iqecovav/.., iqeco39 controller installation instructions - mounting · 2015. 6. 15. ·...

8
IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 1 LT-IQECO-II-07 Rev A Installation Instructions - Mounting IQecoVAV/.., IQeco39 BACnet MS/TP Terminal Unit Controller Important: Retain these instructions These instructions shall be used by trained service personnel only If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. 1 Dimensions ins (mm) It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code). 6-29/64 (164) 5-3/64 (128) 5-7/16 (138) 2-1/4 (58) 6-17/64 (159) 7/16 (1 1) 8-5/16 (211) 10-5/16 (262) 6-27/32 (174) 3 INSTALLATION - MOUNTING 2 STORING CONTENTS 1 Unpacking ..................................................................... 1 2 Storing ........................................................................... 1 3 Installation - Mounting ...................................................1 1 UNPACKING IQecoVAV/.., IQeco39 Installation Instructions - Mounting (TG201088) IQecoVAV/.../PA/ only ! MS/TP Network This product should be connected to a BACnet MS/TP network. The network installation requirements are different from an IQL on its LONWORKS ® network. HO 2 5 %RH 95 %RH +50 °C (+122 °F) 0 °C (+32 °F) +60 °C (+140 °F) -40 °C (-40 °F) IQecoVAV/.. IQeco39

Upload: others

Post on 30-Jan-2021

3 views

Category:

Documents


0 download

TRANSCRIPT

  • IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 1LT-IQECO-II-07 Rev A

    Installation Instructions - Mounting

    IQecoVAV/.., IQeco39BACnet MS/TP Terminal Unit Controller

    Important: Retain these instructions

    These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

    1 Dimensions ins (mm)

    It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

    6-29/64 (164)

    5-3

    /64

    (1

    28

    )

    5-7

    /16

    (1

    38

    )

    2-1/4 (58)

    6-1

    7/6

    4 (

    15

    9)

    7/1

    6 (

    11

    )

    8-5/16 (211)

    10-5/16 (262)

    6-27/32 (174)

    3 InSTAllATIon - MoUnTIng

    2 SToRIng

    ConTenTS1 Unpacking ..................................................................... 12 Storing ........................................................................... 1

    3 Installation - Mounting ...................................................1

    1 UnPACkIng

    IQecoVAV/.., IQeco39 Installation Instructions - Mounting (TG201088)

    IQecoVAV/.../PA/ only

    !MS/TP networkThis product should be connected to a BACnet MS/TP network. The network installation requirements are different from an IQL on its LONWORKS ® network.

    H O2

    5 %RH 95 %RH+50 °C

    (+122 °F)0 °C

    (+32 °F)

    +60 °C(+140 °F)

    -40 °C(-40 °F)

    IQecoVAV/..

    IQeco39

  • IQecoVAV/.., IQeco39 Installation Instructions - Mounting

    2 IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 LT-IQECO-II-07 Rev A

    2 Requirements

    3a Change Actuator Position and/or Direction of Rotation If required, IQecoVAV/.../PA/only. Otherwise go to step 4

    3.1 Installation - Mounting (continued)

    DIN rail end stop

    H O2

    5 %RH 95 %RH

    Go to step 3b

    12

    The unit must installed in an enclosure or outside normal reach (e.g. within a plenum).

    The unit is UL rated as ‘UL916 listed open energy management equipment’.

    +50 °C(+122 °F)

    0 °C(+32 °F)

    +60 °C(+140 °F)

    -40 °C(-40 °F)

    IQecoVAV/..

    IQeco39

    Change Actuator Direction of Rotation ?

    YeS no go to step 3b

    Suitable for DIN rail or surface mounting

  • Installation Instructions - Mounting IQecoVAV/.., IQeco39

    IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 3 LT-IQECO-II-07 Rev A

    3b Change Actuator Position and/or Direction of Rotation (Change Actuator Position)

    3c Change Actuator Position and/or Direction of Rotation (Refi t Actuator Cover)

    3.1 Installation - Mounting (continued)

    Ensure cable is located in cut-out

    1

    2

    Ensure cable is not pinched

    1

    2

    Change Actuator Position ?

    YeS no, go to step 3c

    Go to step 3c

    Ensure cable is not pinched

  • IQecoVAV/.., IQeco39 Installation Instructions - Mounting

    4 IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 LT-IQECO-II-07 Rev A

    6 Mount on Damper Shaft (IQecoVAV/.../PA only)

    7 Set Damper limits (IQecoVAV/.../PA only)

    5 Attach large Barcode label To Panel

    4 Mounting

    8 mm spanner,torque setting:

    70.8 to 88.5 lb.in (8 to 10 Nm)

    Horizontal

    45º

    Note: If the damper stops are changed it may be necessary to change the VAV Damper driver full scale drive time. See IQecoVAV/.., IQeco39 Installation - Confi guring (TG201121)

    U clampDamper shaft (round or square)3/8” to 1/2” (10 mm to 13 mm) diameterMinimum shaft length 1-9/16” (39.68 mm)

