level mmt 1 btech iii

Upload: kerul-modi

Post on 05-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 Level Mmt 1 Btech III

    1/44

    Measurements of LiquidLevel

  • 7/31/2019 Level Mmt 1 Btech III

    2/44

    LEVEL MEASUREMENT

    Level is a kind of displacement.. Effect of temperature and pressure on this

    measurement. Effect of the operating environment on the

    measurement Very simple systems employ external sight glassesor tubes to view the height and hence the volumeof the fluid.

    Floats connected to variable potentiometers or

    rheostats that will change the resistance accordingto the amount of motion of the float.

    More challenging situations are those requiringinferential level measurement.

  • 7/31/2019 Level Mmt 1 Btech III

    3/44

    This technique obtains a level indication indirectlyby monitoring the pressure exerted by the heightof the liquid in the vessel.

    The pressure at the base of a vessel containingliquid is directly proportional to the height of theliquid in the vessel.

    This is termed hydrostatic pressure. As the level in the vessel rises, the pressure

    exerted by the liquid at the base of the vessel willincrease linearly.

    Mathematically, we have:P = S HWhere,

    P = Pressure (Pa)S = Weight density of the liquid (N/m3) = gH = Height of liquid column (m) = Density (kg/m3)g = acceleration due to gravity (9.81m/s2)

  • 7/31/2019 Level Mmt 1 Btech III

    4/44

    The level of liquid inside a tank can be determinedfrom the pressure reading if the weight density ofthe liquid is constant.

    Differential Pressure (DP) capsules are the mostcommonly used devices to measure the pressureat the base of a tank.

    When a DP transmitter is used for the purpose of

    measuring a level, it will be called a leveltransmitter (LT).

    To obtain maximum sensitivity, a pressure capsulehas to be used, that has a sensitivity range thatclosely matches the anticipated pressure of the

    measured liquid. System pressures are often much higher than the

    actual hydrostatic pressure that is to bemeasured.

  • 7/31/2019 Level Mmt 1 Btech III

    5/44

    If the process pressure is accidentallyapplied to only one side of the DP capsuleduring installation or removal of the DPcell from service, over ranging of the

    capsule would occur and the capsule couldbe damaged causing erroneousindications.

  • 7/31/2019 Level Mmt 1 Btech III

    6/44

    Three Valve Manifold

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level

    Figure 1

    A Three Valve Manifold

  • 7/31/2019 Level Mmt 1 Btech III

    7/44

    A three-valve manifold is a device that isused to ensure that the capsule will not beover-ranged.

    It also allows isolation of the transmitterfrom the process loop.

    It consists of two block valves - highpressure and low pressure block valve -

    and an equalizing valve. During normal operation, the equalizing

    valve is closed and the two block valvesare open.

    When the transmitter is put into orremoved from service, the valves must beoperated in such a manner that very highpressure is never applied to only one sideof the DP capsule.

  • 7/31/2019 Level Mmt 1 Btech III

    8/44

    Operational Sequences of Three-Valve

    Manifold Valving Transmitter into Service

    To valve a DP transmitter into service an operator wouldperform the following steps:

    1. Check all valves closed.2. Open the equalizing valve. this ensures that the same

    pressure will be applied to both sides of the transmitter,i.e. zero differential pressure.3. Open the High Pressure block valve slowly, check for

    leakage from both the high pressure and low-pressureside of the transmitter.

    4. Close the equalizing valve. this locks the pressure on bothsides of the transmitter.

    5. Open the low-pressure block valve to apply processpressure to the low-pressure side of the transmitter andestablish the working differential pressure.

    6. The transmitter is now in service. Note it may benecessary to bleed any trapped air from the capsulehousing.

  • 7/31/2019 Level Mmt 1 Btech III

    9/44

    Removing Transmitter from

    Service Reversal of the above steps allows the DP

    transmitter to be removed from service.

    1. Close the low-pressure block valve.

    2. Open the equalizing valve.3. Close the high-pressure block valve.

    The transmitter is now out of service. Note the transmitter capsule housing still

    contains process pressure; this will requirebleeding.

