low voltage cables cu or al - xlpe - pvc
TRANSCRIPT
APPLICATION
Al / XLPE / PVC
CONSTRUCTION CHARACTERISTICS
Conductor
Copper (plain annealed): solid class 1 or stranded class 2 or flexible class 5, circular or sector shaped Aluminium: stranded class 2, circular or sector shaped.
Insulation XLPE – (Cross-linked polyethylene)
Oversheath PVC – (Polyvinyl chloride)
GENERAL CHARACTERISTICS
Construction and test standards IEC 60228 • IEC 60502-1
Rated voltage U /U0 0.6 / 1 kV
Test voltage 3.5 kV a.c. 5 minutes
Conductor maximum operating temperature 90°C
Maximum short-circuit temperature 250°C (t ≤ 5s)
Minimum bending radius (mm) (permanent. after installation) (during installation)
4xd if d<25 • 6xd if d≥25 • 8xd if sector shape cond.6xd if d<25 • 9xd if d≥25 • 12xd if sector shape cond.
Maximum pulling force over conductor (N)Copper – 50 x S
Aluminium – 30 x S
Flame retardantIEC 60332-1-2 • EN 60332-1-2 (cable vertically
mounted, length of charred cable ≤ 540 mm)2S – conductor cross-section (mm )
d – cable outer diameter (mm)
≤≤
FAST
CA
BLES
ADDITIONAL CHARACTERISTICS
Fire retardant (frt)IEC 60332-3-24 • EN 60332-3-24 (bunch of cables
cable ≤ 2.5 m)vertically mounted on a ladder, length of charred
CABLE DESIGNATION
LOW VOLTAGE CABLESINDUSTRIAL CABLES
Cu or Al - XLPE - PVCStandard - Unarmoured IEC-60502-1
LOW VOLTAGE CABLESINDUSTRIAL CABLES
ELECTRICAL AND DIMENSIONAL CHARACTERISTICS
Cu or Al - XLPE - PVCStandard-Unarmoured IEC-60502-1
Cable compositionn.º cond. x cross-section
2(mm )
Approximateouter diameter
(mm)
Approximateweight
(kg/km)
Current carrying capacity(2)In open air T = 30°C
(A)
2 charged conductors 3 charged conductors
26
36
49
63
90
121
161
200
242
310
377
437
504
575
679
783
940
1083
1287
26
36
49
63
86
115
149
185
225
310
377
437
Cu / XLPE / PVC
1x1.5
1x2.5
1x4.0
1x6.0
1x10
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630
2x1.5
2x2.5
2x4.0
2x6.0
2x10
2x16
2x25
2x35
2x50
2x70
2x95
2x120
3x1.5
3x2.5
3x4.0
3x6.0
3x10
5.8
6.2
6.8
7.3
8.2
9.3
10.9
11.9
13.2
15.0
16.9
18.6
20.7
23.0
25.8
28.6
32.2
35.7
41.4
9.6
10.4
11.5
12.6
14.4
16.6
19.8
21.8
24.4
28.2
31.8
35.4
10.1
11.0
12.1
13.4
15.3
50
63
80
103
147
207
302
395
519
724
971
1205
1473
1839
2381
2989
3834
4734
6099
113
140
177
224
319
441
642
840
1079
1517
2042
2537
137
175
228
298
417
20
28
40
53
80
107
141
176
216
279
342
400
484
533
634
736
868
998
1065
23
32
42
54
75
LOW VOLTAGE CABLESINDUSTRIAL CABLES
Cu or Al - XLPE - PVCStandard-Unarmoured IEC-60502-1
ELECTRICAL AND DIMENSIONAL CHARACTERISTICS
Cable compositionn.º cond. x cross-section
2(mm )
Approximateouter diameter
(mm)
Approximateweight
(kg/km)
Current carrying capacity(2)In open air T = 30°C
(A)
2 charged conductors 3 charged conductors
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x400
3x16+1x10
3x25+1x16
3x35+1x16
3x50+1x25
3x70+1x35
3x95+1x50
3x120+1x70
3x150+1x70
3x185+1x95
3x240+1x120
3x300+1x150
3x400+1x185
4x1.5
4x2.5
4x4.0
4x6.0
4x10
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
17.6
18.0
20.0
22.8
26.0
29.1
32.3
36.1
40.0
44.8
49.5
