maintenance handbook on transformer of 3 phase electric locomotive

Upload: aalokeroy

Post on 26-Feb-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    1/59

    Hkkjr ljdkj GOVERNMENT OF INDIAjsy ea=ky; MINISTRY OF RAILWAYS

    egkjktij

    ,Xokfy;j

    474 005

    Maharajpur, GWALIOR - 474 005

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015

    dsoy dk;Zky;hu mi;ksx gsrq(For Official Use Only)

    MMaaiinntteennaanncceeHHaannddbbooookkoonn

    TTrraannss oorrmmeerroo 33PPhhaasseeEElleeccttrriiccLLooccoommoottiivveeEND USER: Loco Maintenance Staff

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    2/59

    MMaaiinntteennaanncceeHHaannddbbooookkoonn

    TTrraannssffoorrmmeerrooff33PPhhaasseeEElleeccttrriiccLLooccoommoottiivvee

    QUALITY POLICY

    To develop safe, modern and cost

    effective Railway Technologycomplying with Statutory and

    Regulatory requirements, through

    excellence in Research, Designs and

    Standards and Continual

    improvements in QualityManagement System to cater to

    growing demand of passenger and

    freight traffic on the railways.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    3/59

    FOREWORD

    Emerging technological changes require dissemination of new technology and

    induction of new maintenance practices. The three phase electric locos were inductedquite some time back in Railway system but still there is no maintenance handbook

    on transformer. The transformer is an important equipment of electric loco (like heart

    in human body). The transformer needs proper maintenance for trouble free and

    reliable operation of locomotives.

    CAMTECH has prepared this handbook on Maintenance of Transformer of

    Three Phase Electric Locomotives with an objective to provide comprehensive

    information on the technical as well as maintenance aspects of the transformer.

    I hope this handbook prove to be useful for the field staff engaged in the

    maintenance of three phase electric locomotives and its transformer.

    CAMTECH, Gwalior A.R.Tupe

    Date: 26th

    March, 2015 Executive Director

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    4/59

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    5/59

    PREFACE

    Transformer is an important equipment of three phase electric locomotives.Proper upkeep of transformer is necessary to ensure trouble free operation of three

    phase electric locomotives.

    This handbook on Maintenance of Transformer of 3 phase electric

    locomotive has been prepared by CAMTECH with the objective of making ourmaintenance personnel aware of correct maintenance and overhaul techniques to be

    adopted in the field. This handbook covers brief technical details, maintenance

    practices, testing along with testing instruments required. This also covers condition

    monitoring of transformer oil and model questions on the subject.

    It is clarified that this handbook does not supersede any existingprovisions/guidelines laid down by Railway Board, RDSO or OEM. The handbook is

    only for guidance and it is not a statutory document.

    I am sincerely thankful to all field personnel who helped us in preparing this

    handbook.

    Technology up-gradation learning is a continuous process. Please feel free to

    write tour for any addition/ modification in this handbook. We shall highly appreciate

    your contribution in this direction.

    CAMTECH, Gwalior Peeyoosh Gupta

    Date: 26th

    March, 2015 Director/ Electrical

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    6/59

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    7/59

    CONTENTS

    Chapter No. Description Page No.

    Foreword iii

    Preface iv

    Contents v

    Correction Slip vii

    1. GENERAL 01

    1.1 Introductions 01

    1.2 Transformer Working Principle 03

    1.2.1 EMF Equation of Transformer 04

    1.3 Description of Three Phase Loco Transformer 04

    1.3.1 Transformer Cooling 04

    1.4 Different Parts of Transformer 07

    1.5 Technical Data of Electric Loco Transformer 10

    1.6 Transport of Transformer 11

    1.6.1 Lifting of the Transformer 11

    1.6.2 Supporting the Transformer on a Point 12

    1.7 Storage of Transformer 12

    1.7.1 Maintenance During Storage 13

    1.9 Factors Affecting Life of Transformer 13

    2. MAINTENANCE 15

    2.1 Periodic Maintenance Schedules 15

    2.2 Trip Inspection 16

    2.3 Oil Circulating Pumps (SR & TFP) IA, IB 17

    2.4 Main Transformer IC Schedule 18

    2.5 Main Transformer (AOH) Schedule 19

    2.6 Main Transformer (IOH) Schedule 20

    2.7 Main Transformer POH Schedule 21

    2.7.1 Painting Procedure 22

    2.8 Procedure for Replacement of Bushings 22

    2.9 Transformer Oil Check 23

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    8/59

    Chapter No. Description Page No.

    2.10 Testing of Loco Transformer 24

    2.10.1 Tests 24

    2.11 Testing Equipment 25

    2.12 Installation of the Transformer on Locomotive 26

    2.13 Check Points While Maintenance 29

    2.14 Transformer Oil 31

    2.14.1 Oil Specification 31

    2.14.2 Purification of Transformer Oil 32

    2.12.3 Condition monitoring of Transformer byDissolved Gas Analysis 34

    3. MODEL QUESTION 39

    ANSWERS 45

    An Approach to Equipment Failure Investigation 46

    ANNEXUREI - Reliability Action Plan (RAP) 47

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    9/59

    ISSUE OF CORRECTION SLIPS

    The correction slips to be issued in future for this handbook will be numbered as

    follows :

    CAMTECH/E/14-15/3Loco Transformer/C.S. # XX date---------

    Where XX is the serial number of the concerned correction slip (starting from 01

    onwards).

    CORRECTION SLIPS ISSUED

    Sr. No. Date of issue Page no. and Item

    no. modified

    Remarks

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    10/59

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    11/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    1

    CHAPTER 1

    GENERAL

    1.1 INTRODUCTION

    The transformer is a static device, which transforms power from one AC circuit to

    another AC circuit at same frequency but having different characteristics. These circuits are

    conductively disjointed but magnetically coupled by a common time varying magnetic field.

    It can raise or lower the voltage with a corresponding decrease or increase in current.

    In all the electric locomotives, limiting the value of current during starting, speedcontrol is achieved by supply of variable voltage to the traction motors. This variation of

    applied voltage can be carried out easily by the use of transformer along with Static

    Convertor provided in the locomotive.

    The windings which form the electrical circuit must fulfill certain basic

    requirements, particularly the di-electric, thermal and mechanical stresses imposed on itduring testing as well as in service and cater for over loads under adverse conditions.

    The WAG9 transformer unit consists of the main transformer active part and two

    different types of reactors, hosed in a tank.

    The main transformer converts the overhead line voltage (25 kV) to the lower

    operating voltages for:

    traction power supply 1268V

    auxiliary 1kV

    The main transformer is integrated into the traction circuit between overhead line

    and rail return line.

    The primary current line flows from the pantograph via roof line, vacuum circuit

    breaker, the roof bushing into the primary winding of the main transformer. It then flows

    back to the rail via the earth return brushes on four of the six axles. And WAP5, WAP7transformer has total load winding in addition toWAG9 transformer.

    Figure 1.1 Three Phase Loco Transformer

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    12/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    2

    Figure 1.2 Schematic Diagram of Power Circuit of 3 Phase Loco (WAG 9 , WAG 7)

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    13/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    3

    1.2 TRANSFORMER WORKING PRINCIPLE

    In general principle of working of a transformer can be expressed on the basis of law

    of electromagnetic induction as following:

    a. When a conductor cuts the magnetic flux or magnetic flux cut the conductor, an emf

    is induced in the conductor.

    b. The magnitude of this emf is proportional to the rate of change of flux.

    E = -d/dt

    Where, E = emf

    = flux

    Kinds of emf

    The emf may be induced by two ways

    i. Dynamically induced emf

    ii. Statically induced emf.

    a. Mutually induced emfb. Self induced emf

    An emf induced in a coil due to variation of flux in another coil placed near to first is

    called mutually induced emf.

    The emf induced in a coil due to change of its own flux linked with it is called self-

    induced emf. (In case of autotransformer)

    In its simplest form, a transformer consists of two conducting coils. The primary is

    the winding which receives electric power, and the secondary is one which delivers the

    electric power. These coils are wound on a laminated core of magnetic material.

    The physical basis of a transformer is mutual induction between two circuits linked

    by a common magnetic flux through a path of low reluctance as shown in fig.1.2

    The two coils possesses high mutual inductance. If one coil is connected to a sourceof alternating voltage, an alternating flux is set up in the laminated core, most of which is

    linked up with the other coil in which it produces mutually induced emf i.e.

    E = M di/dt

    If the second circuit is closed, a current flows in it and so electric energy istransferred (entirely magnetically) from first coil (primary winding) to the second coil

    (secondary winding).

    PRIMARY

    LAMINATED CORE

    SECONDARY

    Figure 1.3 Ideal Transformer

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    14/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    4

    1.2.1 EMF Equation of Transformer

    Let, N1= Number of turns in primary.

    N2 = Number of turns in secondary.

    m= Maximum flux in the core in webres.

    f = Frequency of AC input in Hz.v1 = Instantaneous value of applied voltage in primary winding in volts.

