knowledge is power sm apparatus maintenance and power management for energy delivery assessing the...
TRANSCRIPT
Knowledge Is PowerSM
Apparatus Maintenance and Power Management for Energy Delivery
Assessing the Magnetic Circuit of a TransformerJill DuplessisDoble Engineering Company
2002 Regional Seminar - Denver
Objectives•To provide an explanation of what we are learning about a transformer when we perform an exciting current test and a leakage reactance test.
Magnetic Circuit of a Transformer
2002 Regional Seminar - Denver
•To review which tests Doble recommends that you should be performing & when.•To review how one goes about analyzing results from these tests.•Finally, to reinforce what we learn by reviewing case studies together.
Fundamental Principle of Operation
Energy Transfer from one electrical circuit to another.
A Transformer
2002 Regional Seminar - Denver
Not perfect:
•Some energy is lost and dissipated as heat.•Some energy is temporarily stored.
Assuming a 1:1 turns ratio, the equivalent circuit of an Ideal Transformer looks like this:
Equivalent Circuit of an Ideal Transformer
2002 Regional Seminar - Denver
Energy In
Energy Out
Since there are no losses in an ideal transformer, Energy In = Energy Out
If the energy transfer process was perfect, we’d be talking about an ideal transformer.
Equivalent Circuit of a Transformer
2002 Regional Seminar - Denver
From an energy transfer point-of-view, the elements in this circuit represent the imperfections in a transformer.
Exciting Current and Loss measurement, Zm
Leakage Reactance and Loss measurement, ZL
Dielectric loss (measured in overall tests is lumped in with Rm)
Primary winding dc resistance measurement
Secondary winding dc resistance measurement
Lm CUST
Rm
R L-1 L 1 L 2 R L-2R DC-1 R DC-2
2002 Regional Seminar - Denver
Practical Transformer vs. Ideal Transformer
•Losses occur due to the following imperfections in a transformer:
Losses in a Power Transformer
•Windings have resistance•Real and reactive losses exist in the core•Physical cores have a finite permeability; exciting current is required to produce magnetic flux•There is magnetic flux leakage•Losses in the dielectric circuit
What we measured in the overall tests on a xfmr.
DC resistance tests
Exciting current tests
Leakage reactance tests
Good News
Losses in a transformer are specified & controlled.
Losses in a Power Transformer
2002 Regional Seminar - Denver
Manufacturer bases price on guaranteed losses.Manufacturer designs adequate cooling for a transformer based on losses.even though losses represent a cost to the user, from a diagnostic perspective, we can use loss info to verify the integrity of the unit.We are looking for evidence of a change in the known losses of the transformer.
A History Lesson in Magnetism:
Before we get started...
2002 Regional Seminar - Denver
1820 - Hans Christian Oersted discovered that when an electric current flows through a wire, it causes a compass needle to rotate.
Michael Faraday - his ideas about conservation of energy led him to believe that since an electric current could cause a magnetic field, a magnetic field should be able to produce an electric current.
i.e. he discovered that an electric current produces a magnetic field.
Faraday demonstrated this principle of induction in 1831 with the following experiment:
History of Magnetism
2002 Regional Seminar - Denver
•He moved a coil of wire relative to a magnet & discovered that a voltage was induced in the coil.
Michael Faraday demonstrated the phenomenon of electromagnetism in a series of experiments.
(but only when relative movement is taking place)
•Responsible for the principles by which electric generators and transformers work.
For example We apply Faraday’s discovery to the arrangement where a magnetic field is associated with the turns of a winding.
History of Magnetism
2002 Regional Seminar - Denver
Any variation in the strength of the magnetic field will induce a voltage between the terminals of the winding.
No voltage is produced if the magnetic field strength is constant.
(This time - we are not moving the winding, it stays stationary. Instead, we vary the magnetic field same effect.)
Next consider a winding through which a current is passed.