  • 7/31/2019 Level Mmt 1 Btech III

    10/44

    Open Tank Measurement

    The simplest application is the fluid level inan open tank. Figure 2 shows a typical open tank level

    measurement installation using a pressure

    capsule level transmitter.Click to edit Master text styles

    Second levelThird levelFourth level

    Fifth level

    Figure 2

  • 7/31/2019 Level Mmt 1 Btech III

    11/44

    If the tank is open to atmosphere, thehigh-pressure side of the level transmitterwill be connected to the base of the tank

    while the low-pressure side will be ventedto atmosphere. In this manner, the level transmitter acts

    as a simple pressure transmitter. We have:Phigh = Patm + S HPlow = Patm

    Differential pressureP = Phigh - Plow = S H

    The level transmitter can be calibrated tooutput 4 mA when the tank is at 0% leveland 20 mA when the tank is at 100%level.

  • 7/31/2019 Level Mmt 1 Btech III

    12/44

    Closed Tank Measurement

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level

    Figure 3

    Typical Closed Tank Level Measurement System

  • 7/31/2019 Level Mmt 1 Btech III

    13/44

    Should the tank be closed and a gas or vapour exists ontop of the liquid, the gas pressure must be compensatedfor. A change in the gas pressure will cause a change intransmitter output.

    The pressure exerted by the gas phase may be so highthat the hydrostatic pressure of the liquid columnbecomes insignificant.

    For example, the measured hydrostatic head in a CANDUboiler may be only three meters (30 kPa) or so, whereasthe steam pressure is typically 5 MPa.

    Compensation can be achieved by applying the gaspressure to both the high and low-pressure sides of thelevel transmitter.

    This cover gas pressure, is thus used as a back pressureor reference pressure on the LP side of the DP cell. One can also immediately see the need for the three-

    valve manifold to protect the DP cell against thesepressures.

  • 7/31/2019 Level Mmt 1 Btech III

    14/44

    We have:

    Phigh = Pgas + S H

    Plow = Pgas

    P = Phigh - Plow = S H

    The effect of the gas pressure is cancelledand only the pressure due to thehydrostatic head of the liquid is sensed.

    When the low-pressure impulse line isconnected directly to the gas phase abovethe liquid level, it is called a dry leg.

  • 7/31/2019 Level Mmt 1 Btech III

    15/44

    Dry Leg System

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level Figure 4Dry Leg

    Installationwith Three-

    ValveManifold

  • 7/31/2019 Level Mmt 1 Btech III

    16/44

    If the gas phase is condensable, say steam,

    condensate will form in the low-pressure impulseline resulting in a column of liquid, which exertsextra pressure on the low-pressure side of thetransmitter.

    A technique to solve this problem is to add aknockout pot below the transmitter in the low-pressure side as shown in Figure 4

    Periodic draining of the condensate in theknockout pot will ensure that the impulse line isfree of liquid.

    In practice, a dry leg is seldom used becausefrequent maintenance is required.

    In most closed tank applications, a wet leg levelmeasurement system is used.

  • 7/31/2019 Level Mmt 1 Btech III

    17/44

    Wet Leg System

    Click to edit Master text styles Second level

    Third level

    Fourth level Fifth level

  • 7/31/2019 Level Mmt 1 Btech III

    18/44

    In a wet leg system, the low-pressure impulse line iscompletely filled with liquid (usually the same liquidas the process) and hence the name wet leg.

    A level transmitter, with the associated three-valvemanifold, is used in an identical manner to the dry legsystem.

    At the top of the low pressure impulse line is a small

    catch tank. The gas phase or vapor will condense in the wet legand the catch tank.

    The catch tank, with the inclined interconnecting line,maintains a constant hydrostatic pressure on the low-pressure side of the level transmitter.

    This pressure, being a constant, can easily becompensated for by calibration. (Note that operatingthe three-valve manifold in the prescribed mannerhelps to preserve the wet leg.)

  • 7/31/2019 Level Mmt 1 Btech III

    19/44

    If the tank is located outdoors, trace heating of thewet leg might be necessary to prevent it from

    freezing. Steam lines or an electric heating element can bewound around the wet leg to keep the temperature ofthe condensate above its freezing point.

    Note the two sets of drain valves. The transmitter

    drain valves would be used to drain (bleed) thetransmitter only. The two drain valves locatedimmediately above the three-valve manifold are usedfor impulse and wet leg draining and filling.

    In addition to the three-valve manifold mosttransmitter installations have valves where theimpulse lines connect to the process.

    These isolating valves, sometimes referred to as theroot valves, are used to isolate the transmitter formaintenance.

  • 7/31/2019 Level Mmt 1 Btech III

    20/44

    Level Compensation

    It would be idealistic to say that the DPcell can always be located at the exact thebottom of the vessel we are measuring

    fluid level in. Hence, the measuring system has to

    consider the hydrostatic pressure of thefluid in the sensing lines themselves.

