laramie county community college educational enrichment center - basement renovation ·...

32
DATE ISSUE PLOTTED ON: ARCHITECT #: OWNER: OWNERSHIP OF DOCUMENTS: This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019 Contact Person(s): CONTACT(S): WillIiam W. Wedemeyer AIA, ALEP, LEED AP 307 - 632 - 3144 x120 Zandria Tolliver 307 - 632 - 3144 x119 OWNER #: PROJECT INFORMATION 1820 Dillon Ave Suite 200A Cheyenne, WY 82001 MECHANICAL ENGINEER: Wood 920 E. Sheridan Street, Suite A Laramie, WY 82070 303 - 919 - 2184 Contact Person(s): Nick Pickering, P.E. ELECTRICAL ENGINEER: Wood 920 E. Sheridan Street, Suite A Laramie, WY 82070 307 - 275 - 0722 Contact Person(s): Rick Shields, P.E. CIVIL ENGINEER: Inberg - Miller Engineers 350 Parsley Boulevard Cheyenne, WY 82007 307 - 635 - 6827 Contact Person(s): Daniel Hayes, P.E. 02/19/19 50% SUBMITTAL 03/12/19 95% SUBMITTAL STRUCTURAL ENGINEER: Martin/Martin Wyoming 4020 Laramie Street Cheyenne, WY 82001 Contact Person(s): John Shaffer, P.E. 03/19/19 100% CDs 3/19/2019 3:12:52 PM C100 COVER Laramie County Community College 17 - 07 - 10 1400 E College Dr Cheyenne, WY 82007 Bill Zink (307) 778 - 5222 LCCC EDUCATIONAL ENRICHMENT CENTER BASEMENT RENOVATION 1400 E College Dr, Cheyenne, WY 82007 LARAMIE COUNTY COMMUNITY COLLEGE EDUCATIONAL ENRICHMENT CENTER - BASEMENT RENOVATION

Upload: others

Post on 05-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

  • DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:12:52 PM

    C100

    COVER

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    LARAMIE COUNTY COMMUNITY COLLEGE

    EDUCATIONAL ENRICHMENT CENTER - BASEMENT RENOVATION

  • ?

    A6011 SIM

    MATCHLINE - A10.00

    A01.011

    3

    2

    A011

    1

    3

    2

    INDICATES ROOM NAMEINDICATES ROOM NUMBER

    EXISTING WALLS OR ELEMENTS TO BE DEMOLISHED

    KEY NOTES

    DOOR TAG, SEE SHEET A700 FOR DOOR SCHEDULE

    WINDOW TAG

    WALL TYPE, SEE SHEET A101

    INDICATES SIMILARINDICATES DETAIL NUMBERINDICATES SHEET NUMBER

    CALLOUT TAG

    ROOM TAG

    INDICATES SIMILARINDICATES DETAIL NUMBERINDICATES SHEET NUMBER

    BUILDING SECTION TAG

    NO ARROW INDICATES NOT IN USE

    INDICATES DETAIL NUMBER

    INDICATES SHEET NUMBER

    EXTERIOR ELEVATION TAG

    NO ARROW INDICATES NOT IN USE

    INDICATES DETAIL NUMBER

    INDICATES SHEET NUMBER

    INTERIOR ELEVATION TAG

    CEILING HEIGHT TAG

    ELEVATION MARK

    MATCHLINEINDICATES SHEET NUMBERINDICATES MATCHLINE

    INDICATES SIMILARINDICATES DETAIL NUMBERINDICATES SHEET NUMBER

    WALL SECTION TAG

    INDICATES SIMILARINDICATES DETAIL NUMBERINDICATES SHEET NUMBER

    DETAIL SECTION TAG

    0.1 GRIDLINE

    ROOM NAME101

    10'-0"X

    1

    1111

    1A501

    SIM

    1A501

    SIM

    1A501

    SIM

    W#

    NEW WALL CONSTRUCTION

    EXISTING WALL CONSTRUCTION TO REMAIN

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:12:58 PM

    G100

    GENERAL NOTES

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    A/C AIR CONDITIONINGACT ACOUSTIC TILEADH ADHESIVEADJ ADJACENTAFF ABOVE FINISH FLOORAH ACRYLIC FACED HARDBOARDALUM ALUMINUM ANCH ANCHORALT ALTERNATEARCH ARCHITECT(URAL)ASR AS REQUIREDAWB ACOUSTICAL WALL BOARDAWC ACOUSTICAL WALL COVERING

    BD BOARDBE BLOCK ENHANCERBP BRICK PAVERBM BEAMBTWN BETWEENBLDG BUILDINGBLK(G) BLOCK (ING)BRK BRICKBSMT BASEMENTBTU BRITISH THERMAL UNIT

    CAB CABINETCFM CUBIC FEET / MINUTECG CORNER GUARDCJ CONTROL JOINTCPT CARPET CL CENTER LINECLG CEILINGCLR CLEAR(ANCE)CM CORRUGATED METALCMU CONCRETE MASONRY UNITCOL COLUMNCONC CONCRETECORR CORRIDORCP CEMENT PLASTERCRK CORKCT CERAMIC TILECTR CENTERCW COLD WATER

    DIA DIAMETERDIM DIMENSIONDN DOWNDP DIAMOND PLATE DR DOORDTL DETAIL DWG DRAWING

    EA EACHEJ EXPANSION JOINTEX EXISTINGELEC ELECTRICALELEV ELEVATIONENT ENTRANCEEP EPOXY PAINTEQ EQUALEST ESTIMATEEXP EXPOSEDEXT EXTERIOR

    FE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFD FLOOR DRAINFIN FINISH

    GA GAUGEGAL GALVANIZEDGB GRAB BARGL GLASS, GLAZINGGT GLAZED TILEGYP GYPSUMGYP BD GYPSUM BOARD

    HDWR HARDWAREHT HEIGHTHM HOLLOW METALHVAC HEATING / VENTILATION/ ACHW HOT WATER

    IN INCHINSUL INSULATIONINT INTERIOR

    JAN JANITORJST JOISTJT JOINT

    KIT KITCHENKWH KILOWATT HOUR

    LAM LAMINATELAV LAVATORYLB(S) POUND(S)LCK LOCKERLP LATEX PAINTLT LIGHTLTG LIGHTING

    MAR MARBLEMCP METAL CLAD PANELSMFR MANUFACTURERMEZZ MEZZANINEMH MANHOLEMIN MINIMUMMIR MIRRORMISC MISCELLANEOUSMLWK MILLWORKMTL METAL

    NIC NOT IN CONTRACTNO NUMBERNTS NOT TO SCALE

    OC ON CENTEROD OUTSIDE DIAMETEROP OPERABLE PARTITION

    ABBREVIATIONS

    PC PRECAST CONCRETEPLY PLYWOODPNT PAINTPC PRIME COATPL PLASTERPLAM PLASTIC LAMINATEPLE PLASTER-EPOXYPLP PLASTER-PAINTPOL POLYURETHANEPWR POWER

    QT QUARRY TILEQTY QUANTITY

    RB RUBBER BASERC RUBBER COVE BASERCP REFLECTED CEILING PLANRD ROOF DRAINREQ'D REQUIREDRM ROOMRO ROUGH OPENINGRR RADIAL RUBBER TILERS RUBBER STRAIGHT BASERU RUSTED AND SEALED

    SC SEALED CONCRETESCH SCHEDULESEC SECTIONSHT SHEETSIM SIMILARSL SLATESLR SEALERSPEC SPECIFICATIONST STONESTL STEELSTOR STORAGESUS SUSPENDED SV SHEET VINYL

    T&G TONGUE AND GROOVETEL TELEPHONETEMP TEMPERED THK THICKNESSTHR THRESHOLDTHRU THROUGHTO TOP OFTOB TOP OF BEAMTOC TOP OF CURBTOW TOP OF WALLTL TILETS TUBE STEELTW* TILE WAINSCOT TO 48",

    PAINTED GYP BD ABOVETYP TYPICALTZ TERRAZZO

    UBC UNIFORM BUILDING CODEUR URINALUTIL UTILITY

    VAR VARIESVCB VINYL COVE BASEVCT VINYL COMPOSITION TILEVERT VERTICALVEST VESTIBULEVGB VINYL WRAPPED GYPSUM BOARD VR VARNISHED STAINVIF VERIFY IN FIELDVIN VINYL VT VINYL WITH TEDLAR FINISHVWC VINYL WALL COVERING

    WC WATER CLOSETWD WOODW/O WITHOUTWDP WOOD PANELINGWPR WALL PAPERWR WATER RESISTANT

    NOTE:

    NOT ALL ABBREVIATIONS ARE USED IN THISDRAWING SET. OTHER ABBREVIATIONS MAY BEDEFINED IN OTHER SECTIONS OF THE DRAWINGS,SHOULD QUESTIONS ARISE CONTACT THEARCHITECT FOR CLARIFICATION.

    GENERAL NOTES SYMBOLS LEGENDMAPS SHEET INDEX

    1. DO NOT SCALE DRAWINGS. FIELD VERIFY ALL DIMENSIONS. NOTIFY ARCHITECT IMMEDIATELY WHEN DISCREPANCIES ARE DISCOVERED.

    2. ALL DIMENSIONS ARE TO FACE OF STUD OR MASONRY AT NEW CONSTRUCTION, AND FACE OF FINISH AT ALL EXISTING WALLS, UNLESS NOTED OTHERWISE.

    3. PROVIDE GYPSUM BOARD CONTROL JOINTS, FLOOR TO CEILING, AT 30'-0" O.C. MAX. FOR WALL PARTITIONS EXCEEDING 30'-0" IN LENGTH. WHERE OPENINGS OCCUR WITHIN SPACING, PROVIDE CONTROL JOINTS FROM THE CORNER OF DOOR FRAME HEAD AND JAMB TO CEILING AT STRIKE SIDE, UNLESS NOTED OTHERWISE.

    4. ALL OUTSIDE CORNERS IN CORRIDORS AND CIRCULATION PATH SHALL RECEIVE CORNER GUARDS. CORNER GUARDS SHALL BE FROM 4" ABOVE FINISH FLOOR TO 48" ABOVE FINISH FLOOR, UNLESS NOTED OTHERWISE. SEE SPECIFICATIONS.

    5. ALL INTERIOR FINISH PLANES, LINES AND CORNERS MUST BE STRAIGHT, NEAT AND CLEAN. ANY MATERIALS ABUTTING EACH OTHER MUST ALIGN. EDGES SHALL BE SHARP AND TRUE.

    6. DIMENSIONS FROM DOOR JAMBS (HINGE SIDE) TO ADJACENT WALLS SHALL BE 4" FROM FACE OF STUD OR MASONRY OF ADJACENT WALL TO BACK OF DOOR FRAME JAMB, UNLESS NOTED OTHERWISE.

    7. CONTRACTOR SHALL PROTECT THE EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE DURING SELECTIVE AND BULK DEMOLITION AND RENOVATIONS. ANY DAMAGE THAT OCCURS SHALL BE REPAIRED TO THE FULL SATISFACTION OF THE OWNER AT NO ADDITIONAL COST TO THE OWNER.

    8. CONSTRUCTION DOCUMENTS HAVE BEEN DEVELOPED FROM EXISTING DRAWINGS AND FIELD OBSERVATIONS. CONTRACTOR SHALL FIELD VERIFY EXISTING CONSTRUCTION PRIOR TO START OF DEMOLITION. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN EXISTING CONDITIONS AND CONSTRUCTION DOCUMENTS IMMEDIATELY.

    9. CONTRACTOR SHALL COORDINATE ANY WORK REQUIRED IN ADJACENT SUITES WITH THE OWNER PRIOR TO THE START OF WORK.

    10. AREAS NOT IN CONTRACT (NIC) WILL BE OCCUPIED DURING DEMOLITION AND RENOVATIONS. CONTRACTOR SHALL PROTECT THESE AREAS DURING CONSTRUCTION AND DEMOLITION ACTIVITIES.

    11. CONTRACTOR SHALL KEEP ACTIVITIES TO A MINIMUM IN ADJACENT AREAS DURING CONSTRUCTION.

    12. IT IS THE RESPONSIBILITY OF THE MECHANICAL AND ELECTRICAL SUBCONTRACTORS TO REVIEW ALL DRAWINGS INCLUDING ARCHITECTURAL AND STRUCTURAL FOR WORK UNDER THEIR RESPECTIVE CONTRACTS. NO EXTRAS WILL BE ALLOWED FOR WORK SHOWN IN ANY PART OF THE DRAWINGS OR DESCRIBED IN ANY PART OF THE SPECIFICATIONS.

