Low Voltage Switchgear ®

Upload: others

Post on 26-Jun-2020

19 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Low VoltageSwitchgear

Lo

w V

olt

age

Sw

itch

gea

r

®

Published by Iskra MIS, d. d. • Version 4.0, Oktober 2011 • design Nimbus d.o.o.

® Ljubljanska c. 24a, SI - 4000 Kranj, SloveniaTel.: +386 4 23 72 112, Fax: +386 4 23 72 129E-mail: [email protected], www.iskra-mis.si

®

Page 2: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

1

Index

Contents: Page

Contactors

K03,K07MiniContactors 2BR6Thermaloverloadrelay 8KNL6-KNL30Contactors 10BR16,BR30Thermaloverloadrelay 17KNL6G-KNL30GContactors 19KNL43,KNL63Contactors 23BR63Thermaloverloadrelay 26KNL80-KNL110Contactors 36KNL95-KNL630/1000Contactors 39KC12-KC60CapacitorDutyContactor 45IKA20-IK63InstallationContactors 47IKA20-R,IKA-25RInstallationContactors 60IKNAuxiliarySwitch 64IKA20-IK63InstallationContactorswithULcertificates 65IKNAuxiliarySwitchwithULcertificates 70BIBistableSwitch 71

MotorProtectionSwitches

MS20,MS25 75MS18,MS32 81

MiniatureCircuitBreakers

RI20 88RI50 89RI60 91RI120 95RV60,RV120RS 97SurfaceMounted(INO)andFlushMunted(IPO)CompactDistributionBoards 98

ResidualCurrentCircuitBreakers

FI,NFI 99RFI2 101

ContactorCombinations

KMPL,KPLDirecton-lineStarters 103ZKStar-DeltaMotorStarters 104KO-LD,KNL-LDCombinationsforReversing 105KMSPLCombinationStarters 105Directon-lineStartersupto30A 106ReversingStartersupto30A 109Star-DeltaStartersupto25kW 112

SwitchDisconnectorsDS 115DSPV 122

TimeRelays

TRE701 124TRE702 125TRE703 126TRE704 127TRE705 128TRE706 129

Accessories

Conectioncabinets 130Multi-functionaladapters 131Approvals 133NOTE:DataaboutOVERVOLTAGEPROTECTIONandMOULDEDCASECIRCUITBREAKERScanbefoundinseparatedbrochures.Generalsalesconditionscanbefoundonourwebsite(www.iskra-mis.si)

Page 3: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

2

MINICONTACTORS

TECHNICALDATA MOTORCONTACTORS

GEN

ER

AL

Type K03M K07M K07MG

Standards IEC/EN60947-5-1,IEC/EN60947-4-1,UL508

Approvals(K07CX,K07CGX,K07MX,K07MGXarewithoutapprovals) UL,CSA,GOST

Climaticclass constantdampheat(IEC60068-2-78)cyclicdampheat(IEC60068-2-30)

Ambienttemperature open°C

-20…+60

closed -20…+45

Storagetemperature °C -30…+80

Contactreliability 17V;≥50mA

Mechanicalendurance op.c. 107

Powerdissipationperpole W 1.2

Max.mechanicaloperatingfrequencywithnoload op.c./h 3000

Max.electricaloperatingfrequencyop.c./h 600/600/1200/1200

AC-1/AC-3/AC-15/DC-13

Weight kg 0.16 0.18 0.22

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 20

Ratedfrequency f Hz 50/60

Ratedpower 230V

Pe kW

7.5

400V 13

AC-1 500V 17.5

690V 22

Ratedoperationalcurrent upto50°C openIe A

20

AC-1 upto60°C open 16

Ratedmotorpower single-phase 230V

Pe kW

0.75 1.1 1.1

three-phase

230V 1.5 3 3

AC-3 400V 2.2 5.5 5.5

500V 3 5.5 5.5

690V 4 5.5 5.5

K03C, K07C, K07CG (DC), K07CF, K03M, K07M, K07MG (DC), K07MF, K07CX, K0CGX (DC), K07MX, K07MGX (DC)

• Contactors are used for switching electric motors and other resistive, inductiveandcapacitiveloads• Awidevarietyofsnap-onauxiliaryswitchblocksandaccessories• Uniformmarkingofterminalsinaccordance withtheEN50005andEN50011Europeanstandards• Quickassemblytoa35mmwidemountingrailin accordancewithEN60715orfixingwithtwoscrews• Openandfunnel-shapedconnectionterminals-fastandsimple connection•Highcontactreliabilityatlowvoltages•Possibilityofindividualmarkingonaspecialplate-easy identificationofacontactorinthecircuit• Twocontactorwidths:35and45mm• Optionaloperatingposition• ACorrealDCdrivewithlowconsumption• Possibility of direct connection of the BR6 bimetal relay for protection againstoverloadandincaseofphasefailure• Versionwithallfourmaincontacts(Sp4)• DegreeofprotectionIP20• Highelectricalandmechanicalendurance,andhighswitching capacity• K07CFandK07MFarecontactorsforfast-onconnection• K07CX,K07CGX,K07MXandK07MGXarecontactorswith solderingpins• TechnicaldataforK07MFandK07MXareidenticaltoK07M• TechnicaldataforK07MGXareidenticaltoK07MG• TechnicaldataforK07CXareidenticaltoK07C• TechnicaldataforK07CGXareidenticaltoK07CG

Page 4: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

3

MINICONTACTORS

TECHNICALDATA MOTORCONTACTORS

MAIN

CIR

CU

IT

Type K03M K07M K07MG

Ratedoperationalmotorcurrent single-phase 230V

Ie A

8 10 10

AC-3

230V 6.3 11.5 11.5

three-phase

400V 5 11.3 11.3

500V 5.3 9 9

690V 4.9 6.5 6.5

Ratedmotorpoweracc.toULsingle-phase

115V

Pe HP

1/3 ½ ½

230V ¾ 1½ 1½

three-phase

230V 2 3 3

460V 3 5 5

575V 5 7½ 7½

ElectricalenduranceofcontactsAC-1/AC-3

op.c. 0.2x106/diagram2

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 25

Terminalcapacityrigid

S mm20.75…2.5

flexible 0.5…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.2

AU

XILI

AR

YC

IRC

UIT

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 20

Ratedoperationalcurrent 230V

Ie A

6

400V 4

AC-15 500V 2

690V 1

Ratedoperationalcurrent 24VIe A

4

DC-13 110V 0.25

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20

Terminalcapacityrigid

S mm20.75…2.5

flexible 0.5…2.5

Screw M3,5

Screwhead PZ2

Tighteningtorque Nm 1.2

MAG

NETI

CS

YSTE

M

Coilconsumption

switch-on

Pc

VA 39 −

W 34 3

operationVA 8.1 −

W 4 3

makeNO

ms

10-15 10-10 25-30

NC 10-15 10-15 8-10

Make/Breakdelaybreak

NO 6-15 5-10 7-10

NC 6-15 6-15 10-25

Rangeofcontrolvoltage Uc % 85…110

Controlvoltages Uc V 6-415 6-690 6-250

Terminalcapacityrigid

S mm20.75…2.5

flexible 0.5…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.2

K03C, K07C, K07CG (DC), K07CF, K03M, K07M, K07MG (DC), K07MF, K07CX, K0CGX (DC), K07MX, K07MGX (DC)

Page 5: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

4

TECHNICALDATA CONTACTORRELAYS

GEN

ER

AL

Type K03C K07C K07CG

Standards IEC/EN60947-5-1,UL508

Approvals UL,CSA,GOST

Climaticclass constantdampheatacc.toIEC60068-2-78cyclicdampheatacc.toIEC60068-2-30

Ambienttemperature open°C

-20…+60

closed -20…+45

Storagetemperature °C -30…+80

Mechanicalendurance op.c. 107

Max.mechanicaloperatingfrequencywithnoload op.c./h 3000

Max.electricaloperatingfrequencyAC-15/DC-13 op.c/h 1200/1200

Weight kg 0.16 0.18 0.22

MAIN

CIR

CU

T

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 20

Ratedoperationalcurrent 230V

Ie A

6

400V 4

AC-15 500V 2

690V 1

Ratedoperationalcurrent 24VIe A

4

DC-13 110V 0.25

ElectricalenduranceAC-15 op.c. diagram1

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20

MAIN

CIR

CU

IT

Coilconsumption

switch-on

Pc

VA 39 −

W 34 3

operationVA 8.1 −

W 4 3

Rangeofcontrolvoltage Uc % 85…110

Controlvoltages Uc V 6-415 6-690 6-250

Terminalcapacityrigid

S mm20.75…2.5

flexible 0.5…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.2

Standardcontrolvoltagesanddesignations(AC)V 24 42 48 110/125 220/240 380/415 440 500

50/60Hz B7 D7 E7 F7 M7 Q7 R7 S7

Standardcontrolvoltagesanddesignations(DC)V 12 24 48 60 72 110 125 220

SD BD ED ND SD FD GD MD

MINICONTACTORSK03C, K07C, K07CG (DC), K07CF, K03M, K07M, K07MG (DC), K07MF, K07CX, K0CGX (DC), K07MX, K07MGX (DC)

Page 6: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

5

ContactorsEle

ctric

ale

ndur

ance

(x10

6 op

.c.)

BreakingcurrentIe(A)at230V

Operationfrequency:1200op.c./h

Diagram 1Electricalenduranceofcontactorrelaysandauxiliarycontactsofmotorcontactors

Utilizationcategory:AC-15

Diagram 2Electricalenduranceofmaincontactsofmotorcontactors

Ele

ctric

ale

ndur

ance

(x10

6 op

.c.)

Ratedmotorpower(kW)at400V,50Hz

Operationfrequency:600op.c./h

Utilizationcategory:AC-3

ELECTRICALENDURANCE

CONTACTARRANGEMENTS

MOTORCONTACTORS

TypeArrangementofcontactsandterminal

designation

K03M-01K07M-01K07MG-01K07MF-01K07MX-01K07MGX-01

K03M-10K07M-10K07MG-10K07MF-10K07MX-10K07MGX-10

K03M-10Sp4K07M-10Sp4K07MG-10Sp4

K07M-22Sp4K07MG-22Sp4

K07M-04Sp4K07MG-04Sp4

K07M-01Sp4K07MG-01Sp4

CONTACTORRELAYSType Arrangementofcontactsandterminal

designation

K03C-22K07C-22K07CG-22K07CF-22K07CX-22K07CGX-22

K03C-31K07C-31K07CG-31K07CF-31K07CX-31K07CGX-31

K03C-40K07C-40K07CG-40K07CF-40K07CX-40K07CGX-40

MINICONTACTORSK03C, K07C, K07CG (DC), K07CF, K03M, K07M, K07MG (DC), K07MF, K07CX,

K0CGX (DC), K07MX, K07MGX (DC)

Page 7: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

6

ND2C-02 ND2C-11 ND2C-20 ND2M-02

ND2M-11

ND4C-04 ND4C-13 ND4C-22 ND4C-31

ND4C-40 ND4M-22 ND4M-31 ND4M-13

K03C,K03M K07C,K07M,K07CG,K07MG K07CX,K07CGX,K07MX,K07MGXK07CF,K07MF

DIMENSIONS

ACCESSORIES

ND2 - Two-polesnap-onauxiliaryswitchblocks

ND4 -Four-polesnap-onauxiliaryswitchblocks

MINICONTACTORSK03C, K07C, K07CG (DC), K07CF, K03M, K07M, K07MG (DC), K07MF, K07CX, K0CGX(DC), K07MX, K07MGX(DC)

Page 8: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

7

ACCESSORIESType Version RatedoperationalcurrentIe(A)atAC-15

230V 400V 500V 690V

ND2 -20,-02,-11 6 4 2 1

ND4 -40,-04,-13,-31,-22 6 4 2 1

MOUNTINGPOSITIONSOFACCESSORIES

Whenamechanicalinterlockisused,theminimumtimeof50msisrequiredfromswitchingoffthefirstcontactortoswitchingonthesecondcontactorandviceversa.

MB7 -Mechanicalinterlock

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.Whenorderingsnap-onauxiliaryswitchblocks,onlythetypeisstated.Example:ND2M-22

K07M- 01 -M7

Controlvoltage(seepage4),frequencyVersionofcontactsType

MINICONTACTORSK03C, K07C, K07CG (DC), K07CF, K03M, K07M, K07MG (DC), K07MF, K07CX,

K0CGX (DC), K07MX, K07MGX (DC)

Page 9: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

8

•Athree-polerelayforusewithK07C,K07CG,K07M,K07MG minicontactors•Usedforoverloadprotectionofmotorswithoperational currentsupto14Aandoperationalvoltagesupto690VAC•Electricallyisolatedauxiliarycontacts•ARESETbuttonprovidedwithelementsenablingselection betweenamanualandautomaticmechanismandcontacts resettoinitialposition•Adoubletripleverenablessensitivitytophasefailurein accordancewithIEC/EN60947-4-1•DegreeofprotectionIP20•Ascaleforsettingthemotoroperationalcurrent

Settingrangesandmaximumpermittedback-upfusesSettingrange

(A)

Max.back-upfusegL/gG

Forcoordination“1”:(A)

Max.back-upfusegL/gG

Forcoordination“2”:(A)

0.11-0.16 20 0.5

0.16-0.25 20 1

0.25-0.4 20 2

0.4-0.6 20 2

0.6-0.9 20 4

0.9-1.3 20 4

1.3-1.9 20 6

1.9-2.8 20 6

2.8-4 20 10

4-6 20 10

6-9 20 16

8-11 25 20

11-14 35 25

THERMALOVERLOADRELAYBR6

Page 10: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

9

DIMENSIONS

TECHNICALDATA

GEN

ER

AL

Type BR6

Standards IEC/EN60947-4-1,IEC/EN60947-5-1,UL508

Ambienttemperature open °C -25….+50

closed °C -25…+40

Storagetemperature °C -25…+70

Terminalcapacity solidorstranded

mm2

1x0.75…2x2.5

flexible 1x0.75…2x2.5

flexiblewithendsleeve 1x0.5…2x1.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.0

Weight kg 0.08

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Ratedoperationalvoltage Ue V 690

Ratedfrequency Hz 0…400

Adjustablecurrent A 0.11-14(13ranges)

Overvoltagecategory/pollutioncategory III/3

Tripclassacc.toIEC/EN60947-4-1 10

Powerloss approx.2W/pole

AU

XILI

AR

YC

IRC

UIT

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Ratedoperationalvoltage Ue V 500VAC.220VDC

Overvoltagecategory/pollutiondegree III/3

Thermalcurrent Ith A 6

Ratedoperationalcurrents

makecontact

220/240V

Ie A

0.5

380/415V 0.5

500V 0.3

AC-15break

contact

220/240V 1.5

380/415V 0.7

500V 0.5

Ratedoperationcurrents

bothcontacts

24V

Ie A

0.9

60V 0.75

DC-13 110V 0.4

220V 0.2

BR6THERMALOVERLOADRELAYBR6

Page 11: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

10

Contactorversions: KNL6(-40,-22,-31) KNL9-KNL18(-10,-01,Sp4-01,Sp4-10) KNL9-KNL16(Sp4-22,Sp4-04) KNL22-KNL30(-00)

• Contactorsareusedforswitchingelectricmotorsandotherresistive inductiveandcapacitiveloads•Awidevarietyofsnap-onauxiliaryswitchblocksandaccessories• UniformmarkingofconnectionterminalsinaccordancewithEN50005 andEN50011• Quickassemblytoa35mmwidemountingrailinaccordancewith EN60715orfixingwithscrews• KNL6-KNL18are4-poleandKNL22-KNL30are3-polecontactors• Openandfunnel-shapedconnectionterminals-fastandsimple connection• Plus/minusscrews,protectedagainstfallingout-standardorposidrive screwdriverscanbeused• Highcontactreliabilityatlowvoltages• Possibilityofindividualmarkingonaspecialplate-easyidentificationof acontactorinthecircuit• Auxiliarycontactwithapushbuttonfunction• Uniformcontactorwidth-45mm• Assemblytoverticalorhorizontalsurfacewith±20°deviation• Thirdcoilterminal• Possibilityofdirectconnectionofabimetalrelayforprotectionagainst overloadandincaseofphasefailure• Versionwithallfourmaincontacts(Sp4)(KNL9-KNL18)• DegreeofprotectionIP20• Highelectricalandmechanicalendurance,andhighswitchingcapacity• ExistingversionKNL18St4forutilizationcategoryAC-6b(300uF)

TEHNICALDATA MOTORCONTACTORS

GEN

ER

AL

Type KNL9 KNL12 KNL16 KNL18 KNL22 KNL30

Standards IEC/EN60947-4-1,IEC/EN60947-5-1,UL508

Approvals UL,CSA(exceptforKNL18),GOST

Climaticcategoryconstantdampheatacc.toIEC60068-2-78

cyclicdampheatacc.toIEC60068-2-30

Ambienttemperature open°C

-25…+55

closed -25…+45

Storagetemperature °C -30…+80

Contactreliability 17V;≥50mA

Mechanicalendurance op.c. 107

Max.mechanicaloperatingfrequencywithnoloadc/h 3000

Max.electricaloperatingfrequencyAC-3/AC-4/AC-15/DC-13/DC-1toDC5/AC-6B op.c/h 600/300/1200/1200/300/600

Weight kg 0.3 0.32

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrentat≤40°C Ith A 25 25 25 32 35 35

Ratedfrequency f Hz 50/60

Ratedmotorpower single-phase 230V

Pe kW

1.5 1.5 2.2 2.2 2.2 3.7

three-phase

230V 2.2 3 4 4 5.5 7.5

AC-3 400V 4 5.5 7.5 9 11 15

500V 5.5 5.5 7.5 9 11 15

690V 5.5 7.5 7.5 9 11 15

Ratedoperationalcurrent single-phase 230V

Ie A

12 12 17 17 17 28

AC-3 three-phase

230V 8.7 11.5 14.8 14.8 19.6 26.4

400V 9 12 16 18 22 30

500V 9 9 12.1 14 17.4 23.4

690V 6.5 8.8 8.8 10 12.6 17

Ratedmotorpower

three-phase

230V

Pe kW

0.75 1.1 1.5 1.5 2.2 4

AC-4

400V 1.5 2.2 3 3 4 6.5

500V 1.5 2.2 3 3 4 6.5

690V 1.5 2.2 3 3 4 6.5

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

Page 12: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

11

MAIN

CIR

CU

IT

Type KNL9 KNL12 KNL16 KNL18 KNL22 KNL30

Ratedmotorpowersingle-phase

115V

Pe HP

1 1 1½ 1½ 2 2

accordingtoUL 230V 2 2 3 3 3 5

three-phase

230V 3 3 5 5 7½ 10

460V 5 5 7½ 7½ 15 20

575V 7½ 7½ 10 10 15 20

ElectricalenduranceofcontactsAC-3/AC-4 op.c. diagram2/diagram3

Ratedoperationalcurrentat24/110/220V

DC-1

11)

Ie A

15/6/4 28/7/4

21) 18/12/8 30/23/13

31) 20/15/10 32/25/20

1)Numberofpolesinseries DC-3−DC-5

11) 12/2/0.75 18/2/1

21) 15/8/1.5 23/13/2

31) 18/12/6 28/18/9

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 25 25 35 35 50 50

Terminalcapacityrigid

S mm2 0.75…6 2.5…10

flexible 0.5…6 1.5…10

Screw M3.5 M4

Screwhead PZ2 PZ2

Tighteningtorque Nm 1.4 1.8

AU

XILI

AR

YC

IRC

UIT

Ratedinsulationvoltage Ui V 690 −

Thermalcurrent Ith A 20 −

Ratedoperationalcurrent 230V

Ie A

6 −

400V 4 −

AC-15 500V 2 −

690V 1 −

Ratedoperationalcurrent 24V

Ie A

10 −

60V 4 −

DC-13 110V 0.9 −

220V 0.4 −

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20 −

Terminalcapacityrigid

S mm20.75…6 −

flexible 0.5…6 −

Screw M3.5 −

Screwhead PZ2 −

Tighteningtorque Nm 1.4 −

MAG

NETI

CS

YSTE

M

Coilconsumption

switch-on

Pc

VA 66

W 48

operationVA 8

W 2.5

makeNO

ms

10-20 10-20

NC 15-25 −

Make/Breakdelaybreak

NO 10-15 5-15

NC 8-15 −

Rangeofcontrolvoltage Uc % 85…110

Controlvoltages Uc V 12…600

Terminalcapacityrigid

S mm20.75…4

flexible 0.5…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.4

TECHNICALDATA MOTORCONTACTORS

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

Page 13: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

12

TECHNICALDATA CONTACTORRELAYS

GEN

ER

AL

Type KNL6

Standards IEC/EN60947-5-1,UL508

Approvals UL,CSA,GOST

Climaticclass constantdampheat(IEC60068-2-78)cyclicdampheat(IEC60068-2-30)

Ambienttemperature open°C

-25…+55

closed -25…+40

Storagetemperature °C -30…+80

Mechanicalendurance op.c. 107

Max.mechanicaloperatingfrequencywithnoload op.c./h 3000

Max.electricaloperatingfrequencyAC-15/DC-13 op.c./h 1200/1200

Weight kg 0.3

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 20

Ratedoperationalcurrent 230V

Ie A

6

400V 4

AC-15 500V 2

690V 1

Ratedoperationalcurrent 24V

Ie A

10

60V 4

DC-13 110V 0.9

220V 0.4

ElectricalenduranceofcontactsAC-15 op.c. diagram1

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20

MAG

NETI

CS

YSTE

M

Coilconsumption

switch-on

Pc

VA 66

W 48

operationVA 8

W 2.5

makeNO

ms

10-15

NC 15-20

Make/Breakdelaybreak

NO 10-15

NC 8-15

Ratedcontrolvoltagelimitsforclosing Uc % 85…110

Controlvoltages Uc V 12…600

Terminalcapacityrigid

S mm20.75…4

flexible 0.5…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.4

Standardcontrolvoltagesanddesignations(AC)

V 24 42 48 110/125 220/240 380/415 440 480/520

50/60Hz B7 D7 E7 F7 M7 Q7 R7 S7

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

Page 14: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

13

DIMENSIONS

KNL22,KNL30

DIAGRAM3

Ele

ctric

ale

ndur

ance

(x10

6 op

.c.)

Breakingcurrent(A)

DIAGRAM1

RatedmotorpowerPe (kW)Ele

ctric

ale

ndur

ance

(x10

6op

.c.)

DIAGRAM2

Ele

ctric

ale

ndur

ance

(x10

6 op

.c.)

RatedmotorpowerPe (kW)

ELECTRICALENDURANCE

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

KNL6,KNL9,KNL12,KNL16,KNL18

Page 15: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

14

ACCESSORIES

NDL2-11

NDL1-20 NDL1-11 NDL1-02 NDL1-40 NDL1-31

NDL1-22 NDL1-13 NDL1-04 NDL2-02

NDL2-22 NDL2-31 NDL2-13 NDL2-40 NDL2-04

NDL3-11 NDL3-02 NDL3-22 NDL3-31 NDL3-13

NPL1-10 NPL1-01 NPL2-10 NPL2-01

Type Version RatedoperationalcurrentIe(A)atAC-15

230V 400V 500V 690V

NDL1(forKNL6) -11,-02,-20,-22,-31,-13,-40,-04

6 4 2 1NDL2(forKNL9,KNL12,KNL16,KNL18) -11,-02,-20,-22,-31,-13,-40,-04

NDL3(forKNL22,KNL30) -11,-02,-20,-22,-31,-13,-40,-04

Type Version RatedoperationalcurrentIe(A)atAC-15

230V 400V 500V 690V

NPL1(onlyforKNL9,KNL12,KNL16,KNL18) -10,-016 4 2 1

NPL2(onlyforKNL22,KNL30) -10,-01

NDL2-20 NDL3-20 NDL3-40 NDL3-04

AtallKNL6-KNL30contactorversions,bothsnap-onauxiliaryswitchblockswithKNL+NDL+NPLauxiliarycontactscanbeusedsimultaneously.

NDL1, NDL1, NDL3-Two-andfour-polesnap-onauxiliaryswitchblocks(mountingonabasiccontactor)

NPL1, NPL2-Single-polesnap-onauxiliaryswitchblockforside

mounting+push-button

CONTACTARRANGEMENTS

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

Page 16: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

15

Type RC1 RC2 RC3 RC4

ControlvoltagerangeUc (V) 24…48 48…250 250…380 380…500

ACCESSORIES

RCsuppressor

NTidentificationplate

DZdistancespacerMBLmechanicalinterlock

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

Page 17: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

16

MOUNTINGPOSITIONSOFACCESSORIES

-02-20-11

-02-20-11-20

-11-02

1

-04-40-31-22-13-40

-31-22-13-04

-22-31-13-40-04

BR16, BR30

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.

KNL16-10-M7

Controlvoltage(seepage12),frequencyType

KNLCONTACTORSKNL6, KNL9, KNL12, KNL16, KNL18, KNL22, KNL30

Page 18: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

17

Thermaloverloadrelays

• Athree-poleoverloadrelaysforusewithKNL6toKNL30 andKNL6GtoKNL30Gcontactors• Usedforoverloadprotectionofmotorswithoperational currentsupto16A(BR16)or30A(BR30)andoperational voltagesupto690VAC.• Adjustablecurrentsetting• Ambienttemperaturecompensated• Electricallyisolatedauxiliarycontacts(1×NOand1×NC)• ARESETbuttonprovidesbothmanualandautomatic resetoptions• Adoubletripleverprovidessensitivitytophaselossin accordancewithIEC/EN60947-4-1.• DegreeofprotectionIP20

Settingrangesandmaximumpermittedback-upfuses

TypeSettingrange

(A)Max.back-upfusegL/gG(A)

BR16

0.1-0.16 1

0.16-0.25 1

0.25-0.4 1

0.35-0.5 1

0.45-0.63 1

0.55-0.8 3

0.75-1 3

0.9-1.3 3

1.1-1.6 3

1.4-2 6

1.8-2.5 6

2.3-3.2 6

2.9-4 10

3.5-4.8 10

4.5-6.3 15

5.5-7.5 15

7.2-10 25

9-12.5 30

11.3-16 40

15-20 50

BR30

17.5-21.5 50

21-25 60

24.5-30 70

BR16, BR30

Page 19: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

18

M

A

CONNECTIONDIAGRAM DIMENSIONS

TECHNICALDATA CONTACTORRELAYS

GEN

ER

AL

Type BR16 BR30

Standards IEC/EN60947-4-1,IEC/EN60947-5-1,UL508

Approvals UL

Forusewith KNL6-18,KNL6G-18G KNL22,KNL30

Ambienttemperature open°C

-5…+55

closed -5…+55

Terminalcapacity mm2 1…10(main)0.75…2.5(auxiliary)

Screw mainterminals auxiliaryterminals

M4M3.5

Screwhead PZ2

Tighteningtorque mainterminals auxiliaryterminals

Nm 1.20.8

Dimensions(W×H×D) mm 45×70.5×60 45×69×60

Weight kg 0.115

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Ratedoperationalvoltage Ue V 690

Adjustablecurrent Ir A 0.1…20 17.5…30

Ratedfrequency f Hz 50/60

Overvoltagecategoryandpollutiondegreeacc.toIEC/EN60947-1

III/3

Tripclassacc.toIEC/EN60947-4-1 10

Powerloss P W 5…6.5(dependingonsettingrange)

AU

XIL

IAR

YC

IRC

UIT

S

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Ratedoperationalvoltage Ue Vupto500(AC)upto230(DC)

Overvoltagecategoryandpollutiondegreeacc.toIEC/EN60947-1

III/3

Thermalcurrent(bothcontacts) Ith A 6

Ratedoperationalcurrents(bothcontacts) 230VAC-15 400V 500V

Ie A321

Ratedoperationalcurrents(bothcontacts) 60VDC-13 110V 230V

Ie A0.450.250.10

BR16 BR30

ThermaloverloadrelaysBR16, BR30

Page 20: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

19

• KNLGcontactorsareusedforDCcontrolvoltages• KNL6Gcontactorrelaysaremainlyusedforswitchingcontrol andsignalcircuits,andKNL9G-KNL30Gmotorcontactors areusedforswitchingmotorsandotherresistive,inductive andcapacitiveconsumers• Assemblytoa35mmwidemountingrailinaccordancewith EN60715orfixingwithscrews• Assemblytoverticalorhorizontalsurfacewith±20°deviation• DegreeofprotectionIP20

KNLCONTACTORSKNL6G, KNL9G, KNL12G, KNL16G, KNL18G, KNL22G, KNL30G

TECHNICALDATA

GEN

ER

AL

Type KNL6G KNL9G KNL12G KNL16G KNL18G KNL22G KNL30G

Standards IEC/EN60947-4-1,IEC/EN60947-5-1,UL508

Approvals GOST

Climaticcategory constantdampheatacc.toIEC60068-2-78cyclicdampheatacc.toIEC60068-2-30

Ambienttemperature open°C

-25…+60

closed -25…+40

Storagetemperature °C -30…+80

Contactreliability 17V;≥50mA

Mechanicalendurance op.c. 5x106

Max.mechanicaloperatingfrequencywithnoload op.c/h 3000

Max.electricaloperatingfrequencyAC-3/AC-4/AC-15/DC-13/DC-1toDC-5

op.c/h 600/300/1200/1200/300

Weight NPLG/NDLG kg 0.335/0.385 0.36/0.41

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 20 25 25 25 32 35 35

Ratedfrequency f Hz 50/60

Ratedmotorpower single-phase 230V

Pe kW

− 1.5 1.5 2.2 2.2 2.2 3.7

three-phase

230V − 2.2 3 4 4 5.5 7.5

AC-3 400V − 4 5.5 7.5 9 11 15

500V − 5.5 5.5 7.5 9 11 15

690V − 5.5 7.5 7.5 9 11 15

Ratedoperationalcurrent single-phase 230V

Ie A

− 12 12 17 17 17 28

AC-3 three-phase

230V − 8.7 11.5 14.8 14.8 19.6 26.4

400V − 9 12 16 18 22 30

500V − 9 9 12.1 14 17.4 23.4

690V − 6.5 8.8 8.8 10 12.6 17

Ratedmotorpower

three-phase

230V

Pe kW

− 0.75 1.1 1.5 1.5 2.2 4

400V − 1.5 2.2 3 3 4 6.5

AC-4 500V − 1.5 2.2 3 3 4 6.5

690V − 1.5 2.2 3 3 4 6.5

Ratedmotorpoweracc.toUL single-phase115V

Pe HP

− 1 1 1½ 1½ 2 2

230V − 2 2 3 3 3 5

three-phase

230V − 3 3 5 5 7½ 10

460V − 5 5 7½ 7½ 15 20

575V − 7½ 7½ 10 10 15 20

Page 21: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

20

MAIN

CIR

CU

IT

Type KNL6G KNL9G KNL12G KNL16G KNL18G KNL22G KNL30G

ElectricalenduranceofcontactsAC-3/AC-4 op.c.diagram1(AC-15)

diagram2/diagram3

Ratedoperationalcurrentat:24/110/220V DC-1

11)

Ie A

− 15/6/4 28/7/4

21) − 18/12/8 30/23/13

31) − 20/15/10 32/25/20

1)Numberofpolesinseries DC-3−DC-5

11) − 12/2/0.75 18/2/1

21) − 15/8/1.5 23/13/2

31) − 18/12/6 28/18/9

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20 25 25 25 35 50 50

Terminalcapacityrigid

S mm2 0.75…6 2.5…10

flexible 0.5…6 1.5…10

Screw M3.5 M4

Screwhead PZ2 PZ2

Tighteningtorque Nm 1.4 1.8

AU

XILI

AR

YC

IRC

UIT

Ratedinsulationvoltage Ui V 690 −

Thermalcurrent Ith A 20 −

Ratedoperationalcurrent 230V

Ie A

6 −

400V 4 −

AC-15 500V 2 −

690V 1 −

Ratedoperationalcurrent 24V

Ie A

10 −

60V 4 −

DC-13 110V 0.9 −

220V 0.4 −

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20 −

Terminalcapacityrigid

S mm2 0.75…6 −

flexible 0.5…6 −

Screw M3.5 −

Screwhead PZ2 −

Tighteningtorque Nm 1.4 −

MAG

NETI

CS

YSTE

M

Coilconsumptionswitch-on

Pc W110

operation 3

Make/Breakdelay

makeNO

ms

15-20 15-20

NC 10-20 −

breakNO 5-10 5-10

NC 10-15 −

Rangeofcontrolvoltage Uc % 85…110

Controlvoltage Uc V 12…240

Terminalcapacityrigid

S mm2 0.75…4

flexible 0.5…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 1.4

Volts 12 24 48 60 72 110 125 220 240

JD BD ED ND SD FD GD MD MUD

Standardcontrolvoltagesanddesignations(DC)

TECHNICALDATA MOTORCONTACTORS

KNLGCONTACTORSKNL6G, KNL9G, KNL12G, KNL16G, KNLG18G, KNL22G, KNL30G

Page 22: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

21

A1

A1

A1

A1

A1

A1

A1

A1A1

A1

A1

A1

A1

A1

A1

A1

CONTACTARRANGEMENTS

Ele

ctric

ale

ndur

ance

(x10

6 op

.c.)

