Intelligent Fire Alarm Control Panels

NFS2-640(E)Intelligent Addressable Fire Alarm System

NFS-320Intelligent Addressable Fire Alarm System

NFS2-3030Intelligent Addressable Fire Alarm System

SFP-5UDC / SFP-10UDCConventional Fire Alarm Control Panel5-zone, 10-zone

DVC-EMDigital Voice Command

ONYX FirstVision™Interactive Firefighters’ Display

LCD2-80Terminal Mode/ACSModeAnnunciator

eVance™Service Manager

• Up to 159 detectors and 159 modules per SLC; 318 devices per loop/636 per FACP or network node

• Standard 80-character display, 640-character large display (NCA-2), or display-less (a node on a network)

• High-speed network for up to 200 nodes

• 6.0 A switch mode power supply with four Class A/B built-in Notification Appliance Circuits (NAC)

• Up to 159 detectors and 159 modules per SLC; 318 devices maximum

• Standard 80-character display

• High-speed network for up to 200 nodes

• 6.0 A power supply with four Class A/B built-in Notification Appliance Circuits (NAC)

• Full QWERTY keypad• Battery charger supports

18 – 200 AH batteries

• Up to 159 detectors and 159 modules per SLC; 318 devices per loop/3,180 per FACP or network node

• Large 16 line, 640 character LCD backlit display or use display-less as a network node

• High-speed network for up to 200 nodes

• A Fire Alarm Control Panel that provide reliable fire signaling protection for small to medium-sized commercial, industrial, and institutional buildings

• Outputs include four NACs (Notification Appliance Circuits), three programmable Form-C relays (factory programmed for Alarm, Trouble, and Supervisory) and 24 VDC special application resettable and nonresettable power outputs

• Programmable• Up to 32 minutes of

standard quality or 4 minutes of high quality digital audio storage of user-selected/created messages and tones

• 4-channel analog audio supported

• Up to 1000 audio sequences

• Message prioritization• Firefighters’ Telephone

Communications• Local paging microphone

option

• 22” LCD touch-screen

• Interfaces with ONYX® Series panels or NOTI•FIRE•NET (version 5.0 or higher)

• Compatible with standard and High Speed NOTI•FIRE•NET™

• Supports multiple gateways for large networks and campuses

• 80-character backlit Liquid Crystal Display (20 characters x 4 lines)

• Display mimics panel or NCA: - Event message - 20 characters for point label - 12 characters for extended label - Time, date and point address• Control switches for System

Acknowledge, Signal Silence Drill and System Reset

• LEDS for general off-normal events with UL 864 9th Edition Panels

• Keep track of annual inspection due dates for all fire systems

• Offer additional value to facility owners and managers

• Be proactive by receiving automatic alerts and notifications via Service Manager

• The customer’s equipment, service history and diagnostic information is available in real time

Features FeaturesFeatures Features

Features Features Features Features

Page 3: Life Safety and Emergency Communications Systems

Quezon City: ( 410-1155, 929-9911 • Cebu: ( 346-5413 • Davao: ( 282-8606 • [email protected] • www.multi-linegroup.com

800 SeriesLow-Profile Plug-inSmoke/Heat Detectors

FSM500KManual Call Point

LPX-751Very IntelligentEarly Warning (VIEW®)LASER Smoke Detector

FAPT-851Acclimate Plus™Multi-SensorLow-ProfileIntelligent Detector

NBG-12 SeriesManual Pull Stations

FSP-851(A) SeriesIntelligent Plug-InPhotoelectricSmoke Detectors withFlashScan®

• 2-wire conventional profile plug-in detectors aimed to meet the performance criteria designated by UL

• Operating Temperature Range: 0~38°C (32°F to 100°F) for Heat, 0~49°C (32°F to 120°F) for Photoelectronic

• Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing

• interruptionSensitivity: 63°C (145.4°F) Fixed (Heat only)

• Operating Voltage: 8.5~30 VDC for Heat, 8.5~35 VDC for Photoelectronic

• CSIRO Approved• Two wire connection for

easy installation• Suitable for flush mounting

or surface mounting• Simple rotary decade

setting• Integral LED controlled

from panel

• Very Intelligent Early Warning (VIEW®) smoke detection

• Advanced laser light source and patented optical design

• Sleek low-profile housing (1.66”/42.164 mm height)

