load transfer in composite masonry - group hms · load transfer in composite masonry stephen a....
TRANSCRIPT
372
LOAD TRANSFER IN COMPOSITE MASONRY
STEPHEN A. MATTY Structural Engineer, Greiner, Inc.
Timonj.um, Maryland, USA JAMES COLVILLE
Professor and Chairman, Dept. of Civil Engineering University of Maryland, College Park, Maryland 20742, USA
AMDE M. WOLDE-TINSAE Associate Professor, Dept. of Civil Engineering
University of Maryland, College Park, Maryland 20742, USA
ABSTRACT
The results of an experimental investigation into the load transfer mechanism in composite masonry construction are presented. Results include bed joint strain readings in 46 composite masonry prisms from which an estimate of the distribution of shear force in the collar joint may be obtained.
INTRODUCTION
Although composite masonry construction, consisting of clay brick and
concrete masonry wythes bonded together by a collar joint of mortar or
grout, is widely used in the construction industry, the structural
behavior of composite walls, including the shear capacity of the collar
joint, load transfer mechanism between the wythes, and the effects of
restrained differential movement between the wythes is still not fully
understood.
It is believed that the key to understanding composite masonry lies
in defining the behavior of the interconnection between the wythes. The
primary objective of this pape r is to present the results of a series of
tests to investigate the load transfer mechanism in clay brick and
concrete masonry composite walls. A more comprehensive report on this
subject is presented in Reference [1]. In addition, Reference [2]
presents a synopsis of results of mortared collar joint shear capacities.
373
HATERIALS
Two types Df brick units were used: a Jefferson unit manufactured by
Glen-Gery Brick Corporation, Herndon, Virginia, and a Continental 375
unit manufactured by Potomac VaLley Brick and Supply Corporation, Lorton,
Virginia.
Tests were conducted on these units in accordance with the methods
and procedures described in Standard Methods of Sampling and Testing
Brick and Structural Clay Tiles, ASTM C67-80a. The properties Df the
units were as follows:
Jefferson brick (Note: coefficient of variation in % in parentheses).
Size
Weight
Absorption
Saturation coefficient
rnitial rate of absorption
2 1/4" x 3 7/16" x 7 7/8"
1672 gr (0.1 %)
3.2% (22.0%)
0.62 (7.7%)
15.9 gr/min/30 in2 (5.5%)
Compressive strength 12,500 psi (2.3%)
Continental brick (Note: coefficient Df variation in % in
parentheses)
Size
Weight
Absorption
Saturation Coefficient
rnitial rate of absorption
Compressive strength
2 1/4" x 3 9/16" x 8"
1820 gr (6%)
6.8% (36.2%)
0.80 (8.1%)
35.7 gr/min/30 in2 (21.8%)
12,700 psi (7.2%)
Because Df the relatively high initial rate Df absorption Df the
continental brick units, these bricks were wetted and allowed to surface
dry for approximately 45 minutes before construction Df the composite
test specimen.
The concrete masonry units used were hollow load-bearing units with a
nominal dimension of 6" x 8" x 8", manufactured by Ernest Maier Block
Company, Bladensburg, Maryland. Average properties of the units were as
follows (Note: coefficient of variation in % in parenthesis).
Size 5 5/8" x 7 7/8"
Gross area 44.3 in2
Weight 11.82 lbs (1.35%)
Absorption 11.5% (6.2%)
Compressive Strength
(Gross area)
374
1395 psi (8.7%)
AlI mortars were mixed in accordance with the Standard Specifications
for Mortar for Unit Masonry, ASTM C270-80a. A portland cement-lime
mortar was used for both Type N and Type S mortars.
The average compressive strength of the mortars was determined
according t o ASTM C780-80 and C109-80. For the Jefferson bricks, the
mortar strengths were 520 psi (CV = 20.6%) and 970 psi (CV = 8.9%) for
Type N and Type S mortar respectively . Comparable data for the specimen
made using the Continental 375 units was 520 psi (CV = 36.3%) for Type N
mortar, and 1110 psi (CV = 27 . 7%) for Type S mortar.
