kb a1188 industrial gsm &pstn alarm installation guide
DESCRIPTION
Manufacturer & export supplier of security alarm systems, fire & burglar alarms, network alarms, wireless alarms, alarm panel, security kits, online store of security kits.TRANSCRIPT
User's Manual
Network Alarm System
Network Alarm System
1 Summary----------------------- - - -- ---(1)
2 Main Functions & Features 1
3 Working Diagram of System 2
4 Installations 3
4
5 Instruction of Wired Keypad 8
8
9
10
6 Programming Instructions 3
3
5
6
7
7
8
34
7 Operational Manual 38
38
38
39
39
39
40
8 Technologic Parameter 40
9 Notes 4
10 Solutions of Simple Trouble 41
-------------------( )
------------------( )
-----------------------------( )
------------------- ---( )
----------------------- -- - -( )
------------ - - - --( )
------------------- - -( )
------------------------ - - -( )
------------- - ---( )
----------------- --(1 )
-------------------- - - --(1 )
---------------- - -(1 )
--------------- - - - -(1 )
-------------------- ----(1 )
------------------ - -(1 )
--------------- - - - -(1 )
----- -----(1 )
--- - - - -(1 )
------------ - - - -( )
-----------------------( )
---------- - - - -( )
-------------------( )
--------------- - - - - -( )
----------------- - - -( )
---------------- - - - -( )
------------------ ------( )
------------------ - -( )
----------------------- ------( 1)
-------- ---- - --( )
4.1 Installing Preparation 3
4.2 Installations
5.1 Technologic Parameter
5.2 Installations
5.3 Instruction of LED indicator
5.4 Instruction of Sound Hint 2
5.5 How to Program 2
6.1 Definition of Zone Type
6.2 Factory Setting
6.3 Programming the Panel
6.4 Programming Remotely
6.5 Programming Table of the Alarm Panel
6.6 Programming Commands of the Alarm Panel
6.7 Setup logs of the Alarm Panel
7.1 Instruction of Operator Interface
7.2 Operational Combination
7.3 How to Arm/ Disarm
7.4 How to Activate Alarm
7.5 How to Receive Alarm
7.6 Remote Setting
-
-
-
-
---
-
Table of contents
Network Alarm System
Standard Packaging
Optional Packaging
Alarm panel 1pc
Wireless remote controller 2pcs
Keys of panel 2pcs
Antenna 1pc
2.2K EOL resistor 6pcs
Tap combination screws 3pcs
Mechanical fixings 3pcs
User's Manual 1pc
Wired intelligent keypad
Real-time module
Warning board
GSM module
SD module
Network Alarm System
-1-
1 Summary
2 Main Functions & Features
The Network Industrial Alarm System is the double-network burglar alarm
system with design of a detachable keypad. It adopts with wired telephone
network and GSM wireless network to transmit the alarm signal. There are
12 zones (6 wired zones and 6 wireless zones). It can be collocated with
wireless remote controller, wired/ wireless PIR detector, wired/ wireless
door sensor, hands-on switch, feet-picked switch and wired/wireless siren,
etc., and consist of a security protection system of Burglar, Fire, Gas and
Emergency status. 8 groups of alarm telephones can be set, such as alarm
command center, mobile telephones and telephones. Once there is alarm
occurring, the alarm panel will activate the siren on-site to make sound. At
the same time, the alarm panel will dial the preserved telephones or make
alarm to ADEMCO Contact ID alarm center directly. It is very suitable for
security services, business places, financial constitutions and enterprises.
With design of detachable keypad and alarm panel. The system can be
expanded to 4 keypads and each keypad with a wired zone.
●
●
●
●
●
●
●
●
●
●
●
●
●
●
Compatible with wired/ wireless. 6 wired zones and 6 wireless zones can
be learned. Each wireless zone can expand up to 3 detectors.
Access codes: 1 installer code + 4 master codes + 4 users code.
Support CONTACT ID protocol: it makes test with alarm center terminal
to guarantee the normal working of alarm system.
Support Close Arm type.
Support report of patrolling.
It can realize to control remotely and Arm/ Disarm to the alarm system by
the software of network alarm center. (The eighth alarm telephone as the
remote controlling programmable telephone) (Only for version V1.6)
The advanced function of telecommunication re-dialing makes sure the
reliability of the alarm report, especially when the telecommunication is
occupied.
Home Arm and Overall Arm. The zones list of Home Arm can be defined at
will.
One group of NC & NO relay output interface to set various alarm output.
Anti-false intelligent alarm function: it can reduce the time of false alarm
by judging the logic function between the crossover zones.
Eight groups of telephones, mobile telephones and alarm center
telephones can be set. Also it can set the alarm type of every group of
telephone and the zone list of communication.
It rushes to inform you the alarm message by halting the speaking on
telephone, and then recovers the speaking automatically.
Remote Arm, Disarm and on-site alarm setup on the preserved telephones,
Network Alarm System
-2-
mobile phones or the telephones connected with panel.
●
●
●
●
●
●
●
●
Wired zone reaction speed (100ms-900ms) and support Normal Open,
Normal Close and end-of-line resistor at freedom.
The trouble of telephone line and GSM module can be reacted on the
keypad's buzzer or wired/ wireless siren output.
Both AC220V and 12V, 7Ah rechargeable battery power supplied and
switched each other automatically. The low battery can reminder the host.
The design of power-output limitation is to protect the electronic circuit.
The Real-time module endows the system with two timers can be set to
Arm/ Disarm independently according to the arrangement of the working
days and resting days. Every timer can set Arm/ Disarm of each zone
independently.
GSM module is for option. It is more stable by realizing PSTN and GSM
double-network alarm. Alarm by double-network or only by GSM
network when telephone line is cut off.
GSM module is for option. It can realize sound and SIM message alarm
and support ADEMCO CID center.
SD module is for option. It can monitor the on-site alarm status. It can link
and record the alarm on-site. Then store it into SD card.
Wired board is for option. It is convenient for guard to check the alarm
status during patrol.
3 Working Diagram of System
Mobile Phone
Alarm Center
Telephone
Wireless Smoke/ Gas Detector
Wireless PIR Detector
Wireless Door Sensor
Remote Controller
Wireless Siren
Wired Siren
GS
MG
SM
Wire
less
Tra
nsm
issio
n
Wire
dT
ran
sm
issio
n w
ithTe
lep
ho
ne
Lin
e
PS
TN
Security System Start-up
Such
Wired PIR detector
Curtain Door Sensor
Wired Smoke/ Gas Detector
Camera Wired Keypad
Alarm Panel
NO.1 NO.2 NO.3 NO.4 NO.5 NO.6
NO.7 NO.8 Alarm Printer PC Power
Run Alarm
Pin Print
Exit OK
Network Alarm System
-3-
4 Installations
Thank you for choosing our products! As you known, any kinds of products,
to assure its credibility and fully display all its functions, it should be
installed and used correctly. So we recommend installing by professional
personnel. We assume no liability for inaccuracies. Please contact with our
local agency if you need our professional personnel!
Firstly, make a scheme of all defense zones according to user's needs, and
choose suitable kinds of detectors.
Fix the setup places of all fittings, such as main unit detectors and sirens.
Draw a setup map marking the types and specification of detectors and
cable conductors in all zones, and marking the different usages of all
kinds of color lines. Do not use the same color cables in the different
zones of the same system. (The scheme and the map should be filed for
maintenance afterwards)
Note: Read the following factors when making defense scheme and drawing
the map.
*After making sure the credibility of detector, it should be fixed in hide
places, and the main unit should be fixed in a place where is easy to reach but
not easy to be found, and there should have sockets nearby, it also should be
near to telephone line and within the detector defense zone. Siren or trumpet
should be set in the best place. Emergency button should be set in the most
convince place.
*When installing wired detector, the cable should be fixed in hide place, like
line groove in ceiling. Don't use the same color cables in the different zones
of the same system.