    The instantaneous value of counter electromotive force e1, can be expressed as

    e1= - N1d/dt volt

    The counter emf e1is equal and opposite to applied voltage v1i.e.

    v1= N1d/dt volt

    rms value of emf induced in primary

    E1= 4.44 f N1m

    Similarly, rms value of emf induced in secondary

    E2= 4.44 f N2m

    In an ideal transformer

    V1= E1& V2= E2

    Where V2is the secondary terminal voltage

    With the above expressions we get

    E2/ E1= N2/ N1= K

    Where K is known as voltage transformation ratio.

    (a) If N2 > N1i.e. K > 1 then the transformer is called step up transformer.

    (b)If N2 < N1i.e. K < 1 then the transformer is called step down transformer.

    1.3 DESCRIPTION OF THREE PHASE LOCO TRANSFORMER & ITS PARTS

    Each loco requires one transformer for feeding supply to traction converters/ traction

    motors, to auxiliary converter for supplying to auxiliary machines and to supply Hotel load

    of train. This transformer will consist of Primary winding, 04 Traction windings, Auxiliary

    winding (BUR) and Hotel Load winding. In addition, it has a FILTER winding which isconnected on locomotive to passive filter.

    The transformer tank also contains 02 series resonant chokes (one for each

    converter) & 03 Auxiliary Converter double chokes (one for each of the 03 auxiliary

    converters).

    1.3.1 Transformer coolingTransformer is oil cooled and external cooling of the oil is designed with two

    independent oil circuits with cooling units located within the machine room of locomotives.However, the cooling units / circuit component do not form part of transformer supply.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    15/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    5

    Figure 1.4 Cooling Arrangement

    Figure 1.5 Layout of Winding in Transformer Tank

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    16/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    6

    Figure 1.6 Three phase loco transformer winding diagram

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    17/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    7

    1.4 DIFFERENT PARTS OF TRANSFORMER

    i. Transformer tank fastening

    Material : AluminiumColour : RAL-7009stain

    Weight : 966 kg with lidIdentity No. : HSTN 424007

    Figure 1.7 Transformer Tank Fastening

    ii. Transformer main winding

    Identity No. : HSTN 424337

    Make : ABB Badodara, BHEL Jhansi,

    CGL Mandideep Bhopal,

    EMCO Thane Mumbai,High volt electrical Ltd Mumbai,

    Figure 1.8 Transformer main Winding

    iii. SOD Winding

    Identity No. : HSTN 424005Make ABB Badodara, BHEL Jhansi,

    CGL Mandideep Bhopal,EMCO Thane Mumbai,

    High volt electrical Ltd Mumbai,

    Figure 1.9 SOD Winding

    iv. GOD Winding

    Identity No. : HSTN 424006

    Make ABB Badodara, BHEL Jhansi,CGL Mandideep Bhopal,EMCO Thane Mumbai,

    High volt electrical Ltd Mumbai,

    Figure 1.10 GOD Winding

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    18/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    8

    v. Transformer Bushing

    Identity No. DT 1/250 : HSTN 310500DT 1/630 : HSTN 310501

    DT 1/1000 : HSTN 310502DT 1/2000 : HSTN 310503DT 1/3150 : HSTN 310504

    Figure 1.11 Transformer Bushing

    vi. High Voltage Bushing

    Identity No. : HSTN 420783P0001

    Technical Data: 18/30 kV, 800ASupplier : Elasti mold or RDSO approved

    Figure 1.12 High Voltage Bushing

    vii. Temperature Sensor (Thermometer)

    Identity No. : HSTN 424136P0001Technical Data : PT-100

    Supplier : JUMO Stafa or RDSO approved

    Figure 1.13 Temperature Sensor

    viii. Overflow Valve

    Identity No. : HSTN 4/12/0144RPressure setting : 0.8 bar

    Supplier : Millen Engineer or RDSO approved

    Figure 1.14 Overflow Valve

    ix. Transformer Main Valve

    Identity No. : HSTN 4274037P0001

    Technical Data : NW80 ND6Supplier : Fatco or RDSO approved

    Figure 1.15 Transformer main Valve

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    19/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    9

    x. Slide of oil intake and drainage

    Identity No. : HSTN 422368P0001

    Pressure setting : NW32/25Supplier : Hofiman or RDSO approved

    Figure 1.16 Slide of oil intake and drainage

    xi

    Two conservator tanks including - Air dehumidifier including valve -Oil level gauge

    Identity No. : HSTNMaterial : AluminiumColour : RAl 7030 stainVolume : 137DMQ

    Figure 1.17 Conservation Tanks

    xii. Breather

    Identity No. : HSTN 422029P0001Technical Data : EM3MASupplier : Yogya or RDSO approved

    Figure 1.18 Breather

    The special features of the transformer are :-

    Transformer is mounted under slung on under frame

    Transformer is designed for feeding GTO/IGBT based Power and Auxiliary converterload.

    Very high impedance between primary & traction windings

    100% de-couplings between windings

    Use of continuous transposed conductor for windings

    Use of disc construction of windings

    Transformer and conservator tank of Aluminum Alloy

    Rapid action coupling between transformer and conservators in oil circuit

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    20/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    10

    1.4 TECHNICAL DATA OF 3 PHASE ELECTRIC LOCO TRANSFORMERS (WAP5,WAP7 & WAG9)

    Common Ratings for WAG9, WAP5 & WAP7 Loco Transformers

    Rated voltage

    Normal

    MaximumMinimum

    25.0 kV

    30.0 kV17.5 kV

    Frequency 50Hz 6 %

    Cooling medium Inhibited transformer oil to IEC296/ IS-12463

    Series Resonant Choke (2SOD 240)

    Inductance 0.551 mH ( 15 %), Liner to Ipeak = 1391A

    Thermal current Ith 984A

    Resonant frequency 100Hz

    Voltage stress between terminals to earth Nominal 482 Vac , Max. 3471 V

    Auxiliary Converter Choke (6GOD 120)

    Inductance per PUR - choke

    0A 30 mH

    120A 30 mH

    155A 26 mH

    190A 20 mH

    Frequency 100 hz

    Current Rated 155A, Max. 190A

    Ripple Nominal 38.6%, Max. 50.2%Voltage to earth Rated 1153 V, Max. 2000 V

    Ratings for WAG9 loco transformer

    Winding Power (kVA) Voltage Current

    HV 6531 25000 261.25

    Traction 4 x 1449 4 x 1269 4 x 1142

    BUR 334 1000 334

    Filter 400 1154 347

    Total weight 9450 3 % kg

    Ratings for WAP5 and WAP7 Loco Transformer

    Winding Power (kVA) Voltage Current

    HV 7475/7775 25000 299/311

    Traction 4 x 1449 4 x 1269 4 x 1142

    BUR 334 1000 334

    Filter 400 1154 347

    Hotel load 945/1245 750/960 1260/1296

    Total weight 10000 3 % kg

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    21/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    11

    Weight

    Unit Quantity Kg per unit Kg total

    Transformer active part LOT 7500/ LOT

    6500

    1 5780/ 5380 5780/ 5380

    Series resonant circuit recator 2 SOD 240 1 590/ 590 590/ 590

    Auxiliary Converter DC-Link Reactor 6

    GOD 120

    1 570/ 570 570/ 570

    Tank and lid 1 900/ 900 900/900

    Insulation oil 1 1800/1780 1800/ 1780

    Equipment 1 260/ 230 260/ 230

    Total transformer unit 9900/ 9450

    Expansion tank (oil level at 20C) 2 88 176

    1.5 TRANSPORTATION OF TRANSFORMER

    The transformer is transported full with oil. Any oil volume changing (which is

    caused by temperature variations) during the transport or storage are taken up by the

    transport expansion tank which is mounted on the transformer oil.

    The breather is connected to the transformers expansion tank. The breather should

    only be removed during the installation of the transformer in the locomotive, and rectified as

    soon as possible. The breather must be filled with new or dried silica gel.

    1.5.1 Lifting of the Transformer

    The transformer must never be lifted without its lid. Lifting points are welded to theside of the tank for this purpose. The rope should be attached on these lifting points as

    described in figure shown below. The ropes should never make a smaller angle than = 60

    with the horizontal, otherwise there is a danger that the tank will distort.

    Figure 1.19 Lifting of the Transformer

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    22/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    12

    1.5.2 Supporting the Transformer on a Point

    If for any reason the transformer needs to be supported on a point, then it should

    only be supported on the indicated areas shown by the arrows in the figure given below.

    Figure 1.20 Support Point of Transformer

    1.6 STORAGE OF TRANSFORMER

    The transformer can be stored as long as required, if the maintenance is carried out

    as required if it is under maintenance or ready to use. The various points for storage of

    transformer is described below.

    a. Storing place

    The oil-filled transformer should be

    stored in covered area. The storing place must

    be dry and the transformer must be covered

    with a lose taped plastic sheet.

    Figure 1.21 Storing Place

    b. Connecting flanges

    All pipes, pumps and blocking valves should

    be closed off using blanking flanges.

    Figure 1.22 Connecting Flange

    c. Expansion tank

    Fix the expansion tanks in vertical position on ahigher level than the transformers lid. Join then with

    flexible pipes with transformer in the same way as they are

    installed in the locomotive. The oil level in the expansion

    tank should correspond with the temperature mark.

