HUSSONG MANUFACTURING CO., INC. READ ALL THESE STEPS BEFORE STARTING INSTALLATION. LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE. This kit must be installed by a qualified installer, service agency, or gas supplier at the time of the heater installation. These instructions must be used in conjunction with the installation and operation manual provided with the appliance. Please read the appliance owner’s manual completely before performing any procedures in these instructions. INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. KOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures are hot! WARNING: Minimum clearances below the ceiling is 2-1/2”. Note that staining or streaking may occur on light colored ceilings to any dust, etc. in air flow. Placing the plenum(s) lower on the wall will help reduce the possibility of staining or streaking. For use with the Callway-50 #CLW-50 Direct Vent Gas Fireplace This optional convection duct kit redistributes the warm air flow away from the fireplace opening to a more desirable location using natural convection without the use of a fan. The warm air flow may be relocated to a position higher up the wall, out the sidewalls, or even to an adjacent room. The result is much cooler wall temperatures above the fire- place opening for locating televisions, artwork, etc. The use of this kit will permit lower mantel clear- ances to be used. These lower mantel clear- ances must be only used when the KZK Duct system is installed. English and French installation manuals are available through your local dealer. Visit our website www.kozyheat.com. Les manuels d’installation en français et en anglais sont disponibles chez votre détaillant local. Visitez www.kozyheat.com. Hussong Manufacturing Co., Inc. P.O. Box 577, 204 Industrial Park Drive Lakefield, MN 56150-0577, USA CLW-50 • Rev. 1, 2/18 Report Number: 0216GF054S

Upload: others

Post on 28-Feb-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

HUSSONG MANUFACTURING CO., INC.

READ ALL THESE STEPS BEFORE STARTING INSTALLATION.

LEAVE THESE INSTRUCTIONS WITH THE APPLIANCE.

This kit must be installed by a qualified installer, service agency, or gas supplier at the time of the heater installation. These instructions must be used in conjunction with the installation and operation manual provided with the appliance. Please read the appliance owner’s manual completely before performing any procedures in these instructions.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

KOMFORT ZONE KIT

WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures are hot!

WARNING: Minimum clearances below the ceiling is 2-1/2”. Note that staining or streaking may occur on light colored ceilings to any dust, etc. in air flow. Placing the plenum(s) lower on the wall will help reduce the possibility of staining or streaking.

For use with the Callway-50 #CLW-50Direct Vent Gas Fireplace

This optional convection duct kit redistributes the warm air flow away from the fireplace opening to a more desirable location using natural convection without the use of a fan. The warm air flow may be relocated to a position higher up the wall, out the sidewalls, or even to an adjacent room. The result is much cooler wall temperatures above the fire-place opening for locating televisions, artwork, etc.

The use of this kit will permit lower mantel clear-ances to be used. These lower mantel clear-ances must be only used when the KZK Duct system is installed.

English and French installation manuals are available through your local dealer. Visit our website www.kozyheat.com.

Les manuels d’installation en français et en anglais sont disponibles chez votre détaillant local. Visitez www.kozyheat.com.

Hussong Manufacturing Co., Inc. P.O. Box 577, 204 Industrial Park Drive Lakefield, MN 56150-0577, USA

CLW-50 • Rev. 1, 2/18Report Number: 0216GF054S

Page 2: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures
Page 3: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

Komfort Zone Kit Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 3

A. Kit Contents

497⁄8”(1267mm)

313⁄16”(97mm)

4 take o� collars included

#KZK-050

15¾”(400mm)

7¾”(197mm)

#KZK-158

4 take o� collars included

(4) - 10’ x 5” (aluminum �ex) listed to UL-181Class 0 Air Duct

#KZK-410

Page 4: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

4 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit

B. Suggested Configurations

#KZK-158 SIDE WALL OUTLET

#KZK-158 REAR WALL OUTLET

NOTE: FIREPLACE VENT MAY CONFLICT WITH PLENUM. OFFSET VENT AROUND PLENUM.

#KZK-050 FRONT WALL OUTLET

#KZK-050 REAR WALL OUTLET

#KZK-050 CORNER INSTALLATION

Page 5: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

Komfort Zone Kit Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 5

C. Overview

26½” Min20’ Max

12½”

16¾”

9¾”

39”

2½” Minimum clearance to

ceilingCEILING

Minimum ½”clearance to combustiblesaround pipe

The tubing that connects the plenum to the fireplace must be UL181 Class 0 approved air duct.If you are mounting the plenum above the fireplace 10’ or less, use (1) #KZK-410 kit.If you are mounting the plenum above the fireplace between 10’ to 20’, you will need (2) #KZK-410 kit and #KZK-CPL coupler kit.

Page 6: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

6 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit

MINIMUM BEND RADIUS=5”

12”

4”

IMPORTANT: The air duct pipe cannot run horizontally without a vertical rise. IMPORTANT: The 1/2" clearance around the air duct pipes must be maintained.Use #KZK-410 UL181 Class 0 Air Duct piping to connect the plenum(s) to the unit.Hussong Mfg. requires pipes to be listed as UL181 Class 0 Air Duct to connect the plenum(s) to the unit.

