  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    1/45

    Oleh:

    Gunawan Muhammad

    2209106042

    AN ALISA GANGGUAN PADA ELECTRIC ARC FURN ACE

    (EAF) AKIBAT ARUS IN RUSH TRANSFORM ATOR &

    RESON AN SI FILTER HARM ONISA PABRIK PELEBURAN

    BAJA PT. ISPATINDO

    Dosen Pembimbing:

    1. Prof. Ir. Ontoseno Penangsang, M.Sc, Ph.D.

    2.Heri Suryoatmojo ST, MT, Ph.D.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    2/45

    Teori Penunjang2

    Pendahuluan1

    Sistem Kelistrikan3

    Simulasi dan Analisis4

    Penutup5

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    3/45

    Latar belakang Bebanarc furnace adalahkomponenpentingpadaperusahaan

    peleburanbajaPT. Ispat Indo disisi lain bebantersebutmenimbulkanefekharmonisayang cukupbesar.

    Pengoperasian periodik pada beban arc furnace menyebabkantimbulnya arus inrush dan arus harmonisa ke 2 yang tinggi padasaluran.

    Arus inrush dan arus harmonisa yang tinggi dapat merusakperalatan listrik, mengganggu kordinasi proteksi danmengganggu kualitas daya pada saluran listrik dengan beban arcfurnace

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    4/45

    Tujuan Membuktikan akibat dari operasi beban yang on-off secara

    periodik dapat menyebabkan timbulnya arus inrush dan harmonisayang tinggi antara beban arc furnace dan transformator utama.

    Menekan terjadinya resonansi paralel antara filter harmonisadengan impedansi saluran

    Menjaga kualitas daya pada sistem saat terjadi gangguan

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    5/45

    Batasan Masalah1. Sistemkelistrikanyang dipakaidalamtugasakhir ini adalah

    sistemkelistrikanPT. IspatIndo dari sumbersampai bagianArcFurnace.

    2. Perangkat lunak yang digunakan yaitu ETAP 7.00 untuk analisisstudi aliran daya dan simulasinya.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    6/45

    Teori Penunjang2

    Pendahuluan1

    Sistem Kelistrikan3

    Simulasi dan Analisis4

    Penutup5

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    7/45

    Inrush current Pada saat transformator dihubungkan terhadap suatu sumber

    tegangan (energize) akan mengalir arus yang cukup besar denganperiode waktu yang sangat singkat sampai tercapai kondisi steadystate. Arus awal ini disebut sebagai arus inrush dan besarnya dapatmencapai 8 sampai 30 kali arus nominal. Arus inrush ini perlu

    mendapat perhatian khusus karena pengaruhnya dapatmengganggu pengoperasian pengaman, tergantung keadaan awalsaat transformator tersebut dihubungkan.

    Faktor-faktor yang mempengaruhi besar dan lamanya arus inrushini antara lain adalah magnitude tegangan suplay saat energize, flux

    sisa pada inti trafo dan impedansi sumber dan impedansi sistem.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    8/45

    Inrush current

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    9/45

    Harmonisa

    fn= n f

    o

    fo =frekuensidasarfn

    = frekuensi harmonisake-nn = 1,2,3

    Merupakansuatufenomenayang timbul akibatpenggunaanbeban-bebanlistriknonlinier.

    Dalam sistem tenaga listrik, definisi harmonisa dapat dijelaskan sebagaigelombang terdistorsi secara periodik pada keadaansteady stateyangdisebabkan oleh interaksi antara bentuk gelombang sinus sistem pada

    frekuensi fundamental dengan komponen gelombang lain yangmerupakan frekuensi kelipatan interger dari frekuensi fundamentalsumber

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    10/45

    Besaran Harmonisa

    Ukuran distorsi harmonisa. Distorsi Harmonisa Total (Total Harmonics Distortion, THD)

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    11/45

    Standard HarmonisaArus(IEEE Std. 519-1992) untuklevel tegangan69 kV dandibawahnya

    Isc/ IL h

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    12/45

    Standard HarmonisaTegangan(IEEE Std. 519-1992)

    Bus Voltage at PCCIndividual Voltage

    Distortion (%)

    THD

    (%)

    69 kVand below 3,0 5,0

    69,001 kVthrough 161 kV 1,5 2,5

    161,001 kVand above 1,0 1,5

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    13/45

    Filter pasif Filter pasif tersusun dari induktansi, kapasitansi, dan resistansi.

