iO-FAV-08 FRESH AIR VENTILATION INSTALLATION INSTRUCTIONS (FOR USE WITH 6” OR 8” DAMPER) INTRODUCTION The iO HVAC Controls Fresh Air Ventilation system is designed to improve residential indoor air quality. This is accomplished by introducing fresh, outside air through an intake damper controlled by a logic panel. The panel controls the amount of fresh air required each hour based on the ASHRAE 62.2 - 2013 Ventilation and Indoor Air Quality Standard. INSTALLATION OF INTAKE HOOD, FRESH AIR INTAKE DUCT AND MOTORIZED DAMPER It is recommended that the intake hood be an open metal type with a screen. The fresh air intake should be located away from dryer or furnace vents, driveways, trash containers, swimming pools and at a level above any expected snow accumulation. Check all local codes that might apply. Depending on the CFM requirement, an insulated, 6” or 8” diameter, rigid fresh air intake duct is recommended with a 6” or 8” diameter, 2-wire, motorized fresh air damper. The damper actuator should be power open / spring return closed. Furnace RETURN AIR PLENUM SUPPLY PLENUM MOTORIZED FRESH AIR DAMPER INSULATED FRESH AIR DUCT FRESH AIR INTAKE HOOD VENTILATION CONTROL PANEL TYPICAL BASEMENT INSTALLATION EXTERIOR WALL HVAC Controls HVAC Controls

Upload: others

Post on 27-Aug-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: iO-FAV-08 FRESH AIR VENTILATION - Jackson Systems · 2020. 4. 22. · iO-FAV-08 FRESH AIR VENTILATION INSTALLATION INSTRUCTIONS (FOR USE WITH 6” OR 8” DAMPER) INTRODUCTION The

iO-FAV-08 FRESH AIR VENTILATIONINSTALLATION INSTRUCTIONS(FOR USE WITH 6” OR 8” DAMPER)

INTRODUCTIONThe iO HVAC Controls Fresh Air Ventilation system is designed to improve residential indoor air quality. This is accomplished by introducing fresh, outside air through an intake damper controlled by a logic panel. The panel controls the amount of fresh air required each hour based on the ASHRAE 62.2 - 2013 Ventilation and Indoor Air Quality Standard.

INSTALLATION OF INTAKE HOOD, FRESH AIR INTAKE DUCT AND MOTORIZED DAMPERIt is recommended that the intake hood be an open metal type with a screen. The fresh air intake should be located away from dryer or furnace vents, driveways, trash containers, swimming pools and at a level above any expected snow accumulation. Check all local codes that might apply. Depending on the CFM requirement, an insulated, 6” or 8” diameter, rigid fresh air intake duct is recommended with a 6” or 8” diameter,2-wire, motorized fresh air damper. The damper actuator should be power open /spring return closed.

Furnace

RETURNAIR

PLENUM

SUPPLYPLENUM

MOTORIZEDFRESH AIRDAMPER

INSULATEDFRESH AIR

DUCTFRESH AIR

INTAKEHOOD

VENTILATIONCONTROL

PANEL

TYPICAL BASEMENT INSTALLATION

EXTERIORWALL

HVAC Controls

HVAC Controls

Page 2: iO-FAV-08 FRESH AIR VENTILATION - Jackson Systems · 2020. 4. 22. · iO-FAV-08 FRESH AIR VENTILATION INSTALLATION INSTRUCTIONS (FOR USE WITH 6” OR 8” DAMPER) INTRODUCTION The

PANEL INSTALLATION

To install the panel, remove the cover and slide the PC board out of its base. Screw the base to a flat surface in a location that allows easy access for wiring. Re-install the PC board by carefully centering it over the base and snapping it into the track grooves.

The panel receives its power from the equipment transformer. A separate 24VAC, 20VA transformer is required to power the fresh air damper. Only standard 18-gauge thermostat wire is required.

WARNING!Improper wiring to the HVAC unit can cause damage to the equipment and/or the panel. Disconnect electrical power before wiring the panel to the equipment.

PANEL OVERVIEW

LED1 LED2 LED3 LED4 LED5

PANELPOWER

DAMPERTRAMS.

FANON

DAMPEROPEN

EXHAUSTFAN

0

10

2030

40

50

60 MIN

DAMPER OPENMINUTES PER HOUR

CL

OS

ED

AU

TO

DAMPER

EFEFOOLL

JP1

WG1G2

RC

24V24V

DD

Heating Call Input Signal

Fan Output to HVAC System

Fan Input from Thermostat

HVAC System Hot

HVAC System Common

24VAC to Damper

24VAC to Damper

24VAC In

24VAC In

Page 3: iO-FAV-08 FRESH AIR VENTILATION - Jackson Systems · 2020. 4. 22. · iO-FAV-08 FRESH AIR VENTILATION INSTALLATION INSTRUCTIONS (FOR USE WITH 6” OR 8” DAMPER) INTRODUCTION The

TYPICAL THERMOSTAT WIRING DIAGRAMS

24VLINE

C R W Y G

C R W Y G

HVAC UNIT

THERMOSTAT

VCSTRANSFORMER

WIRETO

DAMPER

SINGLE STAGE HEAT/COOL

C R W1 W2 Y1 Y2 G

HVAC UNIT

THERMOSTAT

C R W1 W2 Y1 Y2 G

C R W1 O/B Y1 Y2 G

INDOOR UNIT

THERMOSTAT

C R W1 O/B Y1 Y2 G

MULTI- STAGE HEAT/COOL

HEAT PUMP

NOTE: ‘Y1’ FROM HEAT PUMP

WIRES TO ‘W’ON VCS

LED1 LED2 LED3 LED4 LED5

PANELPOWER

DAMPERTRAMS.

