GLOBAL RANGE low voltage 1. 1. Moulded Case Circuit Breakers CATALOGUE MCCB

Upload: trandien

Post on 18-May-2018

261 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

GLOBALRANGE

low voltage

1.1.

Moulded Case Circuit Breakers

CATALOGUE

MCCB

Page 2: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

MCCB Standard Range

1.1 Product Overview.1.2 MCCB Specifications

1.3 Switch Disconnector Specifications

1.4 - 1.8 MCCB Dimensions

1.9 MCCB Safety Clearance

1.10 MCCB Environment

1.11 MCCB Diagnostic table

1.12 - 1.15 Characteristic Curves

1.16 Cascading Table

1.17 - 1.18 MCCB Electrical & Mechanical Change System

1.19 - 1.22 MCCB Accessories

1. Moulded Case Circuit Breakers (Standard Range)

Page 3: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Product Overview

Calibrated for 40°C

Amb. Temp -5C 0C 10C 20C 25C 30C 35C 40C 45C 50C

In=15 to 30

In=40 to 100

In=100 to 225

In=225 to 800

111.9%

110.2%

114.3%

110.0%

111.3%

109.8%

113.2%

109.0%

110.0%

108.7%

108.0% 106.6% 104.9% 102.7% 100.0%

100.0%

100.0%

100.0%

96.8% 93.3%

107.0% 105.8% 104.3% 102.4% 97.2% 94.0%

110.6%

107.0%

107.5%

105.0%

105.8%

104.0%

104.0%

103.0%

102.0%

101.5%

97.9%

98.5%

95.6%

97.0%

Effect of Ambient Temperature on rating

* Note: N65D Icu = 0,5 Ics

15 A

20 A

30 A

40 A

50 A

60 A

75 A

100 A

125 A

150 A

175 A

200 A

225 A

250 A

300 A

350 A

400 A

500 A

630 A

700 A

800 A

1000 A

1200 A

MCCB 15A - 125A FIXED 3P37kA @ 415V

Icu = Ics

K50D250

K50D300

K50D350

K50D400

L65D500

L65D630

L65D700

L65D800

N65D1000*

N65D1200*

Current

MCCB

G37D015

G37D020

G37D030

G37D040

G37D050

G37D060

G37D075

G37D100

G37D125

F37D150

F37D200

F37D175

F37D250

F37D225

MCCB 150A - 250A FIXED 3P37kA @ 415V

Icu = Ics

MCCB 250A - 400A FIXED 3P50kA @ 415V

Icu = Ics

MCCB 500A - 1200A FIXED 3P65kA @ 415V

Icu = Ics

125 A

250 A

400 A

630 A

800 A

1200 A

DIS 125A FIXED 3PCBI - X = 1.2 kA

Current

DIS

G37DN125

DIS 250A FIXED 3PCBI - X = 1.2 kA

DIS 400A FIXED 3PCBI - X = 3.2 kA

DIS 630A - 1200A FIXED 3PCBI - X = 6.4 kA/3.6 kA*

F37DN250

K50DN400

L65DN630

L65DN800

N65DN1200*

3990A806 Catalogue

Page 1.1 of 1.22

Standard MCCB

Global Range

Page 4: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

MCCB Specifications

3990A806Catalogue

Page 1.2 of 1.22Standard MCCB

Global Range

* Contact CBI-elelctric for availability

Type 3 Pole

Rated Current A

Rated operational AC(V)

voltage, Ue DC(V)

Rated Insulation Voltage, Ui V

Rated Impulse withstand voltage, Uimp kV

AC 690V

480/500V

415/460V

380V

220/250V

DC (3P) 500V

Service breaking capacity (%Icu), Ics

Category of use

Endurance Mechanical

(Number of operations) Electrical

Type of trip unit

Thermal-magnetic release

Accessories

Electrical auxiliaries Auxiliary switch

Alarm switch

Shunt trip

External accessories

Undervoltage trip

Direct rotary handle*

Extended rotary handle

Terminal cover

Insulation barrier

Rear connection*

Mechanical interlock*

Plug in device*

Dimensions (mm) W x H x D (3p)

