investigation on non-linear grading material ... - core · pdf filemodelled for this study by...
TRANSCRIPT
i
INVESTIGATION ON NON-LINEAR GRADING MATERIAL AS STRESS
CONTROL ON MEDIUM VOLTAGE CABLE TERMINATION
SITI NUR AISHAH BINTI MAHD RAWE
A project report submitted in partial
fulfillment of the requirements for the award of the
Degree of Master of Electrical Engineering
Faculty of Electrical and Electronic Engineering,
Universiti Tun Hussein Onn Malaysia
JANUARY 2014
v
ABSTRACT
Power cable terminations are widely used in power system networks for a last few
decades. A proper design of cable termination is essential in reducing the electric
field distribution around the end of high voltage cable. At the termination of cable,
the electric field was usually the highest, for the insulation layer was cut in this place.
And with the high electric field at the cutting point, there were surely partial
discharge occurs. In order to overcome this issue, some sorts of method were
proposed. Stress control geometry method and non-linear properties of Zinc Oxide
Microvaristor method have been used in this research. The aim was to find an
optimal solution for the electric field distribution. An 11kV power cable has been
modelled for this study by using Finite Elements Method (FEM) computational
solution. The model has been used to simulate the electric field distribution in the
cable termination. The structure of terminations and the critical parts in this design
were also defined through literature. A non-linear grading has been applied to several
design of layer insulation. The proposed model was used to covers the point that
generate high fields at screen cable insulation. Material properties play a key role in
suppresses electric field spread throughout termination area. Based on the switching
point of about 1kV/cm the material changes its conductivity significantly. In this way
it prevents the occurrence of electric fields which are above this switching point.
Different thicknesses also were introduced to get a better design and economically to
produce in cost advantages. This research successfully examines the effectiveness
for both methods in controlling field stress at cable screen termination.
vi
ABSTRAK
Penamatan kabel kuasa digunakan secara meluas dalam rangkaian sistem kuasa
selama beberapa dekad yang lalu. Apabila lapisan penebat penamatan kabel
dipotong, keadaan ini akan menghasilkan medan elektrik yang tinggi. Medan elektrik
yang tinggi pada pemotongan lapisan penebat kabel ini, akan terhasilnya pelepasan
medan elektrik . Untuk mengatasi isu ini, beberapa jenis kaedah telah dicadangkan.
Kawalan tekanan kaedah geometri dan ciri-ciri yang tidak linear iaitu Zink Oksida
‘Microvaristor’ telah digunakan dalam kajian ini. Sasaran utama kajian ini adalah
untuk mencari penyelesaian optimum bagi taburan medan elektrik. Kabel kuasa
11kV telah dimodelkan untuk kajian ini dengan menggunakan „Finite Element
Method’ (FEM) penyelesaian pengiraan. Model ini telah digunakan untuk simulasi
taburan medan elektrik penamatan kabel. Struktur penamatan dan bahagian-bahagian
penting dalam reka bentuk ini juga ditakrifkan melalui literatur. Bahan penggredan
yang tidak linear telah digunakan untuk beberapa reka bentuk lapisan penebat. Model
yang dicadangkan telah digunakan untuk melindungi kawasan yang menghasilkan
medan elektrik tinggi pada penebat kabel skrin. Sifat sesuatu bahan memainkan
peranan penting dalam menyekat medan elektrik merebak di seluruh kawasan
penamatan kabel. Berdasarkan titik pensuisan kira-kira 1kV/cm sifat bahan akan
berubah kepada pengaliran yang berlawanan dengan ketara. Dengan cara ini, ia
menghalang terhasilnya medan elektrik yang tidak diperlukan di atas titik pensuisan
ini. Ketebalan penebat yang berbeza juga telah diperkenalkan untuk mendapatkan
reka bentuk yang lebih baik dan ekonomi bagi menjimatkan sebarang kelebihan kos.
Kajian ini membuktikan keberkesanan untuk kedua-dua kaedah dalam mengawal
tekanan medan elektrik di skrin kabel penamatan telah berjaya.