FANON

DAMPEROPEN

EXHAUSTFAN

0

10

2030

40

50

60 MIN

DAMPER OPENMINUTES PER HOUR

CL

OS

ED

AU

TO

DAMPER

EFEFOOLL

JP1

WG1G2

RC

24V24V

DD

LED1 LED2 LED3 LED4 LED5

PANELPOWER

DAMPERTRAMS.

FANON

DAMPEROPEN

EXHAUSTFAN

0

10

2030

40

50

60 MIN

DAMPER OPENMINUTES PER HOUR

CL

OS

ED

AU

TO

DAMPER

EFEFOOLL

JP1

WG1G2

RC

24V24V

DD

LED1 LED2 LED3 LED4 LED5

PANELPOWER

DAMPERTRAMS.

FANON

DAMPEROPEN

EXHAUSTFAN

0

10

2030

40

50

60 MIN

DAMPER OPENMINUTES PER HOUR

CL

OS

ED

AU

TO

DAMPER

EFEFOOLL

JP1

WG1G2

RC

24V24V

DD

24VLINE

VCSTRANSFORMER

WIRETO

DAMPER

24VLINE

VCSTRANSFORMER

WIRETO

DAMPER

Page 4: iO-FAV-08 FRESH AIR VENTILATION - Jackson Systems · 2020. 4. 22. · iO-FAV-08 FRESH AIR VENTILATION INSTALLATION INSTRUCTIONS (FOR USE WITH 6” OR 8” DAMPER) INTRODUCTION The

WIRING TO OPTIONAL EXHAUST FAN

The panel can be wired to an optional exhaust fan using the ‘EF’ terminals located on the panel. Wire the ‘EF’ terminals in series with the exhaust fan relay. When the panel is in the AUTO mode, the ‘EF’ contacts close when the fresh air damper is opened.

EF

EF

O

O

L

L

24V LINE

L1

L2

FAN RELAY

EXHAUST FAN

WIRING TO OPTIONAL DAMPER OVERRIDE SWITCH

The panel can be wired to an optional damper override switch or timer using the ’O’ terminals located on the panel. A dry contact closure across the ‘O’ terminals will open the fresh air damper and bring on the system fan. When the panel is in the damper override mode, ventilation timing and all other override inputs are ignored.

WIRING TO OPTIONAL OUTDOOR THERMOSTAT AND/OR HUMIDISTAT

The panel can be wired to an optional outdoor thermostat and/or humidistat using the ‘L’ terminals to prevent the fresh air damper from opening based on a temperature and/or humidity setting. The jumper located to the left of the ‘L’ terminals must be removed and the outdoor thermostat and/or humidistat wired so that the contacts are closed during normal operation.

For outdoor thermostat installation:To lockout on high temperature, connect the Blue and Red wires to the “L” terminals. (Black is not used.) To lockout on low temperature, connect the Red and Black wires to the “L” terminals. (Blue is not used)

EF

EF

O

O

L

L

OVERRIDE SWITCHOR TIMER

N.O.

EF

EF

O

O

L

L

OUTDOOR THERMOSTAT

N.C.

REMOVEJUMPER

N.C.

HUMIDISTAT

Page 5: iO-FAV-08 FRESH AIR VENTILATION - Jackson Systems · 2020. 4. 22. · iO-FAV-08 FRESH AIR VENTILATION INSTALLATION INSTRUCTIONS (FOR USE WITH 6” OR 8” DAMPER) INTRODUCTION The

iO-06-1213-020118

FORMULA FOR SETTING THE VENTILATION TIMER

The FAV Ventilation Control System is designed to simplify selecting the minimum ventilation cycle rate to meet ASHRAE 62.2 - 2013 Standard by using a single dial to set the desired number of minutes per hour that ventilation will take place. The timer cycle rate is calculated as follows:

(Home Area in Sq. Ft. x 0.03) + ((Number of Bedrooms + 1) x 7.5) = Required Airflow in CFM(Required Airflow in CFM x 60 ÷ Total Airflow of Fresh Air Duct) x 60 = Ventilation Minutes Per Hour

Example: Home Area = 2,500 Sq. Ft. with 4 bedrooms. (2,500 x 0.03 = 75) + ((4 + 1) x 7.5 = 37.50) = 112.50 CFM

Total airflow of 8” rigid fresh air duct @ 0.1” w.c. = 220 CFM x 60 = 13,200 Cubic Feet Per Hour

(112.50 CFM x 60 Minutes = 6,750) 6,600 ÷ 13,200 x 60 = 30.68 Ventilation Minutes Per Hour

The ventilation timer would be set for 31 Minutes

VENTILATION TIMER QUICK REFERENCE CHART

The reference chart below is designed to provide FAV ventilation timer settings based on using 8” rigid straight duct with friction loss of 0.1” w.g. per 100 ft. This chart can be used for most applications.

<500

501-1000

1001-1500

1501-2000

2001-2500

2501-3000

3001-3500

3501-4000

4001-4500

4501-5000

HO

ME

SIZ

E (

Ft²

)

NUMBER OF BEDROOMS ONE TWO THREE FOUR FIVE

VENTILATION TIMER SETTING (MINUTES PER HOUR)

8 10 12 15 16

12 15 16 19 21

16 19 21 23 25

21 23 25 27 29

25 27 29 31 33

29 31 33 35 37

33 35 37 39 41

37 39 41 43 45

41 43 45 47 49

45 47 49 51 53