sweets.construction.comlaboratory technician managing director date: january 24, 2011january 24,...
TRANSCRIPT
CONSTRUCTION MATERIALS
T E C H N O L O G I E S
RFE-002-02-01 PRI-CMT Accreditations: IAS TL-189; Miami-Dade 06-1116.02; State of Florida TST 5878; CRRC The test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in full without the written approval of this laboratory. PRI Construction Materials Technologies, LLC. assumes no responsibility nor makes a performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies, LLC. 6408 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail [email protected] WebSite: http://www.pricmt.com
LABORATORY TEST RESULTS
Report for: Rieder Faserbeton-Elemente GmbH Date: January 24, 2011 Glasberg 1
D-83059 Kolbermoor Germany
Attention: Ted Devit
Product Name: Fibre C Cement Panel Manufacturer: Rieder
Date Received: June 11, 2009 Source: PRI-CMT
Project No.: RFE-002-02-01 Test Dates: November 30, 2009 – July 21, 2010
Subject: The purpose of this project was to determine certain performance properties of Rieder Faserbeton-Elemente GmbH Fiber C fiber cement siding for compliance with the conditions of acceptance of ICC-ES Acceptance Criteria AC90: Acceptance Criteria For Fiber Cement Siding Used as Exterior Wall Siding using ASTM C 1186-02 and C 1186-08: Standard Specification for Flat Fiber-Cement Sheets, Type A, Grade IV.
Sample Description: The samples used for testing were full sized sheets.
Product Sampling: The sampling complied with the requirements of AC85: Acceptance Criteria for Test Reports, Section 3.2 Testing of Representative Products. The product was sampled by PRI-CMT.
Test Methods: The test methods used included those found in ICC-ES Acceptance Criteria AC90 (November 1, 2005): Acceptance Criteria For Fiber Cement Siding Used as Exterior Wall Siding and including: ASTM C 1186-99: Standard Specification for Flat Fiber-Cement Sheets, Type A: Sheets are intended for exterior applications, subjected to direct action of sun, rain, or snow, ASTM G 155-00a: Standard Practice for Operating Xeon Arc Light Apparatus for Exposure of Non-
Metallic Materials, and ASTM E 330-971: Standard Test Method for Structural Performance of Exterior Windows, Doors, Skylights and Curtain Walls by Uniform Static Air Pressure Difference.
Rieder Faserbeton-Elemente GmbH ICC-ES AC90 for Fibre C Page 2 of 6
RFE-002-02-01 PRI-CMT Accreditations: IAS TL-189; Miami-Dade 06-1116.02; State of Florida TST 5878; CRRC The test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in full without the written approval of this laboratory. PRI Construction Materials Technologies, LLC. assumes no responsibility nor makes a performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies, LLC. 6408 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail [email protected] WebSite: http://www.pricmt.com
Summary Results of Testing:
Test and Performance Requirements Test Method Result Requirement
3.1 Physical Properties
Mechanical and Physical Requirements
Flexural Strength, Wet (psi) ASTM C 1186
MD 3826 ≥ 2610
CMD 3426 ≥ 2610
Flexural Strength, Equilibrium (psi) ASTM C 1186
MD 4001 ≥ 3190
CMD 3801 ≥3190
Density, pcf ASTM C 1186 204 Report
Dimensions and Tolerances
Nominal Length and Width (in) ASTM C 1186
Length 94 Report
Width 47-1/8 Report
Nominal Thickness (in) ASTM C 1186 0.51 Report
Length and Width Tolerance (in) ASTM C 1186
Length Tolerance 1/8 ≤ ±1/4
Width Tolerance 1/8 ≤ ±1/4
Thickness Tolerance ASTM C 1186
Within a sheet (%) 3.9 ≤ 15
Sheet to sheet (in) 0.03 ≤ ±0.05
Squareness Tolerance (in/ft) ASTM C 1186 < 1/32 ≤ ±1/32
Edge Straightness (in/ft) < 1/32 ≤ ±1/32
Workmanship, Finish, Appearance ASTM C 1186
Workmanship [Pass/Fail] Pass Uniform surface on one side,
free of major defects
Finish [Pass/Fail] Pass Exposed surface smooth,
