2_Title Slide Lessons Learned in Achieving Data Center Efficiency Goals – 3 Case Studies Rich Reyher, Director, PayPal Core Platform & Infrastructure: Global Data Center, PayPal, Inc. David Breland, Manager, Enterprise Data Center Facilities, Intuit, Inc. Dale Sartor, Staff Scientist/Engineer, Lawrence Berkeley National Laboratory

Upload: others

Post on 30-Sep-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

2_Title Slide

Lessons Learned in Achieving Data Center Efficiency Goals – 3 Case StudiesRich Reyher, Director, PayPal Core Platform & Infrastructure: Global Data Center, PayPal, Inc.David Breland, Manager, Enterprise Data Center Facilities, Intuit, Inc.Dale Sartor, Staff Scientist/Engineer, Lawrence Berkeley National Laboratory

Page 2: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun
Page 3: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Click to edit Master title styleBetter Buildings and Data Centers

Challenge partners set 10-year, 20% energy-savings targets across portfolio

of buildings and share results

Accelerator partners set 5-year, 25% energy-savings targets across one or more data centers

and provide regular updates on progress

Better Buildings ChallengeCenturyLink

Digital Realty Trust

eBay Inc.

Facebook

Intel Corporation

Intuit

IO Data Centers

Iron Mountain Data Centers

Michigan State University

Sabey Data Center Partners

Staples

Better Buildings AcceleratorANL Defense Health Agency

EMSL Georgia Tech

Indiana University LBNL

LLNL LANL

NERSC NREL

ORNL Stanford

State of Michigan Home Depot

DOD-DISA DOJ-DEA

VA EPA

NASA SSA

University of Colorado University of Iowa

Virtustream Waste Management

Page 4: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Data Center Path to Efficiency and Automation

Page 5: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Data Center Path to Efficiency and Automation

1. PayPal’s data center landscape

2. The efficiency challenge

3. Our journey so far

4. Phase 1 – Improving space and power efficiency

5. Phase 2 – Improving process and tool efficiency

6. Phase 3 – Planned future improvements

Page 6: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

FL

MD

NY

PA

VAWV

OH

NCTN

AL

NJ

GA

DC

Salt Lake City

Bluffdale

Las Vegas

Phoenix

Data Centers (ROTW)

33 Data Centers

900+ DC Procedures

16 Countries

13 Tools & Platforms1M+ Monitoring Endpoints

3 primary DC partners

3,000+ DC Infrastructure Assets

Reduced carbon footprint

~2,500 Racks 27 Megawatts

~130 People

PayPal’s data center landscapePayPal has grown rapidly over the last decade and our data center landscape has become increasingly complex. A key challenge was to maximize efficiency to ensure available capacity.

Phoenix

• PayPal Owned and Operated

• Future PayPal Primary • Tier IV & Tier II Design

Bluffdale Las Vegas Salt Lake City

• Colocation Provider• Tier III Design• Home of DCG 13

• Colocation Provider• Tier IV Design• Home of Analytics

• Colocation Provider• Tier IV & Tier II

Design• Home of CCG & DCG

Page 7: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Our ultimate goal is to reach 70% true utilization for space and power in the data center and this requires tackling efficiency on multiple fronts

Protected IT Load58%Electrical Loss Energy

16%

Data Center Cooling Energy

24%

General Space Energy Use2%

The efficiency challengeWe captured an initial baseline to determine our energy usage and identify several sources of inefficiencies

• Always-on cooling

• Lack of proper containment

• No temperature control zones

• Inefficient CRAH motors

• Lack of transparency on equipment ownership

• No mechanism for clear utilization showback

• Require a large buffer in capacity to ensure we meet business demand

• Over-allocation for failure scenarios

• Significant amount of unused hardware (i.e. zombie assets). Estimated utilization is ~40–50%

• Older transformer-based UPSs

Page 8: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Video

Page 9: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Our journey so farWe tackled efficiency improvements in multiple phases moving from physical space and power efficiency to people, process and tools.

