INSTRUCTION MANUAL UG30 CONTROL mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 1 (44) Uniguard BASE UG30 and mP30 CONTROL FOR PRECISION AIR CONDITIONERS - CHILLED WATER (CW/S-CW) - DIRECT EXPANSION (DX/S-DX) INSTRUCTION MANUAL © UNIFLAIR 2004

Upload: myka-myk

Post on 16-Apr-2015

616 views

Category:

Documents


102 download

TRANSCRIPT

Page 1: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 1 (44)

Uniguard BASE UG30 and mP30 CONTROL FOR PRECISION AIR CONDITIONERS - CHILLED WATER (CW/S-CW) - DIRECT EXPANSION (DX/S-DX)

INSTRUCTION MANUAL

© UNIFLAIR 2004

Page 2: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

2 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

UNIFLAIR ITALIA S.p.A.

Via dell’Industria, 10 35020 BRUGINE (Padova) Italy

Tel. +39 (0)49 9713211 Fax. +39 (0)49 5806906

Internet: www.UNIFLAIR.com E-Mail: [email protected]

Release: 1.5 Date: 18 – 03 - 2004

Checked by:

Page 3: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 3 (44)

CONTENTS

Page Program identification 4

Warnings 4 General characteristics 5 Lay-out of Uniguard Base UG30/mP30 circuit 6 Inputs and outputs 7 Optional sensors 8 Optional circuits 8 Lay-out of CP1 circuit 9

Display 16 Keyboard 17

Information on display when unit is OFF 18 Unit start-up conditions 19 Switching the unit ON and OFF 19

STATUS MASK 20 Information on display when unit is ON 20

Unit status display 21

Access to parameters when consulting or programming 22 Changing the Password 27

Hardware configuration 28

Operation hour-counter 29 Exceeding hour-counter threshold 30 Maintaining the humidifier cylinder 30

Remote control of unit Connecting more than one unit

3132

Temperature set points 33 Humidity set points 34 Calibration and setting 34

Clock/dater – Time-bands 35

Delays due to alarm signals 38 Serious alarms 38 Active alarms 38 Reading the alarms historic record 39 Alarm codes description 40 Default values 43 Memory reset 44

Appendix: Flowchart for UG30/mP30 masks – Access with USER password

44

Flowchart for UG30/mP30 masks – Access with FACTORY password

Page 4: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

4 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

PROGRAM IDENTIFICATION

This manual describes the characteristics of the standard UG30 and mP30 control for conditioners.

The software version can be read by repeatedly pressing key until your reach the "Hr" parameter; this information must be supplied to the technical service centres when they are called in for a job.

Version Parameter

1.6 Hr The setting of some parameters on a special unit version may differ from those described in this manual.

WARNINGS

Do not install the controls in places with the following characteristics: - relative humidity above 80%; - exposed to aggressive and polluting atmospheres (e.g.: sulphur or ammonia gasses, salt mists, fumes) to avoid corrosion and/or oxidation; - high magnetic and/or radio frequency interference (therefore, avoid installing units near transmitter aerials);

Cut power before beginning work on the circuit in the case of assembly, maintenance or replacement jobs.

In general, all the instructions found in the unit’s Installation, Use and Maintenance Manual apply. WARNING: In direct expansion air-conditioners with a three-phase power supply, the controller's power may be cut if the phase sequence relay (RSF) is tripped.

Page 5: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 5 (44)

CHARACTERISTICS

UG30/mP30 is an electronic control for full management of precision air conditioners, for both chilled water (CW-CW/S) and direct expansion (DX-DX/S) versions with 1 or 2 compressors. The control consists of a user interface and a power circuit, both fitted inside a single container. The display shows the unit’s operating status and main parameters by means of symbols and alphanumeric codes consisting of one letter and one number:

1, 2…: probe parameters; r1, r2 …: adjustment parameters (e.g. r1 = cooling set-point); c9, CA…: compressor management parameters; F9, FA…: fan management parameters; P1, P2…: alarm management parameters; H1, H2…: general configuration parameters.

All control parameters are set in the factory according to the type of unit and configuration; programming is effected by a hardware key or via a serial line. To change parameters, the operator may use the keyboard on the front panel. USER or FACTORY parameters are available depending on whether they are accessible to the user or reserved for authorised personnel. TECHNICAL SPECIFICATIONS

Power supply : 24 Vac ±15% 50/60 Hz Maximum absorbed current: 200 mA with 800 mA T (delayed) internal fuse Transformer power for UG30/mP30 and digital inputs: 10 VA Operating conditions: -10 ÷ +54°C with 20-80 non condensating R.H. Storage conditions: -10 ÷ +70°C with 0-80 non condensating R.H.

Alarms are active when the relevant input is open (not powered) Input ID1, for remote ON/OFF, powers up the unit when it is itself powered.

Page 6: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

6 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

LAY-OUT OF UNIGUARD BASE UG30/mP30 CIRCUIT The figure shows the rear of the UG30/mP30 control, with input and output terminals. The following are shown in the figure: - low down: connectors ("1" - "2" - "3"), with the analogue and digital inputs and outputs; - lay-out for the clock circuit (optional); - lay-out for the RS485 serial circuit (optional);

1

C5

C3/4 OUT3

C1/2

Y1

Y2

OUT5

OUT4

OUT2

OUT1

GND

GND

2

G0

B4

B2

B3

ID2

ID4 ID6 ID8 ID10

G

B1

GND

+V

ID1

ID3 ID5 ID7 ID9

3

C6

NO6

C7

NC6

NO7

Page 7: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 7 (44)

INPUTS AND OUTPUTS The following tables shows information on inputs and outputs according to the type of selected unit. CW = 'LEONARDO' chilled water air conditioner; CW/S = 'AMICO' chilled water air conditioner; DX = 'LEONARDO' direct expansion air conditioner with 1 or 2 compressors. DX/S = 'AMICO' direct expansion air conditioner. DIGITAL INPUTS – Connector 2 Equipped with 10 24Vac digital inputs.

CW - CW/S DX - DX/S ID1 Remote ON/OFF Remote ON/OFF ID2 Air flowswitch Air flowswitch ID3 Dirty filters flowswitch

(standard issue on CW/S unit, optional extra on CW unit) Dirty filters flowswitch

ID4 Safety thermostat for heating elements Safety thermostat for electrical resistors ID5 Alarm from temperature and humidity external sensors, and from

flooding sensor (optional) Alarm from temperature and humidity external sensors, and from flooding sensor (optional)

ID6 Humidifier alarm from circuit CDA303 Humidifier alarm from circuit CDA303 ID7 -- Circuit 1 high pressure ID8 -- Circuit 1 low pressure ID9 -- Circuit 2 high pressure Compressor thermal breaker ID10 -- Circuit 2 low pressure GO Common for inputs 1 –10

ANALOGUE INPUTS – Connector 2 Equipped with 3 analogue inputs for NTC sensors and 1 active probe 0-1Vdc / 4-20mA.

CW - CW/S DX - DX/S B1 Room temperature Room temperature B2 External air temperature for summer/winter changeover External air temperature for summer/winter changeover B3 Room relative humidity Room relative humidity B4 STM delivery temperature STM delivery temperature

GND Common for analogue inputs +V Power supply for active sensors 14Vdc (max.30mA)

DIGITAL OUTPUTS The card is equipped with 7 outputs including: 1 200 Vac relay, with exchange contact; 1 200 Vac relay, with normally opened contact. Digital outputs – Connector 1

CW - CW/S DX - DX/S DO1 C1/2 – OUT1 Cold water valve + (opens) Compressor circuit 1 DO2 C1/2 – OUT2 Cold water valve - (closes) Compressor circuit 2 DO3 C3/4 – OUT3 1st stage for heating elements/

Hot water valve + (opens) 1st stage for heating elements/ Hot water valve + (opens)

DO4 C3/4 – OUT4 2nd stage for heating elements/ Hot water valve - (closes)

2nd stage for heating elements/ Hot water valve - (closes)

DO5 C5 – OUT5 Fan Triggering by fire-smoke sensor

Fan Triggering by fire-smoke sensor

Digital outputs with relays – Connector 3

CW - CW/S DX - DX/S DO6 C6-NO6-NC6 Serious alarm Serious alarm DO7 C7-NO7 Dehumidifying solenoid-valve (CW)

Available for non-serious alarm warning (on CW/S) Dehumidifying solenoid-valve (DX) Available for non-serious alarm warning (on DX/S)

ANALOGUE OUTPUTS – Connector 1 Equipped with a 0-10Vdc analogue output and 1 phase cut-out output.

