lantern hotel

106
Bachelor of Science (Honours) (Architecture) Building Science 2 [ARC 3413] Project 1: Lighting & Acoustic PerformanceEvaluation&Design by team: Amelia Michelle Bernard Fam Li Kian Kian Soon Jean Leong Carmen Tan Heng Yee [0310316] [0310639] [0314978] [0314953] [0314941] Tutor: Mr. Rizal

Upload: jean-kian

Post on 08-Sep-2015

122 views

Category:

Documents


6 download

DESCRIPTION

Building Science

TRANSCRIPT

  • Bachelor of Science (Honours) (Architecture)

    Building Science 2 [ARC 3413]

    Project 1: Lighting & Acoustic PerformanceEvaluation&Design

    by team:

    Amelia Michelle Bernard

    Fam Li Kian

    Kian Soon Jean

    Leong Carmen

    Tan Heng Yee

    [0310316]

    [0310639]

    [0314978]

    [0314953]

    [0314941]

    Tutor: Mr. Rizal

  • TABLE OF CONTENT

    1.0 Introduction 1.11.2

    Aim and Objective

    Site Study

    1.2.11.2.21.2.3

    Methodology

    Introduction

    Selection Criteria

    Architectural Drawings

    2.02.1Lighting

    3.1

    3.3.2 Atrium - Daylight Factor Calculation

    - Lumen Method

    - Room Index Calculation

    3.3.3 Corridor - Daylight Factor Calculation

    - Lumen Method

    - Room Index Calculation

    3.3.4 Room - Daylight Factor Calculation

    - Lumen Method

    - Room Index Calculation

    3.3.5 Staircase - Daylight Factor Calculation

    - Lumen Method

    - Room Index Calculation

    Sequence of Working

    3.0Precedent Study

    3.1.13.1.23.1.33.1.4

    Introduction

    Lobby Lighting

    Lounge

    Courtyard and Faade

    3.2 Site Study 3.2.13.2.23.2.33.2.43.2.5

    Zoning of Spaces

    Spatial Quality of Light Natural Lighting

    Spatial Quality of Light Artificial Lighting

    Tabulation of Data

    Interpretation of Data

    3.3 Lighting Analysis 3.3.1 Reception - Daylight Factor Calculation

    - Lumen Method

    - Room Index Calculation

    4.0 Acoustic 4.1 Precedent Studies

    4.1.14.1.24.1.34.1.4

    Introduction

    Room Acoustics

    Sound Insulation & Selection of Surface Materials

    Background Noise

    4.2 Site Acoustics 4.2.14.2.24.2.34.2.44.2.54.2.6

    Data Tabulation

    Data Tabulation Analysis

    Outdoor Noise Sources

    Indoor Noise Sources Equipment Location

    Equipment Specification

    5

    6

    7

    8

    12

    14

    16

    24

    28

    32

    33

    36

    39

    42

    44

    48

    52

    56

    61

    65

    66

    66

    69

    70

    74

    78

    79

    86

    87

  • 4.3 Acoustic Analysis 4.3.1 Reverberation Time

    - Zone A: Reception Area + Atrium + Corridor

    - Zone B-Room with Glass box

    - Analysis

    Sound Presseure Level

    - Zone 1; Reception Area

    - Zone 2; Atrium

    - Zone 3;Corridor

    - Zone 4; Rooms

    - Analysis

    Sound Reduction Index

    - Analysis

    4.3.2

    4.3.3

    5.0 Bibliography

    88

    90

    91

    93

    94

    95

    96

    98

    100

    104

    105

  • Abstract

    This report contains the details of the study conducted on Lantern Hotel, Petaling

    Street with regards to the lighting and acoustical performances. The report is broken down

    into two major segments Lighting followed by Acoustics. Included are the technical data

    such as formulas, equations and calculations that estimate both illuminance levels and

    noise levels for light and acoustics respectively. Architectural drawings are provided by

    the ZLG Design for reference whereas data included in the report are data collected from

    measurement done on site. Pictures are taken on site, figures are made with Adobe

    Photoshop, and analysis diagrams were made with Autodesk Ecotect. A list of references

    are provided at the end of the report.

    4

  • 1.0 INTRODUCTION

    1.1 Aim and Objective

    The aim and objective of conducting this study is to understand and explore on day

    lighting, artificial lighting requirement and performances, acoustic performances and

    requirement of a certain space. In order to analyse and report the quality of the

    lighting and acoustic of the space, the characteristics and function of day lighting,

    artificial lighting and acoustic of the intended space has to be determined.

    Understanding of the surrounding of site plays a vital role for this report and analysis.

    5

  • 1.2 Site Study

    1.2.1 Introduction of Site

    Lantern Hotel is a budget boutique hotel located in a shoplot at the heart of the

    busy Petaling Street. It is located at the second, third and fourth floor of the shop, above

    an existing bank. The shop is stylishly renovated, with an industrial-meets-tropical design

    touch. The hotel consist of 49 rooms and houses mostly foreign tourists as the essence

    of the Chinatown can be experienced at the hotel the sound of the people, smell of

    food and the lights of the lanterns can be heard, smelled, and seen from the hotel.

    6

  • 1.2.2 Selection Criteria

    The location of the hotel at the centre of the busy Petaling Street makes it

    interesting to study its acoustic performances for this project. The sound of the people

    at the street, cooking from the hawker centre behind the hotel, and the vehicles from the

    roads nearby contributes to the sound in the hotel. It is a challenge to design the hotel

    with good acoustic performance in order to provide a comfortable environment for the

    guests to stay in.

    The hotel is designed with a fair amount of daylight entering the space. This is

    done by having an atrium in the middle of the hotel with a skylight to allow penetration of

    daylight. The facades are wrapped with a layer of bricks laid in such a manner that there

    are pocket of holes which allow daylight to enter. The full length windows also aid in

    allowing daylight to enter the space. Designed as such, most parts of the hotel do not

    require artificial lighting on a bright day.

    The hotel consist of a variety of functional spaces to analyse its lighting

    functionality. This includes the entrance which plays an important role to attract

    customers, reception for the receptionist to work at, and the rooms are to have sufficient

    lighting for the comfort of guests.

    7

  • 1.2.3 Architectural Drawings

    Second Floor Plan

    8

  • Third Floor Plan

    9

  • Elevation

    10

  • Section

    11

  • 2.0 METHODOLOGY

    2.1 Sequence of Working

    Precedent Studies

    Took documentation and study research paper that consisted lighting and acoustic study

    similar to the hotel case study that we choose. Read through and identified the important

    criteria of lighting design in difference spaces that consisted in hotel, for example :

    lobby ,corridor ,rooms and entrance. See how evaluation and critique are given to the

    existing lighting design.

    Drawings Preparation

    Most of the plans, section and elevation drawings are provided by the architect of the

    building ,ZLG Design some drawings are drawn by ourselves. Grid lines with 1meter apart

    were then applied for the later data collecting and recording purposes.

    12

    Figure 2 Lutron digital lux meter LX-101Figure 1 01dB digital sound meter

    Figure 2.1a Plan showing data collection points

  • Site visit

    For the three floor Lantern Hotel (located above a two floor Hong Leong Bank),we decided

    to collecting data only for the 2nd floor and 4th floor as 2nd floor is the main spaces with

    reception and balcony. The spatial arrangement of 3rd floor is similar to 4th floor ,therefore

    we study this floor as there are rooms with glass box and is nearer to the skylight.

    Recording data

    Data Collection for lighting was conducted using te Lux Meter. Reading were taken at

    1meter intervals at a position of 1meter and 1.5meter height. Since most of the rooms

    layout are the same,we picked two rooms for each floor to collecting data .The respective

    rooms are room without window and room with lanai located at 2nd floor ,room with glass

    box and room without glass box located at 4th floor level.The materiality of each

    components of the spaces was also recorded

    Tabulation of data and diagramming

    Light and sound contour diagram were established to understand the concentration of

    noise and lightings for different zone using Ecotect 2011.

    13

    Calculations

    For lighting analysis, we are using formula :

    Daylight Factor =

    100%

    Room Index RI = ( )

    (+)

    Illuminance level =

    For Acoutic analysis ,we are using formula:

    Reverberation Time =0.16

    Sound Intensity Level = log10(/0)

  • 3.0 LIGHTING

    3.1 Ligthing Precedent Study

    3.1.1 Introduction

    Hotel and Conference Center in Virginia, USA

    Building Name

    Location

    Occupancy Type

    Size

    Number of Stories

    Dates of Construction

    Cost

    : Hotel and Conference Site

    : Virginia, USA

    : Mixed Use Hotel (R-1) and Conference (A-3)

    : 174,000 SF

    : 7 + 1 below grade

    : Fall 2008 - Summer 2010

    : $50 million

    The recently opened Hotel and Conference Center, on the outskirts of one of the

    countrys most respected universities, embodies the notions of comfort and relaxation

    with professionalism and academic success. The Hotel and Conference Center provides

    a luxurious and warm atmosphere to all patrons, whether residing in the hotel or merely

    attending a business or private event in the conference center. Although the exterior

    faade of the facility does not boast any discrepancies from the architecture of the

    university, the handsome interior spaces display the epitome of bringing the campus

    landscape indoors. Rich colors and woodwork dominate each of the spaces alike,

    reminding one of the outdoors and the campus setting which provided inspiration to the

    interior dcor. The elegant inn houses 148 guest rooms, a lounge and bar area, a

    restaurant, ballroom, 24-hour fitness facility, and various meeting rooms in the conference

    center. Hotel guests not only become immersed in the sophisticated atmosphere, but are

    reminded of the spirit and vivacity of the university when visiting.

    14

  • Plan and Zoning

    15

  • 3.1.2 LOBBYDescription :

    Upon arrival at the Hotel and Conference Center, the Main Lobby serves as a particularly

    important space for guests and staff. Guests enter the main lobby through the vestibule

    and make their way to the front desk and check-in area. There are also seating areas

    throughout the main lobby, providing relaxation for guests and serving as waiting areas.

