man owts-capacitor eng x2
TRANSCRIPT
-
8/4/2019 MAN OWTS-Capacitor Eng x2
1/19
- Stand 20. Oktober 2004Patente: xxx.xxx.xxx.xxx Sach-Nr. 89 900 7175
Mess- und OrtungstechnikMeasuring and Locating Technologies
LeitungsortungLine Locating
RohrleitungsnetzeWater Networks
KommunikationsnetzeCommunication Networks
ElektrizittsnetzePower Networks
Issue: X2 (2006/22)Serial no.: 890010367
Operating Manual
Additional Capacitor forOWTSOscillating Wave Test System(Partial Discharge Cable Diagnosis)
uktbild wie in den Prospekten ohne Rahmen
-
8/4/2019 MAN OWTS-Capacitor Eng x2
2/19
Additional Capacitor OWTS
Consultation with SebaKMT
The present manual has been designed as an operating guide and forreference. It is meant to answer your questions and solve your problems in asfast and easy a way as possible. Please start with referring to this manual
should any trouble occur.
In doing so, make use of the table of contents and read the relevant paragraphwith great attention. Furthermore, check all terminals and connections of theinstruments involved.
Should any question remain unanswered, please contact:
Seba Dynatronic
Mess- und Ortungstechnik GmbH
Hagenuk KMT
Kabelmesstechnik GmbH
Dr.-Herbert-Iann-Str 6D - 96148 Baunach
Phone: +49 / 9544 / 68 0Fax: +49 / 9544 / 22 73
Rderaue 41D - 01471 Radeburg / Dresden
Phone: +49 / 35208 / 84 0Fax: +49 / 35208 / 84 249
E-Mail: [email protected]://www.sebakmt.com
SebaKMT
All rights reserved. No part of this handbook may be copied by photographic or other means
unless SebaKMT have before-hand declared their consent in writing. The content of thishandbook is subject to change without notice. SebaKMT cannot be made liable for technical orprinting errors or shortcomings of this handbook. SebaKMT also disclaim all responsibilityfor damage resulting directly or indirectly from the delivery, supply, or use of this matter.
-
8/4/2019 MAN OWTS-Capacitor Eng x2
3/19
3
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Terms of Warranty
SebaKMT accept responsibility for a claim under warranty brought forward bya customer for a product sold by SebaKMT under the terms stated below.
SebaKMT warrant that at the time of delivery SebaKMT products are free frommanufacturing or material defects which might considerably reduce their valueor usability. This warranty does not apply to faults in the software supplied.During the period of warranty, SebaKMT agree to repair faulty parts or replacethem with new parts or parts as new (with the same usability and life as newparts) according to their choice.
SebaKMT reject all further claims under warranty, in particular those fromconsequential damage. Each component and product replaced in accordancewith this warranty becomes the property of SebaKMT.
All warranty claims versus SebaKMT are hereby limited to a period of 12
months from the date of delivery. Each component supplied by SebaKMTwithin the context of warranty will also be covered by this warranty for theremaining period of time but for 90 days at least.
Each measure to remedy a claim under warranty shall exclusively be carriedout by SebaKMT or an authorized service station.
To register a claim under the provisions of this warranty, the customer has tocomplain about the defect, in case of an immediately detectable fault within 10days from the date of delivery.
This warranty does not apply to any fault or damage caused by exposing aproduct to conditions not in accordance with this specification, by storing,
transporting, or using it improperly, or having it serviced or installed by aworkshop not authorized by SebaKMT. All responsibility is disclaimed fordamage due to wear, will of God, or connection to foreign components.
For damage resulting from a violation of their duty to repair or re-supply items,SebaKMT can be made liable only in case of severe negligence or intention.Any liability for slight negligence is disclaimed.
-
8/4/2019 MAN OWTS-Capacitor Eng x2
4/19
4
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Table of Contents
1 Safety Advice 51.1 General Notes 51.2 General Cautions and Warnings 6
2 Technical Data 83 Scope of Delivery 94 Setting up 10
4.1 Purpose of the Instrument 105 Portable Instrument 11
5.1 Storage 115.2 Transportation 125.3 Installation 13
6 Connections and Operation 147 Disposal of Old Equipment 19
-
8/4/2019 MAN OWTS-Capacitor Eng x2
5/19
5
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
1 Safety Advice
1.1 General Notes
Safety precautions This manual contains basic advice for the installation and operation ofthe product. It is essential to make this manual accessible to theauthorised and skilled operator. He needs to read this manual closely.The manufacturer is not liable for damage to material or humans dueto non-observance of the instructions and safety advices provided bythis manual.
