ksd 2021 hvac replacement projects
TRANSCRIPT
KSD-0.1
LOCATION MAP
KSD 2021 HVAC Replacement Projects
Kirkwood High School (KHS), 801 West Essex Avenue
Nipher Middle School (NIP), 700 South Kirkwood Road
SHEET NO
Keysor Elementary School (KEY), 725 North Geyer Road
North Glendale Elementary School (NGL), 765 North Sappington Road
Tillman Elementary School (TIL), 230 Quan Avenue
KIRKWOOD HIGH SCHOOL
KEYSOR ELEMENTARY SCHOOL
TILLMAN ELEMENTARY SCHOOL
NORTH GLENDALE
ELEMENTARY SCHOOL
NIPHER MIDDLE SCHOOL
SHEET LIST
KSD-0.1
NIP-A0.1
NIP-A1.1
NIP-A1.2
NIP-A2.1
KEY-A0.1
KEY-A1.1
KSD-S0.1
KSD-S0.2
KSD-S0.3
KHS-S1.1
KHS-S2.1
NIP-S1.1
NIP-S1.2
NIP-S2.1
NGL-S1.1
NGL-S2.1
TIL-S1.1
TIL-S2.1
KSD-S3.1
KSD-ME1.1
KSD-ME1.2
KSD-ME1.3
KHS-ME1.1
KHS-ME1.2
KHS-ME2.1
KHS-ME2.2
NIP-ME1.1
NIP-ME1.2
NIP-ME1.3
NIP-ME1.4
NIP-ME1.5
NIP-ME2.1
NIP-ME2.2
NIP-ME2.3
NIP-ME2.4
NIP-ME2.5
KEY-ME1.1
KEY-ME1.2
KEY-ME2.1
NGL-ME1.1
NGL-ME2.1
TIL-ME1.1
TIL-ME2.1
KSD-ME5.1
KSD-ME6.1
KSD-ME6.2
KSD-ME6.3
COVER
GENERAL NOTES
NIPHER - DEMOLITION PLAN & SECTION
NIPHER - FLOOR & ROOF PLAN
NIPHER - ELEVATIONS & SECTIONS
GENERAL NOTES
KEYSOR DEMOLITION & FLOOR PLAN & DETAILS
GENERAL NOTES
GENERAL NOTES
SPECIAL INSPECTIONS TABLES
HIGH SCHOOL - PARTIAL ROOF FRAMING PLAN
HIGH SCHOOL - SECTIONS AND DETAILS
NIPHER - PARTIAL ROOF FRAMING PLAN
NIPHER - PARTIAL FOUNDATION PLAN
NIPHER - SECTIONS AND DETAILS
NORTH GLENDALE - PARTIAL FOUNDATION PLAN
NORTH GLENDALE - SECTION AND DETAILS
TILLMAN - PARTIAL FOUNDATION PLAN
TILLMAN - SECTIONS AND DETAILS
TYPICAL SECTIONS
MECHANICAL AND ELECTRICAL LEGENDS
MECH AND ELECTRICAL NOTES
MECH AND ELEC SEISMIC CODE BLOCKS
KIRKWOOD HIGH SCHOOL - RTU-9 DEMOLITION PLANS
KIRKWOOD HIGH SCHOOL - RTU-21 DEMO PLANS
RTU-9 NEW WORK PLANS
RTU-21 NEW WORK PLANS
NIPHER - AHU-2 & AHU-3 DEMOLITION PLANS
NIPHER - FIRST FLOOR DEMOLITION PLAN
NIPHER - AHU-4, AHU-5, & AHU-6 DEMOLITION PLANS
NIPHER - RTU-9 THRU RTU-15 DEMOLITION PLAN
NIPHER - RTU-W-1 THRU RTU-W-3 DEMOLITION PLANS
NIPHER - AHU-2 & AHU-3 NEW WORK PLANS
NIPHER - FIRST FLOOR NEW WORK PLAN
NIPHER - AHU-4, AHU-5, & AHU-6 NEW WORK PLAN
NIPHER - RTU-9 THRU RTU-15 NEW WORK PLAN
NIPHER - RTU-W-1 THRU RTU-W-3 NEW WORK PLAN
KEYSOR - RTU-3 DEMOLITION PLAN
KEYSOR GROUND FLOOR DEMOLITION PLAN
KEYSOR - RTU-3 NEW WORK PLAN
NORTH GLENDALE - AHU-1 DEMOLITION PLAN
NORTH GLENDALE - AHU-1 NEW WORK PLAN
TILLMAN - AHU-1 DEMOLITION PLAN
TILLMAN - AHU-1 NEW WORK PLAN
MECHANICAL AND ELECTRICAL DETAILS
MECHANICAL AND ELECTRICAL SCHEDULES
MECHANICAL AND ELECTRICAL SCHEDULES
MECHANICAL AND ELECTRICAL SCHEDULES
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
ADDENDUM #2 - 3-3-2021
1
S1.2
PARTIAL FOUNDATION PLAN
SCALE: 1/8"=1'-0"
NORTH
ROOF FRAMING PLAN NOTES:
1. SEE KSD-S0.1 TO KSD-S0.3 FOR GENERAL NOTES AND KSD-S3.1 FOR TYPICAL DETAILS.
2. SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
THE DIMENSIONS AND ELEVATIONS ARE NOT AS-BUILT DIMENSIONS
BUT WERE OBTAINED FROM THE ORIGINAL STRUCTURAL DRAWINGS
AND OTHER DRAWINGS AND DOCUMENTS. IT IS THE RESPONSIBILITY
OF CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, ELEVATIONS,
AND MEMBER SIZES AS REQUIRED PRIOR TO BEGINNING
CONSTRUCTION, FABRICATION, ETC.
KEY PLAN
1
S1.2
NEW 6" THICK CONC
SLAB ON GRADE
PAD EXTENSION
EXIST 2'-6"Ø PIER
EXIST PRECAST CONC
SOUND WALL COLUMN
EXIST FENCE
TO BE RELOCATED
EXIST 6" CONC
MECHANICAL PAD
EXIST BUILDING
EXTERIOR WALL
EXIST PRECAST CONC
SOUND WALL PANEL
EXIST CONC CURB
10'-7"±
VIF
6'-9 1/2"±
VIF
1'-1"±
VIF
60
'-0
"±
VIF
1
S2.1
2
S1.2
2
S1.2
PARTIAL FOUNDATION PLAN
SCALE: 1/8"=1'-0"
NORTH
ROOF FRAMING PLAN NOTES:
1. SEE KSD-S0.1 TO KSD-S0.3 FOR GENERAL NOTES AND KSD-S3.1 FOR TYPICAL DETAILS.
2. SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
EXIST CONCRETE
HOUSEKEEPING PAD
NEW MECHANICAL UNIT
2
S2.1
NEW CONCRETE
HOUSEKEEPING PAD
EXTENTION
NEW MECHANICAL UNIT
NEW MECHANICAL UNIT
2'-5"
7'-0
"
NIPHER SCHOOL NIPHER SCHOOL
11'-0"
1'-8
"
NEW MECHANICAL UNIT
NEW CONCRETE
HOUSEKEEPING PAD
EXTENTION
EXIST CONCRETE
HOUSEKEEPING PAD
2
S2.1
1
1
NIP
HE
R - P
AR
TIA
L F
OU
ND
AT
IO
N P
LA
N
NIP-S1.2
Kir
kwo
od
Sch
oo
l Dis
tric
t
02/12/2021
Professional Design Firm
#184-003476
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2
021
HV
AC
RE
PL
AC
EM
EN
T P
RO
JEC
T
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
PC
PO
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9KI
RKW
OO
D, M
O 6
3122
Lar
son
En
gin
eeri
ng
, In
c.1850 C
raigshire R
oad, S
uite 300
St. Louis, M
O 63146-4013
314.731.4710 F
ax: 314.628.9620
ww
w.larsonengr.com
©
2021 LE
I
Project N
um
ber: 51200922.000
Missouri C
OA
N
um
ber: 2007006032
AD
DE
ND
UM
#
23
-3
-2
1
KEY PLAN
THE DIMENSIONS AND ELEVATIONS ARE NOT AS-BUILT DIMENSIONS
BUT WERE OBTAINED FROM THE ORIGINAL STRUCTURAL DRAWINGS
AND OTHER DRAWINGS AND DOCUMENTS. IT IS THE RESPONSIBILITY
OF CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, ELEVATIONS,
AND MEMBER SIZES AS REQUIRED PRIOR TO BEGINNING
CONSTRUCTION, FABRICATION, ETC.