    Filter pasif ini mempunyai beberapa bentuk, berdasarkan susunanrangkaian komponen-komponen penyusunnya. Secaraumumfilterpasifdapatdibedakandalamtigajenis:

    Filter denganpenalaantunggal (Single Tuned Shunt Filter).

    Filter denganpenalaanganda(Double Tuned Filter).

    High Pass Damp Filter Type.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    14/45

    Resonansi

    Paralel

    Resonansi paralel akanmenghasilkanimpedansi yang tinggi. Sehinggajikafrekuensi harmonisasamadenganfrekuensi resonansi paralel, makaakanterjadi teganganyang tinggipadaterminal kapasitor.

    Seri

    Resonansi seri akan mengakibatkanimpedansi menjadi sangat kecilsehingga arus yang tinggi dapatmengalir ke kapasitor.

    rf

    Z

    f

    rf

    Z

    f

    Gambar Kurva impedansi terhadap frekuensi saat terjadiresonansi paralel.

    Gambar Kurva impedansi terhadap frekuensi saat terjadi resonansi seri.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    15/45

    Sistem Kelistrikan3

    Simulasi dan Analisis4

    Penutup5

    Pendahuluan1

    Teori Penunjang2

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    16/45

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    17/45

    Sigle Line yang Dianalisa

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    18/45

    Simulasi dan Analisis4

    Penutup5

    Pendahuluan1

    Teori Penunjang2

    Sistem Kelistrikan3

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    19/45

    Analisa aliran dayaBus To Bus Load Flow

    ID ID MW Mvar Amp % PF

    ABB Panel

    (Subs.)

    Near Furnace 50883 10265 909.1 98.0

    Bus88 -57183 -1641 1001.9 100

    MainBus(PLN)

    - - - -

    Bus14 Near Furnace -50803 -31485 50107.

    2 85.0

    Bus88

    Bus147 6.849 4.622 433.9 82.9

    MainBus(PLN)

    -6.849 2.571 384.2 -93.6

    ABB Panel(Subs.)

    - - - -

    Bus147 Bus88 -6.828 -4.232 17142.

    5 85.0

    MainBus(PLN)

    Yard 34.565 9217 137.7 96.6

    ABB Panel(Subs.)

    64096 -0.929 246.7 -100

    Near Furnace

    Bus14 68.497 48.754 1472.9 81.5

    ABB Panel

    (Subs.)

    -

    68.497

    -

    24.819 1276.4 94.0

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    20/45

    Simulasi dan analisis (fenomena arus inrush)

    Arus inrush diakibatkan switcing pada beban secara terus menerus, pengukuranarus pada saluran dari trafo utama dan beban didapat hasil :

    Arus

    harmonisa

    1 2 3 4 5 7 11 13

    Trafo 65 100% 58.32% 61.69% 9% 2.89% 1.27% 0.00076 % 0.01%

    Beban Arc

    furnace100% 43.40 % 12.17% 9.6% 7.8% 2.88% 8.35% 6.53%

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    21/45

    Simulasi harmonisa

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    22/45

    Evaluasi gangguan arus harmonisa

    Bus Voltage Distortion To Bus Current Distortion

    IDFund. RMS ASUM THD

    IDFund. RMS ASUM THD

    kV % % % Amp Amp Amp %

    ABB Panel

    (Subs.) 33.000 104.20 157.93 30.06

    Bus 93 249. 81 265. 88 428. 52 36. 44

    Bus 98 1131.23 2157.12 3837. 41 162.36

    Bus 100 300.43 2136.86 2468. 52 704.20

    Near

    Furnace908.11 4007.24 5796. 13 429.79

    Bus14 0.690 109.96 177.96 46. 53 Near

    Furnace50052.2

    3192342.40 289717.50 371. 04

    Bus88 11.000 104.23 157.32 29. 60

    Bus147 433.90 445.84 627.77 23. 63

    Main

    Bus(PLN)384.15 384.15 384.15 0

    Bus147 0.270 103.99 153.30 27. 74 Bus88 7643.09 25040.29 24. 36 251.13

    Main

    Bus(PLN) 150.000 104.24 157.23 29. 43

    Yard 153.49 270.68 49. 27 344.04

    Bus 98276.88 276.88

    00. 50

    Near

    Furnace 33.000 104.20 157.93 30. 06

    Bus14 4028.59 6083.89 361. 99 290. 93

    ABB Panel

    (Subs.)4007.24 5796.13 429. 79 167. 47

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    23/45

    Koordinasi kondisi normal saluran dengan filter harmonisake 2

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    24/45

    Koordinasi kondisi dengan gangguan arus harmonisasaluran dengan filter harmonisa ke 2