*There should be no big mental or other electrical applicants which can
produce interferes (for example television, air-condition, computer and
micro-oven and so on) near to the install place of main unit and other
wireless telecommunication equipments. Otherwise, it will affect the
wireless communication effectiveness.
*Considering all factors, which could cause interferes when adopting
wireless detectors and wireless siren. Usually, in open area, the distance
between the above detector siren and main unit can reach to the standard
index. The main unit should be set indoors. Otherwise, in the course of
transmitting, wireless signal may be absorbed or weaken by all equipment
material indoors. Moreover, other signals of wireless equipment may make
interferes to this transmit signal. Therefore, the transmitting distance is less
than 400m when used indoors.
4.1 Installing Preparation
①
② ,
③
、
Network Alarm System
-4-
He
at S
ink
Running
Re
al-tim
e M
od
ule
Transceiver Inte
rface o
f GS
M M
od
ule
Note:
----All fuse pipes should only be replaced by thesame specification ones to prevent Fire.
---- Remove AC & DC power supply before maintenance.
Ba
tte
ry
Black
Red
2A
fuse
of
sir
en
3A
fuse
of
ba
tte
ry
0.5
Afu
se
ofp
ow
er
au
xilia
ryin
terf
ace
Insert the short jumper,the tamper will be invalid
Sealed lead battery
Wired Siren
Yellow Black Red Blue Green
Seized ring Incoming ring
Voltage 10.5V-14.5VDCThe power current should not exceed 2A.
4.2.1 Mounting
* Remove the circuit board from the cabinet. This will prevent possible
damage to the circuit board when removing the knock-outs.
* Remove the knock-outs.
* Mark the screw mounting holes on the wall.
* Mount the cabinet at the desired height and pass the cables through the
knock-outs.
* Replace the circuit board and reconnect the spade lug to the lower door
hinge.
Note: The nail mounting the main unit should be fastened and can bear three
times of weight of main unit at least.
4.2 Installations
Network Alarm System
-5-
150mm
The mounting holes
4.2.2 Earth ground
4.2.3 Wiring the panel
To ensure the effectiveness of the lightning and transient protection circuits,
the control panel must be connected to “Earth Ground”.
When connecting, the line should be connected strictly according to the
different uses of different color cables. Then spread the line according to the
setup map, and lead the cable to the place where the main unit will be fixed.
And then connect the EOL to the main unit. When connecting, the cable end
should be bared, and the length of bared should be equal to the connect port
where would be inserted. It will cause to poor contact if the line inserted is
too short; and it will cause to short circuit if the line inserted is too long. If
more than two lines should be connected to the same end, the bared line
should be twisted firmly, then insert them into the hole together. After that,
screw the screw cap firmly to guarantee its bearing strength.
AC power is supplied with a 16V/1.5A transformer at 50 or 60 Hz. Please
connect the secondary of the transformer to the terminals labeled AC. The
primary side of the transformer must be connected to an un-switched
receptacle. Do not connect primary to Ground-Fault-Interrupt (GFI)
circuits. After connecting all lines, power it on.
Note: The main unit will indicate if the AC line cut off for 10 seconds. When
there is something wrong with program system, the main unit will report
that AC is cut off. And the main unit also will report that it recovers after
recovering for 10 seconds.
To make sure main unit work normally in case the AC cut off, the alarm host
should be connected with storage battery as picture 1. Connect the red line
1) AC power
2) Backup Battery
Picture 2 Map of Fixing the holes of screws on the bottom of alarm panel
Network Alarm System
-6-
to the anode, and the black line to the cathode. It will damage the battery if
they are connected wrongly, and it uses 12V 7Ah sealed storage battery.
Don't use non-rechargeable battery or non-sealed storage battery. It is
suggested to change the battery every year.
Note: The alarm host will indicate the low power if the voltage is lower
than 11.8V. Moreover, it will send the low-power report if there is
something wrong with program system, and when voltage is lower than
10.5V, it will cut off the power supply to protect the battery. Don't connect
the battery before finishing all lines connection.
Bell &C is the siren-outputting interface. It provides stable 10.5V-14.5V
DC power when alarming. Fast thawing fuse F2 (2A, 3AG) protects the
interface circuit. When the current exceeds 2A, the fuse F2 will melt to cut
off the connection between main unit and siren. Note the polarity before
connecting. The anode is connected to the Bell end, and the cathode is
connected to the C end as picture1.
Note: if the fuse melts, please cut off all main unit power. After clearing all
obstructions, change the fuse, and then power it on. Don't change it with
large capacity fuse.
SW and C end are interfaces, which can be cut off. It provides equipments,
which needs to reset the cut-off state after alarming with 10.5V-14.5V/0.5A
DC. The representative equipments include glass broken sensor and smoke
detector. AUX and C end are interfaces, which cannot be cut off. It can
provide wired fittings with 10.5V-14.5V/0.5mA DC power. SW & C end and
AUX & C end are protected by fast thawing fuse (0.5A, 3AG)
AUX and C end are the interfaces of the keypad and warning board. DAT
end is the interface of the digit between alarm panel and keypad & warning
board. The system can connect 4 keypads at most and each keypad will
consume 55mA current. The wire connected with keypad is 22AWG
(0.643mm) copper core cable and each cable can reach 150m.
Z1-Z6&C have 6 interfaces connecting with line in wired zones. In zone
circuit, Z1-Z6 end is anode, C end is cathode, so when connecting, please
pay attention to the polarity of detector alarm output interface, so as not to
damage other parts of apparatus. But it is no necessary to distinguish the
polarities when fittings are hand-pressing switch or foot-trampling
switch.Every zone circuit can be programmed independently to different
circuit types, such as “normal close” “normal open” or “EOL resistor”.
3)Siren outputting connection
4) Auxiliary connects with power.
5) Wired intelligent keypad & wired warning board connection
6) Wired zones connection
、
Network Alarm System
-7-
If it is programmed to be “normal close” or “normal open”, the detector's
alarm outputting interface can be connected directly to both ends of zone
circuit; If it is programmed to be “EOL resistor
resistor (other zone circuits
unused for the moment also should be connected).
normal open detector should be connected in parallel with 2.2K resistors;
normal close detector should be concatenated with 2.2K resistors (and the
resistor should be as near to detector as possible). In order to avoid zone
circuit lines damaged (be cut off or short circuit), it is better to program
relevant zone circuit to be “EOL resistor”.
If both of resistors down-lead and out-line are connected to the same
interface. They should be twisted and screwed firmly, then inserted into the
interface, and screw the snail firmly. If resistor down lead is wire-wrapped
and connected with out-lines, it should be soldered after wire-wrapped
connection. Moreover, the parts of resistor down lead should be as short as
possible to avoid short circuit by touching with other metals after twisted.
When the detector needs alarm host to provide power, the anode and cathode
of the detector’s power input interface should be separately connected with
SW and C interfaces or AUX and C interfaces.
”, the correspondent zone
circuit end should be connected with 2.2KΩ
Connection principles:
NO interface (with EOL resistor)
Wire terminal of alarm panel
Wire terminal of detector
NC interface (with EOL resistor)
Wire terminal of alarm panel
Wire terminal of detector
NO/ NC interfaces (without EOL resistor)
Wire terminal of alarm panel
Wire terminal of detector
Network Alarm System
-8-
7) Programmable linkage output connection
8) Tamper connection
9) Telephone line connection
NC. NO. and COM are for connection of programmable earth ground. It
means the alarm panel can set the driven relay output of various alarms and
zones alarms. NC is Normal Close, NO is Normal Open and COM is normal
connection. This interface can afford 1A 120VAC/24VDC at most. It should
change the relay of higher-power once the power of controlled equipments
overloads the interfaces.