vii
CONTENTS
TITLE i
DECLARATION ii
DECICATION iii
ACKNOWLEDGEMENT iv
ABSTRACT v
ABSTRAK vi
TABLE OF CONTENTS vii
LIST OF TABLES x
LIST OF FIGURES xi
LIST OF SYMBOLS AND ABBREVIATION xiv
1.0 CHAPTER 1: INTRODUCTION
1.1 Introduction 1
1.2 Effect of Termination on Power Cable Insulation 3
1.3 Problem Statement 3
1.4 Objectives 4
1.5 Scope Project 4
1.6 Project Outline 5
viii
2.0 CHAPTER 2: LITERATURE REVIEW
2.1 Introduction 6
2.2 Power Cable 7
2.2.1 Extruded Polymeric Cable 9
2.2.2 Impregnated –Type Cable 10
2.3 Cable Specification 11
2.4 Damage in High Voltage Cable 13
2.4.1 Ageing 13
2.4.2 Improper Termination Cable 14
2.4.3 Defect by Environmental Condition 15
2.5 Insulation 16
2.6 Electric Parameter 17
2.6.1 Electric Field 17
2.6.2 Electric Stress 18
2.7 Zinc Oxide Microvaristor 19
2.8 Corona Effect at Termination Layer 21
3.0 CHAPTER 3: METHODOLOGY
3.1 Introduction 23
3.2 Finite Element Method (FEM) 25
3.3 Simulation (COMSOL Multiphysics) Flow Chart 27
3.3.1 Geometric Cable Modelling 28
3.3.2 Geometric Parameters 28
3.3.3 Boundary Conditions 30
3.3.4 Generate Mesh 31
3.4 ZnO Microvaristor Modeling 32
ix
4.0 CHAPTER 4: SIMULATION RESULT, ANALYSIS AND
DISCUSSION
4.1 Introduction 33
4.2 The Cable Termination Model without Stress Control 34
4.2.1 Electric Field Distribution at Cable Screen Termination 36
4.3 The Cable Termination with Stress Control 37
4.4 Zinc Oxide Microvaristor Material Design 39
4.4.1 Zinc Oxide Microvaristor Design for Termination Cable 40
4.4.1.1 ZnO Microvaristor Design 1 40
4.4.1.2 ZnO Microvaristor Design 2 41
4.4.1.3 ZnO Microvaristor Design 3 42
4.4.1.4 ZnO Microvaristor Design 4 44
4.5 Comparison ZnO Microvaristor Design Layer 45
4.6 The thickness Effect of the ZnO Microvaristor Shape 46
4.7 Comparison Stress Control Geometry ans Zno Microvaristor
Design 48
4.8 Combination Stress Control Geometry and Zno Microvaristor
Design 49
4.9 Improvement Due to Grading Effect 50
5.0 CHAPTER 5: CONCLUSION AND RECOMMENDATIONS
5.1 Conclusion …………………...……………………………………..51
5.2 Future Work Recommendations ……..…………………...………...53
REFERENCES ………………………….………………………………………..54
x
LIST OF TABLES
Table 2.1 Cable Type Specification 11
Table 3.1 Material Parameters 30
Table 4.1 Tangential Electric Field with Different permittivity 39
Table 4.2 Electric Field in the Critical Area of the Cable Termination Model
with Stress Control for Different Thickness of ZnO Microvaristor
Layer 47
Table 4.3 Improvement Due to Grading Effect 50
xi
LIST OF FIGURES
Figure 1.1 HV power cable in an electricity power system transmission 1
Figure 2.1 Classification of Power Cable 8
Figure 2.2 Extruded Polymeric Cable 9
Figure 2.3 Impregnated-Type Cable 10
Figure 2.4 Cable containing many conductors 11
Figure 2.5 Defect of power cable because of Ageing 14
Figure 2.6 Improper Termination excite breakdown occur 15
Figure 2.7 Environmental Defect 15
Figure 2.8 Electric field represented as vectors 17
Figure 2.9 Field lines used to visualize the electric field 18
Figure 2.10 Characteristic for ZnO micrvaristor material 19
Figure 2.11 Equipotential lines at 5 % interval for dry clean insulator 20
Figure 2.12 Tangential Electric Field along Dry-Clean Insulator 21
Figure 2.13 Uncontrolled cable end – potential 21
Figure 2.14 Corona at outer insulation layer 22
Figure 3.1 Flow Chart Project 24
Figure 3.2 Dimension for 11kV medium cable termination 26
Figure 3.3 Flow chart cable modeling in COMSOL 27
Figure 3.4 Geometric Cable Modeling 28
Figure 3.5 Subdomain Material Setting 29
xii
Figure 3.6 Material for each layer cable model 29
Figure 3.7 Boundary conditions label 30
Figure 3.8 Meshing Model of the cable 31
Figure 3.9 Design of ZnO Microvaristor in insulator 32
Figure 4.1 Termination Electric potential surface 34
Figure 4.2 Cable Equipotential Lines 35
Figure 4.3 Electric Field Distribution at Cable Termination 36
Figure 4.4 Cable Termination Model with Stress Control for Different
Relative Permittivity 37
Figure 4.5 The Equipotential with Different Permittivity 38
Figure 4.6 Proposed Microvaristor characteristics with different switching
threshold at E0 (1) 0.5 kV/cm, (2) 1.0 kV/cm and (3) 5.0 kV/cm 39
Figure 4.7 ZnO Microvaristor Design 1 40
Figure 4.8 Tangential E-Field for Design 1 with Different ZnO Switching
Thresholds 41
Figure 4.9 ZnO Microvaristor Design 2 41
Figure 4.10 Tangential E-Field for Design 2 with Different ZnO Switching
Thresholds 42
Figure 4.11 ZnO Microvaristor Design 3 43
Figure 4.12 Tangential E-Field for Design 3 with Different ZnO Switching
Thresholds 43
Figure 4.13 ZnO Microvaristor Design 4 44
Figure 4.14 Tangential E-Field for Design 4 with Different ZnO Switching
Thresholds 45
Figure 4.15 Equipotential Line for Zno Microvaristor Designs 46
Figure 4.16 Tangential E-Field for Zno Microvaristor All Design 46
Figure 4.17 Tangential E-Field for various Thickness of Stress Control (ZnO
Microvaristor) 47
Figure 4.18 Comparison Electric Field Surface for Different Grading 48
xiii
Figure 4.19 Tangential E-Field Comparison for Two Method 49
Figure 4.20 Equipotential Line for Combination Stress Control Geometry
and ZnO Microvaristor Grading 49
Figure 4.21 Tangential E-Field Combination for Two Method 50
Figure 4.22 Comparison of Tangential Electric Field for all method 50
xiv
LIST OF SYMBOLS AND ABBREVIATION
HV - High Voltage
MV - Medium Voltage
LV - Low Voltage
ZnO - Znic Oxide
XLPE - Cross-Linked Polyethylene
FEM - Finite Element Method
2D - Two Dimension
IEC - International Electrical Commission
LDPE - Low Density Polyethylene