3 pole

G37D

(15, 20, 30, 40, 50, 60, 75, 100, 125)

690

500

750

8

8

25

37

42

85

20

100**

A

fixed

90 x 155 x 60

1

F37D L65DK50D

(150, 175, 200,225, 250)

690

500

750

8

8

26

37

42

85

20

100**

A

fixed

105 x 165 x 60

1.2

(250, 300, 350,400)

690

500

750

8

8

35

50

65

75

20

100**

A

fixed

140 x 257 x 109

6.2

(500, 630,700, 800)

690

500

750

10

8

45

65

75

85

20

100**

A

fixed

210 x 280 x 109

11.5

N65D

(1000)

600

x

690

x

6

50

65

65

100

x

50

A

fixed

220 x 400 x 105

21

N65D

(1200)

600

x

690

x

6

50

65

65

100

x

50

A

fixed

21Weight (kg)

2500

500

2500

500

220 x 400 x 105

Rated short circuit breaking capacity (Icu) kA (Sym)

25000 25000 4000 2500

50010001000010000

525/550V** 25 25 35 35

Available or supplied as standard * Optional - Please specify Not availableNote:

x x

x x

x x

x

x

x

x x

** Icu = Ics 525,550 V

Page 5: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.3 of 1.22

3990A806

Standard MCCB

Global Range

Type

Rated Insulation Voltage, Ui V

Accessories

Electrical auxiliaries Auxiliary switch

Alarm switch

Shunt trip

External accessories

Undervoltage trip

Direct rotary handle*

Daros Extended rotary handle

Terminal cover

Insulation barrier

Rear connection*

Mechanical interlock*

Plug in device*

G37DN125

750

A

L65DN630K50DN400

750 750 750 690 690

Endurance Mechanical

(Number of operations) Electrical

2500

500

2500

500

25000 25000 4000 2500

500 1000 10000 10000

Rated Current Max A (125)

F37DN250 L65DN800 N65DN1200

(250) (400) (630) (800) (1200)

No of Poles 3, 4* 3, 4* 3, 4* 3, 4* 3, 4* 3, 4*

Rated operational Voltage AC(V)

Ue DC(V)

690

500

690

500

690

500

690

500

600

x

600

x

Rated Impulse withstand voltage, Uimp kV 8 8 8 8 6 6

8

25

8

26

8

35

10

45

x

50

x

50

Rated short circuit making capacity Icm (kA peak)

25 25 35 35

37 37 50 65

1 1.2 6.2 11.5 21 213 poleWeight (kg)

Dimensions (mm) W x H x D (3p) 90 x 155 x 60 105 x 165 x 60 140 x 257 x 109 210 x 280 x 109 220 x 400 x 105 220 x 400 x 105

AC 690 V

525/550 V

480/500 V

415/460 V

380 V

220/250 V

DC (3P) 500 V

Category of use

65 65

42 42 65 75 65 65

85 85 75 85 100 100

20 20 20 20 x x

A A A A A

CBI - X = Min kA 1.2 kA 1.2 kA 3.2 kA 6.4 kA 6.4 kA 3.6 kA

* Contact CBI-elelctric for availability Available or supplied as standard Optional - Please specify Not availableNote: x