TAM&C is the anti-tamper zone interface. It can be set two switches on the
case. One is to avoid opening the cap illegally; the other one is to avoid
moving or dissembling the alarm host. Concatenate both anti-tamper
switches, and then connect the EOL with TAM&C interface.
LINE is the interface of telephone incoming line. PHONE is extension
interface. When alarming, in order to make main unit reporting the alarm
information to the manage center and user, LINE interfaces should be
connected with telephone incoming line. Extension and other
telecommunication equipments (including extension) can be connected
with PHONE interface. But don't oppositely connect with incoming line.
They should be connected as picture 1.
Firstly, check whether all lines are connected correctly or not. Next, connect
with battery, and cover the case cap. Then connect with AC power to
program. Lastly, test system to check if all detector fittings can work
normally and can communicate normally with alarm host or if the alarm host
correctly performs all alarm functions. Then the system installation is
finished.
The Keypad is designed to support this Long-distance Network Alarm
System. It can assist the alarm panel to make Arm, Disarm, Duress Alarm
and Emergency Alarm etc. The keypad can display the information from
panel or zones on time. It is endowed with a Tamper interface and a
programmable expanding zone. It is with the design of flip type, aesthetic
appearance and simple operation. 4 pieces of keypads can be connected with
the alarm panel.
Working Voltage: DC12V±20%
Current: 55mA
Length of Wire: 150m (22AWG copper core cable)
4.2.4 System debugging
5 Instruction of Wired Keypad
5.1 Technologic Parameter
≤
Network Alarm System
-9-
Working Temperature: -15
Weight: 190g
℃~ ℃+60
Size: 138*95*34mm (L*W*H)
5.2 Installations
5.2.1 Diagram of panel's bottom and its installation
LIST GSM
12* 1110
#
Picture 4 Diagram of panel's bottom and its installation
4.2.2 Wiring keypad
4.2.3 Connection of expanding zones
There are five pieces of wires lead in the keypad. Wires lead of red, black,
blue and green should be connected with the alarm panel. The yellow one is
the line-connection to expand zones (forming a zone loop with the black
one). The red wire connect with AUX end of alarm panel, the black one with
C end, the yellow one with DAT end and the green one with ATM end.
Each keypad owns an expanding zone. The yellow wire and black wire
forms a zone loop. It can connect with wired detector or wired door sensor
directly to add a zone for alarm panel. ON & OFF of the zone can be
operated on the programming of alarm panel.
All attributes of expanding zones will be controlled by 5 wired zone. The
expanding zone of keypad is 05. The LED of status display is the same one
of 5 zone.
th
th
Network Alarm System
-10-
5.2.4 Trigger type of expanding zones (J2)
5.2.6 Keypad Position
The keypad addressing is realized on the DIP switch of the circuit. The
addressing is complied from 01 to 04.
▲
▲
▲
▲
“ ”: the expanding zone is EOL resistor zone. It shall series with 2.2K
EOL resistor
“ ”: the expanding zone is NO alarm zone. It shall not series with 2.2K
EOL resistor.
“ ”: Turn off the expanding zone
“ ”: Turn on the expanding zone
5.2.5 The expanding zone on/off (J3)
ON
1 2
Picture 5 Diagram of coding switch
Keypad addressing
Note: The addressing of each keypad connected with the system should be
different. Or else the keypad can't work normally with the repeated
addressing.
0-9, *, # keys: program the operation and daily operation
LIST key: query the Armed zone list
GSM key: query the signal of GSM module
5.2.4 Description of keypad's keys
5.3 Instruction of LED Indicator
Key, key, key: it will make Emergency, Fire, Emergency Burglar
Alarm with 3 seconds pressing. (Open it should program again)
Key: bypass
Indicator: Power of alarm panel
Indicator: Running of alarm panel
Indicator: Arm of alarm panel
Indicator: Trouble of alarm panel
Indicator: Emergency alarm of keypad
Indicator: Manual Fire alarm indicator
Indicator: Emergency Burglar of keypad, Emergency alarm of remote
controller and Tamper indicator of alarm panel
Indicator: Bypass indicator of zone
Network Alarm System
-11-
“GSM” indicator: Optional GSM module (When the GSM module is
chosen, the indicator turns on within alarm panel's powering on for 3
minutes)
“1-6” indicators: indicators of 1 to 6 wired zones
“7-12” indicators: indicators of 1 to 6 wireless zones
st th
st th
Network Alarm System
5.4 Instruction of Sound Hint
5.5 How to Program
-12-
-13-
Network Alarm System
6 Programming Instructions
The system can be set according to user's requirement. Please read it
carefully before your using to bring its best value play and protect the set
areas.
Please input the following zone code according to your needs:
This zone isn't used.
This zone is mainly used to entry/ exit the Delaying zone (for example
main door, main entrance). This zone will be active in the end of Delay of
Arming and it should Disarm the system before the end of Delaying, or else
the system will make alarm. The keypad will make beep when entering
Delaying time. (as the clew signal of Disarming system)
It is used outdoor, such as door and window. When it is destroyed, the
system will make alarm immediately and entry Delaying status.
It is used to entry/ exit zone and it should be triggered before entering
the Delaying zone. It is mostly set in the inevitable place when disarming
the system with keypad, such as lounge or lobby (or mobile detector).
It is used in the door, window of thin foil (such as shop) or sensitive
areas (such as warehouse, medical warehouses etc.) or the areas need to be
close attention. In the status of Disarming, the keypad will make fast beep
when triggering the zone; it is used to break into the door or other events (
6.1 Definition of Zone Type
0 type unavailable
1 type Entry/ Exit the Delaying zone
2 type Perimeter zone
3 type Inner zone (Smart alarm)
4 type Day/ Night zone (warning with Disarming and alarming with
Arming)
Network Alarm System
-14-
for example, the sensor is unavailable or thin foil door is broken). In the
status of Arming, the keypad and siren will make alarm when triggering the
zone.
It is used for an emergency button (for example, in bank and jewelry
counter). It will be triggered and send the alarm to the center terminal. The
zone will display in the keypad but without sound alarm. This zone won't be
affected by the operation of Arm/ Disarm.
It is used for an emergency button. It sends the alarm to the center
terminal and forms voiced alarm (for example, the emergency alarm on the
bed). The zone will cause the siren and keypad alarm and display the
information when triggering. This zone won't be affected by the operation of
Arm/ Disarm.
This type is the same as the 3 type. The only difference is that the
system won't make alarm immediately when the entry/ exit zone was
triggered and the zone will enter Delaying.
It is used for the smoke detector or heat detector installing 24 hours
protected areas. The zone will make fire signal when triggering, the keypad
will display the zone no. and trigger the siren to make sound. Meanwhile,
the keypad sends the report to the center terminal. This zone won't be
affected by the operation of Arm/ Disarm.
It is used for the gas detector installing 24 hours detective areas. The
zone will make alarm signal when triggering, the keypad will display the
zone no. and trigger the siren to make sound. Meanwhile, the keypad sends
the report to the center terminal. This zone won't be affected by the
operation of Arm/ Disarm.
It is used for the emergency button or other emergency assistance
devices installing 24 hours protected areas. The zone will make alarm signal
when triggering, the keypad will display the zone no. and trigger the siren to
make sound. Meanwhile, the keypad sends the report to the center terminal.
This zone won't be affected by the operation of Arm/ Disarm.
It is the same as the 4 zone. The only difference is that the keypad willmake fast beep when triggering in the status of Arm/ Disarm. The zone won'tmake alarm.
5 type 24 hours silent alarm
6 type 24 hours voiced alarm
7 type Interior zone (Delaying)
8 type Fire zone
9 type Gas zone
A type Medical zone
B type Bell zone
rd
th
Network Alarm System
-15-
C type Burglar zone
D type Arm once shutting zone
E type Patrolling Test zone
Combinations
Zones
It is used in the doors or windows. When they are intruded or destroyed,
Delaying function doesn't make effect.