    13. CONTRACTOR SHALL PREPARE EXISTING WALLS TO REMAIN FOR REFINISHING AND PAINT AS REQUIRED.

    14. SEAL ALL PENETRATIONS THROUGH EXISTING AND NEW WALL CONSTRUCTION WITH APPROVED SEALANT.

    15. SIGNAGE WILL BE PROVIDED BY OWNER. CONTRACTOR TO COORDINATE LOCATIONS OF SIGNAGE WITH OWNER AND PROVIDE BLOCKING IN WALL CAVITY AS REQUIRED.

    16. ALL RATED PARTITIONS SHALL BE PROVIDED WITH CONTINUOUS UL LISTED FIRESTOP JOINT ASSEMBLY AT TERMINATION OF TOP OF WALL AND STRUCTURE ABOVE.

    17. ALL PENETRATIONS AT RATED PARTITIONS AND WALLS SHALL BE FIRESTOP WITH UL FIRESTOP ASSEMBLIES.

    18. CONTRACTOR SHALL ENSURE THAT EXISTING CONSTRUCTION CARRYING A FIRE OR SMOKE RATING SUCH AS CHASE WALLS, FIRE BARRIERS, SMOKE BARRIERS, FIRE PROTECTION AT STRUCTURAL ELEMENTS, FIRE PARTITIONS ARE NOT COMPROMISED DURING DEMOLITION AND CONSTRUCTION ACTIVITIES. PLEASE NOTIFY ARCHITECT IF THERE IS ANY QUESTION IN REGARDS TO THE INTEGRITY OF THESE ELEMENTS DURING CONSTRUCTION AND DEMOLITION ACTIVITIES.

    M000 MECHANICAL COVER SHEETM101 MECHANICAL FLOOR PLANSM201 MECHANICAL SCHEDULE AND DETAILSM301 MECHANICAL SPECIFICATIONSM302 MECHANICAL SPECIFICATIONSP101 PLUMBING FLOOR PLANSP201 PLUMBING SCHEDULE AND DETAILSFP101 FIRE PROTECTION FLOORPLANS

    E000 ELECTRICAL COVER SHEETE101 LIGHTING DEMOLITION AND NEW PLANSE102 POWER - DEMOLITION AND NEW PLANSE103 SYSTEMS - DEMOLITION AND NEW PLANSE201 ELECTRICAL SCHEDULES AND DETAILSE301 ELECTRICAL SPECIFICATIONS

    SHEET INDEX, MECHANICAL

    SHEET INDEX, ELECTRICAL

    A100 DEMOLITION FLOOR AND REFLECTED CEILING PLANA101 FLOOR PLANA102 DIMENSION PLANA300 ENLARGED PLAN AND GENERAL BUILDING DETAILS A301 ENLARGED PLAN AND GENERAL BUILDING DETAILS A400 REFLECTED CEILING PLANA600 FINISH FLOOR PLANA601 INTERIOR ELEVATIONSA602 CASEWORK DETAILS AND MOUNTING HEIGHTSA700 WINDOW/DOOR SCHEDULEA701 DOOR AND WINDOW DETAILSA702 DOOR AND WINDOW DETAILS

    SHEET INDEX, ARCHITECTURAL

    C100 FIRE LINE SITE PLANC101 FIRE LINE PLAN AND PROFILEC102 FIRE LINE DETAIL SHEET

    SHEET INDEX, CIVIL

    SHEET INDEX, GENERAL SHEETS

    G100 GENERAL NOTESG200 CODE STUDY

  • 2

    OFFICE9

    1

    OFFICE10

    2

    OFFICE11

    1

    OFFICE12

    1

    OFFICE13

    2

    OFFICE14

    1

    FIRE RISER15

    1

    IT SERVER16

    1

    OFFICE18

    1

    OFFICE19

    1

    CUSTODIAL20

    1

    ELECTRICAL CLOSET21

    9

    BREAK ROOM22

    1

    OFFICE23

    1

    OFFICE24

    2

    OFFICE25

    1

    OFFICE261

    OFFICE27

    1

    OFFICE28

    13

    CONFERENCE 22

    21

    CONFERENCE 13

    2

    IT STORAGE5

    1

    OFFICE6

    2

    OFFICE7

    1

    OFFICE8

    2

    OFFICE35 1

    OFFICE34

    1

    OFFICE33

    2

    OFFICE32

    WOMEN30

    MEN292

    OFFICE37

    1

    OFFICE36

    -72

    CORRIDOR1

    -0

    CORRIDOR 317

    36240

    11240

    36 240

    240

    36310

    11 240

    9240

    6' -

    2 5/

    8"

    5' - 5 1/8"

    3' -

    8"

    5' -

    0 1/

    8"

    4' - 8 1/8"

    5' - 7 3/4"

    36 225

    Travel Distance - 142'-6"

    Trav

    el D

    ista

    nce

    - 122

    "-5"

    37' - 3 15/32"

    36 240

    5' -

    1 1/

    8"

    11240

    OCCUPANCY LOAD OF SPACE

    OCCUPANCY LOAD OF SPACE

    OCCUPLANCY LOAD OF SPACE, INCLUDING ACCESSORY SPACE

    NUMBER OF OCCUPANTS EXITING

    DOOR CAPACITY (0.XX PER INCH)

    NUMBER OF OCCUPANTS EXITING

    STAIR CAPACITY (0.XX PER INCH)

    OCCUPANCY LOAD TAG

    OCCUPANCY LOAD TAG

    STAIR EGRESS TAG

    DOOR EGRESS TAG

    1 HOUR FIRE BARRIER CONSTRUCTION

    1 HR

    SMOKE BARRIER

    SMOKE

    TRAVEL DISTANCE

    30' TRAVEL DISTANCE

    Name101XX

    XXXXXX

    Name101

    XXXXXX

    XXXXXX

    LEVEL 1 ALTERATIONS - RENOVATION CONSISTS OF REPLACEMENT OF FINISHES ONLY THIS AREA. 1,882 SF

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:17:18 PM

    G200

    CODE STUDY

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    Occupant Load Schedule

    Number Name Area Load Factor Occupant Load

    1 CORRIDOR 647 SF2 CONFERENCE 2 186 SF 15 133 CONFERENCE 1 311 SF 15 214 ADA UNISEX RESTROOM 63 SF5 IT STORAGE 415 SF 300 26 OFFICE 105 SF 150 17 OFFICE 182 SF 150 28 OFFICE 139 SF 150 19 OFFICE 172 SF 150 210 OFFICE 146 SF 150 111 OFFICE 156 SF 150 212 OFFICE 132 SF 150 113 OFFICE 136 SF 150 114 OFFICE 159 SF 150 215 FIRE RISER 98 SF 300 116 IT SERVER 174 SF 300 117 CORRIDOR 3 1071 SF18 OFFICE 142 SF 150 119 OFFICE 142 SF 150 120 CUSTODIAL 120 SF 300 121 ELECTRICAL CLOSET 132 SF 300 122 BREAK ROOM 121 SF 15 923 OFFICE 141 SF 150 124 OFFICE 140 SF 150 125 OFFICE 189 SF 150 226 OFFICE 138 SF 150 127 OFFICE 138 SF 150 128 OFFICE 135 SF 150 129 MEN 153 SF30 WOMEN 161 SF31 CORRIDOR 2 199 SF32 OFFICE 164 SF 150 233 OFFICE 122 SF 150 134 OFFICE 122 SF 150 135 OFFICE 159 SF 150 236 OFFICE 130 SF 150 137 OFFICE 195 SF 150 238 VESTIBULE 135 SF39 RAMP 213 SF40 STORAGE 158 SF41 ENTRY 68 SFGrand total: 41 7811 SF 80

    1/8" = 1'-0"G2001 Lower Level Code Plan

    CODE PLAN LEGENDCODE INFORMATION

    PROJECT NAME - EEC LOWER LEVEL RENOVATIONCLIENT - LARAMIE COUNTY COMMUNITY COLLEGELOCATION - CHEYENNE, WYOMINGCODES:

    2018 INTERNATIONAL BUILDING CODES2018 EXISTING BUILDING CODE2018 FIRE CODE2018 PLUMBING CODE2018 MECHANICAL CODE2017 NATIONAL ELECTRICAL CODE2018 INTERNATIONAL PLUMBING CODE

    SCOPE - RENOVATION OF THE LOWER GARDEN LEVEL OF THE EEC BUILDING INTO OFFICE SPACE. THE SPACE IS CURRENTLY A MIXTURE OF CLASSROOMS AND OFFICES. A SPRINKLER SYSTEM IS BEING INSTALLED AS PART OF THIS PROJECT FOR THE LOWER LEVEL ONLY. THE FIRE RISER WILL BE SIZED FOR THE UPPER FLOOR TO BE SPRINKLED AT A LATER TIME.

    AREA OF RENOVATION - 7,811 SF1,882 SF - REPLACING FINISHES5,929 SF - RENOVATION

    CONSTRUCTION TYPE - IIBFIRE SPRINKLER - YES, A NEW SPRINKLER IS BEING INSTALLED AS PART OF THIS PROJECT FOR THE LOWER LEVEL ONLY.OCCUPANCY - IBC - B OCCUPANCY

    PLUMBING FIXTURE COUNT

    CLASSIFICATION OF WORK -LEVEL 1 ALTERATION - 1,882 SFLEVEL 2 ALTERATION - 5,929 SF

    NO CHANGE IN OCCUPANCY

    NO ADDITIONS

    SECTION 803 - FIRE PROTECTIONCORRIDOR RATINGS - WHERE AN APPROVED AUTOMATIC SPRINKLER SYSTEM IS INSTALLED THROUGHOUT THE STORY, THE REQUIRED FIRE-RESISTANCE RATING FOR ANY CORRIDOR LOCATED ON THE STORY SHALL BE PERMITTED TO BE REDUCED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE.

    DEAD END CORRIDORS -50 FEET IN BUILDINGS EQUIPPED WITH AN AUTOMATIC FIRE ALARM.

    SECTION 809 PLUMBING -THE OCCUPANT LOAD HAS BEEN REDUCED AND NOT INCREASED BY MORE THAN 20 PERCENT. AN ADA RESTROOM HAS BEEN ADDED ALONG WITH THE EXISTING RESTROOM GROUPS.

  • W

    STST

    CO

    -0+06

    0+00

    1+00

    2+00

    3+00

    3+09

    BP: -

    0+05

    .94

    PI: 0

    +35.

    43

    PI: 1

    +71.

    66

    PI: 2

    +64.

    10

    EP: 3+09.29

    STA

    0+00

    .00

    DESIG

    N SP

    EED

    = 60 m

    i/h

    W

    W

    W

    W

    W

    W

    W

    W

    G

    S

    ST

    W

    UE

    W

    EXISTING GAS LINE

    EXISTING SANITARY SEWER LINE

    EXISTING STORM SEWER LINE

    EXISTING WATER LINE

    EXISTING UNDERGROUND ELECTRICAL LINE

    EXISTING MAJOR CONTOUR

    EXISTING MINOR CONTOUR

    PROPOSED FIRE LINE

    EEC BUILDING

    PROPOSED 6" DUCTILE IRON FIRE LINE

    TIE INTO EXISTING WATER LINEAPPROXIMATELY 6.5' DEEP

    CONNECT TO BUILDINGFIRE LINE (SEE MECHANICAL)

    12'

    10'

    BUSINESS AND TECHNOLOGYBUILDING

    SAWCUT EXISTING CONCRETE AND REPLACEAT EXISTING JOINTS

    SAWCUT EXISTING CONCRETE AND REPLACEAT EXISTING JOINTS ST

    GENERAL NOTES

    1. MAINTAIN A MINIMUM COVER OF 6.5-FEET OVERPROPOSED FIRE LINE

    2. MAINTAIN A MINIMUM OF 18-INCHES OF SEPARATIONAT SANITARY AND STORM SEWER CROSSINGS. IFSEPARATION IS LESS THAN 18-INCHES CONTRACTORSHALL INSTALL CROSSING PROTECTION PER DETAIL ONSHEET C102.

    3. THE UTILITY LOCATIONS SHOWN ARE AS MARKED BYTHEIR OWNERS, FROM THE OWNERS RECORDS. THE SIZEAND LOCATION OF UNDERGROUND UTILITIES WAS NOTVERIFIED BY EXCAVATION. THE CONTRACTOR ISRESPONSIBLE FOR LOCATING AND PROTECTING UTILITIESDURING CONSTRUCTION.

    4. EXISTING UTILITIES BURIED DEPTHS ARE SHOWN FORREFERENCE AND CONVENIENCE ONLY. ACTUAL DEPTHSHAVE NOT BEEN VERIFIED BY EXCAVATION.

    5. IRRIGATION LINES ARE NOT SHOWN ON DRAWING.CONTRACTOR RESPONSIBLE FOR LOCATING ANDPROTECTING/REPLACING ANY IRRIGATION LINES FOUNDDURING CONSTRUCTION.