    Figure 1.23 ExpansionTank

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    23/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    13

    d. Labels

    Covering the transformer with stickers is

    forbidden. If stickers need to be added then they

    should be stuck on separate plates. The plates

    should then be tied to the transformer using

    strings (no wire).

    Figure 1.24 Labels

    e. Checks

    After transport and installation at the storing place the transformer should bechecked for any signs of oil leakage.

    1.6.1 Maintenance During Storage

    a. Checks

    According to the atmospheric conditions the oil level and the silica gel in the

    breather should be checked every 6 months.

    b. Oil level

    If the oil level is lower than the equivalent temperature mark, oil can be

    added by the filling cap on the expansion tank with the oil of the same quality.

    Mixing with oils which have significantly different parameters should be avoided.

    If the oil level is not visible at the expansion tank, the reason for the low oil

    level must be found. Oil should not be added by the filling cap of the expansion tank

    as long as reason has not been found.

    c. Breather

    If more than half of the silica gel is saturated (moisturized), then it must becompletely replaced. The old silica gel may be regenerated.

    The transformer must not stay longer than 3 hours without functional breather.

    1.7 FACTORS AFFECTING LIFE OF TRANSFORMER

    Life of transformer is affected by the following factors:

    1. Moisture2. Oxygen

    3. Solid Impurities4. Varnishes

    5. Slackness of winding

    a. Effect of moisture on transformer life

    Presence of moisture in oil is highly undesirable as it affects adversely the

    dielectric properties of oil. The moisture present in oil also affects the solid

    insulation of transformer. As paper insulation is highly hygroscopic in nature, when

    transformer is filled with oil, it absorbs the moisture from oil which affects itsinsulation properties as well as reduces its life. Solubility of moisture in oil increases

    with increase in temperature and oxidation products of oil. When the oil in service

    TFPG No. : 2027453Make : BHEL

    Date of O/H : 11.05.2014

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    24/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    14

    oxidizes, acids are formed. These acids increase moisture solubility of oil. Acids

    coupled with moisture further decompose the oil forming more acids and moisture.Thus the rate of deterioration of oil increases.

    Check the colour of silica gel in each inspection and if found pink, replace or

    reactivate crystals at 150 degree C. Test transformer oil for electric strength and

    water content in IC schedule & POH and carry out purification with high vacuumtype transformer oil filtration plant if required. Arrest the oil leakage if any.

    b. Effect of Oxygen

    Oxygen may be present inside the transformer due to air remaining in oil.

    The oxygen reacts and decomposes the cellulose of insulation. This forms an organic

    acid soluble in oil and sludge, which blocks the free circulation of the oil. The

    adverse effect of oxygen, which may be aggravated by catalytic action between hot

    oil and bare copper, increase the operating temperature.

    Carry out oil purification with high vacuum type transformer oil purificationplant periodically to remove atmospheric gases (air) and sludge.

    c. Effect of Solid Impurities

    The solid impurity present in the oil reduces its dielectric strength

    considerably. A good remedy is to filter the oil periodically.

    d. Effect of Varnishes

    Some varnishes having oxidizing effect, react with transformer oil

    and precipitate sludge on windings. Synthetic varnishes having acidinhibiting properties, generally delay the natural formation of acid and sludge

    in the oil.

    e. Effect of slackness of winding

    After few months of service, the transformer coils may suffer natural setting.

    This may wear the conductor insulation at some places and lead to an inter-turnfailure. The coils may also get displaced under load conditions or momentary short

    circuit conditions, which may result in electrical and magnetic unbalance andproduce even greater displacement. A good practice is, therefore to lift the core and

    windings to take up any slackness present at the first major schedule.

    Periodic maintenance of transformer is essential to ensure safety, reliability

    and trouble free operation of electric locomotive over a long time period.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    25/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    15

    CHAPTER 2

    MAINTENANCE

    2.1 PERIODIC MAINTENANCE SCHEDULES

    3-Phase (ABB) locomotives

    Ref. : Rly. Bd. Letter No. 97/Elect(TRS)/440/18/44(3-Phase), dt. 23.02.07

    Coaching Locos - WAP5/WAP7 locos

    Maintenance Schedule Periodicity Duration

    Trip inspection (TI)3000 kms or one trip,

    whichever is later

    2 hrs

    IA 90 days 4 hrs

    IB 180 days 6 hrs

    IC 270 days 8 hrs

    MOH 18 months 6 working days

    IOH

    4.5 years + 6 months or

    12 lakh kms. whichever is

    earlier.

    WAP-7 - 11 working days

    WAP-5 - 20 working days

    POH

    9 years + 6 months or

    24 lakh kms. whichever is

    earlier.

    28 working days

    Freight Locos - WAG9/WAG9H locosRef. : Rly. Bd. Letter No. 97/Elect(TRS)/440/18/44(3-Phase), dt. 23.02.07

    Maintenance Schedule Periodicity

    Trip inspection (TI) 45 days

    IA 90 days

    IB 180 days

    IC 270 days

    MOH 18 months

    IOH6 years + 6 months or 12 lakh kms.

    whichever is earlier.

    POH12 years + 6 months or 24 lakh kms.

    whichever is earlier.

    http://elocos.railnet.gov.in/CLW/23.02.07.pdfhttp://elocos.railnet.gov.in/CLW/23.02.07.pdfhttp://elocos.railnet.gov.in/CLW/23.02.07.pdfhttp://elocos.railnet.gov.in/CLW/23.02.07.pdf
  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    26/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    16

    2.2 TRIP INSPECTION

    1. OIL CIRCULATING PUMPS (SR & TFP)

    Visually examine all SR & TFP oil pumps for any oil leakage

    /any abnormal sound and take needful action

    No leakage

    2. MAIN TRANSFORMER

    iInspect the color of the silica gel. If it is pink, remove the filter

    from the locomotiveBlue

    ii Dry the silica gel in oven at 150 degree C and replace Blue

    iii

    Read off the oil level on the gauge situated on the conservator.

    Top up the oil as necessary and

    Check for any signs of leakage

    Middle strip

    +/- 6,

    No leakage

    ivPrismatic level gauge-clean the gauge with a dry cloth and

    check for leaks

    Cleaned & No

    leakage

    v

    Examine the flanges of the pipe couplings and flexible hose that

    link the transformer and conservator and check the holding

    clamps.

    Checked &

    Found intact

    viCheck/attend the condition of earthing shunts of transformer

    body (As per RDSO/SMI/0248)Intact

    vii Check the main TFP and its protection cover of drain cock fordamage/crack & oil leakage Checked &Found intact

    viiiCheck visually the foundation bolts of transformer and nylock

    nuts for proper locking

    Checked &

    Found intact

    ixCheck/attend stoochi coupling pipes of conservator for properlayout and fitment and attend for any leakage

    Intact/ Noleakage

    x Check VPTFP and VPSR for oil leakage on RH. No leakage

    xiExamine the HV bushing for sings of damage, burning etc.

    Replace if defective. Ensure RTV on base.

    Checked /

    Replaced

    xii Check the oil leakage from TFP bushing No leakage

    3. OIL COOLING UNIT CASING WITH RADIATOR

    iExamine flange joint for sign of cracks, oil leakage andloose/missing screws

    Checked/ intact

    ii

    Remove all dust, dirt and debris from the radiator chamber via

    the machine room access cover (using vacuum cleaner) in caseof less air flow booking

    Cleaned

    iiiVisually check the oil cooler radiator for any oil leakage /external damage from top and bottom

    No leakage/Nodamage

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    27/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    17

    2.3 IA, IB SCHEDULE.

    1 OIL CIRCULATING PUMPS (SR & TFP) IA,IB.

    i Visually examine all SR & TFP oil pumps for any oil leakage

    /any abnormal sound and take needful action

    Normal

    ii Check the mechanical support fasteners of all four oil pumps Normal

    2. MAIN TRANSFORMER

    i

    ii Inspect the colour of the silica gel. If it is pink, remove the filterfrom the locomotive

    Blue

    iii Dry the silica gel in oven at 150 degree C and replace Blue

    iv Read off the oil level on the gauge situated on the conservator.Top up the oil as necessary and

    Check for any signs of leakage

    Middle strip+/- 6

    No leakage

    v Prismatic level gauge-clean the gauge with a dry cloth andcheck/attend for leaks

    Cleaned & Noleakage

    vi Examine/attend the flanges of the pipe couplings and flexiblehose that link the transformer and conservator

    Checked &Found intact

    vii Check visually the foundation bolts of transformer and Nylock

    nuts, for proper locking

    Intact

    viii Check the condition of earthing shunts of transformer body (Asper RDSO/SMI/0248)

    Intact

    ix Visually inspect & clean the electrical connection to the

    insulator and condition of insulator for crack

    Intact

    x Visually inspect the condition of oil cooling metallic pipes,

    check/attend for leakage / damage & check all fixing clamps

    Intact /

    No leakage

    xi Check/attend stuchi coupling pipes of conservator for properlayout and fitment and attend for any leakage

    Intact/ Noleakage

    xii Examine the HV bushing for signs of damage, burning etc.

    Replace if defective. (Ensure RTV on base)

    Examined

    xiii Check the availability of hosepipe over the oil pipe

    compensator.