It is mainly used with entrance guard system, door lock and wired door
sensor. And it is only for wired zone. The system will Arm automatically
when the zone turns from Trouble to Normal (controlled by Arm Delay and
the Arm type is controlled by 1# operator). The system will make alarm
when the zone turns from Normal to Trouble (The zone is defined as Entry/
Exit Delay zone at the moment).
This zone is only for wired zone and mainly used to connect with wired
patrolling devices. It is not limited by Arm/ Disarm. Once the zone is
triggered, the system will report the patrolling record to the alarm center,
meanwhile, the siren and the buzzer of keypad will make sound
synchronously.
Note: If you connect power before wiring the loops, install a 2.2K EOL
resistor across each loop.
Installer combination: 012345
User 1# (Master) combination: 1234
User 2# (Master) combination: 2234
Duress: disabled
Arming type: the zone can be Arm only in the Normal or Bypass status.
Zone 01: Entry/ Exit delayEOL circuit
Zone 02: PerimeterEOL circuit
Zone 03: PerimeterEOL circuit
Zone 04: PerimeterEOL circuit
Zone 05: Interior (Delay)EOL circuit
Zone 06: 24-hour voiced alarmEOL circuit
Zone 07: Perimeter
Zone 08: Perimeter
Zone 09: Perimeter
Zone 10: Perimeter
Zone 11: Perimeter
6.2 Factory Setting
Network Alarm System
-16-
Zone 12: Perimeter
Expanding zone of keypad: disabled
Delay Arm: 15 seconds
Enter alarm delaying: 15 seconds
Siren outputting time: 5 minutes
Buzzer outputting time of keypad: 5 minutes
Relay outputting time: 5 minutes
User Duress function: Off
Trouble test for telephone line: On
Buzzer will be active when telephone line is in trouble: Yes
Buzzer will be active when GSM module is in trouble: Yes
Expanding zone of keypad: Off
Operating with Emergency button: Yes
Telephone network and GSM wireless network dial together.
The zone can be armed only in the status of Normal or Bypass.
Delay after 1 minutes turning off the power.
Panic help, Fire and Emergency Burglar of keypad: Yes
Wireless siren: Off
Output way of programmable relay: Mono-stable
All panel wirings for this system should be completed prior to powering
it on. You can only access the programming mode when the control
panel is disarmed.
d
Open the end cover of the keypad and change the address of keypad by
the code switch of keypad circuit board. The AC and battery should be
removed before changing the keypad's address and power it again after
revising the address of keypad.
If two keypads address of the same alarm panel is same, the alarm
panel and keypad won't work normally.
If you want to add a new more keypad, what you should do is reset the
alarm panel in the original keypad. It is no necessary to power it again
and confirm entry of the new keypad.
Timing
Unit Control
6.3.1 Programming the Position of keypa
Note:
6.3.2 To start keypad programming
6.3 Programming the Panel
Network Alarm System
In the status of Disarm without alarming, you can key in installer's
combination * 0 # . The default value of installer's
combination is 012345. The indicators of Run, Arm and Fault are
flashing at the same time. It means to start keypad programming.
If you program the alarm panel with the keypad and want to revise a
command of addressing programming date, please input 2 digits
addressing code at first and the programming digit, then preserve the
digit by keying in # ; If the buzzer of keypad beeps 5 sound, it means
the programming digit inputted wrong; If the buzzer of keypad beeps 2
sound, it mean the programming digit inputted right.
To exit panel programming, please key in * # ; Meanwhile, if the
keypad is not operated in 5 minutes, the panel will exit the programming
automatically.
Callback required: The software of network alarm center is calling
the alarm center. After the alarm panel receives the calling and dials the pre-
preserved telephones to realize the remote connection. (The alarm panel
should pre-set the telephones for remote controlling programming (the
eighth alarm telephone)).
Connect automatically:The software of network alarm center is
calling the alarm center. Once the alarm panel receives the calling, it will
analysis the data telecommunication soon and realizes the remote
connection. (This way is invalid when the alarm system is in the
programming status).
In the status of non-programming, please input Installer's
Combination * 2 # to exit the programming status. The
default state of installer's combination is 012345. The alarm system will
dial the pre-preserved telephones of remote controlling and realize the
remote connection.
「
」 「 」 「 」 「 」
「 」
「 」「 」
①
②
「
」 「 」 「 」 「 」
6.3.1 Programming with the keypad
6.3.2 To exit panel programming
6.41 Connection way
6.42 Remote controlling of keypad start-up
6.4 Programming Remotely (only supported by Version 1.6)
6.5 Programming Table of the Alarm Panel
-17-
Network Alarm System
6.6 Programming Commands of the Alarm Panel
Command Position 00: Installer Combination
Default Values
Digit Position (1)(6): Installer Combination
Combination must have 6 digits. Valid entries are 0-9.
-18-
Network Alarm System
Command Positioning 01-04: User Arming Type and Combination
Definition:
Command digit 01= #1 userCommand digit 02= #2 user
Command digit 03= #3 userCommand digit 04= #4 user
Default Values
Digit Position (1)(2): Arming Type
00= Closing the user01= Arm only, No Disarm, No Bypass02= Arm and Bypass, No Disarm03= Disarm, No Arm, No Bypass04= Disarm and Bypass, No Arm05= Arm and Disarm, No Bypass06= Arm, Disarm and Bypass
Digit Position (3)(6): User's Combination
Combination must have 4 digits. Valid entries are 0-9.Note: Arm type of Remote controllers of part position 01-04 are controlledseparately by #1--#4 users.
Command Position 05-07: the 1 alarm phonest
Command position 05: the 1 alarm phone (Digit 1-6)st
Default Values
Digit position (1)-(6):
Valid entries are 0-9. *1=*; *2=#;*4= End-of-Number (EON) character; *5= 3 seconds Delay;
Note: Program *4 after the last digit, please fill remaining unused positions
with 0.If you want to delete the numbers, please input *4 in the first digit
and add 0 in last digit.
Command Position 06: The 1 alarm phone (Digit 7-12)st
Default Values
-19-
Network Alarm System
Command Position 07: 1 alarm phone (Digit 13-18)st
The
Default Values
Default values: The default values of all the alarm telephones are empty.
Programming conversions
Hexadecimal value Key strockes
Command Positions 08-10: the 2 alarm phonend
Command Positions 11-13: the 3 alarm phonerd
Command Positions 14-16: the 4 alarm phoneth
Command Positions 17-19: the 5 alarm phoneth
Command Positions 20-22: the 6 alarm phoneth
Command Positions 23-25: the 7 alarm phoneth
Command Positions 26-28: the 8 alarm phoneth
Note: The 8 alarm telephone is for programming remotely. (Only supportedby Version 1.6)
th
Command Position 29: Type of alarm telephone
Default Values
Digit position (1): Type of the1 alarm phonest
0= telephone and mobile phone;
1=ADEMCO CONTACT ID alarm center;
Digit position (2): Type of the 2 alarm phonend
Digit position (3): Type of the 3 alarm phonerd
Digit position (4): Type of the 4 alarm phoneth
Digit position (5): Type of the 5 alarm phoneth
Digit position (6): Type of the 6 alarm phoneth
Digit position (7): Type of the 7 alarm phoneth
Digit position (8): Type of the 8 alarm phoneth
-20-
Network Alarm System
Command Position 30: ADEMCO CONTACT ID account
Default Values
Digit position (1)(4): Contact ID accountAccount must have 4 digits. Valid entries are 0-F (except A).
Programming conversions
Hexadecimal value Key strockes
Command Position 31: Dialing times and ringing times
Default Values
Digit position (1)(2): Dialing times
00= off
01-15= dialing times is 1-15 times
Digit position (3)(4): ringing times
00-03= off
04-15= Ringing times is 04-15 times
Command Position 32: Arm Delay and Alarm Entry
Default Values
Digit position (1)(2): Time of Arm Delay
00=off
01-99= Time of Delay Arm (01-99) is *3 seconds.