    EXISTING SIDEWLAKS

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designsincorporated herein, as an instrument ofprofessional service, is the property of Tobin &Associates, P.C. Tobin & Associates, P.C. arethe author of this document and retain allcommon law, statutory and other reservedrights, including copyright. This document isnot to be used, in whole or part, for any otherproject without the written authorization ofTobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA,ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    3/11/2019 2:15:50 PM

    C100

    FIRE LINE SITE PLAN

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 8200

    Bill Zink (307) 778-5222

    LCCC EDUCATIONAL

    ENRICHMENT CENTER

    BASEMENT RENOVATION

    1400 E College Dr,Cheyenne, WY 82007

    20 20

    10

    SCALE 1"=20'

    100% CDs 03/19/19

    \\IM

    ESRVD

    C01\Projects\20422 H

    E TO

    BIN

    AN

    D ASSO

    CIATES LCCC EEC Fire Line\D

    WG

    \LCCC EEC Titleblock M

    AR11.dw

    g, Site Plan, 3/18/2019 4:38:57 PM

  • 5995

    6000

    6005

    6010

    5995

    6000

    6005

    6010

    -0+05 0+00 0+50 1+00 1+50 2+00 2+50 2+95

    Underground Electric Crossing@ Station 2+49.32

    10" Existing Sewer Crossing@ Station 2+74.10

    Storm Sewer CatchBasin Crossing @ Station

    1+86.14

    10" Existing Storm Sewer@ Station 0+23.48

    Tie Into Existing 6"Waterline with Thrust Blocking@ Station 0+00

    Install 6" Gate Valve withThrust Blocking @ Station 0+05

    Install Bend with withThrust Blocking @ Station 0+35.43

    Install Bend withThrust Blocking @ Station 1+71.66

    Install Bend withThrust Blocking @ Station 2+64.10

    Dip pipe per detail 537

    Connect to Building Firelane (See Mechanical Drawings)

    6" Gate Valve with Thrust Blocking

    W

    W

    ST

    ST

    ST

    ST

    CO

    -0+060+00

    1+00

    2+00

    3+00

    3+09

    BP: -0

    +05.9

    4

    PI: 0+

    35.43

    PI: 1

    +71.

    66

    PI: 2

    +64.

    10

    EP: 3+09.29

    STA 0

    +00.0

    0

    DESIG

    N SPE

    ED =

    60 m

    i/h

    W W W W W W W W W W W W W W W W W W

    STST

    3/11/2019 2:15:50 PM

    C101

    FIRE LINE PLAN ANDPROFILE

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 8200

    Bill Zink (307) 778-5222

    LCCC EDUCATIONAL

    ENRICHMENT CENTER

    BASEMENT RENOVATION

    1400 E College Dr,Cheyenne, WY 82007

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designsincorporated herein, as an instrument ofprofessional service, is the property of Tobin &Associates, P.C. Tobin & Associates, P.C. arethe author of this document and retain allcommon law, statutory and other reservedrights, including copyright. This document isnot to be used, in whole or part, for any otherproject without the written authorization ofTobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA,ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    10 10

    5

    SCALE 1"=10'

    100% CDs 03/19/19

    P:\20422 H

    E TO

    BIN

    AN

    D ASSO

    CIATES LCCC EEC Fire Line\D

    WG

    \LCCC EEC Titleblock M

    AR11.dw

    g, Plan &

    Profile, 3/18/2019 4:39:14 PM

  • 3/11/2019 2:15:50 PM

    C102

    FIRE LINE DETAIL SHEET

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 8200

    (307) 778-5222

    LCCC EDUCATIONAL

    ENRICHMENT CENTER

    BASEMENT RENOVATION

    1400 E College Dr,Cheyenne, WY 82007

    DATE

    PLOTTED ON:

    ARCHITECT #:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designsincorporated herein, as an instrument ofprofessional service, is the property of Tobin &Associates, P.C. Tobin & Associates, P.C. arethe author of this document and retain allcommon law, statutory and other reservedrights, including copyright. This document isnot to be used, in whole or part, for any otherproject without the written authorization ofTobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA,ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    100% CDs 03/19/19

    P:\20422 H

    E TO

    BIN

    AN

    D ASSO

    CIATES LCCC EEC Fire Line\D

    WG

    \LCCC EEC Titleblock M

    AR11.dw

    g, D

    etail, 3/18/2019 4:39:19 PM

  • UP

    UP

    UP

    UP

    UP

    87' - 1 1/8" INSIDE TO INSIDE

    86' -

    6 1

    /2" I

    NSI

    DE

    TO IN

    SID

    E

    D24

    D02

    D02

    D02

    D02

    D02D02

    D02D02

    D02D02

    D02

    D02

    D02

    D02

    D02

    D02D02

    D02

    D02D02

    D02

    D02

    D02D02

    D02

    D02

    D03D03 D03

    D03D03

    D03

    D03

    D03

    D03D03

    D03 D03

    D03

    D03

    D03

    D03

    19' -

    10

    5/8"

    3' -

    4 7/

    8" 10' -

    3 1

    /4"

    19' -

    11

    3/8"

    74' - 10 5/16"

    5' -

    6"

    12' -

    1 3

    /8"

    46' -

    11

    5/8"

    2' - 4"

    3' -

    0 7/

    8"7'

    - 6

    3/4"

    4' -

    4 3/

    8"6'

    - 4

    5/8"

    5' - 1 3/4" 10' - 5 7/8" 9' - 9 5/8" 8' - 3 1/2" 4' - 1 15/16"

    D19

    D08

    D14

    D14

    D03

    D18

    D02

    D02

    D04

    D04

    D03

    D04

    D04D04

    D04

    D02

    D18

    D18

    D18

    D18

    D18

    D25

    D12 D12 D12

    D12

    D12

    D12 D12D12D12

    D12

    D12

    D12

    D27

    D06

    D14

    B B

    A A

    C

    1

    1

    2

    2 3

    4

    4

    5

    5

    2.9 3.1

    D05

    D23

    D23

    D21

    D21

    D21

    D09

    D07

    D21

    D10 D10 D10

    D10

    D10

    D10D10

    D10

    D10

    D10

    D10

    D11D13

    D26 D26 D26 D26

    D26

    D26

    D16

    D03D17

    D26 D26

    D26

    D26

    D26

    3A100

    D0 D0

    D0

    D0

    D0

    D0

    D0

    D0

    D0

    D0D0

    D0

    D0

    D0

    D0

    D0 D0

    D0

    D0

    D0

    D0

    D0D0D0D0

    D0

    D0

    D0

    D28

    D17

    D17

    D1

    D29

    D30

    D01 D01 D01

    D01 D01

    D01

    D01

    D01

    D01

    D01

    D01

    D01

    D01

    D01

    D01

    D01D01

    D01

    D01 D01

    D01

    D01

    D01

    D01D01 D01

    D01

    D01

    D01

    D01

    B B

    A A

    C C

    1

    1

    2

    2 3

    4

    4

    5

    5

    2.9 3.1

    D15

    D22

    1. CONTRACTOR SHALL PROTECT EXISTING CONSTRUCTION TO REMAIN FROM DAMAGE DURING DEMOLITION ACTIVITIES. ANY DAMAGE THAT OCCURS SHALL BE REPAIRED TO THE FULL SATISFACTION OF THE OWNER AT NO ADDITIONAL COST TO THE OWNER.

    2. CONTRACTOR SHALL FIELD VERIFY EXISTING CONSTRUCTION PRIOR TO THE START OF DEMOLITION. NOTIFY THE ARCHITECT OF ANY DISCREPANCIES BETWEEN (E) CONDITIONS AND CONSTRUCTION DOCUMENTS IMMEDIATELY.

    3. CONTRACTOR SHALL COORDINATE ANY WORK REQUIRED IN ADJACENT AREAS, OUTSIDE OF LIMITS OF PHASED RENOVATIONS, WITH OWNER PRIOR TO THE START OF WORK.

    4. COORDINATE RENOVATIONS WITH MECHANICAL, PLUMBING AND ELECTRICAL SYSTEMS.

    5. EXISTING BUILDING ENVELOPE SHALL BE MAINTAINED IN A WATER TIGHT CONDITION AT ALL TIMES THROUGHOUT ALL PHASES OF CONSTRUCTION.

    6. CONTRACTOR SHALL NOT BLOCK EGRESS (EXIST, STAIRS, ETC.) FROM THE BUILDING AT ANY TIME THAT THE BUILDING IS OCCUPIED.

    7. CONTRACTOR TO DEMOLISH ALL EXISTING INTERIOR SIGNAGE.

    LEVEL 01100' - 0"

    3' - 1" +/- VIF

    DEMO EXISTING CONCRETE STEPS AND PORTION OF

    EXISTING RAMPDATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:09:26 PM

    A100

    DEMOLITION FLOOR ANDREFLECTED CEILING PLAN

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    N 1/8" = 1'-0"A100

    2 DEMOLITION - FLOOR PLAN

    GENERAL NOTES KEYNOTES

    D01 REMOVE EXISTING ACOUSTICAL TILE CEILING AND GRID.D02 DEMOLISH EXISTING STUD FRAMED WALL PARTITION.D03 DEMOLISH EXISTING DOOR, HOLLOW METAL FRAME AND HARDWARE.D04 DEMOLISH EXISTING HOLLOW METAL WINDOW AND FRAME.D05 DEMOLISH EXISTING CASEWORKD06 REMOVE ALUMINUM STOREFRONT, SALVAGE DECORATIVE OAK BAND.D07 DEMOLISH PORTION OF RAMP AND LANDING SHOWN WITH DIAGONAL HATCHD08 REMOVE EXISTING CARPET FLOORING AND BASE. PREPARE SUBSTRATE FOR NEW FLOORING AS NECESSARY.D09 DEMOLISH EXISTING CONCRETE STEPSD10 DEMOLISH EXISTING WINDOW BLINDS.D11 DEMOLISH EXISTING DOOR, HOLLOW METAL FRAME AND HARDWARED12 EXISTING WINDOW TO REMAIN.PROTECT EXISTING WINDOWS DURING RENOVATION.D13 INFILL WALL OPENING WITH LIKE CONSTRUCTION.D14 DEMOLISH EXISTING HANDRAILD15 REMOVE EXISTING CEILING SOUND SYSTEMD16 DEMOLISH WALK OFF GRATING.D17 SAWCUT SLAB FOR SANITARY SEWER INSTALLATION. COORDINATE WITH MECHANICALD18 EXISTING VINYL WALL COVERING TO BE REMOVED. SKIM COAT GYPSUM WALL BOARD FINISH AS NECESSARY TO MATCH EXISTING

    ADJACENT WALLS. REMOVAL AND REPLACEMENT OF EXISTING DRYWALL IS AN ACCEPTABLE CONTRACTOR OPTION IN LIEU OFSKIM COAT.