1
S1.1
1
S2.1
NEW CONCRETE
HOUSEKEEPING PAD
FOR MECHANICAL UNIT
10'-3"
5'-6
"1
2'-0
"
1'-0"
NEW CONCRETE
HOUSEKEEPING PAD
EXTENTION
NEW MECHANICAL UNIT
1
S1.1
PARTIAL FOUNDATION PLAN
SCALE: 1/8"=1'-0"
NORTH
ROOF FRAMING PLAN NOTES:
1. SEE KSD-S0.1 TO KSD-S0.3 FOR GENERAL NOTES AND KSD-S3.1 FOR TYPICAL DETAILS.
2. SEE MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
3. MECHANICAL CONTRACTOR TO VERIFY NEW RTU UNIT DIMENSIONS AND LOADS.
NEW MECHANICAL UNIT
NORTH GLENDALE SCHOOL11'-0"
8'-0
"1
0'-8
"
11'-8 1/8"
1
S2.1
1
NO
RT
H G
LE
ND
AL
E - P
AR
TIA
L F
OU
ND
AT
IO
N P
LA
N
NGL-S1.1
Kir
kwo
od
Sch
oo
l Dis
tric
t
02/12/2021
Professional Design Firm
#184-003476
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2
021
HV
AC
RE
PL
AC
EM
EN
T P
RO
JEC
T
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
PC
PO
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9KI
RKW
OO
D, M
O 6
3122
Lar
son
En
gin
eeri
ng
, In
c.1850 C
raigshire R
oad, S
uite 300
St. Louis, M
O 63146-4013
314.731.4710 F
ax: 314.628.9620
ww
w.larsonengr.com
©
2021 LE
I
Project N
um
ber: 51200922.000
Missouri C
OA
N
um
ber: 2007006032
AD
DE
ND
UM
#
23
-3
-2
1
1. SEE SHEET KSD ME1.2 FOR GENERAL NOTES THAT MAY APPLY
TO THIS SHEET.
E1 PROVIDE (1) NEW 3P-200A FUSED SWITCH WITH 200A FUSES IN
EXISTING SPACE FOR NEW CH-2.
PROVIDE NEW 1P-20A CIRCUIT BREAKER IN SPACE 17 IN
EXISTING PANEL 1SD TO FEED RECEPTACLE LOCATED IN AHU-6.
BREAKER TO MATCH EXISTING IN TYPE AND RATING.
M1 4" CHS&R DOWN ON WALL THRU FLOOR. KEEP PIPING TIGHT TO
WALL.
ROUTE 4" CHS&R PIPING TIGHT TO STRUCTURE ABOVE. ROUTE
THRU WALL INTO GYMNASIUM AND TURN UP TO ROUTE HIGH ON
WALL. SEE NIP-ME2.3 FOR CONTINUATION.
ROUTE 2-1/2" CHS&R PIPING OVERHEAD INTO CLOSET. TURN UP
THROUGH ROOF INTO AHU-6 PIPE CHASE. COORDINATE WITH
ROOF STRUCTURE.
2" HWS&R PIPING UP ON WALL. SEE NIP-ME2.3 FOR
CONNECTION TO PIPE ABOVE.
ROUTE 2" HWS&R PIPING OVERHEAD INTO CLOSET. TURN UP
THROUGH ROOF INTO AHU-6 PIPE CHASE. COORDINATE WITH
ROOF STRUCTURE.
M2
M3
M4
E2
M5
DP-3
E1
DP-2
CHS
CHR
M1
M2
M3
CHS&R-UPHWS&R-UP
1SD
E2
4"
2-1/2"
M4
2"
M5
1
2
NIP-ME2.2
NIP
HE
R - F
IR
ST
F
LO
OR
N
EW
W
OR
K P
LA
N
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
KEY PLAN
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
1
PARTIAL FIRST FLOOR PLAN - ELECTRICAL NEW WORK
1/8" = 1'-0"
N
AD
DE
ND
UM
#
12
-2
4-2
11
AD
DE
ND
UM
#
23
-3
-2
12
1. SEE SHEET KSD ME1.2 FOR GENERAL NOTES THAT MAY APPLY
TO THIS SHEET.
2. COORDINATE EXACT AHU-4 & AHU-5 LOCATIONS WITH STEEL
SUPPORTS. REFER TO STRUCTURAL DRAWINGS. MECHANICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
UNIT DIMENSIONS WITH SUPPORT FRAMING. UNIT LOCATIONS
SHALL ALLOW FOR FULL MANUFACTURER RECOMMENDED
CLEARANCES.
M1
ROUTE UNIT CONDENSATE DRAIN PIPING TO EXISTING DRAIN AT
GRATING. TERMINATE WITH 1" AIR GAP.
ROUTE 2" HWS&R PIPING UP THRU STEEL AND GRATING TO AIR
HANDLING UNIT HOT WATER COIL CONNECTION. FIELD
COORDINATE EXACT LOCATION.
TURN CHS&R PIPING DOWN TO AIR HANDLING UNIT.
CONNECT NEW SUPPLY DUCT TO EXISTING. FIELD COORDINATE
EXACT SIZE AND LOCATION AND TRANSITION AS REQUIRED.
CONNECT NEW RETURN AIR DUCT TO EXISTING. FIELD
COORDINATE EXACT SIZE AND LOCATION AND TRANSITION AS
REQUIRED.
CONSTRUCT NEW 24" DEEP PLENUM AT EXISTING LOUVER.
MATCH LOUVER SIZE. ROUTE OUTSIDE AIR DUCT FROM
EXISTING LOUVER AND CONNECT TO UNIT AS SHOWN.
ROUTE RELIEF AIR DUCT UP AND CONNECT TO EXISTING. FIELD
COORDINATE EXACT SIZE AND LOCATION. TRANSITION AS
REQUIRED. INSTALL NEW RELIEF FANS RF-4 AND RF-5 ON ROOF.
CONNECT NEW 3" HWS&R PIPING TO EXISTING PIPING BELOW
STEEL AND ROUTE TO UNIT CONNECTIONS.
6" CHS&R DOWN ON WALL. SEE NIP-ME2.2 FOR CONTINUATION.
CONNECT NEW 2" HWS&R PIPING TO EXISTING. VERIFY EXACT
SIZE AND LOCATION IN FIELD AND TRANSITION AS REQUIRED.
ROUTE NEW PIPING OVERHEAD IN STRUCTURE AS SHOWN.
TURN 2" HWS&R PIPING DOWN ON WALL. SEE NIP-ME2.2 FOR
CONTINUATION. COORDINATE EXACT ROUTE WITH CHILLED
WATER PIPING ON WALL. CONCEAL PIPING ON WALL WITHIN A
STEEL ENCLOSURE EQUAL TO SOFFI-STEEL. PAINT TO MATCH
WALL COLOR.
ROUTE CHS&R PIPING RACKED TIGHT TO WALL. CONCEAL
PIPING ON WALL WITHIN A STEEL ENCLOSURE EQUAL TO
SOFFI-STEEL. PAINT TO MATCH WALL COLOR.
ROUTE 30"x30" RA DUCT ON ROOF TO EXISTING EXTERIOR WALL
PENETRATION AS SHOWN. ROUTE THROUGH OPENING AND
CONNECT TO 40"x44"x18" DEEP PLENUM. PROVIDE 36"x40"
HEAVY DUTY STEEL GRILLE AT PLENUM EQUAL TO TITUS 30RL.
2-1/2" CHS&R UP FROM BELOW. COORDINATE EXACT LOCATION
WITH AIR HANDLER PIPE CHASE.
2" HWS&R UP FROM BELOW. COORDINATE EXACT LOCATION
WITH AIR HANDLER PIPE CHASE.
TURN RETURN AIR DUCT DOWN AND CONNECT TO EXISTING
DUCT AT GRATING PENETRATION. VERIFY EXACT SIZE AND
LOCATION IN FIELD AND TRANSITION AS REQUIRED.
INSTALL UNIT ON ROOF CURB. TOP OF CURB SHALL BE 14"
ABOVE FINISH ROOF AND SLOPED TO MATCH ROOF. ATTACH
CURB TO CONCRETE ROOF SLAB AND PROVIDE FLASHING.
