just 1 leg through ct power resistor already installed
TRANSCRIPT
Just 1 leg through CT
Resistor already installed
Power
Kriwan -
1 phase monitoring / resistor installed / Bi-metal 5 pin terminal Plate (Klixon) overloads
The MCC values below are provided for reference only. Before programming, verify MCC values with compressor specificaitons.
Compressor MCC Model Number (Amps) 06C *016D *** 27.0 06C * 016G * * * 13.5 06C * 016J * * * 10.8 06C * 017D * * * 27.0 06C * 017G * * • 13.5 06C * 017 J * * * 10.8 06C * 018D * * * 27.0 06C * 018G * * * 13.5
06C * 018J * * * 10.8 06C * 124D * * * 33.0 06C * 124G * * * 16.5 06C * 124J * * * 13.2 06C * 125D * * * 44.0 06C * 125G*** 22.0 06C * 125J * * * 17.6 06C * 228D * * * 41.6 06C * 228G * * * 20.9 06C * 228J * * * 16.7 06C * 337D * * * 46.6 06C * 337G * * * 23.3 06C*337J*** 18.8 06C * 3370 * * * 37.8 06D * 013 * * A 13 * * 10.5 06D *013 **A31 ** 7.0 06D * 013 * * A32 * * 17.4 06D * 013 * * A36 * * 8.7 06D * 1 09 * * A 13 * * 9.5 06D * 1 09 * * A31 * * 4.4 06D * 1 09 * * A32 * * 12.1 06D * 1 09 * * A36 * * 5,5 06D * 1 09 * * A39 * * 5.5 06D * 228 * * A 13 * * 33.6
ti 06D * 228 * * A31 * * 22.2 06D * 228 * * A32 * * 55.5 06D * 228 * * A36 * * 27.8
Compressor Model Number 06D * 237 * * A06 * * 06D * 237 * * A 12 * * 06D *313** A13 ** 06D*313**A31 ** 06D * 313 * * A32 * * 06D * 313 * * A34 * * 06D * 313 * * A36 * * 06D * 316 * * A13 * * 06D * 316 * * A31 * * 06D * 316 * * A32 * * 06D * 316 * * A34 * * 06D * 316 * * A36 * * 06D * 328 * * A01 * * 06D * 328 * * A05 * * 06D * 328 * * A06 * * 06D * 328 * * A08 * * 06D * 328 * * Ai 2 * * 06D * 328 • * A 13 * * 060 * 328 * * A31 * * 06D * 328 * * A32 * * 06D * 328 * * A34 * * 06D * 328 * * A36 * * 06D * 337 * * A01 * * 06D * 337 * * A05 * * 06D * 337 * * A06 * * 06D * 337 * * A08 * * 06D*337 **A12** 06D *337 **A13* * 060 * 337 * * A31 * * 06D * 337 * * A32 * * 060 * 337 * * A34 * * 06D * 337 * * A36 * * 06D * 537 * * A01 * * 06D * 537 * * A05 * * 06D * 537 * * A06 * *
MCC (Amps)
27.8 69.0 16.4 10.8 27.0 27.4 13.5 16.4 10.8 27.0 27.4 13.5 25.0 69.4 31.0 56.4 69.0 42.0 25.0 62.0 50.5 31.0 25.0 69.4 31.0 56.4 69.0 37.8 25.0 62.0 58.2 31.0 32.0 80.0 40.0
Compressor Model Number 06D * 537 * * A08 * * 06D * 537 * * A 12 * * 06D * 537 * * A 13 * * 06D * 537 * * A31 * * 06D * 537 * * A32 * * 06D * 537 * * A36 * * 060*541 **A01 ** 06D * 541 * * A06 * * 06D * 541 * * A08 * * 06D * 541 * * A09 * * 06D * 541 * * A 12 * * 06D * 541 * * A 13 * * 060 *-541 * * A31 * * 06D * 541 * * A32 * * 06D * 541 * * A36 * * 06D*718 **A13** 06D * 718 * * A31 * * 06D * 718 * * A32 * * 06D * 718 * * A36 * * 06D * 724 * * A01 * * 06D * 724 * * A06 * * 06D * 724 * * A12 * * 06D * 724 * * A13 * * 06D * 724 * * A31 * * 06D * 724 * * A32 * * 06D * 724 * * A36 * * 06D * 725 * * A06 * * 06D * 725 * * A 12 * * 06D * 725 * * A 13 * * 06D * 725 * * A31 * * 06D * 725 * * A32 * * 06D * 725 * * A36 * * 06D * 808 **A 13 * * 06D * 808 * * A31 * * 06D * 808 * * A32 * *
MCC (Amps)
75.0 89.0 54.2 32.0 89.0 40.0 32.0 40.0 75.0 40.0 89.0 54.2 32.0 89.0 40.0 16.4 10.8 27.0 13.5 19.7 22.0 48.8 26.6 17.6 44.0 22.0 22.0 48.8 26.6 17.6 44.0 22.0 10.5 7.0
17.4
Compressor MCC Model Number (Amps) 06D * 808 * * A34 * * 17.8 06D * 808 * * A36 * * 8.7 06D *816**A13** 26.6 06D*816 **A31 ** 17.6 06D.* 816 * * A32 * * 44.0 06D * 816 * * A34 * * 40.0 06D*816**A36** 22.0 06D * 818 * * A01 * * 19.7 06D * 818 * * A04 * * 54.6 06D * 818 * * A06 * * 24.6 06D * 818 * * A 12 * * 48.8 06D * 818 * * A13 * * 26 .. 6 06D *-818 * * A31 * * 17.6 06D * 818 * * A32 * * 44.0 06D * 818 * * A34 * * 40.0 06D * 818 * * A36 * * 22.0 050·• 820 • • A13 • • 2.6.6 06D * 820 * * A31 * * 17.6 06D * 820 * * A32 * * 44.0 06D * 820 * * A36 * * 22.0 06D * 824 * * A01 * * 24.9 06D * 824 * * A06 * * 27.8 06D *824**A12** 69.0 06D * 824 * * A 13 * * 33.6 06D * 824 * * A31 * * 22.2 06D * 824 * * A32 * * 55.5 06D * 824 * * A34 * * 50.5 06D * 824 * * A36 * * 27.8 06D * 825 * * A01 * * · 22.206D * 825 * * f\06 * * 27.8 06D*825**A12** 69.0 06D*825 **A13** 33.6 06D * 825 * * A31 * * 22.2 06D * 825 * * A32 * * 55.5 06D * 825 * * A34 * * 50.5 06D * 825 * * A36 * * 27.8
Open the INTspector App and select the USB Gateway button and wait for the connection to beestablished as shown by the next screen in step 3. (this may take approx. 20 seconds)
Once the connection to the INT 69 i 2 Diagnose is established, the following screen appearsautomatically. It may take a few additional seconds for the Change Parameters button toautomatically appear.
S T - example shown
Set Amps from Table - example shown
** Note: If you tap the buttons to the left & button turns green, this locks out compressor if safety trips
Make sure Disabled
12
** Trip delay means time that CT or module recognizes a problem to the time it trips compressor ** Reset delay is time to restart
0