2
PACKAGED ROOFTOP UNITS • 2-150 tons VAV and single-zone VAV applications, direct replacement options DEDICATED OUTSIDE AIR SYSTEMS (DOAS) • 50-100% outside air High efficiency DX, energy recovery wheel and hot gas reheat options COMMERCIAL SPLIT SYSTEMS • 1.5-50 tons Cooling only or heat pump outdoor units with matching cooling only, heat pump or electric heat indoor air handling units WATER SOURCE HEAT PUMPS 0.5-30 tons Vertical and horizontal (standard, high and premium efficiency), console, vertical stacked (high and premium efficiency), geothermal capable REVERSIBLE CHILLERS • 2-50 tons Water-to-water heat pumps, (2-5 tons & 10-50 tons), modular application, geothermal capable WATER-COOLED SELF-CONTAINED UNITS • 5-105 tons Indoor, VAV application (> 8 tons), various heating options AIR-COOLED SELF-CONTAINED UNITS • 2-25 tons Indoor, VAV application (> 8 tons), rooftop alternative for dense building landscapes AIR-COOLED CONDENSERS & FLUID COOLERS • 65-2,890 MBH Water or glycol, multiple refrigerant options ENERGY RECOVERY SYSTEMS ENERGY RECOVERY VENTILATORS (ERV) 200-12,000 CFM Energy efficient ventilation including many heating and cooling options HVAC LOAD REDUCTION UNITS (HLR) • Replaces up to 4,000 CFM of OA ASHRAE 62.1 compliant product, up to 80% reduction in outside air replacement YORK ® WATER-COOLED CHILLERS ELECTRIC SCROLL (YCWL) • 50–200 tons HFC-410A refrigerant VARIABLE-SPEED SCREW (YVWA) • 125–300 tons HFC-134a refrigerant MAGNETIC BEARING VARIABLE SPEED CENTRIFUGAL (YMC 2 ) • 165–1,000 tons Permanent magnet motor, HFC-134a refrigerant VARIABLE SPEED CENTRIFUGAL (YK) • 250–3,000 tons HFC-134a refrigerant CENTRIFUGAL WITH ECONOMIZER (YK-EP) • 2,500 – 3,500 tons Variable-speed drive, HFC-134a refrigerant CENTRIFUGAL (YD) • 1,500–6,000 tons Smallest footprint per cooling ton, HFC-134a refrigerant, VSD COMPOUND CENTRIFUGAL (CYK) • 300–2,500 tons High-head, HFC-134a refrigerant CUSTOM-DESIGNED CENTRIFUGAL (OM) • 3,000–5,500 tons Electric-motor, steam-turbine or gas-engine drive, HFC-134a refrigerant THERMALLY DRIVEN STEAM-TURBINE DRIVEN CENTRIFUGAL (YST) • 700–2,800 tons HFC-134a refrigerant SINGLE-STAGE ABSORPTION (YIA) • 120–1,380 tons Low-pressure-steam or hot-water driven, water refrigerant TWO-STAGE ABSORPTION (YPC) • 200–700 tons Gas, oil, or high-pressure-steam driven, water refrigerant YORK AIR-COOLED CHILLERS SCROLL (YCAL & YLAA) • 15–175 tons HFC-410A refrigerant HEAT PUMP SCROLL (YLPA) • 1,390-2,040 MBH HFC-410A refrigerant, chiller duty also available (115-170 tons) VARIABLE-SPEED SCREW (YVAA/YCIV/YCAV) • 150–500 tons HFC-134a refrigerant, free cooling options available YORK AIR HANDLING UNITS, COILS & FANS AIR HANDLING UNITS (SOLUTION ) • 2,000-120,000 CFM Indoor and outdoor, 2” foam double-wall panels with external frame, variable aspect, flexible factory-packaged controls CUSTOM AIR HANDLING UNITS • 2,000–200,000 CFM Indoor and outdoor, 2”, 3” or 4” foam double-wall panels with integral frame, full thermal break options, fully customizable COILS • Maximum 96” Finned Height and 168” Finned Length Hot water, chilled water, glycol, steam, refrigerant, aluminum or copper fins, special coatings available BLOWER COILS 800-4,000 CFM Small air handling and large fan coil applications; various configurations FANS 75-100,000+ CFM Commercial and industrial supply and exhaust fans UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEMS UNDERFLOOR TERMINAL UNITS • 15-1,500 CFM VAV or manual diffusers, linear trough, UFAD fan powered terminal units, underfloor chilled beams CHILLED BEAMS OVERHEAD CHILLED BEAMS • Up to 1,700 BTUh and 40 CFM per LF Active and passive chilled beam products available in 2 – 10 foot lengths TERMINAL UNITS FAN-COIL UNITS 250-2,000 CFM Exposed and concealed, horizontal and vertical, vertical stack, variable cabinet sizing, direct-drive, flexible factory-packaged controls UNIT VENTILATORS 500-2,000 CFM Horizontal and vertical units, flexible factory-packaged controls VAV TERMINAL BOXES 75-8,000 CFM Single or dual-duct, series or parallel fan-powered, flexible factory-packaged controls, water and electric heat options INTEGRATED SOLUTIONS TO OPTIMIZE YOUR BUILDING’S PERFORMANCE CHILLED WATER SYSTEMS AIR