    Checked

    xiv Check the main TFP and its protection cover for damage / crack

    & oil leakage. (RDSO/TC/076)

    No crack / No

    leakage

    xv Check the oil leakage from TFP bushing. No leakage

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    28/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    18

    2.4 IC SCHEDULE.

    1 OIL CIRCULATING PUMPS (SR & TFP)

    i. Visually examine all SR & TFP oil pumps for any oil

    leakage / any abnormal sound and take needful action

    Normal

    ii Check the electrical connections of all four oil pumps Normaliii Check the mechanical support fasteners of all four oil

    pumps.

    Normal

    2. MAIN TRANSFORMER

    i Perform the sample test on transformer oil.

    Check specific value of BDV, DGA, moisture and acidity.

    30 kV (serviceableoil)

    ii If BDV value falls below 30KV/ DGA gases more,

    oil centrifuging to be done

    Done

    iii Inspect the color of the silica gel. If it is pink, remove the

    filter from the locomotive

    Blue

    iv Dry the silica gel in oven at 150 degree C and replace Blue

    v Read off the oil level on the gauge situated on theconservator. Top up the oil as necessary and

    Check for any signs of leakage

    Middle strip +/- 6

    No leakage

    vi Prismatic level gauge-clean the gauge with a dry cloth andcheck for leaks

    Cleaned & Noleakage

    vii Examine the flanges of the pipe couplings and flexible hosethat link the transformer and conservator

    Checked & Foundintact

    viii Visually inspect & clean the electrical connection to the

    insulator and condition of insulator for cracked, flashed

    mark & ensure red marking.

    Intact

    ix Check visually condition of foundation bolts of transformerand Nylock nuts for proper locking

    Intact

    x Check / attend the condition of earthing shunts oftransformer body (As per RDSO/SMI/0248)

    Intact

    xi Visually inspect the condition of oil cooling metallic pipes,

    check for leakage / damage & check all fixing clamps

    Checked Intact

    found no leakage

    xii Examine the HV bushing for sings of damage, burning etc.Replace if defective. Ensure RTV on base.

    Checked / Replaced

    xiii Check the availability of hosepipe over the oil pipecompensator

    OK

    xiv Check the main TFP and its protection cover fordamage/crack & oil leakage. (RDSO/TC/076)

    Checked & Foundintact

    xv Check the oil leakage from TFP bushing No leakage

    xvi Check/attend stoochi coupling pipes of conservator for

    proper layout and fitment and attend for any leakage

    Intact/ No leakage

    xvii Check the deformity of TFP drain cock cover guard, if

    deformed, replace it.

    Checked / Replaced

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    29/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    19

    2.5 MAIN TRANSFORMER (AOH) SCHEDULE

    1. MAIN TRANSFORMER (AOH)

    i Perform the sample test on transformer oil. Check specific

    value of BDV and moisture, acidity & DGA.OK

    ii Oil centrifuging to be done. And used separate plant fordifferent transformer oil. & check oil as per SMI 158.

    72 Hrs.

    iii Replace the silica gel with new crystals Blue

    iv Read off the oil level on the gauge situated on the

    conservator. Top up the oil as necessary and

    check for any signs of leakage

    Middle strip +/-

    6

    No leakage

    v Prismatic level gauge-clean the gauge with a dry cloth and

    check for leaksCleaned &

    No leakage

    vi Visually inspect the high voltage cable at the main

    transformer connection for damage or oil contamination.Replace the cable if damaged or if contaminated with oil

    OK

    vii Examine the flanges of the pipe couplings and flexible hose

    that link the transformer and conservatorChecked & Found

    intact

    viii Visually inspect & clean the electrical connection to the

    insulator and condition of insulator for crack & Red markingto be done.

    Intact

    ix Check visually condition of foundation bolts of transformer

    and Nylock nuts for proper lockingIntact

    x Check / attend the condition of earthing shunts of transformerbody (RDSO/SMI/0248 dated 22.11.2007)

    Intact

    xi Visually inspect the condition of oil cooling metallic pipes,check for leakage / damage & check all fixing clamps and

    also check the drain cock, isolating cock for oil leakage &clean it.

    Checked /

    Intact /

    No leakage/

    cleaned

    xii Examine the HV bushing for sings of damage, burning etc.

    Replace, if defective.Checked &Cleaned

    xiii Check the availability of hosepipe over the oil pipe

    compensator.

    OK

    xiv Check the main TFP and its protection cover for

    damage/crack & oil leakage. (RDSO/TC/076)Checked & Foundintact

    xv Check the oil leakage from TFP bushing No Leakage

    xvi Examine the bushing for signs of damage, burning etc.

    Renew if defective. Clean off all deposits and dirt from theinsulators

    Checked &

    Cleaned

    xvii Check conservator foundation welding and conservator stand

    bolts for tightness & ensure provision of double nutIntact

    xviii Check / attend Stoochi coupling pipes of conservator forproper layout and fitment and attend for any leakage

    Intact

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    30/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    20

    2.6 MAIN TRANSFORMER (IOH) SCHEDULE

    1. MAIN TRANSFORMER (IOH)

    i Perform the sample test on transformer oil. Check specificvalue of BDV and moisture, acidity & DGA.

    OK

    ii Oil centrifuging to be done. And used separate plant for

    different transformer oil. & Maintenance oil as per SMI158.

    72 Hrs.

    iii Replace the silica gel with new crystals. Blue.

    iv Read off the oil level on the gauge situated on the

    conservator. Top up the oil as necessary and check for anysigns of leakage.

    Middle strip +/- 6.

    No leakage.

    v Prismatic levels gauge-clean the gauge with a dry cloth and

    check for leaks.

    Cleaned & No

    leakage.

    vi Visually inspect the high voltage cable at the main

    transformer connection for damage or oil contamination.Replace the cable if damaged or if contaminated with oil.

    OK.

    vii Examine the flanges of the pipe couplings and flexible hose

    that link the transformer and conservator.

    Checked & Found

    intact.

    viii Visually inspect & clean the electrical connection to the

    insulator and condition of insulator for crack.

    Intact.

    ix Check foundation bolts of transformer with proper torqueand Nylock nuts for proper locking.

    Intact.

    x Check / attend the condition of earthing shunts of

    transformer body (RDSO/SMI/0248 dated 22.11.2007)

    Intact.

    xi Visually inspect the condition of oil cooling metallic pipes,

    check for leakage / damage & check all fixing clamps. Andalso check the drain cock, isolating cock for oil leakage &

    clean it.

    Checked Intact

    found no leakage.

    xii Examine the HV bushing for sings of damage, burning etc.

    Replace if defective & ensure red marking.

    Checked & Cleaned.

    xiii Check the availability of hosepipe over the oil pipe

    compensator.

    OK.

    xiv Check the main TFP and its protection cover for damage /

    crack & oil leakage. (RDSO/TC/076)

    Checked & Found

    intact.xv Check the oil leakage from TFP bushing. No Leakage

    xvi Examine the bushing for signs of damage, burning etc.

    Renew if defective. Clean off all deposits and dirt from the

    insulators.

    Checked & Cleaned.

    xvii Check conservator foundation welding and conservator

    stand bolts for tightness & ensure provision of double nut.

    Intact.

    xviii Check/ Attend Stoochi pipes of conservator for proper

    layout and fitment and attend for any leakage.

    Intact.

    xix Replace all rubberized cork sheet and bushing oil seal &gasket as per TC-76. Done

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    31/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    21

    2.7 MAIN TRANSFORMER POH SCHEDULE

    Figure 2.1 Lifting of Transformer Winding

    01 Visually inspect the electrical connections, earthing cable, bushing and insulators on

    the main transformer for cracks, chips and evidence of impact damage. Renew ifdefective. Clean the connectors and replace any damaged chipped or cracked

    insulators.

    02 Test oil sample for BDV, DGA, acidity and other lab tests. DGA to be done as per

    RDSO SMI (RDSO/SMI/138 & OEM Doc. Dt. 27th Nov. 1995).Incoming oil test.

    03 Check any leakage sign of oil from bushing, tank, pipe line, oil gauge

    If any attend the same/replased.

    04 Visually inspect the condition of oil cooling metallic pipes, check for leakage /

    damage & check all fixing clamps. Ensure instructions contained in RDSO s letter

    no. EL/3.2.1/3-Ph dated 30.07.09 for arresting oil leakages cases.

    05 Examine the flanges of the pipe couplings and flexible hose that link the transformerand conservator.

    06 Maintenance of assembly of electrical terminal of traction winding bushing 2U1-

    2V1, 2U2-2V2, 2U3-2V3 & 2U4-2V4 in indigenously manufactured transformerstype LOT 6500/7500 used in 3-phase drive locomotives type WAG9/WAP5 .(

    RDSO/ELRS/SMI/0228 dt. 13.08.02)

    07 Replace all sealing gaskets including tank cover gasket.

    08 Replace all rubberized cork sheet.

    09 Replace all TFP bushings rubber seals

    10 Cleaned the transformer winding & tank with filtered transformer oil.

    11 Fit the tank & bushing cover with new gasket

    12 Fit the all bushings, safety valve, temperature censer, gate valve, drain cock with

    new gasket.

