lab rep

Upload: subhranshu-dwibedi

Post on 02-Jun-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 LAB REP

    1/13

    1

    1. Abstract

    The experiment conducted deals with investigating the force-deformation characteristics,

    lateral strength and stiffness, energy dissipation capacity, and failure mode of steel braces

    subjected to cyclic loading. In this experiment, steel brace of equal leg angle section (hot-rolled

    single angle sections of size ISA 40406 @26.0 N/m) is used and tested under lateral cyclic

    load. Displacement level and corresponding level of lateral load applied on the specimen are

    monitored by the in-built LVDT and load cell of the actuator which is used to apply the lateral

    cyclic load to the test specimen. The cyclic inelastic buckling mode shape is observed. The

    guidelines developed for loading history are based on a general concept of cumulative structural

    damage in a component. Loading history considered in the present experiment for slow-cyclic

    testing consisted of gradually-increased reversed-cyclic displacements. The theoretical bucklingload for the steel brace is computed as per IS 800:2007 both in flexure and flexural torsion and

    compared with the experimental result. It is observed that flexural buckling load and flexural

    torsional buckling load are less than observed value. Therefore in actual structure steel brace can

    carry more load than that anticipated.

    2.

    Introduction

    Slow-cyclic testing technique provides a consistent and reliable set of experimental data on

    strength, stiffness, energy dissipation potential, and failure mode of structures. As a result, the

    ability of structures to resist earthquake loads is often assessed reasonably. Steel braces are

    mainly provided in frame structure to enhance the lateral stiffness of a structure. Sometime these

    are also used in structure as a viable alternative of energy dissipation device (such as viscous

    damper, metallic yield damper, Magneto rheological damper), under cyclic loading (such as

    seismic loading). Bracings are designed in such a way that it can dissipate substantial part of the

    imparted seismic energy (into the structure) through its yielding (i.e. as hysteresis energy).

    However, it is noteworthy to mention that the energy dissipation capacity of steel bracing can

    reduce severely due to its premature buckling action, which becomes more adverse in

    conjunction with yielding. To enhance the performance of a structure sometimes buckling

    resisting braces (BRB) are provided, but that does not improve steel braced-structure

  • 8/11/2019 LAB REP

    2/13

    2

    performance significantly under near-fault motion. Slow-cyclic testing technique provides a

    consistent and reliable set of experimental data on strength, stiffness, energy dissipation potential,

    and failure mode of structures.

    Careful planning of the entire test program is essential for obtaining meaningful results, which

    includes fabrication of test specimen, test structure assembly, load application system, supporting

    system, loading history, instrumentation, data acquisition, data reduction, analysis and presentation.

    It is important to mention the boundary conditions, initial conditions, scale effects, etc. to interpret

    the test results.

    3.

    Experimental Setup

    The experimental setup consists of a steel brace of equal leg angle section (hot-rolled

    single angle section ISA 40406).The brace is mounted in a shear loading frame in which four

    members of hot-rolled steel sections of ISMB150 @ 149.0 N/m forming a rectangular loading

    space are pin-connected at ends (Figure 1). Length of the brace between end-to-end is 1400 mm.

    Servo-hydraulic (SH) actuator (MTS make) of capacity 100 KN and stroke length 75 mm is used

    to apply the lateral cyclic load to the test specimen.Two types of sensors, namely, strain gauge

    and LVDT are used. To monitor state of strain of brace at different displacement levels two

    strain gauges are used at about 300 mm distance from the base.One LVDT is used at the top

    beam level at opposite end to actuator to measure horizontal displacement of the specimen and

    another LVDT is placed at the back of actuator to measure displacement of reaction frame. Real-

    time behavior of the test specimen is monitored by System 5000 Data Acquisition (DAQ)

    System. Lateral load, strain and displacement of the specimen are suitably captured by the strain

    and voltage channels.Analog output of the sensors is converted to digital format in the DAQ

    system, which is further transferred to computer for storage as well as online display.

  • 8/11/2019 LAB REP

    3/13

    3

    Figure 1: Experimental setup

    4.

    Procedure

    The SH actuator is started to apply horizontal cyclic load.

    The strain gauge, LVDT and MTS LVDT and load cell readings are recorded

    throughout the loading history.

    It is generally observed that the contributions of large excursions are much larger

    than small excursions. Further, the relative amount of damage caused by an

    inelastic excursion is largest for the symmetric excursion and depends on the

    sequence in which large and small excursions are applied. Loading history

    considered in the present experiment for slow-cyclic testing consisted of

    gradually-increased reversed-cyclic displacements as shown in Figure 2.

    Displacement levels increases linearly from an initial magnitude of 0.5 mm with

    an increment of 0.5 mm.

    Each displacement excursion level is repeated for three times to study the

    behavior of specimen with repetitive cyclic loading.

  • 8/11/2019 LAB REP

    4/13

    4

    Test specimen is loaded with increased magnitude until the failure is observed.

    Figure 2: Loading history

    5. Results and Discussions

    The results obtained are analyzed and discussed as follows through answering the discussion

    items.