Digit position (3)(4): Time of Alarm Delay
00= off
01-99= Entry Delay time (01-99) is *3 seconds
-21-
Network Alarm System
Command Position 33: Outputting duration of extra siren, buzzer of keypadand programmable relay
Default Values
Digit position (1)(2): Outputting time of extra siren
00= off
01-99= outputting time of extra siren is 01-99 minutes
Digit position (3)(4): Outputting time of buzzer keypad
00= off
01-99= outputting time of alarming buzzer is 01-99 minutes
Digit position (5)(6): Outputting time of programmable relay
00= off
01-99= outputting time of programmable relay is 01-99 minutes
Command Position 34: The programmable relay outputs switches
Default Values
0=off 1= on
0=off 1= on
0=off 1= on
0=off 1= on
Digit position (1): Arm the relevant &programmable relay outputs
Digit position (2): Disarm the relevant &programmable relay outputs
Digit position (3): Emergency alarm of keypad/ remotecontroller the relevant & programmable relay outputs
Digit position (5): Shortage of battery or voltageof main panel corresponds to the output of programmable relay
Digit position (4): Trouble AC correspondsto the output of programmable relay
0=off 1= on
Digit position (6): Telephone line is cut off,which corresponds to programmable relay output.
0=off 1= on
Digit position (7): GSM module is in trouble,which corresponds to programmable relay output.
0=off 1= on
Digit position (8): Key starts up, whichcorresponds to programmable relay output.
0=off 1= on
-22-
Network Alarm System
Note: GSM module should be chosen and to realize the relevant functions.
Command Position 35: Loop Switches
Default Setting
Digit Position (1): User's Duress function
0=off 1= on
Digit Position (2): The relevant buzzer clewswhen telephone line is in trouble.
0=off 1= onDigit Position (3): The relevant buzzer clews when
GSM module is in trouble.
0=off 1= on
Digit Position (4): Keypad-expanding zone
0=off 1= on
Digit Position (5): Emergency alarm of remote controller
0=off 1= on
Digit Position (6): Auto-change to GSM wireless networkdial when the telephone line is in trouble.
0=Both PSTN dialer and GSM dialer work together
1= PSTN dialer work, GSM dialer doesn't work.. If PSTN dialer encounter trouble,
GSM dialer will work
Note: * The Duress combination is set to be added 1 with the last number of user's
combination; if the last number of user's combination is “9”, its last number
is “0” without consideration of carry-over.
* GSM module should be chosen and to realize the relevant functions.
Command Position 36: Loop Switches (B)
Default Values
Digit Position (1): Arm type0= Disable to enforce Arm. The zone can be Armed when it is in Normal or Bypass.
1= Allow to enforce Arm. It will auto-bypass the abnormal zones when finishing Delay Arm.
Digit Position (2): Enable 1 minute Delayafter power-up
0=off 1= on
Digit Position (3): Enable to Panic, Fire and Emergencyalarm of keypad.0=off 1= on
Digit Position (4): Enable Wireless Siren
0=off 1= on
Digit Position (5): Enable Sound Hint
0= Mono-stable (Controlled by time and restore in the end of time controlling)1= LEV- stable (Not controlled by time and restore only when Disarm/ Reset)
-23-
Network Alarm System
Note: * It is used to ready the detector when the system is power on again with thefunction of enabling 1 minute Delay after power-up. You can shield the faultalarm during the ready step.
6
Command Position 37: Event Report Switches (A)
Default Values
Digit Position (1): System Failure Report
0=off 1= on
Digit Position (2): Restore Normal Report
0=off 1= on
Digit Position (3): Arm/ Disarm Report
0=off 1= on
Digit Position (4): Bypass Report
0=off 1= on
Digit Position (5): Test Report
0=off 1= on
Digit Position (6): Patrol Report
0= off 1= on
Note: * System Failure composes of low battery, voltage lower, AC trouble and
telephone line trouble.
* Restore Normal composes of Restore Normal of battery & voltage, AC
trouble restoration, telephone line restoration and exiting programming.
* The information report of GSM module is controlled by Event Report of
alarm panel. If one Event Report Switch of alarm panel is off, the alarm
panel will not send this event to GSM module.
The user's accounts of Report Arm/ Disarm to alarm center:
#1 user / 1st remote controller: 1; #2 user / 2nd remote controller: 2;
#3 user / 3rd remote controller: 3; #4 user / 4th remote controller: 4;
User of Timer Arm: 5,6; User of GSM remote Arm/ Disarm: 7;
Account number of Arm/ Disarm remotely: 0;
Command Position 38: Event Report Switches (B)Default Values
Digit Position (1): Report of other information from detector
0=off 1= onDigit Position (2): Wired zone makes alarm and trigger
when storing to report
-24-
Network Alarm System
0=off 1= on
Note: Other information report from detector composes of low battery, voltage lower,
restore to normal battery, open detector and close detector.
Command Position 39: Events reports to the alarm phone
Default Values
Digit Position (1): all events report to the 1 alarm phonest
0=off 1= on
Digit Position (2): all events report to the 2 alarm phonend
Digit Position (3): all events report to the 3 alarm phonerd
Digit Position (4): all events report to the 4 alarm phoneth
Digit Position (5): all events report to the 5 alarm phoneth
Digit Position (6): all events report to the 6 alarm phoneth
Digit Position (7): all events report to the 7 alarm phoneth
Digit Position (8): all events report to the 8 alarm phoneth
6
Command position 40: Extra Siren outputs the relevant events
Default Values
Digit Position (1): extra siren output when AC is in trouble.
0=off 1= on
Digit Position (2): extra siren output when battery or voltage is low.
0=off 1= on
Digit Position (3): extra siren output when the telephone line is in trouble;
0=off 1= on
Digit Position (4): extra siren output when GSM module is in trouble;
Digit Position (5): extra siren output when the alarm panel Arm/ Disarm.
0=off 1= on
0=off 1= on
Digit Position (6): the siren correspond with the patrol output
0= when the patrol test finishes successfully, the siren doesn't output;1= when the patrol test failures, the siren make a sound of clew.
Note: * The siren will make a sound of clew when Arm is successful and make twosound of clew when Disarm is successful.
Command position 41-46: Wired zones control and switches
Definition:
Command Position 41= the 1st wired zone Command Position42= the 2nd wired zone
Command Position 43= the 3rd wired zone Command Position44= the 4th wired zone
Command Position 45= the 5th wired zone Command Position 46= the 6th wired zone
-25-
Network Alarm System
Default Values
Digit Position (1): Receiver telephone select
1= The zone report the alarm information to the 1 alarm phone;
2= The zone report the alarm information to the 2 alarm phone;
3= The zone report the alarm information to the 3 alarm phone;
4= The zone report the alarm information to the 4 alarm phone;
5= The zone report the alarm information to the 5 alarm phone;
6= The zone report the alarm information to the 6 alarm phone;
7= The zone report the alarm information to the 7 alarm phone;
8= The zone report the alarm information to the 8 alarm phone;
9= The zone report the alarm information to the 9 alarm phone;
st
nd
rd
th
th
th
th
th
th
0= The zone won't report alarm information;
Digit Position (2): Zone type
0= bypass; 1= ARM/alarm delay;2= Perimeter; 3= Interior (Smart alarm);4= Day/ Night; 5= 24 hours silence alarm;6= 24 hours sound alarm; 7= Interior zone (Delay);8= Fire; 9= Gas*0= Medical; *1= Bell*2=Burglar; *3= Arm on shutting;*= Patrol test;
Digit Position (3): Zone reaction time
Digit Position (4): Zone triggering type
0= NC alarm; 1= NO alarm; 2= End-of-line resistor;
Digit Position (5): Enable to Bypass zone
0= Disable; 1= Enable;
Digit Position (6): Keypad's buzzer outputs
0= There is no keypad's buzzer can output when the zone makes alarm;
1= There is a keypad's buzzer can output when the zone makes alarm;
Digit Position (7): Extra siren output
0= There is no extra siren can output when alarm happens;
1= There is a extra siren can output when alarm happens;
Digit Position (8): Programmable relay outputs;
0= There is no programmable relay output when alarm happens;
1= There is a programmable relay output when alarm happens;
Note: 24 hour zone can set to be Bypass.When the zone was set to be 24 hours silent
alarm, the keypad's buzzer, siren and programmable relay can't output.