ROUTE 30"x30" SA DUCT ON ROOF TO EXISTING LOUVER
OPENING. ROUTE DUCT THROUGH OPENING AND TURN UP ON
WALL. TRANSITION TO 32"Ø AND ROUTE UP TO STRUCTURE.
TURN OVERHEAD TO CONNECT TO EXISTING SA DUCT
OVERHEAD, TRANSITION AS REQUIRED TO MATCH SIZE.
M2
M3
E1
CONNECT EXISTING 600A FEEDER TO NEW PANEL DP-4.
CONNECT EXISTING 100A FEEDER TO NEW PANEL DP-5.
PROVIDE NEW DUCT DETECTOR IN AHU RETURN DUCT.
CONNECT TO EXISTING FIRE ALARM WIRING AND CONTROL
MODULES.
ROUTE NEW FEEDERS FOR AHU-4 AND AHU-5 UNDER RAISED
FLOOR.
PROVIDE JUNCTION BOX AND EXTEND THE REMAINING PORTION
OF THE EXISTING FEEDER THROUGH THE CURB OF NEW AHU-6
AND MAKE FINAL CONNECTIONS. WIRE AND CONDUIT SIZE TO
MATCH EXISTING.
ROUTE NEW FEEDERS FOR RF-4 AND RF-5 DOWN THROUGH
ROOF AND ALONG SECOND FLOOR CEILING.
PROVIDE CONNECTION TO RECEPTACLE SUPPLIED WITH AHU.
ROUTE 2#10, 1#10G,
3
4
"C FROM RECEPTACLE TO PANEL 1SD
LOCATED ON FIRST FLOOR.
E2
M4
E3
M5
M6
M7
M8
M9
M10
M11
M12
M13
M14
E4
E5
M15
M16
M17
M18
E6
E7
2
2
2
5
AHU
4
AHU
40
x2
4 O
A
40x26 OA
40x24 RA
54x20 SA
50x20
M1
M2
M4
M7
M16
M6
M4
6
AHU
CHS&R
CH
S
CH
R
CHS
CHR
M3
M9
M10
2"
M11
M12
M12
EX. 26x16 EA
DUCT TO REMAIN
EXIST. UH
ETR
EX. HWS&R DN
THRU FLOOR
(PIPE IS BELOW GRATING)
EX. EA DN
THRU FLOOR
EXIST. IFS
PANELS (4)
EXIST.
60x20 SA
EXIST.
60x20 RA
M2
4"
4"
3"
M3
M1
M5
30x30 RA UP
44x20 RA
40x20 RA
EXIST. SA DUCT
TO REMAIN
EXIST. HWS&R
EX
IS
T. S
A
HWS
HWR
E2
DP-5
E3E5
E3E4
E3E4
ROUTE CHS&R PIPING
UP IN STEEL JOISTS
2-1/2"
M8
4"
CHS&R
HWS
HWR
2"
HW
S
HW
R
CHS&R PIPING RACKED
HIGH ON GYMNASIUM WALL
M14
M15
30x30 SA
30x30 SA
30x30 RA
32
"Ø
S
A
M17
M18
M18
M13
5
RF
4
RF
ON ROOF
ON ROOF
E6
E6
E7
1
1
AHU PIPE CHASE
2
RA CONNECTION
AT SIDE OF UNIT
REMOVE EXISTING LOUVER AND FILL
OPENING WITH METAL STUD
CONSTRUCTION. PROVIDE STEEL PANEL
TO SURROUND DUCT PENETRATION AT
EXTERIOR AND INTERIOR AND SEAL
WEATHER TIGHT. PROVIDE INSULATION
IN WALL CAVITY. PAINT PANEL TO MATCH
WALL COLORS.
2
EXISTING
FLOOR DRAIN
EXIST.
FLOOR DRAIN
2
E1
DP-4
NIP-ME2.3
NIP
HE
R - A
HU
-4, A
HU
-5, &
A
HU
-6 N
EW
W
OR
K P
LA
NS
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
KEY PLAN
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
PARTIAL SECOND FLOOR PLAN - MECHANICAL AND ELECTRICAL NEW WORK
1/4" = 1'-0"
1
PARTIAL SECOND FLOOR PLAN - MECHANICAL AND ELECTRICAL NEW WORK
1/4" = 1'-0"
2
NN
AD
DE
ND
UM
#
12
-2
4-2
11
AD
DE
ND
UM
#
23
-3
-2
12
1. SEE SHEET KSD ME1.2 FOR GENERAL NOTES THAT MAY APPLY
TO THIS SHEET.
2. REFRIGERANT PIPING ON GRADE SHALL SUPPORTED WITH
UNISTRUT SECURELY ANCHORED TO CONCRETE SLAB.
M1PROVIDE NEW CONCRETE HOUSEKEEPING PAD BELOW CU-1.
EXTEND THE CONCRETE PAD MIN. 6" AROUND EQUIPMENT
DIMENSIONS. SEE STRUCTURAL DRAWINGS FOR MORE
INFORMATION. EXACT DIMENSIONS SHALL BE VERIFIED
WITH INSTALLED UNIT. CU-2 SHALL BE INSTALLED ON
EXISTING HOUSEKEEPING PAD.
PROVIDE CONCRETE HOUSEKEEPING PAD BELOW AIR
HANDLING UNIT. EXTEND THE CONCRETE PAD MIN. 6"
AROUND EQUIPMENT DIMENSIONS. SEE STRUCTURAL
DRAWINGS FOR MORE INFORMATION. EXACT DIMENSIONS
SHALL BE VERIFIED WITH INSTALLED UNIT.
ROUTE REFRIGERANT PIPING FROM CONDENSING UNIT TO
AIR HANDLING UNIT. SIZE THE REFRIGERANT LINES PER
MANUFACTURER REQUIREMENTS. THE LIQUID AND SUCTION
LINE SHALL BE INSULATED PER SPECIFICATIONS.
CONNECT NEW 2-1/2" HWS&R PIPING TO EXISTING AND
ROUTE TO AHU HOT WATER COIL CONNECTION.
REFRIGERANT PIPING DOWN TO AIR HANDLING UNIT
COOLING COIL.
70"x24" SA DUCT DOWN TO UNIT. TRANSITION DUCT AS
REQUIRED FOR UNIT CONNECTION. TRANSITION 70"x24" SA
DUCT TO PANTS LEG FITTING FOR CONNECTION TO (2)
EXISTING 24"x24" SA DUCT. VERIFY SIZES IN FIELD.
CONSTRUCT 24" DEEP OUTSIDE AIR PLENUM AT EXISTING
OA LOUVER. PLENUM SHALL EXTEND FROM FLOOR TO
MINIMUM 18" ABOVE TOP OF LOUVER. PROVIDE DRAIN AT
BOTTOM OF OUTSIDE AIR PLENUM AND ROUTE PIPE TO
FLOOR DRAIN WITH 1" AIR GAP..
ROUTE FULL SIZE CONDENSATE TO FLOOR DRAIN.
TERMINATE WITH 1" AIR GAP.
ROUTE REFRIGERANT PIPING THROUGH EXISTING EXTERIOR
WALL PENETRATIONS WHERE POSSIBLE. PATCH
ABANDONED PENETRATIONS.
RA INLET ON TOP OF UNIT SHALL BE LEFT OPEN.
INSTALL MANUAL VOLUME DAMPERS IN DUCT AS SHOWN.
BALANCE TO PRE-MEASURED CFM AS PART OF TEST AND
BALANCE.
M2
M3
E1UTILIZE EXISTING 3P-100A SPARE FUSED DISCONNECT SWITCH
IN EXISTING PANEL DP-G TO FEED NEW AHU-1. INSTALL 80A
FUSES.
ROUTE 3#3, 1#8G, 1
1
4
"C FROM NEW AHU TO EXISTING PANEL
DP-G THROUGH CEILING SPACE OF GROUND FLOOR.
RECONNECT EXISTING FEEDER TO NEW CONDENSING UNIT.
M4
E2
M5
M6
M7
M8
M9
M10
E3
M11
2
2
EXIST. 72x30
OA LOUVER
1
CU
1
AHU
RS
RL
RS
RL
M1
M2
M3
M5
M11
M7
M10
EXISTING
FLOOR DRAIN
M9
MDP
EX.