RatedmotorpowerPe (kW)AC4-400V

DIAGRAM3

Breakingcurrent(A)

DIAGRAM1

AC-15-230V

Ele

ctric

ale

ndur

ance

(x10

6 op

.c.)

DIAGRAM2

RatedmotorpowerPe (kW)AC-3-400VEle

ctric

ale

ndur

ance

(x10

6 op

.c.)

ELECTRICALENDURANCE

KNLGCONTACTORSKNL6G, KNL9G, KNL12G, KNL16G, KNL18G, KNL22G, KNL30G

Page 23: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

22

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

A1

(KNL6G-KNL18G)+NDLG KNL22G+NDLG,KNL30G+NDLG

(KNL6G-KNL18G)+NPLG KNL22G+NPLG,KNL30G+NPLG

DIMENSIONS

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.

CONTACTARRANGEMENTS

*ContactorsincombinationwithNDLGcanhavethefollowingversionsofauxiliarycontacts:21,-12,-03,-30,-10,-01-21.-12.-03,-30,-10,-01

SimultaneousapplicationofNDLG+NPLandNDL+NPLGsnap-onauxiliaryswitchblocksisavailable.

KNL16G-10/21 - BD

Controlvoltage(seepage20)NDLGsnap-onauxiliaryswitchblockType

KNLG + NDLG KNLG + NPLG

KNL16G-10 - BD

Controlvoltage(seepage20)

Type

KNLGCONTACTORSKNL6G, KNL9G, KNL12G, KNL16G, KNLG18G, KNL22G, KNL30G

Page 24: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

23

TECHNICALDATA MOTORCONTACTORS

GEN

ER

AL

Type KNL43 KNL63

Standards IEC/EN60947-4-1,IEC/EN60947-5-1,IEC/EN60947-1,UL508

Approvals UL,CSA,GOST

Ambienttemperature open°C

-20…+60

closed -20…+45

Storagetemperature °C -30…+80

Powerdissipationperpole W 5 6

Mechanicalendurance op.c. 3x106

Max.mechanicaloperatingfrequencywithnoload c./h 3000

Max.electricaloperatingfrequencyAC-3/AC-4/AC-15/DC-13 c./h 600/300/1200/1200

Weight kg 0,93

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 75 85

Ratedfrequency f Hz 50/60

Ratedmotorpower three-phase 230V

Pe kW

12,5 15

400V 22 30

AC-3 690V 30 40

Ratedoperationalcurrent three-phase 230V

Ie A

45 63

400V 45 63

AC-3 690V 33 45

Ratedoperationalcurrent three-phase 400VPe kW

15 22

AC-4 690V 18,5 25

ElectricalenduranceAC-3/AC-4 op.c. diagram1/diagram2

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 80 125

Terminalcapacityrigid

S mm235

flexible 25

Screw M6

Screwhead PZ2

Tighteningtorque Nm 4

AU

XILI

AR

Y

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrent Ith A 16

Ratedoperationalcurrent 230V

Ie A

6

400V 4

AC-15 500V 2

690V 1

• KNL43/63contactorsaremainlyusedforswitchingelectric motors• PossibilityofdirectconnectionoftheBR63bimetalrelayfor protectionagainstoverloadandincaseofphasefailure• Quickassemblytoa35mmwidemountingrailinaccordancewith EN60715• PossibilityofmountingtheNDL4snap-onauxiliaryswitchblock withfourauxiliarycontacts• Uniformmarkingofconnectionterminalsinaccordancewith EN50005andEN50011• UseoftheMBL43mechanicalinterlock• DegreeofprotectionIP20

KNLCONTACTORSKNL43, KNL63

Page 25: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

24

DIMENSIONS

elec

tric

ale

ndur

ance

(x10

6 op

.c.)

Pe(kW)

Scha

ltstü

ckle

bens

daue

r (x1

06 Sc

halts

p.)

elec

tric

ale

ndur

ance

(x10

6 op

.c.)

TECHNICALDATA MOTORCONTACTORS

AU

XILI

AR

YC

IRC

UIT

Type KNL43 KNL63

Ratedoperationalcurrent 24V

Ie A

4

DC-13 110V 0.25

220V 0.1

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 10

Terminalcapacityrigid

S mm21…2.5

flexible 1…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 0.8

MAG

NETI

CS

YSTE

M

Coilconsumption

switch-on

Pc

VA 130

W 80

operationVA 10

W 3

Make/brakedelays makems

10-20

brake 8-15

Rangeofcontrolvoltage Uc % 85…110

Controlvoltage Uc V 12…500

Terminalcapacityrigid

S mm21…2.5

flexible 1…2.5

Screw M3.5

Screwhead PZ2

Tighteningtorque Nm 0.8

V 24 42 48 220/240 380/415

50/60Hz B7 D7 E7 M7 Q7

STANDARDCONTROLVOLTAGESANDDESIGNATIONS(AC)

KNLCONTACTORSKNL43, KNL63

Pe(kW)

AC-4AC-3

Page 26: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

25

NDL4Two-andfour-polesnap-onauxiliary

switchblocks(mountingonabasiccontactor)

MBL43 Mechanicalinterlock

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.

KNL43/63-11-M7-50/60

NDL4-11 NDL4-02 NDL4-22 NDL4-31 NDL4-13

NDL4-40 NDL4-04 NDL4-20

Type Version RatedoperationalcurrentIe(A)atAC-15

230V 400V 500V 690V

NDL4 -11,-02,-20,-22,-31,-13,-40,-04 6 4 2 1

ACCESSORIES

FrequencyControlvoltage(seepage24)VersionofcontactsType

KNLCONTACTORSKNL43, KNL63

Page 27: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

26

DIMENSIONS

BR63thermaloverloadrelay

• Athree-polethermaloverloadrelayforusewithKNL43/63 contactors• Usedforoverloadprotectionofmotorswithoperational currentsupto97Aandoperationalvoltagesupto690VAC• Adjustablecurrentsetting• Ambienttemperaturecompensated• Electricallyisolatedauxiliarycontacts(1×NO,1×NC)• ARESETbuttonprovidesbothmanualandautomaticreset options• Adoubletripleverprovidessensitivitytophaselossin accordancewithIEC/EN60947-4-1.• DegreeofprotectionIP20

Settingrangesandmaximumpermittedback-upfuses

TypeSettingrange

(A)Max.back-upfusegL/gG(A)

BR63

17-25 100

24.5-36 100

35-47 125

45-60 150

58-75 200

72-90 250

77-97 250

BR63

94

53 4

85.5

4T2 2T1 6T3

85.5

97.5

56

13.522

21 21

30

BR63

Page 28: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

27

TECHNICALDATA CONTACTORRELAYS

GEN

ER

AL

Type BR63

Standards IEC/EN60947-4-1,IEC/EN60947-5-1,UL508

Approvals UL

Forusewith KNL43/63

Ambienttemperature open°C

-5…+55

closed -5…+55

Terminalcapacity mm2 6…35(main),0.75…2.5(auxiliary)

Screw mainterminals auxiliaryterminals

M5M3.5

Screwhead mainterminals auxiliaryterminals

PZ2

Tighteningtorque mainterminals auxiliaryterminals

Nm 2.50.8

Dimensions(W×H×D) mm 56x85.5x97.5

Weight kg 0.350

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Ratedoperationalvoltage Ue V 690

Adjustablecurrent Ir A 17…97

Ratedfrequency f Hz 50/60

Overvoltagecategoryandpollutiondegreeacc.toIEC/EN60947-1

III/3

Tripclassacc.toIEC/EN60947-4-1 10

PowerlossatIn P W 11…15.5(dependingonsettingrange)

AU

XIL

IAR

YC

IRC

UIT

S

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Ratedoperationalvoltage Ue Vupto600(AC)upto250(DC)

Overvoltagecategoryandpollutiondegreeacc.toIEC/EN60947-1

III/3

Thermalcurrent(bothcontacts) Ith A 10

Ratedoperationalcurrents(bothcontacts) 120V 240V 380VAC-15 480V 500V 600V

Ie A

63

1.91.51.41.2

Ratedoperationalcurrents(bothcontacts)DC-13 125V 250V

Ie A 0.550.27

CONNECTIONDIAGRAM

BR63thermaloverloadrelay

Page 29: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

28

LampsforKNL

SwitchingofLampsType

P[W] C[μF] I[A]Max.numberoflampsperpoleat230V50Hz

KNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

Incandescentlampsandtungsten

halogenlamps

15 - 0.07 90 120 160 180 360 470 560 800

25 - 0.11 55 73 100 110 220 280 340 480

40 - 0.18 35 47 62 70 130 170 210 300

60 - 0.26 23 31 41 46 92 118 140 200

75 - 0.33 19 25 33 37 73 94 110 160

100 - 0.44 14 19 25 28 55 71 85 120

150 - 0.65 9 12 16 18 36 47 56 80

200 - 0.87 7 9 12 14 27 35 42 60

300 - 1.30 5 6 8 9 18 23 28 40

500 - 2.17 2 3 4 5 10 13 17 24

1000 - 4.35 1 1 2 2 5 6 8 12

Energysavinglamps

3 - 0.030 33 43 58 65 150 200 650 1100

5 - 0.040 30 40 53 60 135 180 500 900

7 - 0.055 28 37 49 55 120 160 380 700

8 - 0.065 25 33 44 50 110 150 320 600

9 - 0.075 23 30 40 45 100 140 280 530

10 - 0.080 23 30 40 45 100 140 260 500

11 - 0.090 23 30 40 45 100 140 240 440

12 - 0.100 20 27 35 40 95 120 210 400

14 - 0.110 20 27 35 40 90 120 200 360

15 - 0.120 18 23 30 35 85 115 180 330

16 - 0.130 18 23 30 35 80 105 165 300

18 - 0.145 15 20 26 30 70 95 150 270

20 - 0.160 14 18 24 27 65 85 135 245

21 - 0.170 13 17 22 25 60 80 125 230

23 - 0.185 13 17 22 25 60 70 115 210

24 - 0.195 13 17 22 25 55 70 110 200

30 - 0.160 13 17 22 25 55 70 110 200

Compactfluorescentlamps-

seriescorrection

10 1.4 0.19 33 43 58 65 105 165 200 280

13 1.4 0.18 33 43 58 65 105 165 200 280

18 1.7 0.23 28 37 49 55 85 135 165 230

26 2.5 0.33 19 25 34 38 60 95 115 160

18 2.7 0.38 16 21 28 32 50 80 100 140

24 2.7 0.35 16 21 28 32 50 80 100 140

36 3.4 0.44 14 18 24 27 45 70 85 120

Compactfluorescentlamps-

parallelcorrection

5 2.2 0.18 23 30 40 45 100 150 270 380

7 2.1 0.18 24 31 42 47 104 157 285 400

9 2,0 0.17 25 33 44 50 110 165 300 420

10 2.2 0.19 23 30 40 45 100 150 270 380

11 1.7 0.16 28 37 49 55 125 194 350 490

13 1.8 0.18 28 37 49 55 120 183 330 460

18 2.3 0.23 22 29 38 43 95 143 260 360

26 3.3 0.33 15 20 27 30 66 100 180 250

18 4.2 0.38 11 15 20 23 52 78 140 200

24 3.6 0.35 13 18 24 27 61 91 160 230

36 4.4 0.44 11 15 19 22 50 75 130 190

Compactfluorescentlampswith

electroniccontrolgear(ECG)

5 - 0.05 35 47 62 70 180 250 400 700

7 - 0.05 35 47 62 70 180 250 400 700

9 - 0.07 25 33 45 50 128 180 300 500

10 - 0.07 25 33 45 50 128 180 300 500

11 - 0.07 25 33 45 50 128 180 300 500

Page 30: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

29

LampsforKNL

SwitchingofLampsType

P[W] C[μF] I[A]Max.numberoflampsperpoleat230V50Hz

KNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

Incandescentlampsandtungsten

halogenlamps

15 - 0.07 90 120 160 180 360 470 560 800

25 - 0.11 55 73 100 110 220 280 340 480

40 - 0.18 35 47 62 70 130 170 210 300

60 - 0.26 23 31 41 46 92 118 140 200

75 - 0.33 19 25 33 37 73 94 110 160

100 - 0.44 14 19 25 28 55 71 85 120

150 - 0.65 9 12 16 18 36 47 56 80

200 - 0.87 7 9 12 14 27 35 42 60

300 - 1.30 5 6 8 9 18 23 28 40

500 - 2.17 2 3 4 5 10 13 17 24

1000 - 4.35 1 1 2 2 5 6 8 12

Energysavinglamps

3 - 0.030 33 43 58 65 150 200 650 1100

5 - 0.040 30 40 53 60 135 180 500 900

7 - 0.055 28 37 49 55 120 160 380 700

8 - 0.065 25 33 44 50 110 150 320 600

9 - 0.075 23 30 40 45 100 140 280 530

10 - 0.080 23 30 40 45 100 140 260 500

11 - 0.090 23 30 40 45 100 140 240 440

12 - 0.100 20 27 35 40 95 120 210 400

14 - 0.110 20 27 35 40 90 120 200 360

15 - 0.120 18 23 30 35 85 115 180 330

16 - 0.130 18 23 30 35 80 105 165 300

18 - 0.145 15 20 26 30 70 95 150 270

20 - 0.160 14 18 24 27 65 85 135 245

21 - 0.170 13 17 22 25 60 80 125 230

23 - 0.185 13 17 22 25 60 70 115 210

24 - 0.195 13 17 22 25 55 70 110 200

30 - 0.160 13 17 22 25 55 70 110 200

Compactfluorescentlamps-

seriescorrection

10 1.4 0.19 33 43 58 65 105 165 200 280

13 1.4 0.18 33 43 58 65 105 165 200 280

18 1.7 0.23 28 37 49 55 85 135 165 230

26 2.5 0.33 19 25 34 38 60 95 115 160

18 2.7 0.38 16 21 28 32 50 80 100 140

24 2.7 0.35 16 21 28 32 50 80 100 140

36 3.4 0.44 14 18 24 27 45 70 85 120

Compactfluorescentlamps-

parallelcorrection

5 2.2 0.18 23 30 40 45 100 150 270 380

7 2.1 0.18 24 31 42 47 104 157 285 400

9 2,0 0.17 25 33 44 50 110 165 300 420

10 2.2 0.19 23 30 40 45 100 150 270 380

11 1.7 0.16 28 37 49 55 125 194 350 490

13 1.8 0.18 28 37 49 55 120 183 330 460

18 2.3 0.23 22 29 38 43 95 143 260 360

26 3.3 0.33 15 20 27 30 66 100 180 250

18 4.2 0.38 11 15 20 23 52 78 140 200

24 3.6 0.35 13 18 24 27 61 91 160 230

36 4.4 0.44 11 15 19 22 50 75 130 190

Compactfluorescentlampswith

electroniccontrolgear(ECG)

5 - 0.05 35 47 62 70 180 250 400 700

7 - 0.05 35 47 62 70 180 250 400 700

9 - 0.07 25 33 45 50 128 180 300 500

10 - 0.07 25 33 45 50 128 180 300 500

11 - 0.07 25 33 45 50 128 180 300 500

Page 31: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

30

LampsforKNL

SwitchingofLampsType

P[W] C[μF] I[A]Max.numberoflampsperpoleat230V50Hz

KNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

Compactfluorescentlampswith

electroniccontrolgear(ECG)

13 - 0.07 25 33 45 50 128 180 300 500

18 - 0.22 10 13 17 20 40 57 95 180

24 - 0.22 10 13 17 20 40 57 95 180

26 - 0.22 10 13 17 20 40 57 95 180

32 - 0.22 10 13 17 20 40 57 95 180

36 - 0.22 10 13 17 20 40 57 95 180

40 - 0.22 10 13 17 20 40 57 95 180

42 - 0.22 10 13 17 20 40 57 95 180

55 - 0.28 8 11 14 16 32 45 75 140

57 - 0.28 8 11 14 16 32 45 75 140

70 - 0.35 7 10 13 15 25 36 55 110

80 - 0.41 6 8 11 13 22 30 50 95

120 - 0.58 5 6 8 10 15 22 35 65

2x9 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x10 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x11 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x13 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x18 - 0.30 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x24 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x26 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x32 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x36 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x40 - 0.40 2x4 2x5 2x6 2x7 2x18 2x26 2x45 2x85

2x42 - 0.40 2x4 2x5 2x6 2x7 2x18 2x26 2x45 2x85

2x55 - 0.55 2x3 2x4 2x5 2x6 2x16 2x22 2x37 2x70

2x57 - 0.55 2x3 2x4 2x5 2x6 2x16 2x22 2x37 2x70

Fluorescentlamps-uncorrected

orseriescorrection

11 1.3 0.16 43 65 75 85 150 200 240 340

18 2.7 0.37 22 26 34 42 74 90 110 145

24 2.5 0.35 20 24 32 40 70 85 100 140

36 3.4 0.43 17 21 28 34 59 79 85 125

58 5.3 0.67 11 14 17 21 37 50 60 80

65 5.3 0.67 11 14 17 21 37 50 60 80

85 5.3 0.80 9 12 15 17 31 42 50 65

Fluorescentlamps-lead-lag

circuit

2x11 - 0.07 2x50 2x64 2x80 2x100 2x170 2x240 2x280 2x400

2x18 - 0.11 2x30 2x36 2x46 2x58 2x102 2x135 2x180 2x250

2x24 - 0.14 2x28 2x35 2x45 2x57 2x100 2x120 2x140 2x200

2x36 - 0.22 2x17 2x20 2x25 2x32 2x56 2x75 2x100 2x125

2x58 - 0.35 2x10 2x12 2x16 2x21 2x37 2x45 2x60 2x80

2x65 - 0.35 2x9 2x11 2x15 2x20 2x35 2x43 2x60 2x80

2x85 - 0.47 2x6 2x9 2x12 2x15 2x26 2x35 2x50 2x60

Fluorescentlamps-parallel

correction

11 3.5 0.16 25 33 45 50 79 120 170 240

18 4.5 0.37 20 27 35 40 62 90 130 180

24 4.5 0.35 20 27 35 40 62 90 130 180

36 4.5 0.43 20 27 35 40 62 90 130 180

58 7.0 0.67 13 17 22 25 40 60 85 120

65 7.0 0.67 13 17 22 25 40 60 85 120

85 8.0 0.80 11 15 20 22 34 52 75 100

Fluorescentlampswithelectronic

controlgear(ECG)

18 - 0.09 55 60 70 80 160 220 270 450

36 - 0.16 31 34 40 44 88 122 150 250

58 - 0.25 20 22 26 29 59 82 100 160

2x18 - 0.17 2x31 2x34 2x40 2x44 2x88 2x122 2x135 2x225

2x36 - 0.32 2x15 2x17 2x20 2x22 2x45 2x62 2x75 2x125

2x58 - 0.49 2x10 2x11 2x13 2x15 2x30 2x42 2x50 2x80

Page 32: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

31

LampsforKNL

SwitchingofLampsType

P[W] C[μF] I[A]Max.numberoflampsperpoleat230V50Hz

KNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

Compactfluorescentlampswith

electroniccontrolgear(ECG)

13 - 0.07 25 33 45 50 128 180 300 500

18 - 0.22 10 13 17 20 40 57 95 180

24 - 0.22 10 13 17 20 40 57 95 180

26 - 0.22 10 13 17 20 40 57 95 180

32 - 0.22 10 13 17 20 40 57 95 180

36 - 0.22 10 13 17 20 40 57 95 180

40 - 0.22 10 13 17 20 40 57 95 180

42 - 0.22 10 13 17 20 40 57 95 180

55 - 0.28 8 11 14 16 32 45 75 140

57 - 0.28 8 11 14 16 32 45 75 140

70 - 0.35 7 10 13 15 25 36 55 110

80 - 0.41 6 8 11 13 22 30 50 95

120 - 0.58 5 6 8 10 15 22 35 65

2x9 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x10 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x11 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x13 - 0.11 2x12 2x16 2x22 2x25 2x90 2x125 2x150 2x250

2x18 - 0.30 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x24 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x26 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x32 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x36 - 0.31 2x5 2x6 2x7 2x8 2x20 2x28 2x47 2x90

2x40 - 0.40 2x4 2x5 2x6 2x7 2x18 2x26 2x45 2x85

2x42 - 0.40 2x4 2x5 2x6 2x7 2x18 2x26 2x45 2x85

2x55 - 0.55 2x3 2x4 2x5 2x6 2x16 2x22 2x37 2x70

2x57 - 0.55 2x3 2x4 2x5 2x6 2x16 2x22 2x37 2x70

Fluorescentlamps-uncorrected

orseriescorrection

11 1.3 0.16 43 65 75 85 150 200 240 340

18 2.7 0.37 22 26 34 42 74 90 110 145

24 2.5 0.35 20 24 32 40 70 85 100 140

36 3.4 0.43 17 21 28 34 59 79 85 125

58 5.3 0.67 11 14 17 21 37 50 60 80

65 5.3 0.67 11 14 17 21 37 50 60 80

85 5.3 0.80 9 12 15 17 31 42 50 65

Fluorescentlamps-lead-lag

circuit

2x11 - 0.07 2x50 2x64 2x80 2x100 2x170 2x240 2x280 2x400

2x18 - 0.11 2x30 2x36 2x46 2x58 2x102 2x135 2x180 2x250

2x24 - 0.14 2x28 2x35 2x45 2x57 2x100 2x120 2x140 2x200

2x36 - 0.22 2x17 2x20 2x25 2x32 2x56 2x75 2x100 2x125

2x58 - 0.35 2x10 2x12 2x16 2x21 2x37 2x45 2x60 2x80

2x65 - 0.35 2x9 2x11 2x15 2x20 2x35 2x43 2x60 2x80

2x85 - 0.47 2x6 2x9 2x12 2x15 2x26 2x35 2x50 2x60

Fluorescentlamps-parallel

correction

11 3.5 0.16 25 33 45 50 79 120 170 240

18 4.5 0.37 20 27 35 40 62 90 130 180

24 4.5 0.35 20 27 35 40 62 90 130 180

36 4.5 0.43 20 27 35 40 62 90 130 180

58 7.0 0.67 13 17 22 25 40 60 85 120

65 7.0 0.67 13 17 22 25 40 60 85 120

85 8.0 0.80 11 15 20 22 34 52 75 100

Fluorescentlampswithelectronic

controlgear(ECG)

18 - 0.09 55 60 70 80 160 220 270 450

36 - 0.16 31 34 40 44 88 122 150 250

58 - 0.25 20 22 26 29 59 82 100 160

2x18 - 0.17 2x31 2x34 2x40 2x44 2x88 2x122 2x135 2x225

2x36 - 0.32 2x15 2x17 2x20 2x22 2x45 2x62 2x75 2x125

2x58 - 0.49 2x10 2x11 2x13 2x15 2x30 2x42 2x50 2x80

Page 33: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

32

LampsforKNL

SwitchingofLamps

TypeP[W] C[μF] I[A]

Max.numberoflampsperpoleat230V50HzKNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

FluorescentlampsT5with

electroniccontrolgear(ECG)

FC22 - 0.11 30 40 53 60 90 100 145 23040 - 0.21 15 20 25 30 45 55 75 12055 - 0.28 10 13 18 20 35 40 60 90

HE

14 - 0.08 40 53 70 80 120 150 200 31021 - 0.11 30 40 53 60 90 100 145 23028 - 0.14 25 33 44 50 70 80 110 18035 - 0.18 18 23 30 35 50 60 85 140

HO

24 - 0.12 28 38 50 55 70 100 130 20039 - 0.20 18 23 30 35 40 60 80 12549 - 0.24 14 19 24 28 35 50 65 10054 - 0.27 13 17 22 25 30 45 60 9080 - 0.39 9 11 15 17 20 30 40 65

2xFC2x22 - 0.23 2x15 2x20 2x26 2x30 2x45 2x50 2x72 2x1152x40 - 0.42 2x7 2x10 2x12 2x15 2x22 2x27 2x37 2x602x55 - 0.55 2x5 2x6 2x9 2x10 2x17 2x20 2x30 2x45

2xHE

2x14 - 0.15 2x20 2x26 2x35 2x40 2x60 2x75 2x100 2x1552x21 - 0.22 2x15 2x20 2x26 2x30 2x45 2x50 2x72 2x1152x28 - 0.28 2x12 2x16 2x22 2x25 2x35 2x40 2x55 2x902x35 - 0.36 2x9 2x11 2x15 2x17 2x25 2x30 2x42 2x70

2xHO

2x24 - 0.24 2x14 2x19 2x25 2x27 2x35 2x50 2x65 2x1002x39 - 0.39 2x9 2x11 2x15 2x17 2x20 2x30 2x40 2x622x49 - 0.48 2x7 2x9 2x12 2x14 2x17 2x25 2x32 2x502x54 - 0.54 2x6 2x8 2x11 2x12 2x15 2x22 2x30 2x452x80 - 0.74 2x4 2x5 2x7 2x8 2x10 2x15 2x20 2x32

High-pressuremercury-vapour

lamps-uncorrected

50 - 0.61 8 11 14 16 26 36 43 7280 - 0.80 6 8 10 12 20 27 33 55125 - 1.15 4 5 6 8 13 18 23 38250 - 2.15 2 2 3 4 7 10 12 20400 - 3.25 1 1 2 3 5 6 8 13700 - 5.40 - 1 1 1 3 4 5 81000 - 7.50 - - 1 1 2 2 3 5

High-pressuremercury-vapour

lamps-parallelcorrection

50 7 0.28 12 17 22 25 40 60 85 12080 8 0.41 11 15 20 22 35 52 75 105125 10 0.65 7 9 12 14 22 31 60 80250 18 1.22 4 5 6 7 12 16 30 40400 25 1.95 2 2 3 4 7 10 20 30700 45 3.45 1 1 2 2 4 6 10 151000 60 4.80 - 1 1 1 3 4 7 10

Metalhalidelamps-uncorrected

35 - 0.53 14 18 25 28 50 66 47 8070 - 1.00 8 11 14 16 28 40 25 45150 - 1.80 4 5 7 8 14 20 13 25250 - 3.00 2 2 3 3 5 7 9 15400 - 3.50 1 1 2 2 4 6 8 121000 - 9.50 - 1 1 1 1 2 3 42000 - 16.50 - - - - - 1 2 2

Metalhalidelamps-parallel

correction

35 6 0.25 16 21 26 33 60 65 100 14070 12 0.45 8 10 13 20 36 40 50 70150 20 0.75 5 6 8 9 17 18 25 40250 33 1.50 2 3 4 5 7 8 16 22400 35 2.50 1 2 3 4 5 6 15 201000 95 5.80 - 1 1 1 1 2 4 72000 148 11.50 - - - - - 1 2 3

Metalhalidelampswithelectronic

controlgear(PCI)

20 - 0.10 8 12 14 15 20 22 28 3535 - 0.20 5 7 8 9 13 15 20 2670 - 0.36 4 6 7 8 12 14 18 22

Page 34: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

33

LampsforKNL

SwitchingofLamps

TypeP[W] C[μF] I[A]

Max.numberoflampsperpoleat230V50HzKNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

FluorescentlampsT5with

electroniccontrolgear(ECG)