    1

    2

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    LAN

    Serial No

    Strategy

    Serial No O/S

    LAN

    O/S

    either surface mount

    5 - 3/63”(128 mm)

    6 - 29/64” (164 mm)

    or DIN rail mount

    4 holes Ø 3/16”(4.6 mm)

    LAN

    Serial No

    Strategy

    Serial No O/S

    LAN

    O/S LAN

    Serial No

    Strategy

    Serial No O/S

    LAN

    O/S

    I QECO: Q3 B_ X7 3 0 8 0 0 3 1SERIAL No. IQECO Q3B_X73080031

    TREND IQecoLANNIDStrategy : : : : :

    O/S

    Serial No230 Vac ~24V 10V COM21 22 23 24 25 26 27 281 2 3 24 Vac 0V 10VAO COM1 2 3 54 6 74 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 LON29 30 31 32LONOKSRVPINC

    2 3LANNIDStrategy : : : : :

    O/S

    Serial No230 Vac ~24V 10V COM21 22 23 24 25 26 27 281 2 3 24 Vac 0V 10VAO COM1 2 3 54 6 74 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 1 2 3 4 5 LON29 30 31 32LONOKSRVPINC

    1 4

    3.1 Installation - Mounting (continued)

    8 mm spanner,torque setting: 70.8 to 88.5 lb.in (8 to 10 Nm)

  • Installation Instructions - Mounting IQecoVAV/.., IQeco39

    IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 5LT-IQECO-II-07 Rev A

    8 Connect Differential Pressure Sensor In8 9 Connect Power link to Terminal 3(If using OUT1 to OUT4)

    10 Connect Power

    11 Connect Triac outputs (OUT1, OUT2, OUT5*, OUT6* - *IQeco/39, IQecoVAV/P only)

    (IQecoVAV/.../PA/ or /P only)

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    4.75 mm (3/16”) ID

    IQeco/VAV/../P..

    LowHigh

    49 VA maximum power to terminal 3

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    IQeco

    Power LinkIN8

    Duct

    Ensure snug fit.Observe polarity

    Ensure correct polarity

    O

    I

    Do noT SWITCH on PoWeR

    24Vac

    24V

    2 1

    Panel/enclosure ground.Must connect to known earth/ground

    UL Listed, Class 2, 24 Vac transformer

    For UL rating the input power connections must be made using 18 AWG or larger wire rated at least 90 °C (194 °F).

    This equipment must be earthed (grounded), using its power supply connector (terminal 2).

    24 Vac ±15%, 50/60 Hz25 VA minimum (including power to actuator but with

    terminal 3 disconnected)97 VA maximum (48 VA to terminal 1 + 49 VA to terminal 3)

    A panel/enclosure clean earth (ground) consisting of a short (

  • IQecoVAV/.., IQeco39 Installation Instructions - Mounting

    6 IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014LT-IQECO-II-07 Rev A

    12 Connect to MS/TP Trunk

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    The network installation requirements are different from an IQL on its LONWORKS® network.

    3.1 Installation - Mounting (continued)

    IQ4NC

    12

    0 o

    hm

    s(n

    orm

    ally

    )

    Ground screen

    Cut backscreen

    scre

    en

    120 ohms (normally)

    +82 83

    0V V+

    120 ohms

    Ensure correctpolarity

    230 Vac

    MS / TP

    +34 33

    IQeco/VAV/.. /39

    24V

    2 1

    Ensure correctpolarity

    24Vac

    MS / TP

    +33 34

    IQeco/31, /35 /38

    Ensure correctpolarity

    24Vac

    +

    1 2 3

    0V

    1 2 3

    N L

    24 Vac

    230 Vac

    Either or

    ad

    ditio

    na

    lte

    rmin

    al

    ad

    ditio

    na

    lte

    rmin

    al

    Lay cable as bus topology (not loop or star).

    Ensure correct polarity. Ensure maximum number of devices described below is not exceeded.

    earthing: Connect all ground terminals and 24 Vac power supply neutrals to the panel/enclosure ground. Ensure normal safety earthing (grounding) practice.

    Cable specification/Maximum length: Use tinned copper, screened, twisted-pair cable with characteristic impedance between 100 and 130 ohms. Distributed capacitance between conductors shall be less than 100 pF per metre (30 pF per foot). Distributed capacitance between conductors and screen shall be less that 200 pF per metre (60 pF per foot). Foil or braided screens are acceptable. The maximum recommended length of an MS/TP segment is 1200 metres (4000 feet) with AWG 18 (0.82 mm2) conductor area) cable. There may be up to 3 repeaters between devices. The use of greater distances and/or different wire gauges shall comply with the electrical specifications of EIA-485. Details of recommended cable are given in the Trend TP Cable Data Sheet (TA200541).

    *Screen Each MS/TP segment must have a single point screen ground. Screen should be continuous. Do not ground the MS/TP screen using a controller terminal. Ground screen at one end and cut back at the other end. At connecting points, tie the screen through a terminal.