CW - CW/S DX - DX/S Y1 Y1 – GND Humidifier control Humidifier control Y2

Page 8: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

8 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

OPTIONAL SENSORS The presence of sensors depends on the units configuration and version.. If a sensor is connected to a pre-installed conditioner, one of the “FACTORY” parameters described below must be modified. Prob SENSORS Default

1 B2 sensor present (external air temperature) 0 = absent 1 = NTC

0

2 Sensor B3 present (room humidity) 0 = absent 2 = 4-20 mA

0

3 Sensor B4 present (delivery temperature) 0 = absent 1 = NTC

0

OPTIONAL CIRCUITS UG30/mP30 is designed to be use with the following optional circuits: - RS485 serial circuit making it possible to connect the control to a supervision or remote assistance network; - Clock circuit, allows the user to see date and time, indispensable for operating programmes linked to time (time bands and memorising of the time and date of an alarm event). RS485 SERIAL CIRCUIT To use UG30/mP30 in an RS485 supervision system or remote assistance network, the optional RS485 circuit must be fitted as follows: - cut power to the unit - disconnect the connectors from terminal boards "1", "2" and "3"; - unscrew the rear cover of the control; - fit the RS485 circuit on the connector at the rear of the control; - break the plastic protection to allow access to terminals GND, RX/TX+, RX/TX-; - re-position the cover and connectors; - make the serial line connection observing the indicated polarities; - power up. Set the UG30/mP30’s address in the network with parameter Ho and the speed with parameter HP (see paragraph “REMOTE CONTROL OF UNIT “.

Consult manual for Supervision Systems. CLOCK CIRCUIT To enable the clock, time bands and the alarm historic record function, fit the optional circuit and follow the procedure below: - cut power to the unit - disconnect the connectors from terminal boards "1", "2" and "3"; - unscrew the rear cover of the control; - fit the clock circuit on the connector at the rear of the control; - re-position the cover and connectors; - power up. - set date and time and delete the alarms historic record. HUMIDIFIER INTERFACE CIRCUIT – CP1 The CP1 electronic circuit is fitted on the electrical panel of the unit. It enables the management of the humidifier and signals any alarm statuses. The circuit is not provided with a display, and, therefore, signals are produced by lighting of coloured LEDs.

Page 9: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 9 (44)

LAY-OUT OF CP1 CIRCUIT

The CP******** electronic card has been designed to control the immersed-electrodes OEM KUE* humidifiers. Since the CP********* card is uncovered, it must be installed so as to avoid any accidental contact with people during normal operating conditions and to prevent the danger of possible high tension or high temperature points. As to installation refer to the user manual of the immersed-electrodes OEM series.

Page 10: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

10 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

TECHNICAL SPECIFICATIONS Power supply:24Vac, from -15% to +10%, 50/60Hz Consumption:9VA (solenoid valves not included) - 35VA max (valves included) Operating conditions: 0T60°C; <90%r.H. non condensing Storage conditions: -10T70°C; <90%r.H. non condensing Environmental pollution: normal Digital outputs (relays: micro-interruption 1C type): - electrode power supply (cards CP1* and CP2*): 2 relays SPST, 250Vac 20A resistive (12A inductive cos = 0,4); min. number of commutations: 100.000 -electrode power supply (cards CP3* and CP4*): 1 relay SPST, 250Vac 5A (2A); min. number of commutat.: 100.000 - cumulative alarm relay: 1 relay SPST, 250Vac 5A (2A) Digital inputs: - AB-AB (remote ON/OFF start consent): external potential-free contact: ON= closed contact (Rmax of closed contact= 50, Imax through closed contact= 10mA); OFF= open contact (Vmax across open contact= 32Vdc) - VR-SET (humidistat): external potential-free contact for the production on/off control. Used as an alternative to SET-GND connection (read below under “Analogue input”). START OF PRODUCTION= closed contact (Rmax of closed contact= 50, Imax through closed contact= 10mA); STOP OF PRODUCTION= open contact (Vmax across open contact= 10Vdc) - Manual drainage: 2 external complementary potential-free contacts: ON-GND: closed= control enabled (drainage OFF), Rmax of closed contact= 50, Imax through closed contact= 5mA open= control disabled (drainage ON), Vmax across open contact= 5Vdc DR-GND: closed= drainage ON (disabled control), Rmax of closed contact= 1, Imax through closed contact= 0.5A open= drainage OFF (enabled control), Vmax across open contact= 24Vac Analogue input: - SET-GND (steam production request from ext. regulator; input impedance 15k): 0/10V (default), 2/10V, 0/1V. Used as an alternative to VR-SET (read above under “Digital inputs”) Protection index: IP00 Maximum cable length (TAM inputs, level, conductivity): shorter than 10m

NEW UE HUMIDIFIERS CP1 CARD HARDWARE CONFIGURATION (EXTERNAL TAM)

CP1 card used in single-phase OEM (AMICO unit): 2 relays (2x250V AC) to break phase and neutral (no external contactor needed). CP1 card used in three-phase OEM (Leonardo, Big units): 1 relay (1x250V AC) used to supply power to electrode supply contactor's coil.

MEANING WHEN LED FLASHES Steam production: YELLOW LED (transitory production “short flashes” - steady-state production “long flashes”).

AMICO UNIT CP1 CONFIGURATION (SD/SU 0151 – 0251 – 0331………..) AMICO unit (single-phase OEMs): For all sizes, the Cp1 card must be configured for a nominal steam flow of 3 kg/h

Page 11: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 11 (44)

FACTORY SETTINGS . Dip switches type A (alarm relay and maximum production settings) A1 A2 A3 A4 ON X OFF X

Dip switch 1-not used Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized (contact closed) Dip switches 3-4 set to OFF: 100% of nominal steam

flow ( 3 kg/h)

Dip switches type B (auxiliary functions and automatic draining time) B1 B2 B3 B4 B5 B6 B7 B8 ON OFF Dip switch 1 set to OFF: complete draining after 7 days without production being requested (function enabled) Dip switch 2 set to OFF: automatic draining with or without electrode power supply (electrodes not supplied) Dip switch 3 set to OFF: the new production setpoint is reached by means of evaporation cycles when demand is reduced by less than 25%. Draining is achieved by means of evaporation cycles. Dip switch 4 set to OFF: cylinder exhaustion advance warnings (alarms are displayed when the cylinder is approaching exhaustion). Dip switches 5-6 set to OFF: automatic draining time (default setting) Dip switches 7-8 set to OFF: Evaporation time threshold (default setting) The “TA RATE” dip switches are left in their default positions since an external TAM is being used

Jumper setting on external TAM In the AMICO models used, the jumper must be placed in position 100 (end of scale is quantified in amperes 100=10 amperes) LEONARDO/BIG UNIT CP1 CONFIGURATION (MD/MU ……._ D.G. _ 3 ) LEONARDO/BIG unit (three-phase OEM): Nominal steam flow will be reduced by 50% (4 kg/h) for Leonardo 1-2 frame and by 75% (6 kg/h) for Leonardo 3-4 frame and Big units. Dip switches type A (alarm relay and maximum production settings) A1 A2 A3 A4 ON X OFF X Dip switch 1-not used

Page 12: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

12 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized (contact closed) Dip switch 3 set to ON Dip switch 4 set to OFF . Dip switches type A (alarm relay and maximum production settings) A1 A2 A3 A4 ON X OFF X Dip switch 1-not used Dip switch 2 set to ON: Relay not energized (contact open) with at least one alarm active, otherwise energized (contact closed) Dip switch 3 set to OFF Dip switch 4 set to ON Dip switches type B (auxiliary functions and automatic draining time) B1 B2 B3 B4 B5 B6 B7 B8 ON OFF Dip switch 1 set to OFF: complete draining after 7 days without production being requested (function enabled) Dip switch 2 set to OFF: automatic draining with or without electrode power supply (electrodes not supplied) Dip switch 3 set to OFF: the new production setpoint is reached by means of evaporation cycles when demand is reduced by less than 25%. Draining is achieved by means of evaporation cycles. Dip switch 4 set to OFF: cylinder exhaustion advance warnings (alarms are displayed when the cylinder is approaching exhaustion). Dip switches 5-6 set to OFF: automatic draining time (default setting) Dip switches 7-8 set to OFF: Evaporation time threshold (default setting) The “TA RATE” dip switches are left in their default positions since an external TAM is being used Jumper setting on external TAM IN LEONARDO/BIG MODELS, THE JUMPER MUST BE PLACED IN POSITION 100 (END OF SCALE IS QUANTIFIED IN AMPERES 100=10 AMPERES)

50% of nominal steam flow FRAME 1-2 BIG

75% of nominal steam flow FRAME 3-4 & BIG

Page 13: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 13 (44)

LIST OF ALARMS Alarm state is active when the LEDs flash, and their type is described in the following tables.