FC22 - 0.11 30 40 53 60 90 100 145 23040 - 0.21 15 20 25 30 45 55 75 12055 - 0.28 10 13 18 20 35 40 60 90

HE

14 - 0.08 40 53 70 80 120 150 200 31021 - 0.11 30 40 53 60 90 100 145 23028 - 0.14 25 33 44 50 70 80 110 18035 - 0.18 18 23 30 35 50 60 85 140

HO

24 - 0.12 28 38 50 55 70 100 130 20039 - 0.20 18 23 30 35 40 60 80 12549 - 0.24 14 19 24 28 35 50 65 10054 - 0.27 13 17 22 25 30 45 60 9080 - 0.39 9 11 15 17 20 30 40 65

2xFC2x22 - 0.23 2x15 2x20 2x26 2x30 2x45 2x50 2x72 2x1152x40 - 0.42 2x7 2x10 2x12 2x15 2x22 2x27 2x37 2x602x55 - 0.55 2x5 2x6 2x9 2x10 2x17 2x20 2x30 2x45

2xHE

2x14 - 0.15 2x20 2x26 2x35 2x40 2x60 2x75 2x100 2x1552x21 - 0.22 2x15 2x20 2x26 2x30 2x45 2x50 2x72 2x1152x28 - 0.28 2x12 2x16 2x22 2x25 2x35 2x40 2x55 2x902x35 - 0.36 2x9 2x11 2x15 2x17 2x25 2x30 2x42 2x70

2xHO

2x24 - 0.24 2x14 2x19 2x25 2x27 2x35 2x50 2x65 2x1002x39 - 0.39 2x9 2x11 2x15 2x17 2x20 2x30 2x40 2x622x49 - 0.48 2x7 2x9 2x12 2x14 2x17 2x25 2x32 2x502x54 - 0.54 2x6 2x8 2x11 2x12 2x15 2x22 2x30 2x452x80 - 0.74 2x4 2x5 2x7 2x8 2x10 2x15 2x20 2x32

High-pressuremercury-vapour

lamps-uncorrected

50 - 0.61 8 11 14 16 26 36 43 7280 - 0.80 6 8 10 12 20 27 33 55125 - 1.15 4 5 6 8 13 18 23 38250 - 2.15 2 2 3 4 7 10 12 20400 - 3.25 1 1 2 3 5 6 8 13700 - 5.40 - 1 1 1 3 4 5 81000 - 7.50 - - 1 1 2 2 3 5

High-pressuremercury-vapour

lamps-parallelcorrection

50 7 0.28 12 17 22 25 40 60 85 12080 8 0.41 11 15 20 22 35 52 75 105125 10 0.65 7 9 12 14 22 31 60 80250 18 1.22 4 5 6 7 12 16 30 40400 25 1.95 2 2 3 4 7 10 20 30700 45 3.45 1 1 2 2 4 6 10 151000 60 4.80 - 1 1 1 3 4 7 10

Metalhalidelamps-uncorrected

35 - 0.53 14 18 25 28 50 66 47 8070 - 1.00 8 11 14 16 28 40 25 45150 - 1.80 4 5 7 8 14 20 13 25250 - 3.00 2 2 3 3 5 7 9 15400 - 3.50 1 1 2 2 4 6 8 121000 - 9.50 - 1 1 1 1 2 3 42000 - 16.50 - - - - - 1 2 2

Metalhalidelamps-parallel

correction

35 6 0.25 16 21 26 33 60 65 100 14070 12 0.45 8 10 13 20 36 40 50 70150 20 0.75 5 6 8 9 17 18 25 40250 33 1.50 2 3 4 5 7 8 16 22400 35 2.50 1 2 3 4 5 6 15 201000 95 5.80 - 1 1 1 1 2 4 72000 148 11.50 - - - - - 1 2 3

Metalhalidelampswithelectronic

controlgear(PCI)

20 - 0.10 8 12 14 15 20 22 28 3535 - 0.20 5 7 8 9 13 15 20 2670 - 0.36 4 6 7 8 12 14 18 22

Page 35: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

34

LampsforKNL

SwitchingofLampsType

P[W] C[μF] I[A]Max.numberoflampsperpoleat230V50Hz

KNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

Metalhalidelampswithelectronic

controlgear(PCI)150 - 0.70 3 5 6 7 10 13 15 20

High-pressuresodium-vapour

lamps-uncorrected

150 - 1.8 5 6 7 8 10 12 15 25

250 - 3.0 2 2 3 4 5 7 9 15

400 - 4.7 1 1 2 2 3 4 5 9

600 - 7.1 - 1 1 1 2 3 3 6

1000 - 10.3 - - - 1 1 2 3 4

High-pressuresodium-vapour

lamps-correction

150 20 0.83 5 6 8 9 14 19 28 38

250 33 1.50 3 4 4 5 7 10 16 22

400 48 2.40 2 2 3 3 5 6 10 17

600 68 3.50 1 1 2 2 3 4 6 10

1000 106 6.30 - 1 1 1 1 2 4 7

High-pressuresodium-vapour

lampswithelectroniccontrol

gear(PCI)

20 - 0.10 8 12 14 15 18 20 26 32

35 - 0.20 5 7 8 9 11 13 18 24

70 - 0.36 4 6 7 8 10 12 16 20

150 - 0.70 3 5 6 7 8 10 14 18

Low-pressuresodium-vapour

lamps-uncorrected

18 - 0.35 14 18 25 27 30 42 70 100

35 - 1.50 5 6 8 9 12 14 18 30

55 - 1.50 5 6 8 9 12 14 18 30

90 - 2.40 3 4 5 6 7 9 11 18

135 - 3.50 2 3 4 5 6 7 9 12

180 - 3.30 1 2 3 4 5 6 8 10

Low-pressuresodium-vapour

lamps-parallelcorrection

18 5 0.35 13 18 22 25 30 42 100 150

35 20 0.31 3 6 7 8 10 14 30 40

55 20 0.42 3 6 7 8 10 14 30 40

90 26 0.63 3 4 5 5 6 9 23 30

135 45 0.94 1 2 3 4 5 7 10 17

180 40 1.16 1 1 2 3 4 6 9 15

Transformersforlow-voltage

tungstenhalogenlamps

20 - - 44 56 70 88 110 174 250 320

50 - - 20 25 32 40 50 80 110 140

75 - - 14 17 22 28 35 54 73 93

100 - - 10 13 17 22 27 43 55 70

150 - - 7 9 12 15 19 29 36 45

200 - - 5 6 8 11 14 23 27 35

300 - - 3 4 6 7 9 14 18 23

Page 36: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

35

LampsforKNL

SwitchingofLampsType

P[W] C[μF] I[A]Max.numberoflampsperpoleat230V50Hz

KNL9/KNL9G KNL12/KNL12G KNL16/KNL16G KNL18/KNL18G KNL22/KNL22G KNL30/KNL30G KNL43 KNL63

Metalhalidelampswithelectronic

controlgear(PCI)150 - 0.70 3 5 6 7 10 13 15 20

High-pressuresodium-vapour

lamps-uncorrected

150 - 1.8 5 6 7 8 10 12 15 25

250 - 3.0 2 2 3 4 5 7 9 15

400 - 4.7 1 1 2 2 3 4 5 9

600 - 7.1 - 1 1 1 2 3 3 6

1000 - 10.3 - - - 1 1 2 3 4

High-pressuresodium-vapour

lamps-correction

150 20 0.83 5 6 8 9 14 19 28 38

250 33 1.50 3 4 4 5 7 10 16 22

400 48 2.40 2 2 3 3 5 6 10 17

600 68 3.50 1 1 2 2 3 4 6 10

1000 106 6.30 - 1 1 1 1 2 4 7

High-pressuresodium-vapour

lampswithelectroniccontrol

gear(PCI)

20 - 0.10 8 12 14 15 18 20 26 32

35 - 0.20 5 7 8 9 11 13 18 24

70 - 0.36 4 6 7 8 10 12 16 20

150 - 0.70 3 5 6 7 8 10 14 18

Low-pressuresodium-vapour

lamps-uncorrected

18 - 0.35 14 18 25 27 30 42 70 100

35 - 1.50 5 6 8 9 12 14 18 30

55 - 1.50 5 6 8 9 12 14 18 30

90 - 2.40 3 4 5 6 7 9 11 18

135 - 3.50 2 3 4 5 6 7 9 12

180 - 3.30 1 2 3 4 5 6 8 10

Low-pressuresodium-vapour

lamps-parallelcorrection

18 5 0.35 13 18 22 25 30 42 100 150

35 20 0.31 3 6 7 8 10 14 30 40

55 20 0.42 3 6 7 8 10 14 30 40

90 26 0.63 3 4 5 5 6 9 23 30

135 45 0.94 1 2 3 4 5 7 10 17

180 40 1.16 1 1 2 3 4 6 9 15

Transformersforlow-voltage

tungstenhalogenlamps

20 - - 44 56 70 88 110 174 250 320

50 - - 20 25 32 40 50 80 110 140

75 - - 14 17 22 28 35 54 73 93

100 - - 10 13 17 22 27 43 55 70

150 - - 7 9 12 15 19 29 36 45

200 - - 5 6 8 11 14 23 27 35

300 - - 3 4 6 7 9 14 18 23

Page 37: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

36

TECHNICALDATA MOTORCONTACTORS

GEN

ER

AL

Type KNL80 KNL90 KNL110

Standards IEC/EN60947-1,IEC/EN60947-4-1,UL508

Approvals UL,GOST

Ambienttemperature °C -50…+70

Storagetemperature °C -60…+80

Mechanicalendurance op.c. 15x106

Max.mechanicaloperatingfrequencywithnoload c./h 3600

Weight kg 1.28

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 690

Thermalcurrentat≤ 40°C Ith A 125 125 125

Ratedpowerat≤40°C 230V

Pe kW

47 47 47

400V 82 82 82

AC-1 500V 108 108 108

690V 128 128 128

Ratedmotorpowerat≤55°C

3-fazno 230V

Pe kW

23 27.6 33

400V 41 50 61

AC-3 500V 56 56 59

690V 74 74 80

Ratemotorpoweracc.toUL

3-fazno 240V

Pe HP

30 30 40

480V 60 60 75

600V 75 75 100

RatedmotorpowerAC-4

≤400V Pe kW 20 23 23

• Contactorsareusedforswitchingelectricmotorsandother resistive,inductiveandcapacitiveloads• Possibilityoffixingthesnap-onauxiliaryswitchblockwith auxiliarycontacts• PossibilityofconnectingtheBR90thermaloverloadrelayfor protectionagainstoverloadandincaseofphasefailure• Assemblytoa35mmor75mmwidemountingrail (EN60715)orfixingwithscrews• DegreeofprotectionIP20,atextrainstallationofthe G265protectionunit• Fixingtotheverticalorhorizontalsurfaceby±30°deviation

KNLCONTACTORSKNL80, KNL90, KNL110

Page 38: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

37

TECHNICALDATA MOTORCONTACTORS

MAIN

CIR

CU

IT

Type KNL80 KNL90 KNL110

ElectricalenduranceAC-3/AC-4 x106 op.c. 1.3/0.2 1.2/0.2 0.8/0.2

Ratedoperationalcurrentat:24/110/220V DC-1

11)

Ie A

70/8/6 70/8/6 70/8/6

21) 100/80/40 100/80/40 100/80/40

31) 100/85/55 100/85/55 100/85/55

1) NumberofpolesinseriesDC-3−DC-5

11) 40/3/1 40/3/1 40/3/1

21) 60/40/7 60/40/7 60/40/7

31) 80/60/35 80/60/35 80/60/35

Max.back-upfuseforshort-circuitprotectionCoordinationtype2

gGIv A

160 160 160

aM 80 100 125

Terminalcapacityrigid

S mm26…50

flexible 6…50

Screw M6

Screwhead imbus hexagonsocketovalhead

Tighteningtorque Nm 4.5

MAG

NETI

CS

YSTE

M

Coilconsumption

switch-onAC VA 210

DC W 15

operationAC VA 18

DC W 15

Make/Breakdelay

makeAC

ms

13-25

break 8-12

makeDC

60-90

break 7-12

Rangeofcontrolvoltage Uc % 85…110

Controlvoltages Uc V 12…600

Terminalcapacityrigid

S mm22.5

flexible 2.5

Screw M3.5

Screwhead Phillips1

Tighteningtorque Nm 0.8-1

STANDARDCONTROLVOLTAGES(AC)V 24 48 110 220/230 240 380/400

KNLCONTACTORSKNL80, KNL90, KNL110

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.

KNL80-00 -230/230-50/60

FrequencyControlvoltageVersionofcontactsType

Page 39: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

38

G484 Snap-onauxiliaryswitch

blocks(Type-12,-21)

ACCESSORIES

BR90OVERLOADRELAY

DIMENSIONS

Type Ratedoperationalcurrentat230VandAC-15 Settingranges(A)

BR90 2.5A 60-82;70-95;90-110

KNLCONTACTORSKNL80, KNL90, KNL110

G484

Page 40: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

39

•Contactorsareusedforswitchingelectricmotorsandother resistiveinductiveandcapacitiveloads•Threeandfour-poleversionsupto1000AforAC-1utilizationcategory•Threeandfour-poleversionsupto630AforAC-3utilizationcategory•AC/DCcontrolvoltages•Awidevarietyofsnap-onauxiliaryswitchblocksandaccessories•Fixingtotheverticalandhorizontalsurfaceby±30°deviation

TECHNICALDATA MOTORCONTACTORS

GEN

ER

AL

Type KNL95 KNL115 KNL145 KNL180 KNL250

Standards IEC/EN60947-4-1,UL508

Approvals UL,GOST

Ambienttemperature °C -50…+70

Storagetemperature °C -60…+80

Mechanicalendurance op.c. 10x106

Max.mechanicaloperatingfrequencywithnoloadop.c./h

2400

Weight kg 5.96 5.96 6.10 10.60 10.80

M

AIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 1000

Thermalcurrentat≤40°C Ith A 125 160 250 275 350

Ratedfrequency f Hz 50/60

Ratedpowerat≤40°C230V

Pe kW

47 57 91 95 124

400V 82 98 150 160 214

AC-1500V 103 129 196 213 282

690V 142 173 270 298 380

Ratedmotorpowerat≤55°C

three-phase

230V

Pm kW

27.6 33 46 57 83

400V 50 61 80 100 140

AC-3500V 56 80 100 123 176

690V 74 100 120 144 212

1000V 46 63 75 103 156

RatedmotorpowerAC-4

three-phasePm kW 23 25 31 36 52

Ratedmotorpoweracc.toUL three-phase

240V

Pm HP

30 40 50 75 100

480V 50 75 100 150 200

600V 75 100 125 150 250

RatedmotorpowerAC-4 ≤400V Pm kW 23 25 31 36 52

ElectricalenduranceAC-3/AC-4 x106 op.c. 1.1/0.2 1.1/0.2 1.1/0.2 1/0.2 1/0.2

Ratedoperationalcurrentat: 24/110/220V

DC-1L/R≤ 1ms

11)

Ie A

70/8/6 160/100/- 220/110/- 260/120/- 350/160/-

21) 100/80/40 160/130/130 220/150/150 260/170/150 350/300/250

31) 100/85/55 160/130/130 220/150/150 260/170/170 350/300/300

1)NumberofpolesinseriesDC-3−DC-5L/R≤ 15ms

11) 40/3/1 140/70/- 160/80/- 180/90/- 280/150/-

21) 60/40/7 140/100/80 160/120/90 180/140/100 280/250/200

31) 80/60/35 140/120/100 160/140/120 180/160/140 180/280/250

Max.back-upfuseforshort-circuitprotectionCoordinationtype2

gGIv A

160 200 250 315 400

aM 100 125 160 200 250

Terminalcapacityrigid

S

mm2 70 70 120 150 240

busbar mm20x3

(1xor2x)20x3

(1xor2x)25x3

(1xor2x)25x3

(1xor2x)30x4

(1xor2x)

Screw M6 M6 M8 M8 M10

Wrenchjawopening mm 10 10 13 13 17

Tighteningtorque Nm 3 3 6 6 10

MOTORCONTACTORSKNL95, KNL115, KNL145, KNL180, KNL250, KNL400, KNL500, KNL630/1000

Page 41: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

40

MAG

NETI

CS

YSTE

M

Type KNL95 KNL115 KNL145 KNL180 KNL250

Coilconsumption

switch-on

Pc

VA 300

W 300

operationVA 10

W 10

Make/Breakdelaymake

AC/DC ms13-25/60-90 60-100 80-120

break 8-12 25-60 30-75

Rangeofcontrolvoltage Uc % 85…110

Controlvoltages Uc V 24to480

Connection fast-on 2/2.8x0.8or6.3x0.8

TECHNICALDATA MOTORCONTACTORS

GEN

ER

AL

Type KNL400 KNL500 KNL630 KNL630/1000

Standards IEC/EN60947-4-1,UL508

Ambienttemperature °C -50…+70

Storagetemperature °C -60…+80

Mechanicalendurance op.c. 10x106 5x106

Max.mechanicaloperatingfrequencywithnoload op.c/h 2400 1200

Weight kg 10.80 20.80 21.50 25.62

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 1000

Thermalcurrentat≤40°C Ith A 550 700 800 1000

Ratedfrequency f Hz 50/60

Ratedpowerat≤40°C 230V

Pe kW

200 252 288 350

400V 345 438 500 600

AC-1 500V 452 575 655 750

690V 598 755 860 1000

Ratedmotorpower three-phase 230V

Pm kW

130 156 198 -

400V 225 290 335 -

AC-3 500V 271 367 368 -

690V 352 416 440 -

1000V 208 312 368 -

RatedmotorpowerAC-4

≤ 400V Pm kW 76 99 119-

ElectricalenduranceAC-3/AC-4 x106 op.c. 0.7/0.2 0.7/0.2 0.7/0.2 -

Ratedoperationalcurrentat:75/110/220V

DC-1L/R≤ 1ms

11)

Ie A

400/250/- 650/320/- 800/460/- -

21) 400/400/350 650/550/450 800/800/700 -

31) 400/400/400 650/600/600 800/800/800 -

1)NumberofpolesinseriesDC-3−DC-5L/R≤ 1ms

11) 350/200/- 550/320/- 800/460/- -

21) 350/350/280 650/550/450 800/800/700 -

31) 350/350/350 650/550/550 800/800/800 -

Max.back-upfuseforshort-circuitprotectionCoordinationtype2

gGIv A

630 800 1000

aM 400 500 630 -

Terminalcapacity

rigid

S

mm2 2x150 2x240

busbar mm 30x5(1xor2x)

50x5(1xor2x)

60x5(1xor2x)

Screw M10 M10 M12 2-M12

Wrenchjawopening mm 17 17 19 19

Tighteningtorque Nm 10 10 14 14

MOTORCONTACTORSKNL95, KNL115, KNL145, KNL180, KNL250, KNL400, KNL500, KNL630/1000

Page 42: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

41

STANDARDCONTROLVOLTAGES(AC)V 24 48 60 110/125 220/240 380/415 440/480

160

M6

404040

A B

170

120

170

150

150

130

Ø7.5

184114 4

CONTACTOR TYPE A BB115 M6 15B145 M8 20B180 M8 20

Type A B1.KNL95,KNL115 M6 152.KNL145 M8 203.KNL180 M8 20

KNL95,KNL115,KNL145,KNL180

MAG

NETI

CS

YSTE

M

Type KNL400 KNL500 KNL630 KNL1000

Coilconsumption

switch-on

Pc

VA 300 400

W 300 400

operationVA 10 18

W 10 18

Make/Breakdelaymake

ms80-120 110-180

break 30-75 60-100

Rangeofcontrolvoltage Uc % 85...110

Controlvoltages Uc V 24to480 48to480

Connection fast-on 2/2.8x0.8or6.3x0.8

DIMENSIONS

MOTORCONTACTORSKNL95, KNL115, KNL145, KNL180, KNL250, KNL400, KNL500, KNL630/10000

Page 43: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

42

140

370

180

179

204

204

M8

47.525

47.5

M10

110

Ø10

56.8

M10X35

145

2547.5 47.5

144219.2

5

166.1

140

180

179

204

204

M8 157.5

Ø10

192.547.547.525 144

219.247.55

KNL250,KNL400

Type A B1.KNL250 M10202.KNL400 M1025

MOTORCONTACTORSKNL95, KNL115, KNL145, KNL180, KNL250, KNL400, KNL500, KNL630/10000

Page 44: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

43

KNL500,KNL630

TypeA BC1.KNL500 M1035 2652.KNL630 M1240 270

194

60

476

230

170

270

230

Ø12

150

6565M12 207.6

263

147.2

230

476

170

270

230

215

Ø12

2596565 65

60 M12 207.6263

147.2

KNL630/1000

TypeABCB500M1035 265B630M1240 270

MOTORCONTACTORSKNL95, KNL115, KNL145, KNL180, KNL250, KNL400, KNL500, KNL630/10000

Page 45: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

44

BRA180, BRA400 Thermaloverloadrelay

ACCESSORIES

Description Characteristic Referencecode

SNAP-ONAUXILIARYSWITCHBLOCKS

Auxiliarycontacts 2NO+1NCor1NO+2NC G350

Mechanicalinterlock Side-by-sidecontactorsOneontopofothercontactors

G355

L(mm)225-365 G356/1

265-305 G356/2

305-345 G356/3

345-385 G356/4

390-425 G356/5

470-500 G356/6

Mainterminalcovers forKNL95,KNL115 G360

forKNL145,KNL180 G361

forKNL250,KNL400 G363

forKNL500 G527

forKNL500.4 G528

forKNL630 G529

forKNL630.4 G530

Barsfor3polesstarconnection forKNL95-KNL180 BA1595

forKNL250-KNL400 BA1721

forKNL500-KNL630 BA1846

Barsfor2polesparallelconnection forKNL95-KNL180 BA1594

forKNL250-KNL400 BA1720

forKNL500-KNL630 BA1845

Adapter forscrewterminal G370

Identificationplate BA126/2

THERMALOVERLOADRELAY BRA180,BRA400

Adapterformountingoncontactor BRA180

KNL95-KNL180 G372

KNL250-KNL400 G373

BRA400

KNL145-KNL180 G375

KNL250-KNL400 G376

Electricreset alltypes G228

Sealingkit alltypes G233

Startbutton alltypes G244

Identificationplate alltypes RB6

Type Settingranges(A)

BRA180 60-100;75-125;90-150;120-200

BRA400 150-250;180-300;250-420

BRA25.5+G230+C.T. 300-500;480-800

KNLCONTACTORSKNL95, KNL115, KNL145, KNL180, KNL250, KNL400, KNL500, KNL630/1000

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.

KNL95-00 -220/240-50/60

FrequencyControlvoltageVersionofcontactsType

Page 46: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

45

TECHNICALDATA

When switched on, a capacitor can function as a short-circuitelement. The capacitor inrush or charging current magnitudedependsonACvoltageatturn-onandontheimpedanceofcon-nectioncablesandapowersupplytransformer.

Incaseof individualcapacitor load,chargingcurrentpeaks thatare 30-time greater than rated capacitor current can occur. Incase of a multi-stage capacitor the inrush current can exceed180-timeratedcapacitorcurrent.

Such a strong current can flow through a contactor from thebeginningwheninrushcurrentoccursfrompowersupplynetworkand the capacitor is already connected. Such inrush current isundesirablesincemaincontactsofstandarddutycontactorsarelikelytoweld.

Anewcapacitordutycontactorisdesignedtomeettherequire-mentsofcapacitordutyapplications.Contactorsarefittedwithablockofthreeauxiliarycontactsconnectedinserieswithsixquickdischargedampingresistors,twopereachphase.Peakcurrentislimitedtothevaluewithinthecontactormakingcapacity.

Three-polecontactorsfrom12,5kVArto60kVArareavailableinsevenratingscomplyingwiththeIEC60947-4-1forAC-6butiliza-tioncategory.TheyhavetheULcertificate.

Advantages• ConformstoutilizationcategoryAC-6b• Savescostsofexpensivereplacement• Longelectricallife• Reduceswattlossesduring“ON”condition,savesenergy• Highsafety• Noriskofdangerousvoltage• Switchingofcapacitorbankinparallelwithoutde-rating• Lessmaintenanceanddowntime• Standardcontrolvoltages:24V50/60Hz,220V50/60Hz,230V50/60Hz,415V50/60Hz

ProductCode

Ratingat50/60

HzkVAr

CurrentcarryingcapacityPower

dissipationperpole

MechanicalLife(million) ElectricalLife

≤55°C 220-240V 400-440V kVAr/CurrentratingasperUL 50or60Hz 50/60Hz (Operations)

kVArCurrentat230V

(A)kVAr

Currentat400V

(A)240V 480V 600V W

KC12 12.5 6.7 17.58 12.5 18.04 6kVAr/15A 12.5kVAr/15A 15kVAr/15A 0.36 17 15 200.000

KC16 16.7 8.5 22.3 16.7 24.1 8kVAr/20A 16.7kVAr/20A 20kVAr/20A 0.8 20 15 200.000

KC20 20 10 26.24 20 28.86 10kVAr/24A 20kVAr/24A 25kVAr/24A 1.25 16 12 100.000

KC25 25 15 39.36 25 36.08 12.5kVAr/30A 25kVAr/30A 33.3kVAr/30A 2 16 12 100.000

KC33 33.3 20 52.48 33.3 48.06 16.5kVAr/40A 33.3kVAr/40A 40kVAr/40A 4.2 16 6 100.000

KC40 40 25 65.6 40 57.73 20kVAr/48A 40kVAr/48A 50kVAr/48A 4.2 16 6 100.000

KC60 50 40 104.9 60 86.6 30kVAr/72A 60kVAr/72A 80kVAr/77A 5.1 10 4 100.000

1ForKC12toKC25:clip-onmountingon35mmwiderailForKC33-KC60:clip-onmountingon75mmwiderail

2Averageambienttemperatureshouldnotexceed45°Cwithinthe24-hourperiodinaccordancewithIEC60871andIEC60831

CAPACITORDUTYCONTACTORSKC12, KC16, KC20, KC25, KC 33, KC 40, KC 60

Page 47: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

46

MOUNTINGANDCONNECTION

KC12,KC16,KC20,KC25 KC33,KC40,KC60

CAPACITORDUTYCONTACTORSKC12, KC16, KC20, KC25, KC33, KC40, KC60

ORDERINGDATAThetypedesignationandcontrolvoltagearestatedwhenorderingthecontactors.KC12-11 -230-50/60

FrequencyControlvoltageVersionofcontactsType

TECHNICALDATA

ProductCode

Ratingat50/60HzkVAr

UpperBlock WireDetails CoilConsumption

≤55°C

TimelagbetweenmakecontactsofAuxblock&

contactor

HoldingtimeofmaincontactsofAuxblock

Cross-sectional

AreaLength Material Lugs-at

Contactorend

LugsatAuxBlockend

TighteningTorque VA VA VA

ms ms mm2 mm Nmm2 50Hz 60Hz 50/60Hz

KC12 12.5 2-10 5-12 0.292 174.0 PTFEcoatedResistancewire Ringtypelug Pintype

lug 1.2 7 7.5 8

KC16 16.7 2-10 5-12 0.292 174.0 PTFEcoatedResistancewire Ringtypelug Pintype

lug 1.7 7 7.5 8

KC20 20 2-10 5-12 0.292 174.0 PTFEcoatedResistancewire Ringtypelug Pintype

lug 1.85 7.5 7.5 8.5

KC25 25 2-10 5-12 0.292 174.0 PTFEcoatedResistancewire Ringtypelug Pintype

lug 2.5 7.5 7.5 8.5

KC33 33.3 2-10 5-12 0.196 245.0 PTFEcoatedResistancewire

PintypelugwithConnector

Pintypelug 5.0 20 22 26

KC40 40 2-10 5-12 0.196 245.0 PTFEcoatedResistancewire

PintypelugwithConnector

Pintypelug 5.0 20 22 26

KC60 50 2-10 5-12 0.196 245.0 PTFEcoatedResistancewire

PintypelugwithConnector

Pintypelug 9.0 20 22 26

Page 48: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

47

•Installationcontactorsarebuiltinconsumerunitsindwellings,businesspremises, hotels,hospitals,shoppingcentres,sportcentres,productionhalls,warehousesand

publicplaces •Theyareusedforremoteswitchingandautomaticcontrolofelectric devicesandequipment,suchas: -single-phaseandthree-phasemotors -differentpumps -air-conditioning -electricheating -lighting •Basiccontactortypesare:IKA20-xx,IKD20-xx,IK21-xx,IKA25-xx,IKD25-xx,

IK40-xx,IKA40-xx,IK63-xx,IKA63-xx • IKD20,IKD25,IK40andIK63withavaristorforovervoltageprotectionandarectifierenable dcandacvoltagecontrol • Theyexcelinsilentoperation • IKA20,IK21,IKA25,IKA40andIKA63areacdrivencontactorsonly • Contactscanbeusedasmainorauxiliary • Contactorsaredesignedforassemblingto35mmmountingrailinaccordance withtheEN60715standard• Sealingterminalcoversenabledirectprotectionagainstcontactwithliveparts• IKVventilationmoduleisavailableforpreventingexceededheatingwhencontactorsareusedside-by-side• AllcontactorshavedegreeofprotectionIP20

TECHNICALDATAFORIKA20,IKD20,IKA25andIKD25

GEN

ER

AL

Type IKA20 IKD20 IKA25 IKD25

Standards IEC/EN61095,IEC/EN60947-4-1,IEC/EN60947-5-1

Approvals KEMA,NF,GOST

Modulewidth 1 2

Mechanicalendurance op.c. 3x106

Ambienttemperature °C -5…+55

Storagetemperature °C -30…+80

No.ofcontactors(side-by-side)

≤ 40°C max.3 max.3

nolimitation

max.3

40-55°C max.2 max.2 max.2

Contactreliability 17V; ≥ 50mA

Min.distanceofopencontacts mm 3.6

Powerdissipationperpole W 1.7 1.7 2.2 2.2

Overloadcurrentwithstandcapability A 72 72 68 68

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20 20 25 25

Max.operatingfrequency

DC-1

op.c./h

300

AC-1/AC-3/AC-5b/AC-6b/AC-15 600

noload 3000

Weight kg 0.13 0.13 0.24 0.24

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 230 230 440 440

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 20 20 25 25

Ratedoperationalvoltage Ue V 230 230 400 400

Ratedfrequency f Hz 50/60

Ratedoperationalcurrent AC-1/AC-7a Ie A 20 20 25 25

Operationalpower single-phase 230V

Pe kW

4 4 5.4 5.4

AC-1/AC-7a three-phase 230V - - 9 9

three-phase 400V - - 16 16

Electricalendurance AC-1/AC-7a op.c. 200.000

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 49: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