HDPE - High Density Polyethylene
PD - Partial Discharge
kV - kilo Volt
LSR - Linked Silicone Rubber
mm - Milimeter
m - Meter
SiR - Silicone Rubber
E - Electric Field
εr - Relative Permittivity
σ - Conductivity
1
CHAPTER 1
INTRODUCTION
1.1 Introduction
Power system is become vital nowadays. Purposes of the power system are to
provide energy or electrical power from source (power generation) to the consumers
in a safe and reliable way. Figure 1.1 shows the high voltage (HV) transmission is
one of the most important part of the system because it delivers almost all powers
that generated by power plants. Electric power can be transmitted by overhead power
lines or underground power cables. Underground cables are commonly used in low
voltage and medium voltage solutions.
Figure 1.1: HV power cable in an electricity power system transmission
2
Utilization power cable becomes extremely high due to usage of electric
power. A good characteristic of cable must be considered to ensure there are no
breakdowns occur during power transmission and distribution process. Distribution
of power has been a frequently improving branch ever since the invention of
electricity. High voltage is needed to get high efficiency in distribution of electricity
[1-2]. Higher voltages lead to a smaller current and therefore a smaller conductor
cross section to transfer a certain amount of power as well as can reduce the cost [2].
The development of cable accessories requires basic understanding of the
stress caused by the electric field in different parts of the insulating structures.
Material properties and product design play a key role in the durability of
terminations and joints. As the voltage goes high, even if the losses become
considerably less, the insulation failure becomes critical.
Dielectric plays important parts in electrical system to insulate the potential
charge materials with the earthed object (including human). Failure in dielectric can
cause electrical breakdown or short circuit in which may introduced the risk of
faulty/damage to the equipment as well as causing potential danger to human. In
general, dielectric can be formed of solid like glass, porcelain, or composite polymer
materials, gases such nitrogen and sulphur hexafluoride and liquid such mineral oils.
These dielectric materials mainly used power transformer of high voltage apparatus
such as cable, insulator and etc. [3].
Cable networks strongly depend on the performance of the way of attached
cable accessories. Therefore, to improve the behavior of the electric field in a
medium voltage termination and a joint, Zinc Oxide Microvaristor was introduced
for stress control on high voltage cable in this project. The optimization of these
issues was done using simulation software called COMSOL Multiphysics. Through
this, couple of simulations would be conducted on various designs of power cables as
well as type of material that have been chosen.
3
1.2 Effect of Termination on Power Cable Insulation
Power cables are very importance in power transmission and distribution
systems. Terminations are the basic accessories of the power cables. They are
required to make connections between lines or to an electrical apparatus. The various
aspects are considered while designing the stress control cable terminations because
they must have the same integrity as their associated cables while making the
connection both all indoor and outdoor applications. The parts of termination must
highly prevents with stress cone control because it will cause discharges and lead to
breakdown.
1.3 Problem Statement
Improper installation of HV cable system in the field can generate different
typical defects in cable accessories. It can be stress on the cable and can cause effect
electric field. The insulation of the cable must maintain due to the high-voltage
stress, ozone produced by electric discharges in air. The cable system must prevent
contact of the high-voltage conductor with other objects or persons. Cable
termination must be designed to control the high-voltage stress to prevent breakdown
of the insulation because this circumstances is easy to affect breakdown. If no stress
were applied, discharges could occur and the life termination would be limited
depending on the stress at the end of shield and the discharge resistance of the
primary dielectric [4].
However, the most common defects caused by bad workmanship are wrong
position of stress cone, and pollutants left in cable termination. Wrong position of
stress cone is usually resulted from not following installation instruction, and this can
result in stress cone does not contact well to outer-semiconductor layer, and leaving
void inside cable termination. Left pollutants are usually caused by casually attitude,
irregular edge of out-semiconductor and irregular surface of insulation. These
defects will enhance potential gradient and electric field that lead to breakdown or
partial discharge [5]. This problem can be addressed by designing stress cone shape
and using non-linear grading material such as ZnO Microvaristors.
4
1.4 Objective
The purpose of this project is to investigate the alternative approach to the
existing technique for optimizing field distribution on cable screen termination in
controlling high field stress that will affect the reliability of the power cable
especially at the termination or joint parts. The main objectives for this project are:
To investigate the problem of the environmental issues that related to the
solid insulation for medium cable.