Setting up and operating the system may only be done by authorisedand skilled personnel. According to DIN VDE 0104 (EN 50191) andDIN VDE 0105 (EN 50110) as well as the accident prevention
regulation (Unfallverhtungsvorschrift UVV), skilled personnel isdefined as a person who is qualified to work, judge and realizedangers due to his professional education, knowledge and experienceand his knowledge of applicable regulations. Locally applyingregulations have to be observed.
Important instructions concerning the protection of staff and equipmentas well as technical safety within this document are labelled with oneof the following symbols:
Symbol Description
Indicates a potentially hazardous situation which, ifnot avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, ifnot avoided, may result in minor or moderate injuryor material damage.
Symbols used in thismanual
Notes have important information and useful tips onthe operation of your equipment. Non-observancemay result in useless measure-ment results.
Working with
equipment ofSeba KMT
All electrical regulations of the country where the system is operated
have to be observed as well as national regulations for prevention ofaccidents and existing regulations for the safety and operation ofequipment of the involved companies.
After working with the equipment, make sure to de-energise, protectagainst re-energising, discharge, ground and short-circuit theinstrument and installations that have been worked on.
Original accessories ensure safe operation of the equipment. It is notallowed and the warranty is lost if other accessories than the originalones are used with the equipment.
Operating personal Only trained and/or instructed staff is permitted to deal with thissystem and its peripherals. Keep any other person away from it.
Only authorised persons with sufficient expertise are allowed tooperate the device.
WARNING
CAUTION
-
8/4/2019 MAN OWTS-Capacitor Eng x2
6/19
6
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Repair andmaintenance
Repairs and service must only be done by SebaKMT or authorisedservice departments of SebaKMT. SebaKMT recommends having theequipment serviced and checked once per year at a SebaKMT service
location.
SebaKMT also offers direct on-site support. Please contact our serviceoffice for more information.
1.2 General Cautions and Warnings
Intended application Safe operation is only realised when using the equipment for itsintended purpose. Using the equipment for other purposes may leadto human danger and damage of equipment of involved installations.
The limits described under technical data may not be exceeded.
Operating products of SebaKMT in condensing environment may leadto flash-over, danger and damage. The instruments should only beoperated under tempered conditions. It is not allowed to operateSebaKMT products at direct contact with humidity, water or nearaggressive chemicals nor explosive gases and fumes.
Behaviour atmalfunction of normal
operation
The equipment may only be used when working properly. Whenirregularities or malfunctions appear that cannot be solved consultingthis manual, the equipment must immediately be put out of operationand marked as not functional. In this case inform the person in chargewho should inform the SebaKMT service to resolve the problem. Theinstrument may only be operated when the malfunction is resolved.
Operation in traffic
environment
To ensure safety for operators and traffic, the country-specific
regulations must be observed.
Fife safety rules
The five safety rules must always be followed when working with HV(High Voltage):
1. De-energise
2. Protect against re-energising
3. Confirm absence of voltage
4. Ground and short-circuit
5. Cover up or bar-off neighbouring energised parts
Using cardiac pacemaker
Physical processes during operation of high voltage may endangerpersons wearing a cardiac pacemaker when near these high voltagefacilities.
-
8/4/2019 MAN OWTS-Capacitor Eng x2
7/19
7
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Fire fighting in electrical installations
Recommended extinguishing agent: carbon dioxide (CO2)
Carbon dioxide is electrically non conductive and does notleave residue. It is safe to use in energized facilities as longas the minimum distances are observed.
It is essential to observe the safety instruction on theextinguishing agent.
Applicable is DIN VDE 0132.
Dangers when operating with HV
Special attention and safety-conscious behaviour is needed whenoperating HV facilities and especially non-stationary equipment. The
regulations VDE 0104 about setting up and operation of electric testequipment, i.e. the corresponding EN 50191 as well as country-specific regulations and standards must be observed.
Safety installations may not be by-passed nor deactivated.
Operation requires minimum two people whereas the secondperson must be able to activate the emergency stop in case ofdanger.
To avoid hazardous electric charges of metallic parts in thevicinity, all metallic parts must be grounded.
To avoid drawing dangerous arcs, switching should only bedone in de-energized condition.
HV test equipment and burn-down equipment is short-circuitproof. Hazardous voltage may be present if a short circuit isopened during operation. If measuring short-circuit current isnecessary, it is advisable to connect an arrester in parallelwith the measuring instrument (e.g. 90 V glow arrester).
Adequate safety precautions must be met when usingtransient measuring techniques, using HV test instruments orsurge generators.
The equipment and all accessories must be connectedaccording to applicable standards VDE, EN or DIN as well ascountry-specific regulations.
Never place the test van on the route of the cable under testto avoid the danger of voltage cone at the location of the fault.