48

TECHNICALDATAFORIKA20,IKD20,IKA25andIKD25

MAIN

CIR

CU

IT

Type IKA20 IKD20 IKA25 IKD25

Ratedoperationalcurrent AC-3/AC-7bIe A

NO:9NC:6

NO:9NC:6

8.5 8.5

Operationalpower single-phasemotor230V

Pe kW

NO:1.3NC:0.75

NO:1.3NC:0.75

1.3 1) 1.3 1)

AC-3/AC-7b three-phasemotor 230V - - 2.2 2.2

three-phasemotor 400V - - 4 4

Electricalendurance AC-3/AC-7b op.c. 300.000 300.000 500.000 500.000

Switchingofcapacitors AC-6b 230V C μF 30 30 36 36

Electricalendurance AC-6b op.c. 100.000

DC-1(L/R≤ 1ms)Electricalendurance:

A

1pole Ue =24VDC 20 20 25 25

Ue =48VDC 15 15 20 20

Ue =60VDC 10 10 15 15

Ue =110VDC 6 6 6 6

Ue =220VDC 0.6 0.6 0.6 0.6

2polesconnectedinseries Ue =24VDC 20 20 25 25

Ue =48VDC 18 18 25 25

Ue =60VDC 15 15 20 20

Ue =110VDC 10 10 10 10

Ue =220VDC 6 6 6 6

3polesconnectedinseries Ue =24VDC - - 25 25

Ue =48VDC - - 25 25

Ue =60VDC - - 25 25

Ue =110VDC - - 20 20

Ue =220VDC - - 15 15

4polesconnectedinseries Ue =24VDC - - 25 25

Ue =48VDC - - 25 25

Ue =60VDC - - 25 25

Ue =110VDC - - 20 20

Ue =220VDC - - 15 15

Electricalendurance DC-1 op.c. 100.000 100.000 100.000 100.000

DC-3(L/R≤ 2ms)Electricalendurance:

A

1pole Ue =24VDC 10 10 15 15

Ue =48VDC 5 5 8 8

Ue =60VDC 2 2 4 4

Ue =110VDC 1 1 1.3 1.3

Ue =220VDC 0.1 0.1 0.2 0.2

2polesconnectedinseries Ue =24VDC 20 20 25 25

Ue =48VDC 10 10 16 16

Ue =60VDC 8 8 12 12

Ue =110VDC 4 4 5.5 5.5

Ue =220VDC 0.4 0.4 0.6 0.6

1) Data for single-phase power are valid for versions -22, -20 and -02

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 50: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

49

TECHNICALDATAFORIKA20,IKD20,IKA25andIKD25

MAIN

CIR

CU

IT

Type IKA20 IKD20 IKA25 IKD25

DC-3(L/R≤ 2ms)Ratedoperationalcurrent:

Ie A

3polesconnectedinseries Ue =24VDC - - 25 25

Ue =48VDC - - 25 25

Ue =60VDC - - 25 25

Ue =110VDC - - 15 15

Ue =220VDC - - 3 3

4polesconnectedinseries Ue =24VDC - - 25 25

Ue =48VDC - - 25 25

Ue =60VDC - - 25 25

Ue =110VDC - - 20 20

Ue =220VDC - - 8 8

Electricalendurance DC-3 op.c. 100.000 100.000 100.000 100.000

DC-5(L/R≤ 7,5ms)Ratedoperationalcurrent:

Ie A

1pole Ue =24VDC 10 10 15 15

Ue =48VDC 4 4 5 5

Ue =60VDC 1 1 3 3

Ue =110VDC 0.3 0.3 0.5 0.5

Ue =220VDC 0.06 0.06 0.1 0.1

2polesconnectedinseries Ue =24VDC 20 20 25 25

Ue =48VDC 8 8 15 15

Ue =60VDC 6 6 10 10

Ue =110VDC 2 2 4 4

Ue =220VDC 0.2 0.2 0.4 0.4

3polesconnectedinseries Ue =24VDC - - 25 25

Ue =48VDC - - 25 25

Ue =60VDC - - 20 20

Ue =110VDC - - 12 12

Ue =220VDC - - 2 2

4polesconnectedinseries Ue =24VDC - - 25 25

Ue =48VDC - - 25 25

Ue =60VDC - - 25 25

Ue =110VDC - - 15 15

Ue =220VDC - - 5 5

Electricalendurance DC-5 op.c. 100.000 100.000 100.000 100.000

Terminalcapacityrigid

S mm21…10

flexible 1…6

Screw M3.5

Screwhead PZ1

Tighteningtorque Nm 1.2

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 51: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

50

TECHNICALDATAFORIKA20,IKD20,IKA25andIKD25

AU

XILI

AR

YC

IRC

UIT

Type IKA20 IKD20 IKA25 IKD25

Ratedoperationalvoltage Ue V 230 230 400 400

Ratedinsulationvoltage Ui V 230 230 440 440

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 20 20 25 25

AC-15

Ratedoperationalcurrent single-phase

230V

Ie A

6 6 6 6

single-phase

400V - - 4 4

Electricalendurance AC-15 op.c. 300.000 300.000 500.000 500.000

CO

NTR

OL

CIR

CU

IT

Rangeofcontrolvoltage Uc % 85…110

Kindofvoltages AC AC,DC AC AC,DC

Controlvoltage Uc V 12…230

Frequency(AC) f Hz 50/602)

Surgeimmunitytest(1.2/50µs),acc.toIEC/EN61000-4-5

kV 2

Coilconsumption switch-onVA/W

12/10 2.1/2.1 33/25 2.6/2.63)

operation 2.8/1.2 2.1/2.1 5.5/1.6 2.6/2.63)

Make/breakdelaysmake

ms15−25 15−45 10−30 15−45

break 10−30 20−50 10−30 20−70

Terminalcapacityrigid

S mm21…2.5

flexible 1…2.5

Screw M3.5

Screwhead PZ1

Tighteningtorque Nm 0.6

2) IKD20 and IKD25 can be controlled by ac voltage with frequency from 40 Hz to 400 Hz 3) Coil consumption for version -04 is 3.8 VA/3.8 W

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 52: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

51

TECHNICALDATAFORIK21,IK40,IK63,IKA40andIKA63

GEN

ER

AL

Type IK21 IKA40 IK40 IKA63 IK63

Standards IEC/EN61095,IEC/EN60947-4-1,IEC60947-5-1

Approvals GOST KEMA,GOST

KEMA,NF,

GOST

KEMA,GOST

KEMA,NF,

GOST

Modulewidth 2 3

Mechanicalendurance op.c. 3x106

Ambienttemperature °C -5…+55

Storagetemperature °C -30…+80

No.ofcontactors(side-by-side) ≤ 40°Cnolimitation no

limitation

max.3 nolimitation

max.3

40-55°C max.2 max.2

Contactreliability 17V; ≥50mA

Min.distanceofopencontacts mm 3.6

Powerdissipationperpole W 2 4 8

Overloadcurrentwithstandcapability A 40 176 240

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20 63 80

Max.operatingfrequency DC-1

c./h

300

AC-1/AC-3/AC-5b/AC-6b 600

AC-15 1200

noload 3000

Weight kg 0.17 0.35 0.42 0.35 0.42

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 415 440 440

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 20 40 63

Ratedoperationalvoltage Ue V 400

Ratedfrequency f Hz 50/60

Ratedoperationalcurrent AC-1/AC-7a Ie A 20 40 63

Operationalpower single-phase

230V

Pe kW

4 8.7 13.3

AC-1/AC-7a three-phase

230V 7.5 16 24

three-phase

400V 13 26 40

Electricalendurance AC-1/AC-7a op.c. 200.000 100.000 100.000

Ratedoperationalcurrent AC-3/AC-7b Ie A 5 22 30

Operationalpower single-phase

230V

Pe kW

0.371) 3.71) 51)

AC-3/AC-7b three-phase

230V 1.1 5.5 8.5

three-phase

400V 2.2 11 15

Electricalendurance AC-3/AC-7b op.c. 300.000 150.000 150.000

Switchingofcapacitors AC-6b C μF 36 220 330

Electricalendurance AC-6b op.c. 100.000

DC-1(L/R≤ 1ms)Ratedoperationalcurrent:

1pole Ue =24VDC

A

20 40 63

Ue =48VDC 12 24 26

Ue =60VDC 6 18 20

Ue =110VDC 2 4 4

Ue =220VDC 0.5 1.2 1.2

2polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 15 38 42

Ue =60VDC 10 32 34

Ue =110VDC 4 10 10

Ue =220VDC 1.5 8 8

1) Data for single-phase power are valid for versions -22, -20 and -02

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 53: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

52

TECHNICALDATAFORIK21,IK40,IK63,IKA40andIKA63

MAIN

CIR

CU

IT

Type IK21 IKA40 IK40 IKA63 IK63

DC-1(L/R≤ 1ms)Electricalendurance:

A

3polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 20 40 63

Ue =60VDC 20 40 60

Ue =110VDC 6 30 35

Ue =220VDC 2.5 20 30

4polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 20 40 63

Ue =60VDC 20 40 63

Ue =110VDC 6 40 63

Ue =220VDC 3.5 40 63

Electricalendurance DC-1 op.c. 100.000

DC-3(L/R≤ 2ms)Electricalendurance:

A

1pole Ue =24VDC 10 22 25

Ue =48VDC 5 10 11

Ue =60VDC 2 5 5

Ue =110VDC 1 1.5 1.5

Ue =220VDC 0.1 0.3 0.3

2polesconnectedinseries Ue =24VDC 20 40 45

Ue =48VDC 10 20 22

Ue =60VDC 8 16 18

Ue =110VDC 4 5 5

Ue =220VDC 0.4 1 1

3polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 20 40 45

Ue =60VDC 15 32 35

Ue =110VDC 6 15 18

Ue =220VDC 2.5 4 5

4polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 20 40 63

Ue =60VDC 15 40 63

Ue =110VDC 6 40 63

Ue =220VDC 3.5 10 10

Electricalendurance DC-3 op.c. 100.000

DC-5(L/R≤ 7,5ms)Electricalendurance:

1pole Ue =24VDC

A

10 20 25

Ue =48VDC 4 8 10

Ue =60VDC 1 4 5

Ue =110VDC 0.3 1 1

Ue =220VDC 0.06 0.2 0.2

2polesconnectedinseries Ue =24VDC 20 40 45

Ue =48VDC 8 18 20

Ue =60VDC 6 14 15

Ue =110VDC 2 5 5

Ue =220VDC 0.2 0.8 0.8

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 54: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

53

TECHNICALDATAFORIK21,IK40,IK63,IKA40andIKA63

MAIN

CIR

CU

IT

Tip IK21 IKA40 IK40 IKA63 IK63

DC-5(L/R≤ 7,5ms)Electricalendurance:

3polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 20 40 44

Ue =60VDC 15 28 30

Ue =110VDC 5 12 15

Ue =220VDC 1.5 3 4

4polesconnectedinseries Ue =24VDC 20 40 63

Ue =48VDC 20 40 63

Ue =60VDC 15 40 60

Ue =110VDC 5 35 45

Ue =220VDC 3 8 10

Electricalendurance DC-5 op.c. 100.000

Terminalcapacityrigid

S mm21…2.5 1.5…25

flexible 1…2.5 1.5…16

Screw M3.5 M5

Headscrew PZ2

Tighteningtorque Nm 1.2 3.5

AU

XILI

AR

YC

IRC

UIT

Ratedoperationalvoltage Ue V 400

Ratedinsulationvoltage Ui V 415 440

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 20 40 63

AC-15

Ratedoperationalcurrent single-phase 230VIe A

6

single-phase 400V 4

Electricalendurance AC-15 op.c. 300.000 150.000 150.000

CO

NTR

OL

CIR

CU

IT

Rangeatcontrolvoltage Uc % 85…110

Kindofvoltages AC AC AC.DC AC AC.DC

Controlvoltage Uc V 12…230

Frequency(AC) f Hz 50/602)

Surgeimmunitytest(1.2/50µs),acc.toIEC/EN61000-4-5

kV 2

Coilconsumption switch-onVA/W

30/25 15.4/6 5/5 15.4/6 5/5

operation 5/1.5 7.7/3 5/5 7.7/3 5/5

Make/breakdelaysmake

ms7−20 10−20 15−20 10−20 15−20

break 10−20 10−15 35−45 10−15 35−45

Terminalcapacityrigid

S mm21…2.5

flexible 1…2.5

Screw M3.5 M3

Screwhead PZ2 PZ1

Tighteningtorque Nm 0.6

2) IK40 and IK63 can be controlled by ac voltage with frequency from 40 Hz to 400 Hz

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 55: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

54

SWITCHINGOFLAMPS

Type Power(W) Current(A) C(µF)

Max.numberoflampsperpoleat230V50Hz

IKA20,IKD20,IK21

IKA25,IKD25 IKA40,IK40 IKA63,IK63

Incandescentlampsandtungstenhalogenlamps

15 0.07 − 130 130 260 330

25 0.11 − 80 80 160 200

40 0.18 − 50 50 100 125

60 0.26 − 33 66 65 85

75 0.33 − 26 26 53 66

100 0.44 − 20 20 40 50

150 0.65 − 13 13 26 33

200 0.87 − 10 10 20 25

300 1.30 − 6 6 13 16

500 2.17 − 3 3 8 10

1000 4.35 − 1 1 4 5

Energysavinglamps

3 0.03 − 50 60 150 200

5 0.04 − 45 55 135 180

7 0.055 − 40 50 120 160

8 0.065 − 35 45 110 150

9 0.075 − 30 40 100 140

10 0.08 − 30 40 100 140

11 0.09 − 30 40 100 140

12 0.1 − 25 35 95 120

14 0.11 − 25 35 90 120

15 0.12 − 20 30 85 115

16 0.13 − 20 30 80 105

18 0.145 − 18 26 70 95

20 0.16 − 17 22 65 85

21 0.17 − 15 20 60 80

23 0.185 − 15 20 60 70

24 0.195 − 15 20 55 70

30 0.16 − 15 20 55 70

Compactfluorescentlamps-seriescorrection

10 0.19 1,4 50 60 105 165

13 0.18 1,4 50 60 105 165

18 0.23 1,7 40 50 85 135

26 0.33 2,5 30 35 60 95

18 0.38 2,7 25 30 50 80

24 0.35 2,7 25 30 50 80

36 0.44 3,4 20 25 45 70

Compactfluorescentlamps-parallelcorrection

5 0.18 2,2 13 16 100 150

7 0.18 2,1 14 17 104 157

9 0.17 2,0 15 18 110 165

10 0.19 2,2 13 16 100 150

11 0.16 1,7 17 21 125 194

13 0.18 1,8 16 20 120 183

18 0.23 2,3 13 15 95 143

26 0.33 3,3 9 11 66 100

18 0.38 4,2 7 8 52 78

24 0.35 3,6 8 10 61 91

36 0.44 4,4 6 8 50 75

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 56: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

55

SWITCHINGOFLAMPS

Type Power(W) Current(A) C(µF)

Max.numberoflampsperpoleat230V50Hz

IKA20,IKD20,IK21

IKA25,IKD25 IKA40,IK40 IKA63,IK63

Compactfluorescentlampswithelectroniccontrolgear(ECG)

5 0.05 − 45 63 180 250

7 0.05 − 45 63 180 250

9 0.07 − 32 45 128 180

10 0.07 − 32 45 128 180

11 0.07 − 32 45 128 180

13 0.07 − 32 45 128 180

18 0.22 − 10 14 40 57

24 0.22 − 10 14 40 57

26 0.22 − 10 14 40 57

32 0.22 − 10 14 40 57

36 0.22 − 10 14 40 57

40 0.22 − 10 14 40 57

42 0.22 − 10 14 40 57

55 0.28 − 8 11 32 45

57 0.28 − 8 11 32 45

70 0.35 − 6 9 25 36

80 0.41 − 5 8 22 30

120 0.58 − 4 5 15 22

2x9 0.11 − 2x16 2x22 2x90 2x125

2x10 0.11 − 2x16 2x22 2x90 2x125

2x11 0.11 − 2x16 2x22 2x90 2x125

2x13 0.11 − 2x16 2x22 2x90 2x125

2x18 0.30 − 2x5 2x7 2x20 2x28

2x24 0.31 − 2x5 2x7 2x20 2x28

2x26 0.31 − 2x5 2x7 2x20 2x28

2x32 0.31 − 2x5 2x7 2x20 2x28

2x36 0.31 − 2x5 2x7 2x20 2x28

2x40 0.40 − 2x4 2x6 2x18 2x26

2x42 0.40 − 2x4 2x6 2x18 2x26

2x55 0.55 − 2x3 2x5 2x16 2x22

2x57 0.55 − 2x3 2x5 2x16 2x22

Fluorescentlamps-uncorrectedorseriescorrection

11 0.16 1.3 55 70 125 200

18 0.37 2.7 22 24 90 140

24 0.35 2.5 22 24 90 140

36 0.43 3.4 17 20 65 95

58 0.67 5.3 14 17 45 70

65 0.67 5.3 14 17 35 50

85 0.80 5.3 12 15 25 40

Fluorescentlamps-lead-lagcircuit

2x11 0.07 − 2x50 2x60 2x140 2x200

2x18 0.11 − 2x30 2x40 2x100 2x150

2x24 0.14 − 2x24 2x31 2x78 2x118

2x36 0.22 − 2x17 2x24 2x65 2x95

2x58 0.35 − 2x10 2x14 2x40 2x60

2x65 0.35 − 2x9 2x13 2x30 2x45

2x85 0.47 − 2x6 2x10 2x20 2x30

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 57: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

56

SWITCHINGOFLAMPS

Type Power(W) Current(A) C(µF)

Max.numberoflampsperpoleat230V50Hz

IKA20,IKD20,IK21

IKA25,IKD25 IKA40,IK40 IKA63,IK63

Fluorescentlamps-parallelcorrection

11 0.16 3.5 9 10 62 94

18 0.37 4.5 7 8 48 73

24 0.35 4.5 7 8 48 73

36 0.34 4.5 7 8 48 73

58 0.67 7.0 4 5 31 47

65 0.67 7.0 4 5 31 47

85 0.80 8.0 3 4 27 41

Fluorescentlampswithelectroniccontrolgear(ECG)

18 0.09 − 25 35 100 140

36 0.16 − 15 20 52 75

58 0.25 − 14 19 50 72

2x18 0.17 − 2x12 2x17 2x50 2x70

2x36 0.32 − 2x7 2x10 2x26 2x38

2x58 0.49 − 2x7 2x9 2x25 2x36

High-pressuremercury-vapourlamps-uncorrected

50 0.61 − 14 18 38 55

80 0.80 − 10 13 29 42

125 1.15 − 7 9 20 29

250 2.15 − 4 5 10 15

400 3.25 − 2 3 7 10

700 5.40 − 1 2 4 6

1000 7.50 − 1 1 3 4

High-pressuremercury-vapourlamps-parallelcorrection

50 0.28 7 4 5 31 47

80 0.41 8 4 5 27 41

125 0.65 10 3 4 22 33

250 1.22 18 1 2 12 18

400 1.95 25 1 1 9 13

700 3.45 45 − − 5 7

1000 4.80 60 − − 4 5

Metalhalidelamps-uncorrected

35 0.35 − 18 22 43 60

70 1.00 − 10 12 23 32

150 1.80 − 5 7 12 18

250 3.00 − 3 4 7 10

400 3.50 − 3 3 6 9

1000 9.50 − 1 1 2 3

2000 16.50 − − − 1 1

Metalhalidelamps-parallelcorrection

35 0.25 6 5 6 36 50

70 0.45 12 2 3 18 25

150 0.75 20 1 1 11 15

250 1.50 33 − 1 6 9

400 2.50 35 − 1 6 8

1000 5.80 95 − − 2 3

2000 11.50 148 − − 1 2

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 58: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

57

SWITCHINGOFLAMPS

Type Power(W) Current(A) C(µF)

Max.numberoflampsperpoleat230V50Hz

IKA20,IKD20,IK21

IKA25,IKD25 IKA40,IK40 IKA63,IK63

Metalhalidelampswithelectroniccontrolgear(PCI)+50-125xIn lamp for0,6ms

20 0.10 − 9 9 18 20

35 0.20 − 6 6 11 13

70 0.36 − 5 5 10 12

150 0.70 − 4 4 8 10

High-pressuresodium-vapourlamps-uncorrected

150 1.8 − 5 6 17 22

250 3.0 − 3 4 10 13

400 4.7 − 2 2 6 8

1000 10.3 − − 1 3 3

High-pressuresodium-vapourlamps-correction

150 0.83 20 1 1 11 16

250 1.50 33 − 1 6 10

400 2.40 48 − − 4 6

1000 6.30 106 − − 2 3

High-pressuresodium-vapourlampswithelectroniccontrolgear(PCI)+50-125xIn lamp for0,6ms

20 0.10 − 9 9 18 20

35 0.20 − 6 6 11 13

70 0.36 − 5 5 10 12

150 0.70 − 4 4 8 10

Low-pressuresodium-vapourlamps-uncorrected

18 0.35 − 22 27 71 90

35 1.50 − 7 9 23 30

55 1.50 − 7 9 23 30

90 2.40 − 4 5 14 19

135 3.50 − 3 4 10 13

180 3.50 − 3 4 10 13

Low-pressuresodium-vapourlamps-parallelcorrection

18 0.35 5 6 7 44 66

35 0.31 20 1 1 11 16

55 0.42 20 1 1 11 16

90 0.63 26 1 1 8 12

135 0.94 45 − − 4 7

180 1.16 40 − − 5 8

Transformersforlow-voltagetungstenhalogenlamps

20 − − 40 52 110 174

50 − − 20 24 50 80

75 − − 13 16 35 54

100 − − 10 12 27 43

150 − − 7 9 19 29

200 − − 5 6 14 23

300 − − 3 4 9 14

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 59: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

58

180º

IKA40/63

IKA40/63IK40/63

Type Power(W) Current(A) C(µF)

Max.numberoflampsperpoleat230V50Hz

IKA20,IKD20,IK21

IKA25,IKD25 IKA40,IK40 IKA63,IK63

FluorescentlampsT5withelectroniccontrolgear(ECG)

22 0.11

FC

22 30 80 110

40 0.21 12 15 40 60

55 0.28 8 12 30 45

14 0.08

HE

30 40 105 150

21 0.11 22 30 80 115

28 0.14 18 22 60 90

35 0.18 14 18 48 70

24 0.12

HO

20 26 70 100

39 0.20 12 16 42 62

49 0.24 10 14 35 52

54 0.27 9 13 32 47

80 0.39 6 8 22 32

2x22 0.23

2xFC

2x11 2x15 2x40 2x55

2x40 0.42 2x6 2x7 2x20 2x30

2x55 0.55 2x4 2x6 2x15 2x22

2x14 0.15

2xHE

2x15 2x20 2x52 2x75

2x21 0.22 2x11 2x15 2x40 2x57

2x28 0.28 2x9 2x11 2x20 2x45

2x35 0.36 2x7 2x9 2x24 2x35

2x24 0.24

2xHO

2x10 2x13 2x35 2x50

2x39 0.39 2x6 2x8 2x21 2x31

2x49 0.48 2x5 2x7 2x17 2x26

2x54 0.54 2x4 2x6 2x16 2x23

2x80 0.74 2x3 2x4 2x11 2x16

IK21contactorsoperationpositionisoptional.OperationpositionforcontactorsIKA20,IKD20,IKA25,IKD25,IK40,IKA40,IK63andIKA63:

SWITCHINGOFLAMPS

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 60: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

59

IK63 - 40 /220/230

Ventilationmodule SealingcoverIK40, IK63, IKA40, IKA63

IK21 IKA20, IKD20, IKA25, IKD25

IKA25, IKD25

IKA20, IKD20

IK40, IK63, IKA40, IKA63

IKA20-10

IKD20-10

IKA25-31IKD25-31IK40-31IKA40-31IK63-31IKA63-31

IKA25-04IKD25-04IK40-04IKA40-04IKA63-04

IKA25-22IKD25-22IK40-22IKA40-22IK63-22IKA63-22

IKA20-01

IKD20-01

IKA20-20

IKD20-20

IKA20-11

IKD20-11

IKA20-02

IKA20-02

IKA25-30IKD25-30IK40-30IKA40-30IK63-30IKA63-30

IK21-10 IK21-01

IKA25-40IKD25-40IK40-40IKA40-40IK63-40IKA63-40

IKA25-20IKD25-20IK40-20IKA40-20IK63-20IKA63-20

DIMENSIONS

ORDERINGDATAThetypedesignationandcontrolvoltageshouldbestatedwhenor-deringthecontactors.

ControlvoltageVersionofContactsType

CONTACTARRANGEMENTS

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 61: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

60

• IKA20-R,IKD20-R,IKA25-RandIKD25-Rareupgradedversions ofbasictypesofinstallationcontactors• Besidesbasicfunctionstheyenablemanualcontrolwithahandle• Descriptionofthehandlepositions: - A:thecontactorfunctionsasaninstallationcontactorwithoutmanualcontrol -O:permanentlyswitchedoffcontrolvoltage - I:atmanualshiftingthehandlefrompositionAtoI,makecontacts areclosedandbreakcontactsareopen.Whencontrolvoltageisapplied,thehandleisautomaticallysettopositionA.• IKD20-RandIKD25-Rareprovidedwithavaristorforovervoltage protectionandarectifier,whichenablescontrolwithACandDC voltage• Contactorswithmanualcontrolenable - switchingdependingontariff(selectionofthemostconvenienttariff) - switchingwhencontrolvoltageisnotapplied• DegreeofprotectionIP20• Technicaldataforlampsareidenticaltoinstallationcontactorswithout manualoperationIKA20,IKD20,IKA25andIKD25

TEHNICALDATA

GEN

ER

AL

Type IKA20-R IKD20-R IKA25-R IKD25-R

Standards IEC/EN61095,IEC/EN60947-4-1,IEC60947-5-1

Approvals NF,GOST,KEMA

NF,GOST,KEMA

NF,GOST,KEMA

GOST,KEMA

Modulewidth 1 2

Mechanicalendurance op.c. 3x106

Ambienttemperature °C -5…+55

Storagetemperature °C -30…+80

No.ofcontactors(side-by-side) ≤40°C max.3 max.3nolimit

max.3

40-55°C max.2 max.2 max.2

Contactreliability 17V; ≥ 50mA

Min.distanceofopencontacts mm 3.6

Powerdissipationperpole W 1.7 1.7 2.2 2.2

Overloadcurrentwithstandcapability A 72 72 68 68

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2

Iv A 20 20 25 25

Max.operatingfrequency DC-1

op.c./h

300

AC-1/AC-3/AC-5b/AC-6b/AC-15 600

noload 3000

Weight kg 0.13 0.13 0.24 0.24

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 230 230 440 440

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 20 20 25 25

Ratedoperationalvoltage Ue V 230 230 400 400

Ratedfrequency f Hz 50/60

Ratedoperationalcurrent AC-1/AC-7a Ie A 20 20 25 25

Operationalpower single-phase 230V

Pe kW

4 4 5.4 5.4

AC-1/AC-7a three-phase 230V - - 9 9

three-phase 400V - - 16 16

Electricalendurance AC-1/AC-7a op.c. 200.000

IK-RINSTALLATIONCONTACTORSIKA20-R, IKA25-R, IKD20-R, IKD25-R

Page 62: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

61

TEHNICALDATA

MAIN

CIR

CU

IT

Type IKA20-R IKD20-R IKA25-R IKD25-R

Ratedoperationalcurrent AC-3/AC-7bIe A

NO:9NC:6

NO:9NC:6

8,5 8,5

Operationalpower single-phase

230V

Pe kW

NO:1,3NC:0,75

NO:1,3NC:0,75

1,3 1) 1,3 1)

AC-3/AC-7b three-phase

230V − − 2,2 2,2

three-phase

400V − − 4 4

Electricalendurance AC-3/AC-7b op.c. 300.000 300.000 500.000 500.000

Switchingofcapacitors AC-6b C µF 30 30 36 36

Electricalendurance AC-6b 230V op.c. 100.000

DC-1(L/R≤ 1ms)Ratedoperationalcurrent:

1pole Ue =24VDC

A

20 20 25 25

Ue =48VDC 15 15 20 20

Ue =60VDC 10 10 15 15

Ue =110VDC 6 6 6 6

Ue =220VDC 0.6 0.6 0.6 0.6

2polesconnectedinseries Ue =24VDC 20 20 25 25

Ue =48VDC 18 18 25 25

Ue =60VDC 15 15 20 20

Ue =110VDC 10 10 10 10

Ue =220VDC 6 6 6 6

3polesconnectedinseries Ue =24VDC − − 25 25

Ue =48VDC − − 25 25

Ue =60VDC − − 25 25

Ue =110VDC − − 20 20

Ue =220VDC − − 15 15

4polesconnectedinseries Ue =24VDC − − 25 25

Ue =48VDC − − 25 25

Ue =60VDC − − 25 25

Ue =110VDC − − 20 20

Ue =220VDC − − 15 15

Electricalendurance DC-1 op.c. 100.000

DC-3(L/R≤ 2ms)Ratedoperationalcurrent:

1pole Ue =24VDC

A

10 10 15 15

Ue =48VDC 5 5 8 8

Ue =60VDC 2 2 4 4

Ue =110VDC 1 1 1.3 1.3

Ue =220VDC 0.1 0.1 0.2 0.2

2polesconnectedinseries Ue =24VDC 20 20 25 25

Ue =48VDC 10 10 16 16

Ue =60VDC 8 8 12 12

Ue =110VDC 4 4 5.5 5.5

Ue =220VDC 0.4 0.4 0.6 0.6

3polesconnectedinseries Ue =24VDC − − 25 25

Ue =48VDC − − 25 25

Ue =60VDC − − 25 25

Ue =110VDC − − 15 15

Ue =220VDC − − 3 3

4polesconnectedinseries Ue =24VDC − − 25 25

Ue =48VDC − − 25 25

Ue =60VDC − − 25 25

Ue =110VDC − − 20 20

Ue =220VDC − − 8 8

Electricalendurance DC-3 op.c. 100.000

1)Dataforsingle-phasepowerarevalidforversions-22,-20and-02

IK-RINSTALLATIONCONTACTORSIKA20-R, IKA25-R, IKD20-R, IKD25-R

Page 63: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

62

TEHNICALDATA

MAIN

CIR

CU

IT

Type IKA20-R IKD20-R IKA25-R IKD25-R

DC-5(L/R≤ 7,5ms)Ratedoperationalcurrent:

1pole Ue =24VDC

A

10 10 15 15

Ue =48VDC 4 4 5 5

Ue =60VDC 1 1 3 3

Ue =110VDC 0.3 0.3 0.5 0.5

Ue =220VDC 0.06 0.06 0.1 0.1

2polesconnectedinseries Ue =24VDC 20 20 25 25

Ue =48VDC 8 8 15 15

Ue =60VDC 6 6 10 10

Ue =110VDC 2 2 4 4

Ue =220VDC 0.2 0.2 0.4 0.4

3polesconnectedinseries Ue =24VDC − − 25 25

Ue =48VDC − − 25 25

Ue =60VDC − − 20 20

Ue =110VDC − − 12 12

Ue =220VDC − − 2 2

4polesconnectedinseries Ue =24VDC − − 25 25

Ue =48VDC − − 25 25

Ue =60VDC − − 25 25

Ue =110VDC − − 15 15

Ue =220VDC − − 5 5

Electricalendurance DC-5 op.c. 100.000

Terminalcapacityrigid

S mm21…10

flexible 1…6

Screw M3.5

Headscrew PZ1

Tighteningtorque Nm 1.2

AU

XILI

AR

YC

IRC

UIT

Ratedoperationalvoltage Ue V 230 230 400 400

Ratedinsulationvoltage Ui V 230 230 440 440

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 20 20 25 25

AC-15

Ie A6 6 6 6Ratedoperationalcurrent single-

phase230V

single-phase

400V − − 4 4

Electricalendurance AC-15 op.c. 300.000 300.000 500.000 500.000

CO

NTR

OL

CIR

CU

IT

Rangeofcontrolvoltage Uc % 85…110

Kindofvoltages AC AC,DC AC AC,DC

Controlvoltages Uc V 12…230

Frequency(AC) f Hz 50/602)

Surgeimmunitytest(1.2/50µs),acc.toIEC/EN61000-4-5

kV 2

Coilconsumption switch-on(handleinA)

VA/W

12/10 2.1/2.1 33/25 2.6/2.63)

switch-on(handleinI) 6/3.8 2.1/2.1 10/5 2.6/2.63)

operation 2.8/1.2 2.1/2.1 5.5/1.6 2.6/2.63)

Make/breakdelaysmake

ms15−25 15−45 10−30 15−45

break 10−30 20−50 10−30 20−70

Terminalcapacityrigid

S mm21…2.5

flexible 1…2.5

Screw M3

Screwhead PZ1

Tighteningtorque Nm 0.6

2) IKD20-R and IKD25-R can be controlled by ac voltage with frequency from 40 Hz to 400 Hz 3) Coil consumption for version -04 is 3.8 VA / 3.8 W

IK-RINSTALLATIONCONTACTORSIKA20-R, IKA25-R, IKD20-R, IKD25-R

Page 64: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

63

IKA20 - 20 - R / 230

IKA20-02-RIKD20-02-R

IKA25-04-RIKD25-04-R

IKA25-22-RIKD25-22-R

IKA20-10-RIKD20-10-R

IKA20-20-RIKD20-20-R

IKA20-11-RIKD20-11-R

IKA25-40-RIKD25-40-R

IKA25-31-RIKD25-31-R

IKA25-30-RIKD25-30-R

IKA25-20-RIKD25-20-R

IKA-20-01-RIKD-20-01-R

DIMENSIONS CONTACTARRANGEMENTS

ORDERINGDATAThetypedesignationandcontrolvoltageshouldbestatedwhenorderingthecontactors.

