    RT-SVP04F-EN 2010 Trane All rights reserved

    General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Commonly Used Acronyms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4UCM Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)10Unit Operation Keys. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Password Protected Screens. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    System Operating Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    STATUS Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    System Programming SETUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    SETUP Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Ventilation Override Definitions (with VOM installed). . . . . . . . . . . . . . . . . . 66

    Temperature Input Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

    System Programming SETPOINTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

    SETPOINT Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

    System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101CONFIGURATION Menu. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

    System Testing & Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

    SERVICE MODE Menu (Local Human Interface only) . . . . . . . . . . . . . . . . . . . 108

    DIAGNOSTICS Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    Failure Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

    Communication Link Problems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

    Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

    Contents

  • 8/14/2019 ipak trblshoot

    3/150

    RT-SVP04F-EN 3

    Commonly Used Acronyms

    For convenience, a number of acronyms and abbreviations are used throughout this

    manual. These acronyms are alphabetically listed and defined below.

    General Information

    Table 1. Acronyms

    Act = active HGBP = Hot Gas Bypass

    AH = Air Handler HGP = Hot Gas Bypass

    Annunc = Annunciator Hi = high

    AS = AirSide HI = where all caps Human Interface

    Aux = auxiliary HO = History Only (Diagnostic)

    BAS = building automation systems HVAC = heating, ventilation and air conditioningBCI = BACnetCommunication Interface ICS = Integrated Comfort System

    CCFM = hundreds of cubic-feet-per-minute IGV = inlet guide vanes

    CCW = counterclockwise INFO = Information Only (Diagnostic)

    cfm = cubic-feet-per-minute I/O = input/output

    Cfg = Configured, configuration Indep = Independent

    ckt = circuit IOM = installation/operation/ maintenance manual

    Cmd = command IPC = interprocessor communications

    Comp (s) = compressor, compressors IPCB = interprocessor communications bridge (module)

    Cond = condenser, condensers IWC = inches water column

    Config = configured, configuration LH = left-hand

    Ctrl = control Lo = lowCV = constant volume LCI = LonTalkCommunication Interface

    Cy = cycle LCI-I = LonTalk Communication Interface for IntelliPak

    Module

    CVDA = Constant Speed Fan (CV)/Discharge Air Temp ControlManif = manifolded

    CVZT = Constant Speed Fan (CV)/Zone Temperature Control Max = maximum

    CW = clockwise Min = minimum

    DCV = Demand Control Ventilation Misc = miscellaneous

    Dflt = default MCM = Multiple Compressor Module

    Diag = diagnostic MDM = Modulating Dehumidification Module

    Dmpr = damper Mod = modulating

    DWU = Daytime Warm-up MPM = Multi-Purpose ModuleE/A = exhaust air MWU = morning warm-up

    ECEM = exhaust control/enthalpy module NSB = night setback panel

    Econ = economizer, economizing Num = number

    Ent = entering O/A = outside air

    Evap = evaporator Occ = occupied

    F/A = fresh air OVRD = override

    Funct = function PAR = Partial System Disable, Auto Reset (Diagnostic)

    GBAS = generic building automation system (module) PMR = Partial System Disable, Manual Reset (Diagnostic)

    Pos = position

  • 8/14/2019 ipak trblshoot

    4/150

  • 8/14/2019 ipak trblshoot

    5/150

    RT-SVP04F-EN 5

    General Information

    Comparative Enthalpy. An economizer control strategy which compares return air

    enthalpy with outdoor enthalpy. The air with the least heat content (enthalpy) is used

    for cooling.

    Compressor Protection Switch. A pressure switch installed on the suction line that

    prevents compressor operation below the switchs SETPOINT. The purpose is to prevent

    no-flow scroll compressor operation.

    Comm3/4. Trane proprietary network communication protocol.

    Comm5. Trane's implementation of LonTalk or BACnet (an open network

    communication protocol).

    Condenser Pressure. The saturated condenser pressure measured on each circuit's(2)

    condenser section on Evaporative Condenser units. Condenser pressure is converted

    to Saturated Condenser Temperature for display on the Human Interface. The data

    from these sensors is used in head pressure control.

    Control Band. The range of temperatures or pressures which would normally be

    maintained by the various control functions.

    Control Point. The value of a SETPOINT that an algorithm is using at any given time.

    Deadband. As applied to SA temp control, this refers to a range of temperatures

    equally spaced above and below the SA temp control point in which the control

    algorithm is satisfied.

    Dehumidification Override High Zone Temp. The temperature in the critical zone on

    VAV units where Dehumidification is disabled to prevent over-heating the space due toexcess reheat.

    Dehumidification Override Low Zone Temp. The temperature in the critical zone on

    VAV units where Dehumidification is disabled to prevent sub-cooling the space due to

    insufficient reheat.

    Demand Control Ventilation (DCV). An ASHRAE compliant ventilation scheme that

    varies the Outside Air Damper minimum position or Fresh Air Flow (TRAQs) between

    minimum and maximum ventilation SETPOINTs based on CO2level.

    Dry Bulb. An outdoor temperature above which economizing will be disabled (unless

    comparative enthalpy is the economizer control type being used.)

    Economizer Zone Temp SETPOINT Suppression. a parameter used for setting the Zone

    Temp SETPOINT at a lower value than the mechanical cooling zone temp SETPOINT.

    Emergency Stop. A binary input on the RTM which allows unit shutdown with manual

    reset when connected to a field-supplied switch.

    Energy Recovery Wheel. A device incorporating a specially coated rotating disc that

    spins across both outdoor and exhaust air streams transferring to or removing energy

    from the incoming outdoor air prior to mixing with return air to increase unit efficiency.

  • 8/14/2019 ipak trblshoot

    6/150

    6 RT-SVP04F-EN

    General Information

    Evap Diff. Evap Diff is a calculated value indicating performance of a refrigeration

    system. It is calculated by determining the difference between the Entering and Leaving

    temperatures of the evaporator. If this value rises too high it may indicate a problem

    with the system.

    External Stop. A binary input on the RTM that allows unit shutdown, with automatic

    reset, when connected to a field-supplied switch.

    Hot Gas Bypass. A feature to reduce a refrigeration circuit's cooling capacity by

    bypassing hot discharge line refrigerant directly to the evaporator coil of the system to

    more effectively operate in low load conditions.

    Humidification Control. During modes of continuous fan operation a relay is energized

    when the Humidity measured in the controlled space drops below an adjustable

    Humidification SETPOINT. The humidifier device is a user supplied device placed in the

    supply air stream.

    LonTalk. An open, device networking communications protocol for controls. This

    protocol is defined in ANSI approved standard EIA/CEA-709.1-A-1999.

    Low Ambient Compressor Lockout. A function which prevents compressor operation

    at low outdoor ambient temperatures.

    Night SetBack (NSB). Applies to the control of the rooftop unit during unoccupied

    periods. Also refers to the NSB panel, a communicating wall sensor with night setback

    capability.

    Reference Enthalpy. An outdoor enthalpy value above which economizing will be

    disabled.

    Remote Human Interface. A human interface module designed to be mounted

    remotely from the unit. There are some functional differences between a unit mounted

    and a remote mounted human interface module.

    Reset Amount Maximum. The maximum amount of reset allowed.

    Reset End Temperature. The temperature at which the maximum reset amount will

    occur.

    Reset Start Temperature. The temperature at which reset will begin.

    Return Fan Control. Return Fan Control is a feature which allows units to operate at a

    higher external or duct system static pressure, or to reduce the load (horsepower

    requirement) on the supply fan motor. The fan is placed in the return air path.

    Return Fan Plenum Pressure. The area between the Exhaust and Return Dampers and

    the outlet of the Return Fan defines the return plenum. The absolute static pressure

    measured in this area is the Return Fan Plenum Pressure.

  • 8/14/2019 ipak trblshoot

    7/150

    RT-SVP04F-EN 7

    General Information

    Return Plenum Pressure High Limit. This control feature, available on all return fan

    options, shuts the supply fan and return fan off if the pressure in the return plenum

    exceeds a non-adjustable SETPOINT of 3.5 iwc.

    Space Pressure. The pressure in the building as measured by the Space Pressure

    Transducer, referenced to outside (atmospheric) pressure.

    Supply Air Pressure High Limit. A pressure limit to prevent unit casing and/or ductwork

    over pressurization.

    Statitrac. A trademark for control of space pressurization.

    Supply Air Pressure. The pressure in inches water column (IWC) of the supply duct

    plenum or outlet as measured by the Supply Air Pressure Transducer, referenced to

    local outside (atmospheric) pressure.

    Supply Air Tempering. Turning on heat when the supply air temperature drops below a

    preset value usually due to cold outside air being brought in to provide building

    ventilation.

    Supply Air Temperature Control Point. The revised value of supply air temperature

    SETPOINT after supply air temp reset has been applied.