Page 14: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

14 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

Page 15: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 15 (44)

Page 16: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

16 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

DISPLAY

The display shows the main controlled quantities and the operating status of the unit and its components. Below are the symbols on the display, and their meanings.

The symbol indicates that the display is showing the temperature and relative humidity values instantaneously measured in the environment, plus the relevant measurement units. Temperature may be in Centigrade of Fahrenheit (see paragraph “DISPLAY OF UNIT STATUS”.

When you access the parameter programming mode (providing the symbol is absent) the value and code of the parameters are shown (set-point,….).

Programming (reading and modification of parameters). If flashing, the value of a parameter is being modified.

Always lighted: operating mode – automatic or manual.

OFF status from hour bands.

Unit status (from outside contact): - ON : unit enabled; - OFF : unit on stand-by.

Activation or disabling of the unit is obtained through a remote command (with parameter HE=1) only.

OFF status from remote command

Display of operating hours of devices and clock functions.

Day of the week (1 = Monday,….7 = Sunday)

An alarm status is present. If P4≠0 (see paragraph “READING OF ALARMS HISTORIC RECORD”) is selected, the buzzer is active.

Dehumidification activated.

Heating activated. Indicates heating power

as the opening % of the hot water valve ( ) or as the number of activated heating elements.

Ventilation activated.

Humidifier activated; indicates the steam production percentage.

Cooling activated. Indicates cooling power as the opening % of the cooled water valve

( ) or as the number of activated compressors.

Indicates the compressor operation hour-counter.

All keys locked. To unlock the keyboard, access with the USER password and reset the USER Hi parameter to 0 value (see paragraph “THE KEYBOARD”).

PASSWORD input requested.

Page 17: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 17 (44)

KEYBOARD

The main control statuses (power ON, alarm active, and unit ON) are shown to the user by the lighting of keys on the front panel

ON

OFF (green light) The unit is ON.

(red light) Machine in alarm status.

(yellow light) Power ON: the control is powered.

Display information:

ON

OFF Changes unit status: if ON, pressing the key puts the unit on Stand-by; vice-versa, if the unit is on stand-by, pressing the key will turn ON the unit.

In case of an alarm (the symbol will appear on the display ), it enables the alarm to be shut off. The alarm sound is heard only when the parameter P4 is other than zero (see “ACTIVE ALARMS”). When the power is returned ti the unit press the button in order to reset default values.

When programming, parameter values can be increased

When programming, parameter values can be reduced.

When programming, you can select the value of a parameter, modify it, and confirm its value after modification.

Takes you back to the STATUS MASK to display the unit’s operating status.

Used to scroll through the list of menus in sequence: "Prob", "SetP", "Com", "FAn", "ALAr", "GLb", "Cloc", "AlPG".

If this key is pressed repeatedly, the following are shown cycle-wise: current time, date, room air temperature, operation hour-counters, and the software version.

Functions as an “Exit” key to return to the previous mask.

For scrolling parameters in sequence in the following menus: "Prob", "SetP", "Com", "FAn", "ALAr", "GLb", "Cloc", "AlPG".

2 sec If held down for 2 seconds, it resets the alarm provided the alarm cause was eliminated. If pressed down together for 5 seconds (as from the STATUS MASK) you can access the programming mode for reading and modifying FACTORY parameters.

( + ) 5 sec

If pressed down together for 5 seconds the hour-counters can be reset (but only if the display shows the hour-counter parameter in the USER parameters programming mode).

5 sec If pressed for 5 seconds, you can access the programming mode for reading and modifying USER parameters.

( + )

( + )

Used for adjusting the contrast of the LCD display according to the visual angle being used (starting with the STATUS MASK) If the keys shown here are pressed simultaneously, contrast is increased or reduced.

Page 18: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

18 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

The functions associated with the keys can be disabled by setting the USER Hi=1 parameter (see paragraph “ACCESS TO PARAMETERS WHILE CONSULTING OR PROGRAMMING”). GLb GENERAL INFORMATION Minimum Maximum Measurement

unit Default

Hi Prevents unauthorised operators from modifying parameters (the “padlock” symbol is shown). 0 = no lock 1= lock out of all functions for modifying parameters, and resetting alarms and hour-counters (except access to the USER password and keyboard power down) – the padlock symbol is shown on the display).

0 1 flag 0

INFORMATION ON DISPLAY WHEN UNIT IS OFF STATUS MASK When the unit is powered up but not running, the STATUS MASK is shown on the display indicating the following active fields:

A. Room temperature, room relative humidity (with humidity sensor only);

B. The indication:

• “ ” and " ": unit turned OFF from a remote contact or a Supervisor;

• " unit turned OFF according to set hour bands.

C. Unit turned OFF due to alarm status:

MENU

PARAMETER

DESCRIPTION

Page 19: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 19 (44)

UNIT START-UP CONDITIONS In order for the unit to be Started-up it is necessary that there are no active alarms, that the control programme receives power and that one of the following conditions is verified:

• Check that the yellow light of key is lighted (control powered up);

• Check if the red light of key is OFF (no alarm activated);

• The operator must have pressed key ON

OFF so that the green light on the key is lighted and the fan symbol appears on the display;

• if the remote input was selected (USER parameter HE=1), digital input ID1 must be in the closed contact position. The words on the display refer to the status of the conditioner.

• if the supervisor is connected and the unit is configured (see USER parameters Ho and HP), the unit must be enabled by the supervisor;

• If using daily or weekly hour bands, they must enable power up of the control;

SWITCHING THE UNIT ON AND OFF The unit can be switched ON in one of the following modes:

Local MODE from keyboard: the unit is commanded by the ON

OFF push-button (when first pressed, the unit starts, and when pressed again, it stops. Start-up can be delayed by a time period equal to the value of the USER HG parameter. In Direct expansion units, the control commands the compressor to start so that the starting and stopping cycles are not too close. Compressor start-up can be delayed with respect to pressure of the ON/OFF key (also see parameter FACTORY c7). The unit’s current status is stored in the memory; when power is restored, the unit returns to its status before power failure, and restarts if it had been running. GLb GENERAL INFORMATION Minimum Maximum Measurement

unit Default

HG

Delayed start up. During this phase all unit components remain off. 0 300 sec 0

Com COMPRESSOR Minimum Maximum Measurement unit

Default

C7

Compressor start-up delayed by start-up of fan. 0 300 sec 60

The stop of the unit’s fan is delayed with respect to pressure of the ON/OFF push-button by a time period equal to

FACTORY parameter Fd (default = 10 seconds). While the unit is OFF, the symbol flashes on the display. Fan FANS Minimum Maximum Measurement

unit Default

Fd

Fan switch-off delay (FACTORY). 0 900 sec 10

Automatic MODE: the control is configured so that the unit is started and stopped as follows: 1. a remote ON/OFF contact (the symbol “ ” appears on the display); 2. a supervision system (possible only in units equipped with a serial circuit); 3. programmable hour bands (only in units equipped with a clock circuit).

Page 20: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

20 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

STATUS MASK

The unit’s function parameters (temperature, humidity, ….) can be read by pressing key

INFORMATION ON DISPLAY WHEN UNIT IS ON STATUS MASK When the unit is running, the STATUS MASK is shown on the display, with the following active fields:

B. Room temperature, room humidity (with humidity sensor only); If the measured temperature and humidity values are incorrect, the sensors can be calibrated as described in paragraph “SENSOR CALIBRATION”.