    These seating nooks are ideal for those waiting to enter either the Restaurant or Lounge.

    Floor to ceiling windows provide daylight into the space during the day. The lobby is filled

    with rich colors and finishes, complimenting the relaxing atmosphere.

    Activities | Tasks:

    - Check in at the front desk

    - VDTs at the front desk for employees

    - Lounging areas for guests

    - Reading

    - Socializing

    - Waiting for entrance to the Restaurant or Lounge

    16

  • Materials Used

    17

  • Furnishing

    Lavish furniture and finishes are abundant in the lobby. Wooden and tile built-in display

    cases separate the lobby into larger areas : a Lounge waiting area, Restaurant waiting

    area, Vestibule area, Check-in and Reception Desk Area, and a transition zone to the

    Conference Center corridor with the Elevator Lobby off to the west. The shelving units

    also give an interesting 3-dimensional view of the different areas in the lobby and make

    the seating arrangements more private and relaxing. Neutral colors, such as deep browns

    , taupe, and burgundy are often used, complimenting the wood and porcelain tile finishes.

    18

  • Architectural Features

    The display cases described above are definitely and important architectural feature of

    the lobby. But even more important are the way the Hotel and Conference Center decided

    to help orient and guide the guests throughout the building : through the use of branding

    walls that display important signage. There are four such branding walls in the lobby (note

    : only three are shown to conceal the Owners identity).

    As you step into the Hotel and Conference Center from the vestibule, the branding wall

    directly across from the entrance is an entry feature, displaying the name of the hotel.

    There is both an opaque and translucent graphic present on the wall with aluminium

    letters. The translucent graphic is backlit (note : not shown).

    At the Reception Desk, there is also a branding wall present. This display is an illuminated

    graphic wall with a bronze finish operable glass door frame. The display is tempered

    glass with a translucent digital vinyl applied to the second surface. The actual image on

    display is of a path through Virginia woods and is also backlit.

    19

  • Lighting Layout and Equipment

    The lighting for the lobby is very sophisticated and detailed. While recessed downlights

    provide ambient light, four large ceiling coves with accent lights give emphasis to the

    height of the space and further enhance the wooden millwork and porcelain tile finishes.

    LED striplights underneath the reception desk counter and in the display cases draw the

    eyes horizontally. Decorative pendants in the elevator lobby offer an interesting dimension

    to the smaller space. Backlit and cove-lit branding walls help orient guests throughout the

    main floor of the hotel. The majority of the lamps in the lobby are halogen, although

    fluorescent, metal halide and LED are prominent as well. The lighting in the lobby not only

    augments the rich colours and dcor present in the lobby, but becomes a centrepiece

    itself with its many applications into the architecture.

    20

  • Lobby Lighting Design Consideration and Criteria

    1) Psychological Aspect :The Lobby is the space where guests develop their initial impression of the hotel.

    Therefore, the lobby should create a warm and welcoming atmosphere. The Lobby should

    also be relaxing for all of theguests, as they may be waiting to go into the Restaurant or

    Lounge.

    2) Appearance of Space and Luminaires :Because the Lobby sets the tone for the rest of the Hotel and Conference Center, an

    inviting ambiance is wanted. The lighting design should complement the wood millwork

    and rich finishes and colors in the Lobby. Luminaire selections in the Lobby contribute to

    maintaining a welcoming and relaxing atmosphere.

    3) Color Appearance and Color Contrast :The gold, taupe, chocolate brown, and off-white hues in the Lobby should be enhanced

    by warm light. Lamps with warmer CCTs ought to be used to stimulate a relaxing

    atmosphere by keeping light levels low and enhancing the richer colors. Since the Lobby

    has distinct seating areas for guests, color appearance is important for reading.

    4) Reflected Glare :Because of the glossy surfaces of the reception desk and some of the table tops in the

    reading areas, reflected glare could be a potential risk for guests. Transactions between

    the receptionists and guests at the main desk involve money and paperwork and reflected

    disability glare would be a distraction.Guests reading in the waiting areas would also

    experience glare on the tables.

    5) Modeling of Faces or Objects :

    At the front desk, visual appearance of the receptionist and guests is imperative for

    transactions to take place. In general, the light levels at the main desk will be higher than

    the rest of the Lobby. Lamps with high CRIs (greater than 80) will generate warm skin

    tones much more naturally and should be utilized. Having the receptionist at the front

    desk appear welcoming and friendly will in turn create happier guests staying at the

    Hotel and Conference Center.

    21

  • 6) Daylighting Integration and Control :Floor to ceiling glazing on the east faade of the Lobby provides the space with plenty of

    daylight

    during the day in the summer months. However, in the winter, the sun will not shine

    directly into the windows and the building may even lose heat during this time. Integrating

    a dimming system in the Lobby would be ideal as to provide energy savings during

    daylight hours. Having lower light levels during the evening would help promote the

    relaxing and comforting atmosphere and mood of the space. When the hotel is open but

    not as active, a dimming system could be utilized to further decrease the light levels.

    7) Direct Glare :In a space with a relaxing atmosphere, decorative luminaires should not be the only

    sources of light as they may appear glary to guests reading and relaxing in the seating

    areas of the Lobby. Direct glare should be avoided at all costs as it will make guests feel

    tense and will distract them from the rest of the space. Direct glare in the entrance canopy

    should also be avoided as guests are entering from outside and their eyes need to adjust

    to the light levels inside.

    22

  • Lobby- Evaluation and Critique

    The lobby in the hotel and conference center definitely evokes a naturally warm and

    inviting environment for guests by generally keeping light on the peripherals and directly

    away from the occupants. Four coves in four distinct areas of the lobby give off ambient

    light and keep the light levels low on the floor. The backlit branding walls and cove lighting

    detail help orient and direct guests throughout the entire hotel by distinctly featuring the

    names of the areas. This also helps take light off the guests and onto accented features

    throughout the lobby, creating a relaxing atmosphere and drawing attention to the

    light/artwork. LED strips mounted on the reception desk and into the display case form

    linear bands of light, much like the cove lighting. Recessed halogen downlights create

    pools of light on the floor and also break up the linearity of the layout.

    Overall the layout seems efficient and pretty typical. Each area of the lobby has its own

    lighting, and they are very much linked and related to each other. Regularly spaced

    recessed accent lights and cove lighting create the natural areas of the room.

    Downlights are utilized over the main areas of the lobby, such as the reception desk and

    restaurant entrance, drawing guests attention to the more important areas of the hotel

    with high illuminances. The colour and texture of the pendansts in the elevator lobby

    mirror those in the rest of the space with its neutral colours and fine finish.

    The halogen lamps utilized produce a warmer feel in the lobby, adding to the tone of

    relaxation. The colour temperature is appropriate with the rest of the space. Warm white

    LEDs were even used to complement the warm colours of the halogen lamps. Warmer

    CCTs were definitely a consideration in the lighting design, as they had impact on the

    finished and colours in the lobby.

    23

  • 3.1.3 LOUNGE

    Description The Lounge in the Hotel and Conference Center is a more private space in the hotel for

    customers. It is a space separated from the rest of the hotel where guests can enjoy fine

    food and spirits at the bar during the late afternoon and evening hours. Situated on the

    northernmost part of the building, floor to ceiling glazing spans almost the entirety of the

    faade, allowing daylight into the space. Guests of the Hotel and Conference Center can

    enter the Lounge through the main lobby and corridor on the first floor. A set of double

    doors on the western wall provides access to the outdoor terrace.

    Activities | Tasks:

    Dining

    Drinking

    Socializing

    Bartenders/Servers

    Guests watching television or reading

    Materials used

    24

  • Floor Finish Plan + Furniture Plan

    Furnishing and Accessory

    Furniture in the space consists of various

    tables,chairs, and bookshelves. The two dozen arm chairs (LNG-401) and six circular

    tables (LNG-302) provide guests relaxing group seating areas for conversation. Fifteen

    bar stools (LNG-403) offer patrons seating around the centrally located bar (LNG-702) .

    There is even more seating on the northern part of the lounge, where two plush sofas

    (LNG-400) and for chairs (LNG-402) are situated near the floor to ceiling windows. Coffee

    tables (LNG-301) and shelving units (LNG-300) are also in this area of the lounge. Two

    televisions are set in the center of the bookshelves on the eastern and western wakks.

    There is also some artwork on a couple of the walls.

    Architectural Features On the eastern and western walls of the lounge, large bookcases span about 8-6 wide

    and the entire height of the space. The bookcases are made from medium density

    fibreboard and have diagonal-grid pattern with shelving openings. There is a larger

    opening in the center of each bookcase for a television. Sheer drapes hung from the

    ceiling in front of the glazing provide diffuse daylight in the space during the daytime.

    25

  • Lighting Layout and Equipment

    The lighting for the lounge is very decorative. Small decorative pendants at varying

    heights hang above the bar top. LED strips illuminate bottles on display in the bar display

    and are also utilized underneath the counters. Fluorescent cove lighting is implemented

    into the design, emphasizing the height of the space. Recessed accent lighting is used to

    draw attention to the art on the walls. For general lighting in the room, recessed

    downlights are employed. Most of the lamps are halogen and therefore are ideal for the

    dimming presets.

    26

  • Lounge Evaluation and Critique

    The lounge in the Hotel and Conference Center is a special purpose space geared

    towards making guests feel comfortable and relaxed. This relaxing theme sparks in the

    lobby and is carried into the lounge. Decorative pendants hang at random heights over

    the bar, making the bar a focal point in the room. Cove lighting on the ceiling gives the

    room more dimension as the ceiling pop out hangs in the air. Recessed accent lights in

    the ceiling give the space more sparkle.

    Rich colors and lush finishes are enhanced by the warm CCTs of the lamps. Careful

    thought of the color of the sources was analyzed and followed through, as warmer whites

    were typically selected. The layout of the luminaires over the bar are random and

    therefore do not need to coincide with the furniture. These pendants draw attention

    towards the bar and sparkle in the air.