    Supply Air Temperature Reset. A function that shifts the SA Temp SETPOINT an

    amount based on the value of another parametertypically Zone Temp or Outdoor Air

    Temp. The purpose of this function is to lower unit capacity to better meet load

    requirements.

    Target. Dynamic control point the unit is controlling to at any given time.

    UCM Control System

    Trane Large Commercial Rooftop Units are controlled by a microelectronic control

    system that consists of a network of modules and are referred to as Unit Control

    Modules (UCM).

    The unit size, type (CV or VAV), heating functions, peripheral devices, options, exhaust

    capabilities, etc. determine the number and type of modules that a particular rooftop

    unit may employ.

    The UCM receives analog and binary inputs, then processes this information and

    supplies outputs in the form of modulating voltages, contact closures, etc. to controldamper actuators, fan motors, compressors, valves, electric heating coils and other

    electrical devices in the unit to maintain set comfort levels.

    The UCM provides some equipment protection functions both directly and indirectly,

    such as duct pressure limits and compressor lockouts.

    Listed below are the various modules that may be employed in a UCM control system.

  • 8/14/2019 ipak trblshoot

    8/150

    8 RT-SVP04F-EN

    General Information

    Rooftop Module (1U1 IntelliPak II) (1U48 IntelliPak I)

    (Standard on all units) The RTM is the central processor of the system. It continuously

    receives information from the other unit modules, sensors, the remote control panel,

    and customer supplied relays. It then interprets this information and responds to

    cooling, heating, and ventilation requests by directing the other modules in the system

    to energize the proper unit components. It also directly initiates supply and exhaust fan

    operations, and economizer operation.

    Compressor Module (SCM/MCM) (IU3 IntelliPak II) (1U49 IntelliPak I)

    The Compressor module, (Single Circuit & Multiple Circuit), upon receiving a request

    for mechanical cooling, energizes the appropriate compressors and condenser fans. It

    monitors the compressor operation through feedback information it receives from

    various protection devices.

    Heat Module (1U6 IntelliPak II) (1U50 IntelliPak I)

    (Standard on all heating units) The Heat module directs the units heater to stage up and

    down to bring the temperature in the controlled space to within the applicable heating

    SETPOINT.

    Exhaust/Comparative Enthalpy Module (1U5 IntelliPak II) (1U52 IntelliPak I)

    (Option - used with Statitrac and/or comparative enthalpy) The ECEM receives data

    from the return air humidity sensor, the return air temperature sensor, and the return air

    space pressure transducer to control the economizer, exhaust fan and the exhaust

    dampers to maintain set space pressure.

    Ventilation Control Module (7U14 IntelliPak II) (3U218 IntelliPak I)

    (Option - used with TRAQ dampers, DCV, and Outdoor Air Preheat) The VCM receives

    data from two velocity pressure sensors associated with front and back TRAQ

    assemblies to measure fresh air flow entering the unit. These measurements are

    converted to CFM and added to give total fresh air flow. This value can be used for

    monitoring purposes, to maintain flow to a minimum fresh air flow SETPOINT, or to

    maintain appropriate CO2levels in the controlled space using its space CO2sensor

    input and the DCV feature. Without TRAQ assemblies installed the VCM can use DCV

    and the CO2sensor input to control OA Damper minimum position to maintain CO2

    levels in the space. A preheat control relay output is also provided on this module to

    maintain tempered outdoor air during ventilation using the VCM Auxiliary Temperature

    input. The preheat unit is user-supplied.

    Multi Purpose Module (1U9 IntelliPak II) (1U105 IntelliPak I) (Optional - used

    with Return Fan Control)

    The MPM supports the function of return plenum pressure control by providing inputs

    for measuring return plenum pressure, calibrating that reading, and providing an

    output to control the return fan speed (if variable speed configured) in response to

    control algorithm requests.

  • 8/14/2019 ipak trblshoot

    9/150

    RT-SVP04F-EN 9

    General Information

    Modulating Dehumidification Module (1U15 IntelliPak II) (1U107 IntelliPak I)

    (Optional - used with Dehumidification Control)

    The MDM supports specific control inputs and outputs for Modulating Dehumidification

    control including modulating Reheat and Cooling valve control as well as the Reheat

    Pumpout Coil Relay output.

    Generic Building Automation System Module (1U10 = GBAS 0-5V, 1U11 = GBAS

    0-10V IntelliPak II) (1U51 = GBAS 0-5V/0-10V IntelliPak I) (Optional - used with

    Non-Trane Building Control System)

    The Generic Building Automation System (GBAS) module allows a non-Trane building

    control system to communicate with the unit and accepts external SETPOINTs in form

    of analog inputs (0 - 5 V or 0 - 10 V depending on the module selected) and a binary

    Input for demand limit. Five (5) binary outputs are available on 0 - 5 V modules. One (1)

    binary output and four (4) analog outputs are available on the 0 - 10 V modules. Refer tothe Field Installed Control Wiring section of the Unit Installation, Operation,

    Maintenance Manual (IOM) for the control wiring to the GBAS module and the various

    desired SETPOINTs with the corresponding DC voltage inputs.

    Ventilation Override Module (VOM) (1U8 IntelliPak II) (1U53 IntelliPak I)

    (Optional - used on units with special ventilation requirements)

    The Ventilation Override module can control the units air handling functions to perform

    customer specified functions such as space pressurization, exhaust, purge, unit off, etc.

    Interprocessor Communications Board (IPCB) (1U12 IntelliPak II) (1U55

    IntelliPak I) (Optional - used with Optional Remote Human Interface)

    The Interprocessor Communication Board expands communications from the unit UCM

    network to a Remote Human Interface Panel. DIP switch settings on the IPCB module for

    this application should be; Switches 1 and 2 Off, Switch 3 On.

    BACnet Communication Interface Module (BCI) (1U66 IntelliPak II) (1U104

    IntelliPak I) (Optional - used on units with Trane ICS or 3rd party Building

    Automation Systems)

    The BACnet Communication Interface module expands communications from the unit

    UCM network to a Trane Tracer Summit, or a 3rd party building automation system that

    utilizes BACnet, and allows external SETPOINT and configuration adjustment andmonitoring of status and diagnostics.

    Lontalk Communication Interface Module (LCI) (1U7 IntelliPak II) (1U65

    IntelliPak I) (Optional - used on units with Trane ICS or 3rd party Building

    Automation Systems)

    The LonTalk Communication Interface module expands communications from the unit

    UCM network to a Trane Tracer Summit, or a 3rd party building automation system that

    utilizes LonTalk, and allows external SETPOINT and configuration adjustment and

    monitoring of status and diagnostics.

  • 8/14/2019 ipak trblshoot

    10/150

    10 RT-SVP04F-EN

    General Information

    Human Interface Module (Local = 1U2, Remote = 9U13 IntelliPak II) (1U65 IntelliPak I)

    The Human Interface (HI) Module illustrated in Figure 1is the device which enables the

    customer, building owner, or contractor, to communicate to the Rooftop unit the

    necessary parameters for unit operation such as cooling and heating SETPOINTs,

    demand limiting, ventilation override modes, etc.

    The local (unit mounted) Human Interface and the Remote Human Interface Panel

    functions are identical, except for Service mode which is not available on the Remote

    Human Interface Panel.

    The local HI Module is located in the units main control panel. A small door located in

    the units control panel door allows access to the HI Modules keypad and display

    window.

    There is a 2 line by 40 character LCD screen which provides status information for the

    various unit functions as well as menus used to set or modify the operating parameters.

    There is a 16 key keypad adjacent to the LCD screen, which allows the operator to scroll

    through the various menus and make adjustments to the SETPOINTs, etc.

    The information displayed in the LCD window will be top-level status information

    unless the operator initiates other displays.

    At power-up, the Human Interface LCD will display one of four initial screens illustrated

    in the General Status section.

    1. Unit Status (Unit Off or Stopped) (The unit is configured and operational, but is not

    running). This screen shows state, mode, and function information when the unit is

    off or stopped.

    2. Unit Status (Unit On) (The unit is configured and operational, and is running). Thisscreen shows state, mode, and function information when the unit is on.

    3. VOM Active (a ventilation override command was received) This screen shows that

    the unit is in a Ventilation Override Mode.

    4. No Configuration (the unit needs to be configured). This screen shows that required

    configuration data is missing.

    The LCD screen has a backlight that makes the information easier to read. The light will

    go out if no keys are pressed for 30 minutes. If it goes out, simply press the STATUS

    key.

  • 8/14/2019 ipak trblshoot

    11/150

    RT-SVP04F-EN 11

    General Information

    Menu Keys

    The six keys illustrated in Figure 2in the MENU area (STATUS, SETPOINTS, SETUP,

    CONFIGURATION, DIAGNOSTICS, and SERVICE MODE) are used to bring up the

    various interactive menus where the user inputs and accesses unit operating data.

    Pressing these keys will display the initial screen for the menu designated by the keys

    name. The following information describes the keys and their functions when viewing

    the various menus.