For the taller composite prisma, the Type N mortar compressive
strength was 772 psi (14.5%) for the Jefferson units and 878 psi (43.%)
for the Continental units.
Horizontal ladder type joint reinforcement was provided by DUR-O
WALL, Inc. Because of the r ela tively short specimen length, each collar
joint in the reinforced specimen was crossed by only a single #9 wire
(Note that the joint reinforcement was placed in the joint between
concre t e masonry units) .
The area of the joint reinforcement was 0.0171 in2 • Tests of three
tension specimens indicated that the yield strength of the s t eel was 88.3
ksi with an ultimate strength of 94.7 ksi.
Clay masonry prisms were tested for each combination of unit type and
mortar type. Three specimens were tested for each of the four parametric
combinations. Compressive strengths corrected for h/t ratio in
acco rdance with requirements of the Brick Institute of America are
presented below:
Jefferson units - Type N mort ar (JN) 2155 psi (CV=9.5%)
Jefferson units - Type S mortar (JS) 3050 psi (CV=1.6%)
Continental units - Type N mortar (CN) 1530 psi (CV=11.6%)
Continental units - Type S mortar (CS) 3310 psi (CV=3.9%)
FABRICATION
An experienced mason was used to fabricate 46 composite prisms. Forty
specimens were 16" high by 8" wide symmetrical prisms with two 3/8"
collar joints as shown in Fig la . The other six specimens were 32" high
x indicate s ~jir gage locations
I
(20 gugcs totul - eRch spccimen)
1
2
J
4
5
:1) Short spe~imC'1l 11) Tall Spce c:ímen
igllrc L - Composí tl' Tl'st Spl'cimen
w --...l VI
376
by 8" wide specimens with 3/8" collar joints as shown in Fig. lb. The
nomenclature used to identify the specimens is as follows: J;Jefferson
brick; C;Continental 375 brick; N; Type N mortar; S ; Type S mortar; R;
reinforcement; NR;no reinforcement, and T ; tall wall specimen (32"
high) •
For the 40 short composite prisms there were 8 combinations of 5
prisms fabricated. The combinations were as follows: J-N-NR; J-N-R; J-S
NR; J-S-R; C-N-NR; C-N-R; C-S- NR ; and C-S-R. For the six tal ler
composite prisms two combinations of 3 specimens each were constructed :
JT- N-NR and CT-N-NR. After fabrication, the specimens were covered with
polyethylene and allowed to cure for at least 28 days.
MEASURING DEVICES
Load cells were used to measure the load in each brick wythe and
specially fabricated and calibrated clip gages were used to measure
deEormations across bed joints of the brick wythe and across the collar
joints. A MEGADAC SYSTEM 100 data acquisition system was used to record
alI data.
TESTING DF CDHPDSITE PRISMS
For the short composite prisms, two clip gages were placed across each
brick bed joint. For the taller camposite prisms, two clip gages were
placed across the first, third, sixth, ninth, and eleventh brick bed
joints. Therefore, for both types oE specime ns, a total of 20 gages were
used. (Figures la and lb indicate the location of the clip gages .)
Readings were taken continuously throughout each experimento Since
the specimen is symmetrical the 2 readings obtained on the left hrick
wythe were averaged with the corresponding values obtained on the right
brick wythe.
TEST RESULTS
Typical test results for each specimen consist of bed joint strain
readings versus applied compressive load. A representative plot of this
data for alI C-S-NR prisms is shown in Figure 2. In this figure, it may
be noted that the r e sponse is relatively linear f ollowing an initial
1,0;lU
pl' r Wythc
(klps)
377
o .000 5
Strilln Cln/in)
f' igllfl' 2 - Ikcl Joint Stra Lns - C- S- NR Spl'C Lrnl'n
. 00 10
378
"settling" load of 1000-2000 pounds. The five lines represent the strain
measurements on each of the 5 bed joints (in the short specimens) . Data
obtained in the lowest bed joint was compared to data recorded in simple
prism tests for the same magnitude of loading . Reasonably good agreement
(10% differences in strain) was obtained in this comparison and as a
result it is believed that the individual strain readings ou each bed
joint are representative of actual strains occurring in the composite
specimens.