    It is evident that through the use of light, a relaxing atmosphere is portrayed in the Lounge

    with the current design. Light stays on the peripherals of the space, highlighting the walls

    and ceiling alike. Decorative and more intricate facts were utilized in the Loung but do not

    distract from the mood.

    Light Loss Factors

    *Use of the new procedure to find LDD uxis used. As the new handbook does not address

    RSDD, it was not calculated below. According to the new handbook, a LEDs LLD is

    assumed to be 0.7. A 12 month cleaning interval and clean environment was assumed.

    Any other LLFs not displayed are assumed to be 1.0.

    27

  • 3.1.4 COURTYARD AND FACADE

    Description

    As guests arrive at the Hotel and Conference Center, they will drive through an exterior

    courtyard with a triangular shaped plaza. The faade of the Hotel and Conference Center

    is made up of brick two types of brick. The public spaces of the building on the first floor

    all have a more decorative brick with accent bands. Precast cornices break up the tower

    of the hotel into horizontal lines, accentuating the length of the building. Concrete panels

    beneath the 6-0 x 6-8 windows enhance the height of the hotel tower. Glazed aluminum

    window walls wrap around the first floor of the Hotel and Conference Center, allowing

    natural light into the public areas of the building.

    Activities | Tasks:

    - Hotel and Conference Center entrance and drop-off

    - Walking

    -Sitting outside

    Materials: Brick; precast decorative frames with metal; spandrel panels and screen walls; glazed

    aluminum window walls (double pane, clear, Low-E insulating glazing) with a transmissive

    value of 0.46; metal entry canopies.

    28

  • Lighting Layout and Equipments

    The exterior lighting is made up of multiple layers of light, such as bollards, step lights,

    ground and building mounted accent lighting, and landscape lighting. The hotel canopy

    are is lit with downlights at the entrance. Both the Hotel and Conference Center glow

    from within with light, making the public places more noticeable and welcoming to

    guests from the outside. A combination of LED, ceramic metal halide, and compact

    fluorescent lighting was used for the exterior spaces.

    29

  • 30

  • Facade Design Consideration and Criteria

    Physchological Aspect:

    When arriving at the Hotel and Conference Center, guests should feel welcomed

    as they approach the building. The faade and exterior courtyard should feel

    inviting and relaxing to guests.

    Safety :

    Guests need and want to feel safe and secure when staying at a hotel and

    lighting plays a critical role in this. Having the walkways and parking lots well lit at

    night will make guests feel safer about walking around outside. Lamps with good

    CRIs will enabled good colour appearance and modelling of others.

    Connection With Architecture :

    The lighting design on the faade should enhance the architecture of the

    building. The lighting should lead guests u to the front building. For example,

    highlighting the walking paths that lead up to the columns on the first floor.

    Having the Hotel and Conference Center glow from within on the first floor also

    give the building another dimension as people drive by..

    Horizontal Illuminance :

    Building exteriors

    -Entrances > Active : 5fc

    -Prominent Structures : 5fc

    Gardens

    -General Lighting : 5:1 ratio

    -Trees or shrubbery, emphasized :3fc

    Modelling Of Faces Or Objects : When guests are outside walking to and from their cars late at night, they should

    be able to make out other peoples facial features and the objects around them.

    This is so guests feel safe and comfortable while walking outside at night. The

    use of lamps with high CRIs will help achieves this.

    31

  • 3.2 Site Study 3.2.1 Zoning of Spaces

    Figure 3 Zoning of 2nd FLoor and 4th floor of Latern Hotel

    32

  • 3.2.2 Spatial Quality of Light Natural Lighting

    During the day, the central courtyard is lit up by daylight through the acrylic roof.

    Daylight at the courtyard also light up the corridors. The three facades are made out of

    brick laid in such a manner that daylight penetrates through the pockets of holes, this

    subsequently lights up the three corridors. Openable louvred windows are placed

    alternatively to allow penetration of daylight into the corridors. Hence, artificial lighting is

    not required during a bright day. The white interior walls allow natural light to be reflected.

    This increases the luminence of the wall and brighten up the corridors.

    33

  • Effect of Adjacent Roof to Intensity of Day Light

    Sun Light

    Due to the positioning of the hotel,

    sunlight can enter the space especially in

    the morning and evening. The intensity of

    sunlight is higher than daylight, hence,

    sunlight can increase the luminosity of the

    space.

    An existing roof over Petaling Street

    in front of the hotel affects penetration of the

    sunlight. It can be seen that the intensity of

    sunlight entering the 4th floor is higher than

    the 3rd floor.

    34

  • Design of Louvred Window

    The windows of the hotel is an interesting

    feature to control the amount of natural lighting

    that enters the space. This louvred window has

    fixed louvres at the bottom half of the window

    and adjustable louvres at the top half. The top

    half of the window can also be opened

    completely for maximum natural lighting.

    A quantitative data collection was done

    by measuring the Lux level of a Lanai without

    any artificial lighting at three different situations:

    Closed louvres

    Opened louvres

    Opened window

    35

  • 3.2.3 Spatial Quality of Light Artificial Lighting

    Entrance

    The entrance of the hotel is through the five foot way which leads to the staircase

    lobby and elevator. At the five foot way, a lantern canopy over the entrance door

    illuminates the space with red light to distinct the entrance of the hotel from the entrance

    of the bank at the ground floor. The staircase lobby and the staircase are lit by warm

    lighting. A small seating area is lit up by luminaire hidden between the furniture and the

    wall. This outlines the seating area making it stand out. On the brick wall behind the

    seating area are two wall-mounted downlights which enhances the texture of the wall.

    The stairwell is dimly lit with warm fluorescent light as a continuation of the seating area

    36

  • Reception

    The stairs eventually leads to the reception of the hotel which is brightly lighted up

    contrasting with the staircase and corridor which leads to it. This is to draw attention of

    the customers and at the same time, act as task lamps. Adjacent to the reception is the

    food and drink bar and a high table for customers to do work on with the same luminaires.

    The principal visual task of the receptionist are desk works including typing and writing

    whereas a bartender needs to clearly see the food and drinks. These task lamps are

    essential to help workers do their tasks efficiently. These task lamps are switched on even

    during a bright day. Specular reflection on the glossy black wall behind the high table

    causes glare which may be problematic for customers working at the area.

    37

  • Atrium

    During the night, the daylight at the courtyard will

    be replaced by warm fluorescent light placed at the centre

    of the beam which projects onto surrounding surface

    which is painted orange. The light is reflected on the

    orange surface creating a glow of orange light from the

    beam.

    The courtyard is also lit up with room number

    signages with uplight luminaires in it. These luminaires

    allow the room numbers to be seen in the dark and at the

    same time lights up the corridor in a rhythm.

    The tables at the courtyard for dining purposes are

    dimly lit. The indirect uplights and the soft orange glow

    from the beams along with the wooden flooring and tables

    creates a cosy and comfortable atmosphere for diners.

    38

  • 3.2.4 Tabulation of Data

    The colours used in the table correspond with their respective zone colour. The

    following readings were taken at a level of 1m and 1.5m from the ground as indicated.

    Day Time

    2nd Floor 4th Floor

    Figure 5 2nd Floor Day Time Light Data Figure 4 4th Floor Day Time Light Data

    39

  • Night Time

    2nd Floor 4th Floor

    Figure 7 2nd Floor Night Time Light Data Figure 6 4th Floor Night Time Light Data

    40

  • Based on the lighting data table above, the following observations were noted along

    with relevant discussions.

    Observation 1:

    Light data collected at 4th floor level is higher compare to data collected at 2nd floor.

    Discussion 1This is affected by the 3 floor height existing canopy roof structure of Petaling Street in

    front of Lantern Hotel as it provide shade to the 2nd floor . The natural lighting also blocked

    away by surrounding buildings to penetrate into 2nd floor especially the zone located near

    the south elevation

    Observation 2:

    For most of the zones, light data collected at level of 1.5m above ground are higher than

    the reading taken at 1m from the ground

    Discussion 2 :

    This is due to the proximity of the lux meter to the artificial light source. At 1.5m, the lux

    meter is closer to the artificial light source, thus receiving a higher amount of light.

    However, the large difference in readings only occurs in grids which have artificial

    lightings

    Observation 3:For corridor ,light data collected at level of 1 above ground are higher than the reading

    taken at 1.5m from the ground.

    Discussion 3:This is due to the surface mounted lighting along the corridor are located at 1.5m

    height .The corridor light are shielded with a close top metal box.Therefore , the light

    are controlled and directed to the floor and wall below 1.5m .

    41

  • 3.2.5 Interpretation of Data -Contour Diagram

    Natural Lighting

    2nd Floor 4th Floor

    From the contour diagram, the atrium at 4th floor received maximum 80% of natural

    lighting, however, the maximum natural lighting received at 2nd floor drop to 70% at a

    different of 10.8 meter height.

    For the rooms at both side of atrium at level 2 ,they receive a range of daylighting

    from 0- 30%. However, the room at level 4 receive a range of lighting from 20% - 70%.

    There is a great different between the daylighting level of these two floor.

    42

  • Artificial Lighting

    2nd Floor 4th Floor

    From the contour diagram , the maximum artificial lighting achieved is up to 840

    lux at the reception area. The lighting level of toilets achieved up to 600lux ,However ,the

    lighting level of corridor have relatively low lux level,150lux .From the result of light

    analysis ,we can conclude that the artificial lighting level varies according the hierarchy

    of space and type of activities carried out in the area.