    If no key is pressed for 30 minutes while the LCD is displaying a menu screen, it will

    revert back to the unit operating status screen.

    STATUS Key

    Pressing the STATUS key causes the LCD to display the operating status screen; i.e.

    On, Unit Stop, External Stop, Emergency Stop, Service Mode. Pressing the

    NEXT key allows the operator to scroll through the screens which provide information

    such as air and refrigerant temperatures, humidity levels, fan operation, compressor

    operation, heater operation, economizer positioning, exhaust operation, as well as

    heating, cooling, and compressor lockout SETPOINTs. Pressing the STATUS key while

    viewing any of the data screens will cause the LCD to go back to the operating status

    screen.

    Figure 1. Human Interface Module

  • 8/14/2019 ipak trblshoot

    12/150

    12 RT-SVP04F-EN

    General Information

    SETPOINTS Key

    Pressing the SETPOINTS key will cause the LCD screen to display the first of the

    SETPOINT screens where the operator will designate default temperature and pressure

    SETPOINTs. While scrolling through the SETPOINT screens, pressing this key again will

    cause the LCD to display the first SETPOINT screen.

    DIAGNOSTICS Key

    Pressing the DIAGNOSTICS key at any time will allow the operator to view any unit

    function failures. The LCD screen will display one of the diagnostic screens (depending

    on which diagnostic, if any, is present). If no key is pressed for 30 minutes while the

    screen is displaying diagnostic information, it will revert back to the operating status

    display.

    CONFIGURATION KeyPressing the CONFIGURATION key will cause the LCD screen to display the first of the

    configuration screens where the operator will designate unit configuration data such as

    unit type, capacity, system control, etc....

    This information was programmed at the factory. Pressing the configuration key at any

    level in the configuration menu will display the first configuration screen.

    Note: This key should be used if the units configuration data is lost or new options are

    added in the field, and to view current configuration.

    SETUP Key

    Pressing the SETUP key will cause the LCD screen to display screens where theoperator will designate various operating parameters such as temperature and

    pressure ranges, limits, percentages, SETPOINT source selections, and sensor input

    definitions for the control of the rooftop units various operating modes. Pressing the

    SETUP key at any level in the SETUP menu will display the first SETUP screen.

    SERVICE MODE Key

    Pressing the SERVICE MODE key causes the LCD to display the first of the service test

    mode screens showing various unit components which may be turned on or off for the

    particular test being performed. Once the status of these components is designated, the

    LCD will display screens that allow the operator to designate the TEST START time

    delay for each test.

    Data Manipulation Keys

    The six data manipulation keys illustrated in Figure 2, (ENTER, CANCEL, + (Plus), -

    (Minus), PREVIOUS, and NEXT are used to modify the data within the screens (change

    values, move the cursor, confirm choices, etc....)

  • 8/14/2019 ipak trblshoot

    13/150

  • 8/14/2019 ipak trblshoot

    14/150

    14 RT-SVP04F-EN

    General Information

    STOP Key

    Pressing the STOP key will cause the unit to transition to the stop state. If the current

    display is editable, pressing the STOP key will cancel the desired edit.

    TEST START Key (SERVICE)

    Pressing this key while viewing any screen in the SERVICE Mode menu will start the

    service test. When viewing status, SETUP, SETPOINT, and diagnostics screens, it has no

    function.

    CUSTOM Key

    The Custom menu is simply a status menu that contains screens that the user monitors

    most frequently. The Custom menu can only contain five status screens. To create the

    Custom menu, press the STATUS key, followed by the NEXT key (this brings up the

    initial status screen). If you want to add this screen to the Custom menu, press the +

    (Plus) key, if not, press the Next key again until a status screen appears that you would

    like to add to the Custom menu. Pressing the + (Plus) key while viewing any of the

    various status screens will add that screen to the Custom menu. Once the Custom

    menu is programed it can be accessed by pressing the CUSTOM key. To remove a

    status screen from the Custom menu, press the CUSTOM key, then press the NEXT key

    until the status screen that you want to remove appears, then press the - (Minus) key.

  • 8/14/2019 ipak trblshoot

    15/150

    RT-SVP04F-EN 15

    General Information

    General Status Display

    Anytime the rooftop unit is powered up, or the STATUS, AUTO, or STOP keys are

    pressed, the unit mounted Human Interface will display one of the following four

    general status display screens. The operator will then be able to enter keystrokes which

    will allow him to navigate through a set of menus and submenus in order to provide/

    access various monitoring, SETUP, and configuration information. The Human Interface

    will not display screens or parts of screens for which the unit is not configured.

    Unit Off or Stopped

    If at power up the unit is not running, the following display will appear on the Human

    Interface LCD screen. When this screen is being displayed, the only functional keys arethe six menu keys (STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION,

    and SERVICE MODE), the AUTO key, the CUSTOM key, and the STOP key.

    Figure 2. Human Interface Keypad

  • 8/14/2019 ipak trblshoot

    16/150

  • 8/14/2019 ipak trblshoot

    17/150

    RT-SVP04F-EN 17

    General Information

    Emergency Override Active (units with LCI or BCI module)

    If the unit has entered an Emergency Override mode of operation, one of the following

    displays will appear on the Human Interface LCD screen.

    Ventilation Override Mode

    PRESSURIZE

    Ventilation Override Mode

    DEPRESSURIZE

    Ventilation Override Mode

    PURGE

    Ventilation Override Mode

    SHUTDOWN

    Ventilation Override Mode

    FIRE

    VVDA OA Flow ___ CCFM SupplyFan

    ___________

    CVZT

    VVDA

    CVDA

    Occupied

    Unoccupied

    Morning WU

    Daytime WU

    Standby

    Shutdown

    Occupied TOV

    Initializing

    (Blank)

    Tempering

    ONOFF

    (Blank)

    Diagnostics

    ______ ____________

    Heat

    Cool

    OA Dmpr

    Dehumid

    Purge

    Humidify

    (Blank)

    1-6

    1-6

    0-100%

    OA Flow

    (Blank)

    Range

    0-5980 CCFM

    (Blank)

    Freeze Avoidance

  • 8/14/2019 ipak trblshoot

    18/150

    18 RT-SVP04F-EN

    General Information

    VOM Active

    If at power up the unit is running and has entered a Ventilation Override mode of

    operation, the following display will appear on the Human Interface LCD screen.

    No Configuration

    If at power up the unit has not been programmed with the necessary configuration data

    for normal unit operation, the following display will appear on the Human Interface LCD

    screen. When this screen is being displayed, the only functional key is the

    CONFIGURATION key.

    Note: This screen will only appear when the RTM has been field replaced. Refer to the

    Configuration Menu.

    Factory Presets

    The UCM controlled unit has many operating functions which are preset at the factory,

    but may be modified to meet the unique requirements of each job. The following list

    identifies each of the units adjustable functions and the value assigned to it. If these

    factory presets match the applications requirements, simply press the AUTO key at the

    Human Interface module to begin unit operation (after completing the Pre-Start and

    Start-Up procedures in the Installation, Operation, and Maintenance manual). If the

    application requires different settings, turn to the listed page beside the function, press

    the designated function menu key, then press and hold the NEXT or PREVIOUS keyuntil its screen appears on the LCD. Once the proper screen appears, simply follow the

    programming instructions given below the applicable screen in this manual.

    Note: Record any changes made to the factory-preset values in the corresponding

    space provided.

    VO Mode in Operation

    (A,B,C,D,E)

    Trouble Indicator

    (Blank)

    (Diagnostics)

    Ventilation Override Mode ______

    _____________

    No Configuration Present

    Press Configuration Key

  • 8/14/2019 ipak trblshoot

    19/150

    RT-SVP04F-EN 19

    General Information

    Adjustable Function Factory Preset Changed To

    To adjust

    Press...