    D19 EXISTING FIRE EXTINGUISHER CABINETD21 SAW CUT AND REMOVE PORTION OF PRECAST CONCRETE PANEL FOR INSTALLATION OF NEW HM WINDOW FRAME. SEE WINDOW

    FRAME TYPES FOR SIZES.D22 REMOVE EXISTING CEILING MOUNTED PROJECTOR. RETURN TO OWNER.D23 DEMOLISH WALL CHAIR RAILD24 EXISTING ELECTRICAL PANEL.D25 EXISTING ELECTRICAL PANEL TO BE RELOCATED. COORDINATE WITH ELECTRICAL.D26 REMOVE PORTION OF INTERIOR FRAMING AND GYPSUM WALL FOR INSTALLATION OF NEW HM WINDOW FRAME. SEE FLOOR PLAN

    FOR LOCATIONSD27 DEMOLISH WATER FOUNTAIN.D28 REMOVE EXISTING VCT FLOORING AND BASE. PREPARE SUBSTRATE FOR NEW FLOORING AS NECESSARY.D29 DEMOLISH EXISTING SINKD30 SAWCUT SLAB FOR INSTALLATION OF NEW RAMP

    1/8" = 1'-0"A100 REF: A100 / 31 DEMOLITION - CEILING PLAN

    N

    1" = 1'-0"A100 REF: A100 / 23 DEMO SECTION

  • ELECTRICALCLOSET

    21

    OFFICE9

    OFFICE10

    OFFICE11

    OFFICE12

    OFFICE13

    OFFICE14

    FIRE RISER15

    IT SERVER16

    OFFICE8

    IT STORAGE5

    OFFICE6

    OFFICE18

    OFFICE19

    CUSTODIAL20

    BREAK ROOM22

    OFFICE23

    OFFICE24

    OFFICE25

    OFFICE27

    OFFICE28

    OFFICE7

    OFFICE26

    OFFICE32

    OFFICE33

    OFFICE34

    OFFICE35

    OFFICE36

    OFFICE37 MEN

    29

    WOMEN30

    CONFERENCE 13

    CONFERENCE 22

    CORRIDOR 231 CORRIDOR

    1

    CORRIDOR 317

    W-1

    A3008

    A3007

    A601

    6

    A6017

    ADA UNISEXRESTROOM

    4W-2

    3

    5

    2

    28

    9

    8

    4

    16

    18

    19

    20

    22

    23

    24

    7 6

    10 11 12 13 14

    15

    27 26

    25

    1

    4 58

    4

    5

    HM-6

    17A

    1

    1

    1

    1

    1

    1

    1

    1

    7

    2210

    RICHARD

    TIM

    ERIC KENMIKE

    EDIE

    KIM

    CHAD

    JOHN

    TED

    JOSH

    AUSTIN

    A601

    11

    A601 16

    A601

    12

    W-1

    W-1

    W-1

    W-1

    W-1W-1

    W-1W-1

    W-1

    W-1W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    W-1

    A6011

    A3001

    10

    13

    HM-5 HM-5

    HM-5

    HM-5

    HM-5

    HM-4

    HM-4

    HM-4

    HM-4 HM-4 HM-4

    17

    B B

    A A

    C C

    1

    1

    2

    2

    3

    3

    4

    4

    5

    5

    2.9 3.1

    A601

    8

    A101

    2

    RAMP39

    STORAGE40

    HM-7 HM-7 HM-7

    10

    9A300

    32

    32

    32

    32

    33

    34

    34

    34

    34

    VICTORIA

    W-3

    1

    35

    36

    3737 DN DN

    DN31

    A601 14

    A30011

    A101 5

    A101

    4

    A1013A6019

    A7006

    17A701

    VESTIBULE38

    A601 15

    E31

    36

    48 49

    37

    38

    1

    9

    9

    5655

    57

    54

    AL-8

    11

    W-1

    HM-6

    60

    60

    61

    62

    59

    31

    AL-9

    AL-1

    0

    AL-1

    1

    36

    66

    68

    66

    68

    67

    ENTRY41

    WALL TYPE: W1

    5/8" GYPSUM BOARD3 5/8" METAL STUD FRAMING AT 16" O.C.20 GA.SOUND BATT INSULATION WHERE SHOWN

    NOTE: UNLESS OTHERWISE NOTED, ALL WALLS SHALL EXTEND A MIN. OF 4" ABOVE FINISHED CEILING AND HAVE A SMOOTH FINISH.

    WALL TYPE: W2

    5/8" GYPSUM BOARD6" METAL STUD FRAMING AT 16" O.C., 20 GA.SOUND BATT INSULATION WHERE SHOWN

    WALL TYPE: W3

    EXISTING 5/8" GYPSUM BOARD TO REMAIN7/8" HAT CHANNEL AT 16" O.C.EXISTING CMU WALL TO REMAINNEW LAYER OF 5/8" GYPSUM BOARD

    WALL TYPE: W4

    5/8" GYPSUM BOARD3 5/8" METAL STUD FRAMING AT 16" O.C.20 GA.

    1. DO NOT SCALE DRAWINGS. FIELD VERIFY ALL DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY IF DISCREPANCIES ARE DISCOVERED.

    2. PROVIDE VERTICAL CONTROL JOINTS AT GYPSUM BOARD WALLS EXCEEDING 30'-0" MAXIMUM LENGTH. PROVIDE JOINTS AT DOOR HEAD ON LATCH SIDE AND AT WINDOWS ABOVE AND BELOW WINDOW ON ONE SIDE. COORDINATE JOINT LOCATIONS WITH ARCHITECT.

    3. CONTRACTOR SHALL SEAL ALL NEW AND EXISTING THROUGH WALL PENETRATIONS.

    4. CONTRACTOR SHALL COORDINATE LOCATIONS AND ELEVATIONS OF ELECTRICAL OUTLETS, DATA OUTLETS, SWITCHES AND ANY OTHER WALL MOUNTED EQUIPMENT WITH CASEWORK, FURNISHINGS AND OTHER EQUIPMENT SHOWN ON ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. CONTACT ARCHITECT SHOULD DISCREPANCIES EXIST.

    5. CONTRACTOR SHALL COORDINATE AND PROVIDE BLOCKING AT LOCATIONS WHERE WALL MOUNTED EQUIPMENT IS TO BE INSTALLED.

    6. PROTECT EXISTING CONSTRUCTION DURING DEMOLITION AND RENOVATION ACTIVITIES. CONTRACTOR SHALL REPAIR OR REPLACE ANY PORTIONS OF EXISTING BUILDING DAMAGED DURING THESE ACTIVITIES AT NO COST TO OWNER.

    7. CONTRACTOR SHALL COORDINATE WORK BETWEEN ALL TRADES AND RESPECTIVE MECHANICAL, ELECTRICAL AND ARCHITECTURAL SCOPES OF WORK AND INFORM ARCHITECT OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.

    8. ALL HOLLOW METAL DOORS AND DOOR FRAMES (NEW AND EXISTING, INTERIOR AND EXTERIOR), TO BE PAINTED PAINT COLOR 8.

    9. NEW HORIZONTAL BLINDS AT ALL WINDOWS.

    LEVEL 01100' - 0"

    8" M

    IN. V

    IF

    HM-4 HM-4 HM-4 HM-4

    WINDOW HEAD HT.111' - 5"

    4140 40 40

    46 42

    40

    LEVEL 01100' - 0"

    HM-5 HM-5 HM-5

    MIN

    8" V

    IF

    WINDOW HEAD HT.111' - 5"

    40

    46

    40 40

    42

    LEVEL 01100' - 0"

    HM-5 HM-5

    8" M

    IN. V

    IF

    WINDOW HEAD HT.111' - 5"

    4140

    43

    4041

    4642

    67

    LEVEL 01100' - 0"

    HM-4 HM-4 HM-4

    8" M

    IN. V

    IF 40

    46 42

    45

    40 40

    1/2" MIN. OF FLEXIBLE SEALANT

    DRYWALL J-BEAD APPLIED TO TOP EDGE OF FACELAYER OF GYP BOARD

    FIRE RATED - TOP OF WALLFIRE RESISTANCE AND SOUND CONTROL,

    DESIGN MANUAL - GYPSUM SYSTEMSGA - 600 - 2018

    SRS 7101

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:09:58 PM

    A101

    FLOOR PLAN

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007GENERAL NOTES KEYNOTES

    WALL TYPES

    1/8" = 1'-0"A1011 LOWER LEVEL FLOOR PLAN

    N

    49 SAW CUT AND REMOVE EXISTING SLAB AS NECESSARY FOR INSTALLATION OF NEW FIRE RISER.COORDINATE WITH MECHANICAL, SEE TYPICAL INFILL DETAIL 2/A600.

    54 EXISTING ADA OPERATOR SWITCH TO REMAIN55 ACCESS CONTROL CARD READER. INSTALL AT NEW STOREFRONT.56 REUSE EXISTING ADA OPERATOR.57 REUSE EXISTING DOOR OPERATOR. REMOVE AND REINSTALL FOLLOWING INSTALLATION OF NEW

    STOREFRONT AND DOOR ASSEMBLY.58 WALL INFILL WHERE DOOR OR FRAME HAVE BEEN REMOVED. INFILL WITH STUD FRAMING AND GYPSUM

    BOARD, SEE DETAIL 12/A300.59 MOP HOLDER WITH SHELF, SEE SHEET A700 FOR TYPICAL MOUNTING HEIGHT.60 EXISTING ALUMINUM STAIR TREADS TO REMAIN.61 INSTALL NEW ALUMINUM FRAMED STOREFRONT.62 EXISTING STOREFRONT TO REMAIN.66 FIRE RATED TOP OF WALL. SEE DETAIL ON A101.67 EXISTING DRAIN TO REMAIN.68 FIRE CAULK TOP OF EXISTING WALL.

    1 ALIGN NEW FINISHES WITH EXISTING ADJACENT WALL.4 WALL INFILL WHERE DOOR OR FRAME HAVE BEEN REMOVED. INFILL WITH SIMILAR WALL

    CONSTRUCTION.5 MOP SINK LOCATION. SEE DETAIL 8/A602, COORDINATE WITH PLUMBING.7 REFRIGERATOR, OWNER PROVIDED. WATER CONNECTION NEEDED, SEE PLUMBING.9 EXISTING HANDRAIL TO REMAIN.10 TELEVISION, OWNER PROVIDED. COORDINATE WITH ELECTRICAL. PROVIDE BLOCKING AS NECESSARY.

    CONTRACTOR TO PROVIDE UNIVERSAL MOUNT. COORDINATE FINAL MOUNTING HEIGHT WITHOWNER/ARCHITECT.

    11 EXISTING FIRE EXTINGUISHER CABINET RELOCATED, SEE SHEET A700 FOR TYPICAL MOUNTING HEIGHT.22 PRINTER, OWNER PROVIDED. PROVIDE POWER AND DATA AS REQUIRED. COORDINATE WITH

    ELECTRICAL.31 EXISTING HANDRAIL TO REMAIN. SAND AND REFINISH TO BLEND WITH NEW HANDRAIL.32 EXTEND WALLS TO DECK. FRAMING AROUND NEW AND EXISTING PLUMBING REQUIRED. COORDINATE

    WITH MECHANICAL.33 MURAL, SEE SPECIFICATIONS.34 WOOD ACCENT WALL, SEE SHEET A600.35 CORE DRILL FOR EXHAUST, 8" ROUND. COORDINATE WITH MECHANICAL.36 SAW CUT EXISTING SLAB FOR INSTALLATION OF NEW WASTE LINES. COORDINATE WITH MECHANICAL.

    SEE TYPICAL INFILL DETAIL 2/A600.37 REPLACE EXISTING HANDRAIL WITH NEW, TO MATCH EXISTING SIZE, SHAPE AND COLOR.40 NEW WINDOW, MATCH EXISTING WINDOW HEIGHT.41 EXISTING WINDOW TO REMAIN.42 FOLLOWING INSTALLATION OF NEW WINDOW UNITS, TOUCH UP HIGH PERFORMANCE COATING AT

    EXTERIOR WALL AS NECESSARY (TYPICAL)43 EXISTING CONDENSING UNIT, PROTECT DURING CONSTRUCTION ACTIVITIES45 PROTECT EXISTING SHRUBS DURING CONSTRUCTION ACTIVITIES46 EXISTING DECORATIVE PRECAST BAND TO REMAIN.48 CORE DRILL EXISTING WALL AS NECESSARY FOR INSTALLATION OF NEW FIRE LINE. SEE CIVIL AND

    MECHANICAL DRAWINGS.

    1/8" = 1'-0"A101 REF: A101 / 12 PARTIAL BUILDING ELEVATION - NORTH

    1/8" = 1'-0"A101 REF: A101 / 13 PARTIAL BUILDING ELEVATION - EAST

    1/8" = 1'-0"A101 REF: A101 / 14 PARTIAL BUILDING ELEVATION - SOUTH

    1/8" = 1'-0"A101 REF: A101 / 15 PARTIAL BUILDING ELEVATION - WEST

  • UPUP

    UP

    UP

    ELECTRICALCLOSET

    21

    87' - 1 1/8"

    86' -

    6 1

    /2"

    OFFICE9

    OFFICE10

    OFFICE11

    OFFICE12

    OFFICE13

    OFFICE14

    FIRE RISER15

    IT SERVER16

    OFFICE8

    IT STORAGE5

    OFFICE6

    OFFICE18

    OFFICE19

    CUSTODIAL20

    BREAK ROOM22

    OFFICE23

    OFFICE24

    OFFICE25

    OFFICE27

    OFFICE28

    OFFICE7

    OFFICE26

    OFFICE32

    OFFICE33

    OFFICE34

    OFFICE35

    OFFICE36

    OFFICE37 MEN29

    WOMEN30

    CONFERENCE 13

    CONFERENCE 22

    14' - 10" 10' - 10" 11' - 6 3/16" 10' - 2 7/8" 10' - 0 3/4" 11' - 8 1/4"

    14' -

    4"

    11' -

    0"

    12' - 9"

    16' -

    0"

    9' -

    4 1/

    2"

    8' - 8 1/2" 8' - 10" 19' - 11 7/16"

    9' -

    9"9'

    - 8"

    9' -

    3"8'

    - 4"

    8' -

    0 1/

    4"

    14' - 5" +/-

    11' - 11" 3' - 2"

    17' - 0 1/8"

    5' -

    6 1/

    2"

    11' -

    4 1

    /4"

    15' - 1"

    2' -

    2"

    9' - 0"