To propose an optomize technique for controlling high electric field
region at cable screen termination.
To evaluate the performance of different material properties in controlling
the distribution of electric field in medium voltage cable terminations.
To examine the effectiveness of non-linear grading material in controlling
electric field stress at the cable termination.
1.5 Scope Project
This research focuses on single core high voltage power cable. High voltage
cables have various type of shielding [6-7]. For this project used cross-linked
polyethylene (XLPE) polymer was used as insulation in high voltage power cables
and ZnO microvaristor as stress control field material. For the whole project, largely
depends on the ageing of cable and search:
Finite Element method (FEM) has been used computational simulation
for analyze electrical field stress at screen cable termination.
This research deals with primary insulation cross-linked polyethylene
(XLPE) material and semi-conducting insulation.
Focused on 11kV potential for copper conductor and asymmetrical two-
dimensional (2D) mode.
In modeling geometric structure, this project assumes cable termination
profile in ideal condition without nearby structures.
5
1.6 Project Outline
This study is divided into five chapters. The introduction and the information
about the purposes of high voltage cable, problem that normally occur during
cable terminations and electric field controlling constitutes Chapter 1.
Chapter 2 outlines the review of power cable, power cable structure, and also
electric parameter. In Chapter 3, the simulation procedure computer analysis
is reviewed and Zinc Oxide Microvaristor modelling. The results and
evaluation of the simulation are explained in Chapter 4. The effect of
different electric field controlling methods include by applying non-linear
material are discussed in this chapter. Finally, in Chapter 5, conclusion of the
study and future work are covered.
6
CHAPTER 2
LITERATURE REVIEW
2.1 Introduction
This chapter describes the basic theories that have been used to analyze the
data obtained from the design process and simulation. Power cables are divided into
three groups which are low voltage, medium voltage and high voltage. Low voltage
cable solutions are rated from 300/500 V to 600/1000 V, medium voltage from 1.8/3
kV to 20.8/36 kV and cable solutions greater than 20.8/36 kV are called high voltage
[8]. Stress cone of cable can be categorized depending on company design to or
material used that covered the outer semi-conducting layers [9]. These circumstances
will give impact during termination or jointing cable. Improper circumstances intense
partial discharge issue and corona occur surrounding the cable. It is very dangerous
for human usage and failure transmit power in overhead line. It is also might cause
environmental defect, ageing and also electrical stress otherwise increase of cost.
According to the International Electrotechnical Commission (IEC) International
Standard 60270, Section 3.1 published in 2000, the definition of partial discharge is:
“Localized electrical discharge that only partially bridges the insulation between
conductors and which can or cannot occur adjacent to a conductor. Partial
discharge is in general a consequence of local electrical stress concentrations in the
7
insulation or on the surface of the insulation. Generally such discharge appears as
pulses having duration of much less than 1µs” [10-11].
PD in the insulation is the main cause of aging and failure in insulated cables
[3]. The discharges result in “electrical treeing” that leads to deterioration and
breakdown of the insulation and eventually to cable failure.
2.2 Power Cable
Power cable technology evolved since 1880s when the need for power
distribution cables became pressing. Cable is a conductor which is insulated
electrically and protected mechanically for the safe use of it. The main features found
on the cable construction are conductor, insulator and sheath which are protection for
human safety. Cable is the channel used for a system of transmission and distribution
of electrical energy. The residential and industrial loads today have a highest request
towards their growing density. This requires a tough construction, greater service
reliability, increased safety, and better appearance. These difficulties are easily
overcome by the used of underground cables and a trouble-free service is achieved
under a variety of environmental conditions [11].
There are two ways to transmit and distribute the electrical energy which is
by overhead line transmission or by using underground cable. Earlier underground
cables were mainly used in or near densely populated areas and were operated at low
or medium voltages only, but the present day requirements seek to use them even at
extra high voltages for longer distance [11]. Advantage of using overhead line
transmission, it support a high voltage with the longer distance. Increased working
voltages of the overhead lines require the cables to be insulated for such voltages in
order to meet the requirements of the overhead lines.
8
A power cable consists of the three main components, namely, conductor,
dielectric and sheath [11]. The conductor provides the conducting path for the
current. The insulation or dielectric withstands the service voltage, and isolates the
conductor with the object. The sheath does not allow the moisture to enter, and
protects the cable from all external influences like chemical or electrochemical
attack, fire, etc. Figure 2.1 illustrate classification of power cable which is consists of
insulation of cable, conductor commonly used and sheath for covered the outer semi-
conducting layers.
Figure 2.1: Classification of Power Cable
9
2.2.1 Extruded Polymeric Cables
The development of high voltage such as LDPE, HDPE or XLPE cable
systems goes back to the 1960‟s. Since technology have improved significantly,
providing reliable and maintenance-free products to the utility industry production
and material [12]. Cross-linked polyethylene (XLPE) is the one of the major types of
extruded dielectric insulation. XLPE has high insulation resistance and low dielectric
constant. XLPE has emerged as the generally preferred insulate and in the voltage
range 60-187 kV [13]. It has advantage of a higher permissible operating temperature
of 90º.Nevertheless, the first commercial length of 275 kV XLPE cable was installed
in Japan.