SYSTEMS PACKAGED & SPLIT DX SYSTEMS DUCTLESS & VRF SYSTEMS OPTIMIZATION CENTRAL PLANT OPTIMIZATION (CPO 10 / CPO 30) CPO 10 uses standardized software in Metasys to leverage ASHRAE standards, best practices & equipment data to save 5-15% in energy. CPO 30 uses engineered software to save 15-20% in energy (up to 60% when retrofitting), with real-time analytics to assure performance. DEMAND RESPONSE Optimize building energy usage to reduce load during key periods of high prices, high demand charges and electric grid events to maximize electric bill savings and incentive payments from grid and utility based programs. HEALTHCARE ENVIRONMENT OPTIMIZATION Optimize the operating room and improve the patient care environment by linking building automation with surgical scheduling. METASYS ENTERPRISE OPTIMIZATION Simplify data collection from a variety of building systems to provide a single, integrated view of building and system performance. BUILDING SYSTEMS, SERVICES & SOLUTIONS SECURITY & FIRE SAFETY SECURITY, FIRE & LIFE SAFETY INTEGRATION We are a security integrator with a vast product ecosystem specializing in the design, installation and service of security and life safety solutions for the most complex, mission critical environments. SECURITY MANAGEMENT SYSTEM (P2000) Open security management platform with integrated access control, embedded video management and industry-wide third-party integrations. FIRE ALARM (IFC) & MASS NOTIFICATION SYSTEMS Scalable UL ® approved systems that aid in fire detection and notification of critical events. INTRUSION ALARM SYSTEMS Sensors and control panels to protect against intrusion and burglary; UL approved central station monitoring. VIDEO SURVEILLANCE, VIDEO MANAGEMENT & STORAGE Scalable, integrated video surveillance solutions and advanced video analytics. SERVICES & SOLUTIONS MAINTENANCE & REPAIR SERVICES With 130 locations and more than 4,300 highly skilled technicians across North America, we help your facility perform at optimum levels, extend asset life, reduce repair costs, and realize energy savings. BUILDING WIDE SYSTEMS INTEGRATION (BWSI) We integrate building systems (HVAC, BAS, security), business systems (finance, IT, communications) and specialty systems (nurse call, distance learning, scheduling) onto a unified, intelligent infrastructure. TECHNOLOGY CONTRACTING We are responsible for managing design, integration, installation and service of all technology. Along with innovative partners, we reduce risk, minimize change orders and meet budgets and deadlines. ENERGY SOLUTIONS We assess your facilities and design a plan to prioritize repairs, upgrade equipment, reduce energy use and improve overall efficiency. Use tomorrow’s energy savings to pay for today’s upgrades. METASYS ® BUILDING AUTOMATION NETWORK SERVERS, ENGINES & CONTROLLERS Intuitive, mobile-optimized user interface. Adapts legacy and proprietary systems to current open system architecture. Support of IT standards and technologies. WIRELESS COMPONENTS Field buses and room environment sensing systems designed with the latest wireless technologies. VALVES, ACTUATORS & DAMPERS Global product family, broad selection, easy installation. SENSORS, THERMOSTATS & AIRFLOW MEASURING SYSTEM Temperature, humidity and CO 2 sensors including analog, network, wireless and pneumatic-to-digital. VARIABLE-SPEED DRIVES • 1-250 HP Open, enclosed and bypass drives, optional factory mounting. YORK VARIABLE REFRIGERANT FLOW (VRF) SYSTEMS OUTDOOR UNITS • 6-30 tons Both heat recovery and heat pump types, air cooled condensing units with inverter scroll compressors; up to 29.5 SCHE and 25.2 IEER INDOOR UNITS • 0.5-4 tons Fan coil units in multiple styles (concealed, wall mount, ceiling cassette); ducted and non-ducted; sensor options YORK MINI-SPLIT SYSTEMS SINGLE ZONE • 0.75-4 tons A single condensing unit paired with a single wall mount indoor unit. Multiple styles, capacities, operating ranges and efficiency ratings. Wi-Fi capable; Energy Star ® rated. MULTI ZONE • 1.5-3.5 tons Single condensing unit with 2-5 indoor units per system. Multiple styles, capacities, operating ranges and efficiency ratings. Wi-Fi capable; Energy Star rated. www.johnsoncontrols.com