History of Magnetism
2002 Regional Seminar - Denver
(Remember that Oersted proved that a current flowing through a winding will produce a magnetic field within the winding & in the space surrounding the winding).So, when the current is varied (as by applying an a.c. source), the strength of the magnetic field produced by the winding will vary.If we place a 2nd winding near this 1st winding, the 2nd winding will enclose some of the magnetic field produced by the 1st.
History of Magnetism
2002 Regional Seminar - Denver
Since the varying magnetic field produced by the 1st winding is “linked” by the 2nd winding, a voltage will be produced between the terminals of the 2nd winding.
A Word about Linking:
If windings are only in close proximity to each other, linking or coupling between them is not very effective.
a considerable amt. of the magnetic field produced by the 1st wdg. does not link the 2nd wdg.
How can we improve the linking between windings?
History of Magnetism
2002 Regional Seminar - Denver
By arranging the windings relative to each other using a structure of magnetic material (the core).The core uses suitable magnetic material (usually silicon-iron) that allows a very high degree of coupling between windings.
UNFORTUNATELY...The core material is not perfect.
Recall that one of the properties that differentiates an ideal transformer from an actual transformer sitting in a substation is that ...
Electromagnetism Background
2002 Regional Seminar - Denver
We see this...During an open-circuit measurement in which we observe that a small (usually inductive) current is drawn at the primary terminals even though the secondary terminals are open.
•Physical cores have a finite permeability exciting current is required to produce magnetic flux in the core
Example of Core Characteristics
2002 Regional Seminar - Denver
Permeability (slope) - the ability of a material to conduct flux
Illustrates affect of core construction on magnetizing/ hysteresis effects.
When the Secondary Winding Is Open
Exciting Current Theory
2002 Regional Seminar - Denver
E1
Iex
1:1
+
-E2
The current that flows in the primary winding should be sufficient to excite the core.
If Load was Connected to the Secondary
Exciting Current Theory
2002 Regional Seminar - Denver
IIexex
EE22
1:11:1
11
EE11
++
--
The primary current increases by the value of the secondary current.
ZZLL
II22
22
+ I+ I2222
When We Have a Turn-to-Turn Fault on the Secondary During the Exciting Current Test
Exciting Current Theory
2002 Regional Seminar - Denver
1:11:111
HH11
HH00
++EE11
--
HVHV
LVLV
IIff
ff
ffIIexex + I+ Iff
The primary current increases by the value of the current through the short-circuited turns.
Detection of Winding to Ground Fault in the Secondary During Exciting Current Test?
Exciting Current Theory
2002 Regional Seminar - Denver
1:1
H0
H1
+
-
HV
LV
Iex
If
f
+ If ff
If secondary winding is and one of the windings develops a fault to ground, the primary current will increase by the value of current circulating through the secondary winding and two grounds.
How Do We Detect Fault in the Preventive Autotransformer During Exciting Current Test?
Exciting Current Theory
2002 Regional Seminar - Denver
1:1
H1
H0
HV
LV
Iex
Ia
a
+ Iaaa
When autotransformer is connected across two taps it acts as a load and the primary current goes up.
Useful in Detecting:
Exciting Current Tests
2002 Regional Seminar - Denver
•Turn-to-turn winding failure
•LTC problems
•1 or more turns completely short-circuited.
•Open circuit, shorted turns or high resistance connections in the LTC P.A., series auto or series transformer
•2 or more parallel strands of different turns are short-circuited.
•misalignment, mechanical problems, coking and wear of LTC & DETC contacts
Useful in Detecting (cont):
Exciting Current Tests
2002 Regional Seminar - Denver
•Manufacturing defects.
•Abnormal (multiple) core grounds.
•Changes in the core characteristics.
Exciting Current Test Procedure - Delta
2002 Regional Seminar - Denver
H-V Test Cable
L-V Lead
GND Lead
I&W Meter
Guard Point
H2
H3
Ie (1-2)
Ie (1-3)
L-V Lead
GND Lead
I&W Meter
GuardPoint
H2H3
Ie (1-2)
Ie (1-3)
UST Mode
Note: For Exciting Current tests performed with the M4000, the charging current (mA) and watts-loss are recorded.