Modern XLPE cables consist of a solid cable core, a metallic sheath and a
non-metallic/polymer outer covering. The cable core consists of the conductor,
wrapped with semiconducting tapes, the inner semiconducting layer, the solid main
insulation and the outer semiconducting layer. These three insulation layers are
extruded in one process. The conductor of high voltage cables can be made of copper
or aluminum and is either round ended of single wires or additionally segmented in
order to reduce the current losses [12].
Figure 2.2: Extruded Polymeric Cable
10
2.2.2 Impregnated-Type Cable
This type of cable is divide into three which is mass-impregnated paper-
insulated cables (solid type), fluid-pressurized cable type, and gas-pressurized cable
type. All this type has own characteristic to transmit the electrical energy. Generally,
for the lapped cable type are conductors, conductor screen, cellulose paper
insulation, insulation screen, impregnating compound, metallic sheath to achieve a
water-impervious barrier [14]. The outer finish might be an extruded plastic jacket.
Impregnated paper became the most common form of insulation for cables
used for bulk transmission and distribution of electric power, particularly for
operating voltages of 12.5kV and above. Paper insulated cables were improved
considerably with introduction of the shielded design of multiple conductor cables by
Martin Hochstadter in 1914. From that, the cable is known as Type H [14-15]. The
cable consisted of two concentric conductors insulated with wide strips of paper
applied helically around the conductor and saturated with rosin-based oil as shown in
figure 2.3 below [16].
Figure 2.3: Impregnated-Type Cable
11
Figure 2.4 shows each is insulated from the others by silk and cotton thread.
Because the insulation in this type of cable is not subjected to high voltage, ,
meaning to say for low voltage the use of thin layers of silk and cotton is satisfactory
an contain many small conductors.
Figure 2.4: Cable containing many conductors
2.3 Cable Specification
Table 2.1 shows some sort of specifications or details for cable includes of
conductor, conductor shield, insulation, insulation shield, and etc. Designing
geometric of cable can be followed by this study of specifications
Table 2.1: Cable Type Specification [15]
Description 11kV
Conductor
Plain stranded annealed Copper wires c/w
longitudinal water blocking features. Copper to have
conductivity of 100%. Minimum cross-sectional area
300 mmsq.
Conductor shield
Shall consist of an extruded semi-conducting
thermosetting compound (non-metallic) applied over
the conductor.
Minimum thickness <0.8mm
DC volume resistivity <100000Ωcm
Maximum void size at the insulation interface
<0.005mm.
12
Insulation
High quality, dry-cured, heat, moisture, ozone and
corona-resistance, XLPE. Suitable for operation in
wet n dry locations.
Dielectric constant at 90º C < 2.5
Power factor of insulation at 90º C < 0.1%
Nominal thickness > 20mm
Minimum thickness > 18mm
Maximum void size <0.05mm
Maximum contaminant size <0.125mm
Insulation shield
Shall consist of a semi conducting XLPE compound
simultaneously extruded onto the insulation. It shall
be firmly bonded to the insulation.
Minimum thickness >1.0mm
DC volume resistivity < 50,000 Ω-cm at maximum
conductor temperature at normal operation.
Maximum void size at the insulation interface <
0.05mm
Maximum protrusion at the interfaces <0.125mm
Extrusion process
The conductor shield, insulation and insulation shield
shall be extruded by simultaneously triple extrusion
process.
Swelling tape
A semi-conducting non-woven or woven, non-
biodegradable (synthetic) swelling tape is to be
applied over and under the metallic screen for
continuous longitudinal watertight barrier throughout
the cable length.
Metallic screen
Metallic screen shall be in the form of concentric
round wire shield consisting uncoated copper wires
helically applied over the swelling tape.
It shall be sized to carry the rated fault current.
13
Radial water
barrier
A radial water barrier consisting of laminated
aluminum tape (PE/AL/PE) is to be incorporated
under the PE over sheath.
Outer protective
covering
The oversheath shall be extruded black PE (ST7)
supplied over the laminated aluminum tape.
The oversheath shall be treated with non-hazardous
and effective termite repellent.
Nominal thickness <4.0 mm
Smallest thickness at any point >85% of nominal
thickness.
Each last section of cable terminating into GIS
switchgear, transformer or any other cable box inside
or outside a substation building and where the cables
are installed on the bridge, the cable shall have a fire-
retardant serving complying to IEC 60332 part 3.
Over conducting
layer
The outer surface of the oversheath shall have a baked
on graphite conducting layer to serve as an electrode
for the voltage test on the oversheath.
2.4 Damage in High Voltage Cable
2.4.1 Ageing
The occurrence of discharges within insulation cavities and the generation of
an electrical tree that highest in cable breakdown is the one off aging process in
polymeric insulated power cables [17]. It is assumed that at the electrical field
exceeding a threshold value, the space charge formed by the PD progresses within
the insulation via channel emanating from the cavity. Penetration depth x is
determined by the electrical field at the tip of the channel. This process is argued to
produce the well-known tree-like structure.
14
Figure 2.5 illustrate defect of power cable because of ageing problem upon
frequently electric discharge occur surrounding insulation layer.