    13 Dry out the windings moisture in vacuumed drying plant & fill the filtered oil.

    14 Carry out Insulation Resistance test and Tan delta test.

    15 Check the winding resistance, inductance and continuity test , ratio test of thewindings.

    16 Replace Transformer foundation bolts and bushing nuts.& Tighten with proper

    torque.

    17 Prismatic level gauge Clean the gauge with dry cloth to check for leaks. If any

    attend it.

    18 Replace the silica gel , in clean & attended breather assembly.

    19 Replace the transformer oil. .

    20 Conduct centrifuging of the oil (Use separate plant, the shell DIALA-DX oil should

    not be mixed with any other type of transformer Oil).

    21 Check the oil level on the gauge situated on the conservator. Top up if required andany sign of leakage.

    22 Finally cleaned & paint the transformer with accessories.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    32/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    22

    2.7.1 Painting Procedure

    Cleaning the affected area

    Using sand paper or a sander to smooth down and clean the affected area, a smooth

    transition to the intact paintwork must be made. Cover the area with primer by including the

    intact paint work out side.

    Top coating (Painting of transformer)

    Once the primer has been applied, wait at least 6 hours to apply the top coating. It

    can be applied by painting, rolling or spraying. The drying time at room temperature of

    about 20C is 6 hours; at temperatre of 60C it is 1 hour.

    Primer Two component epoxy resin

    Coating Two component polyurethane paint

    2.8 PROCEDURE FOR REPLACEMENT OF BUSHINGS

    Removal of bushings

    The gaskets and the washers outside of the transformer can be replaced withoutremoving the transformer lid. The oil level has to be decreased to 50mm from the lower side

    of the lid. Once the electrical terminals has been removed, the fixing nut can be untightened.

    Assembly

    Clan the contact surface before assembling, No oil or glue must be applied on the

    gaskets. Fit the gaskets with the insulator and the corresponding washers on the bolt. Beforetightening the fixing nut make sure that the inner insulator mates on the positioning wedge.

    Once the bushing has been assembled, tighten the fixing nut with a dynamometer

    (tightening torque). To ensure the tightness of the gasket, retighten the nut a few hours later.

    The oil level must be topped off to normal level, Use the filling system for this reason. The

    transformer has to be vented after oil filling.

    Gaskets of lid

    In order to avoid leakages

    between the upper frame of the tankand the lid, the fixing bolts must be

    tightened with the following

    tightening torque. It has to be

    applied on the nut where accessible.

    Figure 2.2 Gaskets of Lid

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    33/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    23

    2.9 TRANSFORMER OIL CHECK

    Taking oil samples

    Only clean and dry sample containers should be used. These containers must not

    contain any traces of cleaning fluids. Before taking oil samples, clean the draining valve on

    the transformer; 5 litres of oil should then be drained off; after that the sample containershould be rinsed using roughly litre of oil. The oil sample must be protected from light.

    The following are recommended as sample containers:

    - glass bottles made out of dark-coloured glass, with a polished glass stopper.

    - Tinned steel cans with a screw top.

    - Clear glass bottle which should be covered with an opaque cover after the samplehas been taken.

    The oil sample should be at least 2 litres. For laboratory tests, 5 litres are required. If an

    oil sample is required to determine the amount of water gas or air content, then special

    vacuum bottles should be used. In such a case we recommend that we should be notified

    about the preparation of bottles and suction equipment.

    Checking for any solid impurities in the oil.

    A test tube should be filled with the oil sample and held up against a light source. If

    there are any solid impurities in the oil, then the oil from which the sample comes should be

    filtered.

    Simple test for water content

    This is done using the so-called Spatter-test, i.e. the oil sample heated in the test

    tube up to 105-110C. If there is any water in the oil then this will be noticeable if the oilcracles, snaps or bubbles. If the oil is overheated then the presence of water is falsely

    indicated; the upper temperature should therefore not be exceeded.

    Dielectric strength (IEC test)

    In accordance with the IEC standard 156 (which also complies with the Swiss

    standard), this test should be performed using 12.5mm ball electrodes with a diameter of

    2.5mm or with the half ball electrodes (so-called VDE Kalloten) also with a diameter of

    2.5mm. The oil sample (temperature 15-25C) should be slowly poured (to avoid airbubbles) into the clean test container; the test should be carried out immediately. The

    voltage should be increased evenly up to break down at a rate of 2 kV/second; this should be

    carried out 6 consecutive times. After each time the space between the electrodes must be

    free of traces of breakdown; use a clean and dry glass rod (diameter 2mm) and move it

    slowly in-between the two electrodes. All six break down voltages should be noted and the

    arithmetic average calculated (i.e. the sum of the individual values divided by six). None of

    the individual values should lie more than 15% below the average value, otherwise the test

    must be repeated using a new oil sample.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    34/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    24

    2.10 TESTING OF LOCO TRANSFORMER

    2.10.1 Tests

    Following common tests to be carried out in the transformer either in case of failure or

    during overhauling in oil filled conditions.

    a. Insulation resistance test.(Meggering)

    b. Continuity test

    c. Winding resistance test

    d. Ratio test

    e. Winding inductance test

    a. Meggering

    Check the insulation resistance of windings. It should be minimum 2100 M ohms.

    Primary to earth by 2.5 kV megger. Secondary to earth by 1 kV megger.

    Primary to secondary by 2.5 kV megger.

    Primary to BUR. by 2.5 kV megger.

    BUR. to earth by 1 kV megger.

    Secondary to BUR. by 1 kV megger.

    Primary to H.L. by 2.5 kV megger.

    H.L. to earth. by 1 kV megger.

    GOD Terminal. to earth. by 1 kV megger.

    SOD Terminal. to earth. by 1 kV megger.

    b. Continuity Test

    Check the continuity of the following windings with the multimeter:

    Primary winding

    Secondary windings

    BUR winding

    H.L. winding. SOD. winding.

    GOD. winding.

    c. Winding Resistance Test

    SN WINDING RESISTANCE VALUE

    LOT-6500 LOT 7500

    1 Primary winding

    2 Secondary

    windings

    3 BUR

    winding

    4 H.L.

    winding.5 SOD. winding

    6 GOD. winding

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    35/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    25

    d. Ratio Test / Polarity Test.

    Apply 230V a.c. supply to the primary winding of the transformer across 1U

    1V and check the voltage appearing at the following terminals.

    1 And 2V1 2V1 & 2U2 Sorted 23.35 V

    4 2U3 & 2U4. 2V3 & 2U4 Sorted 23.35 V5 2U1 & 2U2 2V1 & 2V2 Sorted 0 V

    6 2U3 & 2U4 2V3 & 2V4 Sorted 0 V

    e. Winding inductance test

    SN WINDING INDUCTANCE VALUE

    LOT-6500 LOT 7500

    1 Primary winding

    2 Secondary windings

    3 BUR winding

    4 H.L. winding.5 SOD. winding

    6 GOD. winding

    2.11 TESTING EQUIPMENT

    LIST OF TESTING INSTRUMENTS

    Sr.No. Instrument Make / Model No. Range/Capacity

    1 Power Analyzer Yokogawa / WT 330 or similar As per manual

    2 100 KV HV Test set SEV or similar 100 KV, 100 mA

    3 100 KV Motorised Oil Test Set SEV or similar 0-100 KV4 Ratio meter (TR100) Fifty Hertz / TR100 or similar --

    5 Digital Micro ohm meter Prestige / PE-17RP or similar As per manual

    6 Digital Megger Megger Co. or similar 5KV

    7 Digital Frequency meter Prestige or similar 200 HZ

    Power analisor Megger Voltage Ratio Meter

    Oil BDV Tester 100 kV HV SET Micro Ohm Meter

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    36/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    26

    2.12 INSTALLATION OF THE TRANSFORMER ON LOCOMOTIVE

    During assembly in the locomotive, the main valves of the transformer stay closed.

    Lift the transformer slowly under the under frame of the locomotive. Make sure that the twocentering pins fit in the corresponding hole.

    The transformer has 4 fixing points each with 4 bolts. So that the bolts are relived of

    any strains caused by share forces in the horizontal and vertical directions, a centering pin isprovided on two diagonally opposite fixing points. The fixing plates are covered with a layer

    of paint to prevent corrosion which could between aluminium and steel.

    The mounting surfaces are made in such a way that the exchange of the transformer

    is guaranteed; tolerances have been taken into account.

    Assemble the hot dip galvanized washers under the supports when assembling the

    bolts. Tighten the fixing bolts with 675 Nm.

    a. Fitting of Oil Piping

    Before removing the blanking flanges make sure that all blocking valves are

    closed. They stay closed during the whole installation.

    Special care must be taken to ensure that all pipes, pumps and coolers have beenthoroughly cleaned and flushed with insulation oil before one proceeds with

    assembling.

    b. Fitting of the angled connectorBefore the angled connector can be fitted onto the bushing, the bushing must

    be properly cleaned. No dirt should be trapped in the connection. To allow easy

    fitting, the bushing should be slightly greased with silicon. When mounting the

    angled connector care should be taken that no air is trapped inside. The connector

    can be vented using a nylon thread on the bushing, which is pulled out when the

    angled connector is fitted.

    c. Electrical Connections

    The electrical terminations of the bushings have to be carried out in a way,

    that the nut 11.1 stay accessible to be re-tightened.