Exciting Current Test Procedure -Wye
2002 Regional Seminar - Denver
H-V Test Cable
L-V LeadI&W Meter
Guard Point
H2
H1
H3
Ie (1-0)
H0
L-V Lead
I&W Meter
GuardPoint
H2H1H3
Ie (1-0)
H0
UST Mode
Important!!!!
2002 Regional Seminar - Denver
Test Measurement Recommendations
Especially Important!!!!
2002 Regional Seminar - Denver
Test Measurement Recommendations
TEST RESULTS ANALYSIS
Analysis
2002 Regional Seminar - Denver
•It is useful to know whether specimen is capacitive or inductive
•LTC and phase patterns should be analyzed
•Watts loss is always determined by the core
So...•What do we mean by LTC & phase pattern?•What makes a specimen inductive rather than capacitive or vice-versa?
LTC and Phase Pattern
2002 Regional Seminar - Denver
Nomenclature
•LTC pattern•The relationship between exciting current (or loss) measurements recorded within a phase as the LTC is moved from one position to another.•12 LTC patterns
•Phase Pattern•The relationship between exciting current (or loss) measurements recorded for all three phases at a single tap position.•3 Phase patterns
To understand what makes a specimen capacitive or inductive, we revisit the equivalent circuit of a transformer.
Capacitive or Inductive Specimen?
2002 Regional Seminar - Denver
Lm CUST
Rm
R L-1 L 1 L 2 R L-2R DC-1 R DC-2
Exciting Current and Loss measurement, Zm
Practically all of the magnetic flux is confined to the core. the impedance encountered by the current is predominantly determined by the reluctance of the core.
we can neglect the energy storage and loss in the leakage channel.
I2R loss is much lower than loss in the core
Equivalent Circuit of the Open-Circuit Test reduces to:
Capacitive or Inductive Specimen?
2002 Regional Seminar - Denver
I C R
IC
IL
R
ex
I
I
I
I
V
Q
L C R
L I I
ex
V
L - Magnetizing InductanceC - Turn-to-turn CapacitanceR - Resistance associated with losses in the core & turn-to-turn insulation
Capacitive or Inductive Specimen?
2002 Regional Seminar - Denver
•Inductive LTC pattern•Magnetizing current capacitive current in each tap position, so that the resultant measured current is always inductive in nature.
•Characteristic of the vast majority of exciting current test results reported for transformers.
•Capacitive LTC pattern•Capacitive current magnetizing current, at several tap positions.
Analysis for Inductive Specimens
2002 Regional Seminar - Denver
For an inductive specimen (majority of xfmrs):
•The phase pattern at each tap position should be confirmed.•This pattern should be identical at every tap position, for both mA & Watts measurements.
•The LTC pattern should be identified by comparing the behavior of the test data with one of the 12 documented LTC patterns.•The LTC pattern should be the same in each of the 3 phases, for both the mA results & the Watts results.
Analysis for Inductive Specimens
2002 Regional Seminar - Denver
•3-legged core-type transformer with a delta-connected winding if testing two phases of the winding in parallel.
•3-legged core-type transformer that has a wye-connected winding with an inaccessible neutral.
L-H-L Characteristic of: Phase Pattern B
•5-legged core or shell-type transformer that has a delta-connected secondary winding
•3-legged core-type transformerH-L-H Characteristic of: Phase Pattern A•Possible phase patterns:
Wye Winding with No H0 Bushing
2002 Regional Seminar - Denver
Wye Winding with No H0 Bushing
2002 Regional Seminar - Denver
All 3 Readings Dissimilar (H-M-L)•May be indicative of a magnetized core
Analysis for Inductive Specimens
2002 Regional Seminar - Denver
•May actually be “capacitive” specimen - not inductive after all
•Characteristic of four and five legged core-type transformers and shell-type transformers with non-delta secondary windings
All 3 Readings Similar Phase Pattern C
FACTORS OTHER THAN DEFECTS THAT MAY INFLUENCE TEST RESULTS:
Analysis
2002 Regional Seminar - Denver
•UST capacitance
•Test voltage
•Residual magnetism
•Design and position of LTC
•Test Connections
If capacitance inductive component, you have a capacitive specimen & analysis changes.