2.4.2 Improper termination Cable
The purpose of a cable termination is to connect an insulated cable to a
circuit. The termination also protects the cable mechanically, keeps moisture out
form the cable and helps to keep the oil inside an oil impregnated paper cable. The
structure of a cable termination depends on cable type, used voltage and installation
environment. For example terminations used outside must be mechanically strong
and completely waterproof. If termination process done without follows the rule will
give dangerous impact to customer and damage the HV equipment and in the while
increase the cost for maintenance fee [18].
The cable termination must withstand the same electric stress that the cable
does. It is important to note that the electric field rises remarkably at the end of the
screening and some sort of grading is required. There are different techniques for
implementing the grading. Geometric grading can be implemented by adding a cone-
shaped (stress cone) insulation on top of the cable insulation and the end of the
screening. Another solution is to add a shaped layer of insulation with a different
permittivity than the surrounding insulation on top of the cutting point of the
screening [18].
Figure 2.5: Defect of power cable because of Ageing
15
Figure 2.6 shows breakthrough could also be an effect of quality issues in the
stress control mass or even in the cable insulation. Wrong electric properties in the
mass could lead to a much higher electric field at the cutting point of the screening.
Improper structure of the mass could also lead to a breakthrough if air bubbles were
left inside the termination. Partial discharges generated inside the air bubbles would
start to slowly burn the insulation and could lead to failure.
2.4.3 Defect by Environmental Condition
Defect accidently cause by the oxidation process. When the cable is exposed to
moisture and oxygen, it will result in rust. This case may lead the cable cannot work
properly, such as shown in figure 2.7 below:
(a) (b)
Figure 2.6: Improper Termination excite breakdown occur
Figure 2.7: Environmental Defect
16
2.5 Insulation
The vast majority of conventional power cables are insulated with either solid
extruded dielectrics or liquid-impregnated papers. The use of the former now
generally dominates the distribution power cable field, whereas the latter is still
extensively used in high-voltage power transmission cable. Although the solid
extruded insulating materials have undergone marked changes with time, the changes
in the liquid-impregnated papers have been substantially not too vital [19]. Insulating
materials are used in electric devices to keep current from flowing where it is not
desired. Generally, the thicker the insulator, the higher the voltage can sustain. In
recent years natural rubber has been completely replaced by synthetic rubbers and
plastics as cable insulation [20].
Many types of XLPE cables of the first generations are suffering from a
degradation problem known as water treeing. This will gradually decrease the
voltage withstand of the cable and eventually a breakdown will occur. The dielectric
compounds as insulates for power cable should possess the several main properties,
for instant:
High insulation resistance
High dielectric strength
Good mechanical properties
Preferably non-hygroscopic, but if hygroscopic it should be provided with an
economical water-tight covering or sheath.
Capable of being operated at high temperatures
Low thermal resistance
Low power factor.
17
2.6 Electric Parameter
The type of cable to be used will depend upon the working voltage and
service requirements. In general, a cable must fulfill the some necessary requirement
such as electric field, electric stress and capacitance of the cable.
2.6.1 Electric Field
The electric field is defined as the force per unit charge that would be
experienced by a point charge at a given point.
(2.1)
Vectors represented as an electric field which continuous entity. Vectors are
drawn as extended arrows which represent the field at the end of the vector. When
using vectors to represent the field it's good to note that we can't draw them all
because the field still exists at every point in space even if we cannot draw a vector
everywhere as shown in figure 2.8 below.
Figure 2.8: Electric field represented as vectors
18
Figure 2.9 (a) and (b) shows more practical way to visualize electric fields
than using vectors is to use electric field lines. Field lines are continuous lines whose
direction is everywhere the same as that of the electric field. Field lines start at
positive charges or at a negative charge or extend to infinity.
Based on Coulomb's law we can conclude that the field is stronger where the lines
are closer to the charge and weaker when they are farther apart. This allows us to
study the field's relative magnitude and direction from field line pictures [21].
2.6.2 Electric Stress
Normally, cable modeled as a coaxial cylinder system. The electric stress at any point in the
insulation material is given by equation [22].
(2.2)
U = Applied voltage
ri= Conductor radius
ro= Sheath radius
x = radial distance to any point in the insulation.
From equation 2.2, it can be seen that the bigger value of sheath radius, the bigger
value will electric stress produce. This will related to the equation below.
Figure 2.9: Field lines used to visualize the electric field
19
(2.3)
It occurs on the surface of the conductor which is the most probable location
for instantaneous failure. This is more likely to occur if serious insulation defects are
near the conductor surface [22].
(2.4)
The minimum stress occurs at the outer sheath and it becomes a critical factor
if insulation defects are in the vicinity of the outer sheath. The mean stress (i.e. E
min) across the insulation is critical if insulation defects are uniformly located
throughout the bulk of the material.