C. Currently operating functions: the following symbols are lighted according

to work conditions:

D. Unit commanded from a remote contact or a Supervisor.

E. Fans operating automatically.

On standard units (with F1=0 parameter) the fans always run at 100% therefore, the symbol displayed on the right is always OFF.

F. Abnormal status:

• “ ”: turns on during alarm event;

• " ": flashes if the threshold of a work hour-counter was exceeded.

Page 21: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 21 (44)

UNIT STATUS DISPLAY

The unit’s function parameters (temperature, humidity, ….) can be read by repeatedly pressing key At the end of the reading cycle, you return to the initial STATUS MASK.

If you press key you immediately return to the STATUS MASK. The display shows only information and data concerning the selected configuration (e.g. time and date appear only in controls equipped with a clock card).

Whenever key is pressed, the following are shown in sequence: - FA: fan hour-counter; - Fc: air filter hour-counter; - c9: compressor 1 hour-counter (for DX-DX/S units only) - cA: compressor 2 hour-counter (for DX units only) - ro: external air temperature (from SE sensor) - rP: relative humidity (from STU sensor) - rr: delivery temperature (from STM sensor) - hours: minutes (with optional clock card only) - day-month-year (with optional clock card only) - Hr: software version.

0 FA

0 Fc

0 c9

0 cA

23.9 ro

53.0 rP

17.2 rr

2 10:54

3 - 4 - 01

1.6 Hr

By using parameter C, you can select a temperature measurement unit. As this parameter varies, the UG30/mP30 control automatically converts all the configuration parameters (set-point, differentials, etc….). The measurement unit being used is constantly shown on the display. Note: If the Centigrade to Fahrenheit (and vice-versa) changeover is effected by the supervisor, the parameters are not converted (all that changes is the value read by the temperature sensors and the symbol on the display).

Prob SENSORS Minimum Maximum Default

/C Measurement unit 0= Centigrade (°C) is used 1= Fahrenheit (°F) is used

0 1 0

SEtP ADJUSTMENT Measurement unit

ro B2 sensor reading (external air temperature) Only shown if sensor installed.

°C

rP B3 sensor reading (humidity percentage). Only if sensor installed. %R.H. rr B4 sensor reading (delivery air temperature) Only shown if sensor

installed. °C

Page 22: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

22 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

ACCESS TO PARAMETERS

WHEN CONSULTING OR PROGRAMMING Control parameters are read and programmed on the control keyboard:

1. ACCESS IN READ ONLY MODE : data can be consulted but cannot be changed;

1.a. press key to go to the STATUS MASK.

1.b. repeatedly press key to scroll the following menus in sequence: "Prob", "SetP", "Com", "FAn",

"ALAr", "GLb", "Cloc", "AlPG". The menus are presented cycle-wise: if you press key again after

“AIPG”, you return to the “Prob” menu. The symbol appears in the bottom left corner of the display.

1.c. press key to access the first parameter of each menu and key to scroll through the successive menus in sequence (see the masks flowchart in the APPENDIX ). The value of the parameter is shown at the centre of the display, while the parameter code is shown at top right.

The parameters are grouped in menus as shown in the following table:

MENU PARAMETERS

… sensor parameters

r … adjustment parameters (e.g. r1 = cooling set-point)

c… compressor management parameters

F … fan management parameters

P… alarm management parameters

H… general configuration parameters

clock function parameters

alarms historic record

1.d. press key once to return to the initial menu selection mask (see point 1.b.).

1.a. press key again to return to the STATUS MASK.

Page 23: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 23 (44)

EXAMPLE: humidity set-point reading (parameter “r5”).

Prob SetP

23.9°C %rH53

23.0 r1

…. …. 50.0 r5

(*) SetP

23.9°C %rH53

(*) Parameter r5 (= Humidity set-point); Value = 50.0%.

2. ACCESS IN PROGRAMMING MODE (READING AND WRITING) with USER password: USER parameters can be modified:

2.a. press key to go to the STATUS MASK.

2.b. press key for 5 seconds to view the “USER“ password request mask. Symbol appears in the bottom left corner of the display; the abbreviation "uP" (="USER PASSWORD") is shown in the top right corner and value “0” flashes at the centre of the display.

2.c. Input the USER password (see envelope enclosed with the manual) with keys and .

2.d. Press to confirm the value. If the password is incorrect, you automatically return to the status mask (see point 3.a.). If the password is correct “Prob” is shown on the display.

2.e. repeatedly press key to scroll the following menus in sequence: "Prob", "SetP", "Com", "FAn",

"ALAr", "GLb", "Cloc", "AlPG". The menus are presented cycle-wise: if you press key again after

“AIPG”, you return to the “Prob” menu. The symbol appears at bottom left of the display.

2.f. press key to access the first parameter of each menu and key to scroll through the menus in sequence (see the masks flowchart in the APPENDIX ). The value of the parameter is shown at the centre of the display, while the parameter code is shown at top right.

2.g. press key to modify the displayed parameter. Symbol will start to flash.

2.h. Input the value of the parameter with keys and .

2.i. Press key to confirm the value of the parameter. The symbol will stop flashing.

You can, from any point, press key to go back by one mask or press key to return to the STATUS MASK.

Page 24: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

24 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

EXAMPLE: modifying the humidity set-point (parameter “r5”).

(press for

5 seconds) 0 uP …. ** uP

23.9°C %rH53

**: input the “USER” password contained in

the envelope enclosed with the manual.

Prob

SetP

23.0 r1

…. 50.0 r5

50.0 r5 55.0 r5

….

55.0 r5

23.9°C %rH53

This is the meaning of symbol shown on the display: - on with steady light: access to masks is in read only mode;

- on and flashing : access to masks is in programming mode;

Page 25: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 25 (44)

3. ACCESS IN PROGRAMMING MODE (READING AND WRITING) with FACTORY password: FACTORY parameters can be modified:

3.a. press key to go back to the STATUS MASK.

3.b. simultaneously press keys and for 5 seconds to view the “FACTORY” password request

mask. Symbol appears in the bottom left corner of the display; the abbreviation "FP" (="FACTORY PASSWORD") is shown in the top right corner and value “0” flashes at the centre of the display.

3.c. Input the FACTORY password (contact the technical service centre) with keys and .

3.d. Press to confirm the value. If the password is incorrect, you automatically return to the status mask (see point 3.a.). If the password is correct “Prob” is shown on the display.

3.e. repeatedly press key to scroll the following menus in sequence: "Prob", "SetP", "Com", "FAn",

"ALAr", "GLb", "Cloc", "AlPG". The menus are presented cycle-wise: if you press key again after

“AIPG”, you return to the “Prob” menu. The symbol appears in bottom left corner of the display.

3.f. press key to access the first parameter of each menu and key to scroll through the menus in sequence (see the masks flowchart in the APPENDIX ). The value of the parameter is shown at the centre of the display, while the parameter code is shown in the top right corner.

3.g. press key to modify the displayed parameter. Symbol will start to flash.

3.h. Input the value of the parameter with keys and .

3.i. Press key to confirm the value of the parameter. The symbol will stop flashing.

You can, from any point, press key to go back by one mask or press key to return to the STATUS MASK.

After you have modified the machine configuration parameters, to ensure correct operation right away, we advise you to reset the control by turning off power.

Page 26: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

26 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

EXAMPLE: modification of parameter 3 (delivery air presence "B4").

(press

simultaneously 0 FP

….

23.9°C %rH53 for 5 seconds)

…. ** FP

**: ask your nearest technical service centre for the FACTORY password

Prob

0 1

…. 0 3

0 3

1 3

1 3

23.9°C %rH53

Meaning of symbol shown on the display: - on with steady light: access to masks is in read only mode;

- on and flashing : access to masks is in programming mode;

CHANGING THE PASSWORD

The password for all FACTORY parameters can not be modified; the password of the USER parameters can be modified through parameter HH.

GLb GENERAL Minimum Maximum Default HH USER Password 0 200 (**)

(**) the USER password is contained in the sealed envelop enclosed with the Instruction Manual.