    43

  • 3.3 Lighting Analysis

    3.3.1 Reception Area (B13- F14)

    Lighting Specification

    Material Specification

    Type Specification Luminaire Type

    Luminuous Flux per unit (lm)

    Incandescent Pendent Globe Light Bulb

    Watt Lamp Life: 8000 hr

    Downlight With top reflector

    400

    Main Surface Description Color Reflectance

    Ceiling White Plaster Ceiling White 85

    Wall Black Painted Wall Black 2-10

    White Painted Wall White 85

    Floor Light Walnut Timber Plank

    Brown 25

    Window Brown Timber Shutter Light Walnut

    25

    Furniture Marine Plywood Plank Table/Countertop

    44

  • Daylight Factor

    Table 1 Lux Reading at Reception Area

    Table 2 : Average Lux Value at Reception Area

    Table 3 : Daylight Intensity at different condition

    Time Weather Luminance At 1m (1x)

    Average (1x)

    Luminance at 1.5m (1x)

    Average ( 1x)

    12-3pm Cloudy 20-180 102.3 32- 274 177.9 6-8pm Raining 30-81 61.1 34-285 184.1

    Average lux Reading 12-3pm 6-8pm1m 102.3 61.1 1.5m 177.9 184.1 Average lux value 140.1 153.2

    Illuminance Example120,000lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entires clear blue

    sky, midday

    1,000 -2,000 lux Typical overcast day,midday

  • Discussion

    Table 1 Daylight Factor ,DF

    The average lux value during after 12pm-3pm is 280.2 lux ,whereas at night ,6pm-

    8pm, the average lux value is 153.2 lux. There is a great change in lux .

    According to table provided in MS1525 , the 1.4% DF of Reception Area is

    categorized under the average category. This is due to the 3 floor height existing canopy

    roof of Petaling Street right in front of the reception area .The opening of reception area

    are facing west ,therefore ,it only received maximum natural lighting during sunset ,while

    most of the day time hour ,the reception area will still need to lightened up using artificial

    lighting.

    DF , % Distribution>6 Very Bright with thermal & glare problem 3 6 Bright 1 3 Average 0 1 Dark

    46

  • Lumen Method

    47

    Location Reception Area Dimension , m L = 3.5 , W = 8 Area ,2 28 Height of ceiling , m 3.6 Height of work level, m 1.2 Type of light Incandescent Pendent Globe Light Bulb Luminous flux of lighting,F / lm

    400lm

    Height of luminaries , m 2.0 Height of Working Plane,m 1.0 Mounting Height , ,m 2.0-1.0=1.0 Number of existing light bulb/ n x N

    16

    Reflectance Value ,% Ceiling White Plaster Ceiling 40-45 Wall Black Painted Wall 2-10 Window Brown Timber Shutter

    Windows 25

    Floor Light Walnut Timber Plank 25 Room Index ( L x W )

    (L + W ) x H

    = (3.5 x8)( 3.5+8)x 3.6

    = 0.67 Utilization Factor / UF 0.5 Maintenance Factor / MF MF = LLMF x LSF x LMF x RSMF

    = 0.86 x 0.95 x 0.86 x 0.94 = 0.66

    Illuminance level required/E,lux

    E = n x F x UF x MFA

    = 16 x 400 x 0.5 x 0.66 28

    = 75

    Maximum Illuminance recommended by MS1525 (lux)

    300lux

    Number of Fitting Required ,N

    N=

    = 300 x 2816x400x0.5x0.66

    = 3.9 4 Incandescent Pendent Globe Light Bulb Needed to meet the standard illuminance required in reception area

  • 3.3.2 Atrium ( E3 E13)

    Lighting Specification

    Material Specification

    Type Specification Luminaire Type

    Placement Luminuous Flux per unit (lm)

    Fluorescent Light

    Watt Lamp Life: 8000 hr

    Indirect uplighter

    Mounted within Beam

    1350

    Twist CFL Lamp Life : 10,000 hr

    Open top reflector

    Room number signage

    900

    Main Surface Description Color Reflectance

    Skylight Acrylic Skylight Transparent 0

    Beam(ceiling) White Painted White 85

    Wall Concrete Block painted white

    White 85

    Floor Light Walnut Timber Plank

    Brown 25

    Furniture Marine Plywood Plank Table

    Brown 25

    48

  • Daylight Factor

    Table 1 Lux Reading at Reception Area

    Table 2 : Average Lux Value at Reception Area

    Table 3 : Daylight Intensity at different condition

    Time Weather Luminance At 1m (1x)

    Average (1x)

    Luminance at 1.5m (1x)

    Average ( 1x)

    12-3pm Cloudy 93-721 215.5 248-766 416 6-8pm Raining 9-30 15.5 14-53 23.3

    Average lux Reading 12-3pm 6-8pm 1m 215.5 15.5 1.5m 416 23.3 Average lux value 315.8 19.4

    Illuminance Example 120,000lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entires clear blue

    sky, midday

    1,000 -2,000 lux Typical overcast day,midday

  • Discussion

    Table 1 Daylight Factor ,DF

    The average lux value during 12pm-3pm is 315.8 lux ,whereas at night ,6pm-8pm,

    the average lux value is 19.4 lux. There is a great difference because the space is a long

    courtyard with a skylight. In the daytime, the natural lighting directly penetrate through the

    transparent skylight into the space. At the night time the space are lighten up by warm

    lighting ,therefore the lux level is lower.

    According to table provided in MS1525 , the 1.6% DF of Reception Area is

    categorized under the average category. The atrium is functioned as a gathering space

    for the hotel guests , therefore the lighting is sufficient enough as it is not used for working

    purposes.

    DF , % Distribution >6 Very Bright with thermal & glare problem 3 6 Bright 1 3 Average 0 1 Dark

    50

  • Lumen Method

    51

    Location Atrium Dimension , m L = 20 , W = 2.8 Area ,2 60.4 Height of ceiling , m 11.5 Height of work level, m 0.8 Type of light Fluorescent Light Twist Compact fluorescent

    light bulb Luminous flux of lighting,F / lm

    1350 900

    Height of luminaries , m 2.9 2.6 Mounting Height , ,m 2.9-0.8 = 2.1 2.6-0.8 =1.8 Number of existing light bulb/ n x N

    18 12

    Reflectance Value ,% Ceiling Acrylic Skylight 0

    Wall Concrete Block with white plaster

    85

    Floor Light Walnut Timber Plank 25 Room Index ( L x W )

    (L + W ) x H

    = (20 x 2.8)( 20+2.8)x 11.5

    = 0.21 Utilization Factor / UF 0.26 Maintenance Factor / MF MF = LLMF x LSF x LMF x RSMF

    = 0.86 x 0.95 x 0.81 x 0.86 = 0.57

    MF = LLMF x LSF x LMF x RSMF = 0.68 x 0.88 x 0.86 x 0.86 = 0.44

    Illuminance level required/E,lux

    E = n x F x UF x MFA

    = 18 x 1350 x 0.26x 0.57 60.4

    = 59.6

    E= n x F x UF x MFA

    = 12 x 900 x 0.26x 0.44 60.4

    = 20.5

    Maximum Illuminance recommended by MS1525 (lux)

    300lux

    Number of Fitting Required ,N

    N=

    = 300 x 60.41350x0.26x0.57

    = 5 fluorescent light bulb needed to meet the standard illuminance required in reception area

    N=

    = 300 x 60.412x900x0.26x0.44

    = 15 twist compact fluorescent light bulb needed to meet the standard illuminance required in reception area

  • 3.3.3 Corridor

    Lighting Specification

    Material Specification

    Type Specification Luminaire Type

    Placement Luminuous Flux per unit (lm)

    Twist CFL Lamp Life : 10,000 hr

    Open top reflector

    Room number signage & Guiding light

    900

    Main Surface Description Color Reflectance

    Ceiling White Painted White 85

    Wall Concrete Block painted White 85

    in white

    Floor Polish concrete with Grey 70

    vivid colour dye

    52

  • Daylight Factor

    Table 1 Lux Reading at Reception Area

    Table 2 : Average Lux Value at Reception Area

    Table 3 : Daylight Intensity at different condition

    Time Weather Luminance Average At 1m (1x) (1x)

    Luminance Average at 1.5m ( 1x) (1x)

    12-3pm Cloudy 10-450 97.7 5-530 177.7 6-8pm Raining 8-81 21.2 8-30 36.2

    Average lux Reading 12-3pm 6-8pm 1m 97.7 21.2 1.5m 177.7 36.2 Average lux value 137.7 57.4

    Illuminance Example 120,000lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entires clear blue

    sky, midday

    1,000 -2,000 lux Typical overcast day,midday

  • Discussion

    Table 1 Daylight Factor ,DF

    The average lux value during 12pm-3pm is 137.7lux ,whereas at night ,6pm-8pm,

    the average lux value is 57.4 lux. The average lux value is low even during day time.

    According to table provided in MS1525 , the 0.7% DF of Reception Area is categorized

    under the dark category . This can be observed during site visit as the corridor are

    lightened up by artificial lighting even during daytime.

    DF , % Distribution >6 Very Bright with thermal & glare problem 3 6 Bright 1 3 Average 0 1 Dark

    54

  • Lumen Method

    55

    Location Corridor Dimension , m L = 26 , W = 1.5 Area ,2 38.5 Height of ceiling , m 3.6 Height of work level, m 0.8 Type of light Twist Compact fluorescent light bulb Luminous flux of lighting,F / lm

    900

    Height of luminaries , m 1.5 Mounting Height , ,m 0.7 Number of existing light bulb/ n x N

    10

    Reflectance Value ,% Ceiling White Painted Ceiling 85

    Wall Concrete Block with white plaster

    85

    Floor Polish concrete with vivid colour dye

    70

    Room Index ( L x W )

    = (L + W ) x H

    (26 x 1.5)

    ( 26+1.5)x 3.6

    = 0.39 Utilization Factor / UF 0.27 Maintenance Factor / MF MF = LLMF x LSF x LMF x RSMF

    =0.72x0.92x0.86x0.94 = 0.54

    Illuminance level required/E,lux

    E = n x F x UF x MFA

    = 10 x 900 x 0.27x 0.5438.5

    = 34.1

    Maximum Illuminance recommended by MS1525 (lux)

    50lux

    Number of Fitting Required ,N

    N=

    = 50x 38.59000.270.54

    = 15 Twist Compact fluorescent light bulb needed to meet the standard illuminance required in corridor.

