maclaughlin management and design - burlington, vermont

3
RINK REFRIGERATION PLAN MacLaughlin Management 21 $QZ 'ZGVGT 0GY *CORUJKTG 2JQPG ÄÄ and Design 4+0- 4'(4+)'4#6+10 5;56'/ 4'2.#%'/'06 )14&10 * 2#37'66' +%' #4'0# .'&&; 2#4- $74.+0)610 86

Upload: others

Post on 25-Oct-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MacLaughlin Management and Design - Burlington, Vermont

RIN

K RE

FRIG

ERA

TIO

NPL

AN

MacL

au

gh

lin

M

an

ag

em

en

t

an

d D

esig

n

Page 2: MacLaughlin Management and Design - Burlington, Vermont

RIN

K RE

FRIG

ERA

TIO

NPI

PIN

G &

INST

RUM

ENTA

TIO

ND

IAGR

AM

MacL

au

gh

lin

M

an

ag

em

en

t

an

d D

esig

n

Page 3: MacLaughlin Management and Design - Burlington, Vermont

CLOSE COUPLED BASE MOUNT PUMP DETAIL

P-1 COLD FLOOR PUMP BELL & GOSSETT - E-1532 5EB CLOSE COUPLED - END SUCTION 1125 90 1800 40 460/3/60

TAG NO.

SERVICE

BASIS OF SELECTION TYPE

GPM

FT.

HEAD

RPM HP

V/PH/HZFLUID

P-2

P-4 220 37 1800 3 460/3/60

P-5 125 45 1800 3 22% CALCIUM CHLORIDE BRINE 460/3/60

COLD FLOOR BACKUP PUMP

WATER

CLOSE COUPLED - END SUCTION

CLOSE COUPLED - END SUCTION

CLOSE COUPLED - END SUCTION

MOTOR SHALL BE PREMIUM EFFICIENCY VFD COMPATIBLE

REMARKS

PROVIDE W/ SHAFT GROUNDING RING & FLEXIBLE PIPING CONNECTORS

MIN MAX

SYS. TEMP. (°F)

10

NO.

TAG

ET-1

LOCATION SERVICE

TANK

125

(PSI)

RATING

PRESSURE

502070

MIN MAX

120

(GAL.)

VOLUME

TANK

B&G - 116036

BASIS OF SELECTION

B&G - 116031

1125 90 1800 40 460/3/60

PCS-1 130.4 8°F 90°F 2AMMONIA

65ET-2

WARM FLOOR

1255020105 30

LOOP

REFRIGERATION RM.

COLD FLOOR

LOOP

P-3 CLOSE COUPLED - END SUCTION 220 37 1800 3 WATER 460/3/60CONDENSER SPRAY PUMP

BELL & GOSSETT - E-1532 5EB

BELL & GOSSETT - E-1532 2.5AC

BELL & GOSSETT - E-1532 2.5AC

BELL & GOSSETT - E-1532 2AD

MOTOR SHALL BE PREMIUM EFFICIENCY VFD COMPATIBLE

PROVIDE W/ FLEXIBLE PIPING CONNECTORS

REFRIGERATION RM.

1

PIPE SUPPORT AND HANGER DETAIL

94.9 100HP 94.5% 111.0 3550

OPEN DRIVE

SCREW

BITZER AMMONIA SCREW COMPRESSOR PACK

DIRECT COUPLED

REMARKS

BITZER ACP CONTROLER, NEMA 3R STARTER PANEL

PROVIDE W/ (1) REFRIGERANT ECONOMIZER, (1) THERMOIPHON OIL COOLER,

(2) SOFT STARTERS, (1) OIL SEPARATOR, OIL MANAGEMENT SYSTEM,

CONDENSER BACKUP SPRAY PUMP

WARM FLOOR PUMP

22% CALCIUM CHLORIDE BRINE

22% CALCIUM CHLORIDE BRINE

MOTOR SHALL BE PREMIUM EFFICIENCY VFD COMPATIBLE

PROVIDE W/ FLEXIBLE PIPING CONNECTORS

MOTOR SHALL BE PREMIUM EFFICIENCY VFD COMPATIBLE

PROVIDE W/ FLEXIBLE PIPING CONNECTORS

MOTOR SHALL BE PREMIUM EFFICIENCY VFD COMPATIBLE

PROVIDE W/ SHAFT GROUNDING RING & FLEXIBLE PIPING CONNECTORS

PROVIDE W/ TANK DRAINER FITTING, LEVEL GAUGE VALVES

REMARKS

& 5/8" CLEAR RIGID PLASTIC LEVEL GAUGE TUBING - ASME RATED

HX-1 200175°F 90°F AMMONIA

REMARKS

(1) HANSEN HT-100 FLOAT DRAINER

PROVIDE W/ (1) DUAL RELIEF MANIFOLD

(2) 300 PSIG RELIEF VALVES

22% C.C.

BRINE

12573°F70°F

BASIS OF SELECTION

TAG NO.

EF-1

SERVICE

TYPE

DRIVE

F A N D A T A

(Wg)

TSPCFM RPM HP

M O T O R D A T A

AMPSVOLTS PHASE

R E M A R K S

HZ

DELHI - MODEL 212E DUCT BLOWER 2800 0.5" 786 3/4 BELT 120 1 60 10.4

INTERLOCK W/ AMMONIA DETECTION SYSTEM

VENTILATION

EF-2 CENTRAL-AIRE - MODEL K12 SIDEWALL 450 0.375" 1550 1/20 DIRECT 120 1 60 1.4

EMERGENCY

REF. ROOM

PROVIDE W/ 16x16 B.D.D.

VENTILATION

OCCUPANCY

REF. ROOM

INTERLOCK W/ ROOM LIGHTS

PROVIDE W/ GRAVITY WALL SHUTTER

CH-1 1,5648.0°F

REMARKS

- INTEGRATED OIL ASSEMBLY

PROVIDE WITH THE FOLLOWING:

- REMOVABLE INSULATION PACKAGE FOR PLATE AND FRAME CHILLER

22% C.C.

BRINE

1,12514°F17.2°F8.0°F 8.0°F 3724 LB/H 0.405

AMMONIA

R-717

ALFA LAVAL

MK15-BWFD

- "U-Turn" LIQUID SEPARATOR

VESSEL MUST BE ASME RATED

ALFA LAVAL

AMC SERIES

PROVIDE W/ TANK DRAINER FITTING, LEVEL GAUGE VALVES

& 5/8" CLEAR RIGID PLASTIC LEVEL GAUGE TUBING - ASME RATED

W/ OPEN DRIVE OSKA COMPRESSORS

BASIS OF SELECTIONTAG NO.

AGLM-1

SERVICE

TYPE

ELECTRICAL DATA

VOLTS PHASE

R E M A R K S

HZ

BACHARACH - AGM-SZ INFRARED SENSING 120 1 60

INTERLOCK ALARM RELAY W/ EF-1 EMERGENCY EXHAUST FAN

DETECTION SYSTEM

AMMONIA LEAK

REFRIGERATION ROOM

PROVIDE W/ INLET TERMINATION FILTER, 100' OF SAMPLING TUBE

SENSITIVITY

25 PPM

PROVIDE AN ADD ALTERNATE #1 FOR VFDs IN LIEU OF SOFT STARTERS