    Electrical connections must not be numb. They should be made flexible so

    that the bushing isnt stained. Cable connections should be made with a loop, forbars use flexible ribbon to connect them

    on the bushing.

    When assembling the electricalconnections, make sure that the nut 11.1

    does not become loose. Keep a distance

    of min. 3 mm between the 2nuts. After

    assembling of the connection re-tighten

    the nut 11.1. The tightening torque for

    each type of bushing is indicated in the

    table given below

    Figure 2.3 Electrical Connection

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    37/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    27

    Tightening torque and max. horizontal load for DIN bushings

    DIN type Drawing no. D Section (mm2) M F

    Bolt Extern.

    DT 1/250 HSTN 310 500 M12 74.5 84.3 10 50

    DT 1/ 630 HSTN 310 501 M 20 220 245 30 60

    DT 1/1000 HSTN 310 502 M 30 x 2 596 621 65 80

    DT 1/2000 HSTN 310 503 M 42 x 3 1150 1210 150 100

    d. Earthing Terminal Fitting

    In order to avoid discharges and unwanted failures, all metallic parts insideand outside the transformer are earthed. The earthings of the transformer active part

    and the reactors are connected with each other via the tank.

    The marked earthing terminals have to be connected to the locomotives

    earthing terminals.

    Figure 2.4 Inside Earthing Figure 2.5 Outside Earthing

    e. Filling the remaining oil

    Once the transformer has been installed in the locomotive and all piping

    connections to the heat exchanger and the pump have been made, it is necessary to

    fill the remainder of the cooling system with oil. The oil used must comply with the

    relevant specifications. Casting doubt on, an oil test has to be carried out.

    The transformer main valves should only be opened when all pipes and the

    heat exchanger have been filled with oil and vented. No air should enter the

    transformer assembly from the piping or the heat exchanger.

    f. Filling with oil barrel

    The barrel with the insulation oil has to be brought on a higher level than the

    lid of the transformer, join the oil barrel with a flexible pipe to the draining tap (13.1/

    13.3). All apparatus must be cleaned and free of dirt and moisture . Fit a silica

    breather to the barrels breather port.

    g. Filling with pump

    The oil filling system, which should be suitable to a standard oil barrel

    standing vertically, must not exceed a flow of 5litre/min and it must contain a noreturn valve. All apparatus must be cleaned and free of dirt and moisture. Fit a silica

    gel breather to the barrels breather port. Fit the filling system with a flexible pipe tothe draining tap (13.1/13.3). Start pumping and drive any air out of the filling

    system.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    38/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    28

    h. Venting the pipework and heat exchangers

    Make sure that there isno air in the filling hose. Crack open the drawing tap(13.1/13.3). Open the venting tap (13.2) on the heat exchanger until oil runs out.

    Close venting tap (13.2) and draining tap (13.1/ 13.3). Repeat this procedure on the

    opposite side. Connect the filling hose to the draining tap (13.4/ 13.6) and vent thepipe with venting screw (13.5) on the heat exchanger.

    If during the filling process a change of barrel is required, stop pumping

    before air is drawn into the system. Close the venting and the filling tap, change the

    barrel, run the pump and drive any air out of the filling system. Continue filling.

    Figure 2.6 Transformer Layout in the Loco

    i. Oil pumping

    Before the pump is put up into action, make sure that the pumps, piping and

    heat exchanger are filled with oil. Never start the pump without oil.

    j. Checking the direction of rotation

    Remove the screw plug (14.1) and push the head face on the shaft of the

    rotation indicator (14.2). The rotation direction of the pump is correct when therotation indicator turns in the same direction as the arrow. After completing the

    check, refit the screw plug (14.1)

    Figure 2.7 Transformer Layout in the Loco

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    39/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    29

    k. Venting

    Once all pumps, pipes and heat exchangers are filled up with oil, the

    transformer main valves can be opened. Secure the valves in open position. To driveany remaining air out of the system, put the two oil pumps in operation for 30

    seconds. Let the whole system resting during 30 minutes. Connect the filling system

    to one of the draining taps, put it into action and crack open all vent plugs (15.1) onthe transformers lid until oil leaks out. Repeat this procedure until the total breathing

    of the system. Adjust the oil level in the expansion tank after.

    Figure 2.8 Transformer Assembly Venting Layout

    2.13 CHECK POIINTS WHILE MAINTENANCE

    a. Oil Level Check

    The oil level in the expansion tank has to be checked each time beore

    switching on the transformer and in case of non use at least every 6 months. The oil

    level in the expansion tank must be equal to the corresponding temperature mark on

    the sight glass (17.3)

    b. Oil Level beneath the corresponding temperature mark

    In case of the oil level is under the corresponding temperature mark, oil can

    be added directly by the filling plug on the expansion tank. The oil used mustcomply with the relevant specification.

    c. Oil level not visible on the sight glass

    If the oil level isnt visible on the sight glass (17.3), the transformer must not

    be switched on. The oil must not be toped off by the filling plug on the expansion

    tank. One have to control the distance between the lid and the oil level in the

    transformer. For this reason

    open one of the vent plug on the transformer lid and

    measure the distance between the upper side of the plug and the oil level. If the

    distance is lower than 100mm the oil can be topped off by the draining valve of thetransformer or the pipes between transformer and heat exchanger. The transformer

    has to be vented after.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    40/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    30

    If the distance between upper side of the plug and the oil level is more than

    100mm then the level can only be topped off under vacuum conditions. For thisreason the transformer must be removed from the locomotive and put in a vacuum

    oven.

    d. Oil level above the corresponding temperature mark.

    If the oil level is above thecorresponding temperature mark, oil can

    be drained by the draining valve on the

    transformer.

    Figure 2.9 Expansion Tank

    e. Silica Gel Breather

    According to the atmospheric conditions, the colour of the silica gel should

    be checked roughly every six months. When more than half of it is pink (saturated

    with water), then it should be replaced. The saturated silica gel can then be dried out.Put it in an oven and increase the temperature slowly min 115C to max. 150C.

    Keep the temperature until the silica gel turns blue again. Silica gel should not bedried-up in sun light as because of insufficient heat only the outer layer gets dried up.

    However, this process should not be repeated too many times; after a while

    the silica gel appears to be not so effective, probably due to the ingress of dirt.

    Figure 2.10 Silica Gel

    f. Leakage of expansion tank

    Whenever breather, silica gel colour more than half got pink (saturated withwater)

    Bad Condition

    Good Condition

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    41/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    31

    2.14 TRANSFORMER OIL

    The transformer unit is filled with 2000 kg of mineral oil. The oil serves as a

    cooling and insulating agent.

    2.14.1 Oil Specification

    Ref. no Characteristic Unit Value Test method

    00001 Ident. Text -- Insulation oil T1

    00002 Ident no. -- NBT 402614P0201

    01000 Description -- The insulation oil T1 is a pure

    mineral product without any

    additive; it is used in transformer

    and switch gear.

    01120 Density at 20C g/ml 0.895 ISO 3675

    DIN 51757

    01500 Delivery instructions -- ZN 02125

    01800 Documentation -- ZLC documentation and QZ

    HSTC 419458

    05100 Colour -- Pale yellow to yellow

    07900 Special properties -- The oil is not cloudy and is free of

    solid particles and water

    26350 Pour point

    IEC class IA

    IEC class IIA

    C - 30

    - 45

    ISO 3016

    ASTM D 97-66

    DIN 51597

    29300 Flash point in a

    enclosed crucible

    C 130 ISO2719

    ASTM D 9366

    DIN 51758

    22500 Thermal expansion

    coefficient

    K-1 Standard NB

    214200

    31300 Dielectric loss factor

    tan at 90C 50 Hz

    -- 0.005 IEC publ. 247-1978

    VDE 0370/ 12.78

    35300 Break-down voltage kV 50 IEC publ. 156

    43700 Interface tension mN/m 40 ASTM D 971-5045100 Cinematic viscosity

    At + 20C

    At + 40C

    At15C class IEC

    IA

    At30C class IIA

    mm2/s 25

    11

    800

    1800

    ISO 3104

    51370 Corrosive sulphur

    content-- None DIN 51353

    55100 Neutralisation value mgKOH/g 0.03 IEC Publ. 296-197855350 Aniline point C 80 ISO 2977

    DIN 51775

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    42/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    32

    2.14.2 Purification of Transformer Oil

    Figure 2.11 Purification of Transformer Oil

    The object of oil purification is to remove all contaminants such as water, carbon

    deposits, dirt, sludge, dissolved moisture and gases. The most important quality to be

    preserved is the di-electric strength, which is affected by the presence of moisture.

    The insulating materials used in the winding are hygroscopic by nature and therefore

    moisture is absorbed through defective breathers, gaskets and addition of untreated make upoil. It is essential to remove these impurities by purifying the oil when the dielectric strength

    goes below the permissible limits.

    The purification plant should be capable of removing dissolved air/ moisture in the

    form of free and finely dispersed water vapour and moisture in solution, sludge and fibers,

    gases, carbonaceous products formed due to arcing and drum scale or any other solid

    particles from insulating oil.