granular or textured
Color [Pass/Fail] Pass Natural color of product or colored by
additional color mechanism
Supplementary Tests
Moisture Movement (%) ASTM C 1186 0.02 30 - 90
Water Absorption (%) ASTM C 1186 3.4 Report
Moisture Content (%) @ 73±4°F & 50±5%RH
ASTM C 1186 1.2 Report
Water Tightness [Pass/Fail] ASTM C 1186 Pass No drops of water
Continued on Following Page
Rieder Faserbeton-Elemente GmbH ICC-ES AC90 for Fibre C Page 3 of 6
RFE-002-02-01 PRI-CMT Accreditations: IAS TL-189; Miami-Dade 06-1116.02; State of Florida TST 5878; CRRC The test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in full without the written approval of this laboratory. PRI Construction Materials Technologies, LLC. assumes no responsibility nor makes a performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies, LLC. 6408 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail [email protected] WebSite: http://www.pricmt.com
Test and Performance Requirements Test Method Result Requirement
Surface Burning Characteristics ASTM E 84
Flame Spread Index Not Tested 0
Smoke Developed Index Not Tested ≤ 5
Frost Resistance (after 50 cycles) ASTM C 1186
Flexural Strength (psi)
MD – Control 4001 NR
CMD – Control 3801 NR
MD – After Freeze/Thaw 3872 (97%)
≥ 3201
(≥ 80% Control)
CMD – After Freeze/Thaw 3301 (87%)
≥ 3041
(≥ 80% Control)
Appearance Pass No visible cracks or structural
alteration to affect performance
Warm Water Resistance ASTM C 1186
Flexural Strength, psi
MD – Control 3826 Report
CMD – Control 3426 Report
MD – After Soak 2840 (74%)
≥ 2296 (≥ 60% Control)
CMD – After Soak 2977 (87%)
≥ 2056 (≥ 60% Control)
Appearance Pass No visible cracks or structural alteration of sheets and frame
Heat/Rain – Wall Structures, 25 cycles ASTM C 1185 Pass No visible cracks or structural alteration of sheets and frame
assembly to affect performance
3.2 Weather Resistive Considerations
Thickness ASTM C 1185 0.51 0.25 min
3.3 Transverse Load Tests
Transverse Load (psf) 4’ x 8’ specimens; Load to Failure; 25psf increments with 10s duration
ASTM E 330 Procedure B
Positive Load - Panel 1 +200 Report
Positive Load - Panel 2 +175 Report
Positive Load - Panel 3 +200 Report
Positive Load - Average +192 Report
Negative Load - Panel 1 -50 Report
Negative Load - Panel 2 -50 Report
Negative Load - Panel 3 -50 Report
Negative Load - Average -50 Report
Continued on Following Page
Rieder Faserbeton-Elemente GmbH ICC-ES AC90 for Fibre C Page 4 of 6
RFE-002-02-01 PRI-CMT Accreditations: IAS TL-189; Miami-Dade 06-1116.02; State of Florida TST 5878; CRRC The test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in full without the written approval of this laboratory. PRI Construction Materials Technologies, LLC. assumes no responsibility nor makes a performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies, LLC. 6408 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail [email protected] WebSite: http://www.pricmt.com
Test and Performance Requirements Test Method Result Requirement
3.4 Racking Shear Loads
Racking Load (psf) ASTM E 72
Racking Load (wet)
Not Tested Report
3.5 Fire-Resistance-Rated Construction
Fire-Resistance-Rated Construction ASTM E 119 Not Tested Report
3.6 Noncombustible Construction
Behavior at 750°C ASTM E 136 Not Tested Report
3.7 Accelerated Weathering
Accelerated Weathering [Pass/Fail] Expose 2,000h; Observe using 5x magnification
ASTM G 155 Pass No cracking checking crazing erosion
or other performance affecting conditions
Statement of Attestation: Laboratory Test Results for Physical Properties, Weather-resistive Considerations, Transverse Load Tests, and Accelerated Weathering were completed in accordance with ICC-ES AC90: Acceptance Criteria for Fiber Cement Siding Used as Exterior Wall Siding, Type A, Grade IV.
