ispe good practice guide - hvac

199

Click here to load reader

Upload: persacol

Post on 22-Nov-2015

4.149 views

Category:

Documents


357 download

TRANSCRIPT

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    1

    1

    2

    3

    4

    5

    6

    ISPE GOOD PRACTICE GUIDE 7

    8

    HVAC 9

    10

    11

    12

    DRAFT FOR REVIEW 13

    14

    15

    16

    17

    18

    19

    20

    21

    22

    23

    24

    25

    26

    27

    28

    29

    30

    31

    32

    33

    34

    35 36

    37

    38

    39

    2008 ISPE. ALL RIGHTS RESERVED. 40

    41

    42

    43

    44

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    2

    TABLE OF CONTENTS 45

    46

    1 INTRODUCTION ...................................................... 5 47 1.1 BACKGROUND .................................................... 5 48 1.2 SCOPE OF THIS GUIDE ........................................... 5 49 1.3 OBJECTIVES OF THIS GUIDE ...................................... 6 50 1.4 DEFINITIONS ................................................... 6 51 1.5 REFERENCES .................................................... 6 52

    2 FUNDAMENTALS OF HVAC .............................................. 9 53 2.1 INTRODUCTION .................................................. 9 54 2.2 WHAT IS HVAC? ................................................. 9 55 2.3 AIRFLOW FUNDAMENTALS ......................................... 13 56 2.4 PSYCHROMETRICS ............................................... 19 57 2.5 EQUIPMENT .................................................... 21 58 2.6 HVAC SYSTEM CONFIGURATION .................................... 23 59 2.7 HVAC CONTROLS AND MONITORING ................................. 39 60 2.8 SYSTEM ECONOMICS ............................................. 51 61 2.9 SUSTAINABILITY (TO BE WRITTEN LATER) ........................ 58 62

    3 THE DESIGN PROCESS ............................................... 59 63 3.1 INTRODUCTION ................................................. 59 64 3.2 DEVELOPING THE USER REQUIREMENTS SPECIFICATION (URS) ......... 61 65 3.3 HVAC SYSTEM RISK ASSESSMENT .................................. 69 66

    4 HVAC APPLICATIONS BY PROCESS AND CLASSIFICATION .................. 73 67 4.1 INTRODUCTION ................................................. 73 68 4.2 SYSTEM APPLICATIONS .......................................... 73 69 4.3 ROOM LEVEL EXAMPLES .......................................... 78 70 4.4 ACTIVE PHARMACEUTICAL INGREDIENTS (API) - (WET END) .......... 83 71 4.5 ACTIVE PHARMACEUTICAL INGREDIENTS (API) - (DRY END) .......... 84 72 4.6 BIOLOGICS .................................................... 85 73 4.7 ORAL SOLID DOSAGE (NON-POTENT COMPOUNDING) ................... 86 74 4.8 ORAL SOLID DOSAGE (POTENT COMPOUNDING) ....................... 89 75 4.9 ASEPTIC PROCESSING FACILITY .................................. 91 76 4.10 PACKAGING/LABELING ........................................... 94 77 4.11 LABS ......................................................... 95 78 4.12 SAMPLING/DISPENSING .......................................... 99 79 4.13 ADMINISTRATIVE AND GENERAL BUILDING ......................... 100 80 4.14 WAREHOUSE ................................................... 101 81 4.15 PROCESS EQUIPMENT CONSIDERATIONS ............................ 102 82

    5 DESIGN QUALIFICATION / DESIGN REVIEW (DQ/DR) .................... 106 83 5.1 DESIGN REVIEW/ DESIGN VERIFICATION/DESIGN QUALIFICATION ..... 106 84 5.2 INTRODUCTION ................................................ 108 85

    6 EQUIPMENT FUNCTION, INSTALLATION, AND OPERATION ................. 117 86 6.1 EQUIPMENT FUNCTION AND MANUFACTURE .......................... 117 87 6.2 EQUIPMENT INSTALLATION AND STARTUP .......................... 147 88 6.3 EQUIPMENT OPERATION AND MAINTENANCE ......................... 156 89

    7 VERIFICATION AND TESTING ........................................ 165 90 7.1 INTRODUCTION ................................................ 165 91 7.2 PHILOSOPHY .................................................. 165 92 7.3 PRINCIPLES .................................................. 166 93 7.4 REGULATORY EXPECTATIONS ..................................... 167 94

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    3

    7.5 KEY CONCEPTS OF VERIFICATION ................................ 167 95 7.6 DESIGN, SPECIFICATION, VERIFICATION, AND ACCEPTANCE PROCESS . 169 96 7.7 SUPPORTING PROCESSES ........................................ 170 97

    8 DOCUMENTATION REQUIREMENTS ...................................... 172 98 8.1 INTRODUCTION ................................................ 172 99 8.2 ENGINEERING DOCUMENT LIFECYCLE .............................. 172 100 8.3 DOCUMENTS FOR MAINTENANCE AND OPERATIONS (NON-GMP) .......... 173 101 8.4 MASTER/RECORD DOCUMENTS ..................................... 173 102 8.5 GMP HVAC DOCUMENTS .......................................... 174 103

    9 PSYCHROMETRICS .................................................. 176 104 9.1 DRY-BULB TEMPERATURE ........................................ 176 105 9.2 WET-BULB TEMPERATURE ........................................ 176 106 9.3 DEW-POINT TEMPERATURE ....................................... 177 107 9.4 BAROMETRIC OR TOTAL PRESSURE ................................ 179 108 9.5 SPECIFIC ENTHALPY ........................................... 179 109 9.6 SPECIFIC VOLUME ............................................. 180 110 9.7 EIGHT FUNDAMENTAL VECTORS ................................... 183 111

    10 COMMISSIONING AND QIUALIFICATION PROCESS ...................... 185 112 10.1 COMMISSIONING AND QUALIFICATION ............................. 185 113 10.2 IMPACT RELATIONSHIPS ........................................ 186 114 10.3 RISK ASSESSMENT MATRIX ...................................... 187 115

    11 MISCELLANEOUS HVAC INFORMATION ................................ 188 116 11.1 GLOSSARY OF TERMS ........................................... 188 117 11.2 EQUATIONS USED IN HVAC AND THEIR DERIVATION ................. 188 118

    12 REFERENCES .................................................... 195 119 12.1 SUMMARY OF USEFUL CLEANROOM EQUATIONS ....................... 195 120 12.2 PRESSURE CONTROL WHEN AIRLOCKS ARE NOT POSSIBLE ............. 196 121 12.3 HEPA FILTERS FOR HOT ZONES (DEPYROGENATION) ................. 196 122 12.4 USEFUL REFERENCE MATERIALS .................................. 196 123 12.5 HVAC EXAMPLES AND WORKBOOK (???) ............................ 196 124 12.6 EXAMPLE DOCUMENTS ........................................... 196 125