Also, it should be noted that there was no discernable difEerence in
the load transfer results for either of the two clay masonry units used.
Therefore, results for both types of unit have been combined in this
paper.
A summary of the test results for all specimen groups is presented in
Tables 1, 2 and 3. These tables show the percentage of applied load
transferred through each instrumented bed joint. From this data, the
load being transferred through the collar joints of the specimens can be
estimated as the differences in load transferred through each bed joint.
This latter information is presented in Tables 1, 2 and 3 as load in the
collar joint.
Top of Specimen
Joint 1 Joint 3 Joint 6 Joint 9 Joint 11
Bottom of specimen
TABLE Load Distribution - Tall Prisms
Load/bed joint
.1SP
.56P
.81P
.82P 1.OOP
Collar joint load
.1SP
.41P (2 units)
.25P (3 units)
.01P (3 units)
.18P (2 units)
379
TABLE 2 Load Distribution - Short Prisms, Type N mor t a r
No Reioforeement \Hth Reinfo r ce me nt Top oE Load/bed Colla r Load / bed Colla r Speeimen Joint Jo in t Load Joint Joint load
Joint 1 .45P . 45P .14P .14P J oin t 2 . S3P . 08 P .43P .29p Joint 3 .69P . 16P .43P O Joint 4 . S3P .14P .68P .25P Join t 5 1.00P .1 7P I. OOP . 32P
Bot t om oE Speeimen
TABLE 3 Load Distribution - Short Prisms, Type S mortar
No Reinforeement With Reinforeement Top oE Load/ bed Collar Lo ad/bed Collar Speeime n joiot joint load join t joint load
Joint I .1 6P .1 6P .OlP .0lP Joint 2 .1?P . 01P .30P .23P Joint 3 . 32P .15P . 46P .1 6P Joint 4 .58P .26P . 77P .31P Joint 5 1.00P .42P 1. 00P .23P
Bottom of Specime n
ANALYSIS OF RESULTS
In revie wing the data presented in Table 1, it may be noted that
approximately 56% of the load is trans Ee rred Erom the loaded bloek wythe
through the eollar joint to the briek wythes in the top 8" of the
speeimen, and app roxima t ely 80% oE the load is transfe rred io the upper
halE of the specimen. Thus the eollar joint shear s tress is not uniform
along the height Df the speeimen a nd in fae t the eollar joint shear
stress is maximum in the vicinity Df the ap plied load. These
experimental r es ults are in general agreement with nume r ieal s tudies by
Anand [3,4].
Results for the short specimens are more varied. For the t ype N
mortar prisms with no joint reiofo reement, a eonsiderable portioo (45%)
of the applied load is transferred at the top of the speeimen , with 69%
of the load transEerred in the top half of the spec imeo. There is a lso a
fairly uniform distribution oE load through joints 3, 4 and 5. This
380
relatively rapid load transfer is similar to that obtained in the tal 1
prisms. Thus, for type N mortar without joint reinEoreement both the
tal1 and short speeimens are somewhat similar with respeet to load
transfer near the top of the speeimen. On the other hand, the
unreinforced type S mortar speeimens show a markedly different
distribution of load with a signlfleant fraetion of 10ad transEerred near
the bottom of the speeimens.
ANALYTICAL MODEL
Due to the eompexity of the experimental results a simple analytieal
model of the short composite prisms was deveIoped to qualitatively
investigate the effeet of the stiffness of the bed joints and eollar
joints on the load transfer rneehanism. This model, whieh eonsiders eaeh
masonry unit as a rigid mass and represents the mortar joints as linearly
elastie springs, is shown in Figure 3. Three springs were used to
represent the axial bed joint stiffnesses in the block and briek wythes,
respeetively, and the eollar joint shear stiffness. Results of two
combinations of the relative stiffnesses of these springs are presented
below in Table 4.