    5' -

    8"14

    ' - 3

    "

    1' -

    6"

    7' - 11 3/4" +\- 9' - 11 5/16" +\-

    4' -

    5 1/

    2" +

    \-9'

    - 9

    3/4"

    +\-

    9' -

    3 1/

    2" +

    \-17

    ' - 1

    1 1/

    8" +

    \-

    15' -

    8 7

    /8" 6

    ' - 5

    7/8

    "5'

    - 5"

    7' -

    11 1

    /2"

    10' -

    4"

    5' -

    8"3'

    - 7

    1/2"

    3' -

    0"2'

    - 9"

    5' -

    5"

    ADA UNISEXRESTROOM

    4

    5' - 6 1/2" 15' - 1 1/2"

    23' -

    10"

    B B

    A A

    C C

    1

    1

    2

    2 3

    4

    4

    5

    5

    2.9 3.1

    5' - 10" 14' - 5" +/-

    5' -

    6 3/

    4"13

    ' - 5

    3/8

    "

    15' - 1"

    7 3/8"

    7 3/8"8' - 0" 8' - 0" 8' - 4 11/32"

    12' - 1 3/4"

    1' - 8"

    20' -

    2 5

    /8"

    8' -

    1 1/

    2"11

    ' - 1

    "

    6' -

    7 1/

    2"13

    ' - 6

    1/4

    "

    9' - 4 1/2"

    9' -

    3 5/

    8"

    17' - 7 3/16" +/- 19' - 11" +/- 12' - 6 1/4" +/-

    15' -

    10

    1/2"

    +/-

    9' -

    10 1

    /4" +

    /-10

    ' - 1

    0 3/

    4" +

    /-

    9' - 11" +/- 9' - 11" +/-9' - 3 1/16" +/-

    6' - 3 1/2"

    22' - 6 1/8" 9' - 0" 14' - 5" +/-17' - 3 15/32"

    4' - 10 3/4" +/-

    8' -

    0" +

    /-

    13' - 9 9/16"

    ENTRY41

    1. DO NOT SCALE DRAWINGS. FIELD VERIFY ALL DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY IF DISCREPANCIES ARE DISCOVERED.

    2. PROVIDE VERTICAL CONTROL JOINTS AT GYPSUM BOARD WALLS EXCEEDING 30'-0" MAXIMUM LENGTH. PROVIDE JOINTS AT DOOR HEAD ON LATCH SIDE AND AT WINDOWS ABOVE AND BELOW WINDOW ON ONE SIDE. COORDINATE JOINT LOCATIONS WITH ARCHITECT.

    3. CONTRACTOR SHALL SEAL ALL NEW AND EXISTING THROUGH WALL PENETRATIONS.

    4. CONTRACTOR SHALL COORDINATE LOCATIONS AND ELEVATIONS OF ELECTRICAL OUTLETS, DATA OUTLETS, SWITCHES AND ANY OTHER WALL MOUNTED EQUIPMENT WITH CASEWORK, FURNISHINGS AND OTHER EQUIPMENT SHOWN ON ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. CONTACT ARCHITECT SHOULD DISCREPANCIES EXIST.

    5. CONTRACTOR SHALL COORDINATE AND PROVIDE BLOCKING AT LOCATIONS WHERE WALL MOUNTED EQUIPMENT IS TO BE INSTALLED.

    6. PROTECT EXISTING CONSTRUCTION DURING DEMOLITION AND RENOVATION ACTIVITIES. CONTRACTOR SHALL REPAIR OR REPLACE ANY PORTIONS OF EXISTING BUILDING DAMAGED DURING THESE ACTIVITIES AT NO COST TO OWNER.

    7. CONTRACTOR SHALL COORDINATE WORK BETWEEN ALL TRADES AND RESPECTIVE MECHANICAL, ELECTRICAL AND ARCHITECTURAL SCOPES OF WORK AND INFORM ARCHITECT OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.

    8. ALL HOLLOW METAL DOORS AND DOOR FRAMES (NEW AND EXISTING, INTERIOR AND EXTERIOR), TO BE PAINTED PAINT COLOR 8.

    9. NEW HORIZONTAL BLINDS AT ALL WINDOWS.

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:10:05 PM

    A102

    DIMENSION PLAN

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007GENERAL NOTES

    1/8" = 1'-0"A1021 DIMENSION FLOOR PLAN

    N

  • 4" +\-

    CAULK TRANSITIONS AS NEEDED

    EXISTING CHASE TO REMAIN

    3 5/8" METAL STUD FRAMING

    5/8" GYPSUM BOARD

    A

    EXISTING DRAIN TO REMAIN

    EXISTING ROOF DRAIN PIPING TO REMAIN, EXISTING GRILLE TO ALLOW AIR FLOW TO REMAIN

    SEE WALL TYPES

    B

    3

    5/8" GYPSUM BOARD,ADHERE GYP. BOARD TO PRECAST CONCRETE COLUMN

    "L" MOLD AND SEALANT

    EXISTING PRECASTCONCRETE COLUMNTO REMAIN, SACK RUB AND PAINT WHERE EXPOSEDPAINT COLOR 1

    SEE WALL TYPES

    1 3/4" 3/4"3/4"

    1 1/

    4"1

    1/2"

    1 1/

    4"1

    1/2"

    1/2" RADIUS

    OAK

    GLUE

    HANDRAIL SUPPORT @ 4' -0" O.C. MAX

    1-2/"X1-1/2" X 1/4" X 4" STEEL ANGLE

    WOOD SCREWS

    COUNTERSUNK MACH. SCREWS AND EXP. SHIELDS

    AT CMU WALLS, WD SCREWS AT DRYWALL PARTITION, PROVIDE

    BLOCKING AS NECESSARY1

    1/2"

    3' - 0"

    3/4" 2 1/2" 3/4"

    1 1/4"1 1/2"1 1/4"

    HANDRAIL SUPPORT @ 4' -0" O.C. MAX, PROVIDE BLOCKING

    1 3/4"

    1 1/

    2"

    B

    2 3

    DNDN

    2A300

    HM-7 HM-7 HM-7

    NEW RAMP ADDITION

    3A300

    4' -

    8"5'

    - 0

    1/2"

    23' - 11 3/8" 5' - 2" 6' - 7" 5' - 1"

    A601 15

    7/8" / 12"102' - 8"100' - 11"

    100' - 4 3/8"

    100' - 0"

    1' -

    0"

    EXISTING HANDRAILNEW HANDRAIL

    EXISTING HANDRAILTO REMAIN

    AL-1

    1

    11

    SEE PLAN FOR WALL TYPE AND HEIGHT

    4" A

    T PA

    RTI

    AL H

    EIG

    HT

    WAL

    LS

    SUSPENDED ACOUSTIC TILE

    SUSPENSION WIRE TO STRUCTURE

    ABOVE

    3 5/8" METAL STUD BRACING, 32" O.C. AT PARTIAL HEIGHT WALLS

    SUSPENDED CEILING EDGE GRID

    EXISTING CMU, ANDGYPSUM BOARD TO REMAIN

    3/8" METAL STUD FRAMING

    5/8" GYPSUM BOARD

    REPAINT ENTIRE EXISTING WALL AND INFILL, PAINT COLOR 1

    8' - 9"

    7' - 2"

    RECESSED CAN LIGHTING, SEE ELECTRICAL

    ACOUSTICAL CEILING TILE,SEE REELECTED CEILING PLAN

    SUSPENDED CEILING EDGE GRID

    1' -

    7"

    EXTEND TO DECK

    W-1 UPPER CABINET WITH TRIM, SEE A602

    3 5/8" METAL STUD FRAMING

    W-4, 5/8" GYPSUM BOARD, TAPE, FINISH AND PAINT COLOR 9

    6"

    3"

    A7015

    A7017

    8" M

    IN

    HM-510"

    6"

    160.

    00°

    3 5/8" METAL STUD FRAMING

    W-1, 5/8" GYP BOARD,TAPE, FINISH AND

    PAINT COLOR 9

    W-4, 3 5/8" METALSTUD FRAMING

    EXISTING EXTERIORTWIN TEE

    SUSPENDED ACOUSTIC TILE AND CEILING

    EDGE GRID

    1"

    ACOUSTICAL CEILING TILE,SEE REELECTED CEILING PLAN

    SUSPENDED CEILING EDGE GRID

    NEW ALUMINUM/GLASS STOREFRONT, SEE 17/A701

    VERTICAL ACOUSTIC CEILING TILE AND TRACK

    107' - 10 1/2"

    107' - 7"

    7' - 2"

    EXPOSED STRUCTURE TO BE PAINTED, PAINT COLOR 1

    SUSPENDED ACOUSTIC TILE AND CEILING EDGE GRID, REFERENCE REFLECTED CEILING PLAN

    7' -

    10"

    3' -

    0"

    PERFORATED METAL CEILING PANEL, SEE A301

    HM-7 HM-7 HM-7

    EXISTING TWIN TEE STRUCTURELIGHTING, SEE REFLECTEDCEILING PLAN, REFERENCE ELECTRICAL

    NEW HANDRAIL,TO MATCH EXISTINGSEE 5/A301

    EXISTING CONCRETE RAMP AND LANDING TO REMAIN,REFERENCE DEMOLITION PLAN FOR PORTION REMOVED

    3 5/8" METAL STUD FRAMING, COORDINATEEXACT LOCATION OF BULKHEAD WITHLOCATION OF EXISTING DUCTWORK

    1:12

    1' - 0"20' - 4"6' - 0"

    HANDRAIL BRACKET BEHIND,4' - 0" O.C. MAX, SEE 5/A301

    9' - 8 1/2"

    3' -

    0"

    7' -

    9"

    A3016

    COORDINATE EXACT LOCATION OF BULKHEAD WITH LOCATION OF EXISTING DUCTWORK

    A3005

    A3004

    100' - 4 3/8"100' - 11"

    102' - 8"

    EXISTING SLAB

    #3 AT 12" O.C. EA WAY

    DOWEL EA #3 BAR 4" INTO (E) SLAB AND EPOXY W/ HILTI HY 200 EPOXY

    2"

    33 33

    1' - 0" 1' - 5"

    OPEN TO BEYOND

    DUCTDUCT

    7/8" HAT CHANNEL

    5/8" GYPSUM BOARD

    2 1/2" METAL STUD FRAMING

    EXISTING GYP. BOARD WALL TO REMAIN

    1:124' -

    0"

    1' - 0" 4' - 11"

    HANDRAIL BRACKET BEHIND,4' - 0" O.C. MAX, SEE 5/A301

    PERFORATED METAL CEILING PANEL, SEE A301

    A3006

    SEE REFLECTED

    CEILING PLAN

    100' - 4 3/8"

    W-1, GYP. BOARD BULKHEAD,PAINT COLOR TO BE SELECTED

    108' - 0"

    EXISTING SLAB#3 AT 12" O.C. EA WAYDOWEL EA #3 BAR 4" INTO (E) SLAB AND EPOXY W/ HILTI HY 200 EPOXY

    2"

    11

    3' - 0"

    1-1/2" X 3/4" BAR CONT. , WELDED TO SQ. STL. TUBE GUARDRAIL

    1 1/2" X 1 1/2" X 3/16" STL. TUBE ASTM A500

    GRADE B OR C, GRIND WELDED CONNECTIONS SMOOTH, PAINT COLOR 7

    6" x 6" X 1/4" THICK BASE PLATE W/ (4) 1/2" DIA KWIK-HUS EZ FASTENER BY

    HILTI (OR EQUAL), INSTALL PER MANUF. RECOMMENDATIONS INTO

    EXISTING SLAB, EMBED 3", PAINT COLOR 7

    1 1/2" SQ STL. TUBE BARRIER, GRIND WELDED CONNECTIONS SMOOTH,

    PAINT COLOR 7

    HANDRAIL, SEE DETAIL 15/A300

    AREA OF SILK SCREEN BAND

    1/2" TEMPERED GLASS

    4"

    A70111

    6"

    6"

    1" TYP

    1" T

    YP

    6"

    W-1, GYP. BOARD BULKHEAD, TAPEFINISH AND PAINT COLOR TO BE SELECTED

    PERFORATED METAL CEILING PANEL, SEE A301

    1' - 1"

    108' - 0"

    108' - 8"

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:10:12 PM

    A300

    ENLARGED PLAN ANDGENERAL BUILDINGDETAILS

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    3/4" = 1'-0"A300 REF: A101 / 17 COLUMN2 - DETAIL

    3/4" = 1'-0"A300 REF: A101 / 18 COLUMN - DETAIL

    3" = 1'-0"A300 REF: A300 / 25 HANDRAIL DETAIL

    1/4" = 1'-0"A300 REF: A101 / 11 ENLARGED PLAN - RAMP

    1 1/2" = 1'-0"A30013 ACOUSTICAL CEILING TILE DETAIL (TYP)

    3/4" = 1'-0"A30012 DETAIL - WALL INFILL (IT SERVER 16)

    3/4" = 1'-0"A300 REF: A301 / 414 DETAIL - CEILING GYPSUM BOARD SOFFIT

    3/4" = 1'-0"A300 REF: A101 / 19 SECTION - NEW EXTERIOR WINDOW (TYP)

    1 1/2" = 1'-0"A300 REF: A400 / 115 DETAIL - VESTIBULE CEILING SOFFIT

    1 1/2" = 1'-0"A300 REF: A400 / 110 SECTION - ENTRY CEILING

    1/4" = 1'-0"A300 REF: A300 / 12 SECTION - CORRIDOR RAMP

    1/2" = 1'-0"A300 REF: A101 / 111 DETAIL - WALL (OFFICE 32)

    1/4" = 1'-0"A300 REF: A300 / 13 SECTION - COORIDOR RAMP 2

    1 1/2" = 1'-0"A300 REF: A300 / 24 SECTION - RAMP RAILING

    1" = 1'-0"A300 REF: A300 / 36 DETAIL - PERFORATED CEILING AND BULKHEAD

  • B

    1 2 3

    8A301

    2A301

    2A300

    LIGHT FIXTURES CUT INTO METAL PANEL (TYP). PROVIDE MANUFACTURER'S PERIMETER TRIM TO

    CONCEAL CUT EDGE. SEE ELECTRICAL.