2010 Legacy data center PUE / CUE improvements started

2013 Q3New data center build started using lessons learned and latest industry standards

2013 Q4Legacy data center PUE improvements completed

2014 Q4New center

build completed

2015 Q3Transition to

renewable energy completed

2015 Q2PayPal

becomes standalone

company

2016 Q1DCIM application rationalization started

2016 Q4Asset and ticketing application consolidated

2017 Q4Space and power visualization and process improvements completed

2018 Q4Implement predictive space and power analysis

2018 Q3Implement RFID location and automated rack unit position tracking

2018 Q2Build physical network

connection maps and visualization

Phase 1 – PUE and CUE improvements

Phase 2 – Tool and Process improvements

Phase 3 – Optimization and prediction of space and power

2012Hartman Loop

installed

Page 10: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Phase 1 – Improving space and power efficiencyWe began improving efficiency by tackling quick wins in our legacy Phoenix data center

Hartman loop chiller plant optimization

Variable Speed Drives and new high efficiency motors on the CRAH systems

Cold Aisle Containment

Harmonic Mitigating Transformers in the CRAH electrical distribution system

Current Situation Reducing Data Center cooling energy

SolutionThree year energy management plan

• The data center was operated as a standard tier IV facility

• The electrical losses and IT load required long lead times to address

Page 11: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

0.000

0.200

0.400

0.600

0.800

1.000

1.200

1.400

1.600

1.800

2.000

2.200

Jan'05-

Dec'09

Feb'10

Apr'10

Jun'10

Aug'10

Oct'10

Dec'10

Feb'11

Apr'11

Jun'11

Aug'11

Oct'11

Dec'11

Feb'12

Apr'12

Jun'12

Aug'12

Oct'12

Dec'12

Feb'13

Apr'13

Jun'13

Aug'13

Oct'13

Dec'13

Feb'14

Apr'14

Jun'14

Aug'14

Oct'14

Dec'14

Feb'15

Apr'15

Jun'15

Aug'15

Oct'15

Dec'15

Feb'16

Apr'16

Jun'16

Aug'16

Oct'16

Dec'16

Feb'17

Apr'17

Jun'17

Power Load (KW

)Usa

ge E

ffic

ienc

y

All Owned DCs PUE All Owned DCs CUE All owned DCs Load

Phase 1 – Impact on data center efficiencyThe net result of the efficiency projects was an improvement of PUE from 1.85 to 1.49 (19%) across owned data centers.

Cold Aisle Containment Construction Begins April 2010

VSD Installs completeMarch 2011

Holistic Chiller System Install Complete January 2012

EC Fan Install Complete June 2012

Transition to renewable energyComplete July 2015

Humidifier Install Complete July 2011

Page 12: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

©2017 PayPal Inc. Confidential and proprietary.

Phase 2 - How we have traditionally managed our data centersTicketing, monitoring, alarming, and data have historically been fragmented across multiple platforms

• PayPal Excel• Milestone Excel• Brookfield Excel• Tableau

Phoenix

Denver

Computerized Maintenance Management System (CMMS)

Manual Data Center Infrastructure Management (DCIM)

Building Management System (BMS) / Electrical Power management System (EPMS)

Reporting

Las Vegas

Salt Lake City

Rest of the World

• Custom Excel• Delta Systems• Schneider• Automated Logic Control• Dell MDCi• Paladin

• Custom Excel• OSISoft• TigerEyes• Delta Systems• Automated Logic Control

• Email• Infocenter• SharePoint• ServiceNow

Page 13: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

©2017 PayPal Inc. Confidential and proprietary.

Phoenix

Denver

Las Vegas

Salt Lake City

Rest of the World

Phase 2 - How our data centers will be managed moving forwardTicketing, monitoring, alarming, and data will be consolidated into a single pane of glass

• PayPal Excel• Milestone Excel• Brookfield Excel• Tableau

Computerized Maintenance Management System (CMMS)

Manual Data Center Infrastructure Management (DCIM)

Building Management System (BMS) / Electrical Power management System (EPMS)

Reporting

• Custom Excel• Delta Systems• Schneider• Automated Logic Control• Dell MDCi• Paladin

• Custom Excel• OSISoft• TigerEyes• Delta Systems• Automated Logic Control

• Email• Infocenter• SharePoint• ServiceNow

Page 14: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Phase 3 – Planned Future Improvements - “What’s next?”With the physical and application improvements in place we can begin to further automate our systems and predict future demand

Current Situation Solution

Significant ongoing effort needed to continually audit assets to validate their location and position with racks

Lead times for provisioning can be weeks if there is no space and power available at the time of a request

Power Strip Tagging Provides automated asset

unit position within the rack saving time for audits

and provides rack usage indicators.

