Low-Voltage Circuit BreakersSelection Guide

CATALOGUE No. ’05-G90E

Page 2: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

1

Terasaki developed its original breaker for the first time in Japan in 1947.

Since then, the company has been offering, as a specialized breaker

manufacturer, the most advanced breakers not only to the Japanese market, but

also to the world markets.

The TemBreak series of Moulded case circuit breakers, which is evaluated as

highly reliable by our customers, has been improved from time to time for better

performance through Terasaki's advanced technologies.

In 2000, the TemPower 2 series was released to replace the Tempower series of

air circuit breakers, which had received high reputations for many years. This

new series consists of small, high-performance air circuit breakers featuring

advanced information and communication capabilities.

Terasaki is ready to meet the customers' requirements in the 21st century through

its diversified model lineup and its broad range of enhanced products.

circuit breakers. Our mature product line supports the wide ranging needs of our customers.

Contents

In September 1993, Terasaki ob-tained certification for the world quali-ty assurance standard ISO9002. In 1994, we obtained certification forthe even more rigorous ISO9001which covers additional items such as“Management Responsibil i t ies”,“Employee Training”, “Design andDevelopment”, and “Service”. In the future, we will respond to theeven higher level of global needs with“international reliability”.

In April 2000, Terasaki was certifiedas conforming to ISO 14001, an inter-national environment-related stan-dard. The company gives priority toits commitment to the curtailment orabolishment of using environmentallyharmful substances, energy saving inthe production activities, reduction ofwastes, and effective utilization of re-sources.

ISO9001 certificate

ISO14001 certificate

World Class Air Circuit Breaker

Energy saving support

Power Monitoring Equipment

Company profile———————————————————— 2

1. TemPower —————————————————————— 6

¡Air Circuit Breakers AR ———————————————— 6

¡Air Circuit Breakers AT•AH ——————————————— 8

¡Air Circuit Breakers AME ———————————————— 9

2. TemBreak ——————————————————————10

z Moulded Case Circuit Breakers —————————————10

¡Economical XE Series ————————————————10

¡Standard XS Series —————————————————12

¡High-fault Level XH Series ——————————————15

¡Motor Protection XM Series ——————————————16

¡D.C. Application Series ————————————————17

¡Current-Limiting Breakers, TL Series ——————————18

¡TO/TT Series ————————————————————20

¡Mining Series ————————————————————21

¡Non-automatic Trip Breakers —————————————22

¡Thyrister Protection Breakers —————————————24

¡TB Series for Distribution Board use ——————————25

¡Adjustable Thermal Trip ————————————————26

¡Marine Approval ———————————————————28

x Earth-leakage Relays ——————————————————30

¡TZS Series —————————————————————30

3. TemMeasure ————————————————————31

4. TemPlug ——————————————————————32

5. TemDin ———————————————————————33

6. Other Electrical Distribution Equipment ——————34

¡Special Circuit Breakers ————————————————34

Page 3: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

2

TTTTEEEERRRRAAAASSSSAAAAKKKKIIIIPPPPrrrrooooffffiiii lllleeee

Sales departmentfor marine

Technical departmentfor marine

Sales departmentfor industrial

Technical departmentfor Industrial

Imari factoryYao factory Yabakei factory

Sales department

Technical department

Kami factory

Quality assurancedepartment

Business administrationdivision

Accounting & financedepartment

General affairsdepartment

President

Board of directors

Section of inspector

Board of auditors

Industrial systemsMarine systems

Circuit breakers

Quality assurancedepartment

Short-circuittesting station

Division administrationdepartment

Division administrationdepartment

Customers

■Established: October 1,1923

■President: Masakazu Fujita

■Capital: 641 million yen

■Number of employees: 813

■Sales: (Mar. 2004) 19,353 million yen

■Line of business

• Marine Systems Division:

Power distribution systems, Engine monitoring & control

systems, General instrumentation

• Industrial Systems Division:

Power distribution system, Co-generation system,

Independent generation plant (distributed power supply),

System engineering, Electronic equipment and systems for

factory automation, Monitoring & control system

Medical tools and equipment

• Circuit Breaker Division:

Moulded case circuit breakers, Air circuit breakers.

Minuature circuit breakers, Power monitoring equipments

Circuit Breaker Division

Industrial Systems Division

Marine SystemsDivision

Page 4: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

3

TERASAKI ELECTRIC CO., LTD.Osaka, JAPANHeadquarter

Overseas Affiliates

q

o

w

r

t

e

yu

i

TERASAKI (EUROPE) LTD.Glasgow, SCOTLAND U. K.

TERASAKI ITALIA s.r.l.Milano, ITALY

TERASAKI ESPAÑA, S.A.U.Barcelona, SPAIN

TERASAKI SKANDINAVISKA ABSKOGÅS SWEDEN

TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.SINGAPORE

TERASAKI ELECTRIC (M) SDN. BHD.Shah Alam, MALAYSIA

TERASAKI DO BRASIL LTDA.Rio de Janeiro, BRAZIL

TERASAKI ELECTRIC (CHINA) LIMITEDZengcheng, CHINA

TERASAKI ELECTRIC CO., (FAR EAST) PTE. LTD.SINGAPORE

q

w

e

r

t

y

u

i

o

TERASAKI Global NetworkTERASAKI Global Network

●1 TERASAKISKANDINAVISKA AB(SWEDEN)

●2 TERASAKI (EUROPE) LTD.(U.K.)

●3 TERASAKI ESPAÑA, S.A.U.(SPAIN)

●4 TERASAKI ITALIA s.r.l.(ITALY)

■TERASAKI ELECTRIC CO., LTD.(JAPAN)

●5 TERASAKI ELECTRIC(M) SDN. BHD. (MALAYSIA)

●6 TERASAKI CIRCUITBREAKERS (S) PTE. LTD.(SINGAPORE)

●7 TERASAKI ELECTRIC CO.,(FAR EAST) PTE. LTD.(SINGAPORE)

●8 TERASAKI ELECTRIC(CHINA) LTD.(CHINA)

●9 TERASAKI DO BRASIL LTDA.(BRAZIL)

Page 5: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

• Short-circuit Testing Station

q Short-circuit test generator No.1w Short-circuit test generator No.2e Voltage change devicer Back-up breakert Making switchy Reactors, Resistanceu Step-down 3ø transformeri 800V d.c. short-circuit testing

equipmento Pit!0 Impulse generator!1 Control room!2 Computerized control equipment

q

w

e

r

t

y

u

i

o

!0

!2

!1

4

Certifications, Authorizations or Approvals by World's Leading Organizations

Air Circuit BreakersASTA/U.K.ASTA CERTIFICATION SERVICES

SECV/AustraliaState Electricity Commission of Victoria

LR/U.K.Lloyd’s Register of Shipping

BV/FranceBureau Veritas

GL/GermanyGermanischer Lloyd

AB/U.S.A.American Bureau of Shipping

NK/JapanNippon Kaiji Kyokai

Moulded Case Circuit BreakersASTA/U.K.ASTA CERTIFICATION SERVICES

SECV/AustraliaState Electricity Commission of Victoria

LR/U.K.Lloyd’s Register of Shipping

BV/FranceBureau Veritas

GL/GermanyGermanischer Lloyd

AB/U.S.A.American Bureau of Shipping

NK/JapanNippon Kaiji Kyokai

Based Standards

Air Circuit BreakersIEC 60947-2International Electrotechnical Commission

BS EN 60947 Part 2/U.K.British Standard

VDE 0660 Part 101/GermanyVerband Deutscher Elektrotechnicker

NEMA PUB NO. SG3/U.S.A.National Electrical Manufacturers Association

ANSI C37. 13/U.S.A.American National Standard institute

JIS C8372/JapanJapanese Industrial Standard

JEC-160/JapanJapanese Electrical Committee

Moulded Case Circuit BreakersIEC 60947-2International Electrotechnical Commission

BS EN 60947 Part 2/U.K.British Standard

VDE 0660 Part 101/GermanyVerband Deutscher Elektrotechnicker

CEI EN 60947 Part 101/GeramanyItalian Standard

NEMA AB-1/U.S.A.National Electrigal Manufacturers Association

JIS C8370/JapanJapanese Industrial Standard

Short-circuit test generator No.1

Short-circuit test generator No.2

TYPE TESTS on every lot

öConstruction testöOperation testöTripping testöOverload testöOvershooting testöTemperature rise testöEndurance testöInsulation resistance testöWithstand voltage testöShort-circuit testöFlexible cord protection testöShort-circuit making capacity testöShort-time withstand current test

RELIABILITY TESTS

öVibration testöMechanical operation testöRust proof testöMechanical impact testöHeat-shock testöGas proof testöAging test

Combined Short-circuit Capacity(MVA) When TwoShort-circuitTest Generators (No.1 and No.2)are Paralleled.

Time after short-circuit (Cycle)

Sym. 3ø R.M.S.

0 10601/2 9501 8603 710

TERASAKI is always pleasedto send you the world’s top-class products.Already for many decades TERASAKI has beeninternationally minded. This is proved by the num-ber of certifications, authorizations and approvalsby the world’s leading organizations and authori-ties.TERASAKI maintains the top position.TERASAKI will exert its further efforts to attainmore international quality recognition.

Page 6: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

TemBreakMoulded Case �

Circuit Breakers

(AME series for �Generator Protection)

Power Monitoring �Equipment

Direct bus plug-in �mounting base

Air Circuit Breakers

Earth-leakage Relays

Air Circuit Breakers �with enhanced OCR

5

AAAAppppppppeeeeaaaarrrraaaannnncccceeee ooooffff mmmmaaaajjjjoooorrrr pppprrrroooodddduuuuccccttttssss

Page 7: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

6

Air Circuit Breakers

AR Standard Series1AMPERE RATING(A)TYPERATED CURRENT (max) [In](A) IEC, EN, AS

q w JISNEMA, ANSIMarine

NEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLES e rRATED PRIMARY CURRENT OF OVER–CURRENTRELEASE [ICT](A)• for general feeder circuit use

RATED CURRENT OF OVER–CURRENT RELEASE(A)• for generator protection use[In] is generator rated current.

AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) tRATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) yAC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]IEC,EN,AS AC 690V u[Ics = Icu] 440VNEMA AC 600VANSI 480V

240VJIS AC 550V

460V220V

o DC 600V !0

250VNK !2 AC 690V

450VLR, AB, !2 AC 690VGL, BV 450V

RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV)RATED SHORT TIME WITHSTAND 1sCURRENT[Icw][kA rms] 3sLATCHING CURRENT (kA)TOTAL BREAKING TIME (s)CLOSING OPERATION TIMESPRING CHARGING TIME (s) max.CLOSE TIME (s) max.No. of operating cycles Mechanical life with maintenance

without maintenance Electrical life without maintenance AC460V

AC690VWEIGHT (kg) draw-out typeOUTLINE DIMENSION (mm)FIXED TYPE a

bcd

DRAW-OUT aTYPE !3 b

cd

800AR208S8008008008008003 4200400800

100ÖInÖ200200ÉInÖ400400ÉInÖ800

1000690

50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

126550650.03

100.08

3000015000120001000073 86

360 44546029075354 43946034540

1250AR212S125012501250125012503 44008001250

200ÖInÖ400400ÉInÖ800630ÉInÖ1250

1000690

50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

126550650.03

100.08

3000015000120001000073 86

360 44546029075354 43946034540

1600AR216S160016001540160016003 440080012501600

200ÖInÖ400400ÉInÖ800630ÉInÖ1250800ÉInÖ1600

1000690

50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

126550650.03

100.08

3000015000120001000076 90

360 44546029075354 43946034540

2000AR220S200020002000200020003 4400800125016002000200ÖInÖ400400ÉInÖ800630ÉInÖ1250800ÉInÖ16001000ÉInÖ20001000690

50/10565/143 i42/96.650/11565/149.550/10565/14365/14340/4040/4050/11565/153 i50/11565/153 i

126550650.03

100.08

250001200010000700079 94

360 44546029075354 43946034540

2500AR325S250025002500250025003 42500

1250ÖInÖ2500

1000690

65/14385/187 i50/11565/149.585/195.565/14385/195.585/195.540/4040/4065/15385/201 i65/15385/201 i

128565850.03

100.08

200001000070005000105 125

466 58646029075460 58046034540

3200AR332S320032003200320032003 43200

1600ÖInÖ3200

1000690

65/14385/187 i50/11565/149.585/195.565/14385/195.585/195.540/4040/4065/15385/201 i65/15385/201 i

128565850.03

100.08

200001000070005000105 125

466 58646029075460 58046034540

q : Values in open air at 40°C (45°C for marine applications).w : Values of AR208S ~ 216S for draw-out type with horizontal terminals,

Values of AR220S ~ 440S for draw-out type with vertical terminals.e : For 2poles use both opposite ends poles of 3poles ACBs.r : 4poles ACBs without Neutral phase protection can not be applied to

IT earthing systems.t : Rated insulation voltage depends on applied standard: 1000V AC

according to IEC 60947-2.