    4' - 0"

    ALIG

    N

    ALIG

    N

    ALIG

    N

    ALIG

    N

    C-310' - 6" AFF

    3A300

    41' - 9 11/16"

    10' -

    0"

    5' - 3 3/4"

    EXPOSED CEILING ABOVE, PAINT COLOR 6

    6 1/

    4"

    NOTE: HATCH INDICATES MATERIAL TYPE AND IS NOT A REPRESENTATION OF INDIVIDUAL MATERIAL COURSING

    E.Q.

    2' -

    0"2'

    - 0"

    6 1/

    4"

    4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 2' - 0" 2' - 0"

    6 1/2"4 1/2"

    2' - 0" 4' - 0"

    11"

    2' - 0" 1' - 0"

    10"

    10" 2' - 0"

    6"

    7" 3' - 0"

    7 1/

    8"

    1' - 0" 2' - 0"

    7"

    3' - 0"3' - 0"

    6"

    1' - 0"4' - 0"

    7"

    2' - 0" 4' - 0"

    1' -

    0"

    3' - 0" 2' - 5"

    1' -

    0"

    9"2'

    - 0"

    7"

    1' - 0"

    1' -

    0"2'

    - 0"

    1' -

    1"

    C-38' - 8" AFF

    C-38' - 8" AFF

    6 1/

    4"6

    1/4"

    11"3 1/4"

    108' - 0"

    109' - 0"

    108' - 0"

    108' - 0"

    5A301

    1' -

    10 7

    /8"

    C-38' - 6" AFF

    LIGHT FIXTURES CUT INTO METAL PANEL (TYP). PROVIDE MANUFACTURER'S PERIMETERTRIM TO CONCEAL CUT EDGE. COORDINATE WITH ELECTRICAL.

    EXPOSED CEILING ABOVE, PAINT COLOR 6

    8" 2' - 0" 2' - 0" 2' - 0" 2' - 0" 2' - 0" 2' - 0" 8"

    4' -

    0"4'

    - 0"

    4' -

    0"4'

    - 0"

    1' -

    10 7

    /8"

    C-38' - 6" AFF

    1' -

    8"4'

    - 0"

    9"

    3' -

    0"7"

    10"

    4"3'

    - 0"

    7"

    10"

    2' -

    0"

    10"

    2' -

    3"3'

    - 0"

    10"

    2' -

    0"1'

    - 0" 1' - 0"

    1' -

    8"2'

    - 0"

    6"

    5"3'

    - 0"

    9"

    6"2'

    - 0"

    9"

    3 1/4"

    LINEAR DIFFUSERS CUT INTO METAL PANEL (TYP). PROVIDE MANUFACTURER'S PERIMETER TRIM TO CONCEAL CUT EDGE. COORDINATE WITH MECHANICAL.

    108' - 0"

    6"3'

    - 0"

    10"

    7"

    4"3'

    - 0"

    10"

    8"3'

    - 0"

    5"3'

    - 0"

    1' - 0"

    11"

    3' -

    0"4"

    B

    4

    14A300

    2' -

    0"2'

    - 0"

    2' -

    0"

    C-38' - 6" AFF

    E.Q.

    LIGHT FIXTURES CUT INTO METAL PANEL (TYP). PROVIDE MANUFACTURER'S PERIMETERTRIM TO CONCEAL CUT EDGE. COORDINATE WITH ELECTRICAL.

    EXPOSED CEILING ABOVE, PAINT COLOR 6

    4' - 0" 4' - 0"

    2' -

    0"2'

    - 0"

    2' -

    0"11

    "11

    "

    E.Q.

    6" 3' - 0"

    10"

    1' - 8"2' - 0"

    1' -

    4"1'

    - 0"

    6" 3' - 0"

    6" 2' - 0"

    7"

    7"

    2' - 0" 4"

    8" 2' - 0"

    10"

    1' - 7" 2' - 0"

    5" 3' - 0" 6"

    8"

    C-38' - 6" AFF

    3 1/4"

    108' - 0"

    LINEAR DIFFUSERS CUT INTO METAL PANEL (TYP). PROVIDE MANUFACTURER'S PERIMETER TRIM TO CONCEAL CUT EDGE. COORDINATE WITH MECHANICAL.

    3"3' - 0"

    5"

    6" 3' - 0"

    6" 3' - 0"

    10"

    3' - 0" 6"

    6"

    AL-9

    SEE FRAME TYPES

    A3017

    #12 HANGER WIRE, 4'-0" O.C.

    EXISTING TWIN TEE

    ALUMINUM BULKHEAD

    PERFORATED METAL PANEL

    U-PROFILE, 4'-0" O.C. MAX

    RECESSED LIGHTING, SEE ELECTRICAL

    SUSPENDED PENDANT,SEE ELECTRICAL

    8"

    108' - 6"

    108' - 0"

    113' - 3"

    EXISTING TWIN TEE BEYOND

    A3017 Sim

    RECESSED LIGHTING, SEE ELECTRICAL

    PERFORATED METAL PANEL

    6 1/4"

    110' - 6"ALUMINUM BULKHEAD BEYOND

    U-PROFILE, 4'-0" O.C. MAX

    6 1/4"PERFORATED METAL CEILING PANEL

    #12 HANGER WIRE

    LIGHT FIXTURES CUT INTO METAL PANEL (TYP). PROVIDE MANUFACTURER'S PERIMETER TRIM TO

    CONCEAL CUT EDGE. SEE ELECTRICAL.

    EXISTING TWIN TEE

    EXISTING TWIN TEE

    3 5/8" METAL STUD FRAMING

    PERFORATED METAL PANEL

    STUD KICKER

    COORDINATE EXACT LOCATION OF

    BULKHEAD WITH LOCATION OF EXISTING

    DUCTWORK 1' -

    10"

    110' - 6"

    108' - 8"

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:10:45 PM

    A301

    ENLARGED PLANS ANDGENERAL BUILDINGDETAILS

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    1/2" = 1'-0"A301 REF: A400 / 11 ENLARGED REFLECTED CEILING PLAN - RAMP

    1/2" = 1'-0"A301 REF: A400 / 13 ENLARGED REFLECTED CEILING PLAN - CONFERENCE 1

    1/2" = 1'-0"A301 REF: A400 / 14 ENLARGED REFLECTED CEILING PLAN - CONFERENCE 2

    3/4" = 1'-0"A301 REF: A301 / 35 SECTION - PERFORATED METAL CEILING, CONFERENCE 1

    3/4" = 1'-0"A301 REF: A301 / 18 SECTION - PERFORATED METAL CEILING, RAMP

    3" = 1'-0"A301 REF: A301 / 57 PERFORATED METAL CEILING - EDGE TRIM

    1 1/2" = 1'-0"A301 REF: A301 / 12 DETAIL - LIGHTING IN PERFORATED PANEL

    NOTE: HATCH INDICATES MATERIAL TYPE AND IS NOT A REPRESENTATION OF INDIVIDUAL MATERIAL COURSING

    3/4" = 1'-0"A301 REF: A300 / 26 PERFORATED METAL CEILING - WRAP

  • OFFICE9

    OFFICE10

    OFFICE11

    OFFICE12

    OFFICE13 OFFICE14

    FIRE RISER15

    IT SERVER16

    OFFICE18

    OFFICE19

    CUSTODIAL20

    ELECTRICALCLOSET

    21

    BREAK ROOM22

    OFFICE23

    OFFICE24

    OFFICE25

    OFFICE26

    OFFICE27

    MEN29

    WOMEN30

    OFFICE37

    OFFICE36

    OFFICE35

    OFFICE34

    OFFICE33

    OFFICE32

    IT STORAGE5

    OFFICE6

    OFFICE7

    OFFICE8

    CONFERENCE 13

    CONFERENCE 22

    OFFICE28

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-28' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    Ceiling Open to Structure Above

    CORRIDOR 231

    CORRIDOR1

    CORRIDOR 317

    C-18' - 9" AFF

    C-18' - 9" AFFC-1

    8' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-28' - 9" AFF

    C-28' - 9" AFF

    C-18' - 9" AFF

    ADA UNISEXRESTROOM

    4

    B B

    A A

    C C

    1

    1

    2

    2 3

    4

    4

    5

    5

    2.9 3.1

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-18' - 9" AFF

    C-310' - 6" AFF

    C-17' - 7" AFF

    C-17' - 10 1/2" AFF

    C-16' - 10" AFF

    C-38' - 6" AFF

    C-38' - 6" AFF

    9A300

    14A300

    C-111' - 3" AFF

    C-18' - 9" AFF

    C-47' - 2" AFF

    C-17' - 10" AFF

    C-48' - 9" AFF

    A3011

    A3013

    A3014

    15A300

    10A300

    38

    38

    3838

    39

    39

    39

    38

    3' - 2 1/2"

    C-38' - 8" AFF

    C-38' - 6" AFF

    C-38' - 6" AFF

    VESTIBULE38

    RAMP39

    38

    32

    32

    3232

    32

    32

    32

    5' -

    5 3/

    4"

    5' - 8 3/4" 4' - 0 3/4" 4' - 2 3/4" 4' - 1 3/4" 3' - 11 3/4" 3' - 11 3/4"

    4' -

    2 3/

    4"4'

    - 2

    3/4"

    4' -

    2 3/

    4"4'

    - 2

    3/4"

    4' -

    2 3/

    4"

    4' - 2 3/4"4' - 2 3/4"8' - 4 1/4"4' - 2 3/4"

    4' -

    2 3/

    4"4'

    - 2

    3/4"

    1' - 2 7/8" TYP.

    1' - 2 7/8" TYP.

    1' - 2 7/8"

    1' -

    2 7/

    8"

    1' -

    2 7/

    8"

    4' -

    2 3/

    4"4'

    - 2

    3/4"

    108' - 0"

    9A300

    Sim

    C-18' - 9" AFF

    C-18' - 9" AFF

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim9

    A300

    Sim9A300

    Sim9

    A300

    Sim9

    A300

    Sim9

    A300

    Sim

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim

    9A300

    Sim

    ENTRY41

    C-12X2 ACOUSTIC TILE CEILING

    CEILINGS

    NOTE: HATCH INDICATES MATERIAL TYPE AND IS NOT A REPRESENTATION OF INDIVIDUAL MATERIAL COURSING.

    COORDINATE FINAL LIGHTING AND DIFFUSER LOCATIONS WITH MECHANICAL/ELECTRICAL.

    10'-0" AFFC-

    CEILING HEIGHT ABOVEFINISH FLOOR

    C-3PERFORATED METAL PANEL

    C-22X2 TILE CEILING

    C-4GYPSUM BOARD, RATED LIDUL ASSEMBLY #: AER-09038

    CEILING TYPE

    1. DO NOT SCALE DRAWINGS. FIELD VERIFY ALL DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY IF DISCREPANCIES ARE DISCOVERED.

    2. PROVIDE VERTICAL CONTROL JOINTS AT GYPSUM BOARD WALLS EXCEEDING 30'-0" MAXIMUM LENGTH. PROVIDE JOINTS AT DOOR HEAD ON LATCH SIDE AND AT WINDOWS ABOVE AND BELOW WINDOW ON ONE SIDE. COORDINATE JOINT LOCATIONS WITH ARCHITECT.