    Compare the observed buckling load of the brace with analytically predicted value

    using Indian Standard IS:800-2007 provisions of flexural buckling as well as

    flexural torsion buckling.

    Maximum of load measured by the in-built load cell in the actuator = 28.9 kN.

  • 8/11/2019 LAB REP

    5/13

    5

    = tan-1

    (800/1150) = 34.82 (APPROX.)

    Carrying out the truss analysis, observed buckling load = load in the brace = 35.20 kN.

    Analytically predicted value using IS 800:2007

    Flexural buckling

    From Cl. 7.1.2.1, the design compressive strength,

    fcd = fym0/[ + (22)0.5]

    Here = 0.5[1+ ( - 0.2) + 2]

    = (fy/ fcc)0.5

    fcc = 2E/(KL/r)

    2

    Now, from the steel test data, fy= 375 MPa.

    fcc=2

    x 2 x 105/ (0.65 x 1400/7.7)

    2= 141.33 MPa.

    = (375/141.33)0.5

    = 1.63

    Buckling class : c (For all Angle Sections Buckling Class is same)So, = 0.49.

    = 0.5[1+0.49 (1.63 - 0.2) + 1.632] = 2.18

    fcd= 375 x 1.1 / [2.18 + (2.1821.63

    2)0.5

    ] = 113.7 MPa.

    Area of the angle section = 447 mm2.

    Therefore, buckling load in flexure = 447 x 113.7 N = 50.83 kN.

    Flexural torsional buckling

    As per cl. 7.5.1.2, equivalent slenderness ratio, e= (k1+ k2vv2+ k3

    2)0.5

    vv = (l/rvv) / (2E/fy)

    0.5

    = [(b1+ b2) /2t]/ (2E/fy)

    0.5

    = (250 / 375)0.5

    = 0.816.

    So, vv = (1400/7.7) / 0.816(2x 2 x 10

    5/375)

    0.5= 3.07.

    28.9 kN

    34.820

  • 8/11/2019 LAB REP

    6/13

    6

    = [(40 + 40) /(2 x 6)]/ 0.816(2x 2 x 10

    5/375)

    0.5= 0.11.

    k1= 0.2

    k2= 0.35

    k3= 20

    Therefore, e= (0.2 + 0.35 x 3.072+ 20 x 0.11

    2)0.5

    = 1.93

    = 0.5[1+0.49 (1.93- 0.2) + 1.932] = 2.78.

    fcd= 375 x 1.1 / [2.78 + (2.7821.93

    2)0.5

    ] = 86.28 MPa.

    Area of the angle section = 447 mm2.

    Therefore, buckling load in flexural torsion = 447 x 86.28N = 38.56 kN.

    Therefore, theoretical buckling load in flexure>theoretical buckling load in flexural torsion >

    observed buckling load.

    Compare force measurements using strain gauges with that of load cell in the

    actuator arm. Explain sources of discrepancies, if any.

    The loading history is as follows:

    -60

    -40

    -20

    0

    20

    40

    60

    80

    100

    0 200 400 600 800 1000 1200

    Load

    (kN)

    Time elapsed (second)

    Loading history

  • 8/11/2019 LAB REP

    7/13

    7

    Strain gauge SG1 is installed at the unconnected leg of the steel brace, while SG2 is on the

    connected leg. Therefore, SG2 readings are more than SG1 readings.

    Lets consider certain SG2 readings and corresponding load cell readings.

    Connected

    Leg Strain

    Connected

    Leg Area

    Unconnected

    Leg Strain

    UnConnected

    Leg Area

    Connected

    Leg Load

    UnConnected

    Leg Load

    Total Load cell

    values

    201.61 223.50 139.38 223.50 9.01 6.23 15.24 3.47

    200.66 223.50 138.91 223.50 8.97 6.21 15.18 3.48

    200.18 223.50 138.91 223.50 8.95 6.21 15.16 3.48

    199.22 223.50 138.91 223.50 8.91 6.21 15.11 3.47

    200.66 223.50 138.43 223.50 8.97 6.19 15.16 3.47

    200.18 223.50 138.43 223.50 8.95 6.19 15.14 3.47

    200.18 223.50 137.95 223.50 8.95 6.17 15.11 3.47

    200.66 223.50 137.95 223.50 8.97 6.17 15.14 3.47

    200.18 223.50 138.43 223.50 8.95 6.19 15.14 3.47

    201.13 223.50 138.43 223.50 8.99 6.19 15.18 3.47

    200.18 223.50 137.47 223.50 8.95 6.15 15.09 3.46

    Thus, it is observed that load in the steel brace obtained in the load cell in the actuator is less

    than that obtained from strain gauge readings.

    This discrepancy is because of the fact that in calculating loads from strain gauge readings,

    we have assumed uniform strain and stress distribution for the whole angle section, but in reality

    it is not so.

    Do you observe any sign of shear lag effect in any of the measurements that

    has been made during the test?