    The plant should be capable of purifying the rated capacity of transformer oil to the

    following parameters in maximum three phases.

    a. Suspended impurities maximum 1 micron particle size.

    b. Water content from 100 ppm to less than 5 ppm

    c. Gas removal from fully saturated i.e. 10 to 12% by volume with air/gas

    down to less than 0.25%

    d. Acidity correction with addition of clay filters the neutralization index should go

    down from 0.5 to 0.05 mg KOH/ gm

    of oil.

    e. Dielectric strength Minimum 60 kV

    f. Dissipation factor of

    oil/ tan delta at 90C 0.002

    The switching ON & OFF of the heater groups should be thermostatically controlledso that the temperature of the oil during treatment is not be permitted to rise above 60C.Operating vacuum should be better than 1 torr.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    43/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    33

    Filtration of EHV grade oil to be carried out at a vacuum level of 98% at atemperature of 60 degree C and of inhibited oil at a pressure of 0.15 torcillie at a

    temperature of 60 degree C, provided the specific resistance is within limits. Filtrationshould continue till such time the oil is completely dried. Check the filtered oil sample for

    electrical strength and water content and if these parameters are within the limits, the oil is

    fit for use and if not, repeat filtration till electric strength and water content are within limits.

    Water content in Oil

    Test : Water content (PPM)

    Test method : As per IS:335-1983

    Periodicity : IC/ AOH/ IOH/ POH

    Permissible limit : 35 PPM (Max.)

    Requirement of new oil : 25 PPM (max.)

    Figure 2.12 Water content test set

    Acidity in Oil

    Test : Total Acidity

    Test method : As per IS:1448-67

    Periodicity : IC/ AOH/ IOH/ POHPermissible limit : 0.5mg KOH/gm (Max.)

    Requirement of new oil : 0.03mg KOH/gm (Max.)

    Figure 2.13 Acidity Test Set

    Oil breakdown voltage

    Test : Electrical Strength (Break down voltage)

    Test method : As per IS:6792-72

    Periodicity : IC/ AOH/ IOH/ POHPermissible limit : 30KV (rms)(min.)

    Requirement of new oil : 60 KV (rms)

    Flash point

    Test : Flash point

    Test method : As per IS: 1448-1970

    Periodicity : IOH/ POH

    Permissible limit : 125 deg. C (Min)

    Requirement of new oil : 140 deg. C (Min)

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    44/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    34

    INSULATION RESISTANCE DURING DRYING OUT

    Readings of temperature and insulation resistance should be recorded every two

    hours, from commencement until the full operation is completed. If these readings areplotted on a graph, the appearance will be as shown in fig.

    It is observed that there are four distinct stages:

    A. Initially the insulation resistance drops down to a low value because of rise in

    temperature of the oil up to about 60 degree C.

    B. Insulation resistance will continue to remain at a low level despite temperature being

    maintained at a high level until most of the moisture from the windings and oil hasbeen driven out.

    C. The insulation resistance will thereafter rise gradually and level off, indicating that all

    moisture has been driven out and the drying out operation has been completed. At

    this point oil circulation should be discontinued.

    D. As the oil cools off, the insulation resistance will rise much above the leveling off

    point at the end stage (C). This is because the insulation resistance value doubles for afall in temperature of about 10C to 15C.

    2.14.3 Condition Monitoring Of Transformer by Dissolved Gas Analysis

    Test : Dissolve gas analysis

    Test method : As per SMI 138

    Periodicity : IC/ AOH/ IOH/ POH

    Permissible limit : As per SMI 138

    Requirement of new oil : --

    Figure 2.15 DGA Analysis Set (A)

    Fi ure 2.14 Insulation Resistance Gra h

    INSULATIONRESISTANCEINMEGOHMS

    TEMPERATURE

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    45/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    35

    A. Introduction

    In order to detect incipient faults in the transformer and to arrest

    deterioration/ damage to the transformer insulation, gases dissolved in the

    transformer oil are detected, analysed and preventive measures adopted.

    Gas Chromatography method is used for detection of the dissolved gases andidentification of incipient faults. The most significant gases generated bydecomposition of oil and deterioration of paper insulation on the conductor are

    hydrogen, methane, ethane, ethylene and acetylene. The quantities of these gasesdissolved in transformer oil vary depending upon the type and severity of the fault

    conditions.

    B. Sensitivity Limits

    Gas Chromatography apparatus should be able to detect the following

    minimum concentration of dissolved gases:

    Hydrogen : 5 ppmHydrocarbon : 1 ppm

    Carbon oxides : 25 ppm

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    46/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    36

    Figure 2.16 DGA Gas Extraction System

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    47/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    37

    C. Establishment of Reference Values/ Bench Marks

    To establish a reference value/ bench mark, gas as generated from initial

    sample of oil from each healthy transformer should be collected. Results of theanalysis are taken as a reference value/ benchmark. Results of later periodic analysis

    are compared with the benchmark for each transformer.

    D. Establishment of Norms

    The contents of various dissolved gases in the transformer oil vary with

    design and operating conditions. It is desirable that the values of concentration ofgases of healthy transformers of different age groups are to be gathered by the

    Railways concerned to evolve suitable norms. However, as a starting point, the

    permissible concentrations of dissolved gases in the oil of a healthy transformer are

    given below as guidelines:

    Gas Less than 4 years

    in service (ppm)

    4-10 years in

    service (ppm)

    More than 10 years

    in service (ppm)

    Hydrogen (H2) 100/150 200/300 200/300

    Methane (CH4) 50/70 100/150 200/300

    Acetylene (C2H2) 20/30 30/50 100/150

    Ethylene (C2H4) 100/150 150/200 200/400

    Ethane (C2H6) 30/50 100/150 800/1000

    Carbon dioxide (CO2) 3000/3500 4000/5000 9000/12000

    E. Diagnosis of Fault

    Basic Diagnosis of DGA is based upon the quantities of gases generated.

    Types of gases in excess of norms produced by oil decomposition/ cellulosic

    material depend upon the hot spot temperature produced by faults.

    Characteristics of gases associated with various faults are as under:

    Methane (CH4) Low temperature hot spot

    Ethane (C2H6) High temperature hot spot

    Ethylene (C2H4) Strong over heating

    Acetylene (C2H2) Arcing

    Hydrogen (H2) Partial discharge

    Carbon dioxide (CO2) Thermal decomposition of paper insulation

    Carbon monoxide (CO)

    F. Word of Caution

    To start with the diagnosis, it is necessary to be satisfied that measured gas

    concentrations are significant and high enough to warrant diagnosis, because some

    amount of gases will always be there due to normal operating conditions without any

    fault but it can be sufficient to be misleading. The reasons for the situation are:

    Gases formed during the refining processes and not completely removed by oil

    degassing.

    Gases formed during drying and impregnating the transformer in sheds/

    workshops.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    48/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    38

    Gases formed in the event of previous faults and not completely removed from

    the oil-impregnated insulation before being refilled with degassed oil.

    Gases formed during repairs by brazing, welding, etc.

    G. Procedure for Fault Diagnosis

    Obtain the results of concentration of various gases in terms of microlitre (ppm).

    Compare the concentrations with sensitivity limits. These should be at least ten

    times the sensitivity.

    If it exceeds sensitivity limits, compare with benchmarks.

    If it exceeds benchmarks, compare concentrations with norms depending upon

    age and design of transformer.

    If one or more gases are above norms, compare with the last sample results; ifincrease is sufficient, obtain a check sample.

    If the check sample confirms the results, calculate the rate of increase of gas. If

    rate of increase is more than 10% per month, it is considered rapid and warrants

    immediate further investigations including lifting of core and internal inspection.

    If the gas production rate is medium, i.e., less than 10% per month, sampling

    frequency to be increased from quarterly to monthly.

    Take a planned shut down for further investigation.

    *****

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    49/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    39

    Figure 2.17 Typical Arrangement in a Gas Chromotograph

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    50/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    40

    Dissolve Gas Analysis (DGA)

    Dos

    1. Give sufficient time for stabilization.

    2. Replaced the saptan after every 15 injection

    3. Check sapton before start the equipment.

    4. Keep standby colomn.

    5. Use stabilization electricity with proper earthing.6. Flush the syringe after each injection.

    7. While fire use proper fire extinguisher.

    8. Check all leakage before testing.

    Donts

    1. Dont start TCD before opening of gas.

    2. Dont increase filament current out of safe limit.

    3. Dont excess gas flow in column.

    Figure 2.18 Sample Strip Chart

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    51/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    41

    CHAPTER 3

    MODEL QUESTIONS

    3.1 OBJECTIVE

    1. Before starting work on faulty circuit it should be ensured that

    a. The faulty circuit has been isolated from power supply and earthed.

    b. The worker is capable to do the work.

    c. The connections are not approachable.

    d. None of the above.

    2. One can protect himself from electric shock by wearing hand gloves of good.

    a. Conducting materialb. Insulating material

    c. Semiconductor material

    d. Any of the above.

    3. Which of the following are safety precautions?

    a. Dont touch live wire or equipment with bare hands.

    d. Before switching on DJ, see no one is working inside loco.

    c. Use insulated melting and hand gloves.

    d. All of the above.