x x

x x

x x

x x

x x

Switch Disconnector

Page 6: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

18 24

10

8 M8×14

8

16

9

ConnectingetailsdTerminal

30 30 30

60 30 58

608

82

90

120

90

37 37

50

80

50

80

15

5

13

5

10

0

15

5

13

5

10

0

50 50

50

4

8.2

5

16

.5

16

.5

10

8

10

8

22 22

Insulation barrier

Fixing hole

Insulation barrier

Fixing hole

Trip test button Trip test button

3P 4P*

30 92

13

2

30

13

2 52

122

52

M4 or Ø5

3P 4P* 3P 4P*

Panel drilling Front panel cutting

M4 or Ø5

G37D/N MCCB 37kA Fixed 15A - 125A

Dimensions: mm

* Contact CBI for availability

MCCB Dimensions

3990A806 Catalogue

Global Range

Standard MCCBPage 1.4 of 1.22

Page 7: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

3990A806Catalogue

Page 1.5 of 1.22

Standard MCCB

Global Range

MCCB Dimensions

Mo

tor C

on

trol

F37D/N MCCB 37kA Fixed 150A - 250A

Insulation barrierInsulation barrier

Fixing hole Fixing hole

Trip test button Trip test button

Terminal details Connecting

3P 4P*

M4 or Ø 5 M4 or Ø 5

3P 4P* 3P 4P*

Panel drilling Front panel cutting

Page 8: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

MCCB DimensionsMCCB Dimensions

Catalogue

Page 1.6 of 1.22

3990A806

Global Range

Standard MCCB

K50D/N MCCB 50kA Fixed 250A - 400A

Fixing hole Fixing hole

M5 or Ø 6

Trip test button Trip test button

Slot "A"

"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)

Slot "B"

Slot "C"142(3p)

187(4p) 187(4p)142(3p)

Terminal details Connecting

3P 4P*

3, 4P* 3, 4P* 3, 4P*3/4P*

Panel drilling Front panel cutting

Dimensions: mm

Stub busbars supplied

Page 9: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.7 of 1.22

3990A806

Global Range

Standard MCCB

L65D/N MCCB 65kA Fixed 500A - 800A

Slot "A"

"A" (Handle only) "B" (Handle and name plate) "C" (Handle, name plate & button)

Slot "B"

Slot "C"212(3p)

282(4p) 282(4p)

212(3p)

Terminal detailsConnecting

Panel drilling Front panel cutting

3P 3, 4P* 3,4P* 3, 4P*

Trip test button Trip test button

3P 4P*

Dimensions: mm

* Contact CBI for availability

MCCB Dimensions

Page 10: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

MCCB Dimensions

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.8 of 1.22

N65D/N MCCB 65kA Fixed 1000 - 1200 A

Mounting hole Mounting hole

Auxiliary handle

or or

3P 4P*

3P 3P4P* 4P*

Panel drilling Front panel cutting

(4 Poles available only up to1000 A)

Dimensions: mm

* Contact CBI for availability

Page 11: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.9 of 1.22

MCCB Safety Clearance

B: Minimum distance between the lower and the upper breakers

B

Safety clearance

A: Minimum distance to metallic top panels

Framesize

Description A

100AF G37D 100

125AF G37D 100

250AF F37D 100

400AF K50D 100 800AF L65D 100

A (mm)

Framesize

Description

125AF G37D 100

250AF G37D 100

400AF F37D 100

800AF K50D 100

B (mm)

When installing a circuit breaker, safety clearances must be kept between the breaker and the panels,bars and other protection devices installed nearby. These safety clearances are dependant on theultimate breaking capacity and are defined by tests carried out in accordance with standard IEC 60947-2.

When a short circuit interruption does occur, high temperatures and high pressures occur in thecircuit-breaker. In order to allow the pressure to be distributed and to prevent fire and arcingof short circuit currents, safety clearances are required.

Page 12: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

Catalogue

Page 1.10 of 1.22

3990A806

Global Range

Standard MCCB

MCCB environment

Standard Use Environment

Standard Use Environment for Moulded Case Circuit Breaker

The operation characteristic of Moulded Case Circuit Breakers including, short circuit, overload, endurance and insulation is often influenced largely by the external environment and thus shouldbe applied appropriately, taking into consideration the conditions where it will be used. In particularthe operation characteristic of the Circuit Breaker with a Thermal Magnetic trip element (FTU, FMU,ATU). In areas where there is a difference in ambient temperature, the power rating will have to be adjusted accordingly when the Circuit Breaker is actually in use.

1. Ambient temperature within the range of -5ºC ~ +40ºC (However, the average per 24 hour period must not exceed 35ºC).2. Relative Humidity: Within the range of 45 ~ 85%3. Altitude: 2000m or less (If altitude exceeds 1000m, atmosphere correction through humidity test and withstand voltage test can be considered)4. Use in an atmosphere where excessive steam, oil steam, dust, salt and other corrosive material do not exist.