    Control Parameters

    Default system mode Auto SETUP

    Demand limit definition for cooling None SETUP

    Demand limit definition for heating None SETUP

    Economizer control enable type Drybulb SETUP

    Exhaust enable point 25% SETUP

    Morning Warmup type Full SETUP

    Supply air low limit 50 deg F SETUP

    Unit Control Local SETUP

    Coil Frost Cutout Temp 30 deg F SETUP

    Evap Temperature Limit 35 deg F SETUP

    OA Flow Calibration Gain (Front) 1.0 SETUP

    OA Flow Calibration Offset (Front) 0 CFM SETUP

    OA Flow Calibration Gain (Back) 1.0 SETUP

    OA Flow Calibration Offset (Back) 0 CFM SETUP

    OA Flow Calibration Data - Altitude: 0 feet SETUP

    Unit Address (Comm3/Comm4 only) 1 SETUP

    Default SETPOINTs

    Economizer drybulb enable SETPOINT 75 deg F SETPOINTS

    Low ambient compressor lockout (Std. units) 50 deg F SETPOINTS

    Low ambient compressor lockout (Low ambient units) 0 deg F SETPOINTS

    Occupied zone temp SETPOINT - cooling 74 deg F SETPOINTS

    Occupied zone temp SETPOINT - heating 71 deg F SETPOINTS

    Space pressure - deadband .04 iwc SETPOINTS

    Space pressure - SETPOINT 0.08 iwc SETPOINTS

    Occ Dehumidification 60% SETPOINTS

    Occ Dehumid Hysteresis Offset 5% SETPOINTS

    Unocc Dehumidification 60% SETPOINTS

    Unocc Dehumid Hysteresis Offset 5% SETPOINTS

    Supply Air Reheat Setpoint 70 F SETPOINTS

    Supply Air Reheat Deadband 4 F SETPOINTS

    Maximum Reheat Valve Limit 85% SETPOINTSDehumid Ovrd High Zone Temp Stpt 75 F SETPOINTS

    Dehumid Ovrd Low Zone Temp Stpt 68F SETPOINTS

    Cond Coil Purge Interval 90 min SETPOINTS

    Unoccupied zone temp - cool 85 deg F SETPOINTS

    Unoccupied zone temp - heat 60 deg F SETPOINTS

    Unoccupied zone temp - morn warmup 72 deg F SETPOINTS

    Min OA Flow - SETPOINT w\VCM Set per unit size SETPOINTS

    Min OA Flow - deadband Set per unit size SETPOINTS

    Preheat actuate temp 35 deg F SETPOINTS

  • 8/14/2019 ipak trblshoot

    20/150

    20 RT-SVP04F-EN

    General Information

    Design Min CO2(DCV) 1000 PPM SETPOINTS

    DCV Min CO2 8001/4002PPM SETPOINTS

    DCV Min OA Flow Deadband 5 CCFM SETPOINTS

    Design Min OA Flow (DCV) 220 CCFM SETPOINTS

    DCV Min OA Flow 67 CCFM SETPOINTS

    Design Min OA Damper Position(DCV) 15% SETPOINTS

    DCV Min OA Damper Position 5% SETPOINTS

    OA Damper Min Position (non-DCV) 15% SETPOINTS

    Hydronic Heat Freeze Avoidance Open To: 0% SETPOINTS

    Recovery Frost Avoidance Setpoint 27F SETPOINTS

    Functions enable/disable

    Compressor lead/lag Enable SETUP

    Adjustable Function

    Factory

    Preset Changed To

    To adjust

    Press...

    Morning warmup Enable SETUP

    Supply air tempering Enable SETUP

    Unoccupied economizer Enable SETUP

    Unoccupied mechanical cooling Enable SETUP

    Unoccupied heating Enable SETUP

    Occupied Dehumidification Enable SETUP

    Unoccupied Dehumidification Enable SETUP

    Demand Control Ventilation Disable SETUP

    Occupied Humidification Disable SETUP

    Unoccupied Humidification Disable SETUP

    GBAS Input/Output Definitions...

    GBAS analog input definitions Not Assigned SETUP

    GBAS output definitions SETUP

    Information format

    Text displays English SETUP

    Unit displays English SETUP

    RTM alarm output definitions Any Active Diagnostic SETUP

    Sensor source selection for...

    Monitor RTM Zone Temp SETUP

    Morning warmup RTM Zone Temp SETUP

    Occupied zone control RTM Zone Temp SETUP

    Unoccupied zone control RTM Zone Temp SETUP

    Space Humidity Control RTM Space Humidity SETUP

    Dehumid OVRD Zone Temp RTM Zone Temp SETUP

    SETPOINT source selection for...

    Morning warmup Default SETUP

    Occupied zone cooling Default SETUP

  • 8/14/2019 ipak trblshoot

    21/150

    RT-SVP04F-EN 21

    General Information

    Occupied zone heating Default SETUP

    Space Pressure Default SETUP

    Unoccupied zone cooling Default SETUP

    Unoccupied zone heating Default SETUP

    Economizer Dry Bulb Enable Default SETUP

    Occupied Dehumidification Default SETUP

    Unoccupied Dehumidification Default SETUP

    Supply Air Reheat Default SETUP

    OA Damper Actuator (if equipped)

    Actuator SETUP DIRECT SETUP

    Max stroke time 30 sec SETUP

    Max voltage 10 VDC SETUP

    Min voltage 2 VDC SETUP

    Exhaust Damper Actuator (if equipped)

    Actuator SETUP... (Direct/reverse action) DIRECT SETUP

    Max stroke time 30 sec SETUP

    Max voltage 10 VDC SETUP

    Min voltage 2 VDC SETUP

    Adjustable Function

    Factory

    Preset Changed To

    To adjust

    Press...

    Hydronic Heat Actuator (if equipped)

    Actuator SETUP... (Direct/reverse action) Direct Acting SETUP

    (Max stroke time) 60 seconds SETUP

    (Max voltage) 10 VDC SETUP

    (Min voltage) 2 VDC SETUP

    Lo Ambient Damper Actuator Ckt#1 and Ckt #2

    (if equipped)

    Actuator SETUP... (Direct/reverse action) Direct Acting SETUP

    (Max stroke time) 60 seconds SETUP

    (Max voltage) 10 VDC SETUP

    (Min voltage) 2 VDC SETUP

    Cond Fan VFD Ckt #1

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 60 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 0 VDC SETUP

    Cond Fan VFD Ckt #2

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 60 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 0 VDC SETUP

  • 8/14/2019 ipak trblshoot

    22/150

    22 RT-SVP04F-EN

    General Information

    Supply Fan IGV/VFD (if equipped)

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 30 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 2 VDC SETUP

    Exhaust Damper/VFD (if equipped)

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 60 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 0 VDC SETUP

    Return Fan VFD (if equipped)

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 60 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 2 VDC SETUP

    Exhaust bypass damper

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 60 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 2 VDC SETUP

    Outdoor air bypass damper

    Actuator SETUP Direct Acting SETUP

    Max Stroke Time 60 sec SETUP

    Max Voltage 10 VDC SETUP

    Min Voltage 2 VDC SETUP

    Modulating Gas Heat Actuator (if equipped)

    Actuator SETUP... (Direct/reverse action) Direct2/Reverse1

    Acting

    SETUP

    Max stroke time 90 seconds SETUP

    Max voltage 10 VDC SETUP

    Min voltage 2 VDC2/5 VDC1 SETUP

    Head Pressure Control

    Temporary low limit suppression 10 deg F SETUP

    Upper limit 120 deg F SETUP

    Low limit 80 deg F SETUP

    Efficiency check point 105 deg F SETUP

    Low ambient control point 90 deg F SETUP

    Sump Drain Relay Control (on power loss)2 Drain SETUP

    Sump Purge Interval Time2 3 hours SETUP

  • 8/14/2019 ipak trblshoot

    23/150

    RT-SVP04F-EN 23

    General Information

    Password Protected Screens

    Some of the operating displays on the Human Interface LCD screens and require a

    password to change. The following screens display the various programming sections

    that require a password in order to view or to modify the preset operating parameters.

    The password for each screen is a different series of + (Plus) or - (Minus) key strokes in

    a predefined sequence. Shown below are the password protected screens, and the

    passwords for accessing them.

    The following screens display the various programming sections that require a specific

    PASSWORD to be entered by a qualified operator in order to modify the operating

    parameters. The following screen will appear if the PASSWORD is not entered within

    approximately 15 seconds.

    Sump Purge Duration Time2 60 sec. SETUP

    Sump Water Heater Setpoint2 38 F SETUP

    Temperature Input Offset for...

    Heat morning warmup 0 deg F SETUP

    Return air 0 deg F SETUP

    RTM zone temperature 0 deg F SETUP

    RTM aux temperature 0 deg F SETUP

    Outdoor air 0 deg F SETUP

    Ventilation override definition See Definitions SETUP

    Note 1. Reference note 1 applies to IntelliPak I units only.Note 2. Reference note 2 applies to IntelliPak II units only.

    Password Entry Time Limit Exceeded

    1. Press the NEXT key until the following screen is displayed.

    Configuration is Password Protected

    Please Enter Password: __________

    2. Press the + or - keys in this sequence ( + - - - ) to access this restricted screen.

    3. Press the ENTER key to confirm the password and enter the menu.

    4. Press the NEXT key until the following screen is displayed.

    Ventilation Override Mode _______

    Enter Password to Lock Definition:

    1. Press the + or - keys in this sequence ( + - - + ) to lock each VO Mode.

    2. Press the ENTER key to confirm the password and Lock the definitions.

    3. Press the NEXT key until the following screen is displayed.

  • 8/14/2019 ipak trblshoot

    24/150

    24 RT-SVP04F-EN

    General Information

    Diagnostic Reset is Password Protected

    Please Enter Password: ____________

    1. Press the + or - keys in this sequence ( - + + ) to access this restricted screen.

    2. Press the ENTER key to confirm the password and Lock the definitions.

    3. Press the NEXT key until the following screen is displayed.

    Diagnostic Log is Password Protected

    Please Enter Password: __________

    1. Press the + or - keys in this sequence ( - + + -) to access this restricted screen.

    2. Press the ENTER key to confirm the password and Lock the definitions.

    3. Press the NEXT key until the following screen is displayed.

  • 8/14/2019 ipak trblshoot

    25/150

    RT-SVP04F-EN 25

    STATUS MenuThe STATUS menu is used to view various operating conditions such as temperatures

    and humidity levels. Its used to view unit component status such as fan, compressor,

    heater, and economizer operation, as well as SETPOINT status.