    4. Which material is recommended as fire extinguisher in electrical cases?

    a. Carbon tetra chloride

    b. Carbon dioxide

    c. Sulphur hexafluoride

    d. Any of the above.

    5. The BDV of transformer oil should be

    a. 20kV

    b. 30kV

    c. 40kV

    d. 50kV

    6. The colour of moisturized silica gel is

    a. Pink

    b. Blue

    c. Yellowd. Green

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    52/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    42

    7. The material filled in breather of transformer is

    a. Silicagel

    b. Sulphuric acid

    c. SF6

    d. Mineral oil

    8. The protective device to internal fault in a transformer is

    a. Current relay

    b. Bucholz

    c .Lead

    d. Silicon steel

    9. Three phase Loco Transformer Tank & Lid made of material.

    a. Iron

    b. Copper

    c. Stainless Steel

    d. Aluminium

    10. Which of the following is not the function of transformer oil

    a. Cooling of winding and core.

    b. Providing additional insulation

    c. Media for are quenching

    d. Provides inducting coupling

    11. Transformer oil should be free from

    a. Odour

    b. Gases

    c. Temperature

    d. Moisture

    12. The short circuit test of a transformer gives

    a. Copper loss at full load

    b. Copper loss at half load

    c. Iron loss at any load.

    d. Sum of iron loss and copper loss.

    13. The type of oil, which is suitable as transformer oil is

    a. Crude oil

    b. Organic oil

    c. Mineral oil

    d. Animal oil

    14. Transformer is an example of

    a. Current transformer

    b. Potential transformer

    c. Auto transformer

    d. All of the above

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    53/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    43

    15. The colour of fresh transformer oil is

    a. Pale yellow

    b. Dark brown

    c. Blue

    d. Colourless

    16. The purpose of conservator tank in a transformer is to

    a. Monitor oil level

    b. Top up the oil

    c. Both a & b above

    d. None of the above.

    17. The saturated silica gel can be dried out in the oven at the max temperature until

    silica gel turn blue again.

    a. 60C

    b. 160C

    c. 150C

    d. 115C

    18. The oil sample container should be rinsed sample oil quantity

    a. Ltrs.

    b. 1 Ltrs.

    c. 2 Ltrs.

    d. 1 Ltrs.

    19. The oil sample are require to test.

    a. 2 Ltrs.

    b. 3 Ltrs.

    c. 4 Ltrs.

    d. 5 Ltrs.

    20. Dielectric strength of oil should be performed using 12.5 mm ball electrodes with a

    gap of-

    a. 04mm

    b. 05mm

    c. 2.5mm

    d. 03mm

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    54/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    44

    3.2. FILL IN THE BLANKS

    1. Transformer is a .device

    2. G-9 Loco transformer has.windings

    3. G-9 Loco transformer has..tank

    4. G-9 Loco Required variable voltage is achieved by the use of ..

    5. An emf induced in a coil due to variation of flux in another coil is called

    6. The coils of a transformer are wound on a core of .material

    7. The conductors used in HV and LV windings of loco transformer are

    8. In G-9 Loco The primary side is protected from the voltage surges by means of.placed on the roof of the locomotive.

    9. The auxiliary winding is protected from sudden rises in voltage by means ofconnected across the winding.

    10.Ingress of moisture is prevented by means of .

    11.The complete cooling arrangement includes.., ..and..

    12.The oil pump and the cooler are connected to the conservator by

    13.The breather is attached to and contains

    14.Pink colour of silica gel indicates..

    15. The colour of transformer oil become dark brown, it indicates presence of

    16.Operating vacuum of transformer oil purification plant shoul be .

    17.DGA stands for ..

    18.Transformer must never be lift without its.

    19.Oil BDV Test six consecutive reading should not lie more then

    20.The lifting ropes should not make a smaller angle then.with the horizontal.

    3.3 SAY TRUE OR FALSE

    1. Transformer transforms power from one AC circuit to another AC circuit, at samefrequency.

    2. Transformer can raise or lower the voltage.

    3. Transformer can raise or lower the frequency.

    4. Two circuits in a transformer linked by a common magnetic flux through a path of

    low reluctance.

    5. In case of step up transformer, the transformation ratio will be more than one.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    55/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    45

    6. Constructional features of a loco transformer are more or less same other powertransformer.

    7. 25 kV condenser/ cable head bushing is mounted on the top of the tank cover.

    8. The cooling arrangement of the loco transformer is force oil forced air type.

    9. In G-9 Loco the complete cooling equipment is mounted on the cover of the loco

    transformer.

    10. In G-9 Loco spring-loaded safety valve is fitted to the top of the conservator.

    11. Presence of moisture in transformer oil is highly desirable.

    12. The oxygen present in transformer reacts with insulation and forms an organicacid.

    13. The solid impurities present in insulation oil strengthen its dielectric strength aswell as insulation of windings.

    14. The slackness of winding is desirable factor to create electrical and magnetic

    unbalance of the coils.15. Meggering is done to check the insulation resistance of the windings.

    16. The tightening torque of the bolts of tank and lid must be 70 Nm.

    17. To arrest the oil leakage from bushing RDSO has recommended to use ISI makegaskets.

    18. Bushing gaskets to be replaced as per TC- 076.

    19. New M.S. hardware may be used in transformer flange joints fitting.

    20. Periodic maintenance of transformer is essential to ensure safety, reliability andtrouble free operation of Locomotives.

    ANSWERS

    3.1- 1 (a), 2 (b), 3 (d), 4 (b), 5 (d), 6 (a), 7 (a), 8 (a), 9 (d), 10 (d), 11 (a),

    12 (a), 13 (c), 14 (d), 15 (a), 16 (c), 17 (c), 18 (a), 19 (d), 20 (c).

    3.2- 1- Static, 2- 04, 3-Aluminium Alloy, 4-GTO or IGBT, 5-Metual Induction,

    6- Leminated, Silicon Steel, 7-Continuous Transposed Cu Conductor,

    8- Lightening arrester, 9-RCL Damping, 10-Air dehumidifire,

    11- Radiator & Blower, 12-oil Pipe, 13-Conservator, Silicagel, 14-Humid

    15- Acid & Impurties, 16-1Torr, 17-Incipien fault, 18-Lid, 19-15%, 20-60.

    3.3- 1-T, 2-T, 3-F, 4-T, 5-T, 6-T, 7-T, 8-T, 9-F, 10-T, 11-F,12-T, 13-F, 14-T, 15-T, 16-T, 17-F, 18-T, 19-F, 20-T.

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    56/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    March, 2015 Maintenance Handbook on Transformer of 3 Phase Electric Locomotives

    46

    AN APPROACH TO EQUIPMENT FAILURE INVESTIGATION

    A. On Failure Aspects

    1. Occurrence

    2. Date of occurrence

    3. Past similar occurrences if any

    4. Analysis of failure i.e. why did it happen?

    5. Whether the rate of failure is worse than other installations?

    B. On Maintenance Aspects

    1. Whether schedule maintenance & required testing have been carried out on thefailed equipment as per norms stipulated?

    2. Does the frequency of maintenance require change?

    3. Was the work properly supervised?

    4. Was any RDSO modification required to be done?

    5. Is any modification possible to avoid failure?

    C. About Staff

    1. Is the quality of work done satisfactorily?

    2. Is the skilled staff properly trained to carry out the work?

    3. Is the SMI available with them?

    4. Are proper tools available with the staff?

    D. About Material

    1. Is the material received from approved source?

    2. Whether the material is as per approved specification?3. Can a better material be used?

    E. About Testing

    1. Is the testing equipment available?

    2. Could testing procedure be improved to weed out the failures?

    3. Whether testing equipment are calibrated?

    F. General Points

    Whether following points were checked / performed properly?

    1. Proper contact

    2. Clearances

    3. Capacity

    4. Proper contact pressure

    5. Crack detections

    6. Cleaning

    7. Proper connections/alignment

    8. Cross checks/super checks

  • 7/25/2019 Maintenance Handbook on Transformer of 3 Phase Electric Locomotive

    57/59

    CAMTECH/E/14-15/3Loco Transformer/1.0

    Maintenance Handbook on Transformer of 3 Phase Electric Locomotives March, 2015

    47

    ANNEXUREI

    Reliability Action Plan (RAP)

    Condition monitoring of loco transformer by Dissolve Gas Analysis. (RDSO/SMI/138 &OEM Doc. Dt. 27th Nov. 1995).

    Replacement of bushing gaskets during IOH inspection.( ELRS/TC/0076 dt. 17.09.2002).

    Maintenance of transformer oil in service.(RDSO/ELRS/SMI/158 dtd. 19.01.95).

    Maintenance of assembly of electrical terminal of traction winding bushing 2U1-2V1, 2U2-

    2V2, 2U3-2V3 & 2U4-2V4 in indigenously

    manufactured transformers type LOT 6500/7500 used in 3-phase drive locomotives typeWAG9/WAP5.( RDSO/ELRS/SMI/0228 dt. 13.08.02)

    Ensuring tightness of stuchi coupling, base plate and conservator tank foundation bolt

    during overhauling. As per OEM guidelines & present

    practices followed by shed.

    Ensure instructtions contained in RDSOs letter no. EL/3.2.1/3-Ph dated 30.07.09 for

    arrest