RFID Tagging Provides automated building level position and will be used to automatically receive assets and check them in/out of stock

1

2

Predictive analysis of space and power

Projections would be used to automatically issue procurement or work tickets to stay ahead of the demand, reducing provisioning times from weeks to days

Objective is to use data to more accurately project expected space and power usage

Page 15: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun
Page 16: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

HOW HOT CAN I GO?Intuit’s Journey in Quincy Washington

Dave BrelandManager, Enterprise Data Center Facilities

Page 17: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

FIRST- I NEEDED A GUIDEASHRAE Datacom Series formerly TC9.9

Page 18: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

INSIDE ASHRAE’S DATACOM GUIDE

Page 19: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

IN ENGLISH

Recommended vs. Allowable

Page 20: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

HOW DO I KNOW?

Is there some way for me to know for sure?

Page 21: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Dell states 10°C – 35°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within Dell Requirements

Page 22: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Dell states 10°C – 35°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within Dell Requirements

Page 23: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

HP states 10°C – 35°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within HP Requirements

Page 24: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

HP states 10°C – 35°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within HP Requirements

Page 25: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Cisco states 0°C – 40°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within Cisco Requirements

Page 26: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Cisco states 0°C – 40°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within Cisco Requirements

Page 27: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

NetApp states 0°C – 40°C while the ASHRAE Guideline allows 15°C – 32°C. ASHRAE Guidelines are well within NetApp Requirements

Page 28: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Apple states 0°C – 35°C while the ASHRAE Guideline allows 15°C –32°C. ASHRAE Guidelines are well within Apple Requirements

Page 29: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Pure Storage states 5°C – 35°C while the ASHRAE Guideline allows 15°C – 32°C. ASHRAE Guidelines are well within Pure Storage Requirements

Page 30: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun
Page 31: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

INTUIT’S JOURNEY IN QUINCY WASHINGTON

Current Control 78.5°f top of Rack Warn 80°f Alarm

CWS Temp 61°f

Economizer Start OAWBT 58°f with a CWST of <61.5°f.

Economizer Stop 64°f CWST

Now average 65% on water side economizer

THEN NOW

Original Design 72°f top of Rack

CWS Temp 47°f

Economizer Start OAWBT 45°f with a CWST of <47.5°f.

Economizer Stop 48.5°f CWST

Averaged 48% of year on economizer at current load

Page 32: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

One of Our Cooling Plants

Page 33: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

SO THIS IS HOW WE HAVE DETERMINED HOW HOT WE CAN GO

Balance data halls using Purkay instruments and Tileflow Software, to ensure cold aisle temps ≤ 78.5°f. at top of rack.

Raised CWST to get all of the CRAH control valves at their mid range. Operators monitor weather patterns and redundant cooling tower storage to extend

economizer hours when possible. My biggest bang is staying on my economizer as long as possible. With my water side economizer, it’s as far as I can go. Most later version data centers

around me are using 100% outside air or probably half have gone to the Munters Evaporative Cooling units.

Page 34: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

7x24 – Shaping The FuturePhoenix, ArizonaOctober 17, 2017Dale Sartor, PE

National Energy Research Scientific Computing Center

(NERSC)Shyh Wang Hall

Version: 090817

Page 35: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Shyh Wang Hall, the New Home for NERSC

- 2 -

Page 36: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

UC’s Shyh Wang Hall

• 142,000 square feet total• 7 MW IT load to start, then up to 17, then ???• IT load will dominate building• 4 large AHUs for air-cooled loads• 4 cooling towers for water cooled loads• Water-cooled supercomputers• Air and water side economizers• IT loads cooled without compressors• Air-side heat recovery for heating offices

- 3 -

Page 37: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

- 4 -

NERSC hosts Cori (#5 Top 500, Nov 2016)

File Systems and Air Cooled Computers

High and Low Density Computing

Page 38: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

• 2 MW Air Cooling (17 MW max)• Annual PUE less than 1.1• Air-side economizer• Direct evaporative cooling

for humidification & cooling

Free Cooling - Air System Design

Page 39: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Outside Air Based Design

Annual Psychrometric Chart of Oakland, CA(relative humidity lines are stepped by 10%,

wetbulb lines by 10 degrees F)

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105

Drybulb Temp (F)

