lhc critical areas en-el equipment

14
LHC Critical Areas EN-EL equipment 18 May 2010 RadWG – M. Munoz 1

Upload: bella

Post on 06-Feb-2016

39 views

Category:

Documents


0 download

DESCRIPTION

LHC Critical Areas EN-EL equipment. Critical Locations. Safe rooms, US%, UA%, UJ56, UJ76, RE% Experiment Caverns. Dry transformers, LV Switchboards, UPS, batteries 48VDC sources General Emergency Stop Racks RTU, DAU, PLC. RadWG – M. Munoz. 18 May 2010. Other Locations. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: LHC Critical Areas EN-EL equipment

LHC Critical AreasEN-EL equipment

18 May 2010 RadWG – M. Munoz 1

Page 2: LHC Critical Areas EN-EL equipment

Critical Locations

218 May 2010 RadWG – M. Munoz

Dry transformers,

LV Switchboards,

UPS, batteries

48VDC sources

General Emergency Stop Racks

RTU, DAU, PLC

Safe rooms, US%, UA%, UJ56, UJ76, RE%

Experiment Caverns

Page 3: LHC Critical Areas EN-EL equipment

Other Locations

318 May 2010 RadWG – M. Munoz

Dry transformers,

LV Switchboards, Emergency Stop ButtonsLighting

RR%, UPS%

UJ14, UJ16, UJ23

UW85

Tunnel:

Emergency Stop Buttons

Lighting

Safety lighting

F1, F2, F3, F4 distribution boxes

Page 4: LHC Critical Areas EN-EL equipment

EN-EL Safe Rooms

Main equipment:• General Emergency Stop Racks • 48VDC sources, batteries and distribution crates• UPS and UPS battery cubicles (except in UJ56, UJ76, US85)• Low voltage distribution switchboards• Racks with the equipment necessary to control and

monitor the electrical equipment. • Other services:

– GSM– Fire detection– Red téléphone network…

418 May 2010 RadWG – M. Munoz

Page 5: LHC Critical Areas EN-EL equipment

UL86

Additional shielding

US85-0 options

18 May 2010 RadWG – M. Munoz

Page 6: LHC Critical Areas EN-EL equipment

US85-1 relocation

• Four UPS units (machine and cryogenics) UA.– Sensible to radiation since their logic depends on transistors, CMOS,

IGBTs, microprocessors and other electronics.

• EYQ% rack with cryogenics 24VDC generation. – 24VDC PROMEC modules with electronic components sensible to

radiation (EPROMs, diodes, MOS, microprocessors, transistors…) powering cryogenics control PLCs.

18 May 2010 RadWG – M. Munoz

Page 7: LHC Critical Areas EN-EL equipment

Tfo

RM

U

EAD1/56

EBD1/56

EBD2/56

EAD2/56

ESD1/56 48VEOD1/56

ESD2/56

AUG Rack, LV Switchboards,48VDC Distribution

Shielding: 1.5 m

Solution 1:If equipment can stay

7

UJ56 options

18 May 2010 EN-EL/ICL du 5 mai 2010

Page 8: LHC Critical Areas EN-EL equipment

UJ561

Racks de stockage des spares convertisseurs

EN-EL/ICL du 5 mai 2010 8

UJ56 options

18 May 2010

Page 9: LHC Critical Areas EN-EL equipment

UJ76 relocation

• UPS’ relocated to TZ76.• Fenced Safe room: EBD, EAD, RMU,

Transformer • Concrete Safe room: AUG, 48VDC, EOD, ESD.

18 May 2010 RadWG – M. Munoz

Page 10: LHC Critical Areas EN-EL equipment

General Emergency Stop Racks• PCBs with the logic for the AUG

safety functions.• I/O cards, capacitors, diodes and

integrated circuits. • The safety logic is done via

contacts and relays that in principle should not be affected by radiation (LEP equipment).

• Determine behaviour in presence of radiation Monitoring?

1018 May 2010 RadWG – M. Munoz

Page 11: LHC Critical Areas EN-EL equipment

48VDC Sources

• Placed in safe rooms + RE%.• Ackermann manufaturer. Redundant chargers.• Power electronics and sensible components such as zener

diodes, transistors, PCBs with integrated circuits, thyristor bridge and PLC.

• If charger fails battery backup.• Lost of 48VDC AUG, ENS, HV protections, LV distribution,

safety lighting • Determine behaviour in presence of radiation.

Monitoring?

1118 May 2010 RadWG – M. Munoz

Page 12: LHC Critical Areas EN-EL equipment

LV Distribution Switchboards

• Power general services, CV, cryogenics, power converters, and LV distribution.

• Fuses, bornes, switch breakers…• Electronics existing in some protections tripping devices.• Micrologic in the tripping devices.• Radiation effects either make the protections to switch off

randomly or not to switch off at all, which might have important consequences in case of short-circuit or overload.

• Monitoring equipment and displays (DIRIS). No safety function, not right measurements or temporary supervision lost.

1218 May 2010 RadWG – M. Munoz

Page 13: LHC Critical Areas EN-EL equipment

Electrical Network Supervisor• They are vital for our monitoring systems. These racks could

be very sensible to radiation. • Racks contain all of the equipment necessary to control and

monitor the electrical equipment: • DAUs (data acquisition units)• RTUs (remote computers), microcontrollers, switches,

ethernet…• Possible radiation tests.

1318 May 2010 RadWG – M. Munoz

Page 14: LHC Critical Areas EN-EL equipment

Radiation deterioration ?

• Medium voltage transformers whose isolation “resine” (organic material) might decompose in the long term with radiation.

• Battery racks. Not affected by SEE. Deterioration?• General Emergency Buttons. Plastic component that is

deteriorated by radiation button might set an AU safety function off. Safety of people is ensured.

Annual tests of the AU system are carried out and campaigns of replacement of these AU buttons are foreseen.

1418 May 2010 RadWG – M. Munoz