4000AR440S400037003700400040003 44000

2000ÖInÖ4000

1000690

75/165100/22065/149.575/172.5100/23075/165100/230100/23040/4040/4075/179100/24575/179100/245

12100851000.03

100.08

15000800050002500139 176

— ————631 80146037553

y : Rated operational voltage depends on applied standard: 690Vaccording to IEC 60947-2.

u : Cannot apply IT earthing system, ie, insulated from earth.i : For 500V AC.o : Please contact TERASAKI for DC application.!0 : 3poles in series should be applied for 600V DC.!2 : Applicable to only 3poles ACBs.!3 : For vertical terminals or horizontal terminals.

a c d

b

a c d

b

Page 8: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

7

Air Circuit Breakers

AR High Fault Series1AMPERE RATING(A)TYPERATED CURRENT (max) [In](A) IEC, EN, AS

q w JISNEMA, ANSIMarine

NEUTRAL POLE AMPERES FRAME (A)NUMBER OF POLES e rRATED PRIMARY CURRENT OF OVER–CURRENTRELEASE [ICT](A)• for general feeder circuit use

RATED CURRENT OF OVER–CURRENT RELEASE(A)• for generator protection use[In] is generator rated current.

AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) tRATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) yAC RATED BREAKING CAP [kA sym rms]/MAKING CAP [kA peak]¶IEC,EN,AS AC 690V u[Ics = Icu] 440VNEMA AC 600VANSI 480V

240VJIS AC 550V

460V220V

o DC 600V !0

250VNK !2 AC 690V

450VLR, AB, !2 AC 690VGL, BV 450V

RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV)RATED SHORT TIME WITHSTAND 1sCURRENT[Icw][kA rms] 3sLATCHING CURRENT (kA)TOTAL BREAKING TIME (s)CLOSING OPERATION TIMESPRING CHARGING TIME (s) max.CLOSE TIME (s) max.No. of operating cycles Mechanical life with maintenance

without maintenance Electrical life without maintenance AC460V

AC690VWEIGHT (kg) draw-out typeOUTLINE DIMENSION (mm)DRAW-OUT aTYPE !3 b

cd

1250AR212H125012501250125012503 42004008001250

100ÖInÖ200200ÉInÖ400400ÉInÖ800630ÉInÖ1250

1000690

55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186

128055650.03

100.08

3000015000120001000079 94

354 43946034540

1600AR216H160016001600160016003 41600

800ÖInÖ1600

1000690

55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186

128055650.03

100.08

3000015000120001000079 94

354 43946034540

2000AR220H200020002000200020003 42000

1000ÖInÖ2000

1000690

55/12180/17642/96.655/12780/18455/12180/17680/17640/4040/4055/12880/18655/12880/186

128055650.03

100.08

3000015000120001000079 94

354 43946034540

1600AR316H160016001600160016003 420040080012501600100ÖInÖ200200ÉInÖ400400ÉInÖ800630ÉInÖ1250800ÉInÖ16001000690

85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

1210075850.03

100.08

2500012000100007000105 125

460 58046034540

2000AR320H200020002000200020003 42000

1000ÖInÖ2000

1000690

85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

1210075850.03

100.08

200001000070005000105 125

460 58046034540

2500AR325H250025002500250025003 42500

1250ÖInÖ2500

1000690

85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

1210075850.03

100.08

200001000070005000105 125

460 58046034540

3200AR332H320032003200320032003 43200

1600ÖInÖ3200

1000690

85/187100/22050/11580/184100/23085/196100/230100/23040/4040/4085/201100/23385/201100/233

1210075850.03

100.08

200001000070005000105 125

460 58046034540a c d

b

q : Values in open air at 40°C (45°C for marine applications).w : Values for draw-out type with vertical terminals.e : For 2poles use both opposite ends poles of 3poles ACBs.r : 4poles ACBs without Neutral phase protection can not be applied to

IT earthing systems.t : Rated insulation voltage depends on applied standard: 1000V AC

according to IEC 60947-2.

y : Rated operational voltage depends on applied standard: 690Vaccording to IEC 60947-2.

u : Contact TERASAKI for details.o : Please contact TERASAKI for DC application.!0 : 3poles in series should be applied for 600V DC.!2 : Applicable to only 3poles ACBs.!3 : For vertical terminals.

¶ : When the ACB is used without Instantaneous trip function MCR should be set to work. The rated breaking capacity will reduce to the level of the latching currentwithout MCR function.

Page 9: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

8

Air Circuit Breakers

AT•AH Series1Frame Size (A)Type° RATED CURRENT [In] (A) IEC, BS, VDE, AS (Max.) q JIS

JEC !0NEMA, ANSIMarine

Neutral Pole Amperes Frame (A) wNumber of Poles e° RATED PRIMARY CURRENT OF

OVER-CURRENT TRIP DEVICES [ICT] (A)• for general feeder circuit use° RATED CURRENT OF

OVER-CURRENT TRIP DEVICES [Io] (A)• for generator protection use ([Io] is generator rated current)AC Rated insulation voltage [Ui] (V) rRated operational voltage [Ue] (V) t° AC RATED BREAKING CAP.(kA sym.)/MAKING CAP.(kA peak)

with INST AC 690V !1[Ics]=100%[Icu] 600V !1

500VUp to 415V

with MCR AC 690V !1600V !1

Up to 500Vwithout INST AC 690V !1

Up to 500Vwith INST AC 600V

480V240V

with MCR AC 600VUp to 480V

without INST Up to AC 600Vwith INST AC 550V

460V220V

with MCR AC 550VUp to 460V

without INST Up to AC 550Vwith INST only DC 250V uwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500Vwith INST AC 500Vwith MCR AC 500Vwithout INST AC 500V

Rated impulse withstand voltage [Uimp] (kV)Utilization CategoryRated short time withstand current 1Srms [Icw] (kA) 3SLatching current rms (kA)Total breaking time (s)Closing operation timeSpring charging time (s) max.Close time (s) max.Weight (kg) draw-out type (Motor Charging)° OUTLINE DIMENSION (mm)Fixed aType b

cd

Draw-out aType b

cd

NOTE) — : “no”or “not available”.

q Values in open air at 40°C (45°C for marine applications). w Neutral current rating is equal to the max. applicable current rating, which varies depending on applicable standards. e 2-pole type is identical

to 3-pole type except the centre pole is omitted. 4-poles type can not be applied to Marine approval. r 1000V.AC. according to IEC60947-2. t 690V.AC. according to IEC60947-2. y 1700A for JEC

standard. u DC rating is of special application. i Full rated neutral pole available on request. o Values at 480V AC. !0 Ratings are the actual performance not the recommended values of the standard.

!1 Cannot apply IT earthing system, ie, insulated from earth. !2 86.1/203kA at 660V.AC. !3 87.6/203kA at 660V.AC.

IECBS

VDEAS[Ics]

NEMA

JIS

ANSI

JEC

NK

AB

LR

BV

GL

a c d

b

50

a c d

b

50

2000AT20L200020001700—20002000 y3 4320 1600630 20001250—

690480

———130/286————————————130/325130/325————130/322 o——130/322 o——130/322 o——130/322 o—————8A1717170.02

100.0691 115

— ————368 45349245892

2500AT25L250025002300—25002000 i3 42500

690480

———130/286————————————130/325130/325————130/322 o——————————————8A1717170.02

100.06152 188

— ————518 65352645882

4000AH-40C4000400036504000400032002,3 44000

1600ÖIoÖ4000

1000690

85/18785/187120/264120/26485/18785/187100/22060/13260/132100/230120/276120/276100/230100/23060/138100/230120/300120/300100/230100/23060/13240/40120/286100/23160/138120/286100/23160/138124/280 !2108/23962.8/144120/286100/231—120/286100/220—8B10070600.03

100.04240 280

————622 782655566106

5000AH-50C5000500046505000500050002,3 45000

2000ÖIoÖ5000

1000690

85/18785/187120/264120/26485/18785/187100/22070/15470/154100/230120/276120/276100/230100/23070/161100/230120/300120/300100/230100/23070/15440/40120/286100/23170/153120/286100/23170/153124/280108/23976.3/170120/286100/231—120/264100/220—8B10070700.03

100.04350 450

————747 937685589146

6300AH-60C6300615053006150600063002,3 46300

2500ÖIoÖ6300

1000690

85/18785/187120/264120/26485/18785/187120/26470/15470/154100/230120/276120/276100/230120/27670/161100/230120/300120/300100/230100/30070/15440/40120/286120/28670/153120/286120/28670/153124/280 !3124/28077.37/166120/280100/239—120/264——8B12070700.03

100.04380 480

————747 937685589146

Page 10: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

9

Air Circuit Breakers

AME Series for Generator protection1

NOTES: ¡ : Available. — : Not available.q : With long time-delay trip and short time-delay trip.w : Cannot use UVT and SHT jointly.e : Equipped as standard.r : Used for testing instantaneous trip function (separate mounting).

NK standard requires at least one checker per vessel.t : Used for testing tripping characteristics with secondary current.