-26-
1= 100ms; 2= 200ms; 3= 300ms;
4= 400ms; 5= 500ms; 6= 600ms;
7= 700ms; 8= 800ms; 9= 900ms;
Network Alarm System
Command Position 47-52: Wireless zones control and switches
Definition:
Command Position 47= the 1 wired zone Command Position 48= the 2 wired zone
Command Position 49= the 3 wired zone Command Position 50= the 4 wired zone
Command Position 51= the 5 wired zone Command Position 52= the 6 wired zone
st nd
rd th
th th
Default Values
Digit Position (1): Alarm phone report
0= not alarm phone report;
1= the alarm information report to the 1 alarm phone;
2= the alarm information report to the 2 alarm phone;
3= the alarm information report to the 3 alarm phone;
4= T the alarm information report to the 4 alarm phone;
5= the alarm information report to the 5 alarm phone;
6= the alarm information report to the 6 alarm phone;
7= the alarm information report to the 7 alarm phone;
8= the alarm information report to the 8 alarm phone;
9= the alarm information report to the 9 alarm phone;
st
nd
rd
th
th
th
th
th
th
Digit Position (2): Zone type
0= bypass; 1= ARM/alarm delay;
2= Perimeter; 3= Interior (Smart alarm);
4= Day/ Night; 5= 24 hours silence alarm;
6= 24 hours sound alarm; 7= Interior zone (Delay);
8= Fire; 9= Gas
*0= Medical; *1= Bell
*2=Burglar;
Digit Position (3): Enable to Bypass zone
0= Disable; 1= Enable;
Digit Position (4): Keypad's buzzer outputs
0= There is no keypad's buzzer can output when the zone makes alarm;
1= There is a keypad's buzzer can output when the zone makes alarm;
Digit Position (5): Extra siren output
0= There is no extra siren can output when alarm happens;1= There is a extra siren can output when alarm happens;
Digit Position (8): Programmable relay outputs;
0= There is no programmable relay output when alarm happens;1= There is a programmable relay output when alarm happens;
Note: 24 hour zone can set to be Bypass. When the zone was set to be 24 hours silent
alarm, the keypad's buzzer, siren and programmable relay can't output.
Command Position 53: The wired zone list of Home Arm
-27-
Network Alarm System
Default Values
Digit Position (1): the 1 wired zone of Home Armst
0= This wired zone isn't controlled by Home Arm.
1= This wired zone is controlled by Home Arm.
Digit Position (2): the 2 wired zone of Home Armnd
Digit Position (3): the 3 wired zone of Home Armrd
Digit Position (4): the 4 wired zone of Home Armth
Digit Position (5): the 5 wired zone of Home Armth
Digit Position (6): the 6 wired zone of Home Armth
Command Position 54: The wireless zone list of Home Arm
Default Values
Digit Position (1): the 1 wireless zone of Home Armst
0= This wireless zone isn't controlled by Home Arm.
1= This wireless zone is controlled by Home Arm.
Digit Position (2): the 2 wireless zone of Home Armnd
Digit Position (3): the 3 wireless zone of Home Armrd
Digit Position (4): the 4 wireless zone of Home Armth
Digit Position (5): the 5 wireless zone of Home Armth
Digit Position (6): the 6 wireless zone of Home Armth
Command Position 55: Set extra wireless siren
Default Values
Digit Position (1)-(8): the Position codeof wireless siren
The code should be 8 digits and values is in 0-3.
Note: The 8 Digits siren Code is marked on the back of the wireless siren.The extra wireless siren should be chosen to realize the above functions.
「 」
Command Position 56: How to enroll Remote Controller
Default Values
Digit Values (1)-(2): the part Position code of remote controller
The code should be 2 digits and processed in 01-04.
-28-
Network Alarm System
When you hear two sound of “Di…Di…” buzzer with pressing “#”, it means thesystem will enter the status of remote controller enrollment. If the zone's indicator ofpart Position code is flashing quickly, it means this part Position code is blank. Youcan make enrollment with pressing any buttons of remote controller. The alarm panelmakes a sound of “Di…” if the enrollment is successful. Meanwhile, the zone'sindicator will be bright and make clew that the successful learning of remotecontroller. Press “#” to exit the enrollment. If the indicator still lights, that means thiszone have been occupied, You should delete it and then make enrollment again.
In the progress of enrollment, if the buzzer makes five sound of “Di…Di…”, itmeans the Position code of the remote controller has been learned.
01-04 sub-Position codes of remote controllers are controlled by the Arm typesof #1-#4 users set.
91-94 sub-Position codes are to delete the 1 4 remote controllersindependently.
When you press “#”, if you hear two sound of “Di...Di…” from buzzer, itmeans the successful deletion of enrollment; if you hear five sound of
Note:
Note:
How to delete the enrolled remote controller:
Operation Steps: 56→91→#
st th-
Command Position 57: How to Enroll Detectors
Default Values
Digit Position (1)-(2): The zone no. of wireless zones
The zone no. should be 2 digits and processed in 07-12.
Digit Position (3)-(4): The Position of sub wireless zones
The Position should be 2 digits and processed in 01-03.
When you hear two sound of “Di…Di…” buzzer with pressing “#”, it means the
detector will enter the status of enrollment. If the wireless zone's indicator of part
Position is flashing quickly, it means this part Position is blank. You can make
enrollment with triggering the detector by sending the alarm signal (or pressing the
enrolled key of detector). The alarm panel makes a sound of “Di…” if the enrollment
is successful. Meanwhile, the zone's indicator will be lighting on from flashing and
make clew that the successful learning of remote controller. Press “#” to exit the
enrollment. If the wireless zone indicator still lights, that means this zone have been
occupied, You should delete it and then make enrollment again.
The zone no. of wireless zones are 07-12.
In the progress of enrollment, if the buzzer makes five sound of “Di…Di…”,
it means the Position of the detector has been learned.
Each zone can learn 3 detectors of different Position codes.
91-93 sub Positiones are to delete the 1 - 3 detectors independently.
(07 is the 1 wireless zone; 91 is to delete the 1
detector of 1 wireless zone.)
Note: When you press “#”, if you hear two sound of “Di...Di…” from buzzer, it
means the successful deletion of enrollment; if you hear five sound of
“Di…Di…Di…Di…Di”, it means the enrollment deletion is fail.
Note:
How to delete the enrolled detectors:
Operation Steps: 57→07 91→#
st rd
st st
st
-29-
Network Alarm System
Command Position 58: How to Set the Patrol
8
Default Value
Digit Position (1)-(2): Sub-Position of the patrol
The Position should be 2 digits and processed in 01-06.
When press “#”, you can hear two sound of “Di…Di...” from the buzzer. It means the
patrol is in the status of enrolling. If the indicator of relevant wireless zone is
flashing, it means the enrollment is blank. You can press “Patrol” on the patrol or
“Panic” on the remote controller to enroll. If the enrollment succeeds, the alarm panel
will make one sound of “Di”. Press “#” to exit the enrollment. If the indicator of
relevant wireless zone is lighted on, it means this position having been occupied. You
should delete the enrollment and enroll it again.
When you hear five sound of “Di…Di…Di…Di…Di during enrolling, it
means the Position have been occupied. You have to delete it before enroll
new code.