    The screens shown in this section are for example only. Pressing the + (Plus) key while

    viewing any of the status display screens will add that screen to the Custom menu.

    When a status screen is displayed for 30 minutes without a key being pressed, the LCD

    screen will revert to the general operating status display. If this happens, press the

    STATUS key again to return to the status menu. The following are examples of status

    screens that may be viewed by pressing the STATUS key.

    Note: Many of the screens displayed in this section are applicable only for the options

    that are installed in the unit and may not be visible on your unit.

    Press the STATUS key to begin viewing the status screens.

    Note: The range for all temperature inputs is 40 to 200 F. ERR will appear if the

    temperature is out of range.

    System Operating Status

    VAV OA FLOW

    OCCUPIED

    *350.0 CCFM OADMPR 0%

    SUPPLY FAN ONDIAGNOSTICS

    Notes: *VCM only - if the unit does not havea VCM this section of the screen isblank.

    1. Press the NEXT key until the following screen is displayed.

    GENERAL SYSTEM STATUS SUBMENU SCREENS

    General System Status Submenu

    Press ENTER to View Data in this Submenu

    Used With: All Units

    1. Pressing the NEXT key will bypass this section.

    Active Unit Control Source:

    Active Cluster Member Role:

    XXXXXXXXXXXX

    XXXXXXXXXX

    Used With: All Units

    Possible Values:Source = Local,

    BAS/Network

    Role = Standalone, Slave, Master

    1. Pressing the NEXT key will scroll forward through the screens.2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custommenu for the creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (if applicable)

  • 8/14/2019 ipak trblshoot

    26/150

    26 RT-SVP04F-EN

    System Operating Status

    RTM Supply Fan Relay:

    RTM Supply Airflow Proving:

    OFF

    FLOW

    Used With: All Units

    Possible Values:Fan = ON, OFF

    Airflow = FLOW, NO FLOW

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custommenu for the creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (if applicable)

    Supply Fan IGV/VFD Cmd Opening To 30%

    Active Supply Air Pressure 2.0 IWC

    Used With:All units with IGV/VFD.Active SAP only shown if SAP ispresent.

    Possible Values: Opening to/

    Closing to: 0-100%; Active SupplyAir Pressure= 0.0 -7.9 IWC

    1. Press the NEXT key until the following screen is displayed.

    OR

    Active Supply Air Pressure 2.0 IWC

    Used With: Rooftop units and AirHandlers when IGV/VFD is notinstalled and valid SAP sensor ispresent.

    1. Press the NEXT key until the following screen is displayed. Possible Values: 0.0 IWC - 7.9IWC

    Exhaust Fan OFF Used With:All units when PowerExhaust without Statitrac is installed

    without Return FanPossible Values:Fan= ON/OFF,

    1. Press the NEXT key until the following screen is displayed.

    OR

    Exhaust Fan ON

    Exhaust Damper/VFD

    Space Pressure

    Opening to

    0.00 IWC

    32 %

    Used With:All units when PowerExhaust with Statitrac is installedwithout Return Fan

    Possible Values:Fan= ON, OFF,Damper/VFD = 0 to 100%

    1. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Note: "Exhaust Fan" and "Exhaust Damper/VFD" is shown only if

    "Power Exhaust Config" is not = NONE

    "Exhaust Fan" is not shown if Return Fan is installed

    "Space Pressure" is shown only if Power Exhaust or ReturnFan with Statitrac is installed

  • 8/14/2019 ipak trblshoot

    27/150

    RT-SVP04F-EN 27

    System Operating Status

    Electric Heat: ENABLED

    Stage: 6 K11: ON K12: ON K1: ON

    Used With:All units with ElectricHeat installed.

    Possible Values: Electric Heat:

    ENABLED, DISABLED By Setup,LIMITED By Demand Limit

    Stage: 0,1,2,3,4,5,6K*: ON, OFF

    1. Press the NEXT key until the following screen is displayed.

    (If applicable)

    Note: Enabled indicates OK to

    heat; disabled indicates

    NOT OK to heat, such as

    during cooling.

    OR

    Gas Heat: ENABLED

    Stage: 2 K11: ON K12: ON K1: ON

    Used With:All units with StagedGas Heat Installed.

    Possible Values: ENABLED,DISABLED By Setup, LIMITED By

    Demand LimitStage: 0,1,2K*: ON, OFF

    1. Press the NEXT key until the following screen is displayed. (Ifapplicable)

    OR

    Hydronic Heat ENABLED

    Valve Position: Opening To: 100%

    Used With: All units with hydronic

    heat is installed

    1. Press the NEXT key until the following screen is displayed. Low tempair may be OK or tripped (If applicable)

    Possible Values:ENABLED,DISABLED By Setup, LIMITED ByDemand Limit, LIMITED By Low AirTemp; Valve Position: Opening to/Closing to 0-100%

    OR

    Mod Gas Heat ENABLEDValve Position: Opening To: 100%

    Used With: All units withmodulating gas heat is installed

    1. Press the NEXT key until the following screen is displayed. (Ifapplicable)

    Possible Values:ENABLED,DISABLED By Setup, LIMITED By

    Demand Limit; Valve Position:Opening to/Closing to 0-100%

    Chilled Water:

    Valve Position:

    Opening To ENABLED

    100%

    Used With:Air Handler Units withChilled Water Installed

    Possible Values:Chilled Water:ENABLED, DISABLED By SETUP,LIMITED By Demand Limit, LIMITED

    By Low Air Temp; Valve Position -Field One: Opening To, Closing To -Field Two: 0-100%

  • 8/14/2019 ipak trblshoot

    28/150

    28 RT-SVP04F-EN

    System Operating Status

    Dehumidification Status:

    by Comfort Control Override is Active

    DISABLED Used With:All IntelliPak withDehumidification option installed.

    1. Pressing the NEXT key will scroll forward through the screens. Top Line Possible Values:

    ENABLED, DISABLEDBottom line Possible Values: See

    below

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    by Call for Cooling Demand Limit If 1st line is "DISABLED"

    by Compressor Lockout Sources If 1st line is "DISABLED"

    by Occ Dehumid Function Disable If 1st line is "DISABLED"

    by Dehumid Override Zone Temp High If 1st line is "DISABLED"

    by OA Temperature Out Of Range If 1st line is "DISABLED"

    by Unocc Dehumid Function Disable If 1st line is "DISABLED"by Comfort Control Override is Active If 1st line is "DISABLED"

    by Required Sensor Failure Condition If 1st line is "DISABLED"

    by Insufficient Airflow Condition If 1st line is "DISABLED"

    by Sat Reheat Cond Temp Sensor Fail If 1st line is "DISABLED"

    By Reheat Head Pressure High Limit If 1st line is "DISABLED"

    (Blank) If 1st line is "ENABLED"

    Condenser Coil Purge is Active If 1st line is "ENABLED"

    HumidificationStatus:

    Humidification isActive

    ENABLED Used With:Used With: All unitswith Humidification option installed.

    Key Stroke Operation (1)

    1. by Occ Humidification Function Disable

    2. by Unocc Humidification Function Disable

    3. Humidification is Inactive

    4. Humidification is Active

    Possible Values: ENABLED,DISABLEDby Occ Humidification FunctionDisable (If 1st line is "DISABLED"),by Unocc Humidification FunctionDisable (If 1st line is "DISABLED"),Humidification is Inactive (If 1st lineis "ENABLED" and output is de-energized, Humidification is Active(If 1st line is "ENABLED" and outputis energized)

    1. Press the NEXT key until the following screen is displayed. (Ifapplicable)

    End of Submenu (NEXT) to Enter STATUS

    1. Press the NEXT key to leave the submenu and show followingscreen.

    2. Press PREVIOUS to page back through the submenu.

  • 8/14/2019 ipak trblshoot

    29/150

    RT-SVP04F-EN 29

    System Operating Status

    Compressor Status Submenu

    Press ENTER to View Data in This Submenu

    Used With: All Rooftop Units andAir Handlers with DX Coolinginstalled.

    1. Pressing the NEXT key will bypass this section.

    Compressor Relay KXX XXXXXX

    XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)

    Used With:IntelliPak I RooftopUnits and Air Handlers with DXCooling installed.

    Possible Values:K10, K11

    Second Field: ON, OFF, LOCKED

    Bottom Field: Enabled or any itemfrom Lockout Sources List.