CU
EX.
CU
EX.
UNIT
T
EX. 30x30
EXIST. 28x40 SA
RS
RL
RS
RL
EX. ELEC
PANEL
EX. IFS
PANEL
MCC-NG
E2
E3
E1
M3
TO BOILERFROM
PUMP
HWS
HWR
M4
M3
70x24 OA
M8
DP-G
2
CU
M1E3
M3
2
NGL-ME2.1
NO
RT
H G
LE
ND
ALE
- A
HU
-1 N
EW
W
OR
K P
LA
N
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
KEY PLAN
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
1
PARTIAL GROUND FLOOR PLAN - MECHANICAL AND ELECTRICAL NEW WORK
1/8" = 1'-0"
N
AD
DE
ND
UM
#
12
-2
4-2
11
AD
DE
ND
UM
#
23
-3
-2
12
1. SEE SHEET KSD-ME1.2 FOR GENERAL NOTES THAT MAY APPLY
TO THIS SHEET.
M1INSTALL UNIT CU-1 ON EXISTING CONCRETE PAD. CENTER
UNIT BASE ON EXISTING PAD.
ROUTE REFRIGERANT PIPING FROM CONDENSING UNIT TO AIR
HANDLING UNIT. SIZE THE REFRIGERANT LINES PER
MANUFACTURER REQUIREMENTS. THE LIQUID AND SUCTION
LINES SHALL BE INSULATED PER SPECIFICATION.
ROUTE REFRIGERANT PIPING ON GRADE. ROUTE THROUGH
EXTERIOR WALL WITH SLEEVES. EXISTING ABANDONED
CONDUITS SHALL BE CAPPED AND SEALED WEATHER TIGHT
ALONG WITH ANY ABANDONED EXTERIOR WALL
PENETRATIONS.
PROVIDE CONCRETE HOUSEKEEPING PAD BELOW AIR
HANDLING UNIT. EXTEND THE CONCRETE PAD MIN. 6"
AROUND EQUIPMENT DIMENSIONS. SEE STRUCTURAL
DRAWINGS FOR MORE INFORMATION.
CONNECT NEW 36"x30" SA DUCT TO EXISTING. VERIFY EXACT
SIZE IN FIELD AND TRANSITION AS REQUIRED. TURN DOWN TO
UNIT AND TRANSITION AS REQUIRED TO UNIT SA CONNECTION.
CONNECT NEW 36"x30" OA DUCT TO EXISTING. VERIFY EXACT
SIZE IN FIELD AND TRANSITION AS REQUIRED. TURN DUCT
DOWN TO COORDINATE WITH NEW RA DUCT AS SHOWN AND
TRANSITION AS REQUIRED TO UNIT OA CONNECTION.
COORDINATE DUCT DROP WITH EXISTING SINK ON WALL.
CONNECT NEW 36"x30" RA DUCT TO EXISTING. VERIFY EXACT
SIZE IN FIELD AND TRANSITION AS REQUIRED.
60"x20" RA DOWN TO UNIT. TRANSITION AS REQUIRED TO UNIT
RA CONNECTION.
CONNECT NEW 2-1/2" HWS&R TO EXISTING AND ROUTE DN TO
AIR HANDLING UNIT HOT WATER COIL CONNECTION.
ROUTE FULL SIZE CONDENSATE DRAIN TO EXISTING FLOOR
DRAIN AND TERMINATE WITH 1" AIR GAP.
PROVIDE CONTROL DAMPER CONNECTED TO RELIEF FAN
RF-1A & RF-1B OPERATION.
REMOVE INFILL AT UPPER WINDOW CASING. INSTALL FAN AND
WALL COLLAR TO DISCHARGE THROUGH EXISTING OPENING.
SUPPORT FAN PER MANUFACTURER DIRECTION.
M2
M3
E1 RECONNECT EXISTING FEEDER TO NEW AHU-1.
PROVIDE NEW DUCT DETECTOR IN AHU-1 RETURN DUCT.
CONNECT TO EXISTING FIRE ALARM WIRING AND CONTROL
MODULES.
RECONNECT EXISTING FEEDER TO NEW CU-1.
CONNECT NEW RETURN FANS TO EXISTING 30A STARTER WITH
NEW 15A FUSES IN PANEL MCC-T. ROUTE 3#12, 1#12G,
3
4
"C
FROM MCC-T TO RETURN FANS.
E2
M4
M5
M6
M7
M8
M9
M10
E3
E4
M11
M12
1
1
2
1
AHU
1
CU
R
L
R
S
M1
M2
M3
M5
M6
M4
E
X
I
S
T
.
3
6
x
3
0
O
A
E
X
I
S
T
.
3
6
x
3
0
O
A
EXIST. 14'-7"x2'-6"
LOUVER
E
X
I
S
T
.
4
"
H
W
S
E
X
I
S
T
.
4
"
H
W
R
E
X
.
4
"
H
W
R
E
X
.
4
"
H
W
S
E
X
I
S
T
.
2
-
1
/
2
"
H
W
S
E
X
I
S
T
.
2
-
1
/
2
"
H
W
R
E3
E1 E2
R
L
R
S
EXIST.
HSKP PAD
REF. PIPING-DN
BELOW GRADE
REF. PIPING-UP
ON WALL
M2
H
W
S
H
W
R
E
X
I
S
T
.
3
2
x
2
0
R
A
E
X
.
2
8
x
1
2
S
A
E
X
.
3
6
x
3
0
S
A
EXIST. SA & RA UP
THRU FLOOR
E
X
I
S
T
.
3
6
x
2
6
R
A
3
6
x
3
0
R
A
M6
M7
M7
M8
EXIST. FD
M9
TO BUILDING
TO EX.
BOILERS
FROM EX.
HW PUMPS
M10
1A
RF
1B
RF
E4
E4
MCC-T
M
M11
M12
M12
1
1
2
TIL-ME2.1
TILM
AN
- A
HU
-1 N
EW
W
OR
K P
LA
N
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
KEY PLAN
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
1
PARTIAL GROUND FLOOR PLAN - MECHANICAL AND ELECTRICAL NEW WORK
1/4" = 1'-0"
N
AD
DE
ND
UM
#
12
-2
4-2
11
AD
DE
ND
UM
#
23
-3
-2
12
AHU CHILLED WATER COIL DETAIL
NO SCALE
3/4" H.E.V.
GATE VALVE (TYP.)
BALANCING VALVE (TYP.)
THERMOMETER
AIR VENT AT
HIGH POINT
(TYP.)
AIR VENT
STRAINER
3-WAY CONTROL VALVE (AT HIGH SCHOOL)
SUPPLY
RETURN
COIL DRAIN
3/4" H.E.V.
UNION
AHU
COOLING
COIL
AHU HOT WATER COIL DETAIL
NO SCALE
3/4" H.E.V.
BALL VALVE (TYP.)
THERMOMETER
(TYP.)
AIR VENT
STRAINER
FLOW CONTROL INDUSTRIES DELTA P
SUPPLY
RETURN
COIL DRAIN
3/4" H.E.V.
AHU
HEATING
COIL
PRESSURE AND TEMPERATURE TEST PORT
VALVE WITH INTEGRAL PRESSURE PORTS
5
6
PRESSURE AND TEMPERATURE TEST PORT
REFER TO MANUFACTURER FOR
REFRIGERANT PIPE SIZING.
GRADE
THERMAL EXPANSION
SOLENOID VALVE
SIGHT GLASS
FILTER/DRIER
SERVICE VALVE (TYP. 2)
MECHANICAL ROOM
VALVE (TXV)
PIPE SUPPORTS ON GRADE
SHALL BE UNISTRUT
INSULATE PIPING AS
INDICATED IN SPECIFICATIONS.
ROOF
PIPE HOLD DOWN STRAP
GAS COCK
SEAL AROUND
PIPING TO
CABINET
ROOFTOP
HVAC
UNIT
FULL SIZE
DRIP LEG
6" M
IN
.
AIR VENT
VAPOR BARRIER SEALED
TO HYDRANT SUPPORT
3/4" NPT INLET
NO DRAIN
REQUIRED
UNDER DECK
FLANGE
20" MIN.