Signed: Signed:
Steven Mueller Brad Grzybowski
Laboratory Technician Managing Director
Date: January 24, 2011 Date: January 24, 2011
Report Issue History:
Issue # Date Pages Revision Description (if applicable)
Original 11/01/2010 6 NA Revision1 01/24/2011 6 Include Transverse Load Tests results; editorial revisions
Rieder Faserbeton-Elemente GmbH ICC-ES AC90 for Fibre C Page 5 of 6
RFE-002-02-01 PRI-CMT Accreditations: IAS TL-189; Miami-Dade 06-1116.02; State of Florida TST 5878; CRRC The test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in full without the written approval of this laboratory. PRI Construction Materials Technologies, LLC. assumes no responsibility nor makes a performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies, LLC. 6408 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail [email protected] WebSite: http://www.pricmt.com
APPENDIX
Photographs
Accelerated Weathering
After Heat Rain, 25 Cycles
Rieder Faserbeton-Elemente GmbH ICC-ES AC90 for Fibre C Page 6 of 6
RFE-002-02-01 PRI-CMT Accreditations: IAS TL-189; Miami-Dade 06-1116.02; State of Florida TST 5878; CRRC The test results, opinions, or interpretations are based on the material supplied by the client. This report is for the exclusive use of stated client. No reproduction or facsimile in any form can be made without the client's permission. This report shall not be reproduced except in full without the written approval of this laboratory. PRI Construction Materials Technologies, LLC. assumes no responsibility nor makes a performance or warranty statement for this material or products and processes containing this material in connection with this report.
PRI Construction Materials Technologies, LLC. 6408 Badger Drive Tampa, FL 33610 Tel: 813-621-5777 Fax: 813-621-5840 e-mail [email protected] WebSite: http://www.pricmt.com
Data and Uncertainty Analysis
END OF REPORT
Replicate Measurement 1 2 3 4 5 Avg SD 95% CI
ASTM C 1186
Flexural Strength, psi
Wet
MD 3604 4382 3567 3595 3983 3826 354.79 440.53
CMD 3552 2757 4036 3276 3508 3426 464.96 577.33
Equilibrium
MD 4180 3604 4316 3946 3960 4001 270.92 336.39
CMD 3683 3789 3262 4177 3094 3601 431.80 536.15
Density, pcf 204
Nominal
Length, in 94.0 94.0 94.0
Width, in 48.125 48.125 48.125
Nominal Thickness, in
Edge 1 0.52 0.51 0.51 0.52 0.52 0.01 0.01
Edge 2 0.52 0.49 0.52 0.52 0.51 0.02 0.02
Squareness tolerance, in/ft <1/32 <1/32 <1/32
Edge straightness, in/ft <1/32 <1/32 <1/32
ASTM D 1186: Supplementary
Moisture movement, % 0.013 0.017
Water absorption, % 3 3.6 3.5 3.4 3.5 3.4 0.23 0.29
Water Tightness
Moisture Content, % 1.2 1.1 1.3 1.3 1.3 1.24 0.09 0.11
Freeze thaw resistance
Flex, freeze thaw, psi
MD 3872 3612 4008 3666 4200 3872 242.96 301.67
CMD 3037 3667 3860 2796 3144 3301 446.04 553.83
Warm Water Resistance
Flex, sated Control, psi
MD 3604 4382 3567 3595 3983 3826 354.79 440.53
CMD 3552 2757 4036 3276 3508 3426 464.96 577.33
Flex soaked, psi
MD 3156 2930 2868 2514 2732 2840 238.05 295.58
CMD 2928 2829 3047 2913 3168 2977 132.08 164.00
Heat/Rain Resistance Pass
AC90 Adnl Requirements
Minimum Thickness 0.51
Accelerated Weathering Pass
UNCONTROLLED ELECTRONIC COPY
ASTM E 84 Surface Burning Characteristicsof "Fibre C"
A Report To: Sound Solutions
389 Deerhurst Drive
Brampton, Ontario
L6T 5K3
Phone: 416-740-0303
E-mail: [email protected]
Attention: Andrew Rogers
Submitted by: Exova Warringtonfire North America
Report No. 13-002-079
4 Pages
Date: February 21, 2013
ASTM E 84 Testing of "Fibre C" Page 2 of 4
For: Sound Solutions Report No. 13-002-079
ACCREDITATION To ISO/IEC 17025 for a defined Scope of Testing by the International Accreditation Service
SPECIFICATIONS OF ORDER
Determine the Flame Spread and Smoke Developed Indices based upon a single test conducted in
accordance with ASTM E 84-12c, as per Exova Warringtonfire North America Quotation No. 13-002-154,143
accepted January 28, 2013.