The sub-position of 91-96 mean to delete the patrols of 1 -6 separately.
Note: When press “#”, you can hear two sound of “Di…Di…”. It means the deletion
of enrollment is successful. If you hear five sound of “Di…Di…Di…Di…Di”
it means the deletion of enrollment failures.
The event code of patrol in Contact ID protocol is 619. the alarm type is
Testing.The alarm information is Patrolling Test.
Note:
How to delete the enrolled patrol:
Operational procures: 58→91→#
st th
Command Position 59: How to Set Date (Year, Month, day, week)
Digit Position (1)-(2): YearThe year should be 2 digits and processed in 00-99.
Digit Position (3)-(4): Month
The month should be 2 digits and processed in 01-12.
Digit Position (5)-(6): Day
The day should be 2 digits and processed in 01-31.
Digit Position (7)-(8): Week
01-06= From Monday to Saturday00= Sunday
Note: To realize the date, the real-time module is required. If panel didn't equippedthe real-time module, you will hear a clew of fail operation when you set thisstep.
-30-
Network Alarm System
Command Position 60: How to Set the Time (Hour, Minute, Second)
Digit Position (1)-(2): Hour
The hour should be 2 digits and processed in 00-23.
Digit Position (3)-(4): Minute
The minute should be 2 digits and processed in 00-59.
Digit Position (5)-(6): Second
The second should be 2 digits and processed in 00-59.
Note: The real time of alarm panel adopts 24 hour NTSC.
Command Position 61: How to Set Timer Arm/ Disarm (1)
Default Values
Digit Position (1)-(2): The hour rank of Timer Arm (1);
Digit Position (3)-(4): The minute rank of Timer Arm (1);
Digit Position (5)-(6): The hour rank of Timer Disarm (1);
Digit Position (7)-(8): The minute rank of Timer Disarm (1);
Note: If Timer Arm/ Disarm are not applicable, please set the Time of Arm same as
the Time of Disarm or both are more than 24 hours.The Real Time module is
required to perform this function.
Command Position 62: How to Set week list for Timer Arm/ Disarm (1)
Default Values
Digit Position (1): Timer Arm/ Disarm for Monday (1)
0= doesn't perform the timer
1= Perform the timer
Digit Position (2): Timer Arm/ Disarm for Tuesday (1)
Digit Position (3): Timer Arm/ Disarm for Wednesday (1)
Digit Position (4): Timer Arm/ Disarm Thursday (1)
Digit Position (5): Timer Arm/ Disarm for Friday (1)
Digit Position (6): Timer Arm/ Disarm for Saturday (1)
Digit Position (7): Timer Arm/ Disarm for Sunday (1)
-31-
Network Alarm System
Command Position 63: wired zone list for Timer Arm/ Disarm (1)
Default Values
Digit Position (1): The 1 wired zone of Timer Arm/ Disarm (1)st
0= won't be controlled by timer
1= controlled by timer;
Digit Position (2): The 2 wired zone of Timer Arm/ Disarm (1)
Digit Position (3): The 3 wired zone of Timer Arm/ Disarm (1)
Digit Position (4): The 4 wired zone of Timer Arm/ Disarm (1)
Digit Position (5): The 5 wired zone of Timer Arm/ Disarm (1)
Digit Position (6): The 6 wired zone of Timer Arm/ Disarm (1)
nd
rd
th
th
th
Command Position 64: wireless zone list for Timer Arm/ Disarm (1)
Default Values
Digit Position (1): The 1 wireless zone of Timer Arm/ Disarm (1)st
0= won't be controlled by timer
1= controlled by timer.
Digit Position (2): The 2 wireless zone of Timer Arm/ Disarm (1)
Digit Position (3): The 3 wireless zone of Timer Arm/ Disarm (1)
Digit Position (4): The 4 wireless zone of Timer Arm/ Disarm (1)
Digit Position (5): The 5 wireless zone of Timer Arm/ Disarm (1)
Digit Position (6): The 6 wireless zone of Timer Arm/ Disarm (1)
nd
rd
th
th
th
Command Position 65: Timer Arm/ Disarm (2)
Command Position 66: Week list for Timer Arm/ Disarm (2)
Command Position 67: Wired zone list for Timer Arm/ Disarm (2)
Command Position 68: Wireless zone list forTimer Arm/ Disarm (2)
Command Position 69: Test Report Timer
-32-
Network Alarm System
Default Values
Digit Position (1)-(2): Set the test report timer
00= Turn off the test report to alarm center;
01-99= To set the interval time between two test reports in 01-99 hours;
Note: The alarm panel will re-time after powering on or CPU resetting every time.
Command Position 70: The relation of the wired cross zones
Default Values
Digit Position (1)-(2): The 1 zone of wired cross zonesst
The zone should be 2 digits and processed in 01-06.
Digit Position (3)-(4): The 2 zone of wired cross zonesnd
The zone should be 2 digits and processed in 01-06.
Digit Position (5)-(6): Cross time
00= Turn off the relation of wired cross zones
01-99= Cross time is *3 seconds (01-99);
Digit Position (7): The triggering times of wired cross zones
0= It will not make alarm when triggering a single zone; It will take as alarm when
a single wired zone is in the status of triggering.
1-9= When the triggering times of a single zone is more than 1-9 times, it will make
alarm;
The relation of cross zones: It composes of two different zones, cross
time and triggering times.
Note:
?
?
?
When one of the zones is triggered, the cross time timer starts up.
During the cross time, another zone is also triggered and then the
alarm of two zones will be activated; If another zone is not triggered, it
will not make alarm.
During cross time, it will be taken as alarm when the triggered times is
more than pre-set times.
If the two zones inputted the same Position, the triggering times of this
zone can't be more than twice as the set times or always be on the status
of triggering. It will also be as alarm.
The cross zones will not make alarm and enter Delay time. The
triggering times of zones will be counted.24 hour zone can be set as
cross zone.The zone no. of wired zones should be processed to be 01-
06.
-33-
Network Alarm System
Command Position 71: The Relation of Wireless Cross Zones
Default Values
Digit Position (1)-(2): the 1 zone of wireless cross zonesst
The zone should be 2 digits and processed 07-12
Digit Position (3)-(4): the 2 zone of wireless cross zonesnd
The zone should be 2 digits and processed 07-12.
Digit Position (5)-(6): Cross time
00= Turn off the relation of wireless cross zones
01-99= Cross time is *3 seconds (01-99);
Digit Position (7): The triggering times of wireless cross zones
00= It will not make alarm if you trigger a single zone.
01-9= It will make alarm if you trigger a single zone in the times of 1-9.
Note: The zone no. of wireless zones should be processed to be 07-12.
Command Position 72: Re-dialing after communication failure
2
Default Values
Digit Position (1)-(2): Interval time between notice
of fail telecommunication and Re-dialing00= No re-dialer after communication failure
01-99= Interval time is set 01-99 hours
Digit Position (3): Re-dialing loop
0= No re-dialing loop set
1-9= Re-dialing loop is set 1-9 times
Command Position 99: Restore to Default Values
6.7 Setup logs of the Alarm Panel
Default Values
-34-
Network Alarm System
-35-
Network Alarm System
-36-
Network Alarm System
-37-
W
Network Alarm System
7 Operational Manual7.1 Illustration of Operational Interface1) Remote Controller
* Arm : Arm
* Disarm : Disarm
* Home Arm
* Panic : Emergency alarm. Pressing this button long will
make alarm emergency. (including alarm on-site
and dialing all alarm telephones)
Antenna
Indicator
Arm
Disarm
Panic
Home Arm
Picture 6 Remote Controller
7.2 Operational Combination
1) Installer's combination
2) User's combination
3) Duress combination
It is used to set the alarm panel. It can perform all commands for alarm panel
The default value is 012345.
4 user's combinations can be set at most. (#1 combination and #2 combination were
set in the default values)
The Arm type can control the Arm/ Disarm and Bypass of user.