    126

    127

    128

    129

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    5

    1 INTRODUCTION 130 131

    1.1 BACKGROUND 132 133

    The heating, ventilating, and air conditioning (HVAC) system is one of 134

    the more critical systems affecting the ability of a pharmaceutical 135

    facility to meet its key objectives. HVAC systems which are properly 136

    designed, built, operated, and maintained can help ensure the quality 137

    of product manufactured in that facility, improve reliability, and 138

    reduce both first cost and ongoing operating costs of the facility. The 139

    design of HVAC systems for the pharmaceutical industry requires special 140

    considerations beyond those for most other industries, particularly in 141

    regards to cleanroom applications. 142

    143

    Each of the previously published ISPE Baseline Guides for facilities 144

    (Active Pharmaceutical Ingredients, Oral Solid Dosage, Sterile Products 145

    Manufacture, Biopharmaceuticals, etc.) have included some discussion of 146

    the considerations for HVAC systems for facilities of that type. This 147

    Good Practice Guide is intended to supplement those sections with more 148

    detailed information and recommended practices for implementation of 149

    HVAC systems in pharmaceutical facilities. 150

    151

    1.2 SCOPE OF THIS GUIDE 152 153

    The Guide provides supporting information and HVAC practices for 154

    facility types covered by Baseline Guides. 155

    156

    The Guide provides an overview of the basic principles of HVAC only to 157

    the extent required to facilitate a common understanding and consistent 158

    nomenclature. 159

    160

    This guide addresses HVAC requirements in the following areas of 161

    facility lifecycle. 162

    163

    Establishing User Requirements 164

    Design 165

    Construction 166

    Commissioning / Qualification 167

    Operation / Maintenance 168

    Redeployment for other use 169

    Decommissioning 170 171

    The guide does NOT serve as a handbook for HVAC design (e.g. it does 172

    not discuss the details of sizing and selection of equipment. It does 173

    go into boring detail on the physics of air and humidity.) 174

    175

    The guide clarifies HVAC issues critical to the Safety, Identity, 176

    Strength, Purity and Quality (SISPQ) for the production of bulk and 177

    finished pharmaceuticals and biopharmaceuticals, and it considers the 178

    requirements for HVAC control and monitoring systems. 179

    180

    This guide addresses how to implement the recommendations in the 181

    Baseline guides to meet FDA and EMEA regulatory expectations for HVAC 182

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    6

    design. 183

    184

    This guide references but does NOT reiterate the issues or content from 185

    the Baseline guides. The appropriate Baseline Guide should be consulted 186

    for regulatory expectations. 187

    188

    The guide discusses the impact of external conditions on HVAC design. 189

    190

    This guide attempts to give information in I/P and SI units. 191

    192

    The user of this guide should apply good engineering practice in 193

    assessing which of the recommended practices is most applicable to a 194

    situation. 195

    196

    1.3 OBJECTIVES OF THIS GUIDE 197 198

    Provide the Pharmaceutical Engineering Community with common language 199

    and understanding of critical HVAC issues. 200

    201

    Provide guidance on accepted industry practices to address these 202

    issues. 203

    204

    Provide a single common resource for HVAC information currently 205

    included in appendices of the various Baseline guides. 206

    207

    Target a global audience, with particular focus on US (FDA) and 208

    European (EMEA) regulated facilities. 209

    210

    1.4 DEFINITIONS 211 212

    This GPG uses terms as defined in the ISPE Glossary of Pharmaceutical 213

    Engineering Terminology and will not repeat these definitions here. 214

    Only new terms or terms specific to the content of this GPG are defined 215

    in the Glossary. 216

    217

    1.5 REFERENCES 218 219

    a. ISO Standards for Cleanrooms and Associated Controlled Environments 220

    221

    ISO 14644-1 Classification of air cleanliness 222

    ISO 14644-2 Specifications for testing and monitoring to prove 223 continued compliance with ISO 14644-1 224

    ISO 14644-3 Test methods 225

    ISO 14644-4 Design, construction and start-up 226

    ISO 14644-5 Operations 227

    ISO 14644-6 Vocabulary 228

    ISO 14644-7 Separative devices (clean air hoods, glove boxes, 229 isolators, and mini-environments) 230

    ISO 14644-8 Classification of airborne molecular contamination 231

    ISO 14698-1 Biocontamination control, Part 1: General principles and 232 methods 233

    ISO 14698-2 Biocontamination control Part 2: Evaluation and 234 interpretation of biocontamination data. 235

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    7

    236

    b. IEST Recommended Practices 237

    238

    RP-CC034.2- HEPA and ULPA Filter Leak Tests 239

    RP-CC006.3- Testing Cleanrooms 240

    RP-CC012.1- Considerations in Cleanroom Design 241 242

    c. ISPE Baseline Guides 243

    244

    Vol. 1- Active Pharmaceutical Ingredients 245

    Vol. 2- Oral Solid Dosage Forms 246

    Vol. 3- Sterile Manufacturing Facilities 247

    Vol. 4- Water and Steam Systems 248

    Vol. 5- Commissioning and Qualification 249

    Vol. 6- Biopharmaceuticals 250 251

    d. ASHRAE- specific ASHRAE documents which are used in this GPG: 252

    253

    ASHRAE standard 62.1 - Ventilation for Acceptable Indoor Air Quality 254

    ASHRAE standard 90.1 - Energy Standard for Buildings Except Low-Rise 255 Residential Buildings 256

    ASHRAE standard 110 - Method of Testing Performance of Laboratory 257 Fume Hoods 258

    ASHRAE Handbooks - Fundamentals; Applications; Systems & Equipment 259 260

    e. ASTM Standard E2500-07 - Standard Guide for Specification, Design, 261

    and Verification of Pharmaceutical and Biopharmaceutical Manufacturing 262

    Systems and Equipment 263

    264

    f. US FDA Guidance for Industry Sterile Drug Products Produced by 265

    Aseptic Processing- Current Good Manufacturing Practice (2004) 266

    267

    g. EudraLex Volume 4 EU Guidelines to Good Manufacturing Practice 268

    269

    Medicinal Products for Human and Veterinary Use 270

    Annex 1: Manufacture of Sterile Medicinal Products 271

    Annex 2: Manufacture of Biological Medicinal Products for Human Use 272 273

    h. The Good Automated Manufacturing Practice (GAMP) Guide for 274

    Validation of Automated Systems in Pharmaceutical Manufacture 275

    276

    i. WHO document on HVAC- proposed draft, does not apply to this 277

    document. 278

    279

    j. CFR Title 21 Food & Drugs 280

    281

    Part 11: Electronic records 282

    Part 210: Current good manufacturing practice in manufacturing, 283 processing, packing or holding of drugs; general 284

    Part 211: Current good manufacturing practice for finished 285 pharmaceuticals 286

    287

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    8

    k. FDA Guidance for Industry/ICH Guidelines 288

    289

    Q7A: Good manufacturing practice guidance for active pharmaceutical 290 ingredients 291

    Q8: Pharmaceutical Development 292

    Q9: Quality Risk Management 293

    Q10: Quality Systems 294 295

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    9

    2 FUNDAMENTALS OF HVAC 296 297

    2.1 INTRODUCTION 298 299

    Most people live in homes with equipment incorporated into the building 300

    to keep them comfortable. They have windows to allow natural 301

    ventilation and heating and cooling systems to maintain desired 302

    temperatures. 303

    304

    We have the same goal in our pharmaceutical manufacturing workplace 305

    to make people comfortable, but we also have the more exacting 306

    requirement to control the impact of the environment on the finished 307

    product (i.e., product SISPQ). 308

    309

    This guide introduces the fundamentals of the HVAC systems that control 310

    the GMP workplace environment. Only three room environment variables 311

    may have an effect on product and processes (at the critical 312

    locations): 313

    314

    Air temperature at the critical location may affect product or 315 product contact surfaces 316

    Relative humidity of the air at the critical location may affect 317 product moisture content, or may affect product contact surfaces 318

    (via corrosion, etc.) 319

    Airborne contamination at the critical location (may affect product 320 purity or product contact surfaces) 321