Upload: james-matchett

Post on 17-Feb-2017

343 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Johnson Controls Line Card

PACKAGED ROOFTOP UNITS • 2-150 tons VAV and single-zone VAV applications, direct replacement options

DEDICATED OUTSIDE AIR SYSTEMS (DOAS) • 50-100% outside airHigh efficiency DX, energy recovery wheel and hot gas reheat options

COMMERCIAL SPLIT SYSTEMS • 1.5-50 tonsCooling only or heat pump outdoor units with matching cooling only, heat pump or electric heat indoor air handling units

WATER SOURCE HEAT PUMPS • 0.5-30 tons Vertical and horizontal (standard, high and premium efficiency), console, vertical stacked (high and premium efficiency), geothermal capable

REVERSIBLE CHILLERS • 2-50 tons Water-to-water heat pumps, (2-5 tons & 10-50 tons), modular application, geothermal capable

WATER-COOLED SELF-CONTAINED UNITS • 5-105 tonsIndoor, VAV application (> 8 tons), various heating options

AIR-COOLED SELF-CONTAINED UNITS • 2-25 tonsIndoor, VAV application (> 8 tons), rooftop alternative for dense building landscapes

AIR-COOLED CONDENSERS & FLUID COOLERS • 65-2,890 MBH Water or glycol, multiple refrigerant options

ENERGY RECOVERY SYSTEMS

ENERGY RECOVERY VENTILATORS (ERV) • 200-12,000 CFMEnergy efficient ventilation including many heating and cooling options

HVAC LOAD REDUCTION UNITS (HLR) • Replaces up to 4,000 CFM of OAASHRAE 62.1 compliant product, up to 80% reduction in outside air replacement

YORK® WATER-COOLED CHILLERS

ELECTRICSCROLL (YCWL) • 50–200 tons HFC-410A refrigerant

VARIABLE-SPEED SCREW (YVWA) • 125–300 tonsHFC-134a refrigerant

MAGNETIC BEARING VARIABLE SPEED CENTRIFUGAL (YMC2) • 165–1,000 tonsPermanent magnet motor, HFC-134a refrigerant

VARIABLE SPEED CENTRIFUGAL (YK) • 250–3,000 tons HFC-134a refrigerant

CENTRIFUGAL WITH ECONOMIZER (YK-EP) • 2,500 – 3,500 tonsVariable-speed drive, HFC-134a refrigerant