2.7 Zinc Oxide Microvaristor Material
This material is the crucial material in this project as a material to
control stress in cable accessories. ZnO microvaristor can be found inside
heat-curing silicone (HTV) or liquid addition-cross linked silicone rubber
(LSR). Those polymeric material matrices have an elastic property. The
elasticity is necessary to make easier in assemble cable accessories. Figure
2.10 shows the field conductivity of the ZnO microvaristor material. When
switching point reached at 10kV/cm, the material changes its conductivity
extremely. In this way it prevents the occurrence of electric fields which are
above this switching point.
20
Figure 2.10: Characteristic for ZnO micrvaristor material
This material has been demonstrated by previous researcher. Zinc Oxide
Microvaristor were proposed as grading material along the insulator. The electrical
properties of the microvaristor compounds are characterised by a nonlinear field
dependent conductivity. Figure 2.11 illustrate the proposed design, a short length of
ZnO microvaristor compound layer is applied on th core of the insulator near the
insulator HV and ground terminals. Figure 2.11 (a) shows equipotential line without
non-linear grading and figure 2.11 (b) shows non-linear grading were applied.
Results shows after apllied microvaristor grading material between copper and
silicone insulation where 70% interval line refract away from the concerntrated point
[23].
(a) (b)
Figure 2.11: Equipotential lines at 5 % interval for dry clean insulator.
Figures 2.12 show the corresponding electric field profiles along the leakage
path for the clean and polluted graded insulators. As can be clearly observed, the
field distributions on the insulator equipped with grading material under both surface
conditions are improved. Peak magnitudes in the high field regions, particularly at
the HVend are reduced by nearly 30%.
21
Figure 2.12: Tangential Electric Field along Dry-Clean Insulator
2.8 Corona effect at Termination Layer
Regarding previous study, focused on underground cable accessories used in
medium voltage cable. Systems need a highly reliable stress control system in order
to maintain and control the insulation level which is designed for estimated life
times. Figure 2.13 shows the stress concentration at the end of the screen of medium
voltage cables when no stress control system is used.
Figure2.13: Uncontrolled cable end – potential
22
The term „electrical stress control‟ refers to the cable termination function of
reducing the electrical stress in the area of insulation shield cutback to levels that
preclude electrical breakdown in the cable insulation. Figure 2.14 shows breakdown
occur at the edge of outer insulation layer when termination has been done. This
paper focus on metal Oxide-Matrix stress control system to reduce field stress which
has never been attempted before [6].
Figure 2.14: Corona at outer insulation layer
23
CHAPTER 3
METHODOLOGY
3.1 Introduction
To ensure this project will be succeeding, several characteristic of cable will
be study to familiar with cable issues. This study investigates and evaluates different
types of cable termination models by the finite element analysis (FEM) computer
program. The basic steps in simulation procedure steps are explained in this chapter.
The project must consider the cable material and FEM simulation. To achieve the
outcome, some procedure must be followed. First step is to study about power cable
and its properties. After that, electrical parameter of insulating and conductor also
must be studied. There are several ways in gathering the information such as using
references from the books and the most important references are referred to related
journal, previous study, proceedings paper and conference papers.
The simulations with FEM software computer program are demonstrated in three
basic steps which is preprocessing, solution procedure and postprocessing. Which
mean, the preprocessing step involves the model properties (geometrical,electrical)
input and meshing. In the solution procedure, the boundary each geometric
conditions are applied and the program solves the potential values of the model. The
graph plotting and reading of the output is done in the postprocessor step to evaluate
the results.
24
The choice of the appropriate parameters is very important to verify the accuracy of
the output in the analysis. Otherwise, incorrect results and even errors are obtained in
the end of the analysis.
Figure 3.1 shows the flow chart for the whole process for this project of investigation
Zinc Oxide Microvaristor for Stress Control on Medium Voltage Cable
Terminations.
Figure 3.1: Flow Chart Project
Start
Find information regarding of the Power Cable
Cable Conductor Insulator Zno Microvaristor Charateristic
Single phase Three phase
Overhead transmission line & underground
Copper AluminiumLaminated / Lapped
(paper)Non-Linear
gradingExtruded(polymer)
Literature review
Simulation Softwarre (Comsol Multyphysics4.2)
Design Geometric
Analyze of Data
Final Report
Plot graph
Drawing design
Obtain electric field, conductivity, resistivity
Import into Microsoft excell
55
REFERENCES
[1] Cecilia Forss´en, “Power Cable Electro technical Design”, KTH Electrical
Engineering, December 2007.
[2] E. Peschke, R. Von Olshausen, “Cable Systems for High and Extra-High
Voltage”, Publicis MCD Verlag, Erlangen and Munich, 1999, ISBN 3-89578-
118-5
[3] Jasmine James, S.V.Kulkarni, B.R.Parekh , “Partial discharge in High
Voltage Equipments-HV Cable”, Proceeding of IEEE 9th
International
Conference On Properties And Application of Dielectric Materials, pp. 445-
447, July 2009
[4] Blake A.E, ClarkemG., Star W.T: “Improvements in stress control Material”,
7th
IEEE Conference and Exposition on Transmission and Distribution, April
1-6, 1979 Atlanta, Georgia
[5] Chang-Hsing Lee, Yu-Chih, Lin, Min-Yen Chiu, Chih-Hsien Huang, Shih-
Shong Yen, Chiang, Haeng, “Recognition of partial discharge defects in
cable terminations”, Proceeding of IEEE International Conference on
Condition Monitoring and Diagnosis, pp.1-4, April 2008.