    322

    Some variables, such as local contaminants, depend on other HVAC 323

    variables such as room pressure, air changes, airflow volume, airflow 324

    direction and velocity, and air filter efficiency. 325

    326

    2.2 WHAT IS HVAC? 327 328

    HVAC (Heating, Ventilation and Air Conditioning) is the generic name 329

    given to a system that provides the conditioning of the environment 330

    through the control of Temperature, Relative Humidity, Air Movement and 331

    air quality - including fresh air, airborne particles, and vapors. 332

    HVAC systems can increase or decrease temperature, increase or reduce 333

    the moisture or humidity in the air, decrease the level of particulate 334

    or gaseous contaminants in the air. These abilities are employed for 335

    comfort and to protect people and product. 336

    337

    2.2.1 People Comfort 338 339

    The first role of HVAC systems is to make people comfortable. We notice 340

    the HVAC systems performance when we are uncomfortable, but what 341

    conditions are actually required to make people comfortable? 342

    343

    Four criteria are commonly considered for people comfort: 344

    345

    Temperature 346

    Humidity 347

    Air quality (contaminants, both particles and odors) 348

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    10

    Air movement (airflow direction and speed to control drafts) 349 350

    2.2.1.1 Temperature and Humidity 351

    352

    The following drawing shows two boxes which define "comfort" conditions 353

    (Temperature and Humidity) that Americans find comfortable in winter 354

    and summer (from the ASHRAE Handbook). This standard varies across the 355

    world - for example, in parts the tropics people prefer an office at 75 356

    degrees F (24 degrees C) to one at 72 F (22C). 357

    358

    It should also be noted that these are general guidelines, as many 359

    things affect these conditions apart from individual preferences - the 360

    type and consistency of work being performed, for example. 361

    362

    This is apparent in the office workplace, with the different levels of 363

    clothing people wear, some people dressed more heavily than others in 364

    order to be comfortable 365

    366

    367

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    11

    368

    Figure 2-1 Standard Effective Temperature and ASHRAE Comfort Zones 369

    courtesy of ______________________ 370

    371

    2.2.1.2 Air Movement 372

    373

    Some people prefer a light sensation of air movement and some prefer 374

    still air, so a typical design figure of 0.1 m/s (3 ft/sec) is used in 375

    an office environment. Greater air velocities are usually needed for 376

    product protection. 377

    378

    2.2.1.3 Air Quality 379

    380

    People need fresh air to dilute exhaled carbon dioxide and other 381

    environmental contaminants. The amount of fresh air required depends on 382

    the activity; the table below shows typical oxygen use for different 383

    levels of activity. 384

    385

    Level of exertion Oxygen consumed L/min

    Light work LT 0.5

    Moderate work 0.5 to 1.0

    Heavy work 1.0 to 1.5

    Very heavy work 1.5 to 2.0

    Extremely heavy work GT 2.0

    386

    Table2-1 Oxygen Consumption by activity Level 387

    388

    The amount of fresh air required to dilute environmental contaminants 389

    is a minimum of 15 to 20 cubic feet per minute (cfm) or 24 to 32 cubic 390

    meters per hour per person . 391

    392

    2.2.2 Product and Process Considerations 393 394

    Product may be sensitive to temperature and humidity and to airborne 395

    contamination - from outside sources or cross-contamination between 396

    products. Process operators may need protection from exposure to 397

    hazardous or potent materials 398

    399

    It is usually possible to find the products environmental 400

    requirements, as they will be listed in the NDA when they are 401

    considered critical. The impact of conditions outside these ranges 402

    will depend on the duration of exposure prolonged exposure time may 403

    reduce the efficacy of the product. 404

    405

    Control of airborne cross contamination and contamination are always 406

    major issues. These requirements are often interlinked with temperature 407

    and humidity consider the effect of temperature for example; 408

    409

    Comfortable people work more efficiently they are more 410

    productive, and make fewer mistakes. They also produce fewer 411

    environmental contaminants: A typical person will give off 100,000 412

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    12

    particles a minute doing relatively sedentary work (particles sized 413

    0.3 micron and larger a human hair is approximately 100 micron in 414

    diameter). A worker who is hot and uncomfortable may shed several 415

    million particles per minute in this size range, including more 416

    bacteria. 417

    418

    Environmental conditions inside a building can influence the product in 419

    other ways higher temperatures and humidity tend to increase 420

    microbial growth rates, particularly with regard to mold. 421

    422

    If building conditions are significantly different from those outside 423

    and the fabric of the building does not have sufficient integrity, 424

    condensation in interstitial spaces can occur and can lead to microbial 425

    contamination problems and deterioration of the building. 426

    427

    Operator protection also depends on air flow direction both within and 428

    between rooms. Airflow can entrain particles of product, product in 429

    other rooms, or other hazardous materials harmful to operators. Though 430

    differential pressure is commonly used as a control of contamination 431

    between two rooms, it is the airflow generated by the differential 432

    pressure that contains the product 433

    434

    2.2.3 How does the HVAC system control these parameters? 435 436

    2.2.3.1 Temperature and Humidity 437

    438

    The HVAC system controls the temperature and humidity in the room using 439

    the mechanism of supplying the room with air at a condition that, when 440

    mixed with the room air, will yield the desired temperature and 441

    humidity. 442

    443

    The heat gains and losses to and from the space are through the usual 444

    mechanisms of heat transfer - Radiant, conductive and convective heat 445

    transfer. These may be due to solar gain, external temperature outside 446

    the facility, and internal heat gains due to the process, equipment, 447

    people and lighting. 448

    449

    The changes in humidity are due to the process, people and the 450

    environment. Moisture migration into the controlled space from 451

    surrounding areas is governed by the difference in vapor pressure, as 452

    defined by Daltons law, and can sometimes migrate against an air 453

    pressure differential 454

    455

    2.2.3.2 Air velocity 456

    457

    In a working environment, air velocity is not as critical in terms of 458

    human comfort as it is in an office environment. Velocity is critical 459

    to proper mixing of air within the room and transport of airborne 460

    particulates. 461

    462

    2.2.3.3 Particulate/fume and vapor control 463

    464

    The control of the particulate levels in the room, and in some cases 465

    vapors/fumes, may be by dilution and displacement, controlling the 466

    particulate levels in the supply air through filtration, and vapor/fume 467

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    13

    level by the use of exhaust and replacement (makeup) fresh air where 468

    necessary. 469

    470

    2.2.4 What cant the HVAC System do? 471 472

    HVAC systems are not a substitute for good process, facilities and 473

    equipment design and good operating procedures. HVAC can not clean 474

    surfaces that are already contaminated, and as a practical matter, it 475

    cannot control processes that generate an excess of contaminants or 476

    compensate for improperly designed or maintained facilities. HVAC, 477

    while a common suspect area for investigation, is rarely the cause - or 478

    the solution - for persistent contamination problems. 479

    480

    2.3 AIRFLOW FUNDAMENTALS 481 482

    2.3.1 Introduction 483 484

    As was discussed in section 2.1, HVAC can contribute to the control of 485

    temperature, humidity, and particulates within a space. In order to 486

    understand what equipment is needed to achieve this at the HVAC system 487

    level, we must first define what the air is intended to do at the room 488

    level. 489

    490

    Both the quality (temperature, humidity, filtration) and quantity of 491

    air introduced into a room affect its ability to maintain environmental 492

    conditions. This explores the effects of physical layout (geometry), 493

    air velocity and air volume in assuring effective ventilation. 494

    495

    2.3.2 Ventilation Fundamentals 496 497

    Ventilation is the movement and replacement of air for the purpose of 498

    maintaining a desired environmental quality within a space. Ventilation 499

    is responsible for the transport of airborne particles, the movement of 500

    masses of hot or cold air, the removal of airborne contaminants (e.g., 501

    vapors and fumes) and the supply of fresh O2 rich air. 502

    503

    Although the layman may be conscious of the term air change rates 504

    (more properly called ventilation rate), successful pharmaceutical 505

    HVAC design can be attributed to proper filtration and attention to the 506

    physical geometry of airflow in a space. The layout of inlets and 507

    outlets with relation to the sources of contamination/heat and 508

    accommodation for expected obstructions are key to controlling 509

    contamination and yielding effective HVAC design. The relationship 510

    between these factors is expressed in the effective ventilation rate 511

    for a space. This measure expresses the efficiency of the HVAC system 512

    at removing contaminants expressed as a % of the theoretical 513

    performance of perfect dilution. When comparing the effective 514

    ventilation rates of various designs, it becomes clear that good 515

    layout and filtration can produce desired airborne particulate levels 516

    and recovery rates at lower than expected air change rates. 517

    518

    2.3.3 Contamination Control 519 520

    The primary factor that separates pharmaceutical HVAC from comfort HVAC 521

    is the need to control contamination. This stems from the need to 522

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    14

    assure the purity, identity and quality of the product (21CFR211). 523

    Pharmaceutical HVAC is one tool in preventing unwanted environmental 524

    contaminants from adversely affecting a product and to prevent products 525

    from contaminating one another. It can also assist in limiting operator 526

    exposure to potent pharmaceutical compounds, ingredients or reagent 527

    vapors. Contamination control is generally achieved by filtering the 528

    incoming air, to assure that it does not carry particulates, and then 529

    introducing the air to the work space at sufficient velocity and volume 530

    to transport unwanted particulate out of the work zone. The orientation 531

    of these airflows can aligned so as to protect product or personnel by 532

    sweeping across one or the other (or both) on its way from the supply 533

    terminal to the extract point. Local supply or extraction can also 534

    assist in contamination control by creating a local environment that 535

    excludes or removes particulate. 536

    537

    Pharmaceutical HVAC can help control contaminants within a space, but 538

    these facilities must be designed with several additional features that 539

    contribute to this mission of limiting the migration of contaminants. 540

    541

    2.3.4 Airlocks 542 543

    In order to minimize the amount of air that is needed to maintain 544

    particle transport velocities (typically over 100fpm times 21 square 545

    feet of open door area equals 2100 cfm) it is desirable that the doors 546

    of a contamination controlled space remain closed. One way to do this 547

    is to provide airlocks or ante rooms. These rooms control traffic 548

    into and out of a space through a series of interlocked doors to assure 549

    that a door to the space is always closed. 550

    551

    Airlocks serve other purposes as well: 552

    553

    they maintain some differential pressure between the two areas they 554 serve, such that the DP can not drop to zero 555

    they provide a location for gowning/de-gowning prior to 556 entering/exiting a classified space 557

    they provide a location for sanitizing / decontamination of incoming 558 or outgoing materials and equipment 559

    they can be designed with a small volume and high air change rate to 560 allow them to recover quickly and function to minimize the 561

    particulate introduced to a classified space by door openings. 562

    they provide can provide a high or low pressure buffer to control 563 the ingress and egress of contaminants. 564

    565

    2.3.5 Classified Space 566 567

    A key measurement of room environmental conditions for pharmaceutical 568

    operations is the concentration of total airborne particulate and/or 569

    microbial contamination within the space; this is referred to as the 570

    classification of the space. Several systems have been promulgated 571

    for the classification of space; however there is not consensus between 572

    international regulators on a single best standard for classification. 573

    To bridge the gap between the various standards, this guide provides 574

    the following reference to be used across facility types requiring air 575

    classification, (primarily facilities for sterile/aseptic manufacture 576

    and for controlled bioburden processing, such as bulk 577

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    15

    biopharmaceuticals). It should not be used for other facilities, such 578

    as bulk chemical intermediates or oral dosage finishing. See the 579

    appropriate Baseline Guide for specific air quality information. 580

    581

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    16

    582

    REFERENCE DESCRIPTION CLASSIFICATION

    ISPE STERILE BASELINE

    GUIDE

    Draft 2008

    ENVIRONMENTAL CLASSIFICATION GRADE 5 GRADE 7 GRADE 8 Controlled

    Not

    Classified

    with local

    monitoring

    Controlled

    Not

    Classified

    European Commission

    EU GMP, Annex 1,

    Volume lV,

    Manufacture of

    Sterile Medicinal

    Products (1997) also

    PIC/S GMP Annex 1

    2002

    Descriptive Grade A

    (Note1) B C D Not defined

    At

    Res

    t

    (No

    te

    2)

    Maximum no.

    particles

    permitted

    per m3 the

    stated size

    0.5 3 500 3 500 350 000 3 500 000 -

    5 1 1 2 000 20 000 -

    In

    Ope

    rat

    ion

    Maximum no.

    particles

    permitted

    per m3 the

    stated size

    0.5 3 500

    (Note

    3)