- If a standard circuit breaker is used at high temperatures exceeding 40ºC, it is advised to use the Circuit Breaker according to the current correction for each level of ambient temperature in catalogue. Refer to derating curve/s: Holds less load.- If used in conditions of high humidity, the electric strength or electric performance may be degraded.

- Conduction, switch, trip or short circuit isolation functions normally at temperature of -20ºC.- Storage in extreme cold areas are allowed in temperatures of -40ºC- Refer to de-rating curve/s : Holds more load.

- It is highly recommended to use a dust cover or anti-humidty agent if the Circuit Breaker is used in dusty and humid conditions.- Long term humidity may corrode metal parts and prevent operation.- Excessive vibration may cause a nuisance trip.

- If the Circuit Breaker is ON or OFF for a long time, it is recommended to manually switch the load current on a regular basis.- It is recommended to put the Circuit Breaker in sealed protection if corrosive gas is prevalent.

For assistance in regular examination of Moulded Case Circuit Breakers see the

“Moulded Case Circuit Breaker Deterioration Diagnostic Table” on the next page

Page 13: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.11 of 1.22

MCCB Diagnostics table

Moulded Case Circuit Breaker Deterioration Diagnostic Table

Sample No.

Installation location

Model, number of poles, rating

Specifications

Accessories

Serial number

Installation date

Item Factor Condition Points

1. Age of use x 3 Less than 10 years Less than 15 years Less than 20 years Less than 30 years 30 years or more

12345

2. Number of opening - closing operations x 5 Specified number or lessDouble the specified number or less Double the specified number or more

123

Internal Inspec

-tion

(1) Ambient temperature x 4 Low (monthly average 30 °C or less)Normal (monthly average 3°C or less)High (mnthly average over 3°C)

012

(2) Humidity x 4 Low (monthly average 45% or less)Normal (monthly average 85% or less)High (monthly average over 85%)

012

(3) Corrosive gas x 10 Does not existExists

01

(4) Carrying Current (average) x 3 50% or less of rating 80% or less of rating Over 80% of rating

123

Structural

Inspec-tion

(1) Dust / Smear x 4 Almost none Adhesion of dust, oil mist, etc. (Small amount)Adhesion of dust, oil mist, etc. (large amount)

012

(2) Dust at the line side barrier area

x 5 No dust Adhesion of soot (minute amount)Adhesion of soot (large amount)Adhesion o metal particles

0123

(3) Traces of overheating in termal area

x 7 No discoloration Slight overheating discoloration foundSignificant overheating discoloration

012

5. Insulation resistance (Note) In the case of Earth Leakage circuit breakers, insulation resistance between the right poles cannot be measured because the control circuit power is on.

x 5 Over 100 MΩ5 MΩ - 100 MΩ0.5 - Less than 5 MΩ

015

Total score (factor x points)

Necessity of consideration for renewal Need No need

Total evaluation score Judgment guide

0 - 20 points It is judged that continuous use is possible.

21 - 29 points It is judged that renewal should be considered.

30 points or more It is judged that renewal is necessary.

Page 14: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.12 of 1.22

Characteristics curves

Min

.S

ec.

Ope

rationa

l tim

e

Max.

Min.

Max. breaking time

Rated current

Magnetic trip range

Min

.S

ec.

Ope

rationa

l tim

e

Max.

Min.

Max. breaking time

Rated current

Magnetic trip range

Rated current: 15~30A, 40~100A

Rated current: 125A

Rate

d cu

rren

t co

mpe

nsat

ion

rate

(%)

Ambient temp 40ºC

Rate

d cu

rren

t co

mpe

nsat

ion

rate

(%)

Ambient temp 40ºC

Compensation curves

Rated current: 15~100A

Rated current: 125A

G37D MCCB

Page 15: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.13 of 1.22

3990A806

Global Range

Standard MCCB

Characteristics curves

F37D MCCB

Min

.S

ec.

Ope

rationa

l tim

eMax.

Min.

Max. breaking time

Rated current

Magnetic trip range

Rated current: 150 ~ 225A

240180150

10080

60

40

20

40

20

108

6

4

2

108

6

4

2

1

1

1 2 3 4 5 6 7 8 9 10 15 20 30 40 50 60 80 1001.5

0.8

0.6

0.4

0.2

0.10.08

0.06

0.04

0.02

0.01

120

(960~1440%)

Min

.S

ec.