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    25/45

    Contoh perhitungan

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    26/45

    ID ETAP Relay Brands CT Rasio Invers Current Definite Current

    I> t> I>> t>>

    OCR-14 50 MG Sepam 1000 2000/5 0.91 0.1 3.01

    `

    0.2

    OCR-66 50 MG Sepam 1000 2000/5 0.91 0.4 3.4 0.5

    OCR-65 50 MG Sepam 1000 600/5 1 0.4 2.6 0.7

    OCR-207 50 MG Sepam 1000 250/5 2.4 0.6 6.6 0.9

    OCR-208 50 MG Sepam 1000 250/5 2.4 0.6 6.6 0.9

    ID ETAP Relay Brands CT Rasio Invers Current Definite Current

    I> t> I>> t>>

    OCR-14 50 MG Sepam 1000 2000/5 1.15 0.1 3.01 0.2

    OCR-66 50 MG Sepam 1000 2000/5 1.15 0.4 3.4 0.5

    OCR-65 50 MG Sepam 1000 600/5 1 0.4 2.6 0.7

    OCR-207 50 MG Sepam 1000 250/5 2.4 0.6 6.6 0.9

    OCR-208 50 MG Sepam 1000 250/5 2.4 0.6 6.6 0.9

    Setting Normal

    Setting dengan

    gangguanharmonisa

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    27/45

    Fenomena Resonansi Paralel

    Respon frekuensi pada bus ABB 33 kV pada saat timbul arus inrush dan arus harmonisa

    ke 2

    Pada frekuensi 410 Hz terjadi impedansi sistemyang tinggi bernilai 16,11 ohm

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    28/45

    Solusi terhadap perbaikan kualitas daya

    Solusi untuk meredam arus harmonisa ke 2 yang tinggi yang

    bersumber pada transformator 65 dan beban arc furnace ,dalam hal iniakan dipertimbangkan untuk desain filter pasif yang dipasang pada busnear furnace 33 kV, bus ABB panel dan bus 169 agar arus harmonisa ke2 yang ada pada single line diagram masih berada pada batas toleransi.Standar yang digunakan adalah standar IEEE 519 (1992) (keterangan

    pada bab 2). Oleh karena itu dilakukan pencatatan THD tegangan danTHD arus sebelum pemasangan filter dan pemasangan filter

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    29/45

    Perencanaan pemasangan 3 buah filter harmonisa ke 2

    1

    23

    Desain ulang danpemasangan filter pasifdengan penalaan padaorde 2 di pasang padagambar panah disampingyang berguna untukmeredam arus harmonisa

    ke 2 yang timbul padasaat beban arc furnacebekerja

    Besar nilai R,L, C

    yang terpasang:R = 0.5 ohmXL = 14.97 mH

    C = 56,46FQc= 19317 KVAR

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    30/45

    Contoh perhitungan filter pasif

    Tegangan line-line : 33 kVFrekuensi Sudut :

    LebarBand,Q = 30 50, dipilih Q = 30

    Bus ABB Panel (cos = 83%)

    S = 50786 kW +10244 kVAR

    Untukpemasangankapasitor dipakai (cos 96%)

    Jadi, untuk Q1 = 50786tan ( arc cos0.84 )

    = 34128.39 kvar

    UntukQ2 = 50786 tan ( arc cos0.96 )

    = 14812.56kvar

    Maka Qc yang dipilih untuk memperbaiki adalahsebesar

    Qc = Q1 Q2

    = 34128.3914812.56

    =19316,8 kvar

    = 19317kvar ( dibulatkan )

    Cosmenjadi 96%

    BUS ABB PanelSingle Tuned orde2

    kVar yang digunakan (Q-c) sebesar 19317 kVar

    Rating kapasitor (dalam Farad) komponen filter adalah,

    Frekuensi Tuning = 97 Hz ( toleransi dari tuning 100Hz)

    Maka komponen reaktor filter:

    XLdiambil sebesar 14,97 dari hasil perhitunganlangsung dari filter sizing ETAP 7.00

    Dan komponen resistansi filternya adalah,

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    31/45

    Hasil simulasi (sebelum pemasangan filter)

    Spektrum THD sebelumpemasangan filter

    Spektrum tegangansebelum pemasangan filter

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    32/45

    Hasil simulasi (setelah pemasangan filter)