CENTRIFUGAL (YD) • 1,500–6,000 tonsSmallest footprint per cooling ton, HFC-134a refrigerant, VSD

COMPOUND CENTRIFUGAL (CYK) • 300–2,500 tons High-head, HFC-134a refrigerant

CUSTOM-DESIGNED CENTRIFUGAL (OM) • 3,000–5,500 tons Electric-motor, steam-turbine or gas-engine drive, HFC-134a refrigerant

THERMALLY DRIVENSTEAM-TURBINE DRIVEN CENTRIFUGAL (YST) • 700–2,800 tonsHFC-134a refrigerant

SINGLE-STAGE ABSORPTION (YIA) • 120–1,380 tonsLow-pressure-steam or hot-water driven, water refrigerant

TWO-STAGE ABSORPTION (YPC) • 200–700 tonsGas, oil, or high-pressure-steam driven, water refrigerant

YORK AIR-COOLED CHILLERS

SCROLL (YCAL & YLAA) • 15–175 tonsHFC-410A refrigerant

HEAT PUMP SCROLL (YLPA) • 1,390-2,040 MBH HFC-410A refrigerant, chiller duty also available (115-170 tons)

VARIABLE-SPEED SCREW (YVAA/YCIV/YCAV) • 150–500 tonsHFC-134a refrigerant, free cooling options available

YORK AIR HANDLING UNITS, COILS & FANS

AIR HANDLING UNITS (SOLUTION™) • 2,000-120,000 CFMIndoor and outdoor, 2” foam double-wall panels with external frame, variable aspect, flexible factory-packaged controls

CUSTOM AIR HANDLING UNITS • 2,000–200,000 CFMIndoor and outdoor, 2”, 3” or 4” foam double-wall panels with integral frame, full thermal break options, fully customizable

COILS • Maximum 96” Finned Height and 168” Finned LengthHot water, chilled water, glycol, steam, refrigerant, aluminum or copper fins, special coatings available

BLOWER COILS • 800-4,000 CFMSmall air handling and large fan coil applications; various configurations

FANS • 75-100,000+ CFMCommercial and industrial supply and exhaust fans

UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEMS

UNDERFLOOR TERMINAL UNITS • 15-1,500 CFMVAV or manual diffusers, linear trough, UFAD fan powered terminal units, underfloor chilled beams

CHILLED BEAMS

OVERHEAD CHILLED BEAMS • Up to 1,700 BTUh and 40 CFM per LF Active and passive chilled beam products available in 2 – 10 foot lengths

TERMINAL UNITS

FAN-COIL UNITS • 250-2,000 CFM Exposed and concealed, horizontal and vertical, vertical stack, variable cabinet sizing, direct-drive, flexible factory-packaged controls

UNIT VENTILATORS • 500-2,000 CFM Horizontal and vertical units, flexible factory-packaged controls

VAV TERMINAL BOXES • 75-8,000 CFM Single or dual-duct, series or parallel fan-powered, flexible factory-packaged controls, water and electric heat options

INTEGRATED SOLUTIONS TO OPTIMIZE YOUR BUILDING’S PERFORMANCE

CHILLED WATER SYSTEMS AIR SYSTEMS PACKAGED & SPLIT DX SYSTEMS DUCTLESS & VRF SYSTEMS

OPTIMIZATION

CENTRAL PLANT OPTIMIZATION (CPO 10 / CPO 30)CPO 10 uses standardized software in Metasys to leverage ASHRAEstandards, best practices & equipment data to save 5-15% in energy.

CPO 30 uses engineered software to save 15-20% in energy (up to 60%when retrofitting), with real-time analytics to assure performance.

DEMAND RESPONSEOptimize building energy usage to reduce load during key periods of high prices, high demand charges and electric grid events to maximize electric bill savings and incentive payments from grid and utility based programs.