ROOF HYDRANT (RH-1)
BOOT COVERS WELL SEAL THAT
TIGHTENS BETWEEN HYDRANT
SUPPORT AND CASING
HYDRANT SUPPORT
ROOF STRUCTURE
ROOF DECK
MOUNTING BOLTS (4)
CLAMP SCREW (3)
RESERVOIR
61"
STAINLESS STEEL
CLAMP
PRE-MOLDED
SILICONE BOOT
LAP SEALANT
DUAL CHECK
BACKFLOW
PREVENTER
161-300
5.1-50
3"
2"
2
1"2.1-5
51-160
301-425
3/4"
1-1/2"
4"
CONDENSATE DRAIN TRAP
NO SCALE
DRAIN LINE SHALL BE
AT LEAST OF THE SAME
SIZE AS THE DRAIN.
PAN CONNECTION
CLEAN OUT
SEE NOTE 5
DRAIN PAN
PITCH
1" M
IN
AIR
G
AP
SE
E N
OT
E 4
OPEN DRAIN
NOTES:
1. MANUALLY PRIME TRAP BEFORE START UP.
2. SUPPORT DRAIN LINES TO PREVENT SAG.
3. ALLOW SUFFICIENT SPACE BELOW PAN FOR TRAP AND PITCH TO DRAIN.
4. 6" FOR DRAW THRU & 4" FOR BLOW THRU UNITS
5. 1" TO 4" FOR DRAW THRU UNITS ONLY.
CONNECTED
COOLING
LOAD(T)
MIN*
PIPE
SIZE
TYPICAL ROOF HYDRANT DETAIL
NO SCALE
* NOT SMALLER THAN OUTLET SIZE
1
2
ROOF MOUNTED GAS PIPING DETAIL
NO SCALE
3
REFRIGERANT PIPING DETAIL
NO SCALE
7
AHU
4"x4" PRESSURE TREATED
WOOD BLOCK MIN. 12" LONG
OR ERICO PP50-4 PIPE PIER
FOR WOOD BLOCK ONLY,
PLACE RUBBER WALK PAD
MATERIAL UNDER ENTIRE
LENGTH OF EACH BLOCK
ANCHORED TO SLAB
(BY GEN. CONTR.)
EXH. DUCT - SEE
CURB CAP
24" HIGH MINIMUM
ABOVE ROOF
NON-FERROUS
SCREWS OR BOLTS
MUST BE LEVEL
FRAMING BY G.C. (TYP.)
CHANNEL SUPPORT
EXIST. ROOF
SEE PLANS
ROOF OPENING-
PLAN FOR SIZE
(BY V.C.)
ROOFING
CURB WITH
WOOD NAILER
PREFAB. INSUL.
CONDUIT
EXHAUST FAN
SECURE TO WALL &
CAULK BY M.C.
SHUTTER
GRAVITY
HOOD
WEATHER
WALL COLLAR
STEEL GRILLE
FAN MOTOR
ADJUSTABLE WALL
FASTENER
WALL MOUNTED EXHAUST FAN DETAIL
NO SCALE
BASERAIL
NEOPRENE
GROMMET
BOILER ANCHORING DETAIL
NO SCALE
AS
R
EQ
UIR
ED
ROD SIZED FOR
LOAD AND SPACING
CLEVIS PIPE HANGER
PIPE INSULATION
AS SPECIFIED
PIPE SIZES 1/2"-10"
PROTECTIVE INSULATION
SHIELD
NOTES:
1. PIPE HANGERS SHALL BE OVERSIZED AS REQUIRED TO ACCOMMODATE.
THICKNESS OF INSULATION SPECIFIED. HANGER SHALL NOT COME INTO
CONTACT WITH THE INSULATION DIRECTLY, EITHER AT THE VERTICAL
YOKE OR AT THE POINT OF SUPPORT. FOR REQUIREMENTS ON
INSULATION SHIELD USED WITH PIPE HANGERS, SEE SPECIFICATIONS.
1'-0"
ROOF MOUNTED EXHAUST FAN DOWNBLAST
NO SCALE
"T" BRANCH
(SUPPLY)
45
90° ELBOW
"T" BRANCH
(SUPPLY)
"T" BRANCH
(SUPPLY)
(RETURN)
"T" BRANCH
45°
DUCTWORK FITTINGS DETAIL
NO SCALE
SINGLE THICKNESS TURNING
VANES IN 90° ELBOW
1
1
1
1
RIGID CONNECTION2
2
SIDEWALL
GRILLE
(RETURN)
SIDEWALL
GRILLE
(SUPPLY)
3
45°
VOLUME DAMPER3
45°
3
KEYED NOTES:
3
2
MITERED ELBOW
4
SINGLE THICKNESS TURNING
VANES IN MITERED ELBOWS
30° AND GREATER
4
9
10
8
4
PIPE HANGER DETAIL
NO SCALE
12
UNISTRUT (TYP)
1" THICK FIBERGLASS
INSULATION (TYP)
SLAB
3/8"Ø THREADED ROD (TYP)
(OR EQUAL) ANCHORS INTO SLAB MIN. 4".
3/8"Ø HILTI-HKB-SS EXPANSION ANCHOR
1-1/2" UNISTRUT
DOUBLE-NUT (TYP)
REFRIGERANT PIPING
(NOTE: INSULATE HOT GAS PIPING ONLY)
3/8"Ø COUPLER (TYP)
FENDER WASHER
W/NUT
INSULATED MULT-PIPE HANGER
NO SCALE
13
SHUTOFF VALVE -
SEE SPECIFICATIONS
FOR TYPE
FLEXIBLE CONNECTOR -
(TYP.)
SUCTION DIFFUSER
ADJUSTABLE SUPPORT
DRIP PAN - PIPED TO FLOOR DRAIN
4" CONCRETE PAD
USE EXISTING PAD
BASE MOUNTED PUMP
CONCENTRIC REDUCER (AS REQUIRED)
CHECK VALVE
END SUCTION PUMP PIPING DETAIL
NO SCALE
MULTI-PORT
(0-100 PSIG)
PRESSURE GAUGE
WHERE PRESENT
14
PIPE PENETRATION THRU WALL
NO SCALE
CONCRETE OR
CMU WALL
CONCRETE FILL
IN CMU WALL
FIRE SAFING
PIPE SLEEVE
SEAL WATER TIGHT
ALL AROUND WITH
WATERPROOF NON
SHRINKING MASTIC
11
1
NOTES:
NIPHER MIDDLE SCHOOL SHALL HAVE 2-WAY
PRESSURE INDEPENDENT CONTROL VALVES EQUAL
TO FLOW INDUSTRIES DELTA P VALVE WITH INTEGRAL
PRESSURE PORTS. OMIT BYPASS PIPING AND BYPASS
BALANCING VALVE.
1
1
KSD-ME5.1
ME
CH
AN
IC
AL A
ND
E
LE
CT
RIC
AL D
ET
AILS
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
AD
DE
ND
UM
#
23
-3
-2
11
6"
STRAINER (TYP.)
THERMOMETER
(TYP. )
CHECK VALVE
(TYP. )
BUTTERFLY
VALVE (TYP.)
6"
CP
2
GATE VALVES
(TYP.)
6"
6"
CP
1
POT FEEDER
CHEMICAL
3/4"
CHR
CHSCHS
GRADE
GROUND LEVEL
FIRST FLOOR
6"
6"
CHS
CHR
4"
PAD
FLEXIBLE CONNECTION
PIPE SLEEVES THRU WALL (TYP)
CHS
CHS
6" CONCRETE
1
ACC
CHR
ANGLE PIPE SUPPORTS
ATTACH TO CONCR. SLAB
AND PIPING (TYP.)
PAD
CHS
FLEXIBLE CONNECTION
ACC
6" CONCRETE
2
6"
6"
CHS
AIR CHARGING VALVE
(PRESSURIZE DRY TANK EQUAL
TO FILL VALVE PRESSURE)
LOW CAPACITY AIR VENT
DRAIN VALVE W/
HOSE CONNECTION
PRESSURE GAUGE
W/ NEEDLE VALVE
XT
1
AIR AND DIRT
SEPARATOR
REDUCER
(WHERE REQ'D.)
PRESSURE REDUCING VALVE -
(SET AT 12 PSIG)
HIGH CAPACITY
AIR VENTREDUCED PRESSURE BACKFLOW
PREVENTER WITH OPEN AIR GAP
BALL VALVE
TO DRAIN
BLOWDOWN PIPING
TO FLOOR DRAIN
3/4" COLD WATER MAKE-UP.