Page 27: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 27 (44)

HARDWARE CONFIGURATION The units control programme must be adapted to the unit in which it is installed and therefore it must be “configured”. During this phase it is important to define all the elements that are part of the unit and that the Microprocessor will have to control. Normally this operation is performed when the Control programme is installed on the unit, this operation is performed in the FACTORY during final commissioning. It may however be necessary to modify the Control programme due to variations carried out on the unit. GLb GENERAL Min. Max Default H1 Unit model:

0 = DX-DX/S unit 1 = CW-CW/S unit

0 2 (*)

H5 Functioning mode of cooling out puts OUT1 and OUT2: 1 = one compressor 2 = two compressors on two circuits 3 = valve (three points) 5 = two compressors in TANDEM on one circuit

1 5 (*)

H6 Functioning mode of heating out puts OUT3 and OUT4: 0 = no heating elements 1 = one heating phases (**) 3 = hot water valve (three points ) 4 = three heating phases

0 4 0 / 3 / 4 (on CW) 0 / 1 / 3

(on CW/S)

(*)

H8 Humidifier present: 0 = no 1 = si

0 1 (*)

H9 Type of dehumidification: 0 = start up of compressor n.1 (for DX units with 1 compressor on each refrigerant circuit) 2 = start up of all compressors (for DX single circuit units fitted with a TANDEM compressor) 3 = override the opening of the chilled water valve (for CW units) 5 = fan speed reduced with compressor n°1 switched on (for DX/S units) 8 = overriding cold ramp and reducing fan speed (for CW/S units)

0 8 (*)

(*) DEFAULT values depend on the type of unit (DX-DX/S-CW-CW/S), the number of compressors and the construction

version of the unit (C, T, D, H). (**) in T-version AMICO units with standard heating elements, parameter H6 always has the value 1. In units with more

powerful heating elements (models 0331-0601 and 0200-0600), it has the value 3.

Page 28: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

28 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

OPERATING HOUR-COUNTER

The UG30/mP30 control displays the operating hours of the units main components. By using the “hour-counter threshold” parameters, the maintenance intervals for each component can be established. When the device in question exceeds the indicated value, the processor signals the maintenance request by activating an alarm signal and showing the symbol in the top right corner of the display. To modify the hour-counter thresholds, first have access the parameters in the programming mode (USER password ). Com COMPRESSOR Minimum Maximum Measurement

unit Default

c8 Hour-counter threshold for compressors operation. It establishes the number of compressor operating hours beyond which the maintenance request is signalled. If c8 = 0 is selected, the function is disabled.

0 30000 Hours 0

FAn FANS Minimum Maximum Measurement unit

Default

F9 Hour-counter threshold for fan (0=hour-counter disabled) 0 30000 Hours 0 Fb Hour-counter threshold for filter (0=hour-counter disabled) 0 30000 Hours 1000

With the “hour-counter” parameter, the number of hours accumulated by the unit’s component can be read. If you

press keys and for a few seconds, the hour-counter is reset. This operation is executed in programming

mode only, when the symbol flashes.

Com COMPRESSOR Minimum Maximum Measurement unit

Default

c9 cA

Compressor 1 hour-counter Compressor 1 hour-counter Indicates number of operating hours of compressor 1 and/or 2

0 30000 hours 0

FAn FANS Minimum Maximum Measurement unit

Default

FA Fan hour-counter. Indicates number of fan operating hours. 0 30000 hours 0 Fc Filter hour-counter. Indicates number of filter operating hours.

This hour-counter is increased only if the fan is running. 0 30000 hours 0

EXAMPLE: resetting the filter hour-counter (“FC” parameter).

(press for 5 seconds) 0 uP

…. ** uP

23.9°C %rH53

**: input the "USER" password contained in

the envelope enclosed with the manual.

FAn Prob

….

0 F9

…. 1001 Fc

(press keys 1001 Fc

0 Fc

+ Simultaneously for at least 5 seconds)

Page 29: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 29 (44)

EXCEEDED HOUR-COUNTER THRESHOLDS

If the hour-counter threshold is exceeded, the only response is a signal by the control, however, this is not a true alarm status and does not shut down the unit. h c : C 1 Alarm: Compressor 1 hour-counter exceeded h c : C 2 Alarm: Compressor 2 hour-counter exceeded h c : F i Alarm: air filter hour-counter exceeded h c : u F Alarm: re-circulation fan hour-counter exceeded

MAINTENANCE OF HUMIDIFIER CYLINDER

The control does not measure the humidifier operating hours, however, lime scales must be periodically cleaned off the steam cylinder. Excessive lime scales can cause malfunctions or an alarm signal by the humidifier interface circuit. Before the cylinder is removed for replacement or cleaning, water must be thoroughly drained from the boiler. This command is not given directly by the UG30/mP30 control, but by the CDA303 circuit.

Note: To prevent tripping of the differential on the distribution panel, dip-switch N°7 is turned ON: In this way, the CU contactor is de-energised during discharge and, as a result, there is no current dispersion.

To open the solenoid discharge valve and empty the cylinder, you must switch the “MANUAL DRAINING” jumper contacts on the CP1 card from GND-ON (automatic) to GND-DR (manual).

Attention: electronic components are sensitive to static charges emitted by the human body. Touch a grounding facility before handling any electronic component. - Open the humidifier thermal breaker; - Clean or replace the cylinder; - After cleaning or replacing the cylinder, re-position the component and restore normal humidifier operation.

Page 30: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

30 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

REMOTE CONTROL OF UNIT The unit can be started and stopped alternatively by : 1. a remote contact (or “remote control”); 2. a “supervision system” connected to the microprocessor by a serial cable. ON/OFF FROM REMOTE CONTACT: the unit is started via the ID1 digital input. When the input is open, the unit is on stand-by signalled by the “OFF” symbol on the display. If, instead, 24V is supplied, the unit is powered up (signalled by the “ON” symbol on the display). GLb GENERAL Minimum Maximum Default HE ON/OFF digital input: enables the ID1 digital input as a remote ON/OFF.

0= absent 1= present, disables ON/OFF switching from the keyboard. 2= absent, disables ON/OFF switching from the keyboard (only in the case of supervision systems)

0 2 0

SUPERVISION SYSTEM A supervision system exchanges data via serial cable with the unit’s basic circuit which is remotely commanded and controlled: to this end, the RS485 Serial Circuit (optional) must be present. GLb GENERAL Minimum Maximum Default Ho Serial address in the RS485 supervision network. 1 200 1 HP Supervisor serial Baudrate. It sets the line speed on the RS485 supervision

network. 1= 1200 Baud 2= 2400 Baud 3= 4800 Baud 4= 9600 Baud 5= 19200 Baud

1 5 5

Page 31: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 31 (44)

CONNECTING MORE THAN ONE UNIT It is possible to electronically connect up to 6 units on the same local network connection, where 5 units run in normal operation and 1 unit in stand-by. In order to distribute the work load an automatic unit rotation is managed, it works on a temporal base at programmable time intervals (FACTORY H4 parameter). When necessary 1 of the units is turned off and the unit in stand-by is activated. The rotation follows the progressive order of the addresses set (FACTORY H3 parameter). If an Alarm event occurs on one of the units connected the control automatically activates the unit in Stand-by (serious alarms are specified in the section entitled "DESCRIPTION OF ALARM CODES"). IMPORTANT: the Units are electrically connected using digital output DO7 and digital input ID5 (see electric drawings), therefore the connection can not be made in the following cases: - for units that are already using the digital output DO7 for the dehumidification electrovalve(CW-DX air-conditioners) or for reporting of a non-serious alarm status (CW/S-DX/S air-conditioners). - for units that are already using the digital in put ID5 for the connection of optional digital sensors (high/low temperature/humidity sensors, water leak detector). After having performed the electrical connection between the units , it is necessary to modify the parameters "GLb": H2, H3, H4 ed HA. GLb GENERAL Min. Max Measurement

unit Default

H2 Number of units connected: 0 = stand-alone unit; 2…6 = total number of units connected.

0 6 - 0

H3 Address for unit connected for rotation. Each unit must have a different address between 1 and 6. If two units have the same address then they will be placed in stand-by.

1 6 - 0

H4 Rotation time between the units in hours. If H4 = 0 the control will perform a test, the units will rotate at intervals of 2 minutes.