HEALTHCARE ENVIRONMENT OPTIMIZATIONOptimize the operating room and improve the patient care environment by linking building automation with surgical scheduling.

METASYS ENTERPRISE OPTIMIZATIONSimplify data collection from a variety of building systems to provide a single, integrated view of building and system performance.

BUILDING SYSTEMS, SERVICES & SOLUTIONS

SECURITY & FIRE SAFETY

SECURITY, FIRE & LIFE SAFETY INTEGRATIONWe are a security integrator with a vast product ecosystem specializing in the design, installation and service of security and life safety solutions for the most complex, mission critical environments.

SECURITY MANAGEMENT SYSTEM (P2000)Open security management platform with integrated access control, embedded video management and industry-wide third-party integrations.

FIRE ALARM (IFC) & MASS NOTIFICATION SYSTEMSScalable UL® approved systems that aid in fire detection and notification of critical events.

INTRUSION ALARM SYSTEMSSensors and control panels to protect against intrusion and burglary; UL approved central station monitoring.

VIDEO SURVEILLANCE, VIDEO MANAGEMENT & STORAGEScalable, integrated video surveillance solutions and advanced video analytics.

SERVICES & SOLUTIONS

MAINTENANCE & REPAIR SERVICESWith 130 locations and more than 4,300 highly skilled technicians across North America, we help your facility perform at optimum levels, extend asset life, reduce repair costs, and realize energy savings.

BUILDING WIDE SYSTEMS INTEGRATION (BWSI)We integrate building systems (HVAC, BAS, security), business systems (finance, IT, communications) and specialty systems (nurse call, distance learning, scheduling) onto a unified, intelligent infrastructure.

TECHNOLOGY CONTRACTING™

We are responsible for managing design, integration, installation and service of all technology. Along with innovative partners, we reduce risk, minimize change orders and meet budgets and deadlines.

ENERGY SOLUTIONSWe assess your facilities and design a plan to prioritize repairs, upgrade equipment, reduce energy use and improve overall efficiency. Use tomorrow’s energy savings to pay for today’s upgrades.

METASYS® BUILDING AUTOMATION

NETWORK SERVERS, ENGINES & CONTROLLERSIntuitive, mobile-optimized user interface. Adapts legacy and proprietary systems to current open system architecture. Support of IT standards and technologies.

WIRELESS COMPONENTSField buses and room environment sensing systems designed with the latest wireless technologies.

VALVES, ACTUATORS & DAMPERSGlobal product family, broad selection, easy installation.

SENSORS, THERMOSTATS & AIRFLOW MEASURING SYSTEMTemperature, humidity and CO2 sensors including analog, network, wireless and pneumatic-to-digital.

VARIABLE-SPEED DRIVES • 1-250 HPOpen, enclosed and bypass drives, optional factory mounting.

YORK VARIABLE REFRIGERANT FLOW (VRF) SYSTEMS

OUTDOOR UNITS • 6-30 tonsBoth heat recovery and heat pump types, air cooled condensing units with inverter scroll compressors; up to 29.5 SCHE and 25.2 IEER

INDOOR UNITS • 0.5-4 tonsFan coil units in multiple styles (concealed, wall mount, ceiling cassette); ducted and non-ducted; sensor options

YORK MINI-SPLIT SYSTEMS

SINGLE ZONE • 0.75-4 tonsA single condensing unit paired with a single wall mount indoor unit. Multiple styles, capacities, operating ranges and efficiency ratings. Wi-Fi capable; Energy Star® rated.