    Additional Terminal

    **Terminators: The bus must be terminated at each end with a resistor matched to the cable characteristic impedance (i.e. ±1%, ¼ Watt, range 100 to 130 ohms). If the IQ4NC is at one end of a 120 ohm cable, switch in its built-in terminator, otherwise switch it out and fit a resistor at that end of the cable; the other end must be terminated with a matching resistor.

    Maximum number of devices: There may be IQ4NC with up to 64 IQeco’s or other manufacturers’ devices on the MS/TP trunk. A separate limitation is that the MS/TP segment supports up to 32 ‘unit’ loads. IQeco, IQ4NC and IQ3/BINC present a ¼ BACnet ‘unit’ load; other manufacturers’ devices may have different ‘unit’ loads.

    Biassing The IQ4NC provides network biassing (470 ohms); a maximum of two devices on the network can provide network biassing.

    Failure to comply with these practices will result in significant impairment of the communication performance.

  • Installation Instructions - Mounting IQecoVAV/.., IQeco39

    IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014 7LT-IQECO-II-07 Rev A

    15 Connect Analogue outputs (OUT7, OUT8, OUT9*, OUT10* - *IQeco/39 only)

    14 Connect to RD-WMB Room Display(if required)

    13 Connect Inputs (IN1 to IN5, IN6*, IN7* - *IQeco/39 only)

    Ensure correct polarity

    18 AWG (0.8 mm2) 2 wire twisted screened cable should be used for wiring the inputs, with the screen connected to the panel/enclosure ground as shown for IN6 in the adjacent diagram. The far end of the screen should be unterminated.IQeco

    IQeco39 only

    Sensor

    CCCC

    2123 2225 24262728293032 31

    1

    24V III7 23456

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    VV V

    I I

    I I

    Voltage

    0 to 10 V

    Resistance -- Digital --

    Thermistor 10 kohmPotentiometer 1 to 11 kohm

    Fan Speed (TBTS/KEF)

    IN1 to IN7(IN6, IN7 IQeco/39 only)

    wetting current 300 μA

    Current 4 to 20 mA IN2 to IN5 only (IN5 IQeco39 only)

    External powered

    Loop powered

    The sensor type module used for the input channel (as set up in the strategy) sets up the input conditioning (no linking required).

    INn

    C (0 V)

    external power supply

    Panel/enclosure ground.

    Panel/enclosure ground.

    Panel/enclosure ground.

    auxiliary power output

    0 to 10 V at 10 mA maximum (load >1 kohm)

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    IQeco

    Load

    IQeco39 only

    13151618 14

    C

    17

    C

    78910

    18 AWG (0.8 mm2) 2 wire twisted screened cable should be used with the screen connected to the panel/enclosure ground. Connect the return to the central C terminal (e.g. 14 C, as shown for OUT7) not to an input common.

    Panel/enclosure ground.

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    WMB

    1920

    RD-WMB

    RD-WMB

    2 part connector with 2 screw terminals for 20 to 14 AWG (0.5 to 2.5 mm2) cross section area cable

    Use twisted pair, maximum length 60 m (200 ft)polarity independent

    3.1 Installation - Mounting (continued)

  • IQecoVAV/.., IQeco39 Installation Instructions - Mounting

    8 IQecoVAV/.., IQeco39 Installation Instructions- Mounting TG201088 Issue 4, 14-Jul-2014LT-IQECO-II-07 Rev A

    Please send any comments about this or any other Trend technical publication to [email protected]

    © 2014 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

    Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

    Trend Control Systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control Systems USA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

    Printed in USA

    16 Connect Relay outputs (OUT3, OUT4)

    17 Connect Auxiliary Power Output (if required)

    18 Configure IQeco

    Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste.Do not burn.

    Use 18 AWG (0.8 mm2) twisted pair cable

    L T - I Q E C O - I I - 0 7

    4 DISPoSAl

    polarity independent

    Normally open, 24 Vac, 0.5A.

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    0 V

    IQeco

    378C

    9

    24V4 3

    24 Vac

    0V

    OUTn

    CLoad

    Terminal 3 must be supplied with 24 Vac supply for OUT3, OUT4 to be used - see step (9) above..

    Arc suppression recommended

    Relay Output Arc Suppression Installation Instructions(TG200208)

    IQeco Installation Instructions - Configuration (TG201121)

    39

    ecoPOWER:MAX LOAD: 97 VACLASS 2 CIRCUITS ONLYUSE COPPER CONDUCTORS ONLYFOR INDOOR USE ONLYSUITABLE FOR PELNUM MOUNTING

    Use to power sensors.e.g. loop powered - see step (13) above

    This is a QR code readable by dedicated QR barcode readers and smartphones.

    Scan this code to access the Trend PNet website where you can download all the latest and legacy product publications. A PNet user name and password are required to access the site.

    24 Vdc ± 15% @ 100 mA maximum

    3.1 Installation - Mounting (continued)