    350 000 3 500

    000

    Not stated -

    5 1 2 000 20 000 Not stated -

    Maximum permitted

    number of viable

    organisms cfu / m3

    < 1 < 10 < 100 < 200 -

    FDA, October 2004,

    Guidance for Industry

    Sterile Drug Products

    Produced by

    In

    Ope

    rat

    ion

    Maximum

    particl

    es

    permitt

    ed

    stated

    size

    no.

    the

    0.5 ISO 5

    Class

    100

    ISO 7

    (Class

    10 000)

    ISO 8

    (Class

    100

    000)

    - -

    583

    Table 2-2 Comparison of Classified Spaces 584

    585

    586

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    17

    587

    Pharmaceutical HVAC can help control contaminants within a space, but 588

    these facilities must be designed with several additional features that 589

    contribute to this mission of limiting the migration of contaminants. 590

    591

    2.3.6 Total Airflow Volume and Ventilation Rate 592 593

    Much has been made of the importance of air change rate (volume of 594

    air/hour room volume) or ventilation rate, the number of times in 595

    an hour that the air volume of a room is replaced. Little is said about 596

    the relationship between these rates and the classification of the 597

    space, recovery rates and the more important issue of total volume of 598

    ventilation. 599

    600

    When considering the design of classified space, designers will often 601

    first consider the requirement for 20 Air Changes/hour (AC/hr), 602

    expressed in the 1987 FDA Sterile Guide. In lieu of calculating the 603

    airflow required by the process, many will default to rules of thumb 604

    for ventilation rate by the class of space, typically in the ranges: 605

    606

    15-20 AC/hr for Controlled, Not Classified (CNC) spaces 607

    20-40 AC/hr for Grade 8 (EU Grade C) 608

    40-60 AC/hr for Grade 7 (EU Grade B) 609

    300-600 AC/hr for Grade 5 (EU Grade A) 610 611

    As seen below, these rules of thumb may be overkill, or may prove to be 612

    insufficient. The airborne particle levels depend more on a number of 613

    factors. 614

    615

    2.3.6.1 Air change or Air Flow? 616

    617

    These air change rates often drive decisions regarding room size and 618

    airflows, and can have significant cost implications, but do not 619

    relate directly to the particle count in the room. Air change rates are 620

    related to the rooms ability to recover from an upset, not the room 621

    classification as is commonly assumed. To explain this difference: 622

    623

    Assume a 1 cubic foot volume with a process inside it that generates 624

    10,000 particles per minute. If we purge the volume with 1 cubic foot 625

    per minute of clean air, the steady state (equilibrium) airborne 626

    particle level will be 10,000 particle per cubic foot (see the Appendix 627

    for equations). This 1 CFM creates an air change every minute, or 60 628

    air changes per hour. This value (60/hr) is often assumed to be more 629

    than enough to keep a space well below 10,000 particles per cubic foot 630

    (PCF). 631

    632

    Now put the same process into a 100 cubic foot volume and keep the 633

    airflow at 1 cfm, assuming good mixing inside the room. Now the room 634

    sees an air change every 100 minutes, or about 0.67 ac/hr. Yet, when we 635

    calculate the dilution, the equilibrium airborne particle counts are 636

    still 10,000 PCF (10,000 particles per minute divided by 1 cubic foot 637

    per minute = 100 particles per cubic foot). If we would supply 1 air 638

    change per hour (100 CFM) of clean air, the room airborne counts drop 639

    to 100 PCF !!! So its not air changes that determine airborne particle 640

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    18

    counts, but three factors (referring to the Appendix): 641

    642

    1. Particles generated inside the space 643 2. Quantity of dilution air supplied to the space (cubic volume 644

    per time) 645

    3. Cleanliness of dilution air (assumed to be negligible in 646 pharma due to HEPA filtration) 647

    648

    As is demonstrated elsewhere, a room receiving only 1 air change per 649

    hour will take hours to recover from in-use to at-rest conditions. 650

    With clean air supply of 20 air changes per hour, a 100-fold recovery 651

    in particle levels can happen in less than 20 minutes (see the ISPE 652

    Sterile Baseline Guide). So when it comes to RECOVERY, air changes ARE 653

    important, 20/hr often being the minimum for classified spaces. 654

    655

    Although the layman is conscious of the importance of air change rate 656

    (more properly called ventilation rate) successful pharmaceutical 657

    HVAC design can be attributed to proper filtration and attention to the 658

    physical geometry of airflow in a space. 659

    660

    2.3.6.2 Impact of UDF (UFH) hoods on air change rates 661

    662

    Later sections will discuss mixed flow rooms with clean air supplied 663

    at the ceiling through terminal filters as well as clean air being 664

    introduced to the room from Unidirectional Flow Hoods (UFH or UDF, once 665

    called Laminar Flow) operating inside the room. Since air leaving the 666

    space served by the hood is often orders of magnitude cleaner than the 667

    room it leaks into, the relatively clean hood air serves to dilute 668

    airborne particles in the room, along with the supply air from the 669

    HVAC. In many respects the added flow from the hood not only reduces 670

    airborne particles in its path, but can also accelerate the recovery 671

    time of the room from in-use to at-rest conditions. The entire flow 672

    from the hood will likely not be available to add into air change 673

    calculations, however, due to: 674

    675

    Short circuiting of the hood air back to the hood inlet. Only areas 676 near the airflow path will see the added dilution. 677

    Hood air is not as clean as HVAC supply air. Even though the hood 678 might be rated as Grade 5 (class 100) the air leaving the work space 679