ControlvoltageManualcontrolvoltageVersionofContactsType

OPERATIONPOSITIONFORCONTACTORSIKA20-R,IKD20-R,IKA25-R,IKD25-R

Ventilationmodule

IKA25 IKA20

IKA20-R,IKD20-R,IKA25-R,IKD25-R

IKV

SEALINGCOVER

180º

IK-RINSTALLATIONCONTACTORSIKA20-R, IKA25-R, IKD20-R, IKD25-R

Page 65: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

64

IKN-11

IKN-02IKN-20

CONTACTARRANGEMENTS DIMENSIONSIKN

TEHNICALDATA

GEN

ER

AL Type IKN

Standards IEC/EN60947-5-1

Approvals KEMA,NF,GOST

Modulewidth ½

MAIN

CIR

CU

IT

Ratedinsulationvoltage Ui V 500

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 6

RatedoperationalvoltageUe V

230

400

Ratedoperationalcurrent

AC-15 Ue=230VIe A

6

Ue=400V 4

Electricalendurance op.c. 50,000

Mechanicalendurance op.c. 3x106

Min.distanceofopencontacts mm 4

Contactreliability 12V;≥5mA

Powerlossperpole W 0.3

Weight kg 0.035

Max.back-upfuseforshort-circuitprotectiongLCoordinationtype2.

Iv A 6

Terminalcapacity rigidS mm2

1…2.5

flexible 1…2.5

Screw M3

Screwhead PZ1

Tighteningtorque Nm 0.6

TheIKNauxiliaryswitchismainlyusedforindicatingthecontactorswitching condition and also for control of heavier electromagnetic loads(above72VA).TheIKNauxiliaryswitchisprovidedwithtwocontactsinthefollowingversions:• version-11withonebreakandonemakecontact• version-20withtwomakecontacts• version-02withtwobreakcontactsDegreeofprotectionIP20.ThisauxiliaryswitchcanbeusedatcontactorsIKA20-R,IKA25-R,IKD25-R,IKA20,IKA25,IKD25,IK40,IK63AvailablealsospecialversionsofauxiliaryswitchwithULcertificate(contactusfordetails)TheauxiliaryswitchshouldnotbeappliedincombinationwithIKD20andIKD20-R.

IKNAUXILIARYSWITCH

Page 66: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

65

REMOTESWITCHINGANDAUTOMATICCONTROL:•Single-phasemotors•Three-phasemotors•Differentpumps•Air-conditioning•Electricheating•Lightning

SILENTOPERATION:•RectifierenableACorDCvoltagecontrol•Overvoltageprotectionwithvaristor•IKD20,IKD25,IK40andIK63

ACCONTROL:•Fastswitching•IKA20,IKA25,IKA40andIKA63

OTHERBENEFITS:•Usedasmainorauxiliary•MountingonDINrail•Sealingterminalcoversfordirectprotection againstcontactwithliveparts•IKVventilationmoduleforpreventingexceededheating whencontactorsareusedside-by-side

INTENDEDUSE:•Customerunitsindwelings•Businesspremises•Hotels•Hospitals•Shoppingcentres•Sportcentres•Productionhalls•Warehouses•Publicplaces

TECHNICALDATAType IKA20 IKD20 IKA25 IKD25

GEN

ER

AL

StandardsUL508,CSAC22.2No.14,IEC60947-4-1,EN60947-4-1,IEC61095,

EN61095,IEC60947-5-1,EN60947-5-1

Approvals UL,CSA

Protectiondegree IP20

Mechanicalendurance op.c. 3.000.000

Ambienttemperature 23°F…104°F/-5°C…+40°C

Storagetemperature -22°F…176°F/-30°C…+80°C

No.ofcontactorsside-by-sidewithoutventilationmodule

max.3 nolimitation max.3

Contactreliability 17V/≥50mA

Min.distanceofopencontacts in/mm 0.1417/3.6

Powerdissipationperpole W 1.7 1.7 2.2 2.2

Overloadcurrentwithstandcapability(10s) A 72 72 68 68

Max.back-upfuseforshort-circuitprotection20A(gL)20A(K5)

20A(gL)20A(K5)

25A(gL)25A(K5)

25A(gL)25A(K5)

Max.operatingfrequency

Noload

op.c./h

3000

AC-1/AC-3/AC-6b 600

AC-15 1200

El.switchingacc.UL508

360

Weight lb/kg 0.29/0.13 0.29/0.13 0.53/0.24 0.53/0.24

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 67: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

66

TECHNICALDATAType IKA20 IKD20 IKA25 IKD25

MAIN

CIR

CU

IT-U

L/C

SA

Motor power

1-phase 120 V

HP

1/3 1/3 1/3 1/31-phase 208 V 3/4 3/4 3/4 3/41-phase 240 V 1 1 1 13-phase 120 V 1 13-phase 208 V 2 23-phase 240 V 3 33-phase 480 V 5 5

General use1-phase 240 V

A20 20

3-phase 480 V 25 25Discharge lamps

(standard ballast)

1-phase 240 VA

20 20

3-phase 480 V 25 25

Auxiliary circuit B300, P300 B300, P300 B300, P300 B300, P300

MAIN

CIR

CU

IT-IE

C/E

N

Rated insulation voltage Ui V 300 300 500 500Rated impulse withstand woltage Uimp kV 4 4 4 4Thermal current Ith A 20 20 25 25Rated operational voltage Ue V 230 230 400 400Rated frequency f Hz 50/60 50/60 50/60 50/60Rated operational current AC-1/AC-7a Ie A 20 20 25 25

Operational power

AC-1/AC-7a

1-phase 230 VPe W

4 4 5.4 5.43-phase 230 V 9 93-phase 400 V 16 16

Electrical endurance AC-1/AC-7a op.c. 200000Rated operational current AC-3/AC-7b Ie A 9 NO/6 NC 9 NO/6 NC 8.5 8.5

Operational power

AC-3/AC-7b

1-phase 230 VPe A

1.3 NO/0.75 NC 1.3 NO/0.75 NC 1.3 1.33-phase 230 V 2.2 2.23-phase 400 V 4 4

Electrical endurance AC-3/AC-7b op.c. 300000 500000Switching of capacitor AC-6b 230 V C μF 30 30 36 36Electrical endurance AC-6b op.c. 100000Auxiliary circuit

Rated operational current AC-15

1-phase 230 V

Ie A

6 6 6 6

1-phase 400 V 4 4 4 4

Electrical endurance AC-15 op.c. 300000 500000

Terminal capacityRigid

SAWG/mm2

16…10/1…10 16…10/1…10 16…10/1…10 16…10/1…10Flexible 16…8/1…6 16…8/1…6 16…8/1…6 16…8/1…6

Screw M3.5 M3.5 M3.5 M3.5Screw head PZ1 PZ1 PZ1 PZ1Tightening torque lb-in/Nm 10.62/1.2 10.62/1.2 10.62/1.2 10.62/1.2

CO

NTR

OL

CIR

CU

IT

Range of control voltage Uc % 85…110Control voltages Uc V 12…240Kind of voltage Uc AC AC, DC AC AC, DCSurge immunity test (1.2/50 μs), acc. to IEC/EN 61000-4-5

kV 2

Coil consumptionSwitch-on

VA/W12/10 2.1/2.1 33/25 2.6/2.61)

Operation 2.8/1.2 2.1/2.1 5.5/1.6 2.6/2.61)

Make/break delaysMake

ms15…25 15…45 10…30 15…45

Break 10…30 20…50 10…30 20…70

Terminal capacityRigid

SAWG/mm2

16…14/1…2.5 16…14/1…2.5 16…14/1…2.5 16…14/1…2.5Flexible 16…14/1…2.5 16…14/1…2.5 16…14/1…2.5 16…14/1…2.5

Screw M3 M3 M3 M3Screw head PZ1 PZ1 PZ1 PZ1Tightenig torque lb-in/Nm 5.31/0.6 5.31/0.6 5.31/0.6 5.31/0.6

1)Coil consumption for version -04 is 3.8 VA/ W 2) Coil consumption for versions -22 and -04 is 6.1 VA/W

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 68: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

67

TECHNICALDATAType IKA40 IK40 IKA63 IK63

GEN

ER

AL

StandardsUL 508, CSA C22.2 No. 14, IEC 60947-4-1, EN 60947-4-1, IEC

61095, EN 61095, IEC 60947-5-1, EN 60947-5-1Approvals UL, CSAProtection degree IP20Mechanical endurance op.c. 3.000.000Ambient temperature 23 °F…104 °F/-5 °C…+40 °CStorage temperature -22 °F…176 °F/-30 °C…+80 °CNo. of contactors side-by-side without ventilation module

no limitation max. 3 no limitation max. 3

Contact reliability 17 V/≥50 mAMin. distance of open contacts in/mm 0.1417/3.6Power dissipation per pole W 4 4 8 8Overload current withstand capability (10 s) A 176 176 240 240

Max. back-up fuse for short-circuit protection63 A (gL) 60 A (K5)

63 A (gL) 60 A (K5)

80 A (gL) 70 A (K5)

80 A (gL) 70 A (K5)

Max. operating frequency

No load

op.c./h

3000AC-1/AC-3/AC-6b 600AC-15 1200El. switching acc. UL 508

360

Weight lb/kg 0.77/0.35 0.93/0.42 0.77/0.35 0.93/0.42

MAIN

CIR

CU

IT-U

L/C

SA

Motor power

1-phase 120 V

HP

1 1 2 21-phase 208 V 2 2 3 31-phase 240 V 3 3 5 53-phase 120 V 3 3 5 53-phase 208 V 7-1/2 7-1/2 10 103-phase 240 V 7-1/2 7-1/2 10 103-phase 480 V 15 15 20 20

General use1-phase 240 V

A3-phase 480 V 40 40 63 63

Discharge lamps

(standard ballast)

1-phase 240 VA

3-phase 480 V 30 30 40 40

Auxiliary circuit B300, P300 B300, P300 B300, P300 B300, P300

MAIN

CIR

CU

IT-IE

C/E

N

Rated insulation voltage Ui V 600 600 600 600Rated impulse withstand woltage Uimp kV 4 4 4 4Thermal current Ith A 40 40 63 63Rated operational voltage Ue V 400 400 400 400Rated frequency f Hz 50/60 50/60 50/60 50/60Rated operational current AC-1/AC-7a Ie A 40 40 63 63

Operational power

AC-1/AC-7a

1-phase 230 VPe W

8.7 8.7 13.3 13.33-phase 230 V 16 16 25 253-phase 400 V 26 26 40 40

Electrical endurance AC-1/AC-7a op.c. 100000Rated operational current AC-3/AC-7b Ie A 22 22 30 30

Operational power

AC-3/AC-7b

1-phase 230 VPe A

3.7 3.7 5 53-phase 230 V 5.5 5.5 8.5 8.53-phase 400 V 11 11 15 15

Electrical endurance AC-3/AC-7b op.c. 150000Switching of capacitor AC-6b 230 V C μF 220 220 330 330Electrical endurance AC-6b op.c. 100000Auxiliary circuit

Rated operational current AC-15

1-phase 230 V

Ie A

6 6 6 6

1-phase 400 V 4 4 4 4

Electrical endurance AC-15 op.c. 150000

Terminal capacityRigid

SAWG/mm2

14…10/1.5…25 14…10/1.5…25 14…10/1.5…25 14…10/1.5…25Flexible 14…4/1.5…16 14…4/1.5…16 14…4/1.5…16 14…4/1.5…16

Screw M5 M5 M5 M5Screw head PZ2 PZ2 PZ2 PZ2Tightening torque lb-in/Nm 30.98/3.5 30.98/3.5 30.98/3.5 30.98/3.5

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

Page 69: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

68

IKA20/25IKD20/25

IK40, IK63IKD20/25

IKA40/63IKA20/25

IKA20-10ULIKD20-10UL

IKA25-31ULIKD25-31ULIKA40-31ULIK40-31ULIKA63-31ULIK63-31UL

IKA25-04ULIKD25-04ULIKA40-04ULIK40-04ULIKA63-04UL

IKA25-22ULIKD25-22ULIKA40-22ULIK40-22ULIKA63-22ULIK63-22UL

IKA20-01ULIKD20-01UL

IKA20-20ULIKD20-20UL

IKA20-11ULIKD20-11UL

IKA20-02ULIKA20-02UL

IKA25-30ULIKD25-30ULIK40-30ULIK63-30UL

IKA25-40ULIKD25-40ULIKA40-40ULIK40-40ULIKA63-40ULIK63-40UL

CONTACTARRANGEMENTS

CAUTIONSANDWARNINGS

TECHNICALDATA

CO

NTR

OL

CIR

CU

IT

Type IKA40 IK40 IKA63 IK63

Rangeofcontrolvoltage Uc % 85…110

Controlvoltages Uc V 12…240

Kindofvoltage Uc AC AC,DC AC AC,DC

Surgeimmunitytest(1.2/50μs),acc.toIEC/EN61000-4-5

kV 2

CoilconsumptionSwitch-on

VA/W15.4/64) 5/52) 15.4/64) 5/52)

Operation 7.7/33) 5/52) 7.7/33) 5/52)

Make/breakdelaysMake

ms10…20 15…20 10…20 15…20

Break 10…15 35…45 10…15 10…15

TerminalcapacityRigid

SAWG/mm2

16…14/1…2.5 16…14/1…2.5 16…14/1…2.5 16…14/1…2.5

Flexible 16…14/1…2.5 16…14/1…2.5 16…14/1…2.5 16…14/1…2.5

Screw M3 M3 M3 M3

Screwhead PZ1 PZ1 PZ1 PZ1

Tightenigtorque lb-in/Nm 5.31/0.6 5.31/0.6 5.31/0.6 5.31/0.6

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

3)Coil consumption for version -22 and -04 is 12.3/2.8 VA/ W 4) Coil consumption for versions -22 and -04 is 64/52 VA/W

Page 70: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

69

IKA20, IKD20, IKA25, IKD25

IKA40, IK40, IKA63, IK63

VENTILATION MODUL SEALING COVER

IKA25, IKD25 IKA20, IKD20IKA40, IKA63, IK40, IK63,

IKA63- 40UL/230V Controlvoltage

UL/CSAapprovedVersionofcontactsType

ORDERING DATA:

DIMENSIONS

IKINSTALLATIONCONTACTORSIKA20, IKD20, IK21, IKA25, IKD25, IK40, IKA40, IK63, IKA63

(0.689 in)

(0.2677 in)

(1.378 in)(2.5197 in)

(2.5197 in)(2.1063 in)

(1.7323 in)

(1.7323 in)

(1.7

717

in)

(1.7

717

in)

(3.5

433

in)

(3.5

433

in)

Page 71: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactors

70

TECHNICALDATA

GEN

ER

AL

Type IKN

StandardsUL508,CSAC22.2No.14

IEC60947-5-1,EN60947-5-1

Approvals UL,CSA

Protectiondegree IP20

Mechanicalendurance op.c. 3.000.000

Contactreliability 12V;≥5mA

PowerdissipationperpoleatIth=6A W 0,3

Min.distanceofopencontacts in/mm 0.1575/4

Max.back-upfuseforshort-circuitprotection6A(gL)6A(K5)

Weight lb/kg 0.08/0.035

UL

CSA Auxiliarycircuit

C300(120VAC,240VAC)Q300(125VDC,250VDC)

Continuousthermalcurrent Ith A 2.5

IEC

/EN

Ratedinsulationvoltage Ui V 500

Ratedimpulsewithstandvoltage Uimp kV 4

Thermalcurrent Ith A 6

Ratedoperationalvoltage Ue V 230and400

RatedoperationalcurrentAC-15

Ue=230VIe A

6

Ue=400V 4

ElectricalenduranceAC-15 op.c. 50000

TerminalcapacityRigid

S AWG/mm2-/1…2.5

Flexible 16/1…2.5

Screw M3

Screwhead PZ1

Tighteningtorque lb-in/Nm 7.08/0.8

IKN-11

IKN-02

IKN-20

IKN-20UL

UL/CSAapprovedVersionofcontactsType

AuxiliarySwitchIKN

ORDERING DATA:

INTENDED USE:

•TheIKNauxiliaryswitchismainlyusedforindicatingthecontactorswitchingconditionandalsoforcontrolofheavierelectromagneticloads

•TheIKNauxiliaryswitchisprovidedwithtwocontactsintheversions: -11withonebreakandonemakecontact -20withtwomakecontacts -02withtwobreakcontacts

•Thisauxiliaryswitchcannotbeused onlyatcontactorIKD20.

CONTACTARRANGEMENTS DIMENSIONS

(2.5197 in)

(1.7323 in)

(0.3543 in)

(1.7

717

in)

(3.5

433

in)

Page 72: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

BistableSwitch

71

IKN-20UL

UL/CSAapprovedVersionofcontactsType

BI

INTENDED USE:•Residentialbuildings•Buisinesspremises•Hotels•Hospitals•Shopingcentres•Productionhalls•Warehouses•Publicplaces

REMOTE SWITCHINGAND AUTOMATIC CONTROL:•Lightning•Electricheating•Electricmotors•Electricequipment

ADVANCED OPERATION:•Impulsecontrol•Manualcontrol

OTHER BENEFITS:•Smallswitchoncoil consumption•Noholdcoilconsumtion•Wideapplication•Mountingon35mmrail•Sealingterminalcovers

TECHNICALDATA

Type BI220 BI225 BI232

GEN

ER

AL

Standards IEC/EN60669-2-2

Manualcontrol Yes

Controlwithimpulsevoltage Yes

Indication Withactuator

ProtectiondegreeaccordancetoIEC/EN60529 IP20

Modulewidth 1

Ambienttemperature °C -25…+55

Storagetemperature °C -30…+80

Max.resistancetohumidity 95%RHat+55°C

Min.contactreliability 10V/100mA

Max.shockresistanceaccordancetoIEC/EN60068-2-27 g 15

Max.vibrationresistanceaccordancetoIEC/EN60068-2-6 g 3

Min.distanceofopencontacts mm >3

Distancebetweencontactsandcoil mm >6

Mechanicalendurance op.c. 106

Max.back-upfuseforshort-circuitprotection(gL) A 20 25 32

Powerdissipationperpole W 1.5 2 3

MAIN

CIR

CU

IT

Ratedimpulsevoltage Uimp kV 4

Thermalcurrent Ith A 20 25 32

Ratedinsulationvoltage Ui V 440

Ratedoperationalvoltage Ue V 440

Ratedfrequency fe Hz 50/60

Ratedoperationalcurrentforcosφ=0,6acc.toIEC/EN60669-2-2 Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-1acc.toIEC/EN60947-4-1 Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-7aacc.toIEC/EN61095−Slightlyinductiveloadsinhauseholdappliancesandsimilarapplications

Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-21acc.toIEC/EN60947-3−Switchingofresistiveloadsincludingmodetareoverloads

Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-22acc.toIEC/EN60947-3Switchingofmixedresistiveandinductiveloads,includingmoderateoverloads

Ie A20/230V16/440V

25/230V20/440V

32/230V25/440V

Page 73: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

72

BistableSwitch

BI

TECHNICALDATAType BI220 BI225 BI232

MAIN

CIR

CU

IT

RatedoperationalcurrentforAC-23acc.toIEC/EN60947-3Switchingofmotorloadsorotherhighlyinductiveloads

Ie A16/230V/

1-phase20/230V/

1-phase25/230V/

1-phase

RatedoperationalcurrentforAC-3acc.toIEC/EN60947-4-1Squirrel-cagemotors:starting,switchingoffmotorsduringrunning

Ie A7/230V/1-phase

8/230V/1-phase

10/230V/1-phase

RatedoperationalcurrentforAC-7bacc.toIEC/EN61095Motor-loadsforhouseholdapplications

Ie A7/230V/1-phase

8/230V/1-phase

10/230V/1-phase

RatedoperationalcurrentforAC-6aacc.toIEC/EN60947-4-1Switschingoftransformershavinginrushcurrentpeaksofnotmorethan30timespeakofratedcurrent

Ie A3/230V

1.5/400V3.6/230V1.8/400V

4.5/230V2.2/400V

RatedoperationalcurrentforAC-6bacc.toIEC/EN60947-4-1−Switchingofcapacitorbanks

C µF 100µF/230V

RatedoperationalcurrentforDC-1acc.toIEC/EN60947-4-1−Non-inductiveorslightlyinductiveloads,resistancefurnances

Ie A20/24V/

1pole25/24V/

1pole32/24V/

1pole

RatedoperationalcurrentforDC-3acc.toIEC/EN60947-4-1−Shunt-motors:starting,plugging,inching

Ie A10/24V/

1pole15/24V/

1pole25/24V/

1pole

RatedoperationalcurrentforDC-5acc.toIEC/EN60947-4-1−Series-motors:starting,plugging,inching

Ie A10/24V/

1pole16/24V/

1pole20/24V/

1pole

RatedoperationalcurrentforDC-21acc.toIEC/EN60947-3−Switchingofresistiveloadsincludingmoderateoverloads

Ie A20/24V/

1pole25/24V/

1pole32/24/V

1pole

RatedoperationalcurrentforDC-22acc.toIEC/EN60947-3−Switchingofmixedresistiveandinductiveloads,includingmoderateoverloads

Ie A16/24V/

1pole20/24V/

1pole25/24V/

1pole

RatedoperationalcurrentforDC-23acc.toIEC/EN60947-3−Switchingofhighlyinductiveloads(e.g.seriesmotors)

Ie A10/24V/

1pole16/24V/

1pole20/24V/

1pole

RatedoperationalcurrentforAC-5aacc.toIEC/EN60947-4-1−Switchingofelectricdischargelampcontrols

Ie A 16/230V

RatedoperationalcurrentforAC-5bacc.toIEC/EN60947-4-1−Switchingofincandescentlamps

Ie A 10/230V

Ratedoperationalcurrentforfluorescentlampsacc.toIEC/EN60669-2-2 Ie A 16/230V

Fluorescent/energysaving/compactlampswithelectroniccontrolgear Ie A 2/230V

Electricalenduranceforallutilizationcategories op.c. 105

Terminalcapacityformaincircuit S mm2 1…10rigid/flexible

Screwformaincircuit M4

Screw-headformaincircuit (±)PZ2

Tighteningtorqueformaincircuit Nm 1.2

CO

NTR

OL

CIR

CU

IT

Ratetedcontrolvoltages Uc V AC:12,24,48,120,230,240

Ratedfrequencyofcontrolvoltage fc Hz 50/60

Rangeofcontrolvoltage Uc % 90…110

Coilconsumption−inrush VA/W 18/13

Coilconsumption−hold VA/W 9/4

Min.impulsedurationatUc ms 50

Min.impulsedurationat0,85Uc ms 100

Min.durationbetweentwoimpulses ms 150

Max.numberofimpulsesperminute 15 7.5

Max.impulsedurationatUc 1hour

Terminalcapacityforcontrolcircuit S mm2 1…4rigid/flexible

Screwforcontrolcircuit M3

Screw-headforcontrolcircuit (±)PZ1

Tighteningtorqueforcontrolcircuit Nm 0.6

Page 74: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

BistableSwitch

BI

TECHNICALDATA

GEN

ER

AL

Type BI420 BI425 BI432Standards IEC/EN60669-2-2Manualcontrol YesControlwithimpulsevoltage YesIndication WithactuatorProtectiondegreeaccordancetoIEC/EN60529 IP20Modulewidth 2Ambienttemperature °C -25…+55Storagetemperature °C -30…+80Max.resistancetohumidity 95%RHat+55°CMin.contactreliability 10V/100mAMax.shockresistanceaccordancetoIEC/EN60068-2-27 g 15Max.vibrationresistanceaccordancetoIEC/EN60068-2-6 g 3Min.distanceofopencontacts mm >3Distancebetweencontactsandcoil mm >6Mechanicalendurance op.c. 106

Max.back-upfuseforshort-circuitprotection(gL) A 20 25 32Powerdissipationperpole W 1,5 2 3

MAIN

CIR

CU

IT

Ratedimpulsevoltage Uimp kV 4Thermalcurrent Ith A 20 25 32Ratedinsulationvoltage Ui V 440Ratedoperationalvoltage Ue V 440Ratedfrequency fe Hz 50/60Ratedoperationalcurrentforcosφ=0,6acc.toIEC/EN60669-2-2

Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-1acc.toIEC/EN60947-4-1 Ie A 20/440V 25/440V 32/440VRatedoperationalcurrentforAC-7aacc.toIEC/EN61095−Slightlyinductiveloadsinhauseholdappliancesandsimilarapplications

Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-21acc.toIEC/EN60947-3−Switchingofresistiveloadsincludingmodetareoverloads

Ie A 20/440V 25/440V 32/440V

RatedoperationalcurrentforAC-22acc.toIEC/EN60947-3Switchingofmixedresistiveandinductiveloads,includingmoderateoverloads

Ie A20/230V16/440V

25/230V20/440V

32/230V25/440V

RatedoperationalcurrentforAC-23acc.toIEC/EN60947-3Switchingofmotorloadsorotherhighlyinductiveloads

Ie A16/230V/1-phase16/230V/3-phase16/400V/3-phase

20/230V/1-phase20/230V/3-phase20/400V/3-phase

25/230V/1-phase25/230V/3-phase25/400V/3-phase

RatedoperationalcurrentforAC-3acc.toIEC/EN60947-4-1Squirrel-cagemotors:starting,switchingoffmotorsduringrunning

Ie A7/230V/1-phase

6.3/230V/3-phase6.6/400V/3-phase

8/230V/1-phase8.7/230V/3-phase8.5/400V/3-phase

10/230V/1-phase11.5/230V/3-phase11.3/400V/3-phase

RatedoperationalcurrentforAC-7bacc.toIEC/EN61095Motor-loadsforhouseholdapplications

Ie A7/230V/1-phase

6.3/230V/3-phase6.6/400V/3-phase

8/230V/1-phase8.7/230V/3-phase8.5/400V/3-phase

10/230V/1-phase11.5/230V/3-phase11.3/400V/3-phase

RatedoperationalcurrentforAC-6aacc.toIEC/EN60947-4-1Switschingoftransformershavinginrushcurrentpeaksofnotmorethan30timespeakofratedcurrent