    Shear lag effect has been observed in the strain gauge readings. Strain gauge SG1 is

    installed on the unconnected leg, whereas SG2 on connected leg. Since the compression in the

    steel brace is mostly resisted by the connected leg (due to shear lag effect), the strain in the

    connected leg is more than that in the unconnected leg. Here are some data which shows that

    SG1 readings are less than SG2 readings:

  • 8/11/2019 LAB REP

    8/13

    8

    Connected Leg Strain Unconnected Leg Strain Shear lag

    201.61 139.38

    200.66 138.91

    200.18 138.91

    199.22 138.91

    200.66 138.43

    200.18 138.43

    200.18 137.95

    200.66 137.95

    200.18 138.43

    201.13 138.43

    200.18 137.47

    Therefore shear leg effect is observed.

    Obtain an analytical prediction for the observed back-bone curve of the specimen

    and compare the observed behavior.

    For the steel used in the brace, fy= 375 MPa. So, Fy= 375x 447 N = 167.625 kN.

    E = 2 x 105 N/mm

    2. Therefore, y = 167.625x1000 x 1400 / (447 x 2 x 10

    5) = 2.625 mm.

    Therefore the theoretical backbone curve is as follows:

  • 8/11/2019 LAB REP

    9/13

    9

    Fig. Theoretical backbone curve for steel

    Fy= 167.625 kN

    F 6 = 27.937 kN

    = 2.625 mm

    Fy/3 = 55.875kN

    y/3 = 0.875 mm

    2 = 5.25 mm

    F

  • 8/11/2019 LAB REP

    10/13

    10

    Now, the observed cyclic load (lateral) applied by the actuator vs displacement curve is as

    follows:

    From truss analysis, it is obtained that the ordinates of the above curve have to be multiplied by

    1.202 to obtain steel brace load vs displacement curve, as shown next:

    Thus, from the experimental backbone curve, Fy = 72.23kN and y= 23.55 mm.

  • 8/11/2019 LAB REP

    11/13

    11

    Therefore, deviation of the theoretical values of:

    Fy=

    x 100 % = 56.31%.

    y =

    x 100 % = 88.85 %.

    Comment on the observed behavior, such as the axis of buckling, buckling

    mode, inelastic activities, failure, etc. Is there any evidence of flexural torsion

    buckling as anticipated in IS 800 for single angle struts?

    Comments on observed behavior

    Axis of buckling

    The axis of buckling was the minor axis of the channel section,v-v, as shown below.

    Buckling mode

    The buckling occurred in the first mode, since no nodes were observed.

    Inelastic activities

    The load displacement curve shows that loading and unloading didnt follow the same path.

    Therefore, inelastic activities took place during the experiment.

    Failure

    Failure took place when a hinge was fully formed at a section (towards mid-section) of the steel

    brace. At this stage the lateral load applied by the actuator was highest.

    v

  • 8/11/2019 LAB REP

    12/13

    12

    There is evidence of flexural torsion buckling as anticipated in IS 800 for single angle

    struts. As we have already seen, the theoretical flexural torsional buckling load of the angle

    section is obtained as 38.56 kN, whereas the experimental buckling load was 28.9 kN. Thus,

    although there is a deviation, this may be because of the factor of safety assumed in finding out

    the theoretical value as per IS 800:2007. Moreover, during the experiment, it was observed that

    torsion took place along with flexure in the buckling. Therefore, flexural torsional buckling took

    place.

    Quantify the errors in observed values as compared to theoretical results.

    State the source of errors involved in this experimental study.

    Lets consider the buckling load. From the experimental result, the buckling load of the steel

    brace under cyclic loading is 28.9 kN.

    Theoretically, the flexural buckling load as per IS 800:2007 is 50.83 kN and the flexural

    torsional buckling load is 38.56 kN.

    Thus, the error in buckling load (considering flexural buckling) =

    x 100 % =

    43.14 %.

    Error in buckling load (considering flexural torsion) =

    x 100 % = 25.05 %.

    Here in obtaining the theoretical buckling loads, factor of safety has been used, whereas

    the actual steel brace can carry more load before buckling. This is a source of error.

    Besides, in the experiment cyclic load has been applied and the steel brace has reached

    inelastic zone. But in obtaining the theoretical values inelasticity has not been considered. Also,

    the theoretical values do not take into account cyclic loads. Thats why there is a deviation of

    experimental result from theoretical value.

    6. Conclusions

    Interpretation of the experimental results leads to concluding that there is a substantial

    difference between observed buckling loads and theoretical buckling load. This is because of

  • 8/11/2019 LAB REP

    13/13

    13

    inelasticity of the actual structure and cyclic loading. The deviation of the theoretical backbone

    curve from the experimental one is also due to this fact. The factor of safety taken into account

    also affects the theoretical values. Due to shear lag effects, the strains measured by two strain

    gauges are different. Moreover, we can conclude that the buckling occurred in the first mode

    about the minor axis. The buckling is actually flexural torsional buckling. The errors in observed

    values are quite high due to the facts discussed earlier. Also, it is observed that a hinge is formed

    at about the mid-point of the steel brace on account of buckling.