Frame Size [A]TypeNumber of polesRated current of overcurrent trip device [A](ln is generator rated current)

Rated insulation voltage (Ui) [VAC]Rated frequency [Hz]° AC RATED BREAKING CAPACITY [kA sym. rms.] /RATED MAKING CAPACITY [kA peak]LR, AB, GL, with INST 460VBV, NK without INST q 460VRated short-time current (lcw) [kA, rms.]° OPERATIONDirect manualExternal manual (option)Motorized (option)° DIMENSIONS (mm)rear-connected (RC)/plug-in (PM)

abcd

° CONNECTIONS AND MOUNTINGSRear connected Flat bar stud RCPlug-in For switchboard PMweight Direct manual operation/(Rear connected)(kg) Direct manual operation/(Plug-in)° ACCESSORIES (option)Undervoltage trip w UTVShunt trip w SHTAuxiliary switch AXAlarm switch ALHandle extension (For direct manual) EHATerminal cover for rear connected • plug-in TCROCR checker rOCR adapter t° PROTECTIVE FUNCTIONSElectronic type LTD • STD • INST

STD • INST° ENDURANCE

Number of operations with currentNumber of operations without current

c d

Type AME 4B( Direct manual operation ) Type AME 4B( Motorized operation )

250AME3B316 ÖI

nÖ31.5

31.5 ÉInÖ63

63 ÉInÖ125

125 ÉInÖ250

60050/60

16/34.84/6.874 (150ms)

¡¡¡

182/161260/282121/121255/245

¡¡6.58.2

¡¡¡ e¡—¡¡¡

¡¡

20008000

400AME4B3200ÖI

nÖ400

60050/60

16/34.86/10.26 (150ms)

¡¡¡

182/161260/282121/121255/245

¡¡6.58.2

¡¡¡ e¡—¡¡¡

¡¡

10009000

630AME6B3315ÖI

nÖ630

60050/60

20/42.610/17.410 (150ms)

¡¡¡

252/231273/303121/121267/270

¡¡1016.1

¡¡¡ e¡¡ e¡¡¡

¡¡

5004500

800AME8B3500ÖI

nÖ800

60050/60

30/63.815/33.015 (150ms)

¡¡¡

252/231370/370120/138282/336

¡¡19.530.1

¡¡¡ e¡¡ e—¡¡

¡¡

5004500

1000AME10B3800ÖI

nÖ1000

60050/60

30/63.815/33.015 (150ms)

¡¡¡

252/231370/370120/138282/336

¡¡19.530.1

¡¡¡ e¡¡ e—¡¡

¡¡

5004500

Page 11: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

10

TemBreakz Moulded Case Circuit Breakers

Economical XE Series2Frame Size [A]TypeNumber of PolesOutside view

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

3 155 2010 30(40°C only)—220

——2.5—————2.5/1.3(220V)———————A

45.5 689652670.27 0.4

' e——õ————

———

¡ y—

——

— ¡ (AXE)——————————¡¡¡—————

30XE30NS2 3

3 15 405 20 5010 30

6660

1.52.55—1.5/0.8 @52.5/1.3 @52.5/1.32.5/1.35/2.5——5—2.55—A

50 7513068870.48 0.74

' e—õõ—— õ— õ—

———

¡ u—

¡¡

¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡

50XE50NB2 3

15 40 7520 50 10030 60(40°C only)6660

257.5—2/1 @55/2.5 @55/2.55/2.57.5/3.8——7.5—510—A

50 7513068870.48 0.74

' r—õõ————

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡

100XE100CB2 3

10 30 6015 40 7520 50 100

6660

7.51025—7.5/3.8 @510/5 @510/515/7.525/13——25—7.515—A

50 7513068870.48 0.74

' r—õõ—õõ—

———

¡ u—

¡¡

¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡

100XE100NS2 3

15 40 7520 50 10030 60

8690

101425—10/5 @514/714/718/925/13——25—1015—A

60 9015568860.78 1.1

'—õõ—õõ—

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡

100XE100HB2 3

125 200150 225175

8690

57.515—5/2.5 @57.5/3.87.5/3.87.5/3.815/7.5—7.515—1010—A

10516060831.4

'õ (BAR)õ—————

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡————————¡¡¡—¡ !2—¡¡

225XE225CS3

125 200150 225175

8690

101525—10/5 @515/7.515/7.518/925/13—1525—1015—A

10516060831.4

'õ (BAR)õ—õ———

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡—¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡

225XE225NC3

250 400300350

8690

152535—15/7.5 @518/925/1325/1335/18—1835—2020—A

1402601031314.7

'õ (BAR)õ—õ———

———

—¡

¡¡

¡ (AX)¡ (AX)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡

400XE400NS3

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.e : Comes with conductor pressing terminal.r : Comes with conductor pressing terminal for below 50A rating.

y : Hydraulic-magnetic type for below 5A rating.u : Hydraulic-magnetic type for below 10A rating.o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

Page 12: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

11

TemBreakz Moulded Case Circuit Breakers

Economical XE Series2Frame Size [A]TypeNumber of PolesOutside view

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

600XE600NS3

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.

o : The UVT controller is installed externally, when provided with AC UVT.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

500600

8690

182535—18/9 @520/1025/1325/1335/18—2035—2020—A

2102731031459.0

—'õ—õ———

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Page 13: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

12

TemBreakz Moulded Case Circuit Breakers

Standard XS Series2Frame Size [A]TypeNumber of PolesOutside view

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.e : Comes with conductor pressing terminal.

u : Hydraulic-magnetic type for below 10A rating.o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

3 155 2010 30

6660

1.52.55—1.5/0.8 @52.5/1.3 @52.5/1.32.5/1.35/2.5——5—2.55—A

50 7513068870.48 0.74

' e—õõ—— õ— õ—

———

¡ u—

¡¡

¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡

30XS30NB2 3

10 3015 4020 50

6660

57.510—5/2.5 @57.5/3.8 @57.5/3.810/510/5——10—7.515—A

50 7513068870.48 0.74

' e—õõ—õõ—

———

¡ u—

¡¡

¡ (AXE)¡ (ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡

50XS50CB2 3

10 3015 4020 50

6660

7.51025—7.5/3.8 @510/5 @510/515/7.525/13——25—7.515—A

50 7513068870.48 0.74

' e—õõ—õõ—

———

¡ u—

¡¡

¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡

50XS50NB2 3

60

6660

7.51025—7.5/3.8 @510/5 @510/515/7.525/13——25—7.515—A

50 7513068870.48 0.74

'—õõ—õõ—

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡

15 40 7520 50 10030 60

8690

1525505/2.5 @512/6 @525/1325/1330/1550/25——50—1520—A

60 90 12015568860.78 1.1 1.4

'—õõ—õõ ——

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡ !2—¡¡

100XS100NB2 3 4

125 200150 225175

8690

2225508/4 @522/11 @525/1325/1335/1850/25222550—4040—A

105 140165861071.85 2.4

'õ (BAR)õ—õõ——

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡——¡¡

225XS225NS3 4

60XS60NS2 3

FOR JAPANESE MARKET

Page 14: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

13

TemBreakz Moulded Case Circuit Breakers

Standard XS Series2600XS600NE3 4

800XS800NS3 4

800XS800CS3 4

600XS600NS3 4

600XS600CS3 4

400XS400NS3 4

400XS400NE3 4

700800

8690

35508520/10 @535/18 @550/2550/2565/3385/43305085—4040—A

210 2802731031459.4 12.2

—'õ—õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

700800

8690

25355016/8 @525/13 @530/1535/1845/2350/25253550—4040—A

210 2802731031459.4 12.2

—'õ—õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Adjustable300 500350 6004008690

35508520/10 @535/18 @550/2550/2550/2585/4330508510——10 (0.3sec)B

210 2802731031459.6 12.0

—'õ—õõ—õ !3

¡¡—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

300 6004005008690

35508520/10 @535/18 @550/2550/2565/3385/43305085—4040—A

210 2802731031459.0 11.5

—'õ—õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

300 6004005008690

25355016/8 @525/13 @530/1535/1845/2350/25253550—4040—A

210 2802731031459.0 11.5

—'õ—õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Adjustable125 200 200 300150 225 225 350175 250 4008690

35508518/9 @530/15 @542/2150/2550/2585/433042855——5 (0.3sec)B

140 1852601031314.8 6.2

'õ (BAR)õ—õõ—õ !3

¡¡(PTA only)—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡

125 200 300150 225 350175 250 4008690

35508518/9 @530/15 @542/2150/2550/2585/43304285—4040—A

140 1852601031314.7 6.1

'õ (BAR)õ—õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡

125 200 300150 225 350175 250 4008690

22305016/8 @522/11 @530/1535/1835/1850/25223050—4040—A

140 1852601031314.7 6.1

'õ (BAR)õ—õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡

400XS400CS3 4

Frame Size [A]TypeNumber of PolesOutside view

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.

o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!3 : Special specification.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

……

……

Page 15: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

14

TemBreakz Moulded Case Circuit Breakers

Standard XS Series2Frame Size [A]TypeNumber of PolesOutside view* 2 pole breaker is a 3 pole breaker with the center pole omitted.

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.

o : The UVT controller is installed externally, when provided with AC UVT.!0 : One is supplied with every five breakers. Please specify if more are required.!3 : Special specification.!4 : Handle is supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Magnetic trip only. Contact Terasaki for details.@5 : The application on IT systems on this voltage is not available.

2500XS2500NE3 4

2000XS2000NE3 4

1600XS1600NE3 4

1000XS1000NE3 4

1200XS1200NE3 4

Adjustable1200 20001400 250016008690

658513045/42 @565/49 @585/6485/64100/75125/94658512542——42 (0.3sec)B

320 42945018524562.5 78.2

————'———

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡——¡ !4¡¡¡¡———¡—¡

Adjustable1000 16001200 18001400 20008690

658513045/42 @565/49 @585/6485/64100/75125/94658512542——42 (0.3sec)B

320 42945018524554.0 67.0

—õ——'——õ

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡——¡ !4¡¡¡¡———¡—¡

Adjustable800 1200900 14001000 16008690

658513045/34 @565/49 @585/6485/64100/75125/94658512520——20 (0.3sec)B

210 28037014019127.0 35.0

—õ——'——õ

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

Adjustable600 1000700 12008008690

506510025/19 @545/34 @565/4965/4985/64100/7542658515——15 (0.3sec)B

210 28037012017122.0 28.0

—'——õõ—õ !3

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡¡—¡¡—¡

Adjustable500 800600 900700 10008690

506510025/19 @545/34 @565/4965/4985/64100/7542658515——15 (0.3sec)B

210 28037012017122.0 28.0

—'——õõ—õ !3

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡¡—¡¡—¡

800XS800NE3 4

Adjustable400 600450 700500 8008690

35508520/10 @535/18 @550/2550/2550/2585/4330508510——10 (0.3sec)B

210 2802731031459.7 12.5

—'õ—õõ—õ !3

¡¡—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Page 16: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

15

TemBreakz Moulded Case Circuit Breakers

High-fault Level XH Series2

15 4020 50308690

3550858/4 @525/13 @542/2150/2550/2585/43——85—4040—A

90 120155861041.3 1.58

'—õõ—õõ ——

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡

400XH400NE3 4

800XH800PS3 4

800XH800NE3 4

600XH600NE3 4

225XH225NE3 4

225XH225NS3 4

50XH50NS3 4

100XH100NS3 4

700800

8690

658513045/23 @565/33 @585/4385/43100/50125/636585125—4040—A

210 2802731031459.4 12.2

—'——õõ—õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Adjustable400 600450 700500 8008690

506510020/10 @542/21 @565/3365/3365/33100/5042658510——10 (0.3sec)B

210 2802731031459.7 12.5

—'õ—õõ—õ !3

¡¡—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Adjustable300 500350 6004008690

506510020/10 @542/21 @565/3365/3365/33100/5042658510——10 (0.3sec)B

210 2802731031459.6 12.0

—'õ—õõ—õ !3

¡¡—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

Adjustable125 200 200 300150 225 225 350175 250 4008690

506510020/10 @542/21 @565/3365/3365/33100/504265855——5 (0.3sec)B

140 1852601031314.8 6.2

'õ (BAR)õ—õõ—õ !3

¡¡(PTA only)—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡

Adjustable125 200150 2251758690

35508518/9 @530/15 @542/2150/2550/2585/433042855——5 (0.3sec)B

140 1852601031314.8 6.2

'õ (BAR)õ—õõ—õ !3

¡¡ (PTA only)—

——

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2¡—¡

125 200150 2251758690

35508515/7.5 @525/13 @542/2150/2550/2585/43254285—4040—A

105 1401651031242.1 2.6

'õ (BAR)õ—õõ—õ !3

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡

15 40 7520 50 10030 608690

3550858/4 @525/13 @542/2150/2550/2585/43——85—4040—A

90 120155861041.3 1.58

'—õõ—õõ ——

———

¡—

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡

Frame Size [A]TypeNumber of PolesOutside view

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

NOTES: ' : Standard. This configuration is used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.

