manual, control/signal module, ethernet/ip, dkd document ... · the dkd modules provide a 4‑pin...

35
Manual, Control/Signal Module, Ethernet/IP, DKD Document #9620-20-C-DKD-12 Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-1 Table of Contents C. Control and Signal Modules ...................................................................................................C-4 DKD—Ethernet/IP Modules..........................................................................................................C-4 1. Product Overview ..................................................................................................................C-4 1.1 DKD Master ................................................................................................................................ C-4 1.2 DKD Tool .................................................................................................................................... C-4 2. Product Information ..............................................................................................................C-6 2.1 Master Module Node ................................................................................................................. C-6 2.1.1 Class 1 Connection Information ..................................................................................... C-6 2.1.2 IP Address ...................................................................................................................... C-6 2.1.3 Module and Network Status LED’s ................................................................................. C-7 2.2 Arc Prevention Circuit .............................................................................................................. C-9 2.2.1 Arc Prevention Circuit Behavior during Coupling ........................................................... C-9 2.2.2 Arc Prevention Circuit Behavior during Uncoupling ..................................................... C-10 2.2.3 Tool Side TSI .................................................................................................................C-11 2.3 Tool Module ............................................................................................................................. C-13 2.3.1 Tool-ID Switches........................................................................................................... C-13 2.4 Software ................................................................................................................................... C-14 3. Installation ...........................................................................................................................C-16 3.1 Master Module Installation ..................................................................................................... C-16 3.2 Master Module Removal ......................................................................................................... C-17 3.3 Tool Module Installation ......................................................................................................... C-18 3.4 Tool Module Removal ............................................................................................................. C-18 3.5 Setting the Master DIP Switches............................................................................................ C-19 3.6 Setting the Tool-ID................................................................................................................... C-20 3.7 Utility Schematic ..................................................................................................................... C-20 4. Operation .............................................................................................................................C-21 4.1 Lock, Unlock, and RTL Sensor Cable LED Behavior ........................................................... C-21 4.2 Diagnostic Functions and Error Handling ............................................................................ C-22 4.2.1 DeviceNet Power Status .............................................................................................. C-22 4.2.2 Valve Power Status ...................................................................................................... C-22 4.2.3 Error on Latch or Unlatch Output ................................................................................. C-22 4.2.4 “COMM OK” bit ............................................................................................................. C-22 4.2.5 “Tool Power is On” bit ................................................................................................... C-22 4.2.6 “Unlatch Enabled” bit .................................................................................................... C-22 4.3 Recommended Sequence of Operations .............................................................................. C-23

Upload: others

Post on 06-Apr-2020

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-1

Table of ContentsC. Control and Signal Modules ...................................................................................................C-4DKD—Ethernet/IP Modules ..........................................................................................................C-41. Product Overview ..................................................................................................................C-4

1.1 DKD Master ................................................................................................................................ C-4

1.2 DKD Tool .................................................................................................................................... C-4

2. Product Information ..............................................................................................................C-62.1 Master Module Node ................................................................................................................. C-6

2.1.1 Class 1 Connection Information ..................................................................................... C-6

2.1.2 IP Address ...................................................................................................................... C-6

2.1.3 Module and Network Status LED’s ................................................................................. C-7

2.2 Arc Prevention Circuit .............................................................................................................. C-92.2.1 Arc Prevention Circuit Behavior during Coupling ........................................................... C-9

2.2.2 Arc Prevention Circuit Behavior during Uncoupling ..................................................... C-10

2.2.3 Tool Side TSI .................................................................................................................C-11

2.3 Tool Module ............................................................................................................................. C-132.3.1 Tool-ID Switches ........................................................................................................... C-13

2.4 Software ................................................................................................................................... C-14

3. Installation ...........................................................................................................................C-163.1 Master Module Installation ..................................................................................................... C-16

3.2 Master Module Removal ......................................................................................................... C-17

3.3 Tool Module Installation ......................................................................................................... C-18

3.4 Tool Module Removal ............................................................................................................. C-18

3.5 Setting the Master DIP Switches ............................................................................................ C-19

3.6 Setting the Tool-ID ................................................................................................................... C-20

3.7 Utility Schematic ..................................................................................................................... C-20

4. Operation .............................................................................................................................C-214.1 Lock, Unlock, and RTL Sensor Cable LED Behavior ........................................................... C-21

4.2 Diagnostic Functions and Error Handling ............................................................................ C-224.2.1 DeviceNet Power Status .............................................................................................. C-22

4.2.2 Valve Power Status ...................................................................................................... C-22

4.2.3 Error on Latch or Unlatch Output ................................................................................. C-22

4.2.4 “COMM OK” bit ............................................................................................................. C-22

4.2.5 “Tool Power is On” bit ................................................................................................... C-22

4.2.6 “Unlatch Enabled” bit .................................................................................................... C-22

4.3 Recommended Sequence of Operations .............................................................................. C-23

Page 2: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-2

5. Maintenance .........................................................................................................................C-255.1 Pin Block Inspection and Cleaning ....................................................................................... C-26

6. Troubleshooting and Service Procedures ........................................................................C-276.1 Troubleshooting ...................................................................................................................... C-27

6.2 Service Procedures ................................................................................................................. C-296.2.1 V-ring Seal Replacement .............................................................................................. C-29

7. Serviceable Parts ................................................................................................................C-308. Specifications ......................................................................................................................C-319. Drawings ..............................................................................................................................C-33

Page 3: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-3

Glossary of Terms

Term Definition

Auxiliary Power Power Supply interface provided that supports Switched and Un-switched circuits.

Clear Errors An output supplied to the ATI Master Ethernet node to clear all error conditions

Comm. Error An input indicating the status of the Tool-ID communication between Master and Tool modules.

EOAT End-Of-Arm-Tool (end effector).

Error on Latch Output An input indