LampMaximizer® Technology
LampMaximizer® TechnologyWhat is LampMaximizer® Technology?
• Patent pending sensor intelligence that enables users to aggressively target energy savings while still protecting lamp life
• Three feature sets: LampMaximizer, LampMaximizer+ , and Lamp Statistics
LampMaximizer (basic feature set, includes two timers, both user adjustable via push-button)
1. Minimum On Timer (15 min default) – preserves lamp life by eliminating all lamp cycles shorter than lamp manufacturers recommendations.
2. Standard occupancy time delay (10 min default) – lower time delay increases energy savings
LampMaximizer+ (disabled by default)
Advanced operational mode that optimizes lamp life & energy savings
Lamp StatisticsSensor maintains statistics on lamp on time and number of cycles
• Occupied Time: 10 Minutes
• Occupancy Sensor Time Delay:— Typical Sensor Brands: 20 min (default)— Sensor Switch: 10 min (default)
• Total On Time of Lamps:— Typical Sensor Brands: 30 min— Sensor Switch: 20 min
• Minimum On Timer: ― 15 min (however doesn’t effect total on time in this
case)
Extra 33% Savings!
LampMaximizer® TechnologyExample 1: Comparison On Times – Sensor Switch vs. Competition
Example 1
• Occupied Time: 2 Minutes
• Occupancy Sensor Time Delay:
— Typical Sensor Brands: 20 min— Sensor Switch: 10 min
• Minimum On Timer: ― 15 min (in this case it holds lights on
for additional 3 min)
Extra 32% Savings!
LampMaximizer® TechnologyExample 2: Comparison On Times – Sensor Switch vs. Competition
Example 2
• While all brand sensors meet lamp manufactures recommended on times, only Sensor Switch units do so without wasting potential energy savings
• Only Sensor Switch trusts its detection technologies to utilize a 10 min occupancy time delay without the risk of increasing false offs
• LampMaximizer eliminates potential short-cycling caused by confusing “adaptive” or “walk-through” modes, and false off/ons
Conclusions…
LampMaximizer® TechnologyCompetitive Conclusions
Overall savings as high as 40% vs. competition!
Occupied Time
Other Brands Sensor Switch % Extra Energy Savings
Default Time Delay Total Time On
Default Occ. Time Delay
Added Delay to Meet Minimum On Timer Total Time On
1 20 21 10 4 15 28.6%2 20 22 10 3 15 31.8%3 20 23 10 2 15 34.8%4 20 24 10 1 15 37.5%5 20 25 10 0 15 40.0%6 20 26 10 0 16 38.5%7 20 27 10 0 17 37.0%8 20 28 10 0 18 35.7%9 20 29 10 0 19 34.5%
10 20 30 10 0 20 33.3%11 20 31 10 0 21 32.3%12 20 32 10 0 22 31.3%13 20 33 10 0 23 30.3%14 20 34 10 0 24 29.4%15 20 35 10 0 25 28.6%16 20 36 10 0 26 27.8%17 20 37 10 0 27 27.0%18 20 38 10 0 28 26.3%19 20 39 10 0 29 25.6%20 20 40 10 0 30 25.0%21 20 41 10 0 31 24.4%22 20 42 10 0 32 23.8%23 20 43 10 0 33 23.3%24 20 44 10 0 34 22.7%25 20 45 10 0 35 22.2%
LampMaximizer® TechnologyChart of Extra Savings with Minimum on Timer
• Mode where the sensor will automatically adjust the occupancy time delay up or down relative to the observed usage of the space in which it is installed
• The adjustments are based on an algorithm that optimizes both lamp life and energy savings
• A shorter, more energy saving time delay will be utilized only if new time delay will not adversely affect lamp life
• Disabled by default
LampMaximizer® TechnologyWhat is LampMaximizer+ Mode?
• Sensor maintains several running “scores” of lamp life based upon how several time delays would control the lights if selected
• Scoring algorithm calculates effect on lamp life of cycling a lamp on/off vs. letting it run longer
• Every two weeks the time delay with the “winning” lamp life score is selected as the active time delay
• Default algorithm weighting based on published lamp life curves for Program Start Ballasts
• An advanced “pro-level” setting called the “Energy/Lamp Life Factor” can be adjusted to change scoring of lamp cycles vs. run time.
• Initial/max/min time delays also user configurable via settings “pro-level”
LampMaximizer® Technology (behind the scenes)How’s does the LampMaximizer+ Algorithm work?
Energy/Lamp Life Factor
• Works equally well in high-activity areas as well as those of limited use
• To prevent big changes in occupancy behavior from effecting time delay too quickly, a weighted average of new observed data vs. previous data is utilized
• LampMaximizer+ “Scores” can be reset by user
LampMaximizer® TechnologyAdditional LampMaximizer+ Features
• Sensor maintains statistics on sensor/lamp usage
• Total number of On Cycles (two digit number blinked out in 1000s)
• Total Lamp Run Time (two digit number blinked out = number of khrs)
• Lamp Statistics can be reset at any time by user via push-button
Lamp StatisticsTotal Switches & Total Time On
Product Matrix of FeaturesLampMaximizer Feature Sets
Test Mode LampMaximizer (Minimum On Timer)
LampMaximizer+ Mode*
Lamp Statistics*
All WSDs (disabled as default)
CM(R) (enabled as default)
(disabled as default)
RM(R) (enabled as default)
(disabled as default)
CM(R)B (enabled as default)
(disabled as default)
WV (enabled as default)
(disabled as default)
HW (enabled as default)
(disabled as default)
SFR (enabled as default)
SB(R) (enabled as default)
(disabled as default)
* LampMaximizer+ and Lamp Statistic Feature Sets not available on 2-Pole and –ADC versions