Test results are voltage dependent so data can only be compared if performed at identical voltages.
Experience with Capacitive LTC Patterns
•Effects documented as early as 1972
Capacitive LTC Patterns
2002 Regional Seminar - Denver
•1996 - 3rd Component of Exciting Current discussed in detail
•Negligible in Low-voltage Transformers
•Traditionally, IC Im in High-voltage Transformers
•Today, IC may be of same order of magnitude or Im
•Due to Reduced losses & magnetizing power of xfmr cores•Due to high capacitance windings
Effects of a Strong Capacitive Presence
•PHASE PATTERN IS AFFECTED
Capacitive LTC Patterns
2002 Regional Seminar - Denver
•Depends on Relative Magnitudes of Im and IC in Each Phase•Typically all 3 Phases are Capacitive
•CAN RESULT IN ANY PHASE PATTERN
• Measured Phase Pattern Accepted as Benchmark
•Phase Pattern for Current may Differ from Phase Pattern for Loss
Test Voltage
Factors other than defects that can influence test results.
2002 Regional Seminar - Denver
C, I [mA] ICL
5 10 V [kV]
I
IL
IL < IC
IL > IC
RESIDUAL MAGNETISM
Factors other than defects that can influence test results.
2002 Regional Seminar - Denver
•Always present, but in most cases has no significant effect on test results.
•Majority of problems have a much larger effect (> 50%) on test results than residual magnetism would have
•Increases current if specimen is inductive•Increases or decreases current if specimen is capacitive
Example of an LTC Pattern
2002 Regional Seminar - Denver
Test results for all non-bridging positions are equal. Test results for all bridging positions are equal.
Pattern 1:
I1
N 4R 8R 12R 16R
Example of an LTC Pattern
2002 Regional Seminar - Denver
Test results for all non-bridging positions are equal. Test results for all bridging positions are equal, except in one or several positions, with all readings in these positions being equal as well.
Pattern 2:
N 4R 8R 12R 16R
Exciting Current Testing
2002 Regional Seminar - Denver
Case Studies
Case Number 02-06
Unit Tested:
U.S. Transformer, 3Φ two-winding transformer
Exciting Current Case Study 1
2002 Regional Seminar - Denver
•20 MVA
•69/12.47 kV
•Rewound in 2000
•1978 - vintage
•Δ-Y connected
Testing Circumstances:
•Tested upon receipt from the manufacturer’s repair facility where it had been completely rewound.
Case Study 1 (# 02-06)
2002 Regional Seminar - Denver
•overall insulation tests - acceptable
•bushing tests - acceptable
•field power factor test on an oil sample from the main tank - acceptable
Case Study 1 - Exciting Current Results
2002 Regional Seminar - Denver
Tap Position A-phase(mA)
B-phase(mA)
C-phase(mA)
A-phase (W) B-phase (W) C-phase (W)
N 20.06 8.72 19.05 149.6 66.5 142.81R 82.54 72.04 81.98 161.7 75.91 155.32R 20.16 8.94 19.14 150.1 69.06 143.33R 82.7 72.2 82.14 162.7 80.92 156.2
4R 20.37 9.61 19.36 151.4 76.53 144.75R 82.94 72.45 82.37 164.5 90.76 158.26R 20.69 10.72 19.68 153.5 89.04 1477R 83.26 72.86 82.68 166.8 106.2 161.18R 21.09 12.32 20.28 156.3 106.5 152
9R 83.62 73.42 83.39 169.9 126 171.910R 21.57 14.42 22.4 159.7 128.9 17611R 84.07 74.18 84.27 173.6 150.5 194.712R 22.13 17.04 23.93 163.9 156.3 190.513R 84.54 75.17 85.17 178.1 180.4 213.6
14R 22.78 20.18 25.8 168.6 188.7 21115R 85.09 76.45 86.21 183.1 215.3 234.616R 23.49 23.85 27.88 173.9 226.2 232.9
LTC Pattern 4
2002 Regional Seminar - Denver
Test results represent a series transformer or autotransformer exciting current superimposed on pattern 1. This current changes according to increments in the tap winding.