Ie A3/230V

1.5/400V3.6/230V1.8/400V

4.5/230V2.2/400V

RatedoperationalcurrentforAC-6bacc.toIEC/EN60947-4-1−Switchingofcapacitorbanks

C µF 100µF/230V

RatedoperationalcurrentforDC-1acc.toIEC/EN60947-4-1−Non-inductiveorslightlyinductiveloads,resistancefurnances

Ie A 20/24V/1pole 25/24V/1pole 32/24V/1pole

RatedoperationalcurrentforDC-3acc.toIEC/EN60947-4-1−Shunt-motors:starting,plugging,inching

Ie A 10/24V/1pole 15/24V/1pole 25/24V/1pole

RatedoperationalcurrentforDC-5acc.toIEC/EN60947-4-1−Series-motors:starting,plugging,inching

Ie A 10/24V/1pole 16/24V/1pole 20/24V/1pole

RatedoperationalcurrentforDC-21acc.toIEC/EN60947-3−Switchingofresistiveloadsincludingmoderateoverloads

Ie A 20/24V/1pole 25/24V/1pole 32/24/V1pole

RatedoperationalcurrentforDC-22acc.toIEC/EN60947-3−Switchingofmixedresistiveandinductiveloads,includingmoderateoverloads

Ie A 16/24V/1pole 20/24V/1pole 25/24V/1pole

RatedoperationalcurrentforDC-23acc.toIEC/EN60947-3−Switchingofhighlyinductiveloads(e.g.seriesmotors)

Ie A 10/24V/1pole 16/24V/1pole 20/24V/1pole

RatedoperationalcurrentforAC-5aacc.toIEC/EN60947-4-1−Switchingofelectricdischargelampcontrols

Ie A 16/230V

RatedoperationalcurrentforAC-5bacc.toIEC/EN60947-4-1−Switchingofincandescentlamps

Ie A 10/230V

Ratedoperationalcurrentforfluorescentlampsacc.toIEC/EN60669-2-2

Ie A 16/230V

Fluorescent/energysaving/compactlampswithelectroniccontrolgear

Ie A 2/230V

TECHNICALDATAType BI220 BI225 BI232

MAIN

CIR

CU

IT

RatedoperationalcurrentforAC-23acc.toIEC/EN60947-3Switchingofmotorloadsorotherhighlyinductiveloads

Ie A16/230V/

1-phase20/230V/

1-phase25/230V/

1-phase

RatedoperationalcurrentforAC-3acc.toIEC/EN60947-4-1Squirrel-cagemotors:starting,switchingoffmotorsduringrunning

Ie A7/230V/1-phase

8/230V/1-phase

10/230V/1-phase

RatedoperationalcurrentforAC-7bacc.toIEC/EN61095Motor-loadsforhouseholdapplications

Ie A7/230V/1-phase

8/230V/1-phase

10/230V/1-phase

RatedoperationalcurrentforAC-6aacc.toIEC/EN60947-4-1Switschingoftransformershavinginrushcurrentpeaksofnotmorethan30timespeakofratedcurrent

Ie A3/230V

1.5/400V3.6/230V1.8/400V

4.5/230V2.2/400V

RatedoperationalcurrentforAC-6bacc.toIEC/EN60947-4-1−Switchingofcapacitorbanks

C µF 100µF/230V

RatedoperationalcurrentforDC-1acc.toIEC/EN60947-4-1−Non-inductiveorslightlyinductiveloads,resistancefurnances

Ie A20/24V/

1pole25/24V/

1pole32/24V/

1pole

RatedoperationalcurrentforDC-3acc.toIEC/EN60947-4-1−Shunt-motors:starting,plugging,inching

Ie A10/24V/

1pole15/24V/

1pole25/24V/

1pole

RatedoperationalcurrentforDC-5acc.toIEC/EN60947-4-1−Series-motors:starting,plugging,inching

Ie A10/24V/

1pole16/24V/

1pole20/24V/

1pole

RatedoperationalcurrentforDC-21acc.toIEC/EN60947-3−Switchingofresistiveloadsincludingmoderateoverloads

Ie A20/24V/

1pole25/24V/

1pole32/24/V

1pole

RatedoperationalcurrentforDC-22acc.toIEC/EN60947-3−Switchingofmixedresistiveandinductiveloads,includingmoderateoverloads

Ie A16/24V/

1pole20/24V/

1pole25/24V/

1pole

RatedoperationalcurrentforDC-23acc.toIEC/EN60947-3−Switchingofhighlyinductiveloads(e.g.seriesmotors)

Ie A10/24V/

1pole16/24V/

1pole20/24V/

1pole

RatedoperationalcurrentforAC-5aacc.toIEC/EN60947-4-1−Switchingofelectricdischargelampcontrols

Ie A 16/230V

RatedoperationalcurrentforAC-5bacc.toIEC/EN60947-4-1−Switchingofincandescentlamps

Ie A 10/230V

Ratedoperationalcurrentforfluorescentlampsacc.toIEC/EN60669-2-2 Ie A 16/230V

Fluorescent/energysaving/compactlampswithelectroniccontrolgear Ie A 2/230V

Electricalenduranceforallutilizationcategories op.c. 105

Terminalcapacityformaincircuit S mm2 1…10rigid/flexible

Screwformaincircuit M4

Screw-headformaincircuit (±)PZ2

Tighteningtorqueformaincircuit Nm 1.2

CO

NTR

OL

CIR

CU

IT

Ratetedcontrolvoltages Uc V AC:12,24,48,120,230,240

Ratedfrequencyofcontrolvoltage fc Hz 50/60

Rangeofcontrolvoltage Uc % 90…110

Coilconsumption−inrush VA/W 18/13

Coilconsumption−hold VA/W 9/4

Min.impulsedurationatUc ms 50

Min.impulsedurationat0,85Uc ms 100

Min.durationbetweentwoimpulses ms 150

Max.numberofimpulsesperminute 15 7.5

Max.impulsedurationatUc 1hour

Terminalcapacityforcontrolcircuit S mm2 1…4rigid/flexible

Screwforcontrolcircuit M3

Screw-headforcontrolcircuit (±)PZ1

Tighteningtorqueforcontrolcircuit Nm 0.6

73

Page 75: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

74

BistableSwitch

ORDERING DATA:BI220-20230V Controlvoltage

Versionofcontacts

Type

90°

15° 15°90°

BI220, BI225, BI232

BI420, BI425, BI432

17.6 35.260

44

SEALING COVER

90 9045 45 35

BI

CONTACTARRANGEMENTS

DIMENSIONS OPERATIONPOSITIONS

TECHNICALDATA

MAIN

C

IRC

UIT

Type BI420 BI425 BI432Electricalenduranceforallutilizationcategories op.c. 105

Terminalcapacityformaincircuit S mm2 1…10rigid/flexibleScrewformaincircuit M4Screw-headformaincircuit (±)PZ2Tighteningtorqueformaincircuit Nm 1.2

CO

NTR

OL

CIR

CU

IT

Ratetedcontrolvoltages Uc V AC:12,24,48,120,230,240Ratedfrequencyofcontrolvoltage fc Hz 50or60Rangeofcontrolvoltage Uc % 90…110Coilconsumption−inrush VA/W 18/13Coilconsumption−hold VA/W 9/4Min.impulsedurationatUc ms 50Min.impulsedurationat0,85Uc ms 100Min.durationbetweentwoimpulses ms 150Max.numberofimpulsesperminute 15 7.5Max.impulsedurationatUc 1hourTerminalcapacityforcontrolcircuit S mm2 1…4rigid/flexibleScrewforcontrolcircuit M3Screw-headforcontrolcircuit (±)PZ1Tighteningtorqueforcontrolcircuit Nm 0.6

BI420-40BI425-40BI432-40

BI420-31BI425-31BI432-31

BI220-1CBI225-1CBI232-1C

BI220-22BI225-22BI232-22

BI220-11BI225-11BI232-11

BI220-10BI225-10BI232-10

BI220-20BI225-20BI232-20

BI420-30BI425-30BI432-30

BI220-2CBI225-2CBI232-2C

BI420-21BI425-21BI432-21

5

Page 76: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

75

• Versions: -MS25-withthermalandmagneticreleases -MST25-withathermalreleaseonly -MS20-withthermalandmagneticreleasesforsingle-phase consumers -MST20-withathermaloverloadreleaseforsinglephase consumers • Manualcontrol: -START,STOP,push-buttons -Testofreleasefunction(TEST) • Automaticswitch-offwiththermalormagneticrelease • Controlwithunder-voltagereleaseorshuntrelease • Anauxiliaryswitchforsidemountingorflushmountingused forindicationoftheswitchingstate • ON/OFF,push-buttonspositionunequivocallyindicatesthe switchingpositionofmaincircuitcontacts • Contactmaterial: -Resistanttocontactwelding -Enableslowcontactheating

• Isolatingdistancebetweencontacts:4.5mmpercontactplace• Connectionofarigidorflexibleconductor• Assemblyto35mmwidemountingrailinaccordancewithEN60715orfixingwithtwoscrews• Verticalorhorizontaloperationalposition

TECHNICALDATA

GEN

ER

AL

Standards IEC/EN60947-2,IEC/EN60947-4-1,IEC/EN60947-5-1,IEC/EN60204,UL508,CSA22.2No.14

Approvals UL,SEMKO

Climaticclass constantdampheatacc.toIEC60068-2-78cyclicdampheatacc.toIEC60068-2-30

Degreeofprotection IP20,afterterminalscoveringIP40

Ambienttemperature °C -25…+60

Storagetemperature °C -25…+70

Temperaturerangeofthermalcompensationforoverloadrelease

°C -5…+40

Mechanicalandelectricalendurance op.c. 100.000

Max.operatingcycles op./h 25

Shockresistanceacc.toIEC68-2-27 g 20

Vibrationresistanceacc.toIEC68-2-6 5gatf=5…150Hz

Overvoltagecategory/pollutiondegree III/3

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Weight kg 0.252

MS25,MST25,MS20,MST20

Page 77: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

76

SWITCHSELECTIONFORMOTORPROTECTIONStandardmotorpower Settingrange

Single-phase Three-phase

220V230V240V

220V230V240V

380V400V415V

440V 500V 660V690V

kW A

0.02 0.06 0.1…0.16

0.06 0.06 0.06 0.09 0.16…0.25

0.06 0.09 0.12 0.12 0.18 0.25…0.4

0.09 0.12 0.18 0.25 0.25 0.4…0.63

0.06…0.09 0.09…0.12 0.18…0.25 0.25 0.37 0.37…0.55 0.63…1

0.12 0.18…0.25 0.37…0.55 0.37…0.55 0.55…0.8 0.75…1.1 1…1.6

0.18…0.25 0.37 0.75…1.1 0.75…1.1 1.1 1.5 1.6…2.5

0.37 0.55…0.8 1.1…1.5 1.5 1.5…2.2 2.2…3 2.5…4

0.55…0.75 1.1…1.5 2.2…2.5 2.2…3 3 4 4…6.3

1.1…1.5 1.5…2.5 3…4 4…5 4…5.5 5.5…7.5 6.3…10

2.2 3…4 5…7.5 5.5…9 7.5…9 11 10…16

3 5.5 9 11 11…12.5 15 16…20

5.5…7.5 11…12.5 12.5 15 18.5 20…25

TECHNICALDATA

MAIN

CIR

CU

IT

Designationofconnectionterminals 1−L1;3−L2;5−L3;2−T1;4−T2;6−T3

Terminalcapacity rigidS mm2

0.75…6

flexible 0.75…4

Screwwithself-liftingclamp,

protectedagainstfallingout

Screwhead PZ2

Tighteningtorque Nm 1.8

Max.operationalvoltage Ue V 690

Settingrange

A

0.1−0.16(onlyMS25);0.16−0.25(onlyMS25);0.25−0.4;0.4−0.63;0.63−1;1−1.6;1.6−2.5;2.5−4;

4−6.3;6.3−10;10−16;16−20;20-25

No.ofpoles 3

Operatingcurrentofthermaloverloadrelease

I1.05Ir<I≤1.20Ir

Ir….setvalue

Sensitivitytophasefailure yes

PowerdissipationonpoleatloadwithIn

P W2−2.5

Utilizationcategory acc.toIEC/EN60947-4-1 AC-3

acc.toIEC/EN60947-2 A

Tripclassacc.toIEC/EN60947-4-1 10A

MS25,MST25,MS20,MST20

Page 78: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

77

MST25motorprotectionswitchesandmax.back-upfusesforshort-circuitprotection:

TECHNICALDATAType Operating

currentofshort-circuit

release(A)

Ratedultimateshort-circuitbreakingcapacityIcu(kA)

Max.back-upfuse,ifIcp>Icu(gL) (A)

230V 400V 500V 690V 230V 400V 500V 690V

Icu Icu Icu Icu

MS25−0.16 2 50 50 50 50

Noback-upfuserequired

MS25−0.25 3 50 50 50 50

MS25−0.4 6 50 50 50 50

MS25−0.63 8 50 50 50 50

MS25−1 12 50 50 50 50

MS25−1.6 18 50 50 50 50

MS25−2.5 33 50 50 3 2.5 25 20

MS25−4 48 50 50 3 2.5 35 25

MS25−6.3 75 50 50 3 2.5 50 35

MS25−10 110 50 6 3 2.5 80 50 35

MS25−16 160 6 4 2.5 2 80 80 63 35

MS25−20 220 6 4 2.5 2 80 80 63 50

MS25−25 270 6 4 2.5 2 80 80 63 50

Type Max.back-upfuse

Ue<400VgL(A)

MST25−0.4 1

MST25−0.63 2

MST25−1 2

MST25−1.6 4

MST25−2.5 6

MST25−4 16

MST25−6.3 20

MST25−10 25

MST25−16 35

MST25−20 50

MST25−25 50

MS25motorprotectionswitches,ratedultimateshort-circuitbreakingcapacityIcuandmax.back-upfusesifprospectiveshort-circuitcurrentIcpexceedsIcu:

MS25,MST25,MS20,MST20

Page 79: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

78

PSAuxiliaryswitchforlateral

mountingPS11-withonemakeandonebreakcontactPS10-withonemakecontactPS01-withonebreakcontactPS20-withtwomakecontacts

U-Under-voltagereleaseA-Shuntrelease

Ratedinsulationvoltage Ui V 500

Thermalcurrent Ith A 6

RatedoperationalcurrentatAC-15

230V

Ie A

3.5

400V 2

500V 1.5

Terminalcapacity S mm2 0.75…2.5

Tighteningtorque Nm 1

Controlvoltages Uc V 24…600

Ratedfrequency f Hz 50or60

Coilconsumption switchon: W VA 4,3/7,5

operation: W VA 1,3/3,8

ACCESSORIES

MS25,MST25,MS20,MST20

RS-Trip-indieatingauxiliaryswitchand

Ratedinsulationvoltage Ui V 500

Thermalcurrent Ith A 6

RS Ratedoperational

currentatAC-15

230V

Ie A

3.5

400V 2

500V 1.5

Terminalcapacity S mm2 0.75…2.5

Tighteningtorque Nm 1

Page 80: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

79

O-41/55CP-41/55O-41/55

EnclosureIP41/55CP-41/55

FrontplateIP41/55

MS25orMST25withallaccessoriescanbebuiltintoanenclosureorafrontplate.

NAT-Emergencystoppush-button.Itisalsoavailablewithakey-lock.

ENCLOSURES

Z-Padlockingfeature

M-Push-buttondiaphragm

ThemanufactureralsosuppliesanenclosureandafrontplatewithdegreeofprotectionIP55(O-55,CP-55);inthiscasethediaphragmisalreadymounted.However,itshouldberemovedifapadlockingfeatureoranemergencystopbush-buttonisbuilt-in.

NL-NeutrallinkOne N/PE neutral link is usually built in theenclosure0-41/55orCP-41/55.Aplace foran additional neutral link is also available.

SS-Signallamp230,240,400VB-white,R-red,Z-green

MS25,MST25,MS20,MST20

Page 81: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

80

M25 M25

80 95,5

60

55

39

13

5

10

5

18

,5

M4

M4

IP55

Iskra

O-41/55

80

45

35

45

43

73,5

83

4

MS25,MST25,MS20,MST20

IP55

Iskra

85

80

69,6

12

9

CP-41/55

DIMENSIONS

1-pole 2-pole 3-pole

ORDERINGDATAMS25withthesettingrange2.5-4.0A:MS25-4Thesameswitchwithunder-voltagereleaseforcontrolvoltage380VwithanauxiliaryswitchwithtwoNOcontacts,builtintheenclosure,withanemergencystoppush-buttonandagreensignallampfor230V:MS25-4/U380/PS20/0-41/NAT/SSz230

CONNECTIONDIAGRAM

MS25,MST25,MS20,MST20

Page 82: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

81

• Versions: -MS32/MS18-withthermalandmagneticreleases -MSB32/MSB18-withathermalreleaseonly • Manualcontrol: -START,STOP,push-buttons-withatripindication (i.e.push-buttonsstayinthemiddleposition) • Automaticswitch-offatover-currentwiththermalormagnetic release • Controlwithunder-voltagereleaseorshuntrelease • Anauxiliaryswitchforsidemountingorflushmountingused forindicationoftheswitchingstate • Indicationofreleasewithtripindicatingauxiliaryswitch • ON/OFFbuttonspositionunequivocallyindicatesswitching positionofmaincircuitcontacts • Contactmaterial -Resistanttocontactwelding -Enableslowcontactheating • Isolatingdistancebetweencontacts:4.5mmpercontact place • Connectionofarigidorflexibleconductor • Assemblyto35mmwidemountingrailincompliancewith EN60715 • Verticalorhorizontaloperationalposition

TECHNICALDATA

GEN

ER

AL

Standards IEC/EN60947-2,IEC/EN60947-4-1,IEC/EN60947-5-1,IEC/EN60204,UL508,CSA22.2No.14

Approvals UL

Climaticclass constantdampheatacc.toIEC60068-2-78cyclicdampheatacc.toIEC60068-2-30

Degreeofprotection IP20,afterterminalscoveringIP40

Ambienttemperature °C -25…+60

Storagetemperature °C -25…+70

Temperaturerangeofthermalcompensationforoverloadrelease

°C -5…+40

Mechanicalandelectricalendurance op.c. 100,000

Max.operatingcycles op./h 25

Shockresistanceacc.toIEC68-2-27 g 20

Vibrationresistanceacc.toIEC68-2-6 5gatf=5…150Hz

Overvoltagecategory/pollutiondegree III/3

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage Uimp kV 6

Weight kg 0.279

MAIN

CIR

CU

IT

Designationofconnectionterminals 1−L1;3−L2;5−L3;2−T1;4−T2;6−T3

Terminalcapacity rigidS mm2

0.75…10

flexible 0.75…6

Screwwithself-liftingclamp,

protectedagainstdropout

Screwhead PZ2

Tighteningtorque Nm 2.0

MS32,MSB32,MS18,MSB18

Page 83: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

82

SWITCHSELECTIONFORMOTORPROTECTIONStandardmotorpowers Settingrange

Single-phase Three-phase

220V230V240V

220V230V240V

380V400V415V

440V 500V 660V690V

kW A

0.06 0.1…0.16

0.06 0.06 0.06...0.9 0.06...0.12 0.16…0.25

0.06 0.09 0.12 0.09...0.12 0.18 0.25…0.4

0.09 0.12...0.18 0.18 0.18 0.25 0.4…0.63

0.06…0.09 0.09…0.12 0.18…0.25 0.25...0.37 0.25...0.37 0.37…0.55 0.63…1

0.12 0.18…0.25 0.37…0.55 0.37…0.55 0.55…0.75 0.75…1.1 1…1.6

0.18…0.25 0.37 0.75 0.75…1.1 1.1 1.5 1.6…2.5

0.37 0.55…0.75 1.1…1.5 1.5 1.5…2.2 2.2…3 2.5…4

0.55…0.75 1.1…1.5 2.2 2.2…3 2.2...3 4 4…6.3

1.1…1.5 1.5…2.2 3…4 4 4…5.5 5.5…7.5 6.3…10

2.2 2.2…3 5.5 5.5…7.5 5.5…7.5 9...11 9…14

3 4 7.5 7.5...9 9...11 15 13…18

5.5 9...11 11 11 15...18.5 17…23

5.5...7.5 11 11 15 18.5...22 20...27

7.5 15 15 18.5 22 25...32

MS32,MSB32,MS18,MSB18

TECHNICALDATA

MAIN

CIR

CU

IT

MS32/MS18 MSB32/MSB18

Max.operationalvoltage Ue V 690 400

Settingrange A 0.1-0,16;0.16-0.25;0.25-0.4;0.4-0.63;

0.63-1;1-1.6;1.6-2.5;2.5-4;4-6.3;6.3-10;9-

14;13-18;17-23(onlyMS32);20-27(onlyMS32);25-32(onlyMS32)

0.25-0.4;0.4-0.63;0.63-1;1-1.6;1.6-2.5;2.5-4;4-6.3;6.3-10;9-

14;13-18;17-23(onlyMSB32);20-27(onlyMSB32);25-32(onlyMSB32)

No.ofpoles 3

Operatingcurrentofthermaloverloadrelease

I 1,05Ir<I≤1,20IrIr…currentsettingvalue

Sensitivitytophasefailure yes

Powerdissipationperpoleattheuppersettinglimit P W 2-2,5

Utilizationcategory acc.toIEC/EN60947-4-1 AC-3

acc.toIEC/EN60947-2 A

Tripclassacc.ToIEC/EN60947-4-1 10

Page 84: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

83

MSB32/MSB18motorprotectionswitchesandmax.back-upfusesforshort-circuitprotection:

Type Operatingcurrentof

short-circuitrelease

(A)

Ratedultimateshort-circuitbreakingcapacityIcu ,Ics(kA)

Max.back-upfuse,ifIcp>Icu(gL)(A)

230V 400V 500V 690V 230V 400V 500V 690V

Icu Ics Icu Ics Icu Ics Icu Ics

MS32−0.16 MS18-0.16 2 100 100 100 100 100 100 100 100

Noback-upfuserequired

MS32−0.25 MS18-0.25 3 100 100 100 100 100 100 100 100

MS32−0.4 MS18-0.4 5 100 100 100 100 100 100 100 100

MS32−0.63 MS18-0.63 8 100 100 100 100 100 100 100 100

MS32−1 MS18-1 13 100 100 100 100 100 100 100 100

MS32−1.6 MS18-1.6 22 100 100 100 100 100 100 100 100

MS32−2.5 MS18-2.5 33 100 100 100 100 100 100 5 5 16

MS32−4 MS18-4 55 100 100 100 100 100 100 3 3 25

MS32−6.3 MS18-6.3 84 100 100 100 100 6 4.5 3 2 35 35

MS32−10 MS18-10 126 100 100 100 100 6 4.5 3 2 50 35

MS32−14 MS18-14 170 25 12.5 25 12.5 6 4.5 3 2 80 63 50 50

MS32−18 MS18-18 230 25 12.5 25 12.5 6 4.5 3 2 80 63 50 50

MS32−23 270 25 12.5 25 12.5 4 3 3 2 80 80 50 50

MS32−27 360 25 12.5 25 12.5 4 3 3 2 80 80 50 50

MS32−32 400 25 12.5 25 12.5 4 3 3 2 80 80 50 50

Type Max.back-upfuse

Ue<400VgL(A)

MSB32−0.4 MSB18−0.4 2

MSB32−0.63 MSB18−0.63 2

MSB32−1 MSB18−1 4

MSB32−1.6 MSB18−1.6 6

MSB32−2.5 MSB18−2.5 6

MSB32−4 MSB18−4 10

MSB32−6.3 MSB18−6.3 16

MSB32−10 MSB18−10 25

MSB32−14 MSB18−14 25

MSB32−18 MSB18−18 35

MSB32−23 35

MSB32−27 50

MSB32−32 50

MS32motorprotectionswitches,ratedultimateandserviceshort-circuitbreakingcapacityIcuandIcs,andmax.back-upfusesifshortcircuitcurrentIcpexceedsIcu:

MS32,MSB32,MS18,MSB18

Page 85: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

84

HO-41/55 - EnclosureIP41/55 FP-41/55 - FrameIP41/55 P-41/55 -FrontplateIP41/55

E - Emergencystoppush-buttonavailablealsowithakey-lock.

HZ - Padlockingfeature

M - Push-buttondiaphragm Themanufactureralsosuppliesanenclosure,aframeandafrontplatewith degreeofprotectionIP55(HO-55,FP-55,P-55)wherethediaphragmisalreadyinserted.However,itshouldbe removedifapadlockingfeatureoranemergencystopbush-buttonisbuilt-in.

NL - NeutrallinkOneN/PEneutrallinkisalreadymountedintheenclosuresHO-41/55orframesFP-41/55.Aplaceforanadditionalneutrallinkisalsoprovided.

SS - Signallamp(B-white,R-red,Z-green)

TheMS32orMSB32motorprotectivecircuitbreakerwithallaccessoriescanbebuiltinanenclosureorunderaframeandafrontplate

ACCESSORIES

ACCESSORIESUSEDFORALLENCLOSURES

MS32,MSB32,MS18,MSB18

Page 86: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

85

HS-AuxiliaryswitchHS11-with1makeand1breakcontactHS10-with1makecontactHS20-with2makecontacts

HSV -Auxiliarycontactblock*HRS - Tripindicatingcontact

block**HSV10-with1makecontactHSV01-with1breakcontactHRS10-with1makecontactHRS01-with1breakcontact

AUXILIARYSWITCHFORSIDEMOUNTINGHS,AUXILIARYCONTACTBLOCKHSV,TRIPINDICATING CONTACTBLOCKHRS

PP -Sealingplate

UR -Under-voltagerelease AR -Shuntrelease

Controlvoltages Uc V 24…600

Ratedfrequency f Hz 50or60

Terminalcapacity S mm2 0.75…2.5

Tighteningtorque Nm 1

UNDER-VOLTAGERELEASEURANDSHUNTRELEASEAR

Ratedinsulationvoltage Ui V 500

Thermalcurrent Ith A 5

Electricalratingacc.toIEC/EN60947-5-1

B300 AC-15 Ue V 240

Ie A 1,5

R300 DC-13 Ue V 250

Ie A 0,1

Terminalcapacity S mm2 0,75…2,5

Tighteningtorque Nm 1

Ratedinsulationvoltage Ui V 300

Thermalcurrent Ith A 1

Electricalratingacc.toIEC/EN60947-5-1

B300 AC-15 Ue V 240

Ie A 1,5

R300 DC-13 Ue V 125

Ie A 0,22

Terminalcapacity S mm2 0,75…2,5

Tighteningtorque Nm 1

MS32,MSB32,MS18,MSB18

*HSVcontactremainsinitsnormalpositionwhenMS32/MS18isinOFF ortripposition

**HRScontactchangesstatefromitsnormalpositionwhenMS32/MS18 tripduetooverload,short-circuitormanualdepressionoftheTESTlever

Page 87: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

86 HO-41/55

45

17

,5

89

,5

5,4 45,3

63,4

73,1

45

933,4

48,4

66

45

89

,5

15

3,4

12

2

68

55

M4

18

89

,5

45

48.4

66

69,6

85

129

100

80 R4

70+2

116+

2

2...6

70+2

110

M4

64

43+1

45°

99+

1

116+

2

6...20

45

17

,5

89

,5

5,4 45,3

63,4

73,1

45

933,4

48,4

66

45

89

,5

15

3,4

12

2

68

55

M4

18

89

,5

45

48.4

66

69,6

85

129

100

80 R4

70+2

116+

2

2...6

70+2

110

M4

64

43+1

45°

99+

1

116+

2

6...20

FP-41/55

MS32/MS18,MSB31/MSB18Motorprotectionswitch

AuxiliaryswitchHS Under-voltagereleaseURShuntreleaseAR

CONNECTIONDIAGRAM

DIMENSIONS

1-pole 2-pole 3-pole

MS32,MSB32,MS18,MSB18

Page 88: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Motorprotectionswitches

87

MS32...MS18...

MSK07

K07...

MS32...

MSKNL22

KNL22,KNL30...

MS32...MS18...

MSKNL9

KNL9...-KNL18...

MSK07,MSKNL9andMSKNL22adaptersareusedforconnectingamotorprotectionswitchwithacontactorform-ingasingle-unitstarterforquickassemblytoa35mmwidemountingrail(EN60715).