CONNECT TO NEAREST CW SOURCE.
AS
1
M
FLOW MEASURING
DEVICE
CHR
6"
1"
1"
NIPHER - CHILLED WATER PIPING DIAGRAM
NO SCALE
1
CHR
4"
6"
4" BYPASS
(36" PIPE LENGTH)
FLASHING WITH HEMMED
CANT STRIP
WOOD NAILER
ALUMINUM COUNTER
WEATHER SEAL
DRIP EDGE
PACKAGED ROOFTOP UNIT
NEOPRENE GASKET
RAIL, TOP & BOTTOM
EXTRUDED ALUMINUM
TYPICAL AIR HANDLING UNIT
ROOFTOP UNIT CURB DETAIL - AHU-6
NO SCALE
NOTES:
1. ATTACH CURB TO STRUCTURAL STEEL BASE.
2. SOLID BOTTOM PLENUM CURB SHALL BE INTERNALLY LINED
BY THE MANUFACTURER.
2"x2"x1/8" SUPPORT ANGLE IRON
AROUND INSIDE OF CURB WITH
(2) INTERMEDIATE ANGLES
CENTERED EQUALLY.
2
2
KSD-ME5.2
ME
CH
AN
IC
AL F
LO
W D
IA
GR
AM
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
1
AD
DE
ND
UM
#
12
-2
4-2
11
AD
DE
ND
UM
#
23
-3
-2
12
RTU
PACKAGED DX ROOFTOP UNIT SCHEDULE
PLAN MARK MANUFACTURER MODEL NO.
CFM
SUPPLY FAN
ESP HP TYPESENSIBLE (MBH) TOTAL (MBH)
COOLING SECTION
EAT °F
(DB/WB)
EER
HEATING SECTION
TYPE
CAPACITY
(MBH or KW)
WEIGHT
(LBS)
NOTES
LAT °F
(DB/WB)
TSP
EAT °F
(DB)
LAT °F
(DB)
FILTER
CFM
ROOF CURB ADAPTER.
NOTES:
1
PROVIDE SINGLE POINT POWER CONNECTION WITH DISCONNECT SWITCH.
2
STAINLESS STEEL DRAIN PAN.3
DRY-BULB ECONOMIZER.4
TOTAL STATIC PRESSURE DROP SHALL INCLUDE DIRTY FILTER.5
6PROVIDE 120V CONVENIENCE RECEPTACLE. RECEPTACLE SHALL BE FIELD WIRED.
7
8VARIABLE SPEED DRIVE FOR SUPPLY FAN.
9CAPACITIES ARE BASED ON 95°F SUMMER AMBIENT AND 0°F WINTER AMBIENT.
10POWERED EXHAUST.
NIP-RTU-9 AAON RN-011-3-0-EB09-14A 3000 1.5 3 DX 84.83 124.96 81/67.42 12.7 ELEC. 40 KW 200653.14/52.882.04 48 90 MERV 83000
11
MODULATING GAS BURNER SHALL HAVE 3:1 TO TURNDOWN.
12
MODULATING HOT GAS REHEAT.
DCV
OA CFM
MIN/MAX
220/1000
AHU
AIR HANDLING UNIT SCHEDULE
PLAN MARK MANUFACTURER MODEL NO.
CFM
SUPPLY FAN (DUAL DIRECT DRIVE
PLENUM FANS)
ESP
HP (EA.)TYPE
SENSIBLE
(MBH)
TOTAL
(MBH)
COOLING SECTION
EAT °F
(DB/WB)
HEATING SECTION
TYPE
WEIGHT
(LBS)
NOTES
LAT °F
(DB/WB)
TSP
EAT °F
(DB)
LAT °F
(DB)
FILTER
(2 IN.)
PROVIDE 12" INSULATED, SOLID BOTTOM PLENUM CURB.
NOTES:
1
PROVIDE SINGLE POINT POWER CONNECTION WITH DISCONNECT SWITCH.
2
STAINLESS STEEL DRAIN PAN.
3
DRY-BULB ECONOMIZER.
4
TOTAL STATIC PRESSURE DROP SHALL INCLUDE DIRTY FILTER.
5
6
FACTORY CONTROL DAMPERS.
PROVIDE 120V CONVENIENCE RECEPTACLE. RECEPTACLE SHALL BE FIELD WIRED.7
8VARIABLE SPEED DRIVE FOR SUPPLY FAN.
9
CAPACITIES ARE BASED ON 95°F SUMMER AMBIENT AND 0°F WINTER AMBIENT.
10
POWERED EXHAUST.
KHS-AHU-9
11
12NOT USED
DCV
OA CFM
MIN/MAX EWT °F LWT °F GPM
TOTAL
(MBH)
EWT °F LWT °F
AIR PD
(IN WC)
WATER PD
(FT HD)
AIR PD
(IN WC)
GPM
WATER PD
(FT HD)
FACTORY PIPE CHASE ON SAME SIDE AS COIL CONNECTIONS.13
BAROMETRIC RELIEF DAMPER.
14
AIR COOLED CONDENSING UNIT SCHEDULE
PLAN
MARK
MFR. & MODEL NO.
CAPACITY
(MBH)
AMBIENT
TEMP. (°F)
REFRIG.
TYPE
ELECTRICAL DATA
MCA MOP
COMPRESSOR (EA.) COND. FANS (EA.)
NO. FLA
REMARKS
CU
OUTSIDE AIR CONDITIONS: SUMMER 95°F DB, 75°F WB.
NOTES:
1
CONTRACTOR SHALL SIZE REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATIONS.2
SERVING
WEIGHT
(LBS)
NGL-AHU-1
TIL-AHU-1TIL-CU-1
NO. RLA
AAON CFA-040-D-A-8-GC00L 142 150 3.4 250030.1
AAON CFA-050-D-A-8-GC00K 233 250 7.2 254748.1
VOLT/PH/Hz
95 R-410A 208/3/60
95 R-410A 208/3/60
44
44
MOUNT CONDENSING UNIT ON EXTERIOR CONCRETE PAD.3
PROVIDE CONDENSER COIL HAIL GUARDS.4
SINGLE POINT POWER CONNECTION W/ NON-FUSED DISCONNECT.5
NIP-RTU-10 AAON 4000 DX MERV 8360/1400
NIP-RTU-11 AAON RN-020-3-0-EB09-16A 6500 2.0 7.5 DX 163.46 230.03 81/67.42 12.3 60 KW 303754.2/53.83.22 51.5 83 MERV 8425/1700
NIP-RTU-12 AAON RN-020-3-0-EB09-17A 5500 2.0 7.5 DX 154.34 232.38 83/69.09 12.3 80 KW 318553.6/53.53.03 45.8 92 MERV 8360/2000
NIP-RTU-13 AAON RN-020-3-0-EB09-16A 5500 2 5 DX 152.68 227.03 12.3 30373.05 53.7 88 MERV 8
NIP-RTU-14 AAON RN-015-3-0-EB09-15A 4500 2.0 5 DX 124.09 181.76 81/67.42 11.3 50 KW 200653.14/52.883.22 49.6 84.5 MERV 8355/1400
NIP-RTU-15
NIP-RTU-W-1
NIP-RTU-W-2
NIP-RTU-W-3
KEY-AHU-3
RN-013-3-0-EB09-15A
2.0 3.07 5 105.12 150.19 81/67.42 12.154.2/54.1 50 KW 46.8 86.5 2006
AAON RN-011-3-0-EB09-14A 3500 1.5 3 DX 90.78 125.84 81/67.42 12.7 ELEC. 40 KW 200654.59/54.462.23 51.4 87.5 MERV 8200/1000
AAON RN-020-3-0-EB09-12A 7500 102.25 3.60 200/1500 DX 227.29173.98 79/65.7 54.78/54.5 12.3ELEC.
