illustration of unreinforced masonry structure
It is being long recognized that the unreinforced masonry building poses greater possibility
seismic risk to collapse compare to the new reinforced building during an earthquake (Bruneau
1994) According to Abdul Karim (2012) many unreinforced masonry buildings damaged
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
3
during the Hawke‟s Bay earthquake in New Zealand because this type of building cannot resist
lateral load induced by seismic force The similarity between Malaysia unreinforced masonry
building characteristics with other countries cause risk to collapse when ocurrence of earthquake
is highly to occur Unreinforced masonry failed to resist lateral load due to there is no connection
between masonry walls with floor and roof diaphragm There are several failure modes of the
unreinforced masonry building that related with the earthquake seismic According to Boussabah
amp Bruneau (1992) among the failure modes occur to the unreinforced masonry building are
anchor failure in-plane failures out of plane failure and diaphragm-related failure Post-
earthquake studies show that the dominant failure occur during seismic is out-of plane failure
mode in unreinforced masonry building including the previous Newcastle 1989 earthquake
(Vaculik 2012) The out-of plane failure occurs because there are no anchorage systems between
masonry wall and diaphragm Even the unreinforced masonry building has a wall-diaphragm
connection the structure will fail in anchorage and connection because the design of the
connection is not adequate to resist seismic lateral force (Bruneau 1994) From the previous
earthquake tragedy such The Great 1985 Chile earthquake unreinforced masonry buildings
were the most serious damage of structure compares to the reinforced concrete structure (Bolt
1993) This incident shows that the unreinforced masonry building is vulnerable to an earthquake
activity
In Malaysia there are 46 events of earthquake occurrence that be generated from the
Sumatra Indonesia that affect Peninsular Malaysia for the past few decade (The Institution of
Engineers Malaysia 2005) Brownjohn amp Pan (2001) state that although there are no damage
occur in Malaysia earthquake risk cannot be neglected because there are ground tremors have
been increasing reported in the past three decades Sabah earthquake 2015 clearly indicates that
Malaysia poses local seismic risk and most of structural constructions do not take an earthquake
affect into their design consideration In this earthquake there are several minor damages from
modern reinforced concrete buildings had been reported If an earthquake occurs at areas
consisting of unreinforced masonry building it will cause fatal to the people surrounding
because the unreinforced masonry building was not design to resist earthquake loading
In this thesis the main focus was to investigate the strength of the connection between
unreinforced masonry walls with roof diaphragm specifically in timber bolted connection The
failure that always occur at the timber bolted connection can be characterized either brittle failure
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
4
or ductile failure (Jensen amp Quenneville 2011) Quenneville (2009) also state that among the
brittle failure that occur in the timber bolted connection are group tear-out row shear-out
splitting and net tension There are previous research done by Abdul Karim on the assessment of
wall-diaphragm connection of the unreinforced masonry building This research was conducted
in New Zealand using Matai and Rimu timber that are New Zealand local timber In Malaysia
there are previous studies on Meraka and Belian hardwoods but there are no research be found
regarding Selangan Batu wood Thus the timber bolted connection test was conducted on
Selangan Batu wood to determine the connection strength of the wood in order to provide
guidelines for timber design purpose because Selangan Batu wood is categorized as strength
group 1 (SG1) in Malaysia Standard 544 and commonly use in heavy construction of structural
members of timber diaphragms in unreinforced masonry buildings In Malaysia the current
standard that can be used to predict the timber bolted connection strength is Malaysia Standard
544 Code of Practice for Structural Use of Timber (Part 5) that only considered ductile failure
in theirs‟ design European Yield Model and Row Shear Model also be used to predict the
strength of the timber bolted connection strength The effectiveness of these three equation can
be determined by doing the comparison with the experimental result
12 PROBLEM STATEMENTS
Wall-diaphragm connection is the important part that needs to be considered in
strengthening old unreinforced masonry buildings However there are a few research in
strengthening old unreinforced masonry by introducing wall-diaphragm connection (Abdul
Karim 2012) There also are lack of research on wall-diaphragm connection of unreinforced
masonry especially in Malaysia Until now there is no study regarding Selangan Batu wood
connection for wood-steel-wood type Current Standard that be used in Malaysia (MS544 2001
Part 5) only considers a ductile failure but there is also a brittle failure that needs to be
considered as proven in many previous research studies In this research the author tries to fill
the gaps from previous research works done to provide strength of Selangan Batu wood
connection through experimental testing Thus a verification can be done to the use of the
current design equation such as MS 544 European Yield Model and Row Shear Model
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
5
13 SCOPE OF STUDY
In Malaysia there are standard for the structural use of timber known as the Malaysia
Standard (MS5442001) that govern regarding the timber joint The present study was done
because the lack of data regarding the Malaysia wood connection The aim of this study was to
investigate the row shear failure in timber bolted connection of Selangan Batu wood Only
ductile failure is considered in the Malaysia Standard while the brittle failure also need be
considered to determine the bolted connection strength as many previous research observed this
Other than Malaysia Standard Row Shear Model and European Yield Model (EYM) equation
