NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance of beam-column joint H. Shiohara, PhD. FACI Professor Graduate School of Engineering Department of Architectural Engineering The University of Tokyo Tokyo, Japan 113-8656 [email protected] 1

Upload: truonglien

Post on 15-Mar-2018

228 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Japanese Lessons on RC building collapse and importance of beam-column joint

H. Shiohara, PhD. FACI

ProfessorGraduate School of Engineering Department of Architectural EngineeringThe University of TokyoTokyo, Japan [email protected]

1

Page 2: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

2013 Revision of Seismic Retrofit Promotion Act

1968

1971

1978 19

8119

9520

00

2011

Japanese Past Earthquakes and Countermeasures

2011 Tohoku-Taiheyo Earthquake M9.0

gen. III

1981 ~

gen. I

~ 1971

Amendment of RC Shear design provisions 1971 Revision of BSL Enforcement Order

1968 Tokachi-Oki Earthquake M7.9

gen. II

~ 1981

1981 Revision of BSL Enforcement OrderIntroduction of Lateral Capacity Calculation

1978 Miyagi-Oki Earhtuqkae M7.4

1995 Kobe Earthquake M7.3

1995 Seismic Retrofit Promotion Act

Near fault earthquake・Confirmation of the effectiveness of Lateral Capacity Calculation introduced in 1981

220

17

2005 E-Defense Facility, Miki, Kobe

Page 3: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Collapse of Buildings due to Beam-column joints

Guam IEarthquake Engineering Research Institute

BuildingsThe Royal Palm Hotel, west elevation. The Royal Palm Resort was a 22-unit,12 story hotel and condominium complex that opened for occupancy just 18days before the earthquake. The main portion of the complex, that consisted ofthree structurally separate but functionally interdependent structures, was post-ed as hazardous by the building department following the earthquake and wasdemolished by controlled explosion in December 1993.

Slide #11

Guam IEarthquake Engineering Research Institute

BuildingsRoyal Palm Hotel. Damage at masonry in-fill stair enclosure.

Slide #12Kobe 1995

Guam 1993

112 H. Sezen et al. / Engineering Structures 25 (2003) 103–114

Fig. 13. Building collapse due to failure of beam-column joints.

Fig. 14. Damage to new moment-frame beam-column joint.

observed by the team in a dual wall-frame building isshown in Fig. 15. The wall and first-storey exterior col-

Fig. 15. Collapsed dual wall-frame building in Adapazari, (a) view of collapsed 5-storey building, (b) failure of the shear wall and perimeter col-umns.

umns shown (Fig. 15b) failed and shortened. Thesecomponents displaced out of the plane of the facade asseen in Fig. 15b. Another example of damage to beamsand columns in a dual wall-frame building is shown inFig. 16. No cracks were observed in the shear wall, butthe right end settled approximately 500 mm due to bear-ing failure of the supporting soils. Although the shear wallwas likely sufficiently stiff to protect the nonductileframe, the rotation at the base of the shear wall and thesettlement of the footings beneath the moment-frame col-umns contributed to the failure of the first-story columns.Blade columns or narrow shear walls were often con-

structed near stairwells (Fig. 17). These walls or bladecolumns were detailed similarly to regular moment-frame columns with light transverse reinforcement with90-degree hooks and no cross ties. The damage shownin Fig. 17 is similar to that observed in moment-framecolumns.

Turkey 1999

• ERROR of empirically revised seismic design provisions for RC beam-column joints

Page 4: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Design of confinement in RC members

• Japan (AIJ)

• Shear design has been emphasized for beams and columns

• provisions for shear determine the hoop and stirrup

• US (ACI318)

• Seismic detailing of transverse reinforcement has been emphasized for confinement

4

Difference in the background of past earthquake damage makes a minor difference in seismic provisions in two countries

Page 5: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Design of beam-column joint

• Japan (AIJ)

• Large column is necessary

• Minimum joint hoop ratio is 0.2% for joint shear

• No confinement requirement

• US (ACI318)

• Joint hoops for confinement does not allow reducing the dimension of the column section

• Beam-column joint needs to have joint hoop ratio as much as 1.0% because is it a part of column 5

In 1980’s, test data suggested the joint shear strength of beam-column joint is not be the function of joint hoops

(Japan-US-NZ trilateral coordinated research)

Different message to engineer

Page 6: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

6

22

15 m

20 m

X

Y

F igure 2.1 E-Defense shaking table

F igure 2.2 Overview of test setup on the shaking table

93

E-Defense 3D Shaking Table

National Research Institute for Earth Science and Disaster PreventionMiki, Hyogo Prefecture, Japan

December 2010

Nagae et al. (2015) Design Implications of a Large-Scale Shaking Table Test on a Four Story Reinfored Concrete Building, ACI Structural Journal, Vol. 12, No. 2, March 2015, pp. 135-146.