Pattern 4:
I1
N 4R 8R 12R 16R
LTC Pattern - Phase A
2002 Regional Seminar - Denver
Phase A
0
12
24
36
48
60
72
84
N (1R) 2R (3R) 4R (5R) 6R (7R) 8R (9R) 10R (11R) 12R (13R) 14R (15R) 16R
LT C Posit ion
[mA
] B
ridg
ing
0
6
12
18
24
[mA
] N
on-b
ridg
ing
Bridging Positions Non-bridging Positions
LTC Pattern - Phase B
2002 Regional Seminar - Denver
Phase B
0
12
24
36
48
60
72
84
N (1R) 2R (3R) 4R (5R) 6R (7R) 8R (9R) 10R (11R) 12R (13R) 14R (15R) 16R
LT C Posit ion
[mA
] B
ridg
ing
0
5
10
15
20
25
[mA
] N
on-b
ridg
ing
Bridging Positions Non-bridging Positions
LTC Pattern - Phase C
2002 Regional Seminar - Denver
Phase C
0
14
28
42
56
70
84
N (1R) 2R (3R) 4R (5R) 6R (7R) 8R (9R) 10R (11R) 12R (13R) 14R (15R) 16R
LT C Posit ion (Non-bridging superimposed on Bridging)
[mA
] B
ridg
ing
0
6
12
18
24
[mA
] N
on-b
ridg
ing
Briding Posit ions Non-bridging Posit ions
Phase Pattern (bridging positions) - Current
2002 Regional Seminar - Denver
60
65
70
75
80
85
90
1R 3R 5R 7R 9R 11R 13R 15R
[mA
]
A-phase b. B-phase b. C-phase b.
Phase Pattern (non-bridging positions) - Current
2002 Regional Seminar - Denver
0
5
10
15
20
25
30
N 2R 4R 6R 8R 10R 12R 14R 16R
[mA
]
A-phase n.b. B-phase n.b. C-phase n.b.
Phase Pattern (non-bridging positions) - Watts
2002 Regional Seminar - Denver
0
50
100
150
200
250
N 2R 4R 6R 8R 10R 12R 14R 16R
[W]
A-phase n.b. B-phase n.b. C-phase n.b.
Phase Pattern (bridging positions) - Watts
2002 Regional Seminar - Denver
0
50
100
150
200
250
1R 3R 5R 7R 9R 11R 13R 15R
[W]
A-phase b. B-phase b. C-phase b.
Problem Found
2002 Regional Seminar - Denver
Investigation
•Manufacturer electrically isolated the series transformer for tests; exciting current tests indicated a definite problem on the center phase.
The short was at the bottom of the coil between the first turn and the bottom lead. At the location where the lead enters the coil and bends, the insulation on the top strand of the lead and the bottom strand of the first turn was cut, allowing the two strands to come into contact with each other. The factory’s normal practice includes taping a NOMEX pad in between the lead and adjacent strands for added protection since there is a risk of damaging the insulation in this area by moving the leads around. In this case, the pad was missing.
•Problem: a short between turns in the outer coil of the center phase of the series transformer.
Comments
2002 Regional Seminar - Denver
The insulation failure that caused the strands to short affected the current circulating through the series transformer in all LTC positions.
•partial turn-to-turn short circuit acted as a load on the transformer.
in-phase, or loss, component of the exciting current exciting current magnitude
Why, in the bridging tap positions, was the problem not noticeable in the exciting current measurements while it was in the loss readings?