also be used in this thesis to predict the timber bolted connection The test results be compared
with the Malaysia Standard European Yield Model and Row Shear Model equation to determine
the effectiveness of the equation to predict timber bolted connection strength
The main objectives of this study are-
1 To identify basic properties of Selangan Batu woods to use in the strength prediction
calculations
2 To conduct timber bolted connection tests to determine the strength of the connection in
Selangan Batu heavy hardwood
3 To validate the current design equations with the experimental results obtained
14 THESIS OUTLINE
Along this thesis several chapters are discussed This thesis is divided into four (4) chapters
and the arrangement of the chapter shows the flow to fulfill the present study In the paragraph
below represent each chapter as follow
In the Chapter 1 Introduction the background study and scope of the study were discussed
briefly
In Chapter 2 Literature Review journals and thesis that related to the present study scope is
reviewed The history of the unreinforced masonry building and characteristic of the
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
6
unreinforced masonry building is discussed The performance of the unreinforced masonry
building and possibility of earthquake in Malaysia also be provided in this chapter To
understand the wall-diaphragm connection work previous study of the wall - diaphragm
connection are presented in detail To calculate the timber bolted connection the current
standard and current equation to predict the strength of connection are stated clearly
In Chapter 3 Methodology the author describes the workflow of the procedure to testing the
timber bolted connection moisture content and embedding strength The preparation of the
specimen also be stated in this chapter
In Chapter 4 Results and Discussion the result and data of the bolted connection strength
embedding strength test moisture content and density test are presented The design equation of
European Yield Model Row Shear Model and Malaysia Standard are compared with actual
experimental result to validate which design equation that is more suitable to use
In Chapter 5 Conclusions and Recommendation the conclusion of the study and
recommendation for future works is reported in this chapter
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
7
CHAPTER 2
LITERATURE REVIEW
21 GENERAL
This chapter reviews about unreinforced masonry buildings characteristics of the
unreinforced masonry building and statistic of the unreinforced masonry building in Malaysia
Photos of the unreinforced masonry building from several places in Malaysia also be included in
this chapter This chapter also discussed regarding the possibility of earthquake at Malaysia and
performance of the unreinforced masonry building during the past earthquakes This discussion
is important to highlight the risk of failure that will happen to the unreinforced masonry building
during an earthquake The previous studies of the wall-diaphragm connection of the unreinforced
masonry building are summarized to discuss the importance of the present study Current timber
standard of Malaysia are reviewed to compare with the existing design equations to verify their
effectiveness in predicting the strength of bolted connections The uses of Selangan Batu in this
testing also be discussed briefly in this chapter to stress out the importance of this study
22 UNREINFORCED MASONRY BUILDING
Masonry building is one of the oldest building that be constructed by mankind and remained
the least knowledge in construction industrial (Schneider amp Dickey 1987) Masonry building
had been recognized for the durability resistance and isolation properties (Barrantes 2012)
There are three types of structural masonry building that exist the first one is plain masonry or
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building
8
unreinforced masonry the second is the reinforced masonry and the last is pre-stressed masonry
(Ramli Abdullah amp Nawi 2014) In this thesis the author focused on unreinforced masonry
building FEMA (2009) state that unreinforced masonry building can be described as the
building that have a brick wall with no steel reinforcing bars embedded within them There are
still many unreinforced masonry buildings in Malaysia especially in Melaka and Penang from
the British colonial period The unreinforced masonry buildings in Malaysia are made from the
same materials but there is different in their architecture design of the unreinforced masonry
buildings The design of the unreinforced masonry buildings in Malaysia be affected by many
other cultures such as British Chinese Indian and Arabic culture apart from local Malay
traditional cultures (Chun et al 2005) The combination of local and foreign cultures produce a
unique building design that only can be found in Malaysia and this will attract more tourist to
visit Malaysia if the older unreinforced masonry buildings well preserved
In the recent years many of the unreinforced masonry buildings become historical building
that had be gazetted by government because each of the unreinforced masonry building has a
unique histories since it was build There are several unreinforced masonry buildings that
become a landmark and historical building in Malaysia for example St Micheal‟s amp All Angles
Church and Kuala Lumpur Railway Station St Micheal‟s and All Angles Churches in Figure 21
located at the Sandakan Sabah was built on 29 September 1893 by the Governor Charles
Vandeleur and the design of this building be affected from European style This unreinforced
masonry building was designed by the New Zealander Mr BW Mountfort and was first built
with Belian timber followed by brick and lastly using a stone as a material of the structures
(Balakrishnan 2015) Kuala Lumpur Railway Station in Figure 22 is also one of the examples
of the unreinforced masonry building that still be used and become a landmark in Malaysia The
Kuala Lumpur Railway Station was built in 1892 and in 2007 this building was gazetted as the
heritage building by the Malaysia government (Baharuddin et al 2014) Al-Shams and
Badarulzaman (2014) stated that the design of Kuala Lumpur Railway Station is adopting
Mughal style and it gives aesthetic value to the building