    has collected additional contaminants from equipment and people 680

    outside the critical zone. 681

    682

    2.3.7 Room Distribution and Quality of incoming air 683 684

    The layout of inlets and outlets with relation to the sources of 685

    contamination and accommodation for expected obstructions are key to 686

    controlling contamination and yielding effective HVAC design. The 687

    relationship between these factors is expressed in the effective 688

    ventilation rate for a space. This measure recognizes that good layout 689

    and filtration can produce desired airborne particulate levels and 690

    recovery rates at lower than expected air change rates. 691

    692

    Taking the example above, good air mixing (dilution) and faster 693

    recovery can be accomplished in a room where clean air supply is 694

    distributed over a high percentage of the ceiling and not just from one 695

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    19

    air outlet. Although its not necessary to create a laminar flow 696

    ceiling, numerous air outlets equally spaced with equal flow rates can 697

    create a plug flow for faster recovery (often less than 10 minutes 698

    for 20 ac/hr) and also prevent hot spots of high particle count in 699

    the room. 700

    701

    2.3.8 Airflow Direction and Pressurization 702 703

    Since constructing a space that is totally airtight is not practical is 704

    normal construction, other means must be provided to assure that 705

    particulate can be prevented from migrating into or out of a space. 706

    Assuring that air is always flowing in the desired direction through 707

    the cracks in building construction (door gaps, wall penetrations, 708

    conduits, etc.) can influence contamination through the transport of 709

    airborne particulates. A velocity of 1-200 FPM will contain light 710

    powders and bioburden 711

    712

    One method to control this direction of airflow is by controlling the 713

    relative pressurization of adjacent spaces or the Differential Pressure 714

    (DP) between the spaces. 715

    716

    A simplified method (neglecting the orifice coefficient for the 717

    opening) to calculate the expected velocity of airflow from a given 718

    pressure is: 719

    720

    V = 4005 (sqrt VP) or VP =(V/4005) (where V is velocity in ft/min, 721

    VP is pressure difference in inches w.g., A is area of the opening 722

    in square feet, Q is airflow in CFM) 723

    724

    We can breakdown velocity as being volume divided by area, giving 725

    V = Q/A, or 726

    727

    VP = (CFM/4005A) 2 728

    729

    Assuming room DP converts fully to Velocity Pressure thru an 730

    opening (a conservative assumption), calculating the opening area, 731

    such as the crack area around a closed door between rooms, allows 732

    calculation of the airflow (CFM) required to create a pressure, or 733

    the velocity that results from a known DP. 734

    735

    For A=1 sq foot (0.1 sq.M) opening, 890 CFM (about 1500 CuM/hr or 736

    0.45 CuM/sec) will create 0.05" w.g. (12.5 Pa) differential 737

    pressure (V = Q/A = 890 FPM = 4.5 M/s) 738

    739

    2.4 PSYCHROMETRICS 740 741

    2.4.1 Introduction 742 743

    Psychrometrics is the science that involves the properties of moist air 744

    (a mixture of dry air and water vapor) and the process in which the 745

    temperature and/or the water vapor content of the mixture are changed. 746

    Psychrometrics psychro means moisture and metrics means to 747

    measure. A psychrometric chart is used to identify conditions of air 748

    and to illustrate the process of achieving the desired state of the 749

    controlled space. An in-depth knowledge of psychrometrics is impossible 750

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    20

    to impart in this document; the reader is referred to other sources 751

    such as the ASHRAE Fundamentals Handbook. 752

    753

    2.4.2 Basic Properties of Air 754 755

    2.4.2.1 Dry air is comprised of 78.1% nitrogen, 21% oxygen, and has 756

    trace amounts of ten additional elements totaling 0.9%. The air around 757

    us is a mixture of dry air and water vapor. When this moist air 758

    reaches a level at which it can not hold any more moisture, it is said 759

    to be, saturated. The colder the air, the less moisture which can be 760

    held in the air while warmer air can hold larger quantities of moisture 761

    in the air. 762

    763

    2.4.2.2 The moisture in dry air (its specific humidity) is measured in 764

    grains of moisture per pound of air (7,000 grains equal 1 pound). Air 765

    at 75F and 60% RH has a specific humidity of 78 grains of water per 766

    pound (7000 grains) of dry air. Therefore, one pound of this air 767

    contains 77 grains of water and 6923 grains of dry air. 768

    769

    2.4.2.3 A psychrometric chart provides an overview of thermodynamic 770

    properties of air-water mixtures, and shows the relationships of air at 771

    different conditions. If any two properties of the air mixture are 772

    known, the chart allows an engineer to determine all its other 773

    properties. Air-water vapor mixtures have interrelated psychrometric 774

    properties that can be plotted on a psychrometric chart. (See Appendix 775

    for psychrometric chart discussion). 776

    777

    2.4.2.4 Sensible heat causes a change in the temperature of a 778

    substance. Sensible heat can be sensed or felt and quantified by 779

    measurement with a dry bulb thermometer. Addition or removal of 780

    sensible heat will cause the measured temperature to rise or fall. 781

    Sensible heat shows on the psychrometric chart as a horizontal line; 782

    there is no resulting change in the amount of water vapor in the air. 783

    784

    2.4.2.5 Latent Heat comes from the Latin word meaning hidden. 785

    Changes in latent heat are neither sensed or felt; however they will 786

    cause a change of state in the substance. Latent heat is the heat 787

    required to evaporate the moisture which the air contains. 788

    789

    For example, if sufficient latent heat is added to water in the liquid 790

    state, it will change state into a vapor or steam. The change of state 791

    from a liquid to steam is called the latent heat of vaporization and 792

    from a steam to a liquid is called the latent heat of condensation. 793

    The change of state from a liquid to a solid is called the latent heat 794

    of fusion and from a solid to liquid the latent heat of melting. 795

    Latent heat appears on the psychrometric chart as a vertical line. 796

    797

    2.4.3 Psychrometric Properties of Air 798 799

    See the Appendix for a discussion of the terms used in Psychrometrics 800

    and for an explanation of the Psychrometric Chart. 801

    802

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    21

    Dry-bulb temperature tDB Specific enthalpy h

    Wet-bulb temperature tWB Specific volume v

    Dew-point temperature tDP Humidity ratio W

    Relative humidity RH Water vapor pressure p WV

    Barometric pressure PBAR

    Measurable Psychrometric Properties Calculable Psychrometric Properties

    803 Table 2-3 Psychrometric Terminology 804

    805

    2.5 EQUIPMENT 806 807

    2.5.1 Introduction 808 809

    Each piece of HVAC equipment helps contribute to sustaining the user 810

    requirements for room environmental conditions. HVAC equipment serving 811

    GMP areas are intended to work in conjunction with associated controls 812

    and sequences of operation systems to: 813

    814

    Maintain room temperature 815

    Maintain room pressurization and differential pressure cascades 816

    Provide make up air for ventilation and room pressurization 817

    Condition the air stream to remove and/or add moisture content of 818 the air 819

    Minimize airborne contamination to the condition space 820

    Provide required air change rates to maintain room cleanliness 821 classification when required 822

    823

    The following major components of an HVAC system for GMP spaces are 824

    discussed in more depth in Chapter 6. 825

    826

    2.5.2 Air Handling Unit (Ahu) 827 828

    An equipment package that includes a fan or blower, heating and/or 829

    cooling coils, air filtration, etc. for providing heating, ventilation, 830

    and air conditioning (HVAC) to a building. 831

    832

    2.5.3 Fan 833 834

    An electrically driven air moving device used to supply, return or 835

    exhaust/extract air to or from a room through ductwork to generate air 836

    in sufficient amounts to provide ventilation, heating, cooling or to 837

    overcome air pressure losses. 838

    839

    2.5.4 Fume Exhaust/Extraction System 840 841

    A system made up of ductwork, fans and possibly filters that discharges 842

    unwanted air outside into the atmosphere to a safe distance from 843

    buildings and people. 844

    845

    2.5.5 Heating Coil 846 847

    A heat transfer device consisting of a coil of piping which increases 848

    the sensible heat into an air stream, using steam or hot water or 849

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    22

    glycol as the heating medium. And electric air-heating element can also 850

    be called a heating coil. 851

    852

    2.5.6 Cooling Coil 853 854

    A heat transfer device consisting of a coil of piping, which reduces 855

    the sensible heat and possibly latent heat (via condensation of water 856

    vapor) from the airstream using chilled liquid or refrigeration as the 857

    cooling medium. 858

    859

    2.5.7 Humidifier 860 861

    A device to increase the humidity within a controlled space by means of 862

    the discharge of water vapor into the supply air stream or directly 863

    into the room. 864

    865

    2.5.8 Dehumidifier 866 867

    A special device that removes water vapor from the air to reduce 868

    humidity. 869

    870

    2.5.9 Air Filtration 871 872

    Devices to remove particulate material from an airstream by means of 873

    various media types. 874

    875

    2.5.10 Ductwork 876 877

    A network of air conduits distributed throughout a building, connected 878

    to a fan to supply, return or exhaust/extract air to or from zones in a 879

    building. 880

    881

    2.5.11 Damper And Louver 882 883

    2.5.11.1 Found in ductwork, a damper consists of a movable plate(or 884

    numerous plates), plunger, or bladder that opens and closes to 885

    regulate airflow. Dampers are used to regulate airflow to certain 886

    rooms. 887

    888

    2.5.11.2 A louver is an assembly of sloping vanes intended to permit 889

    air to pass through and to inhibit transfer of water droplets from 890

    outdoors into air systems. A louver may also be found in return air 891

    ductwork at room interfaces. 892

    893

    2.5.12 Diffuser And Register 894 895

    Air distribution outlet or grille designed to introduce air to a space 896

    using direct airflow in desired patterns. Air diffusers are usually 897

    located to distribute the air as uniformly as possible through out a 898

    space. 899

    900

    2.5.13 Ultraviolet (UV) Light 901 902

    A UV light uses precise ultraviolet light wavelength to destroy 903

    microorganisms. 904

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    23

    905

    Equipment

    Heating

    Cooling

    Humidification

    Dehumidification

    Room

    Static

    Pressure

    Airflow

    Air Quality

    Air Handler X X X X X X

    Fan X X

    Fume Exhaust/Extract

    Systems X X

    Heating Coil X

    Cooling Coil X X

    Air Filter X

    Humidifier X

    Dehumidifier X

    Ductwork X X

    Damper & Louver X X

    Diffuser & Register X

    UV Light X

    906

    TABLE 2-4 System components and their primary function relating to 907

    environmental parameters 908

    909

    2.6 HVAC SYSTEM CONFIGURATION 910 911

    2.6.1 Introduction 912 913

    This section gives a brief overview of the key factors to consider, the 914

    options available to an HVAC system designer, and the factors 915

    influencing the decision to choose a particular system type. 916

    917

    This section should be read in conjunction with section 4 HVAC 918

    APPLICATIONS BY PROCESS AND CLASSIFICATION. 919

    920

    One question to answer is how many Air Handling Units should be used? 921

    922

    It is common practice to divide a manufacturing area into zones, and 923

    use a separate Air Handling Unit per zone a zone in general Building 924

    Services design would be an area with similar heat gains and losses, a 925

    similar approach is used within the pharmaceutical industry and is 926

    usually considered as an area with one type of manufacturing process or 927

    area classification, e.g. a tablet compression suite or all Grade 7 928

    areas, as the area requirements will be similar. Other factors that are 929

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    24

    considered when dividing a facility into zones include: 930

    931

    Use of multiple units improves reliability of the area it would be 932 unusual for all of the units to fail. 933

    The use of multiple smaller units might make air balancing easier 934

    The use of multiple smaller units means that the main distribution 935 ducts are smaller, making then easier to route in small ceiling 936

    voids. 937

    It is easier to make modifications to parts of the facility in 938 future and upgrade a small unit than change a large single unit 939

    Use of multiple units allows for easier separation of areas within a 940 multi-product concurrent manufacturing plant. 941

    942

    The decisions regarding AHU system zoning are very important as a 943

    factor in subsequent facility commissioning, qualification and related 944

    documentation. 945

    946

    2.6.2 Basic System Types 947 948

    There are three basic categories of HVAC system; 949

    950

    2.6.2.1 Once through - uses treated outside air to provide the design 951

    internal conditions, this air is then extracted from the space and 952

    discarded. 953

    954

    Air Handler Unit

    (AHU)

    Room

    Outdoor

    air

    Supply air

    Exhaust Infiltration

    Exfiltration 955

    956

    Figure 2-2 Once-through HVAC 957

    958

    Advantages of this system: 959

    960

    This system provides an abundance of O2 rich fresh air to dilute 961 contaminants 962

    The system can handle hazardous materials, though the extracted air 963

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    25

    may need treatment before it is discarded. 964

    Lower risk of cross contamination of products from another room via 965 HVAC 966

    Exhaust fan may be located remote from the AHU making duct routing 967 simpler 968