0 250 hours 168

HA Digital output configuration DO7: 0 = excited relay in dehumidification (CW unit) 1 = de-energize in dehumidification (DX unit) 2 = alarm relay for non-serious alarms (CW/S-DX/S only) 3 = output for rotation control

0 3 - 3

Page 32: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

32 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

TEMPERATURE SET-POINTS To change set-points, you have to input the “USER” password to access the “SetP” menu in programming mode. SEtP SETTING Minimum Maximum Measurement

unit Default

r1 Temperature (summer) set-point. Used for setting the cooling set-point. 0 50 °C 23 r2 Cooling differential. 0.1 11.0 °C 1.5 r3 Heating differential. 0.1 11.0 °C 1.5 r4 Temperature neutral zone.

When the temperature measured by sensor B1 is within the neutral temperature zone, all actuators are OFF, except in the following cases: • Minimum ON time or the switch-off delay between the two compressors has not elapsed yet; • the compressors (or the valve) are operating following a dehumidification request.

0.1 20.0 °C 0.2

rn Delivery temperature lower limit.

When the temperature read by delivery sensor B4 drops by 3°C below the set limit (default = 15°C), the cold actuators (compressors or refrigerated water valve) are switched off. The actuators are automatically restored when temperature rises back to rn value.

-20 30 °C 15

temperatura ambiente da sonda B1

100% 100%

r1

r3 r2

SET POINT DI TEMP.

(Default 1.5°C)

(Default 23°C)

(Default 1.5°C)

Zona neutraper la temp.

VALVOLA ACQUACALDA

VALVOLA ACQUAFREDDA

r4(Default 0.2°C)

temperatura ambiente da sonda B1

r1

r3 r2

SET POINT DI TEMP.

(Default 1.5°C)

(Default 23°C)

(Default 1.5°C)

Zona neutraper la temp.

RESISTENZE COMPRESSORI

r4(Default 0.2°C)

C2

C1R1

R2

R1+R2

Page 33: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 33 (44)

HUMIDITY SET-POINT

SEtP SETTING Minimum Maximum Measurement

unit Default

r5 Humidity set-point 20 90 %R.H. 50 r6 Humidification differential. 1 20 %R.H. 5 r7 Dehumidification differential. 1 20 %R.H. 5 r8 Humidity neutral zone. When the temperature measured by sensor B3 is

within the neutral temperature zone, the 0-10V output, which activates the humidifier, equals 0 and dehumidification is not active.

0 20 %R.H. 10

umidità ambiente da sonda B3

10Vdc ON

r5

r6 r7

SET POINT DI UMIDITÁ

(Default 5%)

(Default 50%)

(Default 5%)

Zona neutradi umiditá

UMIDIFICA DEUMIDIFICA

r8OFF

(60%)(40%)

(Default 10%)

CALIBRATION AND SETTINGS By using parameters 6, 7, 8, 9 the measurement of the sensors can be corrected if a difference is noted between the value measured by the sensor and the effective value measured by a precision instrument. Prob SENSORS Minimum Maximum Measurement

unit Default

6 B1 sensor calibration. Room temperature. -6.0 6.0 °C 0

7 B2 sensor calibration. External air temperature. -6.0 6.0 °C 0

8 B3 sensor calibration. Room relative humidity. -10 10 %R.H. 0

9 B4 sensor calibration. Delivery temperature. -6.0 6.0 °C 0

Page 34: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

34 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

CLOCK/DATER – TIME BANDS (with optional clock circuit only) SETTING THE DATE AND TIME To modify date and time, you have to input the “USER” password to access the parameters of the “Clock” menu in programming mode.

(press for 5 seconds) 0 uP

…. ** uP

23.9°C %rH53

**: input the “USER” password contained in

the envelope enclosed with the manual.

…. …. Prob

Cloc

2 10:39

2 10:39

…. 2 10:54

SETTING THE TIME-BANDS If using controls with an optional clock circuit fitted, you can set the automatic start-up and stop of the unit on a time basis (time-bands) obtaining up to 2 daily ON-OFF cycles. N.B.: The ON status from time-bands operates only if the unit is activated from the keyboard and from a remote input. Enabling of time-bands is through the following parameter: Cloc Minimum Maximum Default rt 0= time-band disabled

2= ON/OFF from time-bands 0 2 0

Page 35: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 35 (44)

To enable the time-bands, enter the “Cloc” menu and select the rt=2 parameter.

…. Cloc

….

2 10:39

0 rt

0 rt

2 rt

2 rt

…. (*)

(*) if you press key you can view the time-bands in sequence for every day of the week: 1 (Monday), 2 (Tuesday),… 7 (Sunday).

Keys and can be used to modify the starting time of the selected band in 10-minute steps. on the display indicates unit switch ON time, and indicates switch OFF time.

…. 1 ON 8:30 rt

1 ON 8:30 rt

1 ON 8:40 rt

1 OFF 19:00 rt

….

If the hours of the time-bands of a given day are valid for the following days too, they can be copied by holding down

key for 3 seconds. On completion of copying, symbol automatically stops flashing and the next day is displayed. If the next day

has to be copied as well, release key and then press it again for another 3 seconds. MANUAL OVERRIDE START OR STOP

OFF status from time-bands can be viewed by means of the symbol on the display; the unit is put on stand-by as if the ON/OFF key had been pressed. However, the unit can be manually forced to start.

Access the “Cloc” menu, view the hour-band that caused the OFF status, and then press the ON

OFF key to restart the unit,

…..

Cloc …..

23.9°C %rH53

…..

1 OFF 19:00 rt

1 OFF 19:00 rt

ON

OFF

1 ON 19:00 rt

Page 36: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

36 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

DELAYS DUE TO ALARM SIGNALS

Some alarm signals can be delayed with respect to the activation of a component to allow stable operating conditions to be reached – for example: � Alarm A:FL (airflow absent or presence of fire-smoke) is not read during the first 30 seconds after fan start; this

value is linked to the FACTORY P1 parameter. � Alarms LO:C1 and LO:C2 (1/2 circuit low pressure) are not read during the first 180 seconds after start-up of

the relevant compressor. This value is linked to the FACTORY parameter P3. ALAR ALARM Minimu

m Maximum Measurement

unit Default

PA Delay of low/high temperature/humidity alarm at start-up. This establishes the delay in recognising low/high temperature and humidity alarms at UNIT start-up. N.B.: The low humidity alarm is delayed at humidifier start-up. This is to avoid a low humidity alarm when a possible humidifier alarm is reset.

0 150 min 15

PC General alarm delay. This establishes the activation delay of the ID5 general alarm.

0 250 sec 0

P1 This establishes the delay in recognising the flow alarm from start of fan. 0 250 sec 30 P2 This establishes the delay in recognising the flow alarm while the fan is

operating. 0 90 sec 3

P3 This establishes the delay in recognising the low pressure alarm at compressor start-up to allow reaching a stable situation.

0 250 sec 180

SERIOUS ALARMS

Two different types of alarm warnings are available: "serious " and "non-serious" alarms (see section "DESCRIPTION OF ALARM CODES "). In a configuration with more than one unit connected, serious alarms trigger the activation of the DO7 relay and therefore the activation of the unit in stand-by. In a configuration with no unit rotation, the FACTORY parameters HA and HF can be changed, in such a way as to have two different alarm signals: - "serious alarms" through the general alarm relay DO6; - "non-serious alarms" through the dehumidification relay DO7 (CW/S and DX/S only). GLb GENERAL Min Max Default Setting to manage 2

alarms HA Configuration of digital output DO7:

2 = alarm relay for not critical alarms (follows the logic set through the parameter HF) 3 = output for rotation control

0 3 3 2

HF Alarm relay logic: 0 = de-energise in alarm for all the alarms 2 = de-energise in alarm only for the serious alarms

0 3 0 2

ACTIVE ALARMS When an alarm occurs, the control performs the following actions:

• displays the symbol and the alarm code; • de-energize the DO6 relay (general alarm); the relays functioning logic, normally energised

or de-energised, and the alarm category that activates this relay is set by the HF parameter (default equals 0);

• (in AMICO CW/S and DX/S units, if HA is set to 2) relay D07 de-energised (non-serious alarm); relay logic, normally energised or de-energised, is defined by parameter HF (default setting is 0);

• lights up the red light of key ; • activates the buzzer (if the USER P4 parameter is set at a value other than zero).