Capacitive LTC patterns
Unit Tested:
General Electric, 3Φ two-winding transformer
Case Study 2 (# 02-09)
2002 Regional Seminar - Denver
•7.5 MVA
•67/12.5 kV
•G.E. Type LRT-200A LTC
•1982 - vintage
•Δ-Y connected
Testing Circumstances:
•Concern from utility owner that the protection circuitry for the vacuum bottles in the LTC was not working properly.
Case Study 2
2002 Regional Seminar - Denver
•X1 LTC lead “S” was twisted, which caused the X1 bypass switch to be out of synchronization with the other two phases.
•Power factor & TTR test results - normal
•Exciting current results - unusual
Exciting Current Data: LTC Pattern Analysis
2002 Regional Seminar - Denver
LTC PATTERN 2
Non-Bridging Tap Positions - Current Measurements
Exciting Current Data: Phase Pattern Analysis
2002 Regional Seminar - Denver
Phase Pattern B
Current Measurements - Phase Pattern B
Explanation of Phase Pattern in N.B. Positions
2002 Regional Seminar - Denver
IQ = Quadrature
Component of Exciting Current ~ Measured Exciting Current (L-H-L)
IL = Icore
IC
IQIQ
ICICIL
IL
IL
Non-Bridging Tap Positions - Loss Measurements
Exciting Current Data: Phase Pattern Analysis
2002 Regional Seminar - Denver
Phase Pattern A
Bridging Tap Positions - Loss Measurements
Exciting Current Data: Phase Pattern Analysis
2002 Regional Seminar - Denver
Phase Pattern A
Bridging Tap Positions - Current Measurements
Exciting Current Data: Phase Pattern Analysis
2002 Regional Seminar - Denver
Phase Pattern A
Explanation of Phase Pattern in B. Positions
2002 Regional Seminar - Denver
Icore
IC
IQ
IQ
ICIC
Icore
Icore
IPAIPAIPA
IL = Icore + IPA
IQ = IL + IC =
Quadrature Component ~ Measured Exciting Current
(H-L-H)
Exciting Current Measurements
2002 Regional Seminar - Denver
N 1L 2L 3L 4L 5L 6L 7L 8L 9L 10L 11L 12L 13L 14L 15L 16L
H1-H2
H3-H10
10
20
30
40
50
60
[mA]
LTC Position
Watts Measurements
2002 Regional Seminar - Denver
N 1L 2L 3L 4L 5L 6L 7L 8L 9L 10L 11L 12L 13L 14L 15L 16L
H1-H2
H3-H10
10
20
30
40
50
60
70
80
90
100
[W]
LTC Position
Doble Turns Ratio Test
2002 Regional Seminar - Denver
Doble Transformer Turns Ratio
Benefits of the Turns Ratio Test
2002 Regional Seminar - Denver
•Confirm nameplate ratios
•Detect short-circuited turn-to-turn insulation
•Detect open-circuited windings
Doble TTR Test Procedure
2002 Regional Seminar - Denver
UST
HV Lead
LV Lead
Doble TTR Capacitor
CTRUE
CTRUE=I
V x
Doble TTR Test Procedure
2002 Regional Seminar - Denver
UST
HV Lead
LV Lead
Doble TTR Capacitor
V1
N VV
1
2
CIV
apparent2
CI
V /N)apparent
1
(
Now, if we take the ratio:
CTRUE/CApparent
We obtain:
N - the turns ratio
Doble TTR - DTA Screen
2002 Regional Seminar - Denver
TTR Case Study
2002 Regional Seminar - Denver
Unit Tested:
General Electric, 3Φ two-winding transformer
•5 MVA•50.5/13.09 kV•1980 - vintage
•Δ-Y connected
TTR Case Study
2002 Regional Seminar - Denver
Exciting Current Test Results (4/24/02)
TTR Test Results (4/24/02)
Previous TTR Test Results (7/25/95)
TTR Case Study
2002 Regional Seminar - Denver
TTR Case Study
2002 Regional Seminar - Denver
Leakage Reactance Tests
2002 Regional Seminar - Denver
Doble Leakage Reactance Test
Leakage Reactance Test
2002 Regional Seminar - Denver
IIexex
EE22
1:11:1
11
EE11
++
--
ZZLL
II22
22
+ I+ I2222
The combined action of both currents results in some of the flux being present in the unit permeability space.