    3. CONTRACTOR SHALL SEAL ALL NEW AND EXISTING THROUGH WALL PENETRATIONS.

    4. CONTRACTOR SHALL COORDINATE LOCATIONS AND ELEVATIONS OF ELECTRICAL OUTLETS, DATA OUTLETS, SWITCHES AND ANY OTHER WALL MOUNTED EQUIPMENT WITH CASEWORK, FURNISHINGS AND OTHER EQUIPMENT SHOWN ON ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. CONTACT ARCHITECT SHOULD DISCREPANCIES EXIST.

    5. CONTRACTOR SHALL COORDINATE AND PROVIDE BLOCKING AT LOCATIONS WHERE WALL MOUNTED EQUIPMENT IS TO BE INSTALLED.

    6. PROTECT EXISTING CONSTRUCTION DURING DEMOLITION AND RENOVATION ACTIVITIES. CONTRACTOR SHALL REPAIR OR REPLACE ANY PORTIONS OF EXISTING BUILDING DAMAGED DURING THESE ACTIVITIES AT NO COST TO OWNER.

    7. CONTRACTOR SHALL COORDINATE WORK BETWEEN ALL TRADES AND RESPECTIVE MECHANICAL, ELECTRICAL AND ARCHITECTURAL SCOPES OF WORK AND INFORM ARCHITECT OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.

    8. ALL HOLLOW METAL DOORS AND DOOR FRAMES (NEW AND EXISTING, INTERIOR AND EXTERIOR), TO BE PAINTED PAINT COLOR 8.

    9. NEW HORIZONTAL BLINDS AT ALL WINDOWS.

    1' -

    0"

    C-4 RATED LID UL ASSEMBLY1-HOUR CEILING

    MIN. 2 1/2" DEEP24 GAUGE J-RUNNER

    FOR ONE (1) HOUR ASSEMBLY ATTACH ONE (1) LAYEROF 5/8" THICK GYPSUM PANEL TO THE UNDERSIDE OF THE CEILING OF THE C-H STUD AND THE PERIMETERJ-RUNNERS. USE 1" LONG TYPE S SCREWS THAT ARE SPACED 12" O.C. IN THE FIELD AND AT THE EDGES.

    C-H STUD, 24" O.C.

    1" THICK GYP LINEAR PANEL

    RIPPER BOARD

    12" MINERAL FIBERINSULATION

    GYPSUM BOARD

    B

    1 2 3

    C-110' - 6" AFF

    C-18' - 8" AFF

    39

    110' - 6"

    108' - 0"

    PROVIDE METAL PERIMETER TRIMAT ALL ACOUSTICAL CEILING CLOUDS108' - 0"

    C-18' - 6" AFF

    C-18' - 6" AFF

    39

    PROVIDE METAL PERIMETER TRIMAT ALL ACOUSTICAL CEILING CLOUDS

    108' - 0"

    B

    4

    C-18' - 6" AFF

    C-18' - 6" AFF

    39

    108' - 0"

    PROVIDE METAL PERIMETER TRIMAT ALL ACOUSTICAL CEILING CLOUDS

    6" M

    IN.

    4'-0" MIN. 4'-0" MIN.

    ACOUSTICAL BATT INSULATION ABOVE CEILING FOR SOUND CONTROL. BETWEEN

    ALL ADJACENT OFFICES AND

    BETWEEN OFFICES AND CORRIDORS.

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:11:41 PM

    A400

    REFLECTED CEILING PLAN

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007GENERAL NOTES KEYNOTES

    CEILING LEGEND

    1/8" = 1'-0"A4001 REFLECTED CEILING PLAN

    N

    32 EXTEND WALLS TO DECK. FRAMING AROUND NEW AND EXISTING PLUMBING REQUIRED. COORDINATE WITH MECHANICAL.38 LIGHT FIXTURES CUT INTO METAL PANEL. PROVIDE MANUFACTURER'S PERIMETER TRIM TO CONCEAL CUT EDGE. SEE ELECTRICAL.39 EXPOSED CEILING ABOVE, ALL MECHANICAL, DUCT AND SYSTEMS PAINTED BLACK (PAINT COLOR 6).

    1/4" = 1'-0"A4004 ALTERNATE 3 - ENLARGED REFLECTED CEILING PLAN, RAMP

    1/4" = 1'-0"A4002 ALTERNATE 3 - ENLARGED REFLECTED CEILING PLAN, CONFERENCE 1

    1/4" = 1'-0"A4003 ALTERNATE 3 - ENLARGED REFLECTED CEILING PLAN, CONFERENCE 2

    1" = 1'-0"ACOUSTICAL BATT INSULATION

  • UP

    UP

    UP

    UP

    ELECTRICALCLOSET

    21

    WF - 1B - 1

    OFFICE9

    F-2

    WF - 1B - 1

    OFFICE10

    F-2

    WF - 1B - 1

    OFFICE11

    F-2WF - 1B - 1

    OFFICE12

    F-2

    WF - 1B - 1

    OFFICE13

    F-2

    WF - 1B - 1

    OFFICE14

    F-2

    WF - 1B - 1

    FIRE RISER15

    F-5

    IT SERVER16

    WF - 1B - 1

    OFFICE8

    F-2

    WF - 1B - 1

    IT STORAGE5

    F-5

    WF - 1B - 1

    OFFICE6

    F-2

    WF - 1B - 1

    OFFICE18

    F-2

    WF - 1B - 1

    OFFICE19

    F-2

    WF - 1B - 1

    CUSTODIAL20

    F-5

    WF - 1B - 1

    BREAK ROOM22

    F-4

    WF - 1B - 1

    OFFICE23

    F-2

    WF - 1B - 1

    OFFICE24

    F-2

    WF - 1B - 1

    OFFICE25

    F-2

    WF - 1B - 1

    OFFICE27

    F-2

    WF - 1B - 1

    OFFICE28

    F-2

    WF - 1B - 1

    OFFICE7

    F-2

    WF - 1B - 1

    OFFICE26

    F-2

    WF - 1B - 1

    OFFICE32

    F-2

    WF - 1B - 1

    OFFICE33

    F-2

    WF - 1B - 1

    OFFICE34

    F-2WF - 1B - 1

    OFFICE35

    F-2

    WF - 1B - 1

    OFFICE36

    F-2

    WF - 1B - 1

    OFFICE37

    F-2 MEN29

    WOMEN30

    WF - 1B - 1

    CONFERENCE 13

    F-4

    WF - 1B - 1

    CONFERENCE 22

    F-4

    WF - 4

    ADA UNISEX RESTROOM4

    F-1

    B B

    A A

    C C

    1

    1

    2

    2 3

    4

    4

    5

    5

    2.9 3.1

    WF - 1B - 1

    RAMP39

    F-4

    STORAGE40

    WF-2

    WF - 1B - 1

    CORRIDOR 317

    F-2

    WF-2

    WF - 1B - 1

    CORRIDOR1

    F-4WF - 1B - 1

    CORRIDOR 231

    F-2

    WF-3

    WF-3

    WF-3 WF-3 WF-3

    WF-2

    WF-2

    WF-2

    WF-2

    WF-2

    WF-5WF-5

    WF-5

    WF-5

    WF-5

    WF-5

    WF-5

    WF - 1B - 1

    CORRIDOR 317

    F-2

    WF - 1B - -

    VESTIBULE38

    F-3

    WF-1

    WF - 1B - 1

    ENTRY41

    F-3

    F-1 TILE - 12" X 24"

    F-2 CARPET SHEET

    (PROVIDED BY OWNER, INSTALLED BY CONTRACTOR)

    WALLS

    WF-1 GYPSUM BOARD; PAINT COLOR 1

    WF-2 GYPSUM BOARD; ACCENT COLOR TBD FROM THE FULL SELECTION OF COLORS IN SPECIFICATIONS

    WF-3 WALL MURAL TO BE DETERMINED BY OWNER/ARCHITECT

    WF-4 WATER RESISTANT GYPSUM BOARD;CONTINUE F-1 UP WALL 48" AS TILE WAINSCOT, PAINT ABOVE, PAINT COLOR TBD FROM THE FULL SELECTION OF COLORS IN SPECIFICATIONS

    WF-5 WOOD ACCENT, REFERENCE ELEVATIONS AND SPECIFICATIONS

    BASE

    B-1 RESILIENT BASE

    FLOORS

    WF - XB - X

    Name101

    F-X

    ROOM NAMEROOM NUMBER

    WALLS, SEE SCHEDULE BELOWBASE, SEE SCHEDULE BELOW

    INDICATES CHANGE IN FINISH TYPE OR ACCENT COLOR DIFFERING FROM GENERAL ROOM FINISHES

    FLOORING, SEE SCHEDULE BELOW

    1. HATCH INDICATES MATERIAL TYPE AND IS NOT A REPRESENTATION OF INDIVIDUAL MATERIAL COURSING

    2. CONTRACTOR TO VERIFY CONCRETE SLAB IS CLEAN OF ANY SEALER, HARDENER, CURING MEMBRANE, PAINT, OIL, ADHESIVES OR ANY PENETRATING MATERIAL BEFORE INSTALLATION OF LUXURY VINYL TILE.

    3. CONTRACTOR SHALL VERIFY EXISTING SLAB MOISTURE CONTENT IS WITHIN FLOORING MANUFACTURER'S REQUIREMENTS.

    4. CONTRACTOR TO APPLY MOISTURE MITIGATING COATING. SEE SPECIFICATIONS.

    5. ALL OUTSIDE CORNERS AT CORRIDOR AND CIRCULATION WALLS SHALL RECEIVE CORNER GUARDS EXTENDING FROM TOP OF RESILIENT BASE TO 4'-4" AFF. SEE SPECIFICATIONS.

    X

    F-4 LUXURY VINYL TILE PLANKS

    F-5 SEALED CONCRETE

    F-3 WALKOFF CARPET

    4"

    RESILIENT/RUBBER BASE

    1. DO NOT SCALE DRAWINGS. FIELD VERIFY ALL DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY IF DISCREPANCIES ARE DISCOVERED.

    2. PROVIDE VERTICAL CONTROL JOINTS AT GYPSUM BOARD WALLS EXCEEDING 30'-0" MAXIMUM LENGTH. PROVIDE JOINTS AT DOOR HEAD ON LATCH SIDE AND AT WINDOWS ABOVE AND BELOW WINDOW ON ONE SIDE. COORDINATE JOINT LOCATIONS WITH ARCHITECT.

    3. CONTRACTOR SHALL SEAL ALL NEW AND EXISTING THROUGH WALL PENETRATIONS.

    4. CONTRACTOR SHALL COORDINATE LOCATIONS AND ELEVATIONS OF ELECTRICAL OUTLETS, DATA OUTLETS, SWITCHES AND ANY OTHER WALL MOUNTED EQUIPMENT WITH CASEWORK, FURNISHINGS AND OTHER EQUIPMENT SHOWN ON ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS. CONTACT ARCHITECT SHOULD DISCREPANCIES EXIST.

    5. CONTRACTOR SHALL COORDINATE AND PROVIDE BLOCKING AT LOCATIONS WHERE WALL MOUNTED EQUIPMENT IS TO BE INSTALLED.

    6. PROTECT EXISTING CONSTRUCTION DURING DEMOLITION AND RENOVATION ACTIVITIES. CONTRACTOR SHALL REPAIR OR REPLACE ANY PORTIONS OF EXISTING BUILDING DAMAGED DURING THESE ACTIVITIES AT NO COST TO OWNER.

    7. CONTRACTOR SHALL COORDINATE WORK BETWEEN ALL TRADES AND RESPECTIVE MECHANICAL, ELECTRICAL AND ARCHITECTURAL SCOPES OF WORK AND INFORM ARCHITECT OF ANY DISCREPANCIES PRIOR TO PROCEEDING WITH WORK.

    8. ALL HOLLOW METAL DOORS AND DOOR FRAMES (NEW AND EXISTING, INTERIOR AND EXTERIOR), TO BE PAINTED PAINT COLOR 8.

    9. NEW HORIZONTAL BLINDS AT ALL WINDOWS.

    TILE0.354" THICKNESS

    LUXURY VINYL TILE0.125" THICKNESS

    CTA-XX-L

    WALK-OFF CARPET0.187" THICKNESS

    LUXURY VINYL TILE0.125" THICKNESS

    CD-XX-H

    CARPET0.286" THICKNESS

    LUXURY VINYL TILE0.125" THICKNESS

    CD-XX-C

    FLOOR TRANSITIONS:CONTRACTOR TO PROVIDE FLOOR TRANSITIONS AS NECESSARY AT ALL FLOORING TERMINATIONS OR TRANSITIONS. ALL FLOORING TRANSITIONS AT DOORWAYS ARE AT THE CENTERLINE OF THE DOOR UNLESS OTHERWISE NOTED.

