laboratory lighting controls upgrade

15
2009 CAMPUS LIGHTING RETROFIT FORUM Laboratory Lighting Controls Upgrade New Laboratory Building Biological Sciences 3 Beat Title 24 Energy Standard by 20%+ Challenge to reduce annual energy consumption from lighting by ~50% Extremely low Lighting Power Density (LPD) LPD = Lighting Watts / Square Foot Lab Environment with ~50 Foot-candle Requirement Reducing true LPD not a probable option

Upload: ida

Post on 01-Feb-2016

48 views

Category:

Documents


0 download

DESCRIPTION

Laboratory Lighting Controls Upgrade. New Laboratory Building Biological Sciences 3 Beat Title 24 Energy Standard by 20%+ Challenge to reduce annual energy consumption from lighting by ~50% Extremely low Lighting Power Density (LPD) LPD = Lighting Watts / Square Foot - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Laboratory Lighting Controls Upgrade

• New Laboratory Building Biological Sciences 3

• Beat Title 24 Energy Standard by 20%+

• Challenge to reduce annual energy consumption from lighting by ~50%

• Extremely low Lighting Power Density (LPD)

LPD = Lighting Watts / Square Foot

• Lab Environment with ~50 Foot-candle Requirement

• Reducing true LPD not a probable option

Page 2: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

BE

FO

RE Lab Area LPD = 1.1

Lab Prep LPD = 0.9

Corridor LPD = 0.6

Prep Room LPD = 2.0

Page 3: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Manual Switch to Occupancy Sensor

50% Auto On - Manual to 100% - Auto Off

A-B CIRCUITING

Page 4: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Auto on to 50% Light Level

Page 5: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Lower Blinds to Allow for Daylighting

Page 6: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Photocell to Control Window Fixture

BUTTON PHOTOCELLS

Page 7: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Fixture Closest to the Window is OFF

Page 8: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

AF

TE

RLab Area SAVE +50%

Lab Prep SAVE 40%

Corridor SAVE +50%

Prep Room SAVE +50%

Page 9: Laboratory Lighting Controls Upgrade

2009 CAMPUS LIGHTING RETROFIT FORUM

Summary

• Project Is Scalable (floors, buildings, campuses)

• Simple Payback Period in the 2.3 to 3.4 year range

• Savings Based on Controls not LPD!

• Consider under cabinet task lighting at the work surface to augment overhead lighting

• Consider perforated blinds to increase light and reduce glare through “views” portion of fenestration

Page 10: Laboratory Lighting Controls Upgrade

1. Lighting should be as flexible as the possible

2. Provide task lighting when additional illumination is needed

3. Encourage occupants to be conscious of their lighting needs

4. Do not discount the synergistic savings of heat produced by over illuminated spaces

LIGHTING

Page 11: Laboratory Lighting Controls Upgrade

LIGHTINGPrevious

Best Practice

Space Type Gross

Hall

0.9 watts/sqft Offices 0.49 watts/sqft

1.1 watts/sqft Labs 0.66 watts/sqft

1 watts/sqft Overall Conditioned Space 0.61 watts/sqft

208,561 kWh/year 94,753 kWh/year

Results in a savings of $11,897 per year at $0.105 per kWh

Page 12: Laboratory Lighting Controls Upgrade

Perforated Window BlindsMake use of daylighting without the glare

LIGHTING

Page 13: Laboratory Lighting Controls Upgrade

Lab areas within 15’ of the window line and all private offices and conference rooms are equipped with automatic daylighting controls

LIGHTING

Page 14: Laboratory Lighting Controls Upgrade

Auto on to 50%, Manual on to 100%,

Auto off

LIGHTING

Sequence

ZoningLighting is controlled per lab bay not per lab to maximize

savings

Page 15: Laboratory Lighting Controls Upgrade

LED Task Lighting

Magnetically mounted LED Task Lighting