Leakage Flux
2002 Regional Seminar - Denver
The unit permeability space includes the space between the windings, w/in the windings & between the windings and the tank.
LLFlux that is not confined to the core for the entire length of its path.
•The primary winding is linked by almost all of the leakage flux in addition to the magnetizing flux, while the secondary winding is linked by the magnetizing flux but very little of the leakage flux.
Leakage Flux
2002 Regional Seminar - Denver
the primary winding has a greater voltage induced in each of its turns under load than the secondary winding.
•We can account for this voltage drop by introducing a leakage reactance.
Leakage Reactance Equivalent Circuit
2002 Regional Seminar - Denver
Lm CUST
Rm
R L-1 L 1 L 2 R L-2R DC-1 R DC-2
EE22EE11
21 1 2 L-R L- L L R 2R DC-1 R DC-
EE22EE11
Short-Circuit Impedance
Leakage Reactance
Leakage reactance for most xfmrs is constant & can be measured w/out the presence of the “full load” leakage flux that requires full load current.
Leakage Channel
2002 Regional Seminar - Denver
Leakage channelOuter winding
Inner winding
Top yoke
Bottom yoke
Core leg
The leakage flux path includes the regions occupied by the windings. The leakage reactance may be sensitive to deformations in the windings.
•Confirm nameplate impedance
Benefits of the Leakage Reactance Test
2002 Regional Seminar - Denver
•Investigate winding deformations•Due to through faults•Due to rough handling during transportation
•Easy to perform with the proper additions to the M4000 (M4110 Module)
Capacitance:•Sensitive to temperature & contamination•Normally involves all three phases
Capacitance versus Leakage Reactance
2002 Regional Seminar - Denver
Leakage Reactance:•Not sensitive to temperature & contamination•Can be performed on a per-phase basis•Better sensitivity to winding deformations•Can compare results to N/P Impedance
Excitation Current Tests:•More sensitive to core problems than winding deformations
Initial test:•Perform Three-Phase Equivalent test for comparison to Nameplate•Perform Per-Phase tests to act as benchmark for future tests
Test Procedures
2002 Regional Seminar - Denver
Subsequent tests:•Perform only Per-Phase tests for comparison to benchmark tests
Doble M4110 Leakage Reactance Test Set
Leakage Reactance Test
2002 Regional Seminar - Denver
M4100 & M4110 L.R. Module Test Connections
2002 Regional Seminar - Denver
Nameplate Data Required for LRT
2002 Regional Seminar - Denver
3-Phase Equivalent Leakage Reactance Test
3-Phase Equivalent Leakage Reactance Test
2002 Regional Seminar - Denver
Nameplate Data Required for LRT
2002 Regional Seminar - Denver
Per-Phase Leakage Reactance Test
Per-Phase Leakage Reactance Test
2002 Regional Seminar - Denver
•First, or benchmark test, should be within 3% of Nameplate.
Analysis
2002 Regional Seminar - Denver
•Subsequent tests should be within 2% of benchmark.
•If all three phases on Per-Phase tests agree, it is likely that there is no winding deformation.
LRT Case Study
2002 Regional Seminar - Denver
Unit Tested:
General Electric, 3Φ two-winding transformer
•80/89.6 MVA
•1961 - vintage
•114 GR. Y/65.8 - 13.2 kV
Background:
•During a short outage for normal generator maintenance, the 13.8 kV generator bus PTs were replaced due to PCB contamination.
LRT Case Study - Background
2002 Regional Seminar - Denver
•During the replacement, the secondary wiring on the potential transformers was mistakenly reversed.
•The reversed potential to the synchronizing equipment allowed the generator breaker to be closed, and connected the generator into the transmission system 180 degrees out-of-phase.