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation and

    maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (if

    applicable)

    Ckt 1 Compr Relay K11: ON

    Enabled............................................ (MORE)

    Used With:All IntelliPak II Rooftopunits or Air Handlers with DXCooling.

    Possible Values:K11: ON, OFF,LOCKED; Second Field: Enabled or

    any item from Lockout Sources List

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screen

    to the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Compressor Relay KXX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)

    Used With:IntelliPak I RooftopUnits and Air Handlers with DX

    Cooling installed.

    Possible Values:K11, K12

    Second Field: ON, OFF, LOCKED

    Bottom Field: Enabled or any itemfrom Lockout Sources List.

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Ckt 1 Compr Relay K12: LOCKED

    Disabled By Evap Temp Sensor Fail (MORE)

    Used With:All IntelliPak II Rooftop

    units or Air Handlers with DXCooling.

    Possible Values:K12: ON, OFF,LOCKED; Second Field: Enabled or

    any item from Lockout Sources List

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

  • 8/14/2019 ipak trblshoot

    30/150

    30 RT-SVP04F-EN

    System Operating Status

    Compressor Relay K3 XXXXXX

    XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)

    Used With:All IntelliPak I RooftopUnits and Air Handlers with DXCooling installed.

    Possible Values:Second Field: ON,OFF, LOCKED

    Bottom Field: Enabled or any itemfrom Lockout Sources List.

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Ckt 2 Compr Relay K3: OFF

    Enabled............................................. (MORE)

    Used With:All IntelliPak II Rooftopunits or Air Handlers with DXCooling.

    Possible Values:K3: ON, OFF,

    LOCKED; Second Field: Enabled orany item from Lockout Sources List

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Compressor Relay K4 XXXXXX

    XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX (MORE)

    Used With:All IntelliPak I RooftopUnits and Air Handlers with DXCooling installed.

    Possible Values:Second Field: ON,OFF, LOCKED

    Bottom Field: Enabled or any itemfrom Lockout Sources List.

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screento the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Ckt 2 Compr Relay K4: LOCKED

    Disabled By Evap Temp Sensor Fail (MORE)

    Used With:All IntelliPak II Rooftopunits or Air Handlers with DXCooling.

    Possible Values:K4: ON, OFF,LOCKED; Second Field: Enabled or

    any item from Lockout Sources List

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screen

    to the custom menu. Refer to the custom menu for the creation andmaintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed. (ifapplicable)

  • 8/14/2019 ipak trblshoot

    31/150

    RT-SVP04F-EN 31

    System Operating Status

    Disable or Lockout Sources

    Disabled By Compressor Protection (Compressor proving input did not close)

    Disabled By Contactor Failure (Compressor proving input stuck closed)

    Disabled By Low Pressure Cutout (Low pressure cutout input to MCM)Disabled By Bad Cond Temp Sensor (Temp Sensor is out of -40 F to 200 F range)

    Disabled By Demand Limit (From GBAS or BAS/Network)

    Disabled By Frost Protection (Leaving evap temp sensor colder than coil frost

    temp setpoint (25 F to 35 F)

    Disabled By BAS/Network Lockout

    Disabled By Minimum Off Time (3 minutes)

    Disabled By Low Ambient Lockout (setpoint range -20 F to 80 F)

    Disabled By Ventilation Override (VOM input A-E or BAS/Network)

    Disabled By LPC Delay (3 minutes)

    Disabled By Water Flow Status

    Disabled By Cond Coil Purge Request

    Disabled By Sump Temp Sensor Fail

    Disabled By Low Refrig Charge (Evap temp limit setpoint (24-45 F) has beenexceeded for 10 minutes

    Disabled By Evap Temp Sensor Fail

    Disabled By Sump Min Level Sensor Fail

    Disabled By Sump Pump Failure

    Disabled By Sump Min Level Control

    * These entries apply to the following 4 screens.

    Note: If a compressor output is

    disabled or locked, these

    lockout sources will be

    found in the bottom field forIntelliPak I, or in the second

    field for IntelliPak II.

    Circuit 1 Evap Diff: 5.0

    Enter Evap: 48.5 Leave Evap: 53.5

    Used With: All Rooftop Units and

    Air Handlers when DX cooling isinstalled.Possible Values:Evap Diff. = 0.0

    to 200.0 F, Enter Evap= -40.0 to200.0 F, Leave Evap: -40 to 200.0F

    1. Press the NEXT key until the following screen is displayed. (if

    applicable)

    Note: "Evap Diff" and associated value not displayed on inactive

    circuit or for first ten minutes of circuit operation or if HGBP is

    installed.

    Note: "Enter Evap" and associated value not displayed if HGBP is

    installed

    1. Press the NEXT key until the following screen is displayed.

    Circuit 1

    Saturated Condensing Temp: 100.0

    Used With:All Rooftops or Air

    Handlers with DX Cooling.Possible Values:SaturatedCondensing Temp= -40.0 to 200.0F

    1. Press the NEXT key until the following screen is displayed.

  • 8/14/2019 ipak trblshoot

    32/150

  • 8/14/2019 ipak trblshoot

    33/150

    RT-SVP04F-EN 33

    System Operating Status

    Condenser Sump Pump Relay Command: ON Used With:All IntelliPak II unitswith water-cooled condensers

    installed.Possible Values:Sump PumpRelay: ON, OFF; Sump Proving:FLOW, NO FLOW

    Condenser Sump Pump Proving: FLOW

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Condenser Water Valve Relay Ckt1: OFF Used With:All IntelliPak II unitswith water-cooled condensersinstalled.

    Possible Values:Water ValveRelay: ON, OFF; Water Valve:CLOSED, OPEN

    Condenser Water Valve Ckt1: OPEN

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Condenser Water Valve Relay Ckt2: ON Used With:All IntelliPak II unitswith water-cooled condensersinstalled.

    Possible Values:Water Valve

    Relay: ON, OFF; Water Valve:CLOSED, OPEN

    Condenser Water Valve Ckt2: CLOSED

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Condenser Sump Fill Relay: OFF Used With:All IntelliPak II units

    with water-cooled condensersinstalled.

    Possible Values:Sump Fill Relay:ON, OFF; Sump Fill Valve: CLOSED,

    OPEN

    Condenser Sump Fill Valve: OPEN

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Condenser Sump Drain Relay: ON Used With:All IntelliPak II unitswith water-cooled condensersinstalled.

    Possible Values:Sump Drain

    Relay: ON, OFF; Sump Drain Valve:CLOSED, OPEN

    Condenser Sump Drain Valve: CLOSED

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Note: Valve position with Relay ON is configurable based on if need

    to hold water in the sump or drain it on power loss. See

    Installation and Operations Manual.

  • 8/14/2019 ipak trblshoot

    34/150

    34 RT-SVP04F-EN

    System Operating Status

    Cond Sump Water Level Max Input: OPEN Used With:All IntelliPak II unitswith water-cooled condensersinstalled.

    Possible Values:Max Input:CLOSED, OPEN; Min Input: CLOSED,

    OPEN

    Cond Sump Water Level Min Input: CLOSED

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    External Sump Drain Request: INACTIVE Used With:All IntelliPak II unitswith water-cooled condensersinstalled.

    Possible Values:ACTIVE,INACTIVE

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Reheat Coil Pumpout Relay: OFF Used With:All IntelliPak units withDehumidification installed.

    Possible Values:Coil PumpoutRelay: ON, OFF; Coil Pumpout Valve:CLOSED, OPEN

    Reheat Coil Pumpout Valve: CLOSED

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Dehumid Reheat Valve Position: 0% Used With:All IntelliPak units with

    Dehumidification installed.

    Possible Values:Reheat Valve: 0-Max Reheat Valve Position Setpoint;

    Cooling Valve: 10-100%

    Dehumid Cooling Valve Position: 100%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Outside Air Temperature 70.0F Used With:All Rooftops or AirHandlers with DX Cooling.

    Possible Values: Active Outside AirTemp= -40 to 200.0F; Low Ambient

    Comp Lockout Temp= -20 to 80F(Default: 50 F Standard, 0 F Low-ambient with Hot Gas Bypass, 10 FLow-ambient without Hot GasBypass)

    Low Ambient Comp Lockout Temp: 50F

    1. Press the NEXT key until the following screen is displayed.

  • 8/14/2019 ipak trblshoot

    35/150

    RT-SVP04F-EN 35

    System Operating Status

    End of Submenu (NEXT) to Enter STATUS

    1. Press the NEXT key to leave the submenu and show following

    screen.2. Press PREVIOUS to page back through the submenu.

    ECONOMIZER STATUS SUBMENU SCREENS

    Economizer Status Submenu

    Press ENTER to View Data in This Submenu

    Used With: All Units when aneconomizer is installed

    1. Pressing the NEXT key will bypass the next section.

    Air Economizing: ENABLED

    Outside Air Damper Pos: 10%

    Used With:All units when anEconomizer is installed.