o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!3 : Special specification.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

……

……

FOR JAPANESE MARKET

FOR JAPANESE MARKET

Page 17: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

16

TemBreakz Moulded Case Circuit Breakers

Motor Protection XM Series2

200- 400-220V 440V

[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 2515 32

6660

2.552.5/1.32.5/1.35/2.5—5A

7513068870.74

' e—õõ—õõ—

—¡ i

¡¡

¡ (AXE)¡ (ALE)¡——¡¡¡—¡—¡¡¡¡¡—¡¡

100- 200-110V 220V

[Kw] [A] [A]0.1 40.2 6.3 1.40.4 10 2.60.75 16 4.21.5 7.42.2 103.7 165.5 257.5 33

6220

—2.5——2.5/1.3-(220V)——A

45.5 689652670.27 0.4

' e——õ————

¡—

——

— ¡(AXE)——————————¡¡¡—————

° RATINGSVoltage for motor 50/60 Hz

Motor output and rated current at 40°C(45°C for marine applications)

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 460V

220VIEC 60947-2 Icu/Ics 415VBS EN 60947-2 380V

240VNEMA AB-1 480V

240VUtilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSHydraulic-magnetic tripsThermal and fixed magnetic trips° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

50XM50NB3

225XM225NS3

100XM100NB3

100XM100CS3

50XM50CB3

30XM30PB3

30XM30CS2 3

30XM30NB3

200- 400-220V 440V

[Kw] [A] [A]30 12537 15045 17555 22575 15090 175110 225

8690

255025/1335/1850/252550A

105165861071.85

'õ (BAR)õ—õ———

—¡

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡

200- 400-220V 440V

[Kw] [A] [A]3.7 165.5 257.5 32 1611 45 2515 60 3218.5 75 4022 90 4530 6037 7545 9055 100

8690

255025/1330/1550/25—50A

9015568861.1

'—õõ————

—¡

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡ !2—¡¡

200- 400-220V 440V

[Kw] [A] [A]15 6318.5 7522 9030 6337 7545 9055 100

6660

102510/515/7.525/13—25A

7513068870.74

'—õõ————

—¡

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡—¡¡

200- 400-220V 440V

[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 45 2515 3218.5 4022 456660

10 !62510!6/5!715!6/7.5!725/13—25A

7513068870.74

' e—õõ————

—¡ i

¡¡

¡ (AXE)¡ (ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡—¡¡

200- 400-220V 440V

[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 16 85.5 25 127.5 32 1611 45 2515 3218.5 4022 456660

2.552.5/1.32.5/1.35/2.5—5A

7513068870.74

' e—õõ—õõ—

—¡ i

¡¡

¡ (AXE)¡ (ALE)¡——¡¡¡—¡—¡¡¡¡¡—¡¡

200- 400-220V 440V

[Kw] [A] [A]0.2 1.4 0.70.4 2.6 1.40.75 4 2.01.5 8 42.2 10 53.7 85.5 12

6660

8512585/8585/85125/125—125A

78147.5981171.78

' e—õõ—õ——

¡—

¡¡

¡ (AXE)¡ (ALE)¡——¡¡¡—¡—¡¡————¡¡

Frame Size [A]TypeNumber of PolesOutside view

d

b

ca

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.e : Comes with conductor pressing terminal.i : Hydraulic-magnetic type for below 25A rating.

o : The UVT controller is installed externally, when provided with AC UVT.!2 : Line side interpole barriers are supplied as standard.!6 : 7.5kA for below 8A rating.!7 : 3.8kA for below 8A rating.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.

Page 18: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

17

TemBreakz Moulded Case Circuit Breakers

D.C. Application Series2Frame Size [A]TypeNumber of PolesOutside view* 2 pole breaker is a 3 pole breaker with the center pole omitted.

° RATED CURRENT (In) [A]at 40°C

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VDC]° RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 AC 550V

460V220V

DC 250VIEC 60947-2 Icu/Ics AC 690VBS EN 60947-2 500V

440V415V380V240V

DC 250VNEMA AB-1 AC 600V

480V240V

Without Inst. AC 240-690VRated short time current (lcw) [kA. rms.]Utilization Category° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

d

b

ca

2500XS2500ND*2 3

2000XS2000ND*2 3

1200XS1200ND*2 3

1600XS1600ND*2 3

2500 @4

8600

———40——————40/30—————A

32045018524555.7 62.5

————'———

———

—¡ @4

¡¡

¡ (AX)¡ (AL)¡—¡¡——¡ !4¡¡¡¡———¡—¡

2000 @4

8600

———40——————40/30—————A

32045018524550.0 54.0

—õ——'——õ

———

—¡ @4

¡¡

¡ (AX)¡ (AL)¡—¡¡——¡ !4¡¡¡¡———¡—¡

1600 @4

8600

———40——————40/30—————A

21037014019124.0 27.0

—õ——'——õ

———

—¡ @4

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

1200 @4

8600

———40——————40/30—————A

21037014019123.8 26.0

—'——õ———

———

—¡ @4

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

1000XS1000ND*2 3

1000

8600

———40——————40/20—————A

2102731031459.2 10.3

—'——õ———

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.

!0 : One is supplied with every five breakers. Please specify if more are required.!4 : Handle is supplied as standard.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Magnetic trip only.

Page 19: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

18

600TL-600NE3 4

1200TL-1200NE3 4

1000TL-1000NE3 4

800TL-800NE3 4

400TL-400E3 4

225TL-225F3

100TL-100F3 4

BAdjustable600 1000700 1200800690

6512515045/34 @575/57 @5125/65125/65125/65150/113658512515——815 (0.3sec)

210 28037014019126.0 33.7

—'——õõ—õ !3

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

Frame Size [A]TypeNumber of PolesOutside view

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.o : The UVT controller is installed externally when provided with AC UVT.!0 : One is supplied with every five breakers. Please specify if more are required.

!3 : Special specification.!4 : Rated current shown in ( ) is for 4 poles only, and special specification.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

BAdjustable500 800600 900700 1000690

6512515045/34 @575/57 @5125/65125/65125/65150/113658512515——815 (0.3sec)

210 28037014019126.0 33.7

—'——õõ—õ !3

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

Utilization Category° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.]° DIMENSIONS (mm)

abcd/e

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

BAdjustable400 600450 700500 800690

6512515045/34 @575/57 @5125/70125/70125/70150/113658512515——815 (0.3sec)

210 28037014019125.8 33.5

—'——õõ—õ !3

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

BAdjustable300 500350 600400690

6512515045/34 @575/57 @5125/70125/70125/70150/113658512515——815 (0.3sec)

210 28037014019125.8 33.5

—'——õõ—õ !3

¡¡¡

——

¡¡

¡ (AX)¡ (AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡——¡¡—¡

A250 400 (175)300 (125) (200)350 (150) (225)!4690

7512012045/23 @575/38 @5120/60120/60120/60120/6075120120—40408—

160 2122601331678.5 10

'õ (BAR)õ—õõ ——õ !3

———

—¡

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡——¡——¡ —¡ (TYD)—¡

A125 200150 225175

690

6012012025/13 @560/30 @5120/60120/60120/60120/606075120—40408—

1402601331676.0

'õ (BAR)õ—õõ——

———

¡—

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡——¡———¡ (TYD)—¡

A15 40 7520 50 10030 60

690

4212012025/13 @560/30 @5120/60120/60120/60120/604275120—40408—

105 1401651251433.2 3.8

'—õõ—õ ———

———

¡—

¡¡

¡ (AX)¡ (AL)¡¡¡¡¡¡—¡—¡¡———¡ (TYD)—¡

z Moulded Case Circuit Breakers

Current-limiting Breakers, TL Series (120kA)2

d e

b

ca

Page 20: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

19

800TL-8003

600TL-6003

400TL-4003

100TL-100C3

225TL-225B3

Frame Size [A]TypeNumber of PolesOutside view

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.

!5 : Specify rated frequency, 50 or 60Hz.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@5 : The application on IT systems on this voltage is not available.

Utilization Category° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.]° DIMENSIONS (mm)

abcd/e

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

A15 40 7520 50 10030 60

690

8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—

110230133162/—4.7

'—õõ—õ——

———

¡—

——

¡ (AX)¡ (AL)¡¡¡¡—¡—¡——¡———¡ (TYD)——

A700800 !4

!5690

8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—

240400133199/6327

—'õ—õõ——

———

—¡

——

¡ (AX)¡ (AL)¡¡¡¡—¡¡¡——¡———¡ (TYD)——

A450500600

690

8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—

240400133199/6327

—'õ—õõ——

———

—¡

——

¡ (AX)¡ (AL)¡¡¡¡—¡¡¡——¡———¡ (TYD)——

A125 200 300150 225 350175 250 400

690

8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—

210300133202/5617.7

'õ (BAR)õ—õõ——

———

—¡

——

¡ (AX)¡ (AL)¡¡¡¡—¡¡¡——¡———¡ (TYD)——

A125 200150 225175

690

8518018050/38 @585/64 @5180/135180/135180/135180/13585180180—40408—

140260133183/469.3

'õ (BAR)õ—õõ——

———

¡—

——

¡ (AX)¡ (AL)¡¡¡¡—¡—¡——¡———¡ (TYD)——

z Moulded Case Circuit Breakers

Current-limiting Breakers, TL Series (180kA)2

d e

b

ca

Page 21: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

20

3200TT-32003

4000TO-40003

3200TO-32003

Frame Size [A]TypeNumber of PolesOutside view

NOTES: ' : Standard. This configuration is used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : DC rating available on request.

!3 : Special specificacion.!5 : Specify rated frequency, 50 or 60Hz.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.

A4000

!5690

658513045/3465/4985/6485/64100/75130/986585130—40408—

390560235315120

————'———

———

—¡

——

¡ (AX)¡ (AL)¡¡¡———¡———————¡(TYD)—¡

B250028003200

!5690

658513045/4265/4985/6485/64100/75130/98658513042——842 (0.3sec)

390560235315120

————'——õ

———

¡(with Adi. STD)—

——

¡ (AX)¡ (AL)¡¡¡———¡—¡ !6—————¡(TYD)—¡

A250028003200

!5690

658513045/3465/4985/6485/64100/75130/986585130—40408—

390560235315120

————'——õ

———

—¡

——

¡ (AX)¡ (AL)¡¡¡———¡—¡ !6—————¡(TYD)—¡

Utilization Category° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 550V

460V220V

IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated impulse withstand voltage (Uimp) [kV]Rated short time current (lcw) [kA. rms.]° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INST.Adjustable GFT or Adjustable PTA (option)Trip Indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic trips

° STANDARD FEATURESon • off colour indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.F

z Moulded Case Circuit Breakers

TO/TT Series2

d

b

ca

Page 22: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

21

Frame Size [A]TypeNumber of PolesOutside viewNRC=Nominal Rated CurrentASR=Adjustable Setting Range

NOTES: ' : Standard. This configuration is used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.

o : For AC UVT, a UVT controller is mounted externally.!0 : One is supplied with every five breakers. Please Specify if more are required.!2 : Line side interpole barriers are supplied as standard.!6 : Available on request, contact TERASAKI for details.@2 : Draw out leads horizontally.@3 : Draw out leads vertically.@4 : Values at 1000V AC.

15 5020 6030 7540 1001100

6.510

1051651251433.2

'——õ—õ——

—¡

———

¡———

¡(AX)¡(AL)¡¡¡¡¡¡—¡—¡¡——¡ !2¡ (TYD)—¡—

NRC ASRmin. max.