7500 20 KW 56.0 65 3350MERV 8
AAON RN-030-3-0-EB09-12A 8500 2.25 3.92 10 315/1700 DX 311.75217.91 79/65.7 52.1/51.8 11.0 3500
AAON RN-016-3-0-EB09-349 5200 2 3 5 DX 183.84133.68 79/65.7 52.8/52.6 12.3 3060
81/67.42 53.81/53.50 60 KW
KHS-AHU-21
NIP-AHU-2
NIP-AHU-3
NIP-AHU-4
NIP-AHU-5
NGL-AHU-1
TIL-AHU-1
HOT WATER 32.5 95342.33 0.11 3.6135 MERV 8 1700KLIMOR EVO-S 0750 6000 2 3.5 188.85 264.83 82.7/68.8 54/53.83.05 550/2300 0.53
KLIMOR
KLIMOR
KLIMOR
EVO-S 0950 8000 28002 2.85 7 880/4000 HOT WATER 40 95 0.07 7.5 MERV 884.8/69.6 54/53.8 0.73
EVO-V 0950 93502 3.2 7 895/3500 287.3 394.6 82.6/67.8 54/52.5 0.92 HOT WATER 507.2 43.8 95 0.17 50 4.65 MERV 8 2500
1075/3800EVO-V 115011,300
2 3.42 7 362.8 512.0 82.9/68.154/52.9 1.02 HOT WATER 639.7 43.6 95 0.16 45 11.5 MERV 8 2900
NGL-CU-1
KLIMOR EVO-S 200019,700
31002 3.54 7.5 1990/5880 DX 571.76 852.27 80.69/66.9
54/52.8 0.68 HOT WATER 987.29 49.5 95 0.1867 2.83
MERV 8
KLIMOR EVO-V 140014,000
2 3.6 8.5 1250/3700 DX 397.26 586.03 80.3/66.5 54/52.8 0.63 HOT WATER 670.79 51.5 95 .17 46 1.48 MERV 8 2900
426.1
563.2
AAON RN-015-8-0-EA09-EJL 5000 2.0 3.71 7.5 440/1360 DX 121.99 168.11 80.4/66.3 54.1/53.5 11.1HOT WATER
5000243.2 51.0 95 MERV 8
2600
480/1040N. GAS
5200
270 IN
218.7 OUT
56.0 95 MERV 8
ELEC.8500 20 KW 56.0 65 MERV 8
ELECTRICAL DATA
MCA MOP
60
VOLT/PH/Hz
63.4 80208/3
PROVIDE SCR ELECTRIC HEAT CONTROL
1-6, 8, 9, 10, 12, 14, 16, 17, 18
1-11, 15, 16, 17, 18, 19
1-11, 15, 16, 17, 18
480/3
480/3
1-10, 13, & 14, 16, 17, 18, 19
1-11, 14, 16, 17, 18
13PROVIDE HOT WATER HEATING COIL WITH 3-WAY VALVE. SIZE HOT WATER
HEATING COIL WITH WATER TEMPERATURE DROP OF 20 DEGREE TEMPERATURE.
14ROOF CURB ADAPTER.
18 30
20.3 20
8.5 12.3
18 25
18 20
NIP-AHU-6 KLIMOR 790/3000EVO-V 1150 90002 3.21 7 248.5 419.9 82.9/68.1
54/52.9 0.99 HOT WATER 488.3 45 95 0.16 50 4.5 MERV 8 2630
AAON
AAON HOT WATER
HOT WATER
345/1400
1-11, 15, 16, 17, 18
1-11, 15, 16, 17, 18
1-11, 15, 16, 17, 18
1-11, 15, 16, 17, 18
1-11, 15, 16, 17, 18
1-6, 8, 9, 10, 12, 14, 16, 17, 18
15UNIT BASE INSULATION.
16TERMINAL STRIP FOR FIELD MOUNTED CONTROLLER.
17DIGITAL SCROLL COMPRESSOR.
18HAIL GUARDS
19FULLY REMOVABLE ACCESS PANELS.
RN-016-3-0W0J-EJL
RN-030-3-0W0K-EHN
QTY.
1
1
2
2
2
2
2
3
2
9500
7500 2
1.5
3.86
3.71
10
10
405/1350
300/3500
CHILLED
WATER
CHILLED
WATER
CHILLED
WATER
CHILLED
WATER
CHILLED
WATER
CHILLED
WATER
CHILLED
WATER
190.18
282.5 403.4
279.95
82.8/67.9
80.2/66.8
52.6/52.3
53.5.52.9
0.76
0.44 44
44
44
44
44
44
44
54
54
56
56
56
56
56
50
100
47
70
90
74
MAX VEL
(FPM)
15.7
10.8
27.9
24.5
22.9
22.8
25.7
450
450
450
450
450
450
450
450
450
325.5 55 95 180 1600.6 32 2.1
180 160
180 160
180 160
180 160
180 160
180 160
180 160
180 160
MERV 8
MERV 8
4500
2300
ELECTRICAL DATA
MCA MOP
460/3/6082 100
43 50
VOLT/PH/Hz
63 70
460/3/60
460/3/60
460/3
46032
208/3/60 97 110
39 50
39 50
39 50
72 90
57 70
72 90
39 50
480/3
480/3
480/3
480/3
480/3
208/343.8
18 320
460/3
460/3
460/3
460/3
460/3
DX COIL DESIGNED FOR R-410A REFRIGERANT.15
EC MOTOR FOR SUPPLY FANS.16
COOLING COIL DATA BASED ON 30% PROPYLENE GLYCOL.
17
SUPPLY CFM IS SPLIT BETWEEN FANS.18
SITE GLASS AND COMPRESSOR ISOLATION VALVES.6
LOW SOUND FANS.7
8
EACH CIRCUIT SHALL HAVE VARIABLE CAPACITY COMPRESSOR.
ALL
ALL
RF
FAN SCHEDULE
PLAN
MARK
MANUFACTURER MODEL NO. CFM
S.P.
(IN. WC.)
RPM
HP
MOTOR DATA
TYPE DRIVE NOTES
NOTES:
WEIGHT
1
INTEGRAL DISCONNECT.
2
BACKDRAFT DAMPER.
3
4
TIL-RF-1A GREENHECK AER-E20C-422-A 5000 0.3 1750 1 PROPELLER DIRECT100
FACTORY CURB.
2 3 4
(LBS)
VOLT/PH
208/3
TIL-RF-1B GREENHECK 5000 0.3 1 PROPELLER DIRECT 2100
1750208/3
SERVING
AHU-1
AHU-1 3 4
EC MOTOR.
5BIRD SCREEN
5
5
446.6278.8 80 550.7 55
(4) SPLIT COOLING. (2) VERTICALLY SPLIT HEATING COILS.19
PRE-HEAT COIL SIZED FOR 8000 CFM, 347.2 MBH, 35 GPM.
20
67 95 0.5224.0 25 1.6
1-8,10,20
1-9,13,14,21
ROOF CURB ADAPTER.
1-6,16-18
1-6,11,16-18
1-6,16-18
1-6,16-18
1-6,13,16-18
1-6,15,16,18,19
1-6,15,16,18
CFM
7500
6000
8000
9350
9500
9000
19,700
14,000
11,300
4000
6500
5500
5500
4500
3500
ELEC.
ELEC.
ELEC.
ELEC.
ELEC.
NIP-RF-4 GREENHECK G-240 8000 0.5 970 5 DOWN BLAST DIRECT300
1 2 3 4460/3AHU-4 5
NIP-RF-2 GREENHECK SQ-160-A 4700 0.5 1725 2 INLINE DIRECT200
3 4460/3AHU-2
GREENHECK G-240 9500 0.5 5 DOWN BLAST DIRECT 1 2300
1034460/3AHU-5 3 4 5NIP-RF-5
AER-E20C-422-A
6HANGING NEOPRENE ISOLATORS
6
7WALL COLLAR AND MOTOR GUARD
8WEATHER HOOD
7
7
8
8
1
18 30
1
HW PRE-HEAT COIL, 250 MBH, 25°F RISE, 13 GPM.