    Possible Values:Economizing:

    ENABLED/DISABLED Outside Air:Opening To/Closing To 0 - 100%

    1. Press the NEXT key until the following screen is displayed.

    Note: Enabled = OK to economize

    Disabled = Not OK to

    economize

    Active Outside Air Enthalpy

    ECEM Return Air Enthalpy

    29.5 BTU/LB

    34.0 BTU/LB

    Used With:All Units when anEconomizer is installed. "RA Enth" isdisplayed if Comparative Enthalpy orEnergy Recovery is installed.

    1. Press the NEXT key until the following screen is displayed. Possible Values: 10 to 35 BTU/LB

    Active Outside Air Temperature

    ECEM Return Air Temperature

    86.0 F

    78.0 F

    Used With:All Units when anEconomizer is installed. "RA Temp"is displayed if Comparative Enthalpyor Energy Recovery is installed.

    1. Press the NEXT key until the following screen is displayed. (ifapplicable)

    Active Outside Air Humidity

    ECEM Return Air Humidity

    30 %

    62 %

    Used With:All Units when anEconomizer is installed. "RA

    Humidity" is displayed ifComparative Enthalpy or EnergyRecovery is installed.

    1. Press the NEXT key until the following screen is displayed. Possible Values: 10 to 90 %

    End of Submenu (NEXT) to Enter STATUS

    1. Press the NEXT key to leave the submenu and show followingscreen.

    2. Press PREVIOUS to page back through the submenu.

  • 8/14/2019 ipak trblshoot

    36/150

  • 8/14/2019 ipak trblshoot

    37/150

    RT-SVP04F-EN 37

    System Operating Status

    End of Submenu (NEXT) to Enter STATUS

    1. Press the NEXT key to leave the submenu and show following

    screen.

    2. Press PREVIOUS to page back through the submenu.

    RETURN FAN STATUS SUBMENU SCREENS

    Note: Return Fan and Energy Recovery are mutually exclusive

    features. Only one of the following two status submenus will

    be displayed.

    Return Fan Status Submenu Used With:All units with ReturnFan installed.

    Press ENTER to View Data in This Submenu1. Pressing the NEXT key will bypass this section.

    Return Fan Relay: ON Used With:All units with ReturnFan installed.

    Possible Values: ON, OFFReturn Airflow Proving: ON

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.(if applicable)

    Return Fan VFD Command: 45% Used With:All units with ReturnFan installed.

    Possible Values: 0 to 100%; -0.7to 3.5 IWC

    Return Plenum Pressure: 0.8 IWC

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Note: Top line shown only if Return Fan VFD is installed.

  • 8/14/2019 ipak trblshoot

    38/150

    38 RT-SVP04F-EN

    System Operating Status

    Return Plenum Pressure Target: 0.8 IWC Used With:All units with ReturnFan installed.

    Possible Values: 0.1 to 2.5 IWC;

    Return Fan VFD= Opening to/Closingto 0 to 100%

    Return Fan VFD Pos: Opening to 45%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Max Return Plenum Pressure Stp: 1.2 IWC Used With:All units with ReturnFan installed.

    Possible Values: Max Return= 0.1

    to 2.5 IWC (Default 1.2 IWC);Deadband = 0.1 to 1.0 IWC (Default0.2 IWC)

    Note: High limit is 3.5 IWC and is not

    adjustable.

    High Limit: 3.5 IWC Deadband: 0.2 IWC

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    End of Submenu (NEXT) to Enter STATUS

    1. Press the NEXT key to leave the submenu and show following

    screen.2. Press PREVIOUS to page back through the submenu.

    Energy Recovery Status Submenu Used With:All IntelliPak II units

    with Energy Recovery installed.Press ENTER to View Data in This Submenu

    1. Pressing the NEXT key will bypass this section.

    Energy Wheel Relay: ON Used With:All IntelliPak II unitswith Energy Recovery installed.

    Possible Values:ON, OFFEnergy Wheel Proving: ON

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

  • 8/14/2019 ipak trblshoot

    39/150

    RT-SVP04F-EN 39

    System Operating Status

    Outside Air Bypass Damper Pos: 0% Used With:All IntelliPak II unitswith Energy Recovery installed.

    Possible Values:0-100%Exhaust Air Bypass Damper Pos: 15%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Energy Wheel Frost Avoidance: INACTIVE Used With:All IntelliPak II unitswith Energy Recovery installed.

    Possible Values:Frost Avoidance:

    ACTIVE, INACTIVE;

    Recovery Exhaust Temp: -40.0 to

    200.0 F

    Leaving Recovery Exhaust Temp: 45.0F

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Energy Wheel Preheat Relay: OFF Used With:All IntelliPak II unitswith Energy Recovery Preheatinstalled.

    Possible Values:ON, OFF1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    CONTROLLING SETPOINT STATUS SUBMENU SCREENS

    Controlling SETPOINT Status Submenu

    Press ENTER to View Data in This Submenu

    Used With: All Units

    1. Pressing the NEXT key will bypass this section.

    Active Supply Air Cooling STP From

    HI (KEYPAD) SETPOINT MENU Is 55 F

    Used With: All Units

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Possible Values: HI (Keypad)SETPOINT Menu, Zone SensorSETPOINT Input, NSB PanelSETPOINT Input, GBAS 0-5 VDC

    Module, BAS/Network, GBAS 0-10VDC Module

  • 8/14/2019 ipak trblshoot

    40/150

    40 RT-SVP04F-EN

    System Operating Status

    Active Supply Air Heating STP From

    HI (KEYPAD) SETPOINT MENU Is 100 F

    Used With: All Units whenHydronic Heat, Electric Heat, orModulating Gas Heat is installed.

    Possible Values: HI (Keypad)SETPOINT Menu, Zone Sensor

    SETPOINT Input, GBAS 0-5 VDCModule, BAS/Network, GBAS 0-10VDC Module

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Daytime Warmup SETPOINTs

    Initiate: 67 F Terminate: 71 F

    Used With:All Units when Gas,Electric, Hydronic or External Heat is

    installed.

    Possible Values: HI (Keypad)

    SETPOINT Menu; Initiate= 50-87F;Terminate= 53-90 F (This SETPOINTsource is HI (keypad) or BAS/

    Network

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Occupied Zone Heating STP From

    HI (KEYPAD) SETPOINT MENU Is 71 F

    Used With: All Units when Gas,

    Electric, Hydronic or External Heat isinstalled and Daytime Warmupenabled.

    Possible Values: HI (Keypad)SETPOINT Menu Zone Sensor Setpnt

    Input, NSB Panel SETPOINT Input,GBAS 0-5 VDC Module, BAS/Network, GBAS 0-10 VDC Module;Range 50 - 88F

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Unoccupied Zone Cooling STP From

    HI (KEYPAD) SETPOINT MENU Is 85 F

    Used With: All Units

    Possible Values: HI (KEYPAD)enabled.

    Possible Values: HI (Keypad)

    SETPOINT Menu Zone Sensor SetpntInput, NSB Panel SETPOINT Input,GBAS 0-5 VDC Module, BAS/

    Network, GBAS 0-10 VDC Module;Range: 52 - 90 F

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

  • 8/14/2019 ipak trblshoot

    41/150

    RT-SVP04F-EN 41

    System Operating Status

    Active Unoccupied Zone Heating STP From

    HI (KEYPAD) SETPOINT MENU Is 60 F

    Used With: All Units when Gas,Electric, Hydronic or External Heat isinstalled

    Possible Values:HI (Keypad)SETPOINT Menu, NSB Panel

    SETPOINT Input, GBAS 0-5 VDCModule, BAS/Network, GBAS 0-10VDC Module; Range 50 - 88F

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Morning Warmup SETPOINT From

    HI (KEYPAD) SETPOINT MENU Is 72 F

    Used With: All Units when Gas,Electric, Hydronic or External Heat is

    installed

    Possible Values:HI (Keypad)

    SETPOINT Menu Zone Sensor SetpntInput, NSB Panel SETPOINT Input,GBAS 0-5 VDC Module, BAS/

    Network, GBAS 0-10 VDC Module;Range: 52 - 90 F

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Occ Dehumidification Setpt From

    HI (KEYPAD) SETPOINT MENU is 60%

    Used With:All IntelliPak units with

    Dehumidification installed.

    Possible Values:HI (KEYPAD)

    SETPOINT MENU, BAS/NETWORK,

    GBAS 0-5VDC Module, BAS/Network, GBAS 0-10 vdc Module;

    Range= 40 to 65%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view thepreviously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Unocc Dehumidification Setpt From

    HI (KEYPAD) SETPOINT MENU is 60%

    Used With:All IntelliPak units withDehumidification installed.

    Possible Values:HI (KEYPAD)SETPOINT MENU, BAS/NETWORK,

    GBAS 0-5VDC Module, BAS/Network, GBAS 0-10 vdc Module;

    Range= 40 to 65%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Supply Air Reheat Setpoint From

    HI (KEYPAD) SETPOINT MENU is 70.0F

    Used With:All IntelliPak units withDehumidification installed.