    As there are less concerns about the ductwork noise in the extract 969 ductwork, it can usually be sized for a high velocity, making it 970

    easier to route as high velocity = smaller diameter 971

    972

    Disadvantages of this system: 973

    974

    More expensive to operate than an equivalent recirculating system, 975 especially when cooling and heating. 976

    Filter loading very high = frequent replacement 977

    Potential need for exhaust air treatment (scrubbers, dust 978 collectors, filters) 979

    Room conditions more difficult to maintain 980 981

    2.6.2.2 Recirculating systems - This category is much more common the 982

    room supply air is made up of a percentage of treated outside air mixed 983

    with some of the air extracted from the space. A percentage of the air 984

    is either discarded or lost through leakage to adjacent areas, due to 985

    local area pressurization. 986

    987

    Air Handler Unit

    (AHU)

    Room

    Makeup

    (Fresh)

    air

    Return air

    Supply air

    Exfiltration

    Infiltration

    Possible extract

    988 989

    Figure 2-3 Recirculated HVAC 990

    991

    Advantages of this system: 992

    993

    Usually less air filter loading = lower filter maintenance and lower 994 cost opportunity for higher grade air filtration 995

    Lower energy cost than once through 996

    Less challenge to HVAC means that it is simpler to obtain better 997

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    26

    control of parameters (T, RH, etc) 998

    999

    Disadvantages of this system: 1000

    1001

    Return air ductwork routing to air handler may complicate above 1002 ceiling 1003

    Chance of cross contamination via HVAC = Requires adequate supply 1004 air filtration (and sometimes return air filtration to prevent 1005

    contamination of the air handler) 1006

    Chance of recirculation of odors and vapors and of inadequate fresh 1007 air supply 1008

    1009

    2.6.2.3 Exhaust (Extract) system sometimes a stand-alone system that 1010

    removes airborne contaminants, either solid particles or gasses/vapors. 1011

    It may be interlinked to a once-through or recirculated air supply 1012

    system. Used alone, the extract/exhaust system will create a negative 1013

    differential pressure in the room or enclosure it serves 1014

    1015

    "Space" with airborne contaminants

    Space may be a room, a glovebox or an exhaust hood

    Fan

    Air cleanerStack

    (follow 1.3x

    rule of thumb

    if "foul air"see ASHRAE)

    Ductwork

    Infiltration

    duct leakageExfiltration

    duct leakage

    1016 1017

    Figure 2-4 Exhaust System 1018

    1019

    Advantages of this system: 1020

    1021

    Simple to operate. Makeup air is pulled from surrounding spaces. 1022 1023

    Disadvantages of this system: 1024

    1025

    If used to capture large quantities of contaminants, such as from 1026 open processes, a large energy cost will be associated with 1027