21
1
1
1
NGL-AHU-1AAON CFA-040-D-A-8-GC00L 95 R-410A 208/3/60 4
NGL-CU-2ALL
1
426.1 142 150 30.1 4 3.4 2500
KSD-ME6.1
ME
CH
AN
IC
AL A
ND
E
LE
CT
RIC
AL S
CH
ED
ULE
S
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
AD
DE
ND
UM
#
23
-3
-2
11
55 DP-4-7/9/11 -3P-70A345.7- 480ROOFTOP UNIT
DESCRIPTION
POWER SOURCE-FEEDERLOAD CHARACTERISTICS
VOLT
EQUIPMENT DATA SCHEDULE
HP
KVA FLA PHASE PANEL/CIRCUIT FEEDER CONDUIT
STARTER/DISCONNECT
PROTECTION TYPE RATING
1" -EM
FURNISHED BY
EM
INSTALLED BY NOTES
1
NOTES:
1. DISCONNECT IS INTEGRAL TO UNIT. PROVIDE SINGLE POINT CONNECTION.
NIP-
RTU-9
ROOFTOP UNIT
NIP-
RTU-10
ROOFTOP UNIT
NIP-
RTU-11
ROOFTOP UNIT
NIP-
RTU-12
ROOFTOP UNIT
NIP-
RTU-13
ROOFTOP UNIT
NIP-
RTU-14
ROOFTOP UNIT
NIP-
RTU-15
ROOFTOP UNIT
NIP-RTU
-W-1
ROOFTOP UNIT
NIP-RTU
-W-2
ROOFTOP UNIT
NIP-RTU
-W-3
ROOFTOP UNIT
KEY-
RTU-3
3#4,
1#8G
PLAN
MARK
71 DP-4-13/15/17 -3P-80A359- 480 -EM EM 1
3#3,
1#8G
88 DP-4-19/21/23 -3P-100A373.2- 480 -EM EM 1
3#3,
1#8G
111 DP-4-25/27/29 -3P-125A392.3- 480 -EM EM 1
3#1,
1#6G
1
1
4
"
83 DP-4-14/16/18 -3P-100A369- 480 -EM EM 1
3#3,
1#8G
68 DP-4-20/22/24 -3P-80A356.5- 480 -EM EM 1
3#3,
1#8G
56 DP-4-26/28/30 -3P-70A346.6- 480 1" -EM EM 1
3#4,
1#8G
77 DP-2-(EC) -3P-100A / 100AF364- 480 -EM EM 1
(E)
(E)
59 DP-2-(EC) -3P-100A / 70AF349.1- 480 -EM EM 1
39 DP-2-(EC) -3P-60A / 50AF332.4- 480 -EM EM 1
91 MDP-(EC) -3P-200A / 110AF332.8- 208 -EM EM 1
CHILLER
NIP-
CH-1
166 DP-3-1 -3P-200A / 200AF3138- 480 -EM EM 1
3#
3
0
,
1#6G
2"
CHILLED WATER PUMP
NIP-
CP-1
21 DP-1-1 VFC3P-60A / 30AF317.515 480 1EC EC -
3#10,
1#10G
3
4
"
15
AIR COOLED CONDENSING UNIT
NGL-
CU-1
134 MDP-(EC) -3P-400A / 150AT348.2- 208 -EM EM 1
LEGEND:
EC - ELECTRICAL CONTRACTOR
EM - EQUIPMENT MANUFACTURER
FVNR - FULL VOLTAGE NON REVERSING
MC - MECHANCAL CONTRACTOR
NF - NON FUSED
DPST - DOUBLE POLE SINGLE THROW
TS - TOGGLE SWITCH, MOTOR RATED
VFC - VARIABLE FREQUENCY CONTROLLER
AF - AMP RATING OF FUSES
AT - AMP TRIP RATING OF BREAKER PLUG
AIR COOLED CONDENSING UNIT
TIL-
CU-1
309 DP2-(EC) -3P-400A / 250AF3111.2- 208 -EM EM 1
AIR HANDLING UNIT
KHS-
AHU-9
14 K-4-1 -3P-25A311.6- 480 -EM EM 1
AIR HANDLING UNIT
KHS-
AHU-21
14 DP-P-(EC) -3P-30A / 30AF311.6- 480 -EM EM 1
NIP-
AHU-2
9 DP-1-(EC) -37.5- 480 -EM EM 1AIR HANDLING UNIT
NIP-
AHU-3
18 DP-1-(EC) -315- 480 -EM EM 1AIR HANDLING UNIT
NIP-
AHU-4
18 DP-5-25/27/29 -315- 480 -EM EM 1AIR HANDLING UNIT
NIP-
AHU-5
20 DP-5-26/28/30 -316.6- 480 -EM EM 1AIR HANDLING UNIT
NGL-
AHU-1
63 DP-G-(EC) -322.7- 208 -EM EM 1AIR HANDLING UNIT
TIL-
AHU-1
44 MCC-T-(EC) -315.8- 208 -EM EM 1AIR HANDLING UNIT
3P-30A / 10AF
3P-30A / 25AF
3P-25A
3P-25A
3P-100A / 80AF
STARTER / 60AF
CHILLER
NIP-
CH-2
CHILLED WATER PUMP
NIP-
CP-2
NIP-
AHU-6
18 DP-6-(EC) -315- 480 -EM EM 1AIR HANDLING UNIT 3P-30A / 25AF
NIP-
RF-2
3.4 DP-1-(EC) -32.82 480 -EM EM 1RETURN FAN 3P-30A / 6.25AF
NIP-
RF-4
DP-5-19/21/23 -35 480 -EM EM 1RETURN FAN 3P-15A
NIP-
RF-5
DP-5-20/22/24 -35 480 -EM EM 1RETURN FAN 3P-15A
166 DP-3-23138- 480
21 DP-1-2317.5 480
7.66.3
7.66.3
1
1
4
"
1
1
4
"
1
1
4
"
1
1
4
"
(E)
(E)
(E)
(E)
(E)
(E)
3#
3
0
,
1#6G
2"
3#10,
1#10G
3
4
"
(E)
(E)
(E)
(E)
3#10,
1#10G
3#10,
1#10G
(E)
(E)
(E)
(E)
(E)
(E)
3#10,
1#10G
3
4
"
3#10,
1#10G
3
4
"
3#3,
1#8G
1
1
4
"
(E)
(E)
3P-200A / 200AF
3P-60A / 30AF
- -EM EM 1
VFC 1EC EC -
(E)
(E)
3#12,
1#12G
3
4
"
3#12,
1#12G
3
4
"
TIL-
RF-1A
MCC-T-(EC) -31 208 -EM EM 1RETURN FAN STARTER / 15AF4.81.7
3#12,
1#12G
3
4
"
TIL-
RF-1B
-31 208 -EM EM 1RETURN FAN 4.81.7
3#12,
1#12G
3
4
"
(E)
(E)
MCC-T-(EC) STARTER / 15AF
AIR COOLED CONDENSING UNIT
NGL-
CU-2
134 MDP-(EC) -3P-400A / 150AT348.2- 208 -EM EM 1
(E)
(E)
KSD-ME6.3
ME
CH
AN
IC
AL A
ND
E
LE
CT
RIC
AL S
CH
ED
ULE
S
Kirkw
oo
d S
ch
oo
l D
istrict
02/17/2021
BRiC MO CERTIFICATE OF
AUTHORITY 2002028690
CHECKED
DRAWN
DATE
JOB NO
DE
SC
RIP
TIO
ND
AT
EN
O
SHEET NO
IS
SU
AN
CE
2317-03
KS
D 2021 H
VA
C R
EP
LA
CE
ME
NT
P
RO
JE
CT
CO
NSU
LTIN
G E
NG
INEE
RSPA
RTN
ERSH
IP,
LLC
3636
S. G
EYER
RD
, SUI
TE 3
05
TEL
314
.725
.588
9ST
. LO
UIS,
MO
631
27
THE PROFESSIONAL ENGINEER'S SEAL AFFIXED TO THIS SHEET APPLIES ONLY TO THE
MATERIAL AND ITEMS SHOWN ON THIS SHEET. ALL DRAWINGS, INSTRUMENTS OR OTHER
DOCUMENTS NOT EXHIBITING THIS SEAL SHALL NOT BE CONSIDERED PREPARED BY THIS
ENGINEER, AND THIS ENGINEER EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITY
FOR SUCH PLAN, DRAWINGS OR DOCUMENTS NOT EXHIBITING THIS SEAL.
BJG
CPF
MRJ
CVH
MICHAEL R. HOFF
MO LICENSE NO. 2013000576
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 23
CARL V. HAUCK
MO LICENSE NO. 016688
EXP: 12/31/2021
THE PROFESSIONAL ENGINEERS SEAL AFFIXED TO THIS SHEET IS
RESPONSIBLE FOR THE DESIGN OF WORK SPECIFIED IN DIVISION 26
AD
DE
ND
UM
#
12
-2
4-2
11
AD
DE
ND
UM
#
23
-3
-2
12