Arm/ Disarm of 01-04 sub-address remote controllers were controlled
by the Arm type of #1-#4user.
Add “1” to the last number of each user's combination, it will be a Duress
combination (When the last number is 9, please input “0” in the end and without
carrying digit). When the user is seized by someone, the user can input the Duress
combination to realize the deletion of alarm in surface, but, meanwhile the alarm
panel sends the alarm information out by wired telephone network or GSM wireless
network.
-38-
Network Alarm System
7.3 How to Arm/ Disarm
7.4 How to Activate Alarm
1) Make Arm/ Disarm to the alarm panel by the remote controller;
Please press the relevant keys as the pictures above.
2) Make Arm/ Disarm to the alarm panel by the keypad;
In the status of standby, you can input the user's combination of 4 digits, and then
press “#”. If the combination input is correct, the alarm panel will transfer from
Disarm status to Arm status. Otherwise, the alarm panel will transfer from Arm
status to Disarm status.
3) Make Arm/ Disarm to the different zones of the alarm panel by setting Timer Arm/
Disarm.
4) Make Arm/ Disarm to the alarm panel remotely by inputting the correct remote
telephones and user's combination.
5) Make Arm/ Disarm to the alarm panel remotely by insertting the SMS in the alarm
panel remotely. (Please refer to the <GSM module operation manual>)
Note: When the alarm panel was made Arm, the alarm panel will make two sound
of clew “Di...Di..” and “Arm” indicator will be On; When the alarm panel was
made Disarm, the alarm panel will make two sound of clew “Di…Di..” and “Arm”
indicator will be Off; If the alarm panel has set the Arm Delay Time, you will hear
the clew of “sound for 1 second, halt for 1 second and more quick in last 10
seconds” when the alarm panel entries the status of Arm Delay Time. It clews you
to leave the spot soon. When the Arm Delay Time is finished and clew sound halts,
the alarm panel entries the status of “Arm”.
1) Burglar alarm
When the zone type was set to be “Exit/ Entry the Delay Zone”, “Perimeter Zone”,
“Interior Zone (Smart Alarm)”, “Day/ Eight Zone” and “Interior Zone (Delay)”
Zone, these zones will be in the status of vigilance only when the alarm panel is in
the status of Arm. Therefore, when you want to leave the house or working places,
you should remember to Arm the alarm panel. The alarm panel will make alarm
once there is someone entering.
2) Emergency alarm
When you meet the emergency status in the detective area, you can trigger the
relevant “Emergency Button”,
the alarm panel will receive the signal and it will make panic
alarm. (It will open the alarm on-site or buzzer sound and dial all pre-set
telephones and it will send the panic alarm information out.)
3) Duress alarm
When the user was forced to Disarm the system, the user can input the Duress
combination on the main panel to Disarm the system. Therefore, the alarm panel
will Disarm in surface, but, meanwhile the alarm panel will dial all the center
telephones and send the alarm information out.
7.5 How to Receive Alarm
press the of the remote controller and press the
?? of the keypad,
-39-
Network Alarm System
2) Receive the alarm manually
When the alarm telephones are entering, you can hear the alarm sound after
answering the phones. Then the alarm sound will halt for 5 seconds. During this
period, you can input the directives (please visit the attached list 1) on the keypad
of the telephones or mobile phones; When you don't make any action after
answering the phones (once you press any keys of the alarm panel, the alarm panel
will confirm the successful alarm receiving.), the telephone will be ring off in the
end of four times of alarm sound. And the alarm panel will dial the other groups of
telephones pre-set.
Note: If you input “2#” after receiving the phone to make Disarm, the alarm panel
won't dial the other groups of telephones preset.
When you are not on the alarm site, the alarm panel will make alarm by dialing the
telephones or mobile phones pre-set. After the ringing times pre-set are finished,
the alarm panel will ring off automatically; when you hear a short sound of clew
“Du…”, you can input the user's combination of 4 digits + # on the keypad
of telephones or mobile phones. You can hear a short sound of “Du…” if the
combination input is correct. Then you can make the following operation you want
(as attached list 1); If there is no operation within 30 seconds, the alarm panel will
ring off automatically.
Attached List 1:
7.6 Remote Setting
「 」 「 」
8. Technologic Parameter1) Alarm PanelSize: 258*260*77 mm (L*W*H) (without considering the height of antenna)Weight: 2.8 kgPower: AC 220V±15%, Battery 12V/7AhAssistant Output Current: 500mASystem Output Current: 800mA (The total current of the system's outerequipments should be controlled in this standard.)Wireless Working Frequency: 433MHzWireless Communication Distance: the distance between wireless PIR detector and
alarm panel ( 500m in the open area); Thedistance between wireless remote controllerand alarm panel ( 300m in the open area);Thedistance between wireless siren and alarmpanel ( 300m in the open area).
<≤
≥
≥
≥
-40-
Network Alarm System
2) Wireless Remote ControllerWorking Voltage: 12V 27A (stock battery)Standby Current: 5uATransmitting Power: 10mWTransmitting Frequency: 433MHz
* The user mustn't set “110”, “119” or the local Police telephone as the alarmtelephones without the allowance of Police Bureau.
* The alarm panel and other spares are unable to be swamped.* The alarm system belongs to non-explosion-proof. It can not be used in he
dangerous places (That is a place of flammable & combustible gas,dust and fiber with a definite density.)
* Please don't dismount the alarm panel in random, lest the unexpected events or patdamage happened.
* If there are any troubles of the alarm system happened during using period, pleasecontact with the Customer Service of our company.
* Regular maintenance and inspection by the installer and frequent testing by the userare vital to the continuous and satisfying operation of any alarm systems.
* It is suggested to change the battery (at least one year). The non-recharged batteryand non-sealed battery are forbidden to use.
≤≤
9. Notes
tⅠ,Ⅱ,Ⅲof .
10. Solutions of Simple Trouble
-41-
Network Alarm System
-42-
Network Alarm System
The limitation of this system
While this system is an advanced design security system, it does not offer guaranteed
protection against burglar or fire or other emergency. Any alarm systems, whether
commercial or residential, is subject to compromise or failure to warn for variety of
reasons. For example:
1 Owing to the omission of the user, the system wasn't Armed.
2 Misunderstanding on the user's manual by the user or installer causes the abnormal
working of the system.
3 Intruders may gain access through unprotected openings or have the technical
sophistication to bypass an alarm sensor or disconnect an alarm warning device.
Passive Infrared Motion Detectors can only detect intrusion within the designed
ranges as diagrammed in their installation manual. They do not provide volumetric
area protection. They can not detect motion or intrusion that takes place behind
walls, ceiling, floors, closed doors, glass partitions, glass doors, or windows.
4 Passive Infrared Detector sense changes in temperature; however, as the ambient
temperature of protected area approaches the temperature range of 30 to 40 , the
detection performance will decrease.
5 It is exiting no-power or battery-aging.
6 Alarm warning devices such as sirens, bells or horns may not alert people or wake
up sleeper if they are located on the other side of closed or partly open doors.
7 Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily out of service. Telephone
lines are also subject to compromise by sophisticated intruders.
8 The most common cause of an alarm system not functioning when an intrusion or
fire occurs is inadequate maintenance. This alarm system should be tested weekly to
make sure all sensors and transmitters are working properly.
9 The wireless communication distance is the testing figure in open area. Please make
sure no obstacle in the surrounding environment to guarantee the reliability of the
wireless communication distance farther.
10 If you disagree with the above mentioned items, please return the alarm system to
our company within 3 days from purchasing. Installing an alarm system may make
one eligible for lower insurance rates, but an alarm system is not a substitute for
insurance. Homeowners, property owners and renters should continue to act
prudently themselves and continue to insure their lives and property.
℃ ℃
-43-
P/N:
V1.0
35031000A1188010