Always connect all metal parts in the vicinity of a HVinstallation to earth in order to avoid dangerous charging.Particularly great attention should be paid to non-stationary(mobile) operation.
WARNING
-
8/4/2019 MAN OWTS-Capacitor Eng x2
8/19
8
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
2 Technical Data
Pos. Item Value
Part No. 89 900 7054
Height 700 mm
Width 810 mm
Depth 392 mm
Weight 85 kg
IP-Protection according to EN 60529 IP 00
Protection class according to DIN VDE 014 Part 1 I
Capacity 1 F (2x 0,5 F)
Blocking inductance 32 H/ 270 Ohm
Voltage DC 36 kV/ 25 kV rms
-
8/4/2019 MAN OWTS-Capacitor Eng x2
9/19
9
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
3 Scope of Delivery
Additional Capacity for OWTS, van-mounted or portable.
Portable version additionally supplied with
Aluminium handcart
Holding belt
Packaging
Fig. 1: Scope of delivery of portable version
1x1x
-
8/4/2019 MAN OWTS-Capacitor Eng x2
10/19
10
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
4 Setting up
4.1 Purpose of the Instrument
The Additional Capacitor for OWTS is an optional accessory for the OWTSPartial Discharge diagnostic instrument which detects, evaluates and locatesPartial Discharge sources in the insulation, joints and terminations of mediumvoltage cables.
This Additional Capacitor is applied when doing an OWTS measurement ontest objects with very little capacity (short medium voltage cables, switchinggear). It consists of two capacitors in parallel and a blocking inductivity. The
additional capacity will reduce the oscillation frequency during ameasurement.
.
-
8/4/2019 MAN OWTS-Capacitor Eng x2
11/19
11
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
5 Portable Instrument
5.1 Storage
Fig. 2: Storage
IP 20
CAUTION
-
8/4/2019 MAN OWTS-Capacitor Eng x2
12/19
12
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
5.2 Transportation
IP 20
Fig. 3: Transportation on handcart
Fig. 4: Carrying Additional Capacitor
Fig. 5: Transportation protection
1x
1. 2.
2x
Make sure to take off the transportationprotection of the mounting of the blockinginductivity.
CAUTION
-
8/4/2019 MAN OWTS-Capacitor Eng x2
13/19
13
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
5.3 Installation
The following pictures show the preparation of the Additional Capacitor for
connection to the OWTS measuring system.
Fig. 6: Take screws off
Fig. 7: Take protective cover off
Fig. 8: Placing the Additional Capacitor
Note:: The protective cover is apure transportation protection andmust be kept out of the way during ameasurement.
4x
-
8/4/2019 MAN OWTS-Capacitor Eng x2
14/19
14
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
6 Connections and Operation
Following figures show the connections in general and in detail.
Fig. 9: Connections
blocking inductivity
ca acitors
Test Object OWTS Choke Additional Capacitor
-
8/4/2019 MAN OWTS-Capacitor Eng x2
15/19
15
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Fig. 10: Equal potential bonding
Fig. 11: Mounting of blocking inductivity
1
2a
2b
-
8/4/2019 MAN OWTS-Capacitor Eng x2
16/19
16
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Fig. 12: Complete Additional Capacitor
Fig. 13: Connection to OWTS
-
8/4/2019 MAN OWTS-Capacitor Eng x2
17/19
17
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
Fife safety rules
The five safety rules must always be followed when working with HV (HighVoltage):
1. De-energise
2. Protect against re-energising
3. Confirm absence of voltage
4. Ground and short-circuit
5. Cover up or bar-off neighbouring energised parts
Fig. 14: 5 Safety Rules
Fig. 15: Maintain safety clearance
Fig. 16: Ground and discharge OWTS choke
0,5 m0,5 m
WARNING
-
8/4/2019 MAN OWTS-Capacitor Eng x2
18/19
18
MAN_OWTS-capacitor_eng_x2.doc
Additional Capacitor OWTS
The operation of the OWTS diagnostic system is described in thecorresponding manual. After an OWTS measurement, the capacitors of theAdditional Capacitor have to be discharged with a discharge rod and then
grounded. Now the Additional Capacitor can be unassembled and preparedfor transportation or storage.
Note: The discharge rod is not part of the scope of delivery, neither for theOWTS nor for the Additional Capacitor.
-
8/4/2019 MAN OWTS-Capacitor Eng x2
19/19
19Additional Capacitor OWTS
7 Disposal of Old Equipment
If the SebaKMT products reach the end of the life span, they should be short-circuited and environmentally friendly disposed or recycled.
We are pleased to help you finding the environmentally friendly way. Pleasecontact [email protected].