[6] R. Strobl, W. Haverkamp, G. Malin, F. Fitzgerald, “Evolution of stress
control systems in medium voltage cable accessories,” Transmission and
Distribution Conference and Exposition, 2001 IEEE/PES, pp.843-848 vol.2,
2001.
[7] B. Boettcher, G. Malin, R. Strobl “Stress control system for composite
insulators based on ZnO technology”, Transmission and Distribution
Conference and Exposition, 28 Oct.-2 Nov. 2001, IEEE/PES 2001
56
[8] Aarnio, Anssi. “Characterization of non-metallic materials for medium
voltage cable accessories”, Master's thesis, Tampere: University of
Technology, Material Science. 2010
[9] Chengwei Chen, Gang Liu, Guojun Lu, Jin Wang “Influence of Cable
Terminal Stress Cone install incorrectly”, Proceedings of the 9th
International Conference on Properties and Applications of Dielectric
Materials, , IEEE , July 19-23, 2009
[10] Eberhard Lemke, Sonja Berlijn, Edward Gulski, Micheal Muhr, Edwin
Pultrum, Thomas Strehl, Wolfgang Hauschild, Johannes Richmann, Guiseppe
Rizzi. “Guide for Electrical Partial Discharge Measurement in compliance to
IEC 60270”, Technical Brochure (Electra), no.241, pp.61-67, December 2008
[11] Ashfaq Husain, 1982, Electrical Power Systems. 3rd
ed.Vani Educational
books, New Delhi
[12] “High Voltage Cable System”, Technical User Guide. Brugg Cable AG 2005.
[13] Modern Power Station Practice: EHV Transmission,volume K. 3rd
ed.
Pergamon Press, London
[14] Oswald I. Gilbertson, “Electrical Cables for Power and Signal transmission”,
Wiley Inter-science, Canada, ISBN 0-471-35996-3, 2000
[15] “Medium and High Voltage Power Cable”, 2008, iknowledge, Shah Alam.
[16] William A. Thue, “Electric Cable Engineering”. 2nd
ed. Marcel Dekker Inc.
New York. 2003
[17] Montari,G.C. “Aging and Life Models for Insulation System Based on PD
Detection”, IEEE Trans, vol.2 , no.4, pp. 667, 1995
[18] Hirvonen, Markus. “Effect of assembly error on partial discharge levels in
medium voltage terminations”, Engineering thesis, Helsinki: Stadia, Power
Systems, 2008
[19] R.Bartnikas, K.D.Srivastava, “Power and Communication cables”, John
Wiley and Sons,Inc New Jersy, ISBN 0-7803-1196-5, 2000
[20] Alexandra von Meier, Electric Power Systems: A conceptual introduction,
Wiley Inter-science, Canada, ISBN 0-471-17859-4, 2006
[21] Matthew N. O. Sadiku, “Elements of Electromagnetic”, Oxford University
Press, Incorporated, 2007
[22] Ashfaq Husain, “Electrical Power Systems”, 3rd
ed.Vani Educational books,
New Delhi, 1982
57
[23] R. Abd-Rahman, A. Haddad, N. Harid and H. Griffiths, Stress Control on
“Polymeric Outdoor Insulators Using Zinc Oxide Microvaristor
Composites”, IEEE Transactions on Dielectrics and Electrical Insulatio,Vol.
19, pp.705-713, 2012
[24] Daniel Weida, Christian Richter, Markus Clemens, “Design of Cable
Accessories Using ZnO Microvaristor Material Based on FEM Simulations”,
pp:94-97, IEEE, 2010
[25] COMSOL Multiphysics. [Retrieved 25.2.2013] Available at:
http://www.comsol.fi/products/multiphysics
[26] H. A. Illias, Q. L. Ng, A. H. A. Bakar, H. Mokhlis, “Electric field distribution
in 132 kV XLPE cable termination model from finite element method”, IEEE
International Conference on Condition Monitoring and Diagnosis, A12, 2012
[27] XLPE Insulated Cable, BS 5467 IEC 60502-1, Tenaga Cable Industries
Sdn.Bhd.
[28] F. Greuter, M. Siegrist, P. Kluge-Weiss, R. Kessler, L. Donzel, R. Loitzl and
H. J. Gramespacher, "Microvaristors: Functional fillers for novel
electroceramic composites", J. Electroceramics, Vol. 13, pp. 739-744, 2004.
[29] P. Kluge-weiss, F. Greuter, and R. Strümpler, "Non-linear resistance with
varistor behavior and method for the production thereof", United States
Patent 6469611, 2002
[30] H. Illias, G. Chen and P. L. Lewin, “Modelling of partial discharge activity
in spherical cavities within a dielectric material,” IEEE Electrical Insulation
Magazine, 27, pp. 38-45, 2011
[31] D. Weida, S. Bohmelt, and M. Clemens, "Design of ZnO microvaristor end
corona protection for electrical machines", IEEE International. Symposium
on Electrical Insulation (ISEI), pp. 1-4, San Diego (USA), 2010.