SAMPLE IDENTIFICATION (Exova sample identification number 13-002-S0079)
Extruded concrete panels with fiberglass reinforcement; 13 mm thick, identified as:
"Fibre C"
TEST PROCEDURE
The method, designated as ASTM E 84-12c "Standard Method of Test for Surface Burning Characteristics of
Building Materials", is designed to determine the relative surface burning characteristics of materials under
specific test conditions. Results are expressed in terms of Flame Spread Index (FSI) and Smoke Developed (SD).
Although the procedure is applicable to materials, products and assemblies used in building construction for
development of comparative surface spread of flame data, the test results may not reflect the relative surface
burning characteristics of tested materials under all building fire conditions.
SAMPLE PREPARATION
The test sample consisted of 3 sections of material, each approximately 0.5 inch (13 mm) in total thickness by
21 inches (533 mm) in width by 96 inches (2438 mm) in length. The sections were butted together to form the
requisite specimen length. Prior to testing, the sample was conditioned to constant weight at a temperature
of 73 ± 5°F (23 ± 3°C) and a relative humidity of 50 ± 5%. During testing the sample was self-supporting.
The testing was performed on: 2013-02-13
SUMMARY OF TEST PROCEDURE
The tunnel is preheated to 150 ± 5°F (66 ± 2.8°C), as measured by the floor-embedded thermocouple located
23.25 feet (7087 mm) downstream of the burner ports, and allowed to cool to 105 ± 5°F (40.5 ± 2.8°C), as
measured by the floor-embedded thermocouple located 13 feet (3962 mm) from the burners. At this time the
tunnel lid is raised and the test sample is placed along the ledges of the tunnel so as to form a continuous
ceiling 24 feet (7315 mm) long, 12 inches (305 mm) above the floor. Three 8 foot (2438 mm) sections of
0.25 inch (6 mm) cement board are then placed on the back side of the sample end-to-end, to protect the
tunnel lid, and the lid is then lowered into place.
Exo
va
ASTM E 84 Testing of "Fibre C" Page 3 of 4
For: Sound Solutions Report No. 13-002-079
SUMMARY OF TEST PROCEDURE (continued)
Upon ignition of the gas burners, the flame spread distance is observed and recorded every second. Flame
spread distance versus time is plotted. Calculations ignore all flame front recessions and Flame Spread
Index (FSI) is determined by calculating the total area under the curve for the test sample. If the area under the
curve (A) is less than or equal to 97.5 min·ft, then FSI = 0.515·A; if greater, FSI = 4900/(195-A). FSI is then
rounded to the nearest multiple of 5.