Page 37: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 37 (44)

ALAR ALARM Minimum

Maximum Measurement unit

Default

P4 Establishes buzzer activation time in case of an alarm: 0 = OFF (buzzer always disabled) 1-14 = the buzzer is automatically silenced after P4 minutes have elapsed. 15 = continuous. The buzzer remains active until the alarm situation ceases (on automatic reset) or for as long as the Alarm push-button is pressed.

0 15 min 1

All alarms are manually resettable; to reset an alarm press key for about 2 seconds after eliminating the cause.

READING OF THE ALARMS HISTORIC RECORD (with optional clock card only) When an alarm occurs, the following are automatically stored in the memory: alarm code, hour, minute and date on which alarm occurred, up to a maximum of 300 signalling operations. To view the list of stored alarms, enter the “AIPG” menu: the code of the last alarm occurring is shown and, if you

press repeatedly – the hour, minute and date. LP:C1 2

10:29 2

3 - 4 01

If you press key , the list of all the alarms is displayed; when you reach the first position in which no alarm is stored, "- - - -“ dashes are shown instead to the code. The display includes an incrementing index on the right-hand field, which identifies the current position; the hundreds are shown in the left-hand field (E.g.: “1 ---- 55 “, indicate the alarm code stored in position 155). rES 1

LP:C1 2

….

- - - - 3

….

1 - - - - 55

DELETION OF ALARMS HISTORIC RECORD If you access programming mode with the USER password and reach the “AIPG” menu, you can delete the entire

alarms historic record by simultaneously pressing keys and for 5 seconds. This operation re-initialises the clock card EEprom and must be performed when installing the card itself. When you have “cleaned” the alarms page, the "- - - -“ dashes are shown. The displayed alarm codes are those shown in the following chapter; some special codes are also included to report the following events:

Code Meaning PrOn UNIT started after power failure RES Manual reset of alarms by Alarm key.

Page 38: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

38 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

ALARM CODES DESCRIPTION All possible alarm codes are listed below. All alarms, except the clock alarm, are read only with the UNIT ON. Code Description Restart Alarm type C L o C Clock alarm. Manual Non-serious S P : A External general alarm. - Serious

CLoC: clock alarm faulty An alarm generated by a malfunctioning clock card. It causes an interruption of the hour-bands and the regulator goes into ON status even if it is commanded to OFF by the current band. This event does not shut down the alarms historic record function, which continues recording the signals, but with incorrect time values. SP:A external general alarm Alarm configurable with parameters Pb and PC. TEMPERATURE AND HUMIDITY LIMITS EXCEEDED These are signal-only alarms linked to an excess in the set temperature and humidity levels. Code Description Restart Alarm type H I : R H High room humidity alarm. Automatic Non-serious L O : R H Low room humidity alarm. Automatic Non-serious H I : R t High room temperature alarm. Automatic Serious L O : R t Low room temperature alarm. Automatic Non-serious

The thresholds are defined by FACTORY parameters P6, P7, P8, P9 according to the following diagrams. They are ignored during UNIT start-up for a time period equal to the PA parameter (see paragraph “DELAYS DUE TO ALARM SIGNALLING”). The alarm is tripped if the set threshold is exceeded for at least one minute.

T ambiente da sonda B1

HI:RtLO:Rt10°C 30°C SOGLIA DI INTERVENTO DELL'ALLARME

r1

P6 P7

SET POINT DI TEMPERATURA

(Default 13°C)

(Default 23°C)

(Default 7°C)

SEGNALAZIONE DI ALLARME

If the high temperature threshold is exceeded, this causes immediate start-up of the compressors without respecting the relevant times.

rH umidità ambiente da sonda B3

HI:RHLO:RH30% 80% SOGLIA DI INTERVENTO DELL'ALLARME

r5

P8 P9

SET POINT DI UMIDITÁ

(Default 20%)

(Default 50%)

(Default 30%)

SEGNALAZIONE DI ALLARME

Page 39: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 39 (44)

FUNCTIONAL ALARMS Code Description Restart Alarm type A : F L Airflow alarm or Fire /smoke detector alarm Manual Serious C L : F i Air filter obstructed. Manual Serious C o : F A Cooling function alarm. Manual Serious C t : H Compressor/s thermal breaker alarm. Manual Serious F t : H Fan/s thermal breaker alarm. Manual Serious H E : O H Electrical heating elements overheating. Manual Non-serious H P : C 1 - H P : C 2 Compressor 1./2. high pressure. Manual Serious H U : F A Humidifier alarm. L P : C 1 - L P : C 2 Compressor 1./2. low pressure. (***) Serious

A:FL Airflow alarm or optional Fire/smoke detector alarm The alarm can be delayed by parameters P1 and P2 and causes all devices to switch off immediately. CI:F1 dirty filter Signal only alarm. To reset it, reset the filter hour-counter (USER parameter Fc). CO:FA: delivery (or cooling function) high temperature alarm It is read by the B4 delivery temperature sensor when the cooling function is active, but the difference between the delivery air temperature and room temperature is lower than the value defined by the Pd parameter (default 3°C). The alarm has a fixed delay set at 4 minutes and is tripped only if the cold actuators are ON (at least one compressor ON or refrigerated water valve open by more than 50%) and the hot actuators are OFF. When this alarm is noted, it shuts down only the compressor that is ON (running at that moment) , while the second compressor remains enabled. Ct:H compressor thermal breaker alarm Causes instantaneous shut-down of the compressor. Ff:H fan thermal breaker alarm Causes instantaneous shut-down of all devices. HE:OH heating elements thermal breaker alarm Causes instantaneous shut-down of the heating elements. HP:C1-HP:C2 circuit 1 or 2 high pressure Causes immediate shut-down of the compressor without respecting the relevant times. HU:FA humidifier alarm Alarm delayed by 30 seconds. This is detected by the CDA3403 card and is transmitted to the UG30 control which disables the U1 humidifier output. LP:C1-LP:C2 circuit 1 or 2 low pressure This alarm is detected only if the compressor is ON and is ignored during the first 180 seconds from compressors start. It causes immediate shut-down of the compressor without respecting the relevant times.

Page 40: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

40 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

SENSOR INDUCED ALARMS These alarms are generated for open or short-circuited sensors. Code Description Restart Alarm type S E : 1 F Sensor B1 fault. Automatic Serious S E : 2 F Sensor B2 fault. Automatic Non-serious S E : 3 F Sensor B3 fault. Automatic Non-serious S E : 4 F Sensor B4 fault. Automatic Non-serious

SE:1F room temperature sensor fault. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all components, except the fan, are turned OFF, respecting the configured times with the exception of fan time. SE:2F external air sensor fault. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all functions (summer/winter switch-over) associated with the sensor are disabled. SE:3F humidity sensor. Alarm activates when the sensor is disconnected (if the input is configured as 4÷20mA) and for currents that are lower than 3 mA or above 23 mA. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all functions associated with the sensor (humidification, dehumidification) are disabled SE:4F delivery air temperature sensor. Alarm delayed by 1 minute from the moment when the UNIT is turned ON and from when the error is detected. When the error is detected, all functions associated with the sensor (CO:FA alarm management) are disabled.