•The generator remained connected to the system for 3.06 seconds and operated in an out-of-step manner for the entire period.
LRT Case Study - Background
2002 Regional Seminar - Denver
•The generator was closed into the system, 180 degrees out-of-phase, a second time.
•The generator operated in an out-of-step condition for 200 ms.
•The initial current was about 26,600 amps on the 13.8 kV bus and then declined until the trip occurred.
•The second trip command was initiated by the step-up transformer sudden pressure relay, which tripped into a lockout relay. No further attempts were made to close the generator breaker.
LRT Case Study - Inspection
2002 Regional Seminar - Denver
Inspection:•An external visual inspection was made and no apparent problems were found.
•The secondary wiring on the 13.8 kV bus PT’s was checked and wiring errors were discovered, corrected and tested.•The sudden pressure relay that initiated the second trip was found to have welded contacts and was replaced.
•An oil sample was taken from the transformer and sent in for DGA analysis; no change in gas quantities was found.
LRT Case Study - Investigation
2002 Regional Seminar - Denver
% Power FactorInsul. kV mA Watts
Meas Corr
Corr.Factor
Cap(pF)
RTG
CH + CHL 10 185.6 6.642 1.01 49246CH 10 184.5 6.646 0.36 0.36 1.01 48952 G
CHL (UST) 10 1.101 0 0 0 1.01 292.1 GCHL 1.100 -0.004 -0.04 -0.04 1.01 294 GCL + CHL 10 152 5.190 1.01 40322CL 10 150.90 5.196 0.34 0.34 1.01 40028 ICHL (UST) 10 1.100 0 0 0 1.01 291.90 GCHL 1.100 -0.006 -0.05 -0.05 1.01 294 G
Overall Test Results - Post-fault (2000)
•Insignificant change in the capacitance of the LV winding to ground insulation occurred from 1986 to 1999. (There were no results available for this transformer prior to 1986).
Observations from Overall Test Results
2002 Regional Seminar - Denver
•However, capacitance decreased from 42,371 pF in 1999 to a post-incident capacitance of 40028 pF, a change of 5.53%.
Observations
2002 Regional Seminar - Denver
HV
LV
Inter-winding Shield
CL
CH
CH-S
CL-S
TankandCore
•Due to a grounded shield in between the HV and LV windings, the L-G measurement is actually a combination of insulation systems: CL & CL-S
•Changes in a capacitance measurement usually represent physical changes in the insulation system under measurement.
•The average short circuit impedance listed on nameplate was 10.02%.
Leakage Reactance Test Results
2002 Regional Seminar - Denver
•The 3-phase Leakage Reactance measurement using the M4110 was 11.26%.•The 3-phase equivalent test deviated from the average short circuit impedance by 12.35%.
Three-Phase Equivalent
•The measured per-phase results were 11.92%, 10.79% and 9.12% for phases A, B and C, respectively.
Leakage Reactance Test Results
2002 Regional Seminar - Denver
•The per-phase measurement deviated from the average by as much as 14%.
•An internal inspection was scheduled.
Per-Phase Tests:
Upon entering the transformer it was obvious severe damage had occurred. Damage to top clamping plates and wedge clamps.
Internal Inspection
2002 Regional Seminar - Denver
Internal Inspection
2002 Regional Seminar - Denver
•Damage on phase #1 was somewhat worse.
•Photo 5 shows top end ring pushed up about three inches
•Following the internal inspection, arrangements were made to replace the failed step-up transformer.
•During the disassembly of the transformer, it was expected to see some deformation in the windings from the forces which caused the damage to the clamping plates, wedge clamps and end rings.
Observations from Internal Inspection
2002 Regional Seminar - Denver
•Actual damage to the windings was very minimal with no noticeable deformation.
•The sudden pressure relay operated due to a shock wave in the oil created by mechanical forces. This is assumed due to lack of gas generation and no hot spots were found.
Thank You!
2002 Regional Seminar - Denver
QUESTIONS?