250 125 250400 200 4001100

12.5—

1402601031314.8

'õ (BAR)——õõ——

¡¡

¡¡(PTA only)—

————

¡(AX)¡(AL)¡¡ o¡¡¡¡—¡¡¡¡¡¡¡¡—¡¡

NRC ASRmin. max.

630 315 630

1100

12.518 @4

2102731031459.6

—'——õõ——

¡¡

¡¡—

————

¡(AX)¡(AL)¡¡ o¡¡¡¡¡¡¡¡¡¡¡¡¡—¡¡

NRC ASRmin. max.

800 400 800

1100

12.518 @4

2102731031459.7

—'——õõ——

¡¡

¡¡—

————

¡(AX)¡(AL)¡¡ o¡¡¡¡¡¡¡¡¡¡¡¡¡—¡¡

NRC ASRmin. max.

1000 500 10001250 630 12501100

20—

21037012017122.0

—'——õõ——

¡¡

¡¡¡

————

¡(AX)¡(AL)¡¡ o¡¡¡¡¡ !0¡¡¡¡¡¡¡¡—¡¡

° RATED CURRENT (IN) [A]Calibrated at 40°C

Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]cos ø=0.3 1100V

900V° DIMENSIONS (mm)

abcd

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° STANDARD FEATURESon • off colour indicationTrip button° PROTECTIVE FUNCTIONSElectronic type

Adjustable LTD, STD & INSTAdjustable GFT or Adjustable PTA (option)Trip indicators (option)

Thermal-magnetic typeThermal and fixed magnetic tripsThermal and adjustable magnetic tripsAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips

° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2 LTF

@3 LTSDoor flange D.FIP20 protection (plug-in type) IP20

TemBreakz Moulded Case Circuit Breakers

Mining Series2

d

b

ca

100TL-100EM3

400XV400NE3

630XV630PE3

800XV800PE3

1250XV1250NE3

Page 23: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

22

TemBreakz Moulded Case Circuit Breakers

Non-automatic Trip Breakers2Frame size (A)TypeNumber of polesOutside view

°°°°° RATINGRated current (In) [A] at 45°CRated insulation voltage (Ui) [V AC]Rated operational voltage [V] AC 50/60Hz

DCRated short circuit making capacity [kA peak]Rated short time current (Icw) [kA rms]°°°°° DIMENSIONS (mm)

abcd

Outline dimensions same as forWeight (kg) ' marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

For distribution boardDraw-out (DO)°°°°° STANDARD FEATURESon • off colour indicationTrip button°°°°° ACCESSORIES (option) CODEInternally Auxiliary switch AX,AXEmounted Alarm switch AL,ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear connect/ plug-in type TCRInterpole barrier TBAAccessory lead terminal LTF

LTSDoor flange D.F

Max. Switching Current [A] ACDC

Endurance with current(No. of operating cycles) without current

e : Comes with conductor pressing terminal.o : The UVT controller is installed externally, when provided with AC UVT.

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.

d

b

ca

100XS100NNB2 3 4

1006906902502.51.8 (1sec)

60 90 1201556886XS100NB0.78 1.1 1.4

'—õõ—õõ ——

¡¡

¡(AXE)¡(ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡60025060004000

30XS30NNB2 3

306606602502.51.8 (1sec)

50 751306887XS30NB0.48 0.74

' e—õõ—— õ— õ—

¡¡

¡(AXE)¡(ALE)¡——¡— ¡— ¡—— ¡—¡¡¡¡¡—¡¡1807560004000

50XS50NNB2 3

506606602502.51.8 (1sec)

50 751306887XS50NB0.48 0.74

' e—õõ—õõ—

¡¡

¡(AXE)¡(ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡30012560004000

100XE100NN2 3

1006606602502.51.8 (1sec)

50 751306887XE100NS0.48 0.74

'—õõ—õõ—

¡¡

¡(AXE)¡(ALE)¡¡— ¡¡— ¡— ¡—— ¡— ¡¡¡¡¡¡—¡¡60025060004000

225XE225NNC3

2256906902505.53 (1sec)

1051606083XE225NC1.4

'õ (BAR)õ—õ———

¡¡

¡(AXE)¡(ALE)¡—¡¡¡¡—¡¡¡¡¡¡¡—¡¡135056040004000

225XS225NN3 4

22569069025064 (1sec)

105 14016586107XS225NS1.85 2.4

'õ (BAR)õ—õõ——

¡¡

¡(AXE)¡(ALE)¡¡¡¡¡¡—¡¡¡¡¡¡¡—¡¡135056040004000

400XS400NN3 4

40069069025095 (1sec)

140 185260103131XS400NS4.7 6.1

'õ (BAR)õ—õõ—õ

¡¡

¡(AX)¡(AL)¡¡¡¡¡¡—¡¡¡¡¡¡¡¡—¡2400100010005000

Page 24: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

23

TemBreakz Moulded Case Circuit Breakers

Non-automatic Trip Breakers2Frame size (A)TypeNumber of polesOutside view

°°°°° RATINGRated current (In) [A] at 45°CRated insulation voltage (Ui) [V AC]Rated operational voltage [V] AC 50/60Hz

DCRated short circuit making capacity [kA peak]Rated short time current (Icw) [kA rms] 1sec°°°°° DIMENSIONS (mm)

abcd

Outline dimensions same as forWeight (kg) ' marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

For distribution boardDraw-out (DO)°°°°° STANDARD FEATURESon • off colour indicationTrip button°°°°° ACCESSORIES (option) CODEInternally Auxiliary switch AX,AXEmounted Alarm switch AL,ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear connect/ plug-in type TCRInterpole barrier TBAAccessory lead terminal LTF

LTSDoor flange D.F

Max. Switching Current [A] ACDC

Endurance with current(No. of operating cycles) without current

d

b

ca

600XS600NN3 4

600690690250159.6 (0.3sec)

210 280273103145XS600NS9.0 11.5

—'õ—õõ—õ

¡¡

¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡3600150010005000

800XS800NN3 4

800690690250159.6 (0.3sec)

210 280273103145XS800NS9.4 12.2

—'õ—õõ—õ

¡¡

¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡—¡480020005003500

1000XS1000NN3 4

10006906902503215 (0.3sec)

210 280370120171XS1000NE20.4 26.4

—'õ—õõ—õ

¡¡

¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡—¡¡—¡600025005002500

1200XS1200NN3 4

12006906902503215 (0.3sec)

210 280370120171XS1200NE20.4 26.4

—'õ—õõ—õ

¡¡

¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡¡—¡¡—¡720030005002000

1600XS1600NN3 4

16006906902504520 (0.3sec)

210 280370140191XS1600NE24.9 32.9

—õ——'——õ

¡¡

¡(AX)¡(AL)¡¡¡¡¡¡¡¡¡¡¡——¡¡—¡960040005002000

2000XS2000NN3 4

20006906902509035 (0.3sec)

320 429450185245XS2000NE51.8 64.8

—õ——'——õ

¡¡

¡(AX)¡(AL)¡¡¡¡——¡ !2¡¡¡¡———¡—¡1200050005002000

2500XS2500NN3 4

25006906902509035 (0.3sec)

320 429450185245XS2500NE60 75.7

————'———

¡¡

¡(AX)¡(AL)¡¡¡¡——¡ !2¡¡¡¡———¡—¡1500062505002000

o : The UVT controller is installed externally, when provided with AC UVT.!2 : Handle is supplied as standard.

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.

These are the switches without automatic trip units, and the switching capacity is 6 times the rated current.

Remote tripping is possible when equipped with shunt trip or undervoltage trip.

Auxiliary switch or alarm switch can also be fitted. For the details on the specifications please contact

TERASAKI.

Page 25: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

24

15/30}620/45}935/75}1550/100}20100/200}40250500

6 12.852.5 23.355 170

110230133162—4.7

'—õõ—õ——

¡

¡(AX)¡(AL)¡¡¡¡—¡—¡—¡—¡ (TYD)——

100TL-100SC3

225TL-225SB3

400TL-400S3

600TL-600S3

800TL-800S3

900TL-1000S3

125/300}30200/400}40225/600}60225/750}75

250500

6 12.852.5 23.370 450

140260133183469.3

'õõ—õõ——

¡

¡(AX)¡(AL)¡¡¡¡—¡—¡—¡—¡ (TYD)——

250/500}50300/600}60400/800}80400/1100}110400/1500}150250500

6 12.852.5 23.3140 430

2103001332025617.7

'õõ—õõ——

¡

¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——

600/1100}110600/1500}150600/1900}190600/2300}230

250500

6 12.852.5 23.3140 330

2404001331996327

—'õ—õõ——

¡

¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——

800/1100}110800/1500}150800/1900}190800/2300}230

250500

6 12.852.5 23.3220 400

2404001331996327

—'õ—õõ——

¡

¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——

900/1900}190900/2300}230

250500

6 12.852.5 23.3220 400

2404001331996327

—'——————

¡

¡(AX)¡(AL)¡¡¡¡—¡¡¡—¡—¡ (TYD)——

° RATINGSRated current [A] at 40°C / magnetic trip current [A]

DC rated voltage [V] 2 poles in series3 poles in series

Examples of I2t let-through at faultinterruption (500V DC)Prospective SC fault [kA]Time-constant [ms]I2t×103 A2 • s° DIMENSIONS (mm)

abcde

Weight (kg) ' marked standard type° CONNECTIONS AND MOUNTINGSFront connect (FC) Terminal screw

Attached flat barSolderless terminal (PWC)

Rear connect (RC) Bolt studFlat bar stud

Plug-in (PM) For switchboardFor distribution board

Draw-out (DO)° PROTECTIVE FUNCTIONSFixed magnetic trip (INST trip only)° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip UVT

Externally Motor operator MOTmounted External operating handle OHE

OHJOHH

Extension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle lock HLInterpole barrier TBAAccessory lead terminal @2 LTF

@3 LTSDoor flange D.F

Frame Size [A]TypeNumber of polesOutside view

NOTES: ' : Standard, this configuration used unless otherwise specified.õ : Optional standard, specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.