    Existing Number of lamps are 10, 15-10=5 Therefore ,5 more Compact Fluorescent light bulb more required to fulfil the requirement

  • 3.3.4 Room with Glass Box (D9-F9)

    Lighting Specification

    Material Specification

    Type Specification Luminaire Type

    Placement Luminuous Flux per unit (lm)

    Twist CFL Lamp Life : Open top Wall 900 10,000 hr reflector

    Twist CFL Lamp Life : Enclosed Floor 900 10,000 hr

    Fluorescent Lamp Life: Bare Lamp Ceiling Slot 1350 Light 14000 hr Batten

    Main Surface Description Color Reflectance

    Ceiling White Painted White 85

    Wall Concrete Block painted White 85

    in white

    Window Glass Transparent 4

    Floor Crystal Grain Terrazo Crystal 80

    Tile Grain

    56

  • Daylight Factor

    Table 1 Lux Reading at Reception Area

    Table 2 : Average Lux Value at Reception Area

    Table 3 : Daylight Intensity at different condition

    Time Weather Luminance Average At 1m (1x) (1x)

    Luminance Average at 1.5m ( 1x) (1x)

    12-3pm Cloudy 33-450 184.3 100-820 346.7 6-8pm Raining 13-27 18.7 13-32 24.7

    Average lux Reading 12-3pm 6-8pm 1m 184.3 18.7 1.5m 346.7 24.7 Average lux value 265.5 43.4

    Illuminance Example 120,000lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entires clear blue

    sky, midday

    1,000 -2,000 lux Typical overcast day,midday

  • Discussion

    Table 1 Daylight Factor ,DF

    The average lux value during after 12pm-3pm is 265.5 lux,whereas at

    night ,6pm-8pm, the average lux value is 43.4 lux. There lux value is greatly reduced.

    According to table provided in MS1525, the 1.33% DF of room with glass box is

    categorized under the average category.

    DF , % Distribution >6 Very Bright with thermal & glare problem 3 6 Bright 1 3 Average 0 1 Dark

    58

  • Lumen Method

    59

    Location Room with Glass Box Dimension , m L = 2.7 , W = 4.1 Area ,2 11.07 Height of ceiling , m 2.6 Height of work level, m 0.8 Type of light Fluorescent Light Twist CFL Twist CFL Luminous flux of lighting,F / lm

    1200lm 900lm 900lm

    Height of luminaries , m 2.6 1.5 0.2 Height of Working Plane,m 0.8 Mounting Height , ,m 2.6-0.8=1.8 1.5-0.8=0.7 0.8-0.2=0.6 Number of existing light bulb/ n x N

    1 1 1

    Reflectance Value ,% Ceiling White Painted 85 Wall Concrete Block painted in

    white 85

    Window Glass 4

    Floor Crystal Grain Terrazo Tile 80 Room Index ( L x W )

    = (L + W ) x H

    (2.7x4.1)

    (2.7+4.1)x 2.6

    = 0.63 Utilization Factor / UF 0.47 Maintenance Factor / MF Fluorescent

    Light MF = LLMF x LSF x LMF x RSMF

    = 0.83 x 0.64 x 0.89 x 0.94 = 0.44

    Wall Mounted Twist CFL

    MF = LLMF x LSF x LMF x RSMF = 0.72 x 0.92 x 0.86 x 0.94 = 0.54

    Floor Mounted Twist CFL

    MF = LLMF x LSF x LMF x RSMF = 0.72 x 0.92 x 0.82 x 0.94 = 0.51

    Illuminance level required/E,lux

    Fluorescent Light

    E = n x N x F x UF x MFA

    = 1 x 1200 x 0.47 x 0.44 11.07

    = 22.42 Wall Mounted Twist CFL

    E = n x N x F x UF x MFA

    = 1 x 900 x 0.47 x 0.54 11.07

    = 20.63

  • 60

    Floor Mounted Twist CFL

    E = n x N x F x UF x MFA

    = 1 x 900 x 0.47 x 0.51 11.07

    = 19.49 Maximum Illuminance recommended by MS1525 (lux)

    50lux

    Number of Fitting Required ,N

    Fluorescent Light

    N=

    = 50 x 11.071200x0.47x0.44

    = 2.23 3 fluorescent Light needed to meet the standard illuminance required in Room area.

    Wall Mounted Twist CFL

    N=

    = 50 x 11.07900x0.47x0.54

    = 2.42 3 fluorescent Light needed to meet the standard illuminance required in Room area.

    Floor Mounted Twist CFL

    N=

    = 50 x 11.07900x0.47x0.51

    = 2.56 3 fluorescent Light needed to meet the standard illuminance required in Room area.

  • 3.3.5 Staircase ( A13- A15)

    Lighting Specification

    Material Specification

    Type Specification Luminaire Type

    Placement Luminuous Flux per unit (lm)

    Fluorescent Light

    Watt Lamp Life: 8000 hr

    Bare Lamp Batten

    Hanging from Ceiling

    Mounted within Beam

    Main Surface Description Color Reflectance

    Ceiling White Plaster Ceiling White 85

    Wall White Painted Wall White 85

    Exposed brick Red 25

    Ceramic Tiles Light Cream 70

    Floor Porcelain Tiles Cinnamon 40

    Window Brown Timber Shutter Light Walnut 25

    Furniture - - -

    61

  • Daylight Factor

    Table 1 Lux Reading at Reception Area

    Table 2 : Average Lux Value at Reception Area

    Table 3 : Daylight Intensity at different condition

    Time Weather Luminance Average At 1m (1x) (1x)

    Luminance Average at 1.5m ( 1x) (1x)

    12-3pm Cloudy 25-30 27.3 42-50 45.7 6-8pm Raining 8-17 11.3 9-38 19

    Average lux Reading 12-3pm 6-8pm 1m 27.3 11.3 1.5m 45.7 19 Average lux value 36.5 15.2

    Illuminance Example 120,000lux Brightest sunlight 110,000 lux Bright sunlight 20,000 lux Shade illuminated by entires clear blue

    sky, midday

    1,000 -2,000 lux Typical overcast day,midday

  • Discussion

    Table 1 Daylight Factor ,DF

    The average lux value during after 12pm-3pm is 36.5 lux,whereas at night ,6pm-

    8pm, the average lux value is 15.2 lux. There lux value is reduced by half.

    According to table provided in MS1525, the 0.18% DF of staircase is categorized

    under the dark category. Even though there are windows in the stairwell , most of the

    time ,the window are closed even during daytime.

    DF , % Distribution >6 Very Bright with thermal & glare problem 3 6 Bright 1 3 Average 0 1 Dark

    63

  • Lumen Method

    64

    Location Reception Area Dimension , m L = 3m , W = 7.6m Area ,2 23.4m Height of ceiling , m 3.6 Height of work level, m 0.8 Type of light Fluorescent light

    Luminous flux of lighting,F / lm

    1200lm

    Height of luminaries , m 2.7 Height of Working Plane,m 0.8 Mounting Height , ,m 2.7-0.8=1.9 Number of existing light bulb/ n x N

    2

    Reflectance Value ,% Ceiling White Plaster Ceiling 85 Wall White Painted Wall 85

    Exposed brick 25 Ceramic Tiles 70

    Window Brown Timber Shutter Windows

    25

    Floor Porcelain Tiles 40 Room Index ( L x W )

    (L + W ) x H

    = (3 x 7.6)( 3+7.6)x 3.6

    = 0.60 Utilization Factor / UF 0.47 Maintenance Factor / MF MF = LLMF x LSF x LMF x RSMF

    = 0.83 x 0.64 x 0.89 x 0.94 = 0.44

    Illuminance level required/E,lux

    E = n x N x F x UF x MFA

    = 2 x 1200 x 0.47 x0.44 22.8

    = 21.8 Maximum Illuminance recommended by MS1525 (lux)

    100lux

    Number of Fitting Required ,N

    N=

    = 100 x 22.81200x0.47x0.44

    = 11 Fluorescent Light needed to meet the standard illuminance required in reception area

  • 4.0 ACOUSTIC

    4.1 Precedent Study

    4.1.1 Introduction

    Buxton Crescent Hotel and Spa

    Buxton Crescent Hotel and Spa, a five star spa hotel with conference and

    banqueting facilities is converted and extended from a number of listed buildings. The

    existing buildings designed by John Carr were built in 1780 and it is then transformed by

    Archer Humphreys Architects.

    The two key acoustic challenges in transforming Buxton Crescent Hotel are most

    likely to be achieving the acoustic requirements by providing sufficient absorbent

    finishes within the existing rooms, and also upgrading the existing constructions to

    achieve the proposed sound insulation standards. Due to their involvement in the

    conservation and refurbishment of the Grade I listed Crescent and of the adjacent pump

    rooms and surrounding spaces, they have certain limitation on extending the alterations

    and it may affect the achievement on standards proposed.

    Acoustic design of a hotel is the key factor in its overall quality and the guests

    experience towards the spaces. The three main acoustic factors are:

    a. Room acoustics

    b. Sound insulation

    c. Background noise levels

    65

  • 4.1.2 Room Acoustics

    The effects of acoustic absorbent finishes should be proportionate to their

    respective spaces area. Hence the selection of materials with different acoustical

    absorption characteristics is very important in the preliminary design stage. Taking Buxton

    Crescent Hotel and Spa as precedent study, the heritage constraints of the building are

    more likely to limit the type and amount of finishes that can be integrated into the design

    in order to achieve appropriate acoustical performance.

    In most of the public spaces, such as the offices, guestrooms, bar, restaurant, and

    reception, they use carpeted floor with acoustically absorbent ceiling or suspended

    acoustic rafts in order to control the quality of space.

    4.1.3 Sound Insulation & Selection of Surface Materials

    The existing site buildings are of traditional masonry construction with masonry

    wall and timber floors. Hence, the design team decided to increase the floor mass from

    the existing floor in order to improve sound insulation. Different treatments are done

    towards different systems according to the requirement.

    Proposed sound insulation criteria according to the Hilton design guide.