    conditioned air being thrown away (see once-through system above). 1028

    1029

    2.6.2.1 Use of Air Handling Units in parallel or series 1030

    1031

    It is possible to put units in series, for example if a higher air 1032

    pressure is required to offset the pressure drop through HEPA filters 1033

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    27

    in one area served by an HVAC system. 1034

    1035

    The use of parallel units is common practice where large areas are 1036

    being conditioned, for example warehouses and large research 1037

    laboratories, where this approach may make it possible to maintain 1038

    acceptable conditions in the area should one unit fail. When 1039

    configuring units in parallel, care must be taken to assure that the 1040

    fans can be isolated and started independently. Automatic isolation 1041

    dampers and variable fan drives assist in managing these factors. 1042

    1043

    2.6.2.2 Configurations and combinations 1044

    1045

    The basic components and concepts outlined above can be assembled in an 1046

    infinite variety of ways. Shown below are a few examples of design 1047

    concepts commonly used. 1048

    1049

    (Note: Add some basic block diagram schematics to illustrate these 1050

    combinations.) 1051

    1052

    2.6.3 Air Handling Unit Configurations 1053 1054

    There are two basic types of AHU configuration blow through or draw 1055

    through. The term describes the relationship of the fan to the coils in 1056

    the air handling unit. The two approaches have distinctive 1057

    characteristics; 1058

    1059

    2.6.3.1 Blow through units 1060

    1061

    Air is drawn into the unit, typically through a set of pre-filters used 1062

    to reduce the dirt load on the (usually more expensive) final filters, 1063

    and to prevent build up of dirt onto the heating and cooling coils, 1064

    which would quickly reduce their efficiency. 1065

    1066

    One advantage of this type of unit is that it allows the AHU discharge 1067

    temperature to be at the cooling coil discharge air temperature, 1068

    because the fan heat is removed in the cooling coil. This is 1069

    particularly useful when heat loads are particularly high and supply 1070

    air temperature must be as cold as possible. It is not advisable to 1071

    follow a blow through unit immediately with a set of HEPA filters 1072

    unless special precautions are included to prevent moisture carryover 1073

    from the cooling coil. Another advantage is that if the drain trap on 1074

    the cooling coil runs dry, then air will blow out through the trap 1075

    wasting a small amount of treated air. 1076

    1077

    The disadvantage - the unit typically needs to be longer to allow a 1078

    diffuser to be installed after the fan to ensure that the airflow is 1079

    spread over the entire coil area, and not concentrated on the middle, 1080

    which would cause a drop in system performance. 1081

    1082

    2.6.3.2 Draw through units 1083

    1084

    These units are typically arranged with the pre-filters and coils 1085

    before the fan. The advantage of this is that the unit is often 1086

    smaller, and the motor and fan provide a small amount of reheat 1087

    (usually 1-2 degrees F) to the air coming off the cooling coil. This 1088

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    28

    lowers the RH of the air and prevents the problems with wetting final 1089

    AHU HEPA filter banks. One precaution with draw through units is that 1090

    if the drain trap is dry, then untreated air can be drawn into the unit 1091

    through the trap, with only the final filter to protect the conditioned 1092

    environment. The design must include provisions for maintaining a 1093

    wetted drain trap, which can be several inches in height. 1094

    1095

    2.6.3.3 Air Handling Unit Design variations 1096

    1097

    A design variation worth considering is the use of a face and bypass 1098

    damper the concept is shown below a portion of the air passing 1099

    through the AHU is redirected through a treatment stage, with the 1100

    volume altered to vary the condition of the resulting output air. This 1101

    is a useful concept to use to gain improved accuracy, particularly if 1102

    the treatment process is not easily controllable e.g. chemical 1103

    desiccant dehumidification. 1104

    1105

    Dehumidifier

    _

    1106 1107

    Figure 2-5 Face and bypass control with a packaged dehumidifier and 1108

    cooling coil (-) 1109

    1110

    A similar concept is often employed in the first mixing box of the AHU 1111

    when enthalpy control is used in all cases careful sizing of the 1112

    dampers, to ensure adequate velocity for control, is necessary to 1113

    obtain proper operation of these systems, maintaining constant system 1114

    volume as the proportions of the air streams are varied. 1115

    1116

    2.6.3.4 Air Handling Unit Components 1117

    1118

    Numerous design options are possible within the 2 basic types. Here 1119

    will establish a lexicon of design components, or modules, that can be 1120

    assembled into an AHU design and discuss the motivations that drive the 1121

    selection of each. To illustrate the possible options, the following 1122

    demonstration uses a draw-through, Recirculating AHU: 1123

    1124

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    29

    Mixing Box HumidifierDehumidifier Reheating Coil

    Supply Fan

    Energy

    Recovery

    Coil

    1125 1126

    Figure 2-6 Air Handler Unit Components 1127

    1128

    Return Fan 1129

    1130

    Most recirculating air systems will utilize a return fan. This fan 1131

    allows return pressure and flow to be managed independently from the 1132

    supply. This is particularly important if the downstream system has 1133

    volume control boxes on both the supply and return. It also allows the 1134

    return air to be diverted to exhaust when outside air conditions are 1135

    closer to desired discharge conditions than return air. This function 1136

    is referred to as an economizer and is generally employed in offices 1137

    or other spaces that are not pressure controlled. 1138

    1139

    Mixing Box 1140

    1141

    This pieced of equipment is also common in recirculating air systems. 1142

    The return air can be directed to exhaust or to recirculate, it is then 1143

    mixed with outside air for pressurization and/or ventilation. The 1144

    resulting air stream is referred to as mixed air. In very cold 1145

    environments the mixed air may be subjected to a turbulence inducing 1146

    device to assure thorough mixing and avoid stratification. 1147

    1148

    Prefilter or Prefilter and Intermediate Filter 1149

    1150

    Filters are typically provided upstream of coils in an air handler to 1151

    protect the coils from fouling with dirt or debris. The system 1152

    typically employs a low efficiency dust stop (MERV 7) filter followed 1153

    by a medium or high efficiency intermediate filter (MERV 7-14). 1154

    1155

    Energy Recovery Coil 1156

    1157

    Once through air systems, or other systems with high amounts of exhaust 1158

    may employ an energy recovery coil to return a portion of the energy 1159

    employed in conditioning the exhausted air to the incoming air. These 1160

    coils are typically upstream of all other coils and may be placed 1161

    upstream of the filters if used to melt snow in cold climates. These 1162

    systems may also employ a bypass damper to decrease pressure drop 1163

    across the coil when energy recovery is not advantageous. 1164

    1165

    Preheat Coil 1166

    1167

    Once through air systems, or other systems with high amounts of outside 1168

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    30

    air in cold climates may employ a preheat coil to condition the 1169

    incoming or mixed air. These coils are always upstream of cooling 1170

    coils, to protect them from freezing and may be placed upstream of the 1171

    filters if used to melt snow in cold climates. These coils do not 1172

    typically impose a large pressure drop, so a bypass damper is not 1173

    common. 1174

    1175

    Humidifier 1176

    1177

    Once through air systems, or other systems with high amounts of outside 1178

    air in cold climates may employ a humidifier to inject water vapor to 1179

    condition the incoming or mixed air. These devices are typically 1180

    downstream of the heating coil and may even be mounted in ductwork 1181

    where turbulence and high velocity promote absorption of water vapor. 1182

    When employed in an AHU, mounting upstream of cooling coils provides a 1183

    natural baffle to prevent carryover of liquid water droplets. 1184

    1185

    Cooling Coil 1186

    1187

    Cooling to maintain environmental conditions is common, if not always 1188

    required in Pharmaceutical applications. These coils can eliminate both 1189

    sensible and latent heat and can be upstream or downstream of the fan. 1190

    If latent cooling is expected drainage of these coils is a key design 1191

    issue and mist eliminators may be employed to eliminate carryover of 1192

    liquid water droplets that condense on the coil. These coils do impose 1193

    a large pressure drop so a bypass damper can be employed, but can pose 1194

    a risk of unconditioned air leakage and non-attainment of humidity 1195

    goals. 1196

    1197

    Dehumidifier 1198

    1199

    Dehumidifiers employ a chemical desiccant to remove moisture from the 1200

    supply air stream when humidity below 30-40% is required. The 1201

    dehumidifier is often located downstream of the cooling coil as they 1202

    work most efficiently when airstream relative humidity is high (but 1203

    within desired limits). However care must be taken to assure that 1204

    excessive relative humidity or liquid water droplets do not damage the 1205

    dehumidifier. The choice of desiccant may vary, depending on the 1206

    application but all desiccants are regenerated using heat; therefore, 1207

    air leaving the dehumidifier is both dryer and hotter than upon 1208

    entering. 1209

    1210

    Recool Coil 1211

    1212

    These coils are only commonly installed downstream of dehumidifiers to 1213

    eliminate sensible heat from the supply air. They are also employed 1214

    downstream of cooling coils to provide additional latent heat removal. 1215

    In this second application they operate below chilled water temperature 1216

    and are typically filled with refrigerant or a low temperature brine of 1217

    water and glycol (ethylene or propylene). If latent cooling is expected 1218

    drainage of these coils is a key design issue and mist eliminators may 1219

    be employed to eliminate carryover of liquid water droplets that 1220

    condense on the coil. These coils do not typically impose a large 1221

    pressure drop so a bypass damper would be unusual. 1222

    1223

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    31

    Reheat Coil 1224

    1225

    Systems that require over-cooling to achieve humidity control (in lieu 1226

    of dehumidification) may also employ a preheat coil to condition the 1227

    air leaving the cooling coil. These coils are always downstream of 1228

    cooling coils, to increase the discharge temperature of the air handler 1229

    and avoid condensation in the ductwork or overcooling of the space. 1230

    1231

    Supply Fan 1232

    1233

    All air systems will utilize a supply fan. This fan provides the motive 1234

    force for distribution of air throughout the air handling system. 1235

    1236

    Final Filter 1237

    1238

    Filters may be provided as the last treatment step in an air handler. 1239

    These filters provide assurance of air quality (with reference to 1240

    particulate) downstream of all air handling operations and are 1241

    particularly valuable in protecting terminal filters from fouling with 1242

    dirt or debris and in providing filtration for classified spaces. This 1243

    is of particular interest in systems that employ fan drive belts which 1244

    shed particulate into the airstream. Systems typically employs a high 1245

    efficiency filter in this location (MER V 14+). 1246

    1247

    2.6.4 AIRLOCK STRATEGIES 1248 1249

    2.6.4.1 PRESSURIZATION 1250

    1251

    Airlocks are usually interposed between areas if airflow between the 1252

    spaces needs to be controlled when they are entered or exited. 1253

    Airlocks may also serve as material transfer / decontamination rooms, 1254

    and gown or degown rooms. Three types of airlock pressure arrangements 1255

    are indicated below: 1256

    1257

    Airlock

    "Cascade" "Sink"

    AirlockAirlock

    "Bubble" 1258

    1259

    Figure 2-7 Airlock configurations 1260

    1261

    The cascade pressurization scheme should be used when there are area 1262

    cleanliness classification requirements but no containment issues, or 1263

    where there are containment issues but no cleanliness classification 1264

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    32

    requirements. (i.e., cascade outward from the room for aseptic 1265

    operations, but cascade into the room for hazardous compounds.) Doors 1266

    are usually interlocked to allow only one to be open at a time. The 1267

    normal differential from one air class to the next (ACROSS the airlock) 1268

    is 10-15 Pa (0.04 to 0.06 w.g.). The pressure INSIDE the airlock is 1269

    somewhere between the two classes, depending on which door is open. It 1270

    is not necessary to have 10-15 Pa between a room and its airlock (see 1271

    Not required in the drawing below). 1272

    1273

    If there are requirements for both area cleanliness classification and 1274

    product containment, then the use of pressure sinks and bubbles may be 1275

    necessary. Pressure bubbles are usually used for clean operations 1276

    (i.e., such as gowning or material entry airlock) and pressure sinks 1277

    are usually used for dirty operations (i.e., de-gowning material 1278

    decontamination/exit airlock). Normal design pressure differential 1279

    between classifications should be 0.06 w.g. (15 Pa) with the doors 1280

    closed. Pressure differential will drop momentarily while one door is 1281

    opened, but will not drop to zero (as it would with no airlock or if 1282

    all airlock doors were opened). In no case should pressure differential 1283

    reverse. 1284

    1285

    For unclassified areas the minimum suggested pressure differential is 1286

    0.02 w.g. (5 Pa), being the minimum reliably detectable by current 1287

    pressure sensor technologies. 1288

    1289

    The pressure differential is measured across the airlock, not across 1290

    each door. 1291

    1292

    Airlock Airlock

    0.06" w.g.

    Acceptable Not Required

    0.06" w.g. 0.06" w.g.

    "Cascade" Pressure Relationships 1293

    1294

    Figure 2-8 Example of Cascade Pressure Relationships 1295

    1296

    When using the bubble pressurization scheme, the normal design 1297

    pressure target, with doors closed, between classifications should be 1298

    0.06 w.g. (15 Pa). There may be different pressure drops across each 1299

    door due to building tolerances, or adjacent room conditions, this is 1300

    not considered a problem. If protecting non-sterile processing (areas 1301

    not classified) a lower pressure is acceptable, but should be 1302

    measurable. The pressure of the very clean airlock bubble is usually 1303

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    33

    designed to be about 0.02 to 0.03 in. w.g (about 5-8 Pa) above the 1304

    higher of the two room pressures. 1305

    1306

    The positive pressure airlock provides a robust means of segregating 1307

    areas using positive airflow. 1308

    1309

    Bubble

    Airlock

    @ 0.09" w.g.

    "Bubble" Pressure Relationships

    0.09" w.g. 0.03" w.g.

    Unclassified Space

    @ 0" w.g.

    Clean-Contained Space

    @ 0.06" w.g.

    0.06" w.g. across GMP boundary

    1310 1311

    Figure 2-9 Example of Bubble pressure relationships 1312

    1313

    Similarly, with the sink pressurization scheme, the normal design 1314

    pressure between classifications should be 0.04 to 0.06 w.g. (10-15 1315

    Pa) with doors closed. As with the bubble there may be different 1316

    pressure drops across each door. The pressure of the contaminated 1317

    airlock sink is usually designed to be about 0.02 to 0.03 in. w.g (5-1318

    8 Pa) below the lesser of the two room pressures. 1319

    1320

    Bubble

    Airlock

    @ (-) 0.03" w.g.

    "Sink" Pressure Relationships

    0.03" w.g. 0.09" w.g.

    Unclassified Space

    @ 0" w.g.

    Clean-Contained Space

    @ 0.06" w.g.