AdapterforconnectingMS32/MS18motorprotectionswitchwith

K07minicontactor

AdapterforconnectingMS32/MS18motorprotectionswitchwith

KNL9-KNL18contactor

AdapterforconnectingMS32motorprotectionswitchwith

KNL22,KNL30contactor

CONNECTIONBLOCKS

Page 89: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

88

xIn

t(s)

Numberofpoles 1+NTrippingcharacteristic B,C,DRatedcurrent A 2,6,10,16,20,25,32Ratedvoltage V 230Ratedfrequency Hz 50Ratedshort-circuitcapacity kA 4.5Terminalcapacity mm2 1-10Mountingto35mmwidemountingrailaccordancewithEN60715Ambienttemperature °C -5...+40

TRIPPINGCHARACTERISTICS

TECHNICALDATA Changedratedvaluesregardingambienttemperature Ratedcurrent Ambienttemperature (A) -10°C 0°C 10°C 20°C 30°C 40°C 50°C 60°C 2 1.18 1.14 1.09 1.05 1 0.96 0.90 0.86 6 1.17 1.13 1.09 1.04 1 0.96 0.91 0.84 10 1.21 1.16 1.10 1.06 1 0.94 0.88 0.82 16 1.18 1.13 1.09 1.04 1 0.94 0.91 0.84 20 1.17 1.13 1.09 1.04 1 0.96 0.91 0.84 25 1.18 1.13 1.09 1.04 1 0.96 0.91 0.84 32 1.17 1.13 1.09 1.04 1 0.96 0.91 0.84

DIMENSIONS CONNECTIONDIAGRAM

Trip

ping

tim

e

Ratedcurrent

RI20

Page 90: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

89

• RI50isusedfortheprotectionofinstallationsanddevices(overloadandshortcircuit),andasadisconnectorincaseofelectricshock

• Simpleandquickfixingtoa35mmmountingrailinaccordancewithEN60715

• Lowlet-throughenergyundershort-circuitconditionsensureslongerlifeofcontactsandreducesthermalstressesinthedistributioncircuit

• RI50reducestheenergylossduetoauniquecontactconfigurationandreductionofhotspots.WattlossperpoleforRI50isfarlowerthanthatspecifiedinIEC/EN60898

• Anoptionaloperatingposition

• IP20degreeofprotection;IP40degreeofprotectionafterinstallationinadistributionbox

• Anadditionalcolourindicationofthepositionofmaincontacts(red:contactsclosed;green:contactsopen)

TypesRI51 single-poleRI51N single-pole+neutralpoleRI52 two-poleRI53 three-poleRI53N three-pole+neutralpoleRI54 four-pole

TECHNICALDATAStandards IEC/EN60898

Approvals SEMKO,GOST-R

No.ofpoles 1,2,3,4,1+N,3+N

Trippingcharacteristic(IEC/EN60898) B,C

Ratedvoltage singlepole

multi-pole

Un V

230/400AC

400AC

Insulationvoltage Ui V 500

Impulsewithstandvoltage(1,2/50µs) Uimp kV 4

Ratedfrequency f Hz 50/60

Ratedcurrent In A6−63(characteristicB)

0.5−63(characteristicC)

Ratedshort-circuitcapacity Icn kA 10

Selectivityclass 3

Terminalcapacity S mm2 upto25

Ambienttemperature °C −5…+40

RI50

Page 91: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

90

DIMENSIONS-Novaslika

TRIPPINGCHARACTERISTIC

B,C(EN60898)

RI50

Page 92: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

91

ORDERINGDATA RI61 - B - 16

RatedcurrentIn(A)TrippingcharacteristicType

•RI60isusedforover-current(overloadandshort-circuit)protectionofinstallationsanddevices,andasadisconnectorincaseof electricshock•RI60miniaturecircuitbreakersareprovidedwithtwospringsfor assemblytoa35mmwidemountingrail(EN60715).Thesprings enablesimpletakingoffirrespectiveofwhetherabusbaris positionedbeloworabove•Specialspringsareavailableforfixingminiaturecircuitbreakerswith twoM5screws•AhandlecanbesealedinONorOFFposition•Optionaloperationposition•DegreeofprotectionIP20;degreeofprotectionIP40after installationinadistributionbox•Additionalcolourindicationofthepositionofmaincontacts(red-contactsclosed;green-contactsopen)

TypesRI61 single-poleRI61N single-pole+neutralpoleRI61J single-pole(forDCcircuits)RI62 two-poleRI62J two-pole(forDCcircuits)RI63 three-poleRI63N three-pole+neutralpoleRI64 four-pole

TECHNICALDATAAC DC

Standards IEC/EN60898,IEC/EN60947-2

Approvals VDE,GOST-R

No.ofpoles 1,2,3,4,1+N,3+N 1.2

Trippingcharacteristic(IEC/EN60898) B,C,D,M C,M

Ratedvoltage Un V 230/400 -

RatedDCvoltageUn V

max.40-1polefort=15ms

440-2-pole220-1-pole

Ratedinsulationvoltage Ui V 500

Ratedfrequency f Hz 50/60 -

Ratedcurrent In A 0.2to63

Short-circuitcapacity Icn kA 10 4.5

Selectivityclass 3

Terminalcapacity CuS mm2

1.5…25

Al 2.5...25

Ambienttemperature °C −25…+55

Vibrationresistance 3g(8-50Hz)

RI60

Page 93: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

92

B,C,D(EN60898)

In≥10A

nazna~enitok xIn

izkl

opni

~as

t(s)

AUXILIARYANDSIGNALCONTACTS•TheyareusedwithRI60miniaturecircuitbreakersandRV60disconnectionswitches(0.5modulewidth).•DeliveredasasingleunitorwithRI60orRV60,respectively;mountedontheleftsidebymeansofpinsandscrew.•Serveforsignallingofcontactpositionofthebreaker•DegreeofprotectinIP20•Types: - PKJ,2PKJ−oneortwoauxiliarychangeovercontacts;positionofcontactscorrespondstothepositionof themaincontactsofthebreaker - PKJ+SKJ−oneauxiliarychangeovercontactandonesignalchangeovercontact(faultindicatingcontact) - PKJ+SKJ+TEST−testbuttonwithtwofunctionsisadded:signallingthepositionofsignalcontactsand testingofcontrolcircuit(non-stablechangeofpositionofthecontacts)byslightmovementofpush-button upwardsanddownwardswithoutchangeofcontactpositionofthebreaker

*Connectionoftwoauxiliarycontactsinseriesat220V

ACCESSORIES

Standards IEC/EN60947-5-1 Ratedinsulationvoltage Ui V 400 Ratedoperationalvoltage Ue V 230 Ratedthermalcurrent Ith A 16 Ratedoperationalcurrent AC-15 Ie A 4(Ue=230V) DC-13 0.5(Ue=110V)* Terminalcapacity S mm2 0.5...2.5

TRIPPINGCHARACTERISTIC

TECHNICALDATA

ratedcurrent

trip

ping

tim

e

RI60

Page 94: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

93

•UsedwithRI60miniaturecircuitbreakersandRV60disconnectionswitches.• Enablesremoteswitch-off.•AvailableasasingleunitortogetherwithRI60orRV60;mountedonthetherightsidebymeansofpinsandscrew.

•UsedwithRI60,RI120miniaturecircuitbreakersandRV60,RV120disconnectionswitches;•Protectionoftheloadintheeventofvoltagedrop(between85%and35%ofitscontrolvoltage);uncontrolledrestartingis prevented;• Indicationofreleasepositiongreen/red;•Mountedontherightsideofthebreaker;• Testbuttonforthecorrectfunctioncontrol;•DegreeofprotectionIP20

Busbar-universal (forone-polecircuitbreakersandone-polecircuitbreakerswithanauxiliaryswitch)

DesignationLength(m)Cross-section(mm2)G-1L-210/12iso0.21 12G-1L-1000/12iso1 12G-2L-1000/10 1 12

Busbar-fork-type,3-phase (forthree-polecircuitbreakersandone-polecircuitbreakersinthree-phasecircuits)

DesignationLength(m)Cross-section(mm2)G-3L-1000/10C1 10G-3L-1000/16C1 16G-4L-1000/16 1 16

TECHNICALDATAStandards IEC/EN60947-1

Controlvoltages ACUc V

12,24,48,60,110,230,400

DC 24,48,110

Rangeofcontrolvoltage

Uc % 70…110

Max.trippingcurrent(atcoilvoltage)

ACA(V)

6(12);2.8(24);0.8(48);0.9(60);0.5(110);0.6(230);0.5(400)

DC 3(24);2(48);0.6(110)

Ratedfrequency f Hz 50

Trippingtime ms <50

Terminalcapacity S mm2 1.5…6

TECHNICALDATAStandards IEC/EN60947-1Controlvoltage Uc V 24,48,120,230,400Ratedfrequency f Hz 50

Coilpowerconsumption W 3

Mechanicalendurance op.c. 10,000

Terminalcapacity S mm2 0.75…2,5

SHUNTTRIPRELEASEVC

UNDERVOLTAGERELEASEPC60

OTHERACCESSORIES

RI60

Page 95: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

94

3-pole+N

1-pole+N 2-pole

4-pole

3-pole

2-pole1-pole12 14 1

211 11 2

1

95

96 98 12 14

PKJ 2PKJ,PKJ+SKJ

RI60,RV60

PC60

59

59

4317.5

84 45

DIMENSIONS

Endcaps(forthree-phasebusbars)

DesignationCross-section(mm2)EK-C-3/1010EK-C-2+3/1616

CONNECTIONDIAGRAM

AUXILIARYCONTACTSAC DC

RI60

Page 96: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

95

• Theyareusedforprotectinghouseandindustrial installations.• RI120miniaturecircuitbreakersareprovidedwithtwo springsforassemblytoa35mmwidemountingrail inaccordancewithEN60715.Thespringsenable simpletakingoffirrespectiveofwhetherabusbar ispositionedbeloworabove.• AhandlecanbesealedinONorOFFposition.• Optionaloperationposition.• DegreeofprotectionIP20;degreeofprotection IP40afterinstallationinadistributionbox.

TECHNICALDATAStandards IEC/EN60898-1

No.ofpoles 1,2,3,4,1+N;3+N

Trippingcharacteristic B,C,D

Ratedvoltage Un V 230,230/400,400

RatedDCvoltageUn V

max.110−1pole

forT1=4ms

Ratedisulationvoltage Ui V 690V

Ratedfrequency f Hz 50/60

Ratedcurrent In A 40,50,63,80,100,125

Short-circuitbreakingcapacity kA 10(15)*

Selectivityclass 3

Ambienttemperature °C -5...+40

Terminalcapacity S mm2 2.5...50

Accessories ShunttripreleaseVC

RI120

*optional

Page 97: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

96

DIMENSIONS

TRIPPINGCHARACTERISTIC

D

trip

ping

tim

e

ratedcurrent xIn

t(s)

B,C,D(EN60898)

RI120

27

100

78 100

118,

5

45 115

78100

78100

78

54 81

108

44

60

68

74

Page 98: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

MiniatureCircuitBreakers

97

DISCONNECTIONSWITCHRV60-TECHNICALDATA

•Theyareusedasmainswitchesinhousedistributionboxesoras switchesforindividualelectriccircuits.•AhandlecanbesealedinONorOFFposition.•Assemblyto35mmwidemountingrailinaccordancewithEN60715.•Optionaloperationposition.•DegreeofprotectionIP20;degreeofprotectionIP40afterinstallationin adistributionbox.•Additionalcolourindicationsofthepositionofmaincontacts(red−contactsclosed,green−contactsopen).•ExternaldimensionsofRV60andRV120disconnectionswitches matchwithdimensionsofRI60orRI120miniaturecircuitbreakers.

DISCONNECTIONSWITCHRV120-TECHNICALDATA

•Assemblytoa35mmwidemountingrailinaccordancewithEN60715•Optionaloperationposition•DegreeofprotectionIP20,degreeofprotectionIP40afterinstallation inadistributionbox

Standards IEC/EN60947-5-1No.ofpoles 1Ratedvoltage AC DC

Un V 24,48,110,23024,48,110,220

Lightsource highcapacityLEDdiodeLightsourcecapacity W 0,8Colours green-G,red-R,blue-B,transparent-T,yellow-YIllumination constant-RS,blinking-RSBTerminalcapacity S mm2 0,75…6Ambienttemperature °C −25…+55

SIGNALLAMPRS,RSB

TECHNICALDATA

RV60,RV120,RS

Standards IEC/EN60947-3No.ofpoles 1,2,3,1+N,3+NRatedvoltage Un V 230/400Ratedfrequency f Hz 50/60Ratedcurrent In A 25,63Utilizationcategory AC-22ARatedconditionalshort-circuitcurrent kA

3(RV6063Awith63AgGback-upfuse)6(RV6063Awith35AgGback-upfuse)10(RV6025Awith25AgGback-upfuse)

Terminalcapacity S mm2 seepage70Ambienttemperature °C -25…+55Vibrationresistance 3g(8−50Hz)Accessories SeeaccessoriesforRI60miniaturecircuitbreaker

Standards IEC/EN60947-3No.ofpoles 1,2,3,1+N,3+NRatedvoltage Un V 230/400Ratedinsulationvoltage Ui V 690Ratedimpulsevoltage Uimp V 6000Ratedfrequency f Hz 50Ratedthermalcurrent Ith A 125Ratedcurrent In A 100(forutilizationcategoryAC-22A),40(forutilizationcategoryAC-23A)Ratedconditionalshort-circuitcurrent kA 3(with100AgGback-upfuse),6(with63AgGback-upfuse)Electricalendurance op.c. 1500Mechanicalendurance op.c. 10000Terminalcapacity S mm2 2,5…50Ambienttemperature °C −25…+55Vibrationresistance 3g(8-50Hz)

Page 99: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Accessories

98

• Transparentorwhitedoor• AdditionalterminalsforPE-andN-conductors• No.ofmodulesfrom4to36• ProtectionclassII• DegreeofprotectionIP40

TECHNICALDATAType INO-4 INO-12 INO-18 INO-24 INO-36

IPO-4 IPO-12 IPO-24 IPO-36

Standards IEC60670-24

Ratedvoltage Un V 400

Max.powerdissipation INOW

12 22 22 24 26

IPO 14 22 24 26

No.ofmodules 4(+4) 12 18 24 36

PE-andN-conductorterminals 2x8 2x10 2x13 2x13 2x15

Ambienttemperature °C −20…+70

Dimensions INOmm

215x263x112 287x236x112 396x236x112 287x361x112 287x482x112

IPO 211x232x70 283x232x70 283x357x70 283x482x70

SURFACEMOUNTED(INO)andFLUSHMOUNTED(IPO)COMPACTDISTRIBUTIONBOARDS

Page 100: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

ResidualCurrentCircuitBreakers

99

•Residualcurrentcircuitbreakers(RCCB)areusedforprotectionagainstindirectcontact,fireprotectionand additionalprotectionagainstdirectcontact.•Theyaresuitableforisolation.•Nooverloadprotectionorshort-circuitprotectionisbuiltinRCCB.•Twoversionsaccordingtobehaviourinpresenceofd.c.components: -TypeA(markedNFI)-sensitivetoalternatingandpulsatingd.c.residualcurrents. -TypeAC(markedFI)-sensitivetoalternatingresidualcurrentsofsineform.•Assemblytoa35mmwidemountingrailinaccordancewithEN60715.•Optionaloperationposition.•DegreeofprotectionIP20,degreeofprotectionIP40afterinstallationinadistributionbox.•Additionalcolourdisplayofthepositionofmaincontacts(red-contactsclosed,green-contactsopen).•Aterminalshapepreventsconnectionofaconductoroutsidetheconnectionarea.•Specialversions:

- Type S:aswitchwithdelayedbreakenablingselectivityregardingageneraltypeandashort-timedelayedtype(typeG)connectedontheloadside.Breaktimeislongerthan40ms.Theswitchesexcelinhighresistancetosurgecurrents(upto3kA),whichpreventsunwantedtrippings.Theirratedcurrentsarefrom25to100A,andratedresidualoperatingcurrentsare100,300and500mA.ThisistypeA,andacustomercanchoosebetweenNFI2Stwo-poleandNFI4Sfour-poleswitches.

- Type G:ashort-timedelayedbreakingcharacteristic(min.non-actuatingperiodis10ms).Theswitchesareresistanttounwantedtrippingsatcurrentimpulsesorwhenbuilt-ininspecialcriticalconditions.Theyexcelinhighresistancetosurgecurrents(upto3kA)andareliableoperationincaseofhighmakingcurrents.Ratedcurrentsarefrom25to100A,andratedresidualoperatingcurrentsare30,100,300and500mA.ThisistypeA,andacustomercanchoosebetweenNFI2Ktwo-poleandNFI4Kfour-poleswitches.VersionsSandGcomplywiththeEN61008standard.Regardingtrippingtimes,typeGalsocomplieswithÖVE/ÖNORME8601(supplementtoÖVEEN61008).BothtypesareVDEapproved.

- FIR – FIT combination:Itisusedfortheprotectionincircuitswhereoperationalcurrentsarehigherthatratedcurrentsofresidualcurrentcircuitbreakers.AnactuatingrelayFIRisseparatedfromaFItransformer(FIT).Thefunctionofloadswitchingisperformedbythecontactororacircuit-breakerwithanundervoltagerelease.Acombinationratedcurrentthereforedependsonselectedswitchingdevices.Itislimitedwithcablecross-sectionswhichcanbeinsertedthroughtheholeoftheFItransformer.Rateddifferentialcurrentsare0.3A,0.5A,1Aand2A.

FI,NFI

Page 101: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

ResidualCurrentCircuitBreakers

100

FI2,NFI2 FI4,NFI4,FIR FIT

FI2 - 25 /0,03 NFI4 - 40 /0,3

Asealingcoverfortwo-pole(SCNFI2)andfour-pole(SCNFI4)switches

ORDERINGDATA

RatedresidualoperatingcurrentIΔn(A)RatedcurrentIn(A)Type

ACCESSORIES

DIMENSIONS

FI,NFI

TECHNICALDATATypeAC

A

A-G

A-S

FI2

NFI2

NFI2K

NFI2S

FI4

NFI4

NFI4K

NFI4S

Standards IEC/EN61008,typeA-Gacc.toÖVEE8601

Approvals VDE,NF,GOST-R

No.ofpoles 2 4

Ratedvoltage Un V 230 230/400

Ratedimpulsevoltage Uimp kV 4

Ratedfrequency f Hz 50

Ratedcurrent In A 16,25,40,63,80,100 25,40,63,80,100

Ratedresidualoperatingcurrent IΔn mA 10(In=16,25A),30,100,300,500 30,100,300,500

Ratedmakingandbreakingcapacity

=RatedresidualmakingandbreakingcapacityIm=IΔm A

800(In=16-80A)

1000(In=100A)

Max.back-upfuseforshort-circuitcurrent

Iv A

63(In=16-40A)

80(In=63,80A)

100(In=100A)

Ratedconditionalshort-circuitcurrent Inc kA 10

Terminalcapacity S mm2 1…35

Max.trippingtimes,typesAC,A ms 1xIΔn:≤300ms;5xIΔn:≤40ms

Responsetimedelay,typesA-G,A-Sms

typeA-G-1xIΔn:10ms<T≤300ms;5xIΔn:10ms<T≤40mstypeA-S-1xIΔn:130ms<T≤500ms;5xIΔn:50ms<T≤150ms

Ambiemttemperature °C −25…+40

Storagetemperature °C −35…+60

Weight kg 0.23 0.39

Tighteningtorque Nm 2.0

Page 102: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

ResidualCurrentCircuitBreakerswithovercurrentprotection

101

•RFI2isacombinationofaresidualcurrentcircuitbreaker andaminiaturecircuitbreaker(RCBO)• Abuilt-inprotectionagainstoverloadandshort-circuit•RFI2maybeusedtoprovide:-faultprotection(protectionagainstindirectcontact)-protectionagainstfire-additionalprotectionagainstdirectcontact• TheswitchistypeAwhichmeansthatitissensitiveto alternatingandpulsatingd.c.residualcurrents• SealinginONorOFFposition• Assemblytoa35mmwidemountingrailinaccordance withEN60715•Optionaloperationposition•DegreeofprotectionIP20,degreeofprotectionIP40after installationinadistributionbox•Additionalcolourindicationofthepositionofmaincontacts (red-contactsclosed,green-contactsopen)

RFI2

TECHNICALDATATypeA RFI2

Standards IEC/EN61009

Approvals VDE,GOST-R

No.ofpoles 2

Trippingcharacteristic B,C

Ratedvoltage Un V 230

Ratedimpulsevoltage Uimp kV 4

Ratedfrequency f Hz 50

Ratedcurrent In A 6,10,16,20,25,32,40

Ratedresidualoperatingcurrent IΔn mA 10(In=6-25A),30,100,300,500

Ratedshort-circuitcapacity kA 10

Selectivityclass 3

Terminalcapacity S mm2 1.5…25

Ambienttemperature °C −25…+40

Storagetemperature °C −35…+60

Tighteningtorque Nm 2.0

Accessories Auxiliaryandsignalchangeovercontacts

Page 103: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

ResidualCurrentCircuitBreakers

102

CONNECTIONDIAGRAM

DIMENSIONS

ORDERINGDATA

RFI2 - B - 16 /0,03

RatedresidualoperatingcurrentIΔn(A)RatedcurrentIn(A)Trippingcharacteristic(BorC)Type

Trip

ping

tim

e

Ratedcurrent xIn

t(s)

In=6-40A

TRIPPINGCHARACTERISTIC

B,C(EN60898)

RFI2

Page 104: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

103

DIMENSIONS

They are mainly used for start-up, overload protection andswitch-offofelectricmotorsandalsoforotherloads.Acontac-torandacorrespondingbimetalrelayarebuiltintheenclosureof degree of protection IP55. They are switched onwith theONpushbuttonandswitchedoffwiththeOFFpushbutton.Themushroompushbuttonfunctionsasanemergencystoppush-button.

Corresponding back-up fuses should be built in a circuit infrontofanautomaticcontactorfortheprotectionagainstshort-circuit.TheKPLstartersarenotprovidedwithoverloadprotec-tion,whileKMPLstartersare.

TECHNICALDATA Typeofdirectstarterwithoutoverloadprotection KPL9 KPL12 KPL16 KPL18 KPL22

Typeofdirectstarterwithoverloadprotection KMPL9 KMPL12 KMPL16 KMPL18 KMPL22

Correspondingthermaloverloadrelay BR16,BR30

Standards IEC/EN60947-4-1

Ratedinsulationvoltage Ui V 690

Max.permittedpowersof 230V 2.2/3 3/4 4/5.5 4/5,5 5.5/7.5

three-phasemotorsatAC-3 400V 4/5.5 5.5/7.5 7.5/10 9/10 11/15

500V 5.5/7.5 5.5/7.5 7.5/10 9/10 11/15

690V 5.5/7.5 7.5/10 7.5/10 9/10 11/15

Max.back-upfuseforshort-circuitprotectiongL A 25 25 35 35 50

Coordinationtype2

Rangeatcontrolvoltage Uc % 85…110

Max.operatingfrequency op.c./h 15

Degreeofprotection IP55

Ambienttemperature °C -20…+40

Terminalcapacity rigid 0.75...6 2.5...10

flexible 0.5...6 1.5...10

PmkW/

HP

S mm2

KMPLANDKPLDIRECTON-LINESTARTERSKMPL9, KMPL12, KMPL16, KMPL18, KMPL22, KPL9, KPL12, KPL16, KPL18, KPL22

Page 105: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

104

TECHNICALDATA

Permittedmotorpower

Startertype Relaytype 230V 400V 500V

kW HP kW HP kW HP

ZK12 BR16/8,5-12,5 4 5.5 7.5 10 7.5 10

ZK16 BR16/12,5-18 5.5 7.5 11 15 11 15

ZK18 BR16/15-20 5.5 7.5 15 20 15 20

ZK22 BR30/17-24 8 11 18.5 25 18.5 25

ZK30 BR30/22-30 12.5 17 25 34 25 34

ZK43 BR43/30-43 20 27 37 50 45 60

ZK63 BR43/40-63 25 34 55 75 65 88

ZK95 BRA180/75-125 40 54 75 100 100 136

ZK115 BRA180/90-150 63 86 110 150 147 200

ZK145 BRA180/120-200 80 108 132 180 185 252

ZK180 BRA180/120-200 92 125 160 220 210 272

Allrequiredelementsforstart-up,overloadprotectionandswitch-offofasynchronouselectricmotorsarebuiltintheenclosureofdegreeofprotectionIP55.

ZKSTAR-DELTAMOTORSTARTER

Page 106: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

105

Theyaremainlyusedforstart-upandswitch-offofelectricmotorsupto11kWpower.MS25motorprotectionswitchwithundervoltagereleaseandacorresponding contactor are built in the enclosure of degree of protectionIP55.Theadvantagesofcombinationstartersoverdirectstartersare:• itisnotnecessarytobuildinback-upfusesforprotectionagainst short-circuituptoratedmotorpower1.5kWat400V• aftereachoverloadandpowerlinefailuretheautomaticswitch-onisnot possible

TECHNICALDATAType AC-3Ratedoperationalpower(kW)

230V 400V 500V 690V

K0-LD7 3 5.5 5.5 5.5

KNL-LD9 2.2 4 5.5 5.5

KNL-LD12 3 5.5 5.5 7.5

KNL-LD16 4 7.5 7.5 7.5

KNL-LD18 4 9 9 9

KNL-LD22 5.5 11 11 11

KNL-LD30 7.5 15 15 15

TECHNICALDATATypeofcombinationstarter KMSPL3 KMSPL9 KMSPL12 KMSPL16 KMSPL18 KMSPL22

Typeofmotorprotectionswitch MS25-6,3 MS25-10 MS25-16 MS25-16 MS25-20 MS25-25

Settingrangeofbimetalrelease 4…6,3 6,3…10 10…16 10…16 10…16 20…25

AC-3,max.permittedpowers 230V

Pm kW

1.5 2.2 3 4 4 5.5

ofthree-phasemotors 400V 2.2 4 5.5 7.5 9 11

500V 3 5.5 5.5 7.5 9 11

690V 4 5.5 7.5 7.5 9 11

KO-LD,KNL-LDCOMBINATIONSFORREVERSING

KMSPLCOMBINATIONSTARTERS

Page 107: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

106

D120

D121

Todefinethestarter,thefollowingdatahavetobeknown:•motorpower,operationalcurrent•coilcontrolvoltage•requiredpushbuttons(none,start,stop,reset)•mainswitch(yesorno)Basedonthesedata,aconvenientcontactorandanoverloadrelayaswellascorrespondinglyequippedenclosureareselected.YoucanchoosebetweenoverloadrelayBR16/30.

COMPONENTSELECTION

DIRECTON-LINESTARTERSUPTO30A

D1 ...0,1,2... ...0,1,2,3 ...S,M

ORDERINGDATA

S-forKNL9-KNL16,M-forKNL22,KNL30Mainswitch(0-none,1-25A,2-32A)

Pushbuttons(0-none,1-resetpushbutton,2-start&stop)Enclosuresize

Enclosures:IP66,ametalbasewithapolycarbonatecover

*Standardcontrolvoltages(50/60Hz)B7 24VF7 110/125VM7 220/240VQ7 380/415VOthercontrolvoltagesonrequest.**NDL6-11snap-onauxiliaryswitchblockincluded.

Settingrangeforthermaloverloadrelay

KindofthermaloverloadrelayBR Controlvoltage

Permitted motor power Thermal overload relay BR16/30Direct-on contactor*

Enclosure

400/415 V, three-phase Operational current (A) Push-button arrangement Main switch Ordering code

kW HP min.-max

BR

16/K

NL1

8

0.06 0.08 0.16 - 0.25

KNL9

start & stop

reset

none

D120S**

D110

D100

0.12 0.16 0.25 - 0.4

0.18 0.25 0.45 - 0.63

0.25 0.33 0.75 - 1

0.55 0.75 1.1 - 1.6

1.1 1.5 2.3 - 3.2

1.5 2 2.9 - 4

start & stop

reset

none

with main switch

D121**

D111

D101

2.2 3 4.5 - 6.3

4 5.5 7.2 - 10

5.5 7.5 9 - 12.5 KNL12

7.5 10 11.3 - 16 KNL16

9 10 15 - 20 KNL18

BR

30/K

NL3

0 11 15 17.5 - 21.5 KNL22

start & stop

D120M**

reset D110

none D120M

15 20 24.5 - 30 KNL30

start & stop

with main switch

D122**

reset D112

none D102

Page 108: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

107

pomik

Connectionforthree-phasethree-wiresystem-asshownabove

Connectionforfour-wiresystem:1.Removeconnection1(L1)-A12.ConnectaneutralconductortoA1terminal

Connectiondiagram

Connectionforremotestart-inch-stopcontrol

Connectionforremotepush-buttoncontrol:

1.Removeconnection96-642.Connectasillustrated

KNL9-KNL30direct-on-linestarters

Connectionforremotepilotswitchcontrol

Connectionforremotecontrolwithselectionswitch,

manual-0-automatic

Connectionforsingle-phasemotors

WIRINGDIAGRAMS

KNL9-KNL30direct-on-linestarters

Page 109: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

108

Anenclosureforcontactorsanddirect-on-linestarters(sizeD1)

DIMENSIONS

IP66 A B C D E F G H J K L

KNL9-KNL30(enclosureD1) 212 124 146 164 76 117 132.5 - 29.5 3x20 5.5

KNL9-KNL30+mainswitch(enclosureD1)

212 124 156 164 76 117 132 146 29.5

3x20 3x5.5

HolesforcableinletswithKdiameter,topandbottom

FixingholeswithLdiameter

DIRECTON-LINESTARTERSUPTO30A

Page 110: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

109

R420

R221

RS9

R2,R4 ...0,1,2... ...0,1,2 ...S,M -....

Todefine thestarter, the followingdatahave tobeknown:•motorpower,operationalcurrent•coilcontrolvoltage•requiredpushbuttons(none,I,II,0,reset)•mainswitch(yesorno)Basedonthesedata,aconvenientcontactorandanoverload relay aswell as correspondingly equippedenclosureareselected.

ORDERINGDATA

Settingrangeforthermaloverloadrelay.S-forKNL9-KNL16,M-forKNL22,KNL30Mainswitch(0-none,1-25A,2-32A)Pushbuttons(0-none,1-resetpushbutton,2-I,IIand0)Enclosuresize

Enclosure:I,IIand0pushbuttonscanbemarked:FOR/REV,UP/DOWN,OPEN/CLOSED,LEFT/RIGHTDegreeofprotectionIP66,ametalbaseandapolycarbonatecover

*Standardcontrolvoltages(50/60Hz)B7 24VF7 110/125VM7 220/240VQ7 380/415VOthercontrolvoltagesalsoavaiable

REVERSINGSTARTERSUPTO30A

KindofthermaloverloadrelayBR Controlvoltage

COMPONENTSELECTION

Motorpowerat ThermaloverloadrelayBR16/30

Reversingstarter*

Enclosure

400/415V,three-phase Operationalcurrent(A)Push-buttonarrangement Mainswitch Orderingcode

kW HP min.-max

BR

16/K

NL1

8

0.06 0.08 0.16-0.25

RS9

I,IIand0

reset

none

R420S

R410

R400

0.12 0.16 0.25-0.4

0.18 0.25 0.45-0.63

0.25 0.33 0.75-1

0.55 0.75 1.1-1.6

1.1 1.5 2.3-3.2

1.5 2 2.9-4

I,IIand0

reset

none

withmainswitch

R221

R211

R201

2.2 3 4.5-6.3

4 5.5 7.2-10

5.5 7.5 9-12.5 RS12

7.5 10 11.3-16 RS16

9 10 15-20 RS18

BR

30/K

NL3

0

11 15 17.5-21.5 RS22

I,IIand0resetnone

—R420MR410R400

I,IIand0resetnone

withmainswitch

R221R211R201

15 20 24.5-30 RS30

I,IIand0resetnone

—R420MR410R400

I,IIand0resetnone

withmainswitch

R222R212R202

Page 111: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

110

Wiringifapositionswitchisrequired:1.Removeconnections52-632.Connectasillustrated

NOTE:Auxiliarycontact13-14belongstoaKNL9-KNL16contactorstandardequipment

CONTROLCIRCUITSUPPLYARRANGEMENTS

KNL9-KNL30reversingstarters

SUPPLY WIRINGPhasetophase SeeafigurePhasetoneutralRemoveconnectionDconnect neutraltoterminal96SeparatesupplyRemoveconnectionsDandE. Connectseparatecoilsupplyto terminal96onoverloadrelayand terminal64onK2contactor

CONNECTIONDIAGRAM

ConnectionD

ConnectionE

Pushtorun

Asimplepush-to-runarrangementcanbeachivedinoneorbothdirectionsbychangingthetopstartswitches.