    Airborne Sound Insulation (Walls and Floors)Guestroom to Guestroom (walls and

    floors)

    55dBRw

    Guestrooms to all other rooms (bar,

    meeting rooms, office etc)

    60dBRw

    Conference rooms to Conference room 55dBRw

    Walls within Guestrooms (to ensuite) Rw45

    Airborne Sound Insulation (Doors)Guestrooms, Conference rooms (and

    adjacent lobbies), Assembly room

    Rw35

    Executive lounges, offices Rw30

    Impact Sound Insulation (Floors)Guest room to Guest room 50dBLnT,w

    Guest room to Conference rooms 55dBLnT,w

    Conference rooms to Living/drawing

    room

    55dBLnT,w

    66

  • Floors

    The existing floors will be developed to achieve the double construction principle

    where there is large air cavity in between the upper and lower boards (floor and ceiling

    from different floor level rooms). The treatment taken is to add floating floors, to remove

    the existing floor boards and to replace the existing floor boards on resilient clips, adding

    new plasterboards on the resilient hangers. Since, the space in existing floor is limited to

    accommodate the floating floor, carpets are more likely to be able to achieve the impact

    sound insulation requirement.

    Figure: GypFloor Silent sound insulation floor system.

    Floor boards with resilient clips

    3. Sound insulation airbourne: 54 - 63 (Rw dB)

    4. Sound insulation impact: 63 - 55 (Lnw dB)

    5. Fire resistance: 30 - 90 (mins)

    DoorsAcoustical rated doors with minimum thickness of 54mm thick solid core timber is useful

    in providing good insulation.

    WallsThe highest standard of wall sound insulation required is Rw55. Generally it should be

    possible to achieve this standard with 300mm thick dense masonry. But in some cases,

    there are walls which are less than 300mm thick masonry, and so these will be upgraded

    in order to achieve the requirement. Hence, the solution is to add an independent

    plasterboard lining to the wall.

    67

  • Independent Wall Lining System

    6. Sound insulation airbourne: 59 - 61 (Rw dB)7. Fire resistance: 30 - 90 (mins)8. Thermal performance: 0.35 - 0.16 (W/mK

    68

  • 4.1.4 Background Noise

    The background noise within internal spaces will be dedicated by two main factors:

    Building services noise (ventilation etc) and intrusive external noise (road traffic noise

    etc)

    a. Proposed Building Services Noise Criteria

    b. Intrusive Noise

    Daytime (07:00-23:00): 35dBLAeq, 16h

    Night-time (23:00-07:00): 30dBLAeq, 8h / 45dBLAmax (fast)

    Controlling building services noise will be critical in controlling the noises level.

    In conclusion, the selection of materials in a hotel design is very important as hotel is

    spaces that provides rest and comfort the users. Due to the limitation of preserving the

    existing listed buildings, Buxton Crescent Hotel and Spa has very limited use of materials

    and the structure could not be demolish and reconstruct.

    Room Maximum building services noise level (NR)

    Guestroom (at bedhead) NR25

    Guestroom bathroom NR35

    Conference rooms 1 to 3 NR30

    Assembly room NR25*

    Drawing/living room NR35

    Lobbies, reception, guest corridors,

    public

    toilets

    NR40

    Bar, restaurant, retail units NR35

    Staff toilets/changing NR45

    Back of house / service areas NR45

    Kitchens NR45

    Offices NR35

    69

  • 4.2 Site Acoustics

    4.2.1 Data

    Tabulation 12pm 3pm; 2nd Floor

    70

  • 12pm - 3pm; 4th Floor

    4th Floor

    Grid Noise

    Level (dB)

    A6 63

    A13 60

    A14 60

    A15 60

    B3 67

    B4 67

    B5 63

    B6 61

    B7 61

    B8 62

    B9 62

    B10 62

    B11 63

    B12 63

    B13 63

    B14 65

    B15 65

    C14 65

    D14 64

    E14 64

    F14 64

    G14 65

    H14 65

    I14 65

    C2 67

    D2 67

    E2 67

    F2 66

    G2 66

    H2 63

    I2 62

    I3 62

    I4 62

    I5 62

    I6 65

    I7 65

    I8 65

    I9 65

    I10 65

    I11 64

    I12 64

    I13 64

    C9 47

    D9 40

    E9 40

    C11 45 D11 40

    71

  • 6pm - 8pm; 2nd Floor

    72

  • 6pm - 8pm; 4th Floor

    4th Floor

    Grid Noise

    Level (dB)

    A6 64

    A13 66

    A14 66

    A15 64

    B3 62

    B4 65

    B5 61

    B6 64

    B7 62

    B8 62

    B9 62

    B10 62

    B11 63

    B12 65

    B13 63

    B14 64

    B15 64

    C14 62

    D14 64

    E14 64

    F14 64

    G14 64

    H14 63

    I14 64

    C2 61

    D2 61

    E2 61

    F2 61

    G2 61

    H2 61

    I2 62

    I3 61

    I4 67

    I5 64

    I6 65

    I7 62

    I8 63

    I9 70

    I10 65

    I11 70

    I12 64

    I13 64

    C9 58

    D9 54

    E9 50

    C11 42 D114 0

    73

  • 4.2.2 Data Tabulation Analysis

    12pm - 3pm (Non-Peak)

    2nd/Reception Floor 4th Floor

    According to data tabulated in the images above, rooms on the 4th floor

    experience lower noise levels than rooms on the reception floor in the afternoon (non-

    peak period). This may be due to the building materials employed for room enclosure.

    In the Eastern region of 4th floors corridor, there are higher noise levels compared to

    the reception floor due to activities from the back-alley and the location of a lounge

    nearby (circled).

    74

  • 6pm - 8pm (Peak)

    2nd/Reception Floor 4th Floor

    According to data tabulated in the images above, overall noise level during peak

    hours (night time) is higher on the lower reception floor compared to the upper 4th floor

    especially within the cor- ridors.

    However, this may be due to a higher density of human population where people

    prefer renting rooms nearer to ground floor perhaps for sake of convenience.

    75

  • 2nd/ Reception Floor

    6pm - 8pm (Peak) 12pm - 3pm (Non-Peak)

    According to data tabulated in the images above, overall noise level on the

    reception floor is higher during peak hours (night time) compared to the non-peak period

    in the afternoon.

    This may be due to noise emitted from the Petaling Street market activities

    surrounding the hotel on the ground floor which peaks at night.

    76

  • 4th Floor

    6pm - 8pm (Peak) 12pm - 3pm (Non-Peak)

    According to data tabulated in the images above, noise level is generally higher in

    the 4th floor rooms during peak hours. This may be due to different building materials

    enclosing the two different room types and human population level.

    On the other hand, noise level is higher in the corridor nearest to the backalley.

    This maybe due to the outdoor air conditioning units operating by the hotel wall facing

    the backalley.

    77

  • 4.2.3 Outdoor Noise Sources

    Surrounding the Lantern Hotel on the ground floor is the Petaling Street market

    held daily. The market is a popular tourist spot, thus it is always busy throughout the

    year. The market sees its biggest crowds at night daily, thus noise levels would naturally

    be higher in the hotel as sound travels upwards (on the path of least resistance) through

    air and solids. The porous facade of the lantern hotel facing the market may be a

    strategy to reduce noise levels within the building as sound is known to travel fastest

    through solids. In this regard, the exterior perimeter walls as seen in the figure below are

    made porous and permeable by wind movement and sound waves.

    78

    Western Facade (Avadhanulu and Kshirsagar, 2013)

  • 4.2.4 Indoor Noise Sources

    Air circulators

    2nd Floor

    4th Floor

    Air cirulators such as ceiling fans and air conditioners are used in the lantern hotel

    for improving human thermal comfort. Ceiling fans are used in the corridors in order to

    minimise electrical consumption and improve energy efficiency of building. The perimeter

    exterior walls are punctured with holes, thus a lot of cool air would be lost to the outside if

    air conditioners are used. However, this increases sound levels around the rooms. In

    certain areas, ceiling fans installed clatter against steel service pipings running along

    ceilings, thus producing unwanted noise.

    79

  • Zoning

    4th floor

    Reception floor

    80

  • Human Activity

    4th floor

    Reception floor

    Primary noise from human activity occur mainly on the reception floor where light

    refreshments are provided. Apart from the atrium and outdoor deck zones on the

    reception floor, two small lounge areas on the 4th floor are popular spots for human

    gatherings and therefore add to the overall noise level from human activities.

    81

  • Speakers

    Music is randomly turned on from a personal laptop in the reception floor of the hotel

    throughout the day at moderate levels of speaker volume. Sound levels reach as high as

    80 dB in the reception area with the music turned on. Music is used to create a warmer

    atmosphere in the greeting space and may add to human comfort and pleasure.

    82

  • Speakers (Acoustic Ray Diagram - Plan View)

    On plan, sound waves generated from the 500Hz speaker set in Lantern Hotel can be seen to

    be dispersed and reflected by the concrete and brick walls from 15 milliseconds(ms) onwards. Sound

    is not transmitted into the hotel rooms which is good. Useful sound waves on the other hand where

    clarity of sound is concerned also only travel within the reception area. The painted concrete block

    wall in front of the speaker set works well to reflect sound back towards the source and contain sound

    within the desired area.

    However there is too much echo, reverb and masked sounds travelling along the corridor and atrium

    areas. This may be solved by installing absorptive materials such as acoustic panels along the walls

    of the two areas.

    Area analysed: Type of ray:

    5.0 ms 10.0 ms 15.0 ms 20.0 ms

    25.0 ms 30.0 ms 35.0 ms 40.0 ms

    45.0 ms 50.0 ms 55.0 ms 60.0 ms

    65.0 ms 70.0 ms 80.0 ms 90.0 ms

    83

  • Speakers (Acoustic Ray Diagram - Elevation 1 View)

    Area analysed: Type of ray:

    E1

    On elevation 1, masked and reverb sound waves can be seen to bounce from the acrylic

    skylight roof on the 5th floor to the 2nd floor in the atrium area. In the corridor area, sound is contained

    within the same floor together with useful sound waves where clarity of sound is concerned. From

    15ms to 30ms, echoes are transmitted through the concrete block wall and into the hotel rooms next

    to the corridor.