@2 : Draw out leads horizontally.@3 : Draw out leads vertically.

d e

b

ca

z Moulded Case Circuit Breakers

Thyristor Protection Breakers2

Page 26: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

25

10 30 (6) (32)15 40 (16) (63)20 50 (25)q460

— 2.5 2.5 2.52.5 2.5 — —2.5 5 w 5 w 5 w— 5 5 —5 5 — —— 6(3) 6(3) 6(3)6(3) — — —— 6(3) 6(3) 6(3)6(3) — — —— 6(5) 6(5) —r 10(5) 10(5) —10(5) 10(5) 10(5) —1 5 — —

25 50 75 100956077 79160 340 500 660

'

'¡——

¡

¡¡¡ —¡ —¡¡ — ¡ —— ¡

10 30 (25)15 40 (32)20 50 (63)q460

— 2.5 —2.5 2.5 —2.5 5 w —— 5 —5 5 —— — 6(3)— — —— 6(3) 6(3)6(3) — 6(5)— 6(5) 10(5)r 10(5) 10(5)10(5) 10(5) 10(5)— 5 —

25 50 7574.56077 79130 280 410

'

——¡ —¡ —

¡

—¡¡ —¡ ———— ¡

10 3015 4020 50

250

—————————5555

5074.56079280

'

——¡¡

¡

—¡————¡

60 (80)75100q460

— 5 5 55 5 — —5 5 5 55 5 5 —5 5 — —— 6 6 66 — — —— 6 6 66 — — —— 10 10 1010 10 10 —10 10 10 —1 5 — —

25 50 75 100956077 80210 420 630 840

'

'¡——

¡

¡¡¡ —¡ —¡¡— ¡

60 (80)75100q460

—————— 6 66 — —— 6 66 — —— 10 1010 10 1010 10 101 5 —

25 50 7577.56077 80210 420 490

'

————

¡

—¡¡¡ ———— ¡

50TB-5S1 2 3 4

50TB-5P1 2 3

50TB-5D2

100TB-10S1 2 3 4

100TB-10P1 2 3

° RATED CURRENT (In) [A]at 40°C (45°C for marine applications)

Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]JIS C 8370 460V

265V220V110/220V110V

BS 3871 part1 e 440V254/440V380V,415V220/380V,240/415V220V,240V120/240V120V

° DC RATED BREAKING CAPACITY [kA] 125V° DIMENSIONS (mm)

abcd

Weight (g)° CONNECTIONSFront-connect (FC)Plug-in (line end)Front-connect (load end)Plug-in° MOUNTINGS (optional)ClipClip-in chassisDouble mounting baseSingle mounting base° PROTECTIVE FUNCTIONSThermal and fixed magnetic trips° ACCESSORIES (option) CODEShunt trip SHTHandle holder HHHandle lock HLHandle capFlash plateProtection coverInterpole barrier TBA

Frame Size [A]TypeNumber of polesOutside view

Accessories for TB series

NOTES: ' : Standard.¡ : “yes” or “available”.— : “no” or “not available”.

q : Rated current shown in ( ) available on request. (except JIS and marine standard).w : 2.5kA for 10A rating.e : Rated breaking capacities shown in ( ) are applied to 6A and 10A ratings.r : Apply its breaking capacity at 120V. AC if necessary.

shunt trip protective cover handle holder handle lock(for single poletype use only)

handle cap flash plate

type: TKB-50SGH (red) type: TKB-50SG (red)

type: TAA-5CR (red)TAA-5CY (yellow)TAA-5CG (green)

d

b

ca

Miniature Circuit Breakers

TB Series for Distribution Board Use2

Page 27: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

26

TemBreakz Moulded Case Circuit Breakers

Adjustable Thermal Trip2° RATED CURRENT (In) [A]at 45°C

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V400V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category°°°°° DIMENSIONS (mm)

abcd

Weight (kg) ' Marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

For distribution boardDraw-out (DO)°°°°° PROTECTIVE FUNCTIONSAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips°°°°° STANDARD FEATURESon • off color indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.FIP20 protection Plug-in type IP20

125 125 160 250 250 400 400 630XS125CJ XS125NJ XS160NJ XS250NJ XS250PJ XS400CJ XS400NJ XS630CJ*3 4 *3 4 *3 4 *3 4 *3 4 *3 4 *3 4 *3 4

d

b

ca

Frame Size [A]TypeNumber of PolesOutside viewNOTE: *2 pole breaker is 3 pole breaker with centre pole

omitted.

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : D C rating available on request.o : The UVT controller is installed externally when provided with AC UVT.@2 : Draw out leads horizontally@3 : Draw out leads vertically@5 : The application on IT systems on this voltage is not available.

Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj.range Rated Adj.range Rated Adj.range Rated Adj.range Rated Adj.rangeCurr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. 20 12.5 20 20 12.5 20 160 100 160 160 100 160 160 100 160 250 160 250 250 160 250 400 250 400 32 20 32 32 20 32 250 160 250 250 160 250 400 250 400 400 250 400 630 400 630 50 32 50 50 32 50 63 40 63 63 40 63100 63 100 100 63 100125 80 125 125 80 1258 8 8 8 8 8 8 8690 690 690 690 690 690 690 690

— 5/2.5 @5 8/4 @5 8/4 @5 8/4 @5 16/8 @5 18/9 @5 16/8 @57.5/3.8 @5 12/6 @5 22/11 @5 22/11 @5 22/11 @5 22/11 @5 30/15 @5 25/13 @510/5 22/11 25/13 25/13 25/13 30/15 42/21 30/1514/7 25/13 25/13 25/13 35/18 35/18 50/25 35/1818/9 30/15 35/18 35/18 35/18 35/18 50/25 45/2318/9 30/15 35/18 35/18 35/18 35/18 50/25 45/2325/13 50/25 50/25 50/25 50/25 50/25 85/43 50/25— 12 22 22 22 22 30 2510 22 25 25 25 30 42 3525 50 50 50 50 50 85 50— — — — — — — —10 15 40 40 40 40 40 4015 20 40 40 40 40 40 40— — — — — — — —A A A A A A A A

90 120 90 120 105 140 105 140 105 140 140 185 140 185 210 280155 155 165 165 165 260 260 27386 86 86 86 103 103 103 103104 104 107 107 124 131 131 1451.3 1.58 1.3 1.58 1.85 2.4 1.85 2.4 2.1 2.6 4.7 6.1 4.7 6.1 9.0 11.5

' ' ' ' ' ' ' —— — õ (BAR) õ (BAR) õ (BAR) õ (BAR) õ (BAR) 'õ õ õ õ õ õ õ õõ õ — — — — — —– – õ õ õ õ õ õõ õ õ õ õ õ õ õõ — õ — — — — — — —— — — — õ õ õ õ

¡ ¡ ¡ ¡ ¡ — — —— — — — — ¡ ¡ ¡

¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡

¡(AXE) ¡(AXE) ¡(AXE) ¡(AXE) ¡(AXE) ¡(AX) ¡(AX) ¡(AX)¡(ALE) ¡(ALE) ¡(ALE) ¡(ALE) ¡(ALE) ¡(AL) ¡(AL) ¡(AL)¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡— — — — — — — ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡— — — — — ¡ ¡ ¡¡ ¡ ¡ ¡ ¡ — — —¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡õ õ õ õ õ õ õ õ

Page 28: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

27

TemBreakz Moulded Case Circuit Breakers

Adjustable Thermal Trip2630 800 125 160 250XS630NJ XS800NJ XH125NJ XH160NJ XH250NJ*3 4 *3 4 *3 4 *3 4 *3 4

Frame Size [A]TypeNumber of PolesOutside viewNOTE: *2 pole breaker is 3 pole breaker with centre pole

omitted.

° RATED CURRENT (In) [A]at 45°C

Rated impulse withstand voltage (Uimp) [kV]Rated insulation voltage (Ui) [VAC]° AC RATED BREAKING CAPACITY [kA sym. rms.]IEC 60947-2 Icu/Ics 690VBS EN 60947-2 500V

440V415V400V380V240V

NEMA AB-1 600V480V240V

Without Inst. 240-690V° DC RATED BREAKING CAPACITY [kA] q 250V

125VRated short time current (lcw) [kA. rms.]Utilization Category°°°°° DIMENSIONS (mm)

abcd

Weight (kg) ' Marked standard type°°°°° CONNECTIONS AND MOUNTINGSFront Terminal screwconnect (FC) Attached flat bar

Solderless terminal (PWC)Rear Bolt studconnect (RC) Flat bar studPlug-in (PM) For switchboard

For distribution boardDraw-out (DO)°°°°° PROTECTIVE FUNCTIONSAdjustable thermal and fixed magnetic tripsAdjustable thermal and magnetic trips°°°°° STANDARD FEATURESon • off color indicationTrip button° ACCESSORIES (option) CODEInternally Auxiliary switch AX, AXEmounted Alarm switch AL, ALE

Shunt trip SHTUndervoltage trip o UVT

Externally Motor operator MOTmounted External Panel mount. type OHE

operating Breaker mount. type OHJhandle Variable depth type OHHExtension handle EHAMechanical Front type MIFinterlock Rear type MIBHandle holder HHHandle lock HLTerminal Front connect type TCFcover Rear / plug-in type TCRInterpole barrier TBAAccessory lead terminal @2LTF

@3LTSDoor flange D.FIP20 protection Plug-in type IP20

d

b

ca

Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj. range Rated Adj. rangeCurr. min. max. Curr. min. max. Curr. min. max. Curr. min. max. Curr. min. max.400 250 400 800 500 800 20 12.5 20 160 100 160 160 100 160630 400 630 32 20 32 250 160 250

50 32 50 63 40 63100 63 100125 80 125

8 8 8 8 8690 690 690 690 690

20/10 @5 20/10 @5 8/4 @5 15/7.5 @5 15/7.5 @535/18 @5 35/18 @5 25/13 @5 25/13 @5 25/13 @550/25 50/25 42/21 42/21 42/2150/25 50/25 50/25 50/25 50/2565/33 65/33 50/25 50/25 50/2565/33 65/33 50/25 50/25 50/2585/43 85/43 85/43 85/43 85/4330 30 25 25 2550 50 42 42 4285 85 85 85 85— — — — —40 40 40 40 4040 40 40 40 40— — — — —A A A A A

210 280 210 280 90 120 105 140 105 140273 273 155 165 165103 103 86 103 103145 145 104 124 1249.0 11.5 9.4 12.2 1.3 1.58 2.1 2.6 2.1 2.6

— — ' ' '' ' — õ (BAR) õ (BAR)õ õ õ õ õ— — õ — —õ õ — õ õõ õ õ õ õ— — õ — — —õ õ — õ õ

— — ¡ ¡ ¡¡ ¡ — — —

¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡

¡(AX) ¡(AX) ¡(AXE) ¡(AXE) ¡(AXE)¡(AL) ¡(AL) ¡(ALE) ¡(ALE) ¡(ALE)¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ — — —¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ ¡ ¡ ¡¡ ¡ — — —— — ¡ ¡ ¡¡ ¡ ¡ ¡ ¡õ õ õ õ õ

NOTES: ' : Standard. This configuration used unless otherwise specified.õ : Optional standard. Specify when ordering.¡ : “yes” or “available”.— : “no” or “not available”.q : D C rating available on request.o : The UVT controller is installed externally when provided with AC UVT.@2 : Draw out leads horizontally@3 : Draw out leads vertically@5 : The application on IT systems on this voltage is not available.

Page 29: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

28

Approvals and Applicable Breaking Capacities to Marine Standards.