Ope

rationa

l tim

e

Rated current

Magnetic trip range

Max. breaking time

Max.

Min.

Rated current: 250A

150

100

500 10 20 30 40 50Ra

ted

curr

ent

com

pens

atio

n ra

te (%

)

150

100

500 10 20 30 40 50Ra

ted

curr

ent

com

pens

atio

n ra

te (%

)

Compensation curves

Rated current: 150~225A

Rated current: 250A

Ambient temp 40ºC

Ambient temp 40ºC

Page 16: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.14 of 1.22

Characteristics curves

Min

.S

ec.

Ope

rationa

l tim

e

Max.

Min.

Max. breaking time

Rated current

Magnetic trip range

1

0.1

0.2

0.4

0.60.8

1

2

4

68

10

20

40

1

2

4

6

810

20

40

60

120

180

240

0.01

0.02

0.04

0.060.08

1.25 2 3 4 5 6 7 8 9 10 15 20 30 40 50 70 100

(800~1200%)

Min

.S

ec.

Ope

rationa

l tim

e

Max.

Min.

Max. breaking time

Rated current

Magnetic trip range

Rated current: 250~400A

Rated current: 500~800A

0 10 20 30 40 5050

150

100

Rate

d cu

rren

t co

mpe

nsat

ion

rate

(%)

50

100

150

0 10 20 504030Rate

d cu

rren

t co

mpe

nsat

ion

rate

(%)

Compensation curves

Rated current: 250~400A

Rated current: 500~800A

K50D / L65D MCCB

Ambient temp 40ºC

Ambient temp 40ºC

Page 17: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.15 of 1.22

3990A806

Global Range

Standard MCCB

Characteristics curves

N65D MCCB

Min

.S

ec.

Op

era

tio

nal ti

me

Max.

Min Ranges of instantaneous trip

MaxMin

Rated current

.

Max. breaking time

Rated current

Rated current: 1000~1200A

Rate

d cu

rren

t co

mpe

nsat

ion

rate

(%)

Compensation curves

Rated current: 1000~1200A

Ambient temp 40ºC

Page 18: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.16 of 1.22

Cascading Table

Ca

sc

ad

ing

Ta

ble

(C

BI

MC

CB

’s)