    CONTRACTOR TO VERIFY TRANSITION SELECTIONS AND MATERIAL THICKNESS.

    TRENCH PATCH

    EDGE OF SAWCUT CONCRETE. S.O.G.

    CONC. S.O.G. ON 4" FREE DRAINAGE GRAVEL. REINFORCE W/ #4 X 2'-0" @ 24" O.C.. EMBEDDED INTO EXIST. SLAB 6" W/HILTI HY150 OR APPROVED EQUAL. STAGGER REINFORCING 12" O.C.

    4"

    WOOD ACCENT WALL,SEE SPECIFICATIONS

    RESILIENT BASE, FLUSHWITH ACCENT WALL

    BLOCKING AS NEEDED

    DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:12:02 PM

    A600

    FINISH FLOOR PLAN

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    FINISH LEGEND

    GENERAL NOTES

    1/8" = 1'-0"A6001 FINISH FLOOR PLAN

    N

    1 1/2" = 1'-0"A6005 WALL BASE

    6" = 1'-0"A6003 FLOOR TRANSITIONS

    3/4" = 1'-0"A6002 TYPICAL SLAB REPLACEMENT

    1 1/2" = 1'-0"A6004 WOOD ACCENT WALL

    GENERAL

  • LEVEL 01100' - 0"

    21

    29

    11' - 11"

    4' -

    7"2'

    - 5"

    LEVEL 01100' - 0"

    10

    63

    6' -

    8"

    EQEQ

    26

    53

    LEVEL 01100' - 0"

    21

    4' -

    7"2'

    - 5"

    29

    19' - 8"

    LEVEL 01100' - 0"

    63

    6' -

    8"

    EQ EQ

    1026

    53

    LEVEL 01100' - 0"

    3' - 0"2' - 0"3' - 0"3' - 0"

    3' - 0" 3' - 0" 2' - 0" 3' - 0"

    4"1'

    - 4"

    2' -

    6"

    W-1 W-2 W-1

    B-1 B-3 B-1

    21

    78

    24 23

    27 25

    25

    2727

    27 27 27

    25

    25 21

    5052

    LEVEL 01100' - 0"

    FILL

    ER2'

    - 6"

    1' -

    2"4"

    FILLER 1' - 6" 3' - 0" 3' - 0" 3' - 1 31/32"

    FILLER 1' - 6" 3' - 0" 3' - 0" 3' - 0"

    W-1 W-1

    B-1 B-1 B-1

    2324

    25

    27 27

    272727

    27

    27

    B-1

    25

    W-3

    1' - 0"

    3/4"

    11"

    3/4"

    1' - 0"

    W-1

    21

    LEVEL 01100' - 0"

    20

    19

    4' -

    8"4"

    3"5'

    - 3"

    52

    LEVEL 01100' - 0"

    3"4"

    4' -

    8"

    28

    19

    18

    14

    20

    5' -

    3"

    52

    LEVEL 01100' - 0"

    20 1915

    4"3" 52

    LEVEL 01100' - 0"

    28

    1920

    16

    1' - 7"

    3"4"

    4' -

    8"

    5' -

    3"

    52

    LEVEL 01100' - 0"

    3' -

    0"4"1

    ' - 2

    "2'

    - 6"

    7' -

    0"

    FILLER2' - 8"2' - 8"FILLER

    FILLER2' - 8"2' - 8"FILLER

    W-1

    B-1

    W-1

    23 24

    27 27

    27

    B-1

    27 21

    52

    A601 5

    3

    2

    4

    2814

    18

    16

    15

    ADA UNISEXRESTROOM

    4

    LEVEL 01100' - 0"

    63 63

    26 26AL-9 AL-10

    LEVEL 01100' - 0"

    2' -

    9"

    21

    51

    LEVEL 01100' - 0"

    B.O. WINDOW104' - 1"

    WINDOW HEAD HT.111' - 5"

    33

    LEVEL 01100' - 0"

    3' -

    0"

    3' -

    0"

    4' - 11" 4' - 4" 1' - 0"

    3' - 4" 3' - 4" 3' - 4" 4"

    AL-11DATEISSUE

    PLOTTED ON:

    ARCHITECT #:

    OWNER:

    OWNERSHIP OF DOCUMENTS:This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of Tobin & Associates, P.C. Tobin & Associates, P.C. are the author of this document and retain all common law, statutory and other reserved rights, including copyright. This document is not to be used, in whole or part, for any other project without the written authorization of Tobin & Associates, P.C. Copyright 2019

    Contact Person(s):

    CONTACT(S):

    WillIiam W. Wedemeyer AIA, ALEP, LEED AP307-632-3144 x120

    Zandria Tolliver307-632-3144 x119

    OWNER #:

    PROJECT INFORMATION

    1820 Dillon AveSuite 200ACheyenne, WY 82001

    MECHANICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070303-919-2184

    Contact Person(s):Nick Pickering, P.E.

    ELECTRICAL ENGINEER:Wood920 E. Sheridan Street, Suite ALaramie, WY 82070307-275-0722

    Contact Person(s):Rick Shields, P.E.

    CIVIL ENGINEER:Inberg-Miller Engineers350 Parsley BoulevardCheyenne, WY 82007307-635-6827

    Contact Person(s):Daniel Hayes, P.E.

    02/19/1950% SUBMITTAL

    03/12/1995% SUBMITTAL

    STRUCTURAL ENGINEER:Martin/Martin Wyoming4020 Laramie StreetCheyenne, WY 82001

    Contact Person(s):John Shaffer, P.E.

    03/19/19100% CDs

    3/19/2019 3:12:11 PM

    A601

    INTERIOR ELEVATIONS

    Laramie County Community College

    17-07-10

    1400 E College DrCheyenne, WY 82007

    Bill Zink (307) 778-5222

    LCCC EDUCATIONALENRICHMENT CENTERBASEMENT RENOVATION1400 E College Dr,Cheyenne, WY 82007

    1/4" = 1'-0"A601 REF: A101 / 113 CONFERENCE 2 - EAST

    1/4" = 1'-0"A601 REF: A101 / 112 CONFERENCE 2 - NORTH

    1/4" = 1'-0"A601 REF: A101 / 110 CONFERENCE 1 - EAST

    1/4" = 1'-0"A601 REF: A101 / 111 CONFERENCE 1 - NORTH

    1/4" = 1'-0"A601 REF: A101 / 16 BREAK ROOM - SOUTH

    1/4" = 1'-0"A601 REF: A101 / 17 WORK ROOM - CASEWORK

    1/4" = 1'-0"A601 REF: A601 / 15 RESTROOM - EAST

    1/4" = 1'-0"A601 REF: A601 / 13 RESTROOM - NORTH

    1/4" = 1'-0"A601 REF: A601 / 14 RESTROOM - SOUTH

    1/4" = 1'-0"A601 REF: A601 / 12 RESTROOM - WEST

    1/4" = 1'-0"A601 REF: A101 / 18 CORRIDOR 2 SOUTH BREAK AREA

    KEYNOTES

    7 REFRIGERATOR, OWNER PROVIDED. WATER CONNECTION NEEDED, SEE PLUMBING.8 MICROWAVE, OWNER PROVIDED. ELECTRICAL OUTLET INSIDE CASEWORK. CASEWORK INSTALLATION AND POWER

    REQUIREMENTS SHALL BE COORDINATED WITH ELECTRICAL.10 TELEVISION, OWNER PROVIDED. COORDINATE WITH ELECTRICAL. PROVIDE BLOCKING AS NECESSARY. CONTRACTOR TO

    PROVIDE UNIVERSAL MOUNT. COORDINATE FINAL MOUNTING HEIGHT WITH OWNER/ARCHITECT.14 TOILET TISSUE HOLDER DISPENSER PROVIDED BY OWNER, INSTALLED BY CONTRACTOR. PROVIDE BLOCKING AS NECESSARY.15 SOAP DISPENSER PROVIDED BY OWNER, INSTALLED BY CONTRACTOR. PROVIDE BLOCKING AS NECESSARY.16 MIRROR, PROVIDED BY CONTRACTOR, INSTALLED BY CONTRACTOR. PROVIDE METAL FILLER TO MATCH FRAME WHERE

    MIRROR STRADDLES TILE AND GYP. WALL.18 SANITARY NAPKIN DISPOSAL, PROVIDED BY OWNER, INSTALLED BY CONTRACTOR.19 TILE WAINSCOT20 BULNOSE TILE, SEE SPECIFICATIONS21 RESILIENT BASE, SEE SPECIFICATIONS.23 PLASTIC LAMINATE 2, COUNTERTOP. SEE SPECIFICATIONS.; ALTERNATE 2: SOLID SURFACE 124 BACKSPLASH TO MATCH COUNTERTOP, SEE SPECIFICATIONS.25 PROVIDE FINISHED END PANEL TO MATCH.26 WOOD ACCENT WALL, SEE SPECIFICATIONS.27 PLASTIC LAMINATE 1, CASEWORK. SEE SPECIFICATIONS.28 GRAB BARS, SEE SPECIFICATIONS29 MARKERBOARD, SEE SPECIFICATIONS. PROVIDE BLOCKING AS NECESSARY.33 MURAL, SEE SPECIFICATIONS.50 ALUMINUM EDGE TRIM, SEE SPECIFICATIONS51 NEW WATER FOUNTAIN WITH BOTTLE FILLER, SEE MECHANICAL52 TILE ACCENT, SEE SPECIFICATIONS.53 AROUND RECEPTACLES AT WOOD ACCENT WALL, PROVIDE MUDRING AND PICTURE FRAME OF SIMILAR MATERIAL.63 RESILIENT BASE AT WOOD ACCENT WALL, SEE DETAIL 4/A600.

    1/4" = 1'-0"A601 REF: A101 / 11 ENLARGED PLAN - ADA UNISEX RESTROOM

    1/4" = 1'-0"A601 REF: A101 / 114 COORIDOR 1 ACCENT WALL

    1/4" = 1'-0"A601 REF: A101 / 19 NEW WATER COOLER

    1/4" = 1'-0"A601 REF: A101 / 116 ENTRANCE STAIR

    1/4" = 1'-0"A601 REF: A101 / 115 GLASS WALL 3 AT RAMP

  • 17' M

    AX

    15" MAX

    1' - 0" 3' - 6"

    4' - 6"

    27" - 29"

    1-1/

    2" M

    IN

    33" -

    36"

    39" -

    41"

    18" M

    IN

    7" - 9"

    15" M

    IN

    3' - 6"

    3' - 0" 6"

    2' - 0" 1' - 0"

    17" -

    19"

    33" -

    36"

    1' - 6" 15" MIN

    40

    " MIN

    27" M

    IN34

    " MAX

    17" MIN

    27' M

    IN34

    " MAX

    BOTT

    OM

    ED

    GE

    OF

    REF

    LEC

    TIVE

    SU

    RFA

    CE

    25" -

    30"

    17" MIN

    MIRRORSOAP DISPENSER 48" MAX MOUNTING HEIGHT

    LAVATORY, SEE MECHANICAL

    SINK IN COUNTERTOP,SEE MECHANICAL

    BUMPER PADDING REQ'D TOMEET ADA & ANSI STANDARDS(TYPICAL AT ALL EXPOSED PIPING)

    MIRROR

    TOILET, SEE MECHANICAL

    TOILET, SEE MECHANICAL

    LAVATORY, SEE MECHANICAL

    SANITARY NAPKIN DISPENSER

    TOILET PAPERDISPENSER

    GRAB BAR,TYPICAL

    GRAB BARGRAB BAR

    GRAB BAR

    GRAB BAR

    TOILET PAPERDISPENSER

    GRAB BAR

    TO WALL

    PAPER TOWEL DISPENSER48" MAX MOUNTING HEIGHT

    TO WALL

    URINAL

    STANDARD ADA MOUNTING HEIGHTS - ADULT

    FIXTURES AND EQUIPMENT SHOWN ARE FORDIMENSION PURPOSES ONLY.

    ADA DOOR OPERATOR

    4' -

    0"

    FIRE EXTINGUISHER CABINET

    MOP SHELF

    WATER COOLER, SEE MECHANICAL FOR TYPE, INSTALL PER MANUFACTURER'S RECOMMENDATION

    33" M

    AX.

    4' -

    3"6' -

    0"

    CABINET FRAME: 3/4" SIDES, SUBFRONT, TOP AND BOTTOM3/4" FACE FRAME AND DOOR

    ADJUSTABLE SHELF HOLES @ 2" O.C.

    3/4' ADJUSTABLE SHELVES

    1' - 0"

    2' -

    6"

    1X BLOCKING

    1/2" CABINET BACK

    1X BLOCKING

    CABINET