Breaker Rated Poles Rated

type current[A] voltage[V]

XS30NB 3,5,10,15,20,30 2,3 500250125

XE50NB 3,5,10,15,20,30,40,50 2,3 500250125

XS50CB 10,15,20,30,40,50 2,3 500250125

XS50NB 10,15,20,30,40,50 2,3 500250125

XH50NS 15,20,30,40,50 3 500FOR JAPANESE MARKET 250

XS60NS 60 2,3 500FOR JAPANESE MARKET 250

125

XE100NS 10,15,20,30,40, 2,3 50050,60,75,100 250

125

XS100NB 15,20,30,40,50, 2,3 50060,75,100 250

XH100NS 15,20,30,40,50, 3 50060,75,100 250

XE225NS!7 125,150,175,200,225 3 500FOR JAPANESE MARKET 250

XS225NS 125,150,175,200, 3 500225 250

XH225NS 125,150,175,200, 3 500225 250

XH225NE 125~225 3 500125,150,175,200, 250225 500

FOR JAPANESE MARKET 250

XS400CS 125,150,175,200,225 3 500250,300,350,400 250

XS400NS 125,150,175,200,225 3 500250,300,350,400 250

XS400NE 125~225,200~400 3 500125,150,175,200, 250225,250,300,350, 500400 250

XS600CS 300,400,500,600 3 500250

XS600NS 300,400,500,600 3 500250

XS600NE 300~600 3 500300,350,400,500, 250600 500

250

XS800CS 700,800 3 500250

XS800NS 700,800 3 500250

XS800NE 400~800 3 500400,450,500,600, 250700,800 500

250

AC Rated breaking capacity [kA sym. rms.]/Rated making capacity [kA peak]

NK LR AB GL BV2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.642/96.785/19810/18.525/53.242/95.610/18.525/53.242/95.622/50.150/11542/96.785/19815/31.325/53.225/56.250/11542/96.785/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w

5 5 5

5 5 5

7.5 7.5 7.5

7.5 7.5 7.5 7.5 7.515

40 40.6 40 40

7.5 7.85 7.5 7.515

7.5 7.85 7.5 7.515

15 15 15 15 15

40 40.6 40 40

10 10.1 10 10

40 40.6 40 40

40 40.6 40 40

40

DC Ratedbreaking capacity [kA]

NK LR AB GL BV2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.643.7/96.888.8/20410.25/18.125.6/53.243.3/96.910/17.2!1

25/60.5!2

42/97.9!4

22/50.150/11543.7/96.888.8/20415.4/31.425.6/53.226.0/56.651.0/11643.7/96.888.8/20451.9/121q88.8/204q5.09/9.4w5.09/9.4w33.1/72.651.0/11653.5/12588.8/20451.9/121q88.8/204q5.09/9.4w5.09/9.4w33.1/72.651.0/11653.5/12588.8/20453.5/125q88.8/204q10.2/19.3w10.2/19.3w33.1/72.651.0/11653.5/12588.8/20453.5/125q88.8/204q10.2/19.3w10.2/19.3w

2.5/3.85/8.77.5/13.72.5/3.85/8.77.5/13.77.5/14.410/19.342/95.610/18.525/53.242/95.642/96.785/19810/18.525/53.242/95.610/18.525/53.242/95.622/50.150/11542/96.785/19815/31.325/53.225/56.250/11542/96.785/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/121q85/198q5/8.8w5/8.8w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w30/70.750/11550/11685/19850/116q85/198q10/19.3w10/19.3w

10/18.5!1

25/52.5!2

42/95.6!9

42/88.2!1

85/187!2

10/18.5!1

25/52.5!2

42/95.6!9

10/18.5!1

25/52.5!2

42/95.6!9

25/52.5!1

50/105!2

42/88.2!1

85/187!2

15/30!1

25/52.5!2

25/52.5!1

50/105!2

42/88.2!1

85/187!2

42/88.2!1q

85/187!2q

30/63!1

50/105!2

42/88.2!1

85/187!2

42/88.2!1q

85/187!2q

30/63!1

50/105!2

50/105!1

85/187!2

50/105!1q

85/187!2q

30/63!1

50/105!2

50/105!1

85/187!2

50/105!1q

85/187!2q

10/17!1

25/52.5!2

42/88.2!9

10/17e25/52.5!3

25/52.5!1

50/105!2

42/88.2!1

85/187!2

25/52.5!1

50/105!2

42/88.2!1

85/187!2

42/88.2!1

85/187!2

50/105!1

85/187!2

NOTES: q : with INSTw : without INSTe : at 450V AC!1 : The value is Icu at 450V AC. Contact Terasaki for Ics value.!2 : The value is Icu at 240V AC. Contact Terasaki for Ics value.!3 : at 240V AC!4 : at 120V AC!5 : Being or will be applied!7 : Plug-in type only. For the mounting and the other details refer to XS225NS.!9 : The value is Icu at 120V AC. Contact Terasaki for Ics value.

TemBreakz Moulded Case Circuit Breakers

Marine Approval2

Page 30: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

29

NOTES: q : with INSTw : without INSTe : at 450V ACr : at 220V ACt : 50/116kA at 660V ACy : 50/115kA at 690V ACu : 2.5/4.1kA for 10A ratingi : at 110V AC

o : at 225V AC!0 : at 250V DC!1 : The value is Icu at 450V AC. Contact Terasaki for Ics value.!3 : at 240V AC!5 : Being or will be applied!6 : The value is Icu!8 : Contact Terasaki for Ics value.!9 : 2.5/3.57kA for 10A rating.

Approvals and Applicable Breaking Capacities to Marine Standards.

Breaker Rated Poles Rated

type current[A] voltage[V]

XH800PS 700,800 3 460

XS1200NE 200~400,400~800, 3 500600~1200 250200,225,250,300,350,400,450 500500,600,700,800,1000,1200 250

XS1600NE 800~1600 3 500800,900,1000, 5001200,1400,1600

XS2000NE 1200~2000 3 5001200,1400,1600 5001800,2000

XM30NB 0.7,1.4,2,2.6,4,5, 3 5008,10,12,16,25,32 250

XM50CB 0.7,1.4,2,2.6,4,5,8,10, 3 50012,16,25,32,40,45 250

TB-5D 10,15,20,30,40 2 25050 125

TB-5S 10,15,20,30,40 2 25050 125

TB-5P 10,15,20,30,40 2 25050 125

TL-100F 15,20,30,40,50 3 46060,75,100

TL-225F 125,150,175,200, 3 460225

TL-400E 250,300,350,400 3 460

TL-600NE 300~600 3 690300,350,400, 460500,600 240

TL-800NE 400~800 3 690400,450,500, 460600,700,800 240

TL-1000NE 500~1000 3 690500,600,700, 460800,900,1000 240

TL-1200NE 600~1200 3 690600,700,800, 4601000,1200 240

TL-100C 15,20,30,40,50, 3 50060,75,100

TL-225B 125,150,175,200, 3 500225 250

TL-400 125,150,175,200,225, 3 500250,300,350,400 250

TL-600 450,500,600 3 500250

TL-800 700,800 3 500250

AC Rated breaking capacity [kA sym. rms.]/Rated making capacity [kA peak]

NK LR AB GL BV85/19350/117q85/198q15/31.3w15/31.3w85/196q20/46w

85/195q42/99w

2.5/3.85/8.72.5/3.85/8.75/8.0u42/99.35/8.0u42/99.35/8.0u42/99.3120/280

120/280

120/280—125/295——125/295——125/295——125/295—180/396

180/396

180/396

180/396

180/396

5 5 5

5 5

5 5 5

40 40

40 40

40 40

40 40

DC Ratedbreaking capacity [kA]

NK LR AB GL BV85/19353.5/125q88.8/204q15.4/31.4w15.4/31.4w87.1/194.9q21.5/51.5w

87.1/194.9q43.0/102.9w

2.5/3.85/8.72.5/3.85/8.75/8.0u43.5/101.65/8.0u43.5/101.65/8.0u43.5/101.6120/280

120/280

120/280—125/295——125/295—45/93.8!8

125/295!1

150/345!8

45/93.8!8

125/295!1

150/345!8

180/419y!1

180/419y!1

180/419y!1

180/419y!1

180/419y!1

85/19350/117q85/198q15/31.3w15/31.3w85/196q20/46w

85/195q42/99w

2.5/3.85/8.72.5/3.85/8.75/8.0u42/99.3

5/8.0u42/99.3120/280

120/280

120/280—125/295——125/295——125/295——125/295—180/396

180/396

180/396

180/396

180/396

85/187!1

65/143q!1

100/220q!2

85/187q!1

85/187q!1

5/7.98r!9

42/102i5/7.98r!9

42/102i5/7.98r!9

42/102i120/288!1

120/288!1

120/288!1

45/92!8

125/298!1

150/347!8

45/92!8

125/298!1

150/347!8

45/92!8

125/298!1

150/347!8

45/92!8

125/298!1

150/347!8

180/419!1

180/419!1

180/419!1

180/419!1

180/419!1

65/143q!1

5/8.0uo

7.5/13.7i

5/8.0uo

7.5/13.7i120/280!6

120/280!6

120/280!8

45/94.5!8

125/275!1

150/330!8

45/94.5!8

125/275!1

150/330!8

45/94.5!8

125/275!1

150/330!8

45/94.5!8

125/275!1

150/330!8

180/415!8

180/415!8

180/415!8

180/415!8

180/415!8

Page 31: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

30

ø1002.0

1185A850mm2

45mm1185A850mm2

45mm992A600mm2

38mm

TZS-100

ø681.1

650A325mm2

29mm650A325mm2

29mm556A250mm2

26mm

TZS-68

ø400.7

298A100mm2

17mm298A100mm2

17mm257A80mm2

15.5mm

TZS-40

ø240.3

139A30mm2

10.5mm139A30mm2

10.5mm115A22mm2

9.5mm

TZS-24

ø150.2

61A8mm2

6mm61A8mm2

6mm49A5.5mm2

5mm

TZS-15

120 qw24096-132192-26430100300 e5001000below 0.040.30.5 er1260/78/1000.22

t1C yLED (Red)electrical u1VA

TZS-AD¡¡

TypePhase and 3ø3W, 1ø2Wwires 3ø4WOutside view

° RATINGSRated control voltage [V AC]

50/60HzApplicable range 120V AC

240V ACRated sensitivity current [mA]

Rated operating time (sec)

Dimensions [mm] (surface mount) W/H/DWeight [kg] (surface mount)° MOUNTINGSurface mountFlush mount° STANDARD FEATURESEarth leakage detectionOutput contactEarth leakage indicationReset functionPower source required

Ratings of Relays

TypeOutside view

Diameter of transit part [mm]Weighr [kg]Applicable numbers, size and continuous currentof wires (IV cable wires)2 max. continuous currentwires max. wire size

max.diameter of wire3 max. continuous currentwires max. wire size

max.diameter of wire4 max. continuous currentwires max. wire size

max.diameter of wire

Ratings of ZCT (Core Balanced Current Transformers)

NOTE ' : Standard, this configuration is used unless otherwise specified.¡ : “yes” or “available”.q : Terminals for 120V AC and 240V AC are provided.

CAUTION : DO NOT APPLY 240V AC TO THE 12OV AC TERMINAL.,BURNOUT CAN RESULT.

w : For 415V AC or 440V AC, Please contact to TERASAKI.e : Adjustable type by Dip slide swnch.r : Operating time range and Non-operating time range.

t : Solied-state type, current operating type.y : Ratings of output contact.

u : The output contacts remain until the RESET button is operated.Provided the control power supply fails the contacts automatically reset.

gnitarepodetaR)ces(emit

)ces(egnaremitgnitarepOgnitarepo-noN

)ces(egnaremit

3.0 63.0~2.0 51.0

5.0 6.0~4.0 83.0

1 2.1~8.0 7.0

2 2~3.1 52.1

daolecnatsiseR1=øsoc

daolevitcudnI)sm7=R/L(4.0=øsoc

daol.niM

CAV021 A6 A5.3

CDV5taAm01CAV042 A6 A5.3

CDV03 A6 A3

xEarth-leakage Relays

TZS Series2

Page 32: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

31

TemMeasurePower Monitoring Equipment3

To protect the world's ecology, Terasaki addresses ourselves to energy saving and minimization of environmental pollution.TemMeasure allows power consumption to be monitored for each branch circuit, assisting you in saving energy. Features ofTemMeasure include the following:

¡Current, voltage, instantaneous power, integrated power, and power factor of low-voltage power distribution systems can bemeasured and displayed.

¡Easy-to-use membrane switches and a clear 6-digit LED display, with a wide viewing angle.¡Applicable both to 3-phase and single-phase circuits.¡A cable extension permits separation between the display unit and the sensor unit and therefore installation of the display unit

anywhere.¡Field fittable to the load side of the existing TemBreak range, MCCB 400AF, 600AF, 800AF.¡RS-485 serial transmission or pulse output of measured values is available.