WB = 30

WB = 40

WB = 50

WB = 60

WB = 70

1. Blue = original design supply

2. Green can become blue mixing return and outdoor air

3. Most of the conditions below and right of blue can be satisfied w/ evaporative cooling

4. Hot and humid hours will enter the “allowable” range

- 6 -

Page 40: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

• 10 MW liquid cooling (20 MW max)

• Annual PUE less than 1.1• Closed-loop treated cooling

water from cooling towers • Headers, valves and caps for

modularity and flexibility

Free Cooling - Water Based Design

Page 41: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Real Life Results

• Performance• Opportunities for improvement/optimization• Lessons learned

Page 42: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

0

50

100

150

200

250

300

350

32 34 36 38 40 42 44 46 48 50 52 54 56 58

Pow

er (k

W)

Outside Air Wetbulb Temperature (°F)

Baseline

Baseline CWGP Pump kW Baseline TWGP Pump kW

Baseline Total CT Fan Power kW Baseline Total System kW

Liquid Cooling Performance Baseline

- 9 -

Page 43: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

0

50

100

150

200

250

300

350

32 34 36 38 40 42 44 46 48 50 52 54 56 58

Pow

er (k

W)

Outside Air Wetbulb Temperature (°F)

5 Degree Approach

5 Deg Approach CWGP Pump kW 5 Deg Approach TWGP Pump kW

5 Deg Approach Total CT Fan Power kW 5 Deg Approach Total System kW

Liquid Cooling Performance Balanced

- 10 -

Page 44: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Taking Full Advantage of Recommended Ranges

- 11 -

• Allowable ranges have expanded• Trade off between high humidity

and high temperature We chose high humidity

• Allowing dryer air would save water

Page 45: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

0

50

100

150

200

250

300

350

32 34 36 38 40 42 44 46 48 50 52 54 56 58

Pow

er (k

W)

Outside Air Wetbulb Temperature (°F)

Total Power Comparison

Baseline Total System kW Reduced Min Speed Total System kW

4 Deg Approach Total System kW 5 Deg Approach Total System kW

Cooling System Optimization

- 12 -

Page 46: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

UPS Double Conversion Losses

- 13 -

Page 47: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Electricity and Water Savings

- 14 -

Water Savings Cost Savings PUEMeasure Title Estimated Verified Gallons $ Reduction

Controls

1 Optimize Cooling Tower Fan and Pump Controls - 360,000 100,000 20,880$ 0.007

2 Optimize Closed Loop Pump Control 240,000 - 110,000 13,920$ 0.005

3 Optimize AHU SAT and Flow Control 300,000 - - 17,400$ 0.006

4 Reset Cooling Water Supply Temperature 600,000 - 220,000 34,800$ -

5 Install Firmware to Enable ESS Mode for UPSs 190,000 - 65,000 11,020$ 0.004

Physical Projects -$

6 Cold Aisle Partial Containment 100,000 - - 5,800$ 0.002

Total 1,400,000 400,000 500,000 100,000$ 0.025

IT kWh 48,200,000 Extrapolated based on typical operationTotal Non-IT kWh 3,200,000 Does not include CRAY fans

PUE 1.07 Estimated Post-Case PUE 1.04

Savings as a Fraction of Cooling System kWh 56%

Energy Savings (kWh)

Page 48: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Our Improvement Team Approach

1. Identify opportunities2. Identify critical control boundaries3. Try it out!4. Verify using trend data5. Repeat until optimized

All parties work closely throughout the project

- 15 -

Page 49: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Takeaways

• Involve full team from measure development through implementation

• Question everything• Incremental, iterative process can be most effective• Don’t underestimate interconnectivity of systems• A sub 1.1 PUE data center can still be improved!

- 16 -

Page 50: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Our Identified Savings are Equivalent to a 1 MW Solar Array

- 17 -

37% Implemented To-Date

1 MW Solar Array –~4 football fields and $4 Million

B59/NERSC

Page 51: Lessons Learned in Achieving Data Center Efficiency Goals ... · '12. Jun '12. Aug '12. Oct '12. Dec '12. Feb '13. Apr '13. Jun '13. Aug '13. Oct '13. Dec '13. Feb '14. Apr '14. Jun

Dale Sartor, P.E.Lawrence Berkeley National LaboratoryMS 90-3111University of CaliforniaBerkeley, CA 94720

[email protected](510) 486-5988

http://datacenters.lbl.gov/

Speaker Contact Information