Proving joint hinging by shaking table test

Page 7: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

7

This test confirmed joint hinging at JMA Kobe 100%

Beam-column joint conformed to Japanese seismic provisions

Specimen H02

-80

-60

-40

-20

0

20

40

60

80

-3 -2 -1 0 1 2 3-4 4

Dc

Db

=1.0

Vju

Vj=1.03

Specimen B02

-80-60-40-20

020406080

-3 -2 -1 0 1 2 3-4 4

Dc Db =1.0

Vju Vj =1.03

Beam Hinging

Joint Hinging

MR = 1.0

MR = 2.0

Page 8: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Recent earthquakes and building collapseBeam-column joint Failure

Page 9: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

Overturning

b. Failure of floor members d. Sinking down due to gravity

Shear due to earth reaction

bump is made

e. Infill brick fall into pieces

Lateral force

Basement (parking)

Continuous overturning

1 2 3

4 5

Wing

Penthouse

Street

EastWest

Collapse mechanism of the RC16story building by Hitoshi Shiohara 2016.2.25

f. Crushed and touch down

a. Failure of beam-column joints c. Fracture of column at lap splice joint

a. a.

b.

c.

d.

e.

Page 10: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Uto Municipal Building collapsed by 2016 Kumamoto earthquake, Kumamoto, Japan, built in the 1970’s, but probably satisfied the current seismic provisions for beam-column joint of Japan. Detailed investigation is underway.

Recent earthquakes and building collapse

�-23

3.2� �k�Vd��o�V

1)� �Þ UT-1ȲèÍāŶƌƏȳ� ĎǥĄȶ1965Ą

ŔĎƹƅ-�5 ȜĎ%, RC ȃąNJ&�>�ăȧēƇ-wǢē,ąNJŤ'ȑńē,LDŤ

ȲȜŭì�Hd[hQh�SEdȳ�<ŦħȲj 3.2.1-1ȳ�?>�¤ǂ-r'�%ah_

fŝŦȲjȜ3(Ş,łȧ�ô� ȳ�ĕǂ-ȄúǃȥØŝŦ&�>�)�ǃȥǦł-ëŅ

�?% !�ǃȥǚđ-Œu&�>',ĤÓBȖ�ǂ�<ė% >�

ĒǨĎƹƅ,ąNJŤ- 4�5Ȝ,�Ş·/¯äēŞţĴ¼Ȋ,ÞƢ*;=öȊûÙȲWÊ

3.2.1-1đ3.2.1-3ȳ�% >�5!ĒǨŞ*Ĵƽ�?% >ţ9Þ��ÞƢ�% >��<*�

LDŤ,­Ŧȧ&- 2 ȜDžȊ&ō�ÎƿƢÙȲWÊ 3.2.1-4ȳBDZ���iȊ-ȍƴČ÷�

Ɗ�% >�ąNJŤ'LDŤ'-´� 110mm,ćPaZ&Ĵƽ�?% >�� ,ĴƽȊ

*-Þ�)./§?�ƕƊ�%�=� ?<,i�ġ�(,ƪċƣ��?% >�-lŊ

&�>�

WÊ 3.2.1-1wêčcæPĎ WÊ 3.2.1-2wêčc¨PĎ

WÊ 3.2.1-3cæP 5Ăªĉú WÊ 3.2.1-4a¨P 2ĂÜú

j 3.2.1-1q¸Ă�±ÂKj

ąNJŤ

LDŤ

Key plan

Kumamoto 2016After removal of architectural mullion

Page 11: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Beam-column Joint & Collapse of Buildings

Key plan

• The reinforcing detailing provisions for seismic design of RC beam-column joints is crucial for seismic performance of moment resisting frame structure.

• Careful selection of “test specimen,” “boundary condition” and “interpretation of statistical data” is necessary.

•Well designed 3D full scale shaking table tests provides most valuable lessons for such purpose.

Page 12: Japanese Lessons on RC building collapse and importance · PDF fileNCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017 Japanese Lessons on RC building collapse and importance

NCREE Tainan Laboratory Grand Opening Ceremony and Forum 2017

Thanks for your attention