    Possible Values:HI (KEYPAD)SETPOINT MENU, BAS/NETWORK,

    GBAS 0-5VDC Module, BAS/

    Network, GBAS 0-10 vdc Module;

    Range= 60 to 80 F

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the NEXT key until the following screen is displayed.

    (if applicable)

  • 8/14/2019 ipak trblshoot

    42/150

    42 RT-SVP04F-EN

    System Operating Status

    Active Occ Humidification Setpt From Used With:All units with OccupiedHumidification option enabled.

    Possible Values: HI (KEYPAD)

    SETPOINT MENU, GBAS 0-5VDCModule, BAS/Network, GBAS 0-10

    vdc Module; Range= 20 to 50%

    HI (Keypad) Setpoint Menu is _________ 40%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Unocc Humidification Setpt From Used With:All units withUnoccupied Humidification optionenabled.

    Possible Values: HI (KEYPAD)SETPOINT MENU, GBAS 0-5VDCModule, BAS/Network, GBAS 0-10vdc Module; Range= 20 to 50%

    HI (Keypad) Setpoint Menu is_____________ 20%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Econ DB Enable SETPOINT From

    HI (Keypad) Setpoint Menu is__________ 75 F

    Used With: All Units when an

    Economizer is installed

    Possible Values: HI (KEYPAD)

    SETPOINT MENU, GBAS 0-5VDC

    Module, GBAS 0-10VDC Module;SETPOINT range: 40 F to 90 F

    1. Press the NEXT key until the following screen is displayed. (if applicable)

    Active OA Damper Min Position STP From Used With:All units with 0-25%Motorized Damper or 0-100% AirEconomizer and i) OA CFMCompensation function is DISABLEDor ii) OA Damper Min PositionSETPOINT source selection is otherthan HI (KEYPAD) SETPOINT

    Possible Values: HI (KEYPAD)SETPOINT MENU, RTM Min PositionPot, GBAS 0-5VDC Module, GBAS 0-

    10VDC Module, BAS/Network;Range from 0 to 100%

    HI (Keypad) Setpoint Menu is_________ 25%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the

    previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.(if applicable)

  • 8/14/2019 ipak trblshoot

    43/150

    RT-SVP04F-EN 43

    System Operating Status

    Active Min OA Flow SETPOINT From

    HI (KEYPAD) SETPOINT MENU 34.2 CFM

    Used With: All Units when FreshAir Measurement VCM is installed

    Possible Values: HI (Keypad)

    SETPOINT Menu, GBAS 0 - 5 VDCModule, BAS Network GBAS 0-10

    VDC Module SETPOINT range: 0 toMax Unit Airflow

    Refer to the table in the SETPOINTsection, "Default Min OA FlowSETPOINT Screen" for max airflow

    SETPOINTs.

    1. Press the NEXT key until the following screen is displayed. (if applicable)

    Active Design Min OA Flow SETPOINTFrom HI (KEYPAD) SETPOINT MENU 34.2 CFM

    Used With: All Units when FreshAir Measurement VCM is installed

    Possible Values: HI (Keypad)SETPOINT Menu, GBAS 0 - 5 VDC

    Module, BAS Network GBAS 0-10VDC Module SETPOINT range: 0 toMax Unit Airflow

    Refer to the table in the SETPOINTsection, "Default Min OA FlowSETPOINT Screen" for max airflow

    SETPOINTs.

    1. Press the NEXT key until the following screen is displayed. (if applicable)

    Active Min OA Flow Stp DCV Disabled Used With: All Units when FreshAir Measurement VCM is installed

    Possible Values: HI (Keypad)SETPOINT Menu, GBAS 0 - 5 VDCModule, BAS Network GBAS 0-10

    VDC Module SETPOINT range: 0 toMax Unit Airflow

    Refer to the table in the SETPOINTsection, "Default Min OA FlowSETPOINT Screen" for max airflowSETPOINTs.

    1. Press the NEXT key until the following screen is displayed. (if applicable)

    Active Supply Air Pressure STP From

    HI (KEYPAD) SETPOINT MENU is 2.0 IWC

    Used With: Rooftop units and AirHandlers when IGV/VFD is installed.

    Possible Values:HI (Keypad)SETPOINT Menu, GBAS 0-5 VDCModule, GBAS 0-10 VDC Module,BAS/Network SETPOINT Range:

    0.7=5.1 IWC

    1. Press the NEXT key until the following screen is displayed.

    Active Supply Air Pressure SETPOINTS

    High Limit: 4.0 IWC Deadband: 0.5 IWC

    Used With: Rooftop units and AirHandlers with IGV/VFD installed orwith SAP present.

    Possible Values: High Limit: 1.2 -4.7 IWC Deadband: 0.1 - 2.0 IWC

    1. Press the NEXT key until the following screen is displayed.

  • 8/14/2019 ipak trblshoot

    44/150

    44 RT-SVP04F-EN

    System Operating Status

    Active Space Pressure SETPOINT From

    HI (KEYPAD) SETPOINT MENU is 0.08 IWC

    Used With: All Units when PowerExhaust with Statitrac is installed orReturn Fan with Statitrac installed

    Possible Values: HI (Keypad)SETPOINT Menu, GBAS 0-5 VDC

    Module, BAS/Network, GBAS 0-10VDC Module; SETPOINT range: -0.2to 0.30 IWC

    1. Press the NEXT key until the following screen is displayed. (if applicable)

    Active Space Pressure Deadband 0.10 IWC

    Used With: All Units when Power

    Exhaust with Statitrac is installed orReturn Fan with Statitrac Installed

    Possible Values: HI (KEYPAD)SETPOINT MENU, SETPOINT range:0.02 to 0.20 IWC

    1. Press the NEXT key until the following screen is displayed.

    End of Submenu (NEXT) to Enter SETUP Status

    1. Press the NEXT key to leave the submenu and show followingscreen.

    2. Press PREVIOUS to page back through the submenu.

    CONTROLLING SENSOR STATUS SUBMENU SCREENS

    Controlling Sensor Status Submenu

    Press ENTER to View Data in This Submenu

    Used With: All Units

    1. Pressing the NEXT key will bypass this section.

    Active Supply Air Temp Sensor Input From

    SUPPLY AIR is 50.0 F

    Used With: All Units

    Possible Values: RTM Supply AirTemp Input, BAS/Network1. Press the NEXT key until the following screen is displayed.

    Active Daytime WU Temp Sensor Input From

    RTM ZONE TEMP INPUT is 82.0 F

    Used With: All units when Gas,Electric, Hydronic or External Heat isinstalled and DWU is enabled

    Possible Values: RTM Zone TempInput, NSB Panel Temp Sensor

    Input, RTM Aux Temp Input, HeatModule Aux Temp Input, ECEMReturn Air Temp Input, BAS/NetworkSensor range: -40 F to 200 F

    1. Press the NEXT key until the following screen is displayed.(ifapplicable)

    Active Unocc Zone Temp Sensor Input From

    RTM ZONE TEMP INPUT is 75.0 F

    Used With: All Units

    Possible Values: RTM Zone TempInput, NSB Panel Temp SensorInput, RTM Aux Temp Input, HeatModule Aux Temp Input, ECEMReturn Air Temp Input, BAS/Network, Sensor range: -40 F to200 F

    1. Press the NEXT key until the following screen is displayed. (ifapplicable)

  • 8/14/2019 ipak trblshoot

    45/150

    RT-SVP04F-EN 45

    System Operating Status

    Active Morning WU Temp Sensor Input From

    RTM ZONE TEMP INPUT is 82.0 F

    Used With: All Units when Gas,Electric, Hydronic or External Heat isinstalled and Morning Warmup is

    enabled1. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Possible Values: RTM Zone TempInput, NSB Panel Temp SensorInput, RTM Aux Temp Input, HeatModule Aux Temp Input, ECEMReturn Air Temp Input, BAS/Network, Sensor range: -40 F to

    200 F

    Active Space Humidity Sensor Input From Used With:All units withHumidification option enabled.

    Possible Values: RTM Space,Humidity Input, BAS/Network, ECEM

    RA Humidity Input; Range 10-90%

    RTM space Humidity Input is 55%

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing the PREVIOUS key will scroll backwards to view the previously displayed screen.

    3. Press the + (Plus) key while viewing any screen to add that

    screen to the custom menu. Refer to the custom menu for the

    creation and maintenance of customized menus.

    4. Press the NEXT key until the following screen is displayed.

    (if applicable)

    Active Space CO2Sensor Input From Used With:All units with VCM

    installed.

    Possible Values: VCM SPACE CO2INPUT, BAS/Network; Range 50-

    2000 ppm

    VCM Space CO2Input is 600 ppm

    1. Pressing the NEXT key will scroll forward through the screens.

    2. Pressing th