loading on canopy

7
Loading on Canopy Dead load Aluminium Clad = 0.5 = kN/m Other = Imposed load On roof = 0.25 Wind load Basic wind speed ( V ) = 38 m/s Design wind speed (Vs) = VxS1xS2xS3 S1 = 1.1 T:b-2 b condition S2 = 0.7 T:b-3 2c S3 = 1.0 Vs = 29.26 m/s Dynamic pressure (q) = k = 0.59 q = 0.51 if wind angle = 0 deg if wind angle = 180 deg Cp -1 -1 Cp 1 0 1 0 F1 F2 F3 F4 wind load -0.51 0.51 -0.51 0.51 load combination for canopy DL = 0.50 Critical canopy loads IL = 0.25 WL 1 F1 = -0.51 downwards = 1.51 2 F2 = 0.51 upwards = -0.21 3 F3 = -0.51 4 F4 = 0.51 case 1 : 1.4DL+1.6IL = 1.10 case 2 : 1.0DL+1.4WL 1 = -0.21 2 = 1.21 3 = -0.21 4 = 1.21 case 3 : 1.2DL+1.2IL+1.2WL 1 = 0.29 2 = 1.51 3 = 0.29 4 = 1.51 kN/m² kN/m² kN/m² kXVs² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m² kN/m²

Upload: umesh-chamara

Post on 28-Oct-2015

31 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Loading on Canopy

Loading on Canopy

Dead load

Aluminium Clad = 0.5 = kN/m

Other =

Imposed load

On roof = 0.25

Wind load

Basic wind speed ( V ) = 38 m/s

Design wind speed (Vs) = VxS1xS2xS3S1 = 1.1 T:b-2 b conditionS2 = 0.7 T:b-3 2cS3 = 1.0

Vs = 29.26 m/s

Dynamic pressure (q) =k = 0.59q = 0.51

if wind angle = 0 deg if wind angle = 180 deg

Cp -1 -1

Cp 1 0 1 0

F1 F2 F3 F4

wind load -0.51 0.51 -0.51 0.51

load combination for canopy

DL = 0.50 Critical canopy loadsIL = 0.25WL 1 F1 = -0.51 downwards = 1.51

2 F2 = 0.51 upwards = -0.213 F3 = -0.514 F4 = 0.51

case 1 : 1.4DL+1.6IL = 1.10

case 2 : 1.0DL+1.4WL 1 = -0.212 = 1.213 = -0.214 = 1.21

case 3 : 1.2DL+1.2IL+1.2WL 1 = 0.292 = 1.513 = 0.294 = 1.51

kN/m²

kN/m²

kN/m²

kXVs²

kN/m²

kN/m² kN/m² kN/m² kN/m²

kN/m²kN/m²kN/m² kN/m²kN/m² kN/m²kN/m²kN/m²

kN/m²

kN/m²kN/m²kN/m²kN/m²

kN/m²kN/m²kN/m²kN/m²

Page 2: Loading on Canopy
Page 3: Loading on Canopy

Load combination for truss or fram

truss space = 5 m

Dead load as Udl as point loadroof = 2.50 kN/m #REF! kNswif wt = 0.5 kN/m #REF! kN

Total = 3.00 kN/m = #REF! kN

Imposed load as Udl as point loadroof = 1.25 kN/m = #REF! kN

Wind load as Udl as point load

F1 = -2.53 kN/m = #REF! kNF2 = 2.53 kN/m = #REF! kNF3 = -2.53 kN/m = #REF! kNF4 = 2.53 kN/m = #REF! kN

Page 4: Loading on Canopy
Page 5: Loading on Canopy

Sanken Project-Toyota Wattala

Job Ref.

CONSTRUCTION (PVT) LTD Section- Canopy Beams Sheet no./rev.

sky's the limit Calc. by Date Chk'd by Date App'd by Date

Steel Design -BS5950-1:2000 Umesh 4/17/2023 PP

Ref. Calculations Output

Design for I sections

Use 150x 100x 21.1 kg/m section

Design Load (ULS-from slab) 2.84 kN/mSpan 2.10 m

Section Properties Use 150x 100x 21.1 kg/m sectionWeight = 21.10 kg/m

275D = 148 mmB = 100.0 mmT = 9 mmt = 6 mmr = 11 mm

1020

61.7 mm

23.7 mm

Loading

Ult. load (UDL-with Self Load)= 3.14 kN/mUlt. Point Load (Edge of Beam)= 0.00 kNSer. load (UDL-with Self Load)= 2.09 kN/mService load = 0.00 kN

6.91 kNm 6.91 Check Manually

6.58 kN 6.58 Check Manually

Shear Capacity Check

BS5950-1:2000 Steel Grade S275

Table9 275.00BS5950-1:2000

Cl. 4.2.3

146.52 kN 146.52Shear Force = 6.58 kN 6.58

Section is Satisfied for Shear.

Section Classification CheckBS5950-1:2000 Section Classification for Flange

Table 11 b/T 5.56

Limiting Values€ 1.00

9 € 9.0010 € 10.0015 € 15.00

Flange Section is Class 1 Plastic

Section Classification for Web

d/t 21.67

Limiting Values€ 1.00

80 € 80.00100 € 100.00120 € 120.00

Web Section is Class 1 Plastic

Therefore I Section is Class 1 Plastic

Moment Capacity CheckBS5950-1:2000

Cl. 4.2.5.2 Low Shear Low Shear

S(Plastic Section Modulus)=

150450.00

41373750.00 Nmm41.37 kNm 41.37

Bending Moment = 6.91 kNm BMmax = 6.91

Section is Satisfied for Bending.

BS5950-1:2000 DeflectionTable 8 Allowable Deflection (Length/180) 11.67 mm

Actual Deflection = 2.43 mm

Section is Satisfied for Deflection.

Hence the selected I - section is ok for the floorUse 150x 100x 21.1 kg/m section

Chuan Eu International

Pte Ltd-Product Guide

Py = N/mm2

IX = cm4

RX =

RY =

BMmax = BMmax =

SFmax (When Point load at support)= SFmax =

Design Strength (Py) N/mm2

Shear Capacity (Pv)= .6 x Py x Av

Pv =

SFmax =

Section is Satisfied for Shear.

Flange Section is Class 1 Plastic

Web Section is Class 1 Plastic

Therefore I Section is Class 1 Plastic

Moment Capacity (Mc )= Py x S

btf ( d - tf ) + 0.25tw ( d - 2tf )2

mm3

Mc =

Mc =

Section is Satisfied for Bending.

(wSerl4/8EI )

Section is Satisfied for Deflection.

Hence the selected I - section is ok for the

floor