    This leads to two compensations required.

  • 7/31/2019 Level Mmt 1 Btech III

    21/44

    Zero Suppression

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level

  • 7/31/2019 Level Mmt 1 Btech III

    22/44

    In some cases, it is not possible to mountthe level transmitter right at the base level

    of the tank. Say for maintenancepurposes, the level transmitter has to bemounted X meters below the base of anopen tank as shown in Figure 6.

    The liquid in the tank exerts a varyingpressure that is proportional to its level Hon the high-pressure side of thetransmitter.

    The liquid in the high pressure impulse line

    also exerts a pressure on the high-pressure side.

    However, this pressure is a constant (P =S X) and is present at all times.

  • 7/31/2019 Level Mmt 1 Btech III

    23/44

    When the liquid level is at H meters, pressure on thehigh-pressure side of the transmitter will be:

    Phigh = S H + S X + Patm

    Plow = PatmP = Phigh - Plow = S H + S X

    That is, the pressure on the high-pressure side isalways higher than the actual pressure exerted by the

    liquid column in the tank (by a value of S X

    ). This constant pressure would cause an output signalthat is higher than 4 mA when the tank is empty andabove 20 mA when it is full.

    The transmitter has to be negatively biased by a valueof -S X so that the output of the transmitter is

    proportional to the tank level (SH) only. This procedure is called Zero Suppression and it can

    be done during calibration of the transmitter. A zero suppression kit can be installed in the

    transmitter for this purpose.

  • 7/31/2019 Level Mmt 1 Btech III

    24/44

    Zero Elevation

    When a wet leg installation is used (see Figurebelow), the low-pressure side of the leveltransmitter will always experience a higherpressure than the high-pressure side.

    This is due to the fact that the height of the wetleg (X) is always equal to or greater than themaximum height of the liquid column (H) insidethe tank.

    When the liquid level is at H meters, we have:

    Phigh = Pgas + S H

    Plow = Pgas + SX P = Phigh - Plow = SH - S X

    = - S (X - H)

  • 7/31/2019 Level Mmt 1 Btech III

    25/44

    Requirement for Zero Elevation

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level

  • 7/31/2019 Level Mmt 1 Btech III

    26/44

    The differential pressure P sensed by thetransmitter is always a negative number (i.e., low

    pressure side is at a higher pressure than highpressure side).

    P increases from P = -SX to P = -S (X-H) as thetank level rises from 0% to 100%.

    If the transmitter were not calibrated for thisconstant negative error (-SX), the transmitteroutput would read low at all times.

    To properly calibrate the transmitter, a positive

    bias (+SX) is needed to elevate the transmitter

    output. This positive biasing technique is called zero

    elevation.

  • 7/31/2019 Level Mmt 1 Btech III

    27/44

    Bubbler Level Measurement

    System

    If the process liquid containssuspended solids or is chemically

    corrosive or radioactive, it is desirableto prevent it from coming into directcontact with the level transmitter.

    In these cases, a bubbler levelmeasurement system, which utilizesa purge gas, can be used.

  • 7/31/2019 Level Mmt 1 Btech III

    28/44

    Open Tank Application for

    Bubbler System

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level

  • 7/31/2019 Level Mmt 1 Btech III

    29/44

    A bubbler tube is immersed to the bottom of the vessel inwhich the liquid level is to be measured.

    A gas (called purge gas) is allowed to pass through thebubbler tube. Consider that the tank is empty.

    In this case, the gas will escape freely at the end of thetube and therefore the gas pressure inside the bubbler tube(called back pressure) will be at atmospheric pressure.

    However, as the liquid level inside the tank increases,pressure exerted by the liquid at the base of the tank (andat the opening of the bubbler tube) increases.

    The hydrostatic pressure of the liquid in effect acts as aseal, which restricts the escape of, purge gas from thebubbler tube.

    As a result, the gas pressure in the bubbler tube willcontinue to increase until it just balances the hydrostaticpressure (P = S H) of the liquid.

    At this point the backpressure in the bubbler tube is exactlythe same as the hydrostatic pressure of the liquid and itwill remain constant until any change in the liquid leveloccurs.

    Any excess supply pressure will escape as bubbles throughthe liquid.