Smoke Developed (SD) is determined by dividing the total area under the obscuration curve by that of red oak,
and multiplying by 100. SD is then rounded to the nearest multiple of 5 if less than 200. SD values over 200
are rounded to the nearest multiple of 50. Section 5.1.9.1 of ASTM E 84-12c specifies a single combination of
lamp and photocell to create the requisite optical system. It is anticipated that alternative, equivalent systems
will be permitted in future revisions of the test standard. In May 2012, the Exova tunnel was modified to
include a specially-designed optical measurement system that is utilized by many other tunnel systems
worldwide. Although an improvement to performance and reliability is realized, as of this date the new system
is not specifically recognized by ASTM E 84 so this represents a deviation to the test protocol.
TEST RESULTS
Flame Spread Smoke
SAMPLE Index (FSI) Developed (SD)
"Fibre C" 0 0
Observations of Burning Characteristics
- The sample did not ignite. Spalling and discolouration of the surface was observed.
Authorities having jurisdiction usually refer to these categories:
Flame-Spread Index Smoke Development
Class 1 or A 0 - 25 450 Maximum
Class 2 or B 26 - 75 450 Maximum
Class 3 or C 76 - 200 450 Maximum
Note: This is an electronic copy of the report. Signatures are on file with the original report.
Robert A. Carleton, Ian Smith,
Technologist. Technical Manager.
Note: This report and service are covered under Exova Canada Inc. Standard Terms and Conditions of Contract which
may be found on the Exova website (www.exova.com), or by calling 1-866-263-9268.
Exo
va
ASTM E 84 Testing of "Fibre C" Page 4 of 4
For: Sound Solutions Report No. 13-002-079
FLAME SPREAD INDEX
SMOKE DEVELOPED
Flame Spread SmokeIndex (FSI) Developed (SD)
0 0
0 60 120 180 240 300 360 420 480 540 600
0
2
4
6
8
10
12
14
16
18
20
Time in Seconds
Fla
me S
pre
ad in F
eet
RED OAK (FSC=100)
SAMPLE
"Fibre C"
0 60 120 180 240 300 360 420 480 540 600
0
10
20
30
40
50
60
70
80
90
100
Time in Seconds
% L
igh
t A
bso
rptio
n
RED OAK (SD=100)
SAMPLE
"Fibre C"
E xo
va
UNCONTROLLED ELECTRONIC COPY
ASTM E 84 Surface Burning Characteristicsof "Fibre C"
A Report To: Sound Solutions
389 Deerhurst Drive
Brampton, Ontario
L6T 5K3
Phone: 416-740-0303
E-mail: [email protected]
Attention: Andrew Rogers
Submitted by: Exova Warringtonfire North America
Report No. 13-002-079
4 Pages
Date: February 21, 2013
ASTM E 84 Testing of "Fibre C" Page 2 of 4
For: Sound Solutions Report No. 13-002-079
ACCREDITATION To ISO/IEC 17025 for a defined Scope of Testing by the International Accreditation Service
SPECIFICATIONS OF ORDER
Determine the Flame Spread and Smoke Developed Indices based upon a single test conducted in
accordance with ASTM E 84-12c, as per Exova Warringtonfire North America Quotation No. 13-002-154,143
accepted January 28, 2013.
SAMPLE IDENTIFICATION (Exova sample identification number 13-002-S0079)
Extruded concrete panels with fiberglass reinforcement; 13 mm thick, identified as:
"Fibre C"
TEST PROCEDURE
The method, designated as ASTM E 84-12c "Standard Method of Test for Surface Burning Characteristics of
Building Materials", is designed to determine the relative surface burning characteristics of materials under
specific test conditions. Results are expressed in terms of Flame Spread Index (FSI) and Smoke Developed (SD).
Although the procedure is applicable to materials, products and assemblies used in building construction for
development of comparative surface spread of flame data, the test results may not reflect the relative surface
burning characteristics of tested materials under all building fire conditions.
SAMPLE PREPARATION
The test sample consisted of 3 sections of material, each approximately 0.5 inch (13 mm) in total thickness by
21 inches (533 mm) in width by 96 inches (2438 mm) in length. The sections were butted together to form the
requisite specimen length. Prior to testing, the sample was conditioned to constant weight at a temperature
of 73 ± 5°F (23 ± 3°C) and a relative humidity of 50 ± 5%. During testing the sample was self-supporting.