    5.0 ms 10.0 ms 15.0 ms 20.0 ms

    25.0 ms 30.0 ms 35.0 ms 40.0 ms

    45.0 ms 50.0 ms 55.0 ms 60.0 ms

    65.0 ms 70.0 ms 80.0 ms 90.0 ms

    84

  • Speakers (Acoustic Ray Diagram - Elevation 2 View)

    Area analysed: Type of ray:

    E2

    On elevation 2, masked and reverb sound waves can be seen to bounce from the acrylic

    skylight roof on the 5th floor to the 2nd floor in the atrium area which is considered undesirable due

    to disturbance in the upper floors. Useful sound waves where clarity of sound is concerned is seen

    to be contained within the reception area which is positive as music is only wanted in that area.

    5.0 ms 10.0 ms 15.0 ms 20.0 ms

    25.0 ms 30.0 ms 35.0 ms 40.0 ms

    45.0 ms 50.0 ms 55.0 ms 60.0 ms

    65.0 ms 70.0 ms 80.0 ms 90.0 ms

    85

  • 4.2.5 Equipment Location

    2nd Floor

    4th Floor

    Symbol Equipment Equipment Type No.

    Daikin Wall Mounted

    Air Conditioner

    31

    Daikin Ceiling Cassette

    Air Conditioner

    2

    Khind Ceiling Fan 14

    86

  • 4.2.6 Equipment Specification

    Product Specification

    Name: Daikin Cooling King Indoor Model: FT10MV1l Unit

    Weight: 9kg

    Unit Dimension (mm): 288 X 800 X 216 Refrigerant: R22

    Total Cooling Capacity: 10,000 Btu/hr Indoor Air Flow: 342

    CFM

    Sound Pressure Level: 38 dBA (Highest); 27 dBA (Lowest)

    Outdoor Model: R09/15CV1 Unit Weight: 25kg

    Unit Dimension (mm): 497 X 600 X 245

    Name: Daikin Air Surround Indoor Model: FF10/15CV1 Unit

    Weight: 28kg

    Unit Dimension (mm): 250 X 570 X 570 Refrigerant: R22

    Capacity Range: 1.0 -1.5 hp

    Total Cooling Capacity: 10,000 Btu/hr Indoor Air Flow: 410

    CFM

    Sound Pressure Level: 41 dBA (Highest); 31 dBA (Lowest)

    Outdoor Model: R09/15CV1 Unit Weight: 17.5kg

    Unit Dimension (mm): 543 X 700 X 250

    Name: Khind Ceiling Fan Model: CF604

    Number of Blades: 3 Voltage:220-240V ~ 50Hz Power:

    75W

    Size: 60 Feature: Electronic regulator with 5-speed setting

    Name: Logitech Multimedia Speakers Z213 Model: PN 980-

    000941

    Dimensions: 5.6 x 3.1 x 3 (Satellites) 7.2 x 5.1 x 7.6 (Subwoofer) Weight: 1.76kg

    Power: 7W Frequency: 500 Hz

    87

  • 4.3 Acoustic Analysis

    4.3.1 Reverberation Time

    Zone A : Reception Area + Atrium + Corridor

    Building Element

    Material Absorption Quantity Total Area, S/m S x a Coefficient,a

    Ceiling Raw Concrete with Paint

    0.02 1 31.7 0.634

    Acrylic Skylight

    0.04 1 65.1 2.604

    Cement board

    0.04 1 8.24 0.330

    88

    Reverberation Time

    Space volume = (90.7x3.6)+(51.3x11.5)=403.53

    Material Absorption Coefficient in 500Hz at Peak Hour

  • RT = (0.16 x V) / A

    = (0.16 x 403.5) /52.194

    = 1.236s

    Floor Parquet 0.07 1 101.7 7.119 Fixed on Concrete

    Concrete 0.02 1 40 0.8 Floor

    Wall Brickwork 0.03 2 17.7+27.84=45.5 1.365 Painted 0.06 2 83.1+ 28.386 Concrete 195+195=473.1 Block

    Painted 0.02 1 93.6-10.8=82.8 1.656 Brickwall

    Door 900x2400mm 0.05 18 18x2.16=38.9 1.945 1hr fire rated timber door

    Window Timber 0.03 6 6x4.0= 24.0 0.72 Louvres

    Glass Panel 0.04 26 26x2.16=56.2 2.246

    Glass box 0.04 6 6 x 3.6=21.6 0.864

    Furniture Metal Stool 0.14 3 0.75 0.105 Human 0.42 per 5 - 2.1

    person

    Air Oxygen and 0.01 - 132.01m 1.32 Carbon Dioxide

    Total 52.194 Absorption, A

    89

  • Zone B :Room with Glassbox

    Reverberation Time

    Space Volume = (4.2x2.6)+(1.1x1.6) x 2.7

    = 34.2m

    Building Material Element

    Absorption Quantity Total Area,Coefficient, S/m a

    S x a

    Ceiling Cement board ceiling

    0.04 1 10.9 0.436

    Glass

    Floor Terrazzo tiles

    0.01 1 12.7 0.127

    Wall Painted Concrete Block

    0.06 1 44.8 2.69

    Glass 0.04 1 9.1 0.365

    Door 1hr fire rated timber door

    0.05 1 1.9 0.096

    Glass Door 0.04 1 1.9 0.076

    Human 0.42 2 - 0.84

    90

  • Air Oxygen and Carbon Dioxide

    0.01 - 12.7 0.127

    Total Absorption, A

    4.82

    Analysis of Reverberation Time

    According to ASHRAE 2011 standard

    The result reverberation time for zone A Reception in 500Hz of absorption

    coefficient is 1.236s where the standard reverberation according to ASHRAE 2011 is from

    0.6-0.8s. The result shown is comparatively higher compare to the standard set although

    it is still falls on the excellent design category. Based on our case study on Lantern Hotel,

    the spaces in zone A especially the reception and partially of the corridor end has less

    wall surfaces.

    Zones Calculated Reverberation Time,s

    Standard Reveberation Time, s

    Zone A Reception Area 1.236 0.8 Atrium (gathering space)

    1.236 0.6-0.8

    Corridor 1.236 0.6-0.8

    Zone B Room 1.13

  • For instance, the wall in the reception which is facing the street has three timber

    louvered windows. This is the main reason that sounds in Zone A escapes by penetrating

    through the window to the surrounding external environment. This openness leads to a

    very low absorption level of sound for Zone A(less wall surface is provided) and the

    chances for sound waves to reflect back have reduced and hence it takes longer time for

    the reverberation to take place.

    Besides, the differences in the height of the spaces in Zone A might be one of the

    key issues which influence the consistency of reverberation movement. As sound waves

    penetrating thorough the space, the big changes in volume of atrium will increase the time

    for sound waves to reflect.

    However in the hotel room with glass box, the result shown is 1.13s which is

    definitely exceed the reverberation time standard of less than 0.6s. As experiencing on

    site, the noises from hotel servicing (vacuuming) can clearly be heard in room and it is

    consider as a distraction to the users. This might be affected by the wall material use,

    such as glass wall facing towards the atrium area. The design should take more

    consideration in provide a comfortable resting area to the users.

    92

  • 4.3.2 Sound Pressure Level (SPL)

    ZONE 1 : Reception Area

    93

    Highest Reading = 78dB

    = 1010

    11012

    78 = 1010

    1 10

    17.8 =

    1 10

    = 6.31105

    Total Intensities ,I = (6.31105) + (6.31 105 )

    = 1.26 x 105

    Using the formula : combined SIL = 10log10( 12 )1 10

    Combined SIL = 10 log10[(1.26 105 ) / (1 1012)] x

    = 71.0 dB ,at Reception Area

    Lowest Reading = 63dB

    = 10

    63 = 10

    1 10

    16.3 =

    1 10

    = 6.31105

  • ZONE 2 ; Atrium ( Dining Area)

    94

    Highest Reading = 78dB

    = 1010

    11012

    78 = 1010

    1 10

    17.8 =

    1 10

    = 6.31105

    Total Intensities ,I = (6.31105) + (1.0 105 )

    = 7.31 x 105

    Using the formula : combined SPL = 10log10( 12 )1 10

    Combined SPL = 10 log10[(7.31 105 ) / (1 1012)] x

    = 78.6 dB at Atrium

    Lowest Reading = 70dB

    = 10

    70 = 10

    1 10

    17.0 =

    1 10

    = 1.0105

  • ZONE 3: 2nd Floor North Corridor (near entrance)

    95

    Highest Reading = 78dB

    = 1010

    11012

    78 = 1010

    1 10

    17.8 =

    1 10

    = 6.31105

    Total Intensities ,I = (6.31105) + (1.0 105 )

    = 7.31 x 105

    Using the formula : combined SPL = 10log10( 12 )1 10

    Combined SIL = 10 log10[(7.31 105 ) / (1 1012)] x

    = 78.6 dB ,at North Corridor

    Lowest Reading = 70dB

    = 10

    70 = 10

    1 10

    17.0 =

    1 10

    = 1.0105

  • ZONE 4 : Rooms

    2nd Floor

    Rooms

    96

    Highest Reading = 63dB

    = 1010

    11012

    63 = 1010

    1 10

    16.3 =

    1 10

    = 2.0108

    Total Intensities ,I = (2.0108) + (2.5 107)

    = 2.25 x 106

    Using the formula : combined SPL = 10log10( 12 )1 10

    Combined SPL = 10 log10[(2.25 106 ) / (1 1012)] x

    = 63.5 dB ,at 2nd Floor Room

    Lowest Reading = 54dB

    = 10

    54 = 10

    1 10

    15.4 =

    1 10

    = 2.5107

  • 4th Floor Rooms

    97

    Highest Reading = 58dB

    = 1010

    11012

    58 = 1010

    1 10

    15.8 =

    1 10

    = 6.31108

    Total Intensities ,I = (6.31108) + (2.5 107)

    = 3.13 x 107

    Using the formula : combined SPL = 10log10( 12 )1 10

    Combined SPL = 10 log10[(3.13 107 ) / (1 1012)] x

    = 54.9 dB ,at 4th Floor Room

    Lowest Reading = 54dB

    = 10

    54 = 10

    1 10

    15.4 =

    1 10

    = 2.5107

  • Analysis of Sound Pressure Level

    According to BS8233:2014 and ASHRAE Standard

    For the reception area, the sound pressure level is 20dB higher than ASHRAE

    standard which is 50dB. This falls under the category of 70-79dB with reference to the

    table of general sound environments which is considered to be twice as loud as an

    ordinary conservation. However , in the case of reception area, most of the sound

    intensity level is attributed to the speakers that are being employed for the whole day to

    act as a background music and provide relaxation for guests and serving as waiting

    areas.