WHEN INSTALLING AIR DUCT PIPE MAINTAIN A MINIMUM 4" VERTICAL RISE FOR EVERY 12" HORIZONTAL RUN

Page 7: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

Komfort Zone Kit Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 7

D. Dimensions

3”

4”

17⁄8”

12”

5”

811⁄16”

12” 12” 12”

48”

½”STANDOFF

¾”STANDOFF

1½”STANDOFF

½”STANDOFF

#KZK-050

13½”3”

65⁄8” 4” 5”

57⁄8”

12”

811⁄16”½”STANDOFF

½”STANDOFF

¾”STANDOFF

1½”STANDOFF

#KZK-158

Page 8: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

8 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit

E. Rough Frame Openings

4¼” 49”

#KZK-050 FRAMING DIMENSIONS

8¼” 14½”

#KZK-158 FRAMING DIMENSIONS

Page 9: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

Komfort Zone Kit Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 9

F. Framing and Clearances

6”

22”

(REFER TO ROUGH OPENING DIMENSIONS ON PREVIOUS PAGE)

4¼”

8¼”

2½” 1½”

½”

6”

2½”

½”

½”½”

1½”

#KZK-050

#KZK-158

Page 10: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

10 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit

G. Combustible Finish, Mantel, & Hearth Clearances

NOTE: It is not required to use the #KZK-050 discharge trim if desired to run finishing material up to the edge of the plenum discharge. Finishing material must not block the opening and must be run evenly along the plenum opening.

WARNING! RISK OF OVERHEATING AND FIRE! Ensure the KZK duct system is installed in accordance to this manual AND the convection baffle is removed when using these combustible clearances.

9¾”(248mm)

26½”(673mm)

16¾”(425mm)

NOTE: THESE MANTEL CLEARANCES APPLY ONLY WHEN THE KZK DUCT SYSTEMIS INSTALLED AND THE CONVECTION BAFFLE REMOVED.

Page 11: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

Komfort Zone Kit Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 11

Combustible wall �nishmay be installed over cement board

If surround is used, the combustiblewall �nish must maintain a 3/4” clearance

to the top �nishing edge

FIREPLACE ENCLOSURE FLOOR

FINISHING EDGE

SURROUND

¾”(19mm)

Page 12: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

12 Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces Komfort Zone Kit

H. InstallationThe Kozy Zone Kit requires that the convection baffle, located above the firebox inside the appliance metal cabinet, to be removed to allow the hot airflow to convect upwards into the air ducts installed on the fireplace.

1. Remove the convection baffle from the appliance. The baffle is secured by (2) screws right behind the upper edge of the fireplace opening. Recycle this panel if it is no longer needed.

2. Remove the four cover plates on top of the appliance (4 screws each).

3. Align the vent collars to the corresponding holes on top of the appliance. Secure with screws previously removed. Install the vent collars to the corresponding opening(s) on the plenum(s). Use supplied screws.

4. Frame a rough opening at the desired location. See previous pages of this manual for allowable plenum

FIREBOX

CONECTIVE AIRFLOW WITHTHE BAFFLE IN PLACE

CONVECTION BAFFLETO BE REMOVED

TAKE-OFF COLLAR

CONVECTION AIRFLOW WITH BAFFLE REMOVED

positions and rough frame opening sizes.

5. Install the plenum(s) into the rough frame opening maintaining minimum clearances to combustibles as listed (see previous pages). Fix the plenum to the framing using nails or screw through the top mounting bracket. NOTE: Mounting brackets are not intended to carry the weight of the plenum and pipes. Provide support to the underside of the plenum and ensure the plenum is level and its outlet is not distorted.

6. Use metal strapping (all-around, not supplied) as required to further secure the plenum to framing.

7. Attach the piping from all (4) plenum vent collars to all (4) fireplace vent collars. If you are mounting the plenum 10' or less above the fireplace, use (1) #KZK-410 kit or UL-181 Class 0 approved air duct. If you are mounting the plenum between 10' to 20' above the fireplace then you will need (2) #KZK-410 kits and #KZK-CPL or UL-181 Class 0 approved air duct.

8. An upward slope must be maintained in horizontal sections of pipes for proper convection. Support horizontal sections every 24 inches.

9. Paint the inside surfaces of the plenum using high-temperature flat black spray for installations where the inside of the plenum(s) may be visible.

10. Install the #KZK-050 discharge trim to the plenum after the wall finish is completed using (2) screws if using the #KZK-050 plenum. Finishing material must not block and should run evenly along plenum opening. The #KZK-050 discharge trim is optional depending on finishing material choice.

CONVECTION BAFFLE

CONVECTION BAFFLE

Page 13: KOMFORT ZONE KITKOMFORT ZONE KIT WARNING: DO NOT cover or place objects in front of the air outlet(s). AVOID locating outlet within 7 feet above floor level as discharge temperatures

Komfort Zone Kit Hussong Mfg. Co., Inc. • Kozy Heat Fireplaces 13

11. Install the 14" x 6" air grille provided with the kit using (2) screws if using the #KZK-158 plenum.

12. If desired, the air grille/discharge trim may be painted. Use high temperature paint (250°F).

13. Continue with fireplace installation.