MULTI ZONE • 1.5-3.5 tonsSingle condensing unit with 2-5 indoor units per system. Multiple styles, capacities, operating ranges and efficiency ratings. Wi-Fi capable; Energy Star rated.

www.johnsoncontrols.com

Page 2: Johnson Controls Line Card

-5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100

105

110

115

120

125

130

DR

Y BU

LB T

EMPE

RAT

UR

E - °

F

.001

.002

.003

.004

.005

.006

.007

.008

.009

.010

.011

.012

.013

.014

.015

.016

.017

.018

.019

.020

.021

.022

.023

.024

.025

.026

.027

.028

.029

10% RELATIVE HUMIDITY20%

30%

40%

50%

60%

70%

80%

90%

0 5 1015

2025

30

35

40

45

50

55

60

65

70

75

80

85 WET BULB TEMPERATURE - °F

90

12.0

12.5

13.0

13.5

14.0 VOLU

ME- C

U.FT. PER

LB. DR

Y AIR

14.5

15.0

15.5

HU

MID

ITY

RAT

IO -

POU

ND

S M

OIS

TUR

E PE

R P

OU

ND

DR

Y AI

R

0 5 10 15 20 25 30

35

40

45

50

55

55

60

60

ENTHALPY - BTU PER POUND OF DRY AIR

0

5

10

15

20

25

30

35

40

45

50

ENTH

ALPY

- BT

U PE

R PO

UND

OF

DRY

AIR

.1

.2

.3

.4

.5

.6

.7

.8

.9

1

1.1

1.2

1.3

VAPO

R P

RES

SUR

E - I

NC

HES

OF

MER

CU

RY

0 10

20 25

30

35

40

45

50

55

60

65

70

75

80

85

DEW

PO

INT

TEM

PER

ATU

RE

- °F

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

1.00

0.95

0.90

0.85

0.80

0.75

0.70

0.65

0.60

0.55

0.50

0.45

SEN

SIBL

E H

EAT

RAT

IO =

Qs

/ Qt

-5 0 510

1520

25

30

35

40

45

50

55

60

65

70

75

80

85

Chart by: HANDS DOWN SOFTWARE, www.handsdownsoftware.com

Psychrometric Chart for HVAC Analysis

Johnson Controls, the Johnson Controls logo, Metasys® and YORK® are registered trademarks of Johnson Controls, Inc. in the United States of America and other countries.

Technology Contracting™ and Solution™ are trademarks of Johnson Controls, Inc. in the United States of America and other countries. Other trademarks used herein may be trademarks or registered trademarks of other companies.

© 2015 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201All rights reserved worldwide. Printed in USA MISC-692 (Rev. 10/15) www.johnsoncontrols.com

Air-Conditioning Formulas and Conversion FactorsAtmospheric pressure = 29.921" Hg. at sea level

1 BTU = Amount of heat required to raise (or lower) the temperature of one pound of water 1°F

1 ton of refrigeration = 12,000 Btu/hr = 200 Btu/min

1 watt = 3.414 Btu/hr

1 horsepower = 2545.6 Btu/hr

1 ft (head) = 0.433 psi (at 62°F)

1 boiler horsepower = 33,475 Btu/hr

Air changes per hour (N) in a space N = (60 x CFM) / space ft3 CFM = airflow rate (ft3/min)

Water quantity (GPM) required for heating and cooling GPM = q / (500 x Δt) q = load in Btu/hr t = water temperature

Chiller capacity (Tons) Tons = (GPM x Δt) / 24 GPM = gallons per minute of chilled water t = water temperature

Pump hp = x specific gravity

Fan hp = x

Total cooling (Btu/hr) = CFM x 4.5 x Δh

Sensible cooling (Btu/hr) = CFM x 1.085 x Δt

Latent cooling (Btu/hr) = CFM x 4840 x Δw

CFM = airflow rate (ft3/min) h = enthalpy (Btu/lb) t = dry bulb air temperature (°F) w = humidity ratio (lb water / lb dry air)

Fan Laws CFM2 = CFM1 x (RPM2 / RPM1) SP2 = SP1 x (RPM2 / RPM1)

2 HP2 = HP1 x (RPM2 / RPM1)

3 1 = initial; 2 = desired

GPM x ft head3960 x efficiency

CFM x static pressure (in. W.G.)6356 x efficiency

density of air density of standard air

Altitude Air Density Ratio at 70˚F

2000 ft 0.930

4000 ft 0.864

6000 ft 0.801

8000 ft 0.743