G37D

15 -

125 A

F

37D

150 -

250 A

K

50D

250 -

400 A

L

65D

5

00 -

800 A

Typ

e

No o

f P

ole

s

Fa

ult

Le

ve

l kA

65

50

35

30

25

20

15

10

33

33

33

33

33

33

33 65

50

35

25

50

35

25

15

35

25

15

35

25

15

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37D

/F

37D

QF

QF

QH

,QF

QH

,QF

QH

,QF

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DQ

F

QH

/QF

QH

/QF

QF

QF

Dow

nst

ream

kA QF

QF

QF

QF

QH

/QF

QF

QF

QF

QF

QF

QF

QF

QF

QF

QF

QF

QH

/QF

G3

7D

/F

37

D

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37

D/

F3

7D

QH

/QF

QH

/QF

BU

SB

AR

RA

TIN

GkA

RM

S

20

15

10

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37D

/F

37D

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37D

/F

37D

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37D

/F

37D

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37D

/F

37D

G3

7D

/F

37

DG

37

D/

F3

7D

G3

7D

/F

37

DG

37D

/F

37D

QH

/QF

Page 19: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.17 of 1.22

3990A806

Global Range

Standard MCCB

MCCB Electrical & Mechanical Change System

CN

1-1

CN

1-2

CN

1-3

CN

1-4

CN

1-5

CN

1-6

CN

1-7

CN

1-8

CN

1-9

CN

-10

CN

1-11

CN

1-1

2

Norm

al p

ow

er L

1 vo

ltage o

utp

ut

Norm

al p

ow

er L

3 vo

ltage o

utp

ut

Norm

al P

ow

er L

2 vo

ltage o

utp

ut

Em

erg

ency O

N m

oto

r AC

pow

er in

put

Norm

al O

N sig

nal o

utp

ut

Norm

al O

N m

oto

r AC

pow

er in

put

Norm

al O

N m

oto

r AC

pow

er in

put

Em

erg

ency O

N sig

nal o

utp

ut

Em

erg

ency O

N m

oto

r AC

pow

er in

put

Em

erg

ency p

ow

er L

2 vo

ltage o

utp

ut

Em

erg

ency p

ow

er L

3 vo

ltage o

utp

ut

Em

erg

ency p

ow

er L

1 vo

ltage o

utp

ut

PIN

NO

.D

ES

CR

IPT

ION

12P

AM

P H

ousin

g

10

74

1

11

12

89

56

23

NO

RM

AL S

UP

PLY

L2

L3

NL

1

#N

LS

>>

No

rma

l Au

xilia

ry S

witch

#E

LS

>>

Em

erg

en

cy A

uxilia

ry S

witch

L1

L2

L3

N

LO

AD

CB

1C

B2

NLS

ELS

M2

20

V

ELS

NLS

BROWN

ORANGE

RED

PURPLE

GREEN

BLUE

YELLOW

GRAY

WHITE

PINK

BLACK

RED / WHITE

CN1-1

CN1-3

CN1-2

CN1-7

CN1-5

CN1-6

CN1-4

CN1-8

CN1-9

CN1-11

CN1-10

CN1-12

øø

øø

øø

øø

EM

ER

GE

NC

Y S

UP

PLY

L2

L3

NL

1

øøøø

CB

I-Electric M

CC

B T

ype Transfer Sw

itch wiring d

iagram

(Ne

utra

l Ph

ase

ma

y b

e o

ptio

na

l)

Page 20: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.18 of 1.22

MCCB Electrical & Mechanical Change System

CM-MI 125 CM-MI 250 CM-MI 400 CM-MI 800

- MCCB styled electrical change over with manual option.- Easy to read mechanical status.- Compatible with most ATS controllers- Fully built and pre-wired to accept mains and controller interface.- Customer selected combinations.- Factory assembled and tested.- Factory fitted combined Busbars on load side. - Electrical locking system with factory fitted MCCB, Aux Circuit.- 3P System standard (4 Pole optional*)

Motor specifications200 - 240 VAC (50 / 60Hz)Ui AC 750 VUe 220 V

5 - 125 A

150 - 250 A

250 - 400 A

500 - 800 A

Select any MCCB combination

Frame Selectable Amps System is frame &

size dependant, eg. the selection must be fromthe same frame size.

230 - 400 V Network

* Contact CBI for availability

GD

FD

KD

LD

Page 21: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.19 of 1.22

3990A806

Global Range

Standard MCCB

MCCB Accessories

Electrical auxiliaries of 125~250AF

GD & FD (common 15 A - 250 A)

Option of connecting SHT or UVT

or AX or AL or AX+AL

Shunt Trip

Undervoltagetrip

AuxiliarySwitch

Alarm Switch

Combinationswitch

AuxiliarySwitch

Alarm Switch

AX

SHT

UVT

AX*

A*

AX+AL*

AX+AL

ALLeft-hand seat Right-hand seat

Combination switch

Option of connecting AX or AL or AX+AL

* Non standard: Contact CBI for availability

Maximum possibilities

Position

Left-hand

seat

Right-hand

seat

Type

AX

AL

AX+AL

AX

AL

AX+AL

SHT/UVT

GD FD

3p

1

1

1

1

1

1

1

1

1

1

1

1

1

1

3p

Page 22: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.20 of 1.22

MCCB Accessories

Electrical auxiliaries of 400~800AF

Maximum possibilities

Position TypeKD/LD

400~800 A

2

2

1

2

2

1

Option of connecting

AX or AL or AX+AL

AL

*SHT

UVT

AX

Alarm Switch

Shunt Trip

Undervoltage trip

Auxiliary Switch

AL*

SHT

UVT

AX*

Alarm Switch

Shunt Trip

Undervoltage trip

Auxiliary Switch

KD / LD (common 250 A - 800 A)

*

* Non standard: Contact CBI for availability

Left-hand

seat

Right-hand

seat

AX

AL

SHT/UVT

AX

AL

SHT/UVT

*

*

*

Page 23: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

Mo

uld

ed

Case

Circ

uit B

reakers

low voltage

Catalogue

Page 1.21 of 1.22

3990A806

Global Range

Standard MCCB

MCCB Accessories

Shunt trip, SHT

The shunt trip opens the mechanism in response to an externally applied voltage signal. The releases include

coil clearing contacts that automatically clear the signal circuit when the breaker has tripped.