    Spektrum THD sebelumpemasangan filter

    Spektrum tegangan sebelum

    pemasangan filter

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    33/45

    Hasil simulasi setelah pemasangan filter

    BusTHDV(%)

    Standard

    (%)Condition PF (%)

    Bus 14 1.86 5 OK 85

    Bus Near

    Furnace 2.77 5 OK 83

    Bus ABB panel 2.85 5 OK 98.7

    Bus 169 2.97 5 OK -63.8

    Bus 88 1.16 5 OK -93.6

    Line To Line (Feeder)THDi(%)

    33kV Tranformator 65 ABB Panel 60

    ABB panel Near furnace 70

    THD Tegangan

    THD Arus

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    34/45

    Penutup5

    Simulasi dan Analisis4

    Pendahuluan1

    Teori Penunjang2

    Sistem Kelistrikan3

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    35/45

    Kesimpulan Fenomenainrush current padatrafoterjadi karenapada

    bebanarc furnace bekerjasecaraperiodic, dalamarti bebantersebuttidaksekali switch, namundiperlukanswitchingdalamwaktutertentuuntuksebuahprosespeleburanbaja,hal tersebutmenimbulkanfenomenainrush current danarus

    harmonisaorde2 yang tinggi. Arusinrush danarusharmonisayang tinggi mempengaruhi

    setting relay, sehinggaperludilakukankoreksi.

    Hasil yang diperolehsetelahpemasanganke3filterharmonisadengantuning padaordeke2 adalahTHD

    teganganberkurangdari 16,95% menjadi 3,5 % danTHDarusyang masihcukuptinggi yaitusekitar 60 %.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    36/45

    Terima Kasih

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    37/45

    2nd harmonics in transformerTypical harmonics generated by the transformer inrush current are shown inFig. 17-8. Overexcitationof transformers in steady-state

    operation can produceharmonics. The generated fundamental frequency emf is given byV 4:44fTphBmAc 17:13where Tphisthe number of turns in aphase, Bmis the flux density (consisting offundamental and higher order harmonics), and Ac is the areaofcore. Thus, thefactorV=f is ameasure of the overexcitation, though these currents do not normallycause awave distortion of anysignificance. Exciting currents increase rapidly withvoltage, and transformer standards specify application of 110% voltage without

    overheating the transformer. Under certain systemupset conditions, the transformersmay be subjected to even higher voltages andoverexcitation.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    38/45

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    39/45

    Polaritas dan akibat urutan harmonisa

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    40/45

    Eksitasi awal dan eksitasi adanya harmonisa

    Komponen DC

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    41/45

    Yang dimaksud dengan inrush current

    Pada saat transformator dihubungkan terhadap suatusumber tegangan (energize) akan mengalir arus yangcukup besar dengan periode waktu yang sangat singkatsampai tercapai kondisi steady state.

    Perbedaan dg short circuit:Arus gangguan karenahubungan fasa dengan fasa ataupunnetral pada arus AC tanpa melalui tahanan sehinggamengakibatkan arus meningkat dan menjadi besar.

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    42/45

    Masalahnya dalam tugas akhir ini adalah saat transformatorutama di energize pada saat pertama kali, arus kemudianmengalir menuju transformator beban arc furnace, kemudiankarena dalam saluran tersebut terdapat filter pasif orde ke 2dan setelah di run menggunakan study case harmonics

    analysis pada software ETAP masih terjadi resonansi paralel.

    Kemudian karena proses switching berkali-kali pada bebanmengakibatkan penguatan arus yang mengalir antara trafoutama menuju filter harmonisa ke 2, hal ini yang dapat

    mempengaruhi setting pengaman pada filter harmonisa ke 2

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    43/45

    Transformator

    Dalam transformator ini pada saat beban bekerja maupuntidak bekerja, kondisinya dalam keadaan on

    Karena beban yang tidak sepenuhnya on, dalam arti setiapsaat bisa on atau off, hal tersebut akann menimbulkan arus

    harmonisa ke 2Akibat power faktor leading

    Tegangan akan menjadi lebih besar( overvoltage)

    Masih timbul resonansi paralel pada bus ABB Panel

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    44/45

    Memasukkan parameter harmonisa ke dalamsoftware ETAP 7.00

    Parameter harmonisapada beban arc furnace

    Parameter harmonisa pada trafoutama 150/33/ 11 kV

  • 8/13/2019 ITS Paper 21884 2209106042 Presentation

    45/45

    Akibat power faktor leadingTegangan saluran menjadi overvoltage