NOTES: ¡ : “yes” or “available”.q : Do not perform a dielectric strength test between poles. Doing so may cause damage to the internal VT or CT.w : When the breaker is OFF or tripped, control power is lost, resulting in the measuring, display and transmission functions being disabled. Stored data including

setting data and integrated power, however, are preserved.e : Not available for Display separate type.r : When control power is lost, integrated power is not measured and not integrated.t : A lead terminal block is fitted. An external transformer with a capacity of 30 VA or more is needed, because of inrush current occurring at control power ON.y : When the ambient temperature is 25°Cu : The device reads 0 for less than 2%.i : Integrated time error: 0.01% ±1 sec.o : If current is 0A, the device reads “FF”.

Display separate typeAdd-on type

sepyT 3ABX 4ABX 6ABX 8ABX

rekaerbelbacilppA,SN004SX,SC004SX,SN004EX

EN004HX,EN004SX,EN522HXEN006SXEN006HX

EN008SXEN008HX

eriwdnaesahP3 3ø W ¡ ¡ ¡ ¡

1 3ø W ¡ ¡ ¡ ¡

° sgnitaR

]CAV[egatlovtiucricniaM q 064

]A[tnerrucgnirusaemdetaR 052 004 006 008

]zH[ycneuqerfdetaR zH06/05

rewoplortnoClanretnI ew .tiucricniamV001–042CAehtmorfdeilppussirewoplortnoC

lanretxE tr–064CAehtotdeilppaebnacecivedeht,V001–042CAsirewoplortnocnehW

.tiucricniamV001° yalpsiDdnagnirusaeM

esahpT/S/RfotnerrucdaoL uegnaR tnerrucgnirusaemdetarfo%003–2

ycarucca y tnerrucgnirusaemdetarfo%1±

neewtebfoegatloveniLsesahpT/S/R

egnaR V064–001CA

ycarucca y egatlovdetarfo%1±

rewopsuoenatnatsnIegnaR Wk999999–0

ycarucca y %5.2±

rewopdetargetnIegnaR hWM9.99999rohWk9.99999.xaM

ycarucca y %5.2± i

rotcafrewoPegnaR %001–1 o

ycarucca y %5.2±

Page 33: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

32

TemPlugDirect bus plug-in mounting base4

Just plug the TemPlug into the main bus.That completes the connection!We offer solutions to downsizing and standardizing them,shortening the manufacturing periods, and reducing the costs.

°Downsizing of switchboardsThe TemPlug is inserted directly into themain bus, requiring no space for branchedbus bars. This allows for decreasing thewidth of a switchboard.

°Standardization of switchboardsThe size of the main bus is determined bythe power capacity. Therefore, theswitchboards of the same capacity can bestandardized.

°Shortening of manufacturingperiods

The time-consuming jobs for making andmounting branched bus bars are no longerrequired.The working time can be greatly saved,resulting in shorter lead-time of aswitchboard.

°Flexibility in changingspecification

If there is any change in the frame size orrated current of a breaker, you can complywith that change by merely changing theTemPlug.

°Standardization of order ofphases

The order of load-side phases can bestandardized into R, S, and T from the topregardless of the mounting orientation ofthe breaker.

°Improvement of safety byseparating sections

The use of the TemPlug allows you toseparate the bus and breaker sections tomanufacture a safer switchboard.

Applicable to 100A to 630A frame circuit breakers

FigA

FigB

a

d

d c

70

70

c

b

600/630A400A225/250A100/125A

¶Supply the round-edge type main bus with plate thickness of 10 mm and corner radius of 5 mm. Suitable for 70mm main bus pitch.

epyT S2IDX H2IDX S3IDX ZS3IDX H3IDX 4IDX 5IDX

)A(ezisemarF 001 521 052 522 052 004 036

tiucricelbacilppAsrekaerb

,BN001SX,BNN001SX

BN001ZT

,SN001HX,JC521SX,JN521SX

JN521HX

,SN522SX,JN061SX,JN052SX

NN522SX

BN522ZT ,SN522HX,JN061HX,JP052SX

JN052HX

,SC004SX,SN004EX,EN004SX,SN004SX,EN004HX,EN522HX

,JN004SX,JC004SXNN004SX

,SC006SX,SN006EX,EN006SX,SN006SX,JC036SX,EN006HX

JN036SX

snoisnemiD

a 032 272 782

b 09 021 081 042

c )B.giF(721 )A.giF(421 )A.giF(221

d 521

Page 34: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

33

NOTES: ¡ : Yes or available.— : No or not available.q : AC breaking capacity (kA) @ 415V – 6/6kA. [Icu/Ics]w : Available on request – ICP–M, U and L characteristics.e : 1 pole + neutral and 3 pole + neutral available on request.

(4.5kA and 6kA types only).r : Inst is set between 3 In to 5 Int : Inst is set between 5 In to 10 Iny : Inst is set between 10 In to 20 In

Ampere FrameSeriesNumber of polesAC RATED INSULATION VOLTAGE [Ui]AC BREKING CAPAClTY sym. r.m.s.(kA)EN 60 898 [Icn]/[Ics]EN 60 947-2 [Icu]/[Ics]MCB Characteristics wEN 60 898 0.5AType TDB 1A

2ACharacteristics: B 3Ar 4A

6A10A13A16A20A25A32A40A50A63A

EN 60 898 0.5AType TDC 1A

2ACharacteristics: C 3At 4A

6A10A13A16A20A25A32A40A50A63A

EN 60 898 0.5AType TDD 1A

2ACharacteristics: D 3Ay 4A

6A10A13A16A20A25A32A40A50A63A

OUTLINE DIMENSIONS (mm)abcdef

STANDARD FEATURESContact position indicatorNumber of units per boxIP 20 Terminal protectionACCESSORIESShunt tripAuxiliary contactsTerminal coversPadlock device

TemDinMiniature Circuit Breakers5

bc f

a e d

5

63E–Series1 2 3 4415

e 4.5/4.5—

————————————————————¡¡¡¡¡¡¡¡¡¡———————————————

457343873617.8 35.6 53.4 71.2

—12 6 4 3¡

——¡¡

63S–Series1 2 3 4415

e 6/610/6

—————¡¡¡¡¡¡¡¡———————¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡¡

457343873617.8 35.6 53.4 71.2

—12 6 4 3¡

——¡¡

63R–Series1 2 3 4415

10/7.510/7.5

—————¡¡¡¡¡¡¡————————¡¡¡¡¡¡¡¡ q¡ q¡ q¡¡¡¡¡¡¡¡¡¡¡¡¡ q¡ q¡ q

457343873617.8 35.6 53.4 71.2

¡12 6 4 3¡

¡¡¡¡

Page 35: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

34

This is a standard breaker excluding thermaloverload trip. It has an instantaneous trippingcharacteristic only. This is used where short-circuit protection is exclusively needed.

Circuit Breaker withMagnetic Trip Only

High-lNST Trip Breaker

This is a standard molded case circuit breaker(electronic type) with a high instantaneous trip-ping value, in one-point fixed. This is recom-mended for zone selective interruption or theprimary side of transformer application.

Breakers for Coordination

TERASAKI Standard Breakers are manufac-tured based on the “standard operating condi-tions”If an application in other places than those of“standard operating conditions”, specify as “Spe-cial Environment Breakers” when ordering yourbreakers.

Special Environment Breakers

Standard Operating Conditions

• Operating ambient temperature: –5°C to 40°CIf used at a higher temperature than 40°C, the operating currenthas to be reduced;50°C: Approx. 90%60°C: Approx. 70%

• Relative humidity: Below 85%• Altitude: Below 2000m• Atmosphere: Contents of dust, smoke, corrosive gases, flammable gases, moisture and salt should

be moderately low.

Low-temperature Circuit Breaker

This is a breaker designed for use in low tem-perature environment. Storage and operatingconditions are –40°C and –20°C respectively.Since the operating characteristics of the low-temperature breaker are adjusted at 40°C(45°C), the characteristics vary at a lower tem-perature.Conditions: This type of breaker should not be

used where thermal changes arerapid and dew-formation and freez-ing exist.

Anti-fungus Circuit Breaker (Tropical-proof)

Dielectric strength and other electrical propertiesmay deteriorate under unusual high temperatureand high-humidity conditions. This type ofbreaker is specially prepared with specialsurface treatment, special materials and tropical-proof processing.Operating conditions are:

Temperature: Below 60°CHumidity: Below 95%

Conditions: This type of breaker should be usedin a constant humidity environmentwithout rapid thermal changes anddew formation.

Highly Anti corrosive Circuit Breaker

In highly corrosive or saline atmosphere,breakers are used in sealed corrosion-proofboxes or enclosures.However, in a place where the influence ofcorrosive gases is relatively low a simplermethod is applicable:This is the Highly Anti-corrosive Breaker withspecial surface treatment of high corrosion-proofness.This eliminates needs for such a box orenclosure.

Low-INST Trip Breaker

Low Instantaneous Trip Breakers is also avail-able on request. Ask TERASAKI or its agent fordetails.

Other Electrical Distribution EquipmentSpecial Circuit Breakers ¶ Special Circuit Breakers are available on request.6

Page 36: Low-Voltage Circuit Breakers - doilco.com Voltage... · Low-Voltage Circuit Breakers ... air circuit breakers, which had received high reputations for ... Minuature circuit breakers,

CAUTION!

Be sure to read the instruction manual carefully to ensure

correct and safe use of the product.

OVERSEAS NETWORK

TERASAKI (EUROPE) LTD.80 Beardmore Way, Clydebank Industrial Estate, Clydebank, Glasgow, G81 4HT. SCOTLAND (U. K.)Telephone : 44-141-941-1940 / Fax : 44-141-952-9246E-mail : [email protected]://www.terasaki.com/

TERASAKI ITALIA s.r.l.Via Ambrosoli 4a, 20090 Rodano, Milano, ITALYTelephone : 39-02-92278300 / Fax : 39-02-92278320E-mail : [email protected]://www.terasaki.it/

TERASAKI ESPAÑA, S.A.U.Roma, s/n, 08400 Granollers, Barcelona, SPAINTelephone : 34-93-879-60-50 / Fax : 34-93-870-39-05E-mail : [email protected]://www.terasaki.es/

TERASAKI SKANDINAVISKA ABFrasarvagen 32 SE-142 50 SKOGÅS SwedenTelephone : 46-8-556-282-30 / Fax : 46-8-556-282-39E-mail : [email protected]://www.terasaki.se/

TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.9 Toh Guan Road East 03-01 Alliance Building, Singapore 608604, SINGAPORETelephone : 65-6744-9752 / Fax : 65-6748-7592E-mail : [email protected]

TERASAKI ELECTRIC (M) SDN. BHD.Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor Darul Ehsan, MALAYSIATelephone : 60-3-5549-3820 / Fax : 60-3-5549-3960 E-mail : [email protected]

TERASAKI DO BRASIL LTDA.Rua Cordovil, 259-Parada de Lucas, 21250-450 Rio de Janeiro-R. J., BRAZILTelephone : 55-21-3301-9898 / Fax : 55-21-3301-9861E-mail : [email protected]://www.terasaki.com.br/

TERASAKI ELECTRIC (CHINA) LIMITED72 Pacific Industrial Park, Xingtang Zengcheng, Guangzhou 511340, CHINATelephone : 86-20-8270-8556 / Fax : 86-20-8270-8586E-mail : [email protected]

Head Office : 7-2-10 Hannancho, Abenoku, Osaka, JAPANCircuit Breaker Division : 7-2-10 Kamihigashi, Hiranoku, Osaka, JAPANTelephone : 81-6-6791-9323 / Fax : 81-6-6791-9274E-mail : [email protected]://www.terasaki.co.jp/

JUN ’05-2.0K Catalogue No. The contents of this publication may be subject to change without notice.Recycled paper used for environmental protection.

’05-G90E