Rating for GD & FD

Voltage

Max.opening time

Tightening torque of terminal screw

AC/DC 12V

AC/DC 24V

AC/DC 48V

AC/DC 60V

AC/DC 100~130V

AC/DC 200~250V

AC 380~450V

AC 525~550V*

AC (VA)

0.35

0.64

1.09

1.2

0.73

1.21

1.67

1.68

Power consumption

DC (W)

0.36

0.65

1.1

1.22

0.75

1.35

-

-

50ms (max.)

12 kgf∙ cm

mA

30

27

23

20

5.8

5.4

3.8

3.5

Control voltage, Ue

Rating for KD & LD

AC/DC 24~48

AC 100~125/DC 100~110

AC 200~240/DC 200~220

AC 380~460

AC 480~550

Control voltage, Ue

AC 24 14 0.3

DC 24 15.4 0.4

AC 48 14 0.7

DC 48 16 0.8

AC 110 6 0.7

DC 110 6.6 0.7

AC 220 6.8 1.5

DC 200 7.6 1.5

AC 440 4.3 1.9

AC 480 4.4 3.3

AC 550 4.6 2.4

Power consumption

Note: 1. Range of operational voltage: 0.7 ~ 1.1VnFrequency (Only AC): 45Hz ~ 65Hz

Note: Range of operational voltage AC: 0.85 ~ 1.1VnDC: 0.75 ~ 1.25Vn

Terminal block type

Lead wire type

* 550 V in process of being tested

V mA A

Page 24: low voltage GLOBAL. MCCB... · GLOBAL RANGE low voltage 1.1. Moulded Case Circuit Breakers CATALOGUE MCCB

low voltage

Mo

uld

ed

Case

Circ

uit B

reakers

3990A806

Global Range

Standard MCCB

Catalogue

Page 1.22 of 1.22

MCCB Accessories

Undervoltage release, UVT

The undervoltage release automatically opens a circuit breaker when voltage drops to a value ranging between

20% to 70% of the line voltage. The operation is instantaneous, and after tripping, the circuit breaker cannot be

re-closed again until the voltage returns to 85% of line voltage.

Continuously energized, the undervoltage release must be functioning before the circuit breaker can be closed.

- Range of tripping voltage: 0.2 ~ 0.7Vn

- Reset and closing of a breaker is possible when the control voltage is over 0.85Vn

- Frequency (Only AC): 45Hz ~ 65Hz

Rating for GD & FD

Voltage

Max.opening time

Tightening torque of terminal screw

Operating

voltage range

AC/DC 24V

AC/DC 48V

AC/DC 100~110V

AC/DC 200~220V

AC 380~440V

AC 440~480V

Trip

Reset / Closing

AC (VA)

0.64

1.09

0.73

1.21

1.67

1.68

Power consumption

DC (W)

0.65

1.1

0.75

1.35

-

-

50ms (max.)

12 kgf∙ cm

20~70% Vn

≥ 0.85Vn

mA

27

23

5.8

5.4

3.8

3.5

Control voltage, Ue

Rating for KD & LD

Control voltage, Ue Trip voltage Reset/closing voltage Time rating

Terminal numbering

Auxiliary Switch (AX) Alarm Switch (AL) Shunt Trip (SHT) Undervoltage trip (UVT)

AC/DC 48

AC/DC 100~125

AC/DC 200~240

AC 380~440

AC 440~480

∙ AC: 0.2~0.7Vn

∙ DC: 0.2~0.7Vn

∙ AC: 85~1.1Vn

∙ DC: 85~1.25VnContinuous

AC 525~550V*

AC 525~550*

* 550 V in process of being tested

* 550 V in process of being tested