Page 41: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 41 (44)

DEFAULT VALUES Prob SENSORS Type Minimu

m maximum Measurement

unit Default

/1 Sensor B2 presence (external air temperature) FACTORY 0 1 flag 0,1 /2 Sensor B3 presence (room relative humidity) FACTORY 0 2 flag 0,2 /3 Sensor B4 presence (delivery temperature) FACTORY 0 1 flag 0,1 /4 Humidity value at 4mA FACTORY 0 /5 %R.H. 0.0 /5 Humidity value at 20mA FACTORY /4 100 %R.H. 100.0 /6 Sensor B1 calibration (room temperature) FACTORY -6.0 6.0 °C 0 /7 Sensor B2 calibration (external air temperature) FACTORY -6.0 6.0 °C 0 /8 Sensor B3 calibration (room relative humidity) FACTORY -10 10 %R.H. 0 /9 Sensor B4 calibration (delivery temperature) FACTORY -6.0 6.0 °C 0 /C Measurement unit (0=C,1=F) USER 0 1 flag 0

SEtP REGULATOR Type Minimum

maximum Measurement unit

Default

r1 Temperature (summer) set-point. USER rA rb °C 23 r2 Cooling differential. USER 0.1 11.0 °C 1.5 r3 Heating differential. USER 0.1 11.0 °C 1.5 r4 Temperature neutral zone. USER 0.1 20.0 °C 0.2 r5 Humidity set-point USER rC rd %R.H 50 r6 Humidification differential USER 1 20 %R.H. 5 r7 Dehumidification differential USER 1 20 %R.H. 5 r8 Humidity neutral zone. USER 0 20 %R.H. 10 rA Minimum temperature set point FACTORY -20 rb °C 0.0 rb Maximum temperature set point FACTORY rA 60 °C 35.0 rC Minimum humidity set point FACTORY 0 rd %R.H. 20 rd Maximum humidity set point FACTORY rC 100 %R.H. 90 rE Adjustment type FACTORY 0 1 flag 1 rF Integration time for P+I FACTORY 10 3600 sec 600 rG Enable compensation FACTORY -2.0 2.0 - 0.0 rn Minimum delivery temperature set point FACTORY -20 30 °C 15

Com COMPRESSOR Type Minimum

maximum Measurement unit

Default

c4 Delayed start-up between two compressors FACTORY 0 300 sec 90 (DX-DX/S)c6 Compressor rotation FACTORY 0 1 flag 1 (DX-DX/S) c7 Delayed compressor start from fan start-up. FACTORY 0 300 sec 60 (DX-DX/S)c8 Hour-counter threshold for compressor (0=disabled hour-counter) USER 0 30000 hours 0 (DX-DX/S) c9 Compressor 1 hour-counter USER 0 30000 hours 0 (DX-DX/S) cA Compressor 2 hour-counter USER 0 30000 hours 0 (DX-DX/S)

FAn FANS Type Minimum

maximum Measurement unit

Default

F1 Fan mode functioning FACTORY 0 1 flags 0= no RV 1= con RV

F9 Hour-counter threshold for fan (0=disabled hour-counter) USER 0 30000 hours 0 FA Delivery fan hour-counter USER 0 30000 hours 0 Fb Hour-counter threshold for filter (0=disabled hour-counter) USER 0 30000 hours 1000 Fc Filter hour-counter USER 0 30000 hours 0 Fd Fan delayed switch-off FACTORY 0 900 sec 10

ALAR ALARM Type Minimum

maximum Measurement unit

Default

P1 Delayed flow alarm at start FACTORY 0 250 sec 30 P2 Delayed flow alarm during operation FACTORY 0 90 sec 3 P3 Delayed low pressure alarm at compressor start-up FACTORY 0 500 sec 180

(DX-DX/S) P4 Buzzer activation USER 0 15 min 1 P5 Reset alarms FACTORY 1 5 flag 3 P6 Delta from set for low temperature alarm FACTORY 0 50 °C 13.0 P7 Delta from set for high temperature alarm FACTORY 0 50 °C 7.0 P8 Delta from set for low humidity alarm FACTORY 0 50 %R.H. 20.0 P9 Delta from set high humidity alarm FACTORY 0 50 %R.H. 30.0 PA Alarm start delay high/low temperature /humidity USER 0 150 min 15 Pb Management type general alarm input ID5 FACTORY 0 6 flag 2 PC General alarm delay USER 0 250 sec 0

Page 42: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

42 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

GLb GENERAL Type Minimum

maximum Measurement unit

Default

H1 Unit model FACTORY 0 2 flag 0 (DX-DX/S) 1,2 (CW-CW/S)

H2 Number of connected units FACTORY 0 6 flag 0 1…6

H3 Address of connected unit FACTORY 1 6 flag 1…6 H4 Rotation time between all connected units FACTORY 0 250 ore 168 H5 Functioning mode of chilled water outputs OUT1-OUT2 FACTORY 1 5 flag 3 (CW)

1 (DX/S) 1 / 2 / 5 (DX)

H6 Functioning mode of hot water outputs OUT3-OUT4 FACTORY 0 4 flag 0 / 3 / 4 (CW-DX) 0 / 1 / 3

(CW/S-DX/S)H7 3 point valve excursion time end dumper FC FACTORY 0 600 sec 150 H8 Humidifier present FACTORY 0 1 flag 0 / 1 H9 Dehumidification present FACTORY 0 8 flag 3 (CW)

8 (CW/S) 0 / 2 (DX) 5 (DX/S)

HA Digital output function DO7 FACTORY 0 3 flag 0 (CW) / 3 2 (CW/S) / 3

1 (DX) / 3 2 (DX/S) / 3

Hb Output function Y2 FACTORY 0 2 flag 0 HC Functioning of B2 sensor FACTORY 0 3 flag 0 Hd Functioning of B3 sensor FACTORY 0 1 flag 0 HE Digital input ON/OFF USER 0 2 flag 0 / 1 / 2 HG Delay at power up USER 0 300 sec 0 HH USER Password USER 0 200 - 22 (**) Hi Keyboard lock-out USER 0 1 flag 0 HL Parameters setting FACTORY 0 3 flag 1 Ho Serial address for supervision network USER 1 200 - 1 HP Serial baud rate for supervisor USER 1 5 flag 5 Cloc CLOCK Type Minimu

m maximum Measurement

unit Default

rt Hour-bands setting USER 0 2 flag 0

(**): "USER" password contained in envelope enclosed with manual

MEMORY RESET

With the control programme on, press the button in order to reset the parameter values. After having performed this first step: - Set the default values, see above paragraph “Default Values”; - Configure the devices and the sensors fitted according to the type of unit, adjust the set-points that needed to

be different from the default values.

APPENDIX – mask flowcharts

Page 43: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN 43 (44)

Page 44: k Uniflair Ug30

UG30 Screen Flow Chart - Access password "USER"

(press button for 5

seconds) 00 uP

(insert password

"USER") ** uP (press button

to confirm)

(reading only)

(reading and programming )

(*)

Prob

C

SetP

r1

r2

r3 r4 r5 r6

r7 r8

r9

ro

rP rr

Con

c8

c9

cA

FAn

F9

FA

Fb FC

Page 45: k Uniflair Ug30

ALAr

P4

PA

PC

GLb

H2

H3

H4 HE HF HG

HH Hi

Ho

HP

Hr

Cloc

11:54

3 - 4 - 01

0 rt

AlPG

rES 1

10:37 1

3 - 4 - 01

(alarm history)

LP:C1 2

10:29 1

3 - 4 - 01

return to PROB screen by pressing

again on the button:

Prob

(*)

Page 46: k Uniflair Ug30

UG30 Screen Flow Chart – Access password “FACTORY”

(press on both buttons at the

same time for 5 seconds ) 00 FP (insert password

"FACTORY") *** FP (press button to confirm)

(reading and programming)

(**)

Prob

1

2

3 4 5 6

7 8

9

A

b c

SetP

r1

r2

r3 r4 r5 r6

r7 r8

r9

rA

rb rC ……

Con

c1

c2

c3 c4 c5 c6

c7 c8

c9

cA

Page 47: k Uniflair Ug30

FAn

F1

F2

F3 F4 F5 F6

F7 ……

ALAr

P1

P2

P3 P4 P5 P6

P7 ……

GLb

H1

H2

H3 H4 H5 H6

H7 H8

H9

HA

Hb ……

Cloc

11:54

3 - 4 - 01

0 rt

AlPG

rES 1

10:37 1

3 - 4 - 01

(alarm history)

return to PROB screen by pressing

again on the button:

LP:C1 2

10:29 1

3 - 4 - 01

Prob

(**)

Page 48: k Uniflair Ug30

INSTRUCTION MANUAL

UG30 CONTROL

44 (48 mP30-UG30 - Rev. 1.5 - Date: 18-03-2004 EN

UNIFLAIR ITALIA S.p.A. Via dell’industria, 10 35020 BRUGINE (Padova) - Italy Tel. +39 (0)49 9713211 Fax +39 (0)49 5806906

Internet: www.UNIFLAIR.com E-mail: [email protected]

Man

ual c

ode

@ d

igit:

06M

C03

1 @

00B

0150