    Zone Calculated Sound Pressure Level,dB

    Standard Sound Pressure Level ,dB

    Reception Area 71.0 50 Atrium (Dining Area) 78.6 45 Corridor 78.6 45 2nd Floor Rooms 63.5 35 4th Floor Rooms 54.9

    98

  • For the three floor height atrium at the middle of Lantern Hotel ,the calculated

    sound intensity level is 78.6dB which is 33.6dB higher than the standard sound intensity

    level .45dB. It is also fall under the category of 70-79dB which is 2 times louder than an

    ordinary conservation. The sound pressure level is attributed to the speaker which is just

    located at the reception area right beside atrium. Other than that ,both ends of the long

    atrium allow noise from the street to penetrate through.

    For the corridor ,it is located at the most inner part Lantern Hotel ,the sound

    intensity level is up to 78.6dB ,which is higher than the standard sound pressure level It

    falls under category of 70-79dB which is considered to be 2 times loud as an ordinary

    conservation. From our observation during site visit , the sound is mainly attributed to the

    noise by the fans and the service and machine room along the corridor.

    In comparing the hotel room at 2nd floor and 4th floor ,the sound pressure level are

    63.4dB and 54.9dB respectively there is a minor decrease when the level goes up. This

    is due to transmission of sound from other zones. Both the rooms of different level do not

    achieve the standard sound pressure level , however it is still fall under the categories of

    50-69dB ,which is considered as loud and ordinary conservation which si definitely

    secured acoustic trait for a private rooms in hotel.

    99

  • 4.3.3 Sound Reduction Index (SRI) at 500 Hz

    Zone: 2nd Floor

    SRI Formulae: R = 10 log (1/T)

    Building Componen

    t

    Material Surface Area (m)

    SRI (dB)

    Energy Transmission Coefficient (T)

    T x Area

    Wall 1 5 Windows Brick Wall 100mm unfinished

    15 9.5

    10 39

    0.1 1.3 x 10-4

    1.5 1.2 x 10-3

    Wall 2 Plastered Brick Wall 83.3 58 1.6 x 10-6 1.3 x 10-4

    4 Timber Doors 7.7 37 2.0 x 10-4 1.5 x 10-3

    Wall 3 2 Windows 8.4 10 0.1 8.4 x 10-1

    Brick Wall 100mm 16.1 39 1.3 x 10-4 2.1 x 10-3

    unfinished

    Wall 4 Painted Concrete Block 75.6 45 3.2 x 10-5 2.4 x 10-3

    Wall 15.4 37 2.0 x 10-4 3.1 x 10-3

    8 Timber Doors

    Wall 5 Painted Concrete Block 59.2 45 3.2 x 10-5 1.9 x 10-3

    Wall 11.5 37 2.0 x 10-4 2.3 x 10-3

    6 Timber Doors

    Wall 6 Painted Concrete Block Wall

    70.7 45 3.2 x 10-5 2.3 x 10-3

    100

  • Wall 1 Overall Energy Transmission Coefficient:

    Windows

    (T x A) = 1.5

    Brick Wall:

    (T x A) = 1.2 x 10-3

    A + A = 24.5

    T = (T x A) + (T x A ) A + A

    T = 6.1 x 10-2

    Using reduction index formula and substituting

    R = 10log (1/T) R = 12 dB

    Wall 2 Overall Energy Transmission Coefficient:

    Doors

    (T x A) = 1.5 x 10-3

    Plastered Brick Wall:

    (T x A) = 1.3 x 10-4

    A + A = 91

    T = (T x A) + (T x A ) A + A

    T = 1.8 x 10-5

    Using reduction index formula and substituting

    R = 10log (1/T) R = 47 dB

    101

  • Wall 3 Overall Energy Transmission Coefficient:

    Windows

    (T x A) = 8.4 x 10-1

    Brick Wall:

    (T x A) = 2.1 x 10-3

    A + A = 24.5

    T = (T x A) + (T x A ) A + A

    T = 3.4 x 10-2

    Using reduction index formula and substituting R = 10log

    (1/T) R = 14 dB

    Wall 4 Overall Energy Transmission Coefficient:

    Doors

    (T x A) = 3.1 x 10-3

    Concrete Block Wall

    (T x A) = 2.4 x 10-3

    A + A = 91

    T = (T x A) + (T x A ) A + A

    T = 6.0 x 10-5

    Using reduction index formula and substituting

    R = 10log (1/T) R = 42 dB

    102

  • Wall 5 Overall Energy Transmission Coefficient: Doors

    (T x A) = 2.3 x 10-3

    Concrete Block Wall:

    (T x A) = 1.9 x 10-3

    A + A = 70.7 T = (T x A) + (T x A )

    A + A

    T = 5.9 x 10-5 Using reduction index formula and substituting

    R = 10log (1/T) R = 42 dB

    Wall 6 Overall Energy Transmission Coefficient: Concrete Block Wall (T x A) = 2.3 x 10-3

    A= 70.7 T = T x A

    A

    T = 2.3 x 10-3

    Using reduction index formula and substituting

    R = 10log (1/T) R = 26 dB

    103

  • Sound Reduction Index (SRI) Analysis

    According to the table above, Wall 1 has the lowest SRI whereas Wall 2 has the highest SRI. Wall 1 being the most porous as it has the most openings would reasonably have a lower SRI. On the other hand, Wall 2 is plastered and has relatively high number of timber doors, thus it obtains the highest SRI value.

    SRI values for Walls 4, 5 and 6 could be increased by plastering of surfaces as these walls are partitions to hotel rooms which require more privacy.

    Wall SRI (dB)

    1 12

    2 47

    3 14

    4 42

    5 42

    6 26

    104

  • 5.0 BIBLIOGRAPHY

    Acoustic Performance. (2013) (1st ed.). Retrieved from http://www.nzcma.org.nz/document/279- 25/NZCMA_MM_-_2.4_-_Acoustic_Performance.pdf

    Ashrae.org,. 'TC 2.6 Sound And Vibration Control | Ashrae.Org'. N.p., 2015. Web.

    17 May 2015.

    Avadhanulu, M., & Kshirsagar, P. (2013). A Textbook Of Engineering Physics (17th ed.). New Delhi: Nirja Publishers & Printers Pvt. Ltd.

    Awad Khidir, E., Harun, Z., Mohd Nor, M., & Razi, M. (2012). A Comparative Study of Sound Transmission Loss Provided by Glass, Acrylic and Polycarbonate. Jurnal Teknologi, 60(0). doi:10.11113/jt.v60.1432

    Azkorra, Z., Prez, G., Coma, J., Cabeza, L., Bures, S., & lvaro, J. et al. (2015).

    Evaluation of green walls as a passive acoustic insulation system for buildings. Applied Acoustics,

    89, 46-56. doi:10.1016/j.apacoust.2014.09.010

    Bacon, D. (2015). Building acoustics. Kayelaby.npl.co.uk. Retrieved 16 May 2015, from http://www.kayelaby.npl.co.uk/general_physics/2_4/2_4_4.html

    Chan, L. (2008). Sound Insulation. Personal.cityu.edu.hk. Retrieved 16 May 2015, from http://personal.cityu.edu.hk/~bsapplec/sound4.htm

    Fernndez Solla, I. (2013). GLASS ON WEB - Articles - Acoustic properties of glass: not so simple. Glassonweb.com. Retrieved 16 May 2015, from http://www.glassonweb.com/articles/article/836/

    Fundamentals Of Lighting. 2nd ed. New York: Fairchild Books, 2015. Print.

    Guidance On Sound Insulation And Noise Reduction For Buildings. 5th ed. London:

    British Standard Publication, 2014. Web. 17 May 2015.

    Herve, D. Architectural Lighting: Designing With Light And Space. 2015. Print.

    Innes, Malcolm. Lighting For Interior Design. London: Laurence King Pub., 2012.

    Print.

    Knowland, P., & Uno, P. Acoustics - Acoustic Properties of Precast Concrete -

    National Precast Concrete Association Australia. Nationalprecast.com.au. Retrieved 16 May 2015,

    from https://www.nationalprecast.com.au/resources/acoustics-acoustic-properties-precast-concrete

    Lanternhotel.com,. 'Lantern Hotel'. N.p., 2015. Web. 17 May 2015.

    Machacoustics.com,. 'Performance Standards BB93, HTM And BREEAM'. N.p., 2015. Web. 17 May 2015.

    Mommertz, E. Acoustics and sound insulation (p. 30).

    Natura Pro, Textura & Pictura. (2012) (7th ed.). North Wales. Retrieved from http://www.kingspanbenchmark.com/media/244428/bm%20cementitious%20boards%20pds.pdf

    Noise Control Optimizer. Retrieved 16 May 2015, from http://www.techwide- engineering.com/catalogue/nco_door_timber.pdf

    105

  • Sipari, P. Studies On Impact Sound Insulation Of Floors (1st ed.). Espoo. Retrieved from http://www.sea-acustica.es/fileadmin/publicaciones/Sevilla02_rba07004.pdf

    The Trevor Osborne Property Group,. Buxton Crescent Hotel & Spa: Acoustic

    Strategy Report. UK: Ove Arup & Partners Ltd, 2011. Print.

    User, Super. 'Buxton Hotel & Spa - Archer Humphryes Architects'.

    Archerhumphryes.com. N.p., 2015. Web. 17 May 2015.

    106