TABL.E 4 Load Distribution - Short Prisms
Top of Speeimen
Joint 1 Joint 2 Joint 3 Joint 4 Joint 5
Bottom of Speeimen
Load/bed Joint
.20P
.45P
.83P
.80P 1.00P
Model 1*
Collar Joint Ioad
.20P
.25P
.38P -.03P
.20P
*Model - KI ** Model 2 - Kl
70, K2 20, K3 20 70, K2 5, K3 20
Model 2**
Load/bed Joint
.20P
.42P
.66P
.80P 1.0OP
Collar Joint
.20P
.22P
.24P
.14P
.20P
These results indieate that the distribution of load transferred through
the eollar joint is not uniform. However, as the shear stiffness of the
eollar joint is redueed in relation to the axial bed joint stiffness of
the rnasonry wythes, there is a more uniform load transfer through the
eollar joint.
382
CONCLUSIONS
The results of the load transfer data indicate that the type of mortar
and presence of joint reinforcement influence the load transfer across
the collar joint. For the taller composite prisms, the shearing stress
along the collar joint is nonuniform and the are a of high shear stress
occurs in the upper region of the specimen. AIso, approximately 80% of
the load is transferred through the collar joint to the brick wythe in
the upper half of the eomposite prism. The smaller composite prisms with
similar characteristics to the taller composite prisms, namely, Type N
mortar and no joint reinforcement, showed a similar load transfer
mechanism.
The smaller composite prisms with type S mortared collar joints, and
Type N mortared collar joints with joint reinforcement did not show the
same load transfer distribution as the prisms with Type N mortared collar
joints and no joint reinforcement.
Thus, for the Type S and Type N reinforced specimens, the area of
high shear stress occurs in the lower half of the collar joint although
the load distribution along the eollar joint seems to be more uniform.
Since the simple model analysis indicates a more uniform load transfer as
the stiffness of the collar joint is r educed in comparison to the bed
joint stiffness, the test data would only be consistent with this result
if the Type S mortar produces an increase in collar joint stiffness that
is relatively smaller than the corresponding increase in bed joint
stiffness as compared to Type N mortar. Also, it would appear that the
joint reinforcement has a more pronounced effect on the bed joint
stiffness than the shear joint stiffness.
The results presented clearly indicate that the interaction of
composite masonry through a mortared collar joint is complicated and that
a more accurate and comprehensive analytical model is needed to fully
comprehend the load transfer mechanism data obtained from the
experimental t ests. The major contribution of this paper is the
presentation of previously unavailable data on this interaetion which may
serve as a be nchmark in the evaluation of future analytical methods of
analysis of composite masonry construction.
383
ACKNOWLEDGEMENTS
The work reported in this paper was funded by the International Masonry
Institute. Any opinions expressed herein are solely the responsibility
of the authors and do not necessarily reflect the views of IMI.
REFERENCES
1. Matty, S.A., Colville, J., and Wolde-Tinsae, A.M., "An Experimental Study on the Shear Capacity of Collar Joints and the Load Tra ns fer Mechanism in Composite Masonry," Volumes I and 11, Final Report, submitted to the International Masonry Institute, July 1987.
2. Colville, J., Matty, S.A., and Wolde-Tinsae, A.M., "Shear Capacity of Mortared Collar Joints," Proceedings, Fourth North American Masonry Conference, Los Angeles, California, August 1987.
3. Anand, S.C., "Shear Stresses in Composite Masonry Walls," New Analysis Techniques for Structural Masonry, American So ciery-of Civil Engineers, New York, Sept. 1985, pp. 106-117.
4. Anand, S.C., and Yalamanchili, K., "Evaluation of Loads at Cracking in Collar Joints of Composite Masonry Walls," Department of Civil Engineering, Clemson University, Clemson, S.C.