    0.06" w.g. across GMP boundary

    1321 1322

    Figure 2-10 Pressure sink relationships 1323

    1324

    It is often necessary to have pressure differentials at boundaries 1325

    within the same air class area for operational reasons. The minimum 1326

    operational differential between areas of the same classification 1327

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    34

    (where required) is suggested to be 0.02 w.g. (5 Pa), with a design 1328

    target of 0.04 (10Pa) suggested. It is also sometimes necessary to 1329

    have directional air flows for operational reasons without a measurable 1330

    pressure differential, such as may be found in non-classified areas, 1331

    such as oral dosage manufacture. 1332

    1333

    Pressure may be maintained across doors between air classes when no 1334

    airlocks are present. However, without the added protection provided by 1335

    the airlock, significant airflow volumes and pressure actuated dampers 1336

    are required. (See the Appendix) This scheme should be adopted only 1337

    when airlocks are not possible. 1338

    1339

    The airflow leakage rate should be calculated for each room. This 1340

    calculation must be based on the design pressure differential 1341

    established in the project documents and not on some rule of thumb 1342

    method, e.g., percentage of supply air. Door seals are the primary 1343

    path of room air leakage. Therefore, doors and doorframes are crucial 1344

    components of the facility construction, as more leakage air must be 1345

    designed into the system for doors with poor seals. The HVAC design 1346

    engineer should consult with the facility architect to assure 1347

    specifications are adequate for pressurization requirements. Door 1348

    frames may include continuous seals which would reduce leakage required 1349

    to maintain the desired pressure, as well as provide isolation in case 1350

    of airflow failure. Doors may be provided with a provision for 1351

    operable floor sweeps which drop down as the door closes, but these may 1352

    present cleaning problems. Where double doors are used in the 1353

    facility, gasketed astragals are required. Door grilles should be 1354

    avoided unless part of a pressure scheme without airlocks (as discussed 1355

    in the Appendix). Figure 14, Chapter 27 of the 2005 ASHRAE Handbook- 1356

    Fundamentals should be used in calculating the air leakage rate of 1357

    doors. Common practice is to design for a 0.10 average crack between 1358

    the door and frame on sides, top, and bottom. Note that corrections 1359

    are to be applied for design pressure differentials using the formula 1360

    contained in Figure 14. A similar leakage calculation is discussed in 1361

    the article, Airlocks for Biopharmaceutical Plants, del Valle, 1362

    Pharmaceutical Engineering , Volume 21, Number 2, March/April 2001 1363

    1364

    Material transfer openings are another key room air leakage path. To 1365

    calculate leakage through these and other fixed openings use the 1366

    formula, 1367

    1368

    Q = A x 4005sqrt (VP) (Sqrt = square root) 1369

    1370

    Q = airflow (CFM) 1371

    1372

    A = area of opening (sq. ft.) 1373

    1374

    VP = velocity pressure the velocity pressure at the opening (in. w.g.) 1375

    is roughly the same as the differential pressure across the opening, 1376

    (or the, room differential pressure), 1377

    1378

    This method provides a conservative leakage number. In most cases, a 1379

    slightly smaller leakage airflow will produce the desired pressure 1380

    differential for a given leakage path. Because of this, during 1381

    commissioning there may be more return air leaving the room than 1382

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    35

    designed, so return air dampers should have some extra capacity. 1383

    1384

    In some cases the calculated room leakage may exceed the minimum air 1385

    change rate for small rooms such as airlocks. In these instances the 1386

    total supply air to the space must match the calculated leakage. 1387

    However, provisions should be made in the design for some return air 1388

    from the space in case the actual leakage is less than calculated. A 1389

    good rule-of-thumb is to size the return for half the supply air flow 1390

    into the room. In applying this approach, care should be taken in 1391

    sizing any volume control (damper or CV box) on the return air side to 1392

    ensure that the actual flow rate is with the operable range of the 1393

    control device. 1394

    1395

    For this reason it is a good engineering practice to put a tighter 1396

    specification on the supply air volume, being more critical to maintain 1397

    the room conditions, and a larger design range on the return, which 1398

    will be whatever value is needed to maintain desired differential 1399

    pressures. 1400

    1401

    Two methods of measurement are commonly applied to monitor room 1402

    pressure relationships; room-to-room and common reference point. While 1403

    both have been used successfully, the preferred is the common reference 1404

    point method in order to minimize compounded error. Here, one port of 1405

    the differential pressure transmitter (usually, but not always, the 1406

    High side) is piped to the room being monitored and the other side 1407

    (usually, but not always, the Low side) is piped to a common 1408

    reference in the interstitial space. 1409

    1410

    PDTH L

    PDTH L

    Interstitial Space- common reference

    Space A Space B

    PDTH L

    PDTH L

    Space A Space B Space C

    Room-to-Room Monitoring Common Reference Monitoring 1411

    1412

    Figure 2-11 Differential Pressure Sensor Locations 1413

    1414

    The common reference point should not be outdoors, as the effect of 1415

    wind direction may give unstable readings. Where room to room 1416

    monitoring is used it is a good practice to confirm through the system 1417

    balancing that net airflow into the facility is greater than the 1418

    extract/exhaust. 1419

    1420

    All signals are sent to the control system where differentials are 1421

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    36

    calculated by means of an algorithm. In the event that the reference 1422

    (interstitial) space is partitioned by fire walls or other means, it 1423

    may be necessary to provide multiple common reference points by 1424

    building zone. In this case the pressure relationship across a 1425

    zone will need to be room-to-room or the use of two differential 1426

    pressure transmitters, one to each reference point, will be required. 1427

    1428

    For information on monitoring system see section 2.7 Control and 1429

    monitoring. 1430

    1431

    2.6.5 Ventilation/supply strategies 1432 1433

    2.6.5.1 Room Air Distribution: 1434

    1435

    There are two basic types of room air distribution: dilution and 1436

    displacement air distribution. 1437

    1438

    In a dilution design, room air is mixed continuously with supply air to 1439

    help achieve uniform air temperatures within the space. In areas where 1440

    temperature uniformity is the only factor, aspirating-type diffusers 1441

    are used to allow turbulent mixing of room air with supply air. From a 1442

    particulates perspective, dilution also mixes less clean room air 1443

    with the clean supply air. Aspirating-type diffusers are not acceptable 1444

    in any of the clean classified rooms. Even though non-aspirating 1445

    diffusers do not eliminate turbulent air patterns in the room, using 1446

    non-aspirating diffusers in clean rooms reduces the mixing effect. The 1447

    particulate level in the room can be reduced with dilution by 1448

    increasing the air-change rate of clean air supply. Dilution 1449

    distribution with non-aspirating diffusers (typically perforated face 1450

    plate over the terminal HEPA media) is acceptable to clean classified 1451

    areas up to ISPE-7. 1452

    1453

    In a displacement design, room particulates are displaced by clean 1454

    terminal HEPA filtered unidirectional air. This design requires 1455

    continuous HEPA coverage at the ceiling and properly sized and located 1456

    low level return or exhaust grills. ISPE-Grade 5 should use 1457

    displacement air distribution (typically a unidirectional flow hood 1458

    UFH). 1459

    1460

    2.6.5.2 Room Air Distribution options 1461

    1462

    Conventional air distribution techniques are generally acceptable for 1463

    administrative, warehouse, and unclassified spaces. Large warehouse 1464

    spaces, however, may see hot and cold spots with poor air distribution. 1465

    GMP spaces and cleanrooms require more stringent methods. Supply air 1466

    should be introduced at the ceiling level and return/exhaust air should 1467

    be extracted near the floor. The use of non-aspirating diffusers on 1468

    the face on terminal HEPA filters may improve airflow patterns. 1469

    1470

    Within mixed airflow rooms, airflow patterns should be from clean side 1471

    of the space to the less clean. For example, within a space that 1472

    contains an ISO 5 micro-environment/zone with an ISO 7 background, 1473

    airflow should always be from the cleaner zone into the less clean 1474

    background area. 1475

    1476

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    37

    Mixed Airflow GMP Space

    ISO Class 5 ISO Class 7

    1477 1478

    Figure 2-12 Mixed Airflow Space 1479

    1480

    Some process operations, i.e., centrifugation, are inherently particle 1481

    generating. Airflow patterns within the spaces that contain these 1482

    processes should take this into account by locating returns/exhausts at 1483

    floor level near the particle generating operation. 1484

    1485

    Airlocks and gown rooms are usually divided, often by a physical line 1486

    on the floor, into clean and dirty zones in accordance with the flow 1487

    of personnel, material, and equipment. Within such spaces, the air 1488

    pattern should from the clean to the dirty side of the airlock. 1489

    Therefore, HEPA supplies should be located on the clean side and low 1490

    wall returns should be located on the opposite side of the room. 1491

    1492

    Low wall returns should be located no more than 12 above the floor. 1493

    Returns should be generously sized with a maximum grille face velocity 1494

    of no more that 400 FPM. Ductwork should be sized for a maximum 1495

    pressure drop or 0.1 per 100 or a maximum velocity of 850 FPM, 1496

    whichever is more restrictive. The heel of the connecting elbow should 1497

    have a minimum 6 radius to facilitate cleaning. The elbow and 1498

    connecting ductwork, up to an elevation of 5 feet above the floor, 1499

    should be Type 304 or 304L stainless steel. 1500

    1501

  • ISPE GOOD PRACTICE GUIDE HVAC

    DRAFT FOR REVIEW JULY 2008

    38

    6" Radius

    1'-

    0" m

    ax

    imu

    m

    Typical Low Wall Return

    1502 1503

    Figure 2-13 Typical Low Wall Return 1504

    1505

    Return air ducts located in stud wall spaces need not be insulated 1506

    within the walls. Insulation shall terminate at the top of the wall. 1507

    The mechanical engineer should consult with the facility Architect to 1508

    assure that, where needed, wall cavities are adequate to contain low 1509

    wall returns. 1510

    1511

    2.6.6 EXTRACT (EXHAUST AND / OR RETURN) STRATEGIES 1512 1513

    Why we use low level or high level extract, the area affected by an 1514

    extract point do we want to cover dust extract systems at all here?? 1515