ConnectionD

ConnectionE

Wiringifremotecontrolwithpushbuttons:1.RemoveconnectionsD

2.Connectasillustrated

REVERSINGSTARTERSUPTO30A

Page 112: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

111

DIMENSIONS

Enclosuresforreversingstarters(enclosuresizesR2andR4)

EnclosureR2

FixingholeswithLdiameterTopandbottomholes

forcableinletswithKdiam-eter

EnclosureR4FixingholeswithLdiameter

HolesforcableinletswithKdiameter,topandbottom

IP66 A B C D E F G H J K L

KNL9-KNL30(enclosureR4) 260 158 160 210 108 132 147 - 27.52x201x25

3x5.5

KNL9-KNL30+mainswitch(enclosureR2)

260 230 171 210 180 133 148 16128.5

2x201x25

4x5.5

REVERSINGSTARTERSUPTO30A

Page 113: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

112

S320

S321

SD16

Todefinethestarter,thefollowingdatahavetobeknown:•motorpower,operationalcurrent•coilcontrolvoltage•requiredpushbuttons(none,start,stop,reset)•mainswitch(yesorno)Basedonthesedata,aconvenientcontactorandanoverloadrelayaswellascorrespondinglyequippedenclosureareselected.

STAR-DELTASTARTERSUPTO25kW

*Standardcontrolvoltages(50/60Hz)B724VF7110/125VM7220/240VQ7380/415V

Othercontrolvoltagesalsoavailable

STAR-DELTA STARTERS APPLICATIONForastar-deltaunit,theoverloadrelayisconnectedtoadeltaloopandthereforeprotectsthemotoronlyatthisconnection.Foreasierselectionoftherelay,motorcurrentsarestatedinatable.Astar-deltastarterisequippedwithanelectronictimerelaywithaminimumrangefrom3to45seconds.Thetimerelayassuresrequireddelaybetweena“star”contactoropeninganda“delta”contactorclosing.

SettingrangeforthermaloverloadrelayS-forKNL9-KNL16,M-forKNL22,KNL30Mainswitch(0-noswitch,1-25A,2-32A)Pushbuttons(0-noswitch,1-resetpushbutton,2-startandstop)Enclosuresize

S3 ...0,1,2... ...0,1,2,3 ...S,M -....

ORDERINGDATAKindofthermal

overloadrelayBR Controlvoltage

COMPONENTSELECTION

MotorpoweratThermaloverloadrelay

BR16/30 Star-delta

starter*

Enclosure

400/415V,three-phase Operationalcurrent(A)Push-buttonarrangement Mainswitch Orderingcode

kW HP min.-max

BR

16/K

NL1

8

2.2

4

7.5

11

15

3

5.5

10

15

20

2.3-3.2

4.5-6.3

07.2-10

11.3-16

15-20

SD16

start&stop

reset

none

S320S

S310

S300

start&stop

reset

none

withmain

switch

S321

S311

S301

BR

30/K

NL3

0

18.5 25 21-25 SD22

start&stop

reset

none

S320

S310

S300

start&stop

reset

none

withmain

switch

S321

S311

S301

22

25

30

34

21-25

24.5-30SD30

start&stop

reset

none

S320

S310

S300

start&stop

reset

none

withmain

switch

S322

S312

S302

Page 114: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

113

PovezavaD PovezavaE

PovezavaE

PovezavaD

Zunanjivklop

Connectiondiagram(controlwithpushbuttons)

CONTROL CIRCuIT SuPPLY ARRANGEMENTS

SUPPLY WIRINGPhasetophase SeeafigurePhasetoneutral RemoveconnectionD Connectterminal96toaneutralconductorSeparatesupply RemoveconnectionsDandE Connectseparatecoilsupplytoterminal96onoverloadrelayandterminal64onK2contactor

NOTE:AUXILIARYCONTACT13-14BELONGSTOAKNL9-KNL16CONTACTORSTANDARDEQUIPMENT

Wiringforremotecontrolwithpushbuttons 1.RemoveconnectionD 2.Connectasillustrated

MotorwindingsConnecttoappropriateterminalson

thestarter

CONNECTIONDIAGRAM

KNL9-KNL30stardeltastartercontactors

Connectiondiagram(RemotePilotSwitchControl)1.Removeconnection63to52ontheK2contactor2.Connectbetween52and64ontheK1contactorandfromterminal51ontheK1contactortoterminal52ontheK2contactor3.ConnectthepilotswitchinplaceofconnectionE4.Setoverloadrelaytomanualresetposition.

STAR-DELTASTARTERSUPTO25kW

Page 115: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Contactorscombinations

114

DIMENSIONS

Enclosuresforstar-deltastarters(sizesS2andS3)

EnclosuresS2andS3

fixingholeswithLdiameterHolesforcableinletswithKdiameter,topandbottom

IP66 A B C D E F G H J K L

KNL16-KNL30(enclosureS2) 260 230 161 210 180 133 148 - 28.52x201x25

3x5.5

KNL16-KNL30+mainswitch(enclosureS3)

260 332 171 210 282 133 148 161 28.5

3x201x25

4x5.5

STAR-DELTASTARTERSUPTO25kW

Page 116: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

115

DS

Positivecontactsopening(IEC60947-5-1AnnexK)

Mechanicalprotectiondegree-frontpartIP65,connectionterminalsIP20(forswitchesCS40,63,80-optionwithprotectioncoverisrequired)

Looselyscrewed“self-lifting”clampsoffereasierconnectionDIN-railorscrewmounting

• •

• Type Type I/Uthi

DS16 A0(48) 16A/600V

DS25 A0(48) 25A/600V

DS32 A0(48) 32A/600V

DS40R A0(48) 40A/600V

DS40 A1(65) 40A/600V

DS63 A1(65) 63A/600V

DS80 A1(65) 80A/600V

SwitchesseriesDShavebeendevelopedtothelatestachieve-mentsinthefieldofswitchingdevicesthroughtheapplicationofqualityinsulationmaterialsandcontactsmadewithsilveralloys.Modularconstructionallowssubsequentchanges,sostockingcostscanbelowered.Elementsthatcanbefixedtotheleftand/orrightsideoftheswitch:

fourthpole(N-pole)

auxiliarycontacts2n/oauxiliarycontacts1n/o+1n/c

PEterminalNterminal

• •

• •

BecauseofthelargeropeningclearancestheswitchesseriesDSareparticularlysuitableformainswitches(switchdis-connectors)andsafetyswitches(emergency-offswitches).SwitchesseriesDSarebuiltinaccordancewiththefollowingstandards:IEC60947-1,-3,IEC60204,DINEN61058,UL508,C22.2No.14etc.

General:

•Twomodularframesizes: A0size(16-25-32-40A) A1size(40-63-80A)

Page 117: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

116

DS

MOUNTINGSIZES

TECHNICALDATASwitchtype DS16 DS25 DS32 DS40R DS40 DS63 DS80

Ratedinsulationvoltage Ui V 690

Ratedimpulsewithstandvoltage(III/3)1) Uimp kV 6

Ratedthermalcurrent Ith A 16 25 32 40 40 63 80

Ratedshort-timewithstandcurrent(1s) Icw A 400 500 600 600 1100 1300 1400

Max.fusesizeforshort 10kA

In A

35 35 35 40 80 80 80

circuitprotection 25kA 32 32 32 32 63 63 63

gGcharacteristic 50kA 32 32 32 32 63 63 63

RatedoperationalcurrentAC1/AC21A Ie A 16 25 32 40 40 63 80

Motorswitchin

3ph

ase

AC

3

220/240V

kW

3.7 5.5 7.5 7.5 11 11 15

utilizationcategory 380/440V 3.5 7.5 11 11 15 22 25

500V 7.5 11 15 15 22 25 30

690V 7.5 11 15 15 22 25 25

3ph

ase

AC

23

220/240V 4 7.5 9 9 11 15 18.5

380/440V 7.5 11 15 15 18.5 25 30

500V 9 15 15 15 22 30 37

690V 9 15 15 15 22 30 30

Conductorsizerigid

S

mm2 10 10 10 10 25 25 25

AWG 8 8 8 8 4 4 4

flexiblemm2 6 6 6 6 16 16 16

AWG 10 10 10 10 6 6 6

1) valid for neutral earthed systems, overvoltage category III, polution degree 3

AUXILIARYCONTACTSType DSX

Ratedinsulationvoltage Ui V 690

Ratedthermalcurrent Ith A 10

Ratedoperationalcurrent 110V

Ie A

8

220-240V 8

380-400V 3

660-690V 1

Conductorsizerigid

S

mm2 1.5

AWG 14

flexiblemm2 1.5

AWG 14

Page 118: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

117

DS

Page 119: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

118

DS

ACCESSORIES

ORDERINGCODESFORACCESSORIES

Page 120: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

119

DS

ORDERINGCODESFORACCESSORIES

DIMENSIONS

Page 121: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

120

DS

DIMENSIONS

Page 122: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

121

DS

ORDERINGCODE

Page 123: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

122

DSPV

Dc

AC kWh

ACSWITCH-DISCONNECTOR

PHOTOVOLTAICMODULE

DC/ACINVERTER

Ratedoperationalcurrentforspecifiedvoltageisachievedbyserialwiringofthepolesasshowninthetablebelow.

DSPVtypeofswitch-disconnectorscanmeetallrequirementsofinstallationwithratedoperationalvoltageupto1000Vandoperationalcurrentsupto80AinutilizationcategoryDC21B.Switch-disconnectorsaredesignedtobeplacedbetweenphotovoltaiccellsandDC/ACinverter.SWITCH-DISCONNECTORDSPV

Thedevelopmentofrenewableenergysourcesonthebasisofphotovoltaicpanelshasresultedwiththedevelopmentofswitch-disconnectorswhichareusedforswitchingoffDCcircuit.Switch-disconnectorsseriesDSPVwithdoublebreak-ingsystemcompletelyfulfilrequirementsforisolationaccordingtoIEC60364-7-712forphotovoltaicinstal-lations.

Compactdesign

ProtectiondegreeIP65

AccordingtoIEC60947DINrailorscrewmountings

11 21 201(DSPV40 - 750 V)

22 202(DSPV40 - 750 V)

31

53

DSPV40 DSPV80

+

-

0

11 3 5

2 4 6

+

-

-

+ -

+

0

11 3

2 4 6

5 7

8

+ +

0

11 3 5

2 4 6

-

- -

+ -+

0

11 3 5

2 4 6

7

8

+ -+

0

1

1 3

2 4 6

5 7

-

8

+ -

0

11 3 59 7

-+

2 4 610 8

-

+ -

+

0

11 3 59 7

2 4 610 8

301(CSP40 - 750V)

-

+ -

+

0

11 3

2 4 6

0

11 3 5

2 4 6

5

SW1 SW2

33

0

1

0

1

+

7

-

7

+ -

1 3 1 3 55

8 82 4 2 4 66

44

SW1 SW2

-

0

1

0

1

+

+ -

9 51 3 7 1 35

10 62 4 8 2 46

SW1 SW2

0

1

0

1

+ -

7 71 3 1 3 55

8 82 4 2 4 66

SW1 SW2

+ -

OutOut OutIn In

nI nIIn InIn Out OutIn Out In Out In OutIn InOut

Out Out Out Out Out

In In In In In InOut In In In In

Switch-Disconnectors for

Page 124: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Switchdisconectors

123

Compactdesign

ProtectiondegreeIP65

AccordingtoIEC60947DINrailorscrewmountings

DSPV

DSPV40-22-O48D DSPV80-31-O48,56

DSPV40-21-O75DSPV40-31-O25

Switcheswithlocking(75/25)

DSPV40-21-O108D

Doorcoupling(108D)

DSPV40-31-P Plastic enclosure

Servicecover(48D) Servicecover(48,56)

DSPV80-33-O DSPV40-53-O102

Door coupling (102) Rear mounting

TECHNICALDATA

TypeRatedoperational

voltageU

Ratedoperational

currentI(DC21B)

Numberofpolesin

series

DSPV40-21

220

40 3

DSPV80-21 50 3

DSPV80-31 80 4

DSPV40-11

450

7 2

DSPV40-21 16 3

DSPV40-31 30 4

DSPV40-33 40 6

DSPV80-31 63 4

DSPV80-33 80 6

DSPV40-21

500

10 3

DSPV40-31 30 4

DSPV40-33 35 6

DSPV40-44 40 8

DSPV80-31 35 4

DSPV80-33 50 6

DSPV80-44 80 8

DSPV40-21

750

8 3

DSPV40-31 12 4

DSPV40-33 35 6

DSPV40-44 40 8

DSPV80-33 45 6

DSPV80-44 50 8

DSPV40-33

1000

16 6

DSPV40-44 20 8

DSPV80-33 20 6

DSPV80-44 30 8

Page 125: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Timerelays

124

TRE701

TRE701isamultifunctionmultitimetimerelaywithbuild-inmicroprocessortechnology.Itcoversmostoftheuserneeds.Itcomprehendssimpleandmoresophisticatedtimefunctionswithverywidetimeranges.Itcanbedeliveredinmanyvarietiesaccordingtooperatingvoltagesandthenumberofoutputcontacts.

A:Apulseafterpower-onoraftertherisingedgeoftriggerpulseS. B:Delayafterpower-onoraftertherisingedgeoftriggerpulseS.C: A pulseafterpower-onoraftertherisingedgeoftriggerpulseS.Retriggerable. D: Delayafterpower-onoraftertherisingedgeoftriggerpulseS.Retriggerable. E:ThefirstedgeoftriggerpulseSturnsrelayonwhilethesecondedgestartscountingdowntillrelayoff.AdditionaltriggerSbeforetheprocessisfinishedprolongstheon-state.F:EachrisingedgeoftriggerSappendsadditionalperiodTtothetimeofon-state. G:PulsatingoperatingwithastartingpulseorpausewhichdependsonthestateoftriggerSatpower-on. H:Bistableoperating.EachrisingedgeoftriggerSswapstherelayintotheoppositestate. I: Prolongedpulseafterpower-on.ThepresenceoftriggerStemporarilystopscounting. J:Prolongedpauseafterpower-on.ThepresenceoftriggerStemporarilystopscounting.

NotesFunctionsA-D:Iftriggeringatpower-onisrequired,thenthecontrolsignalSmustbeactive.Whenchangingfunction,therelaymustbepoweredOFFandONagain.Itispossibletoupgradetherelaywithsomeuser-definedfunctionswithoneortwoindependentoutputrelays(forlargerquantities).

Orderind data:

TRE701224-240VTRE701-relaytype2-numberofcontacts(1,2,3)24-240V-operatingvoltage(12VAC/DC,230VAC,24-240VAC/DC)

NOTE:Combinationwith3outputcontactsand230VACoperatingvoltagecannotbedelivered.Fortechnicaldataseepage129.

Connection diagram:

Function description:

Basic technical data Timeranges (timerangesselectedwith seconds:1,10 amicroswitch)minutes:1,10 hours:1,10,100,500 ON,OFF

Operatingvoltageranges (selectonerange)24-240VAC/DC 12VAC/DC 230VAC Outputcontacts 1-3x8A/250V

Page 126: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Timerelays

125

TRE702

TRE702isamultifunctionT1-T2timerelaywithbuilt-inmicroprocessortechnology.Itcoversmostoftheuserneeds.Thetimerelaycomprehendssimpleandmoresophisticatedtimefunctionswithverywidetimeranges.Itcanbedeliv-eredinmanyvarietiesaccordingtooperatingvoltagesandthenumberofoutputcontacts.ItexcelsinthepossibilityofsettingextremelyasymmetricalT1-T2timefunctions.

Basic technical data Timeranges (timerangesselectedwithseconds:1,10 amicroswitch)minutes:1,10 hours:1,10,100, T1,T2:1h-1min; 10h-10min;100h-1h

Operatingvoltageranges (selectonerange)24-240VAC/DC 2VAC/DC 230VAC Outputcontacts1-3x8A/250V

Connection diagram:

Ordering data:

TRE702224-240VTRE702−relaytype2-anumberofcontacts(1,2,3)24-240V-operatingvoltage(12VAC/DC,230VAC,24-240VAC/DC)

A:Apulseafterpower-onoraftertherisingedgeoftriggerpulseS.EventualsignalsS occurringbeforetimeTexpiryhavenoinfluence.B:Delayafterpower-onoraftertherisingedgeoftriggerpulseS.EventualsignalsS occurringbeforetimeTexpiryhavenoinfluence.C:Apulseafterpower-onoraftertherisingedgeoftriggerpulseS.Retriggerable.D:Delayafterpower-onorafterrisingedgeoftriggerpulseS.Retriggerable.E:ThefirstedgeoftriggerpulseSturnsrelayonwhilethesecondedgestartscountingdowntillrelayoff.AdditionaltriggerSprolongstheon-statebeforetheprocessisfinished.F:Prolongedpulseafterpower-on.ThepresenceoftriggerStemporarilystopscounting.G:Pulsatingoperatingwithanon-equalpulse-pauserate.Astartingpulseorapause whichdependsonthestateoftriggerSatpower-on.H:AftertherisingedgeoftriggerS,thedevicewaitsforperiodT1andtherelayisactivated(iftriggerSisstillpresent).AfterperiodT2,itisdeactivated.IfthetriggersignalisshorterthanperiodT1,therelaydoesnotactivateatall.IftriggerSreappearsduringperiodT2,ithasnoinfluence.I:AftertherisingedgeoftriggerS,thedevicewaitsforperiodT1andtherelayisactivated(ifthetriggerSisstillpresent).AtthefallingedgeoftriggerSthesecondcountingstartsandwhenitreachesT2,therelayisdeactivated.IfthetriggersignalisshorterthanperiodT1,therelaydoesnotactivateatall.IftriggerSreappearsduringperiodT2,ithasnoinfluence.J:TherisingedgeoftriggerSactivatestherelayforperiodT1.ThefallingedgeoftriggerSactivatestherelayforperiodT2.IftriggerSfallsdownduringperiodT1,periodwillbecancelled.IftriggerSreappearsduringperiodT2,ithasnoinfluence.

Note:FunctionsA-D:triggeringpower-on,isrequiredthecontrolsignalSmustbeactive.Whenchangingfunction,therelaymustbepoweredOFFandONagain.

Forlargerquantities,itispossibletoupgradetherelaywithsomeuser-definedfunctionsbymeansofoneortwoindependentoutputrelays.

NOTE:Acombinationwiththreecontactsand230VACoperatingvoltagecannotbedelivered.Fortechnicaldataseepage129.

Functiondescription:

Page 127: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Timerelays

126

TRE703

TRE703isaone-functionone-timetimerelayusedformoresensitiveapplications.Itcanbedeliveredinmanyvarie-tiesaccordingtofunction,timerange,operatingvoltageandthenumberofoutputcontacts.

Basictechnicaldata Timeranges(selectonerange) seconds:3,15 minutes:1,3,15 hours:1,3 Operatingvoltageranges (selectonerange) 24-240VAC/DC 12VAC/DC

230VAC

Outputcontacts 1-3x8A/250V

Connectiondiagram

Orderingdata

TRE703224-240VA1hTRE703-relaytype2-numberofcontacts(1,2,3)24-240V-operatingvoltage(12VAC/DC,230VAC,24-240VAC/DC)A-timefunction(A,B,C,D)1h-timerange(3s,15s,1min,3min,15min,1h,3h)

NOTE:Acombinationwiththreecontactsand230VACoperatingvoltagecannotbedelivered.

Fortechnicaldataseepage129.

A:Pulseatpower-onoratfallingedgeofcontrolsignalS B:Pauseatpower-onoratfallingedgeofcontrolsignalS C:Pulsatingwithstartingpulse D:Pulsatingwithstartingpause

Functiondescription

Page 128: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Timerelays

127

TRE704

TRE704isastar-deltaswitch.TimeT1canbeadjustedwithintheselectedtimerange.Itcanbedeliveredinmanyvarietiesaccordingtotimerangeandoperatingvoltage.

Functiondescription

Basictechnicaldata Timeranges(selectonerange)seconds:10,30,60,100,600 Operatingvoltageranges (selectonerange) 24-240VAC/DC 12VAC/DC 230VAC Outputcontacts 2x8A/250V

Connectiondiagram

Orderingdata

TRE70424-240V100sTRE704-relaytype24-240V-operatingvoltage(12VAC/DC,230VAC,24-240VAC/DC)100s-timerange(10,30,60,100,600)

Fortechnicaldataseepage129.

Afterpower-on,therelayYisactivatedfortimeT.Afterthepause.T2=100ms,therelayΔ isactivated.

Page 129: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Timerelays

128

TRE705isabistabletimerelaywithhold-onafterpoweroff.TimeT1canbeadjustedwithintheselectedtimerange.Itcanbedeliveredinmanyvarietiesaccordingtotimerangeandoperatingvoltage.

BasictechnicaldataTimeranges(selectonerange)seconds:3,10,30,60,100,300Operatingvoltageranges(selectonerange) 24-240VAC/DC 12VAC/DC Outputcontacts 6A/250V

Connectiondiagram

Orderingdata

TRE705-24-240VA100sTRE705-relaytype24-240V-operatingvoltage(12VAC/DC,24-240VAC/DC)A-timefunction100s-timerange(3,10,30,60,100,300seconds)

Fortechnicaldataseepage129.

A:Therelayisactivatedafterpower-on.After power-off,itremainsactivatedfortheperiodT. B:Therelayisactivatedatpower-offandremains activatedfortheperiodT.

Functiondescription

TRE705

Page 130: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Timerelays

129

TRE706isastaircaseswitch.Timecanbeadjustedintherangefrom0.5to10minutes.Itisedgetriggered,whichmeansthatitisbroken-switchproof.EnhancedversionBhasthepossibilityofmultiplyingONtimebyfactor8.Thisfast-onfunctionisactivatedbyholdingtheswitchforprolongedtime(6-to8-second).Thisisveryusefulatcleaning,repairsetc.

OptionB

Ordering data

TRE706A

TRE706-relaytypeA-option(A,B):Aisabasicversion,Bhasthepossibility

oftimeprolongedoperation

Basic technical data Timeranges 0.5-10minutes ON,OFF OptionB:extra 4-80minutes ON,OFF

Operatingvoltage 230VAC

Outputcontact 16A/250V

Numberofbulblamps(<1mA) 10

Technical data for time relays TRE 701 to TRE 706

Operatingvoltagerange:-15%,+10%InputresistanceofcontrolinputS:(TRE701,702,703,706):100kOhmMin.durationoftriggerpulseS:50msTimesettingrepeatability:TRE703/704/705/706/CRT<2%TRE701/702<1%NominaltimerangetoleranceTRE703,704,705,706:5%TRE701/702:1%Operatingtemperature:0°Cto55°C(-20°Cto+65°Cavailableonorder)Storagetemperature:-25°Cto+70°CDegreeofprotection:IP20Diameterofconnectioncable:2.2mmmax.Mechanicalendurance:>107cyclesStandards:EN60669,EN60256;EN61000,EN61010,EN61812

DIMENSIONS

Connectiondiagram

Functiondescription

ThesignalSactivatestherelayforperiodT.IfthedurationofthesignalSislongerthan6seconds,theperiodTisprolongedbyfactor8(versionB).ThisisindicatedbychangingthebrightnessofthecontrolredLED.

IfthesignalSreappearsbeforetheperiodTexpires,thecountingtimestartsagainfromthebeginning.

TRE706

Page 131: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Accessories

130

TypeOS1/2P+Pe/IP55OS1/3P+Pe/IP55

TypeOS3/2P+Pe/IP55OS3/3P+Pe/IP55

TypeOS4/2P+Pe/IP55OS4/3P+Pe/IP55

TypeOS5/2P+Pe/IP55OS5/3P+Pe/IP55

TypeOS6/2P+Pe/IP55OS6/3P+Pe/IP55

TypeOS2/2P+Pe/IP55OS2/3P+Pe/IP55OS2/4P+Pe/IP55

CONNECTIONCABINETSOS1, OS2, OS3, OS4, OS5, OS6 (WITH EXTENSION FOR MECHANICAL INTERLOCK)

Page 132: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Accessories

131

UMP90E

UMP90UMP45

1 2

3

Type WidthUMP4545mm UMP90 90mm UMP90E 90mm

WKWIRINGSYSTEMType Description

WK1.1 Forreversingswitch,suitableforcontactors:2.2-5.5kW (forminicontactorsK03,K07)(max.current16A) 5terminalinline,(3mainterminals,1auxiliaryterminal,1coilterminal)WK2.1 Forreversingswitch,suitableforcontactors:4:5.5:7.5or9kW (forKNL9-KNL18)(max.current25A),4terminalsinline(3mainterminals, 1auxiliaryterminal)WK4.1 Forreversingswitch,suitableforcontactors:11and15kW(forKNL22-KNL30) (max.current40A),3terminalsinline(3mainterminals)WK5.1Forreversingswitchwithmechanicalinterlock(suitableforcontactors:4:5.5: 7.5or9(kWforKNL9-KNL18)(max.current25A),4terminalsinline(3mainterminals,1auxiliaryterminal)WK1.2 Forstar-deltastarters,suitableforcontactors:2.2-5.5kW(forminicontactorsK03, K07)(max.current16A),5terminalsinline(3mainterminals,1auxiliaryterminal,1coilterminal)WK2.2 Forstar-deltastarters,suitableforcontactors:4:5.5;7.5or9kW (forKNL18)(max.current25A),4terminalsinline(3mainterminals,1auxiliaryterminal)WK4.2 Forstar-deltastarters,suitableforcontactors:11and15kW(forKNL22-KNL30) (max.current40A),3terminalsinline(3mainterminals)

DST-UCONNECTIONBLOCKBETWEENMOTOR-PROTECTIONSWITCHANDCONTACTOR

Type CablelengthCross-section WidthDST-U-2,5(20A) 40mm 2.5mm2 45mmDST-U-4(35A) 40mm 4mm2 45mmDST-U-2,5L(20A) 70mm 2.5mm2 45mm

Forreversingstarterupto30A

1 Fordirect-starterupto30A

2

3 Forstar-deltastarterupto30A

MULTI-FUNCTIONALADAPTERS

Page 133: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Accessories

132

MSS-3LCONNECTIONBLOCKFORMOTORPROTECTIONSWITCH

Type Module/length MSS-3L-M2-45 2x3/80 MSS-3L-M3-45 3x3/125 MSS-3L-M4-45 4x3/170 MSS-3L-M5-45 5x3/215 MSS-3L-M2+Hi-45+9 2x3/90 MSS-3L-M3+Hi-45+9 3x3/145 MSS-3L-M4+Hi-45+9 4x3/200 MSS-3L-M5+Hi-45+9 5x3/250

ESB-S/V-MSSUPPLYBLOCK(25MM2)FORMOTORPROTECTIONSWITCH

BS-MS0PROTECTIONFORCONNECTIONCABLE

M25X1.5CABLEINLET

Page 134: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Approvals

133

ESB-S/V-MSSUPPLYBLOCK(25MM2)FORMOTORPROTECTIONSWITCH

Typeofproduct Certificates

MS25 UL/CSA,GOSTMST25 UL/CSAMS20 MST20 PS UL/CSA,GOSTU,Arelease UL/CSA,GOSTRS,PSV UL/CSA,GOSTMS32 UL/CSA,GOSTMSB32 UL/CSA,GOSTHS,HSV,HRS UL/CSA,GOSTUR,ARrelease UL/CSA,GOSTFI2,FI4,NFI2,NFI4,NFIS,NFIK VDE,NF,GOST,FIREK03C,K07C,K07CG,K07CF UL/CSA,GOSTK03M,K07M,K07MG,K07MF,K07MX UL/CSA,GOSTND2,ND4 UL/CSA,GOSTBR6 GOSTKNL6 UL/CSA,GOSTKNL9,KNL12,KNL16 UL/CSA,GOSTKNL18 GOSTKNL22,KNL30 UL/CSA,GOSTKNL6G UL/CSA,GOSTKNL9G,KNL12G,KNL16G UL/CSA,GOSTKNL22G,KNL30G UL/CSA,GOSTNDL1,NDL2,NDL3,NDL4 UL/CSA,GOSTNPL1,NPL2 UL,GOSTTRB14/KNL GOSTKNL40,KNL65 GOSTBR43 GOSTKNL80,KNL90,KNL110 UL,GOSTG480,G484 BR90 GOSTKNL95-KNL1000 UL,GOSTBRA180,BRA400 GOSTG350KC12-KC60 ULIKA20,IKA25,IKD20,IKD25,IK40,IK63 NF,UL/CSA,GOST,KEMA-KEURIKA20-R,IKA25-R NF,UL/CSA,GOST,KEMA-KEURIKN NF,UL/CSA,GOST,KEMA-KEURRI20RI50 KEMA-KEURRI60 VDE

ZK12-ZK180 K0-LD7 KNL-LD7,…,KNL-LD30 KMSPL3-KMSPL22

DS KEMA-KEUR

Page 135: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

134

Notes

Page 136: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

135

Notes

Page 137: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

136

Notes

Page 138: Low Voltage Switchgear - Eurotronix › files › shares › Eurotronix... · Low Voltage Switchgear Low Voltage Switchgear ® Published by Iskra MIS, d. d. • Version 4.0, Oktober

Low VoltageSwitchgear

Lo

w V

olt

age

Sw

itch

gea

r

®

Published by Iskra MIS, d. d. • Version 4.0, Oktober 2011 • design Nimbus d.o.o.

® Ljubljanska c. 24a, SI - 4000 Kranj, SloveniaTel.: +386 4 23 72 112, Fax: +386 4 23 72 129E-mail: [email protected], www.iskra-mis.si

®