56.4
19.3
21.6
24.1
27.7
32.2
36.1
40.3
45.0
50.1
56.1
62.0
70.7
10.8
11.9
13.2
14.5
16.7
19.3
21.6
24.1
27.7
32.2
36.1
40.3
45.0
600
846
1125
1495
2087
2834
3552
4361
5434
7059
8877
11145
714
1037
1322
1781
2496
3372
4314
5149
6512
8395
10512
13178
165
210
279
368
537
772
1122
1492
1986
2803
3804
4587
5876
100
127
158
192
246
298
346
399
456
538
626
720
100
127
158
192
246
298
346
399
456
538
626
720
23
32
42
54
75
100
127
158
192
246
298
346
399
LOW VOLTAGE CABLES INDUSTRIAL CABLES
Cu or Al - XLPE - PVCStandard-Unarmoured IEC-60502-1
ELECTRICAL AND DIMENSIONAL CHARACTERISTICS
Cable compositionn.º cond. x cross-section
2(mm )
Approximateouter diameter
(mm)
Approximateweight
(kg/km)
Current carrying capacity(2)In open air T = 30°C
(A)
2 charged conductors 3 charged conductors
4x185
4x240
4x300
4x400
50.1
56.1
62.0
70.7
7350
9521
11962
15004
456
538
626
720
LOW VOLTAGE CABLESINDUSTRIAL CABLES
Al - XLPE - PVCUnarmoured - Controlled Unscreened - IEC 60502-1
ELECTRICAL AND DIMENSIONAL CHARACTERISTICS
Cable compositionn.º cond. x cross-section
2(mm )
Approximateouter diameter
(mm)
Approximateweight
(kg/km)
Current carrying capacity(2)In open air T = 30°C
(A)
2 charged conductors 3 charged conductors
96
121
150
184
237
289
337
389
447
530
613
740
856
996
Al / XLPE / PVC
1x16
1x25
1x35
1x50
1x70
1x95
1x120
1x150
1x185
1x240
1x300
1x400
1x500
1x630
3x16
3x25
3x35
3x50
3x70
3x95
3x120
3x150
3x185
3x240
3x300
3x25+1x16
3x35+1x16
3x50+1x25
3x70+1x35
3x95+1x50
3x120+1x70
3x150+1x70
3x185+1x95
3x240+1x120
3x300+1x150
9.3
10.9
11.9
13.2
15.0
16.9
18.6
20.7
23.0
25.8
28.6
32.2
35.7
41.4
17.6
18.0
20.0
22.8
26.0
29.1
32.3
36.1
40.0
44.8
49.5
21.6
24.1
27.7
32.2
36.1
40.3
45.0
50.1
56.1
62.0
116
161
196
246
325
417
504
620
764
967
1188
1485
1845
2321
387
485
592
742
969
1253
1559
1882
2309
2926
3557
580
693
892
1172
1521
1872
2250
2759
3488
4272
84
107
135
165
215
264
308
358
413
492
571
694
806
942
77
97
120
146
187
227
263
304
347
407
455
97
120
146
187
227
263
304
347
407
455
ELECTRICAL AND DIMENSIONAL CHARACTERISTICS
Cable compositionn.º cond. x cross-section
2(mm )
Approximateouter diameter
(mm)
Approximateweight
(kg/km)
Current carrying capacity(2)In open air T = 30°C
(A)
2 charged conductors 3 charged conductors
Al / XLPE / PVC
4x16
4x25
4x35
4x50
4x70
4x95
4x120
4x150
4x185
4x240
4x300
19.3
21.6
24.1
27.7
32.2
36.1
40.3
45.0
50.1
56.1
62.0
766
613
753
965
1281
1661
2016
2487
3050
3861
4748
77
97
120
146
187
227
263
304
347
407
455
LOW VOLTAGE CABLESINDUSTRIAL CABLES
Al - XLPE - PVCUnarmoured - Controlled Unscreened - IEC 60502-1
Other compositions are available, contact [email protected] for information.
(1) Phase conductors sector shape.(2) Installation in free air or on perforated cable tray, horizontal or vertical.
Single core cables – Flat touching installation.Cables with 2 and 3 conductors: 2 charged conductors.Cables with 4 and 5 conductors: 3 charged conductors.For compositions of 4 conductors. the same characteristics apply if the fourth conductor is the earth conductor or neutral conductor.