  • 7/31/2019 Level Mmt 1 Btech III

    30/44

    As the liquid level rises, the backpressure inthe bubbler tube increases proportionally,

    since the density of the liquid is constant. A level transmitter (DP cell) can be used to

    monitor this backpressure. In an open tank installation, the bubbler tube

    is connected to the high-pressure side of thetransmitter, while the low pressure side isvented to atmosphere.

    The output of the transmitter will beproportional to the tank level.

    A constant differential pressure relay is oftenused in the purge gas line to ensure thatconstant bubbling action occurs at all tanklevels.

  • 7/31/2019 Level Mmt 1 Btech III

    31/44

    The constant differential pressure relay maintains aconstant flow rate of purge gas in the bubbler tuberegardless of tank level variations or supply

    fluctuation. This ensures that bubbling will occur to maximum

    tank level and the flow rate does not increase at lowtank level in such a way as to cause excessivedisturbances at the surface of the liquid.

    Note that bubbling action has to be continuous or themeasurement signal will not be accurate.

    An additional advantage of the bubbler system is that,since it measures only the backpressure of the purgegas, the exact location of the level transmitter is notimportant.

    The transmitter can be mounted some distance fromthe process. Open loop bubblers are used to measure levels in

    spent fuel bays.

  • 7/31/2019 Level Mmt 1 Btech III

    32/44

    Closed Tank Application for

    Bubbler System If the bubbler system is to be applied to measure level in a

    closed tank, some pressure-regulating scheme must beprovided for the gas space in the tank.

    Otherwise, the gas bubbling through the liquid willpressurize the gas space to a point where bubbler supply

    pressure cannot overcome the static pressure it actsagainst. The result would be no bubble flow and, therefore,

    inaccurate measurement signal. Also, as in the case of aclosed tank inferential level measurement system, the low-pressure side of the level transmitter has to be connectedto the gas space in order to compensate for the effect ofgas pressure.

    Some typical examples of closed tank application ofbubbler systems are the measurement of water level in theirradiated fuel bays and the light water level in the liquidzone control tanks.

  • 7/31/2019 Level Mmt 1 Btech III

    33/44

    Effect of Temperature on Level

    Measurement Level measurement systems that use differential pressure

    P as the sensing method, are affected by temperature andpressure.

    The measured height H of a column of liquid is directlyproportional to the pressure P exerted at the base of the

    column and inversely proportional to the density of theliquid.

    H P/ Density (mass per unit volume) of a liquid or gas is

    inversely proportional to its temperature. 1/T

    Thus, for any given amount of liquid in a container, thepressure P exerted at the base will remain constant, butthe height will vary directly with the temperature.

    H T

  • 7/31/2019 Level Mmt 1 Btech III

    34/44

    Consider thefollowing scenario.A given amount of

    liquid in acontainer [figure(a)] is exposed tohigher process

    temperatures[figure (b)].

    Click to edit Master text styles

    Second levelThird levelFourth levelFifth level

    Click to edit Master text styles

    Second levelThird level

    Fourth levelFifth level

    (b) High Process Temperature

    (a) Low Process Temperature

  • 7/31/2019 Level Mmt 1 Btech III

    35/44

    As the amount (mass) of liquid does not changefrom figure (a) to (b), the pressure exerted on the

    base of the container has not changed and theindicated height of the liquid does not change. However, the volume occupied by the liquid has

    increased and thus the actual height hasincreased.

    The above scenario of figure (a, b) is a commonoccurrence in plant operations. Consider a level transmitter calibrated to read

    correctly at 750C. If the process temperature is increased to 90oC as

    in figure , the actual level will be higher thanindicated.

  • 7/31/2019 Level Mmt 1 Btech III

    36/44

    The temperature error can also

    occur in wet-leg systems

    Click to edit Master text styles Second level

    Third level Fourth level

    Fifth level

  • 7/31/2019 Level Mmt 1 Btech III

    37/44

    If the reference leg and variable leg are at thesame temperature that the level transmitter (LT)

    is calibrated for, the system will accuratelymeasure liquid level.

    However, as the process temperature increases,the actual process fluid level increases (aspreviously discussed), while the indicated

    measurement remains unchanged. Further errors can occur if the reference leg and

    the variable (sensing) leg are at differenttemperatures.

    The level indication will have increasing positive(high) error as the temperature of the wetreference leg increases above the variable(process) leg.

  • 7/31/2019 Level Mmt 1 Btech III

    38/44

    As an example, consider temperature changes around aliquid storage tank with a wet leg.

    As temperature falls and the wet leg cools off, the densityof the liquid inside it increases, while the temperature inthe tank remains practically unchanged (because of a muchbigger volume and connection to the process).