• NOTIFIER Analog Addressable communications protocol provides extremely reliable operation proven in millions of worldwide detector installations

• Sensitivity to 0.03%/foot

• Automatically adjusts sensitivity levels without the need for operator intervention or programming, sensitivity increases with heat

• Microprocessor-based, combination photo and thermal technology

• Addressable-analog communication• Rotary, decimal addressing (1 – 99

on current classic systems, 1 – 159 on ONYX® Series FlashScan® systems, 1 – 99 on the AFC-600)

• Addresses can be viewed and changed without the need for electronic programmers

• Dual bi-color LED design provides 360° viewing angle

• LEDs lock red when in Alarm. In FlashScan®, LEDs flash green in Standby for normal condition

• Built-in tamper-resistant feature• Sealed against back pressure

• non-coded manual pull stations which provide a Fire Alarm Control Panel (FACP) with a single alarm initiating input signal

• This series includes both single-action and dual-action models equipped with either a hex or key lock / reset

• photoelectric detector’s unique optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-temperature thermal sensing on the FSP-851T(A)

• Sleek, low-profile design

• Addressable-analog communication

• Stable communication technique with noise immunity

• Two-wire SLC connection

Features

Features

FeaturesFeatures

Features

Features

882 Photoelectronic Detector

885 Heat Detector

FSP-851(A) in B210LP(A) Base

Fire Alarm Devices

Kobishi MBA-6Fire Alarm Bells

• DC 12.1mA• FWR 12.4mA• UL 83dB• Typical 87dB• Can used at outdoor• Very low current

consumption only 12.1mA at 24VDC

Features

EXITPOINTDirectional Sounder

• Four field-selectable routing evacuation patterns

• Ideal in unfamiliar surroundings or poor visibility

• Works in open areas, corridors or stairs

• Reduces evacuation times by as much as 75%

Features

Page 4: Life Safety and Emergency Communications Systems

Quezon City: ( 410-1155, 929-9911 • Cebu: ( 346-5413 • Davao: ( 282-8606 • [email protected] • www.multi-linegroup.com

FMM-1(A)Monitor Module with FlashScan®

FCM-1(A)Control and Relay Module

Portable Fireman’sTelephone Handset

Telephone Receptacles

FRM-1(A)Control and Relay Module

D42404-Wire PhotoelectricDuct Smoke Detector

• Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors

• Typically mounts to a 4” [10.16 cm] square box

• Addressable Control Module provides Notifier intelligent fire alarm control panels a circuit for Notification Appliances (horns, strobes, speakers, etc.)

• Addressable Relay Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers, control equipment, etc.

• Allows the dry contact to be activated, either manually or through panel programming, on a select basis

• Photoelectric, integrated low-flow technology

• Air velocity rating from 100 ft/min to 4,000 ft/min (0.5 m.s to 20.32 m/sec)

• Versatile mounting options square or rectangular configuration

• Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 90% non-condensing)

Features

Features

Features

Features

FMM-1(A) (Type H)

Fire Alarm Devices

Fire Alarm Modules

800 900 SeriesLinear Heat Detector

SpectrAlertIndoor Selectable-Output Speaker Strobes and Dual VoltageEvacuation Speakers

• Multiple alarm temperature ratings available for both digital and analogue type

• Maximum zone length (Digital) - 1000 meters

• Maximum zone length (Analogue) – 600 meters

• Resettable temperature up to 120°C (248°F)(Analogue)

• Compatible with any conventional or intelligent fire alarm panel

• Plug-in design and protective cover reduce ground faults

• Universal mounting plate with an onboard shorting spring tests wiring continuity before installation

• Field selectable candela settings

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Rotary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (¼, ½, 1 and 2 watts)

Features

Features

800 Series 900 Series

SpectrAlertAdvance SeriesIndoor Selectable-Output Horns, Strobesand Horn Strobes for Wall Applications

• Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela

• Field-selectable candela settings on wall units: 15, 15/75, 30, 75, 95, 110, 115, 135, 150, 177, and 185

• Rotary switch for horn tone and three volume selections

• Universal mounting plate for wall units

Features