The testing was performed on: 2013-02-13
SUMMARY OF TEST PROCEDURE
The tunnel is preheated to 150 ± 5°F (66 ± 2.8°C), as measured by the floor-embedded thermocouple located
23.25 feet (7087 mm) downstream of the burner ports, and allowed to cool to 105 ± 5°F (40.5 ± 2.8°C), as
measured by the floor-embedded thermocouple located 13 feet (3962 mm) from the burners. At this time the
tunnel lid is raised and the test sample is placed along the ledges of the tunnel so as to form a continuous
ceiling 24 feet (7315 mm) long, 12 inches (305 mm) above the floor. Three 8 foot (2438 mm) sections of
0.25 inch (6 mm) cement board are then placed on the back side of the sample end-to-end, to protect the
tunnel lid, and the lid is then lowered into place.
Exo
va
ASTM E 84 Testing of "Fibre C" Page 3 of 4
For: Sound Solutions Report No. 13-002-079
SUMMARY OF TEST PROCEDURE (continued)
Upon ignition of the gas burners, the flame spread distance is observed and recorded every second. Flame
spread distance versus time is plotted. Calculations ignore all flame front recessions and Flame Spread
Index (FSI) is determined by calculating the total area under the curve for the test sample. If the area under the
curve (A) is less than or equal to 97.5 min·ft, then FSI = 0.515·A; if greater, FSI = 4900/(195-A). FSI is then
rounded to the nearest multiple of 5.
Smoke Developed (SD) is determined by dividing the total area under the obscuration curve by that of red oak,
and multiplying by 100. SD is then rounded to the nearest multiple of 5 if less than 200. SD values over 200
are rounded to the nearest multiple of 50. Section 5.1.9.1 of ASTM E 84-12c specifies a single combination of
lamp and photocell to create the requisite optical system. It is anticipated that alternative, equivalent systems
will be permitted in future revisions of the test standard. In May 2012, the Exova tunnel was modified to
include a specially-designed optical measurement system that is utilized by many other tunnel systems
worldwide. Although an improvement to performance and reliability is realized, as of this date the new system
is not specifically recognized by ASTM E 84 so this represents a deviation to the test protocol.
TEST RESULTS
Flame Spread Smoke
SAMPLE Index (FSI) Developed (SD)
"Fibre C" 0 0
Observations of Burning Characteristics
- The sample did not ignite. Spalling and discolouration of the surface was observed.
Authorities having jurisdiction usually refer to these categories:
Flame-Spread Index Smoke Development
Class 1 or A 0 - 25 450 Maximum
Class 2 or B 26 - 75 450 Maximum
Class 3 or C 76 - 200 450 Maximum
Note: This is an electronic copy of the report. Signatures are on file with the original report.
Robert A. Carleton, Ian Smith,
Technologist. Technical Manager.
Note: This report and service are covered under Exova Canada Inc. Standard Terms and Conditions of Contract which
may be found on the Exova website (www.exova.com), or by calling 1-866-263-9268.
Exo
va
ASTM E 84 Testing of "Fibre C" Page 4 of 4
For: Sound Solutions Report No. 13-002-079
FLAME SPREAD INDEX
SMOKE DEVELOPED
Flame Spread SmokeIndex (FSI) Developed (SD)
0 0
0 60 120 180 240 300 360 420 480 540 600
0
2
4
6
8
10
12
14
16
18
20
Time in Seconds
Fla
me S
pre
ad in F
eet
RED OAK (FSC=100)
SAMPLE
"Fibre C"
0 60 120 180 240 300 360 420 480 540 600
0
10
20
30
40
50
60
70
80
90
100
Time in Seconds
% L
igh
t A
bso
rptio
n
RED OAK (SD=100)
SAMPLE
"Fibre C"
E xo
va