    As a result the pressure of the reference leg rises and theindicated level decreases.

    If it happens to the boiler level measurement for ashutdown system it can even lead to an unnecessaryreactor trip on boiler low level.

    However, high-level trips may be prevented under thesecircumstances.

    In an extreme case the wet leg may freeze invalidating themeasurement scheme completely, but it could be easily

    prevented with trace heating as indicated earlier (Figure 5). False high level indication can be caused by an increased

    wet leg temperature, gas or vapor bubbles or a drained wetleg.

  • 7/31/2019 Level Mmt 1 Btech III

    39/44

    A high measured tank level, with the real level

    being dangerously low, may prevent the actuationof a safety system on a low value of the tripparameter.

    The real level may even get sufficiently low to

    cause either the cavitations of the pumps thattake suction from the tank or gas ingress into thepumps and result in gas locking and a reduced orno flow condition.

    If the pumps are associated with a safety system

    like ECI or a safety related system like PHTshutdown cooling, it can lead to possible safetysystem impairments and increased probability ofresultant fuel damage.

    Eff t f P L l

  • 7/31/2019 Level Mmt 1 Btech III

    40/44

    Effect of Pressure on Level

    Measurement Level measurement systems that use differential pressure

    P as the sensing method, are also affected by pressure,although not to the same degree as temperaturementioned in the previous section.

    Again the measured height H of a column of liquid isdirectly proportional to the pressure PL exerted at the baseof the column by the liquid and inversely proportional to

    the density of the liquid:H PL/

    Density (mass per unit volume) of a liquid or gas is directlyproportional to the process or system pressure Ps.

    Ps Thus, for any given amount of liquid in a container, the

    pressure PL (liquid pressure) exerted at the base of thecontainer by the liquid will remain constant, but the heightwill vary inversely with the process or system pressure.

    H 1/Ps Most liquids are fairly incompressible and the process

    pressure will not affect the level unless there is significant

    vapor content.

  • 7/31/2019 Level Mmt 1 Btech III

    41/44

    Level Measurement System

    Errors The level measurement techniques

    described in this module use inferredprocesses and not direct measurements.Namely, the indication of fluid level is

    based on the pressure exerted on adifferential pressure (DP) cell by theheight of the liquid in the vessel.

    This places great importance on the

    physical and environmental problems thatcan affect the accuracy of this indirectmeasurement.

  • 7/31/2019 Level Mmt 1 Btech III

    42/44

    1. Connections

    As amusing as it may sound, manyavoidable errors occur because the DP cellhad the sensing line connections reversed.

    In systems that have high operating

    pressure but low hydrostatic pressure dueto weight of the fluid, this is easy to occur. This is particularly important for closed

    tank systems.

    With an incorrectly connected DP cell theindicated level would go down while thetrue tank level increases.

  • 7/31/2019 Level Mmt 1 Btech III

    43/44

    2. Over-Pressuring

    Three valve manifolds are provided on DP cells toprevent over-pressuring and aid in the removal ofcells for maintenance.

    Incorrect procedures can inadvertently over-

    pressure the differential pressure cell. If the cell does not fail immediately the internal

    diaphragm may become distorted. The measurements could read either high or low

    depending on the mode of failure. Note that if the equalizing valve on the three-valve

    manifold is inadvertently opened, the levelindication will of course drop to a very low level asthe pressure across the DP cell equalizes.

    3 S i li

  • 7/31/2019 Level Mmt 1 Btech III

    44/44

    3. Sensing lines The sensing lines are the important cord to the DP cell and must be

    functioning correctly. Some of the errors that can occur are:Obstructed sensing lines The small diameter lines can become clogged with particulate, with

    resulting inaccurate readings. Sometimes the problem is first notedas an unusually sluggish response to a predicted change in level.

    Periodic draining and flushing of sensing lines is a must.Draining sensing lines As mentioned previously, the lines must be drained to remove any

    debris or particulate that may settle to the bottom of the tank andin the line. Also, in closed tank dry leg systems, condensate must be removed

    regularly to prevent fluid pressure building up on the low-pressureimpulse line.

    Failure to do so will of course give a low tank level reading. Procedural care must be exercised to ensure the DP cell is not over-

    ranged inadvertently during draining. Such could happen if the block valves are not closed and equalizing

    valve opened beforehand. False high level indication can be caused by a leaking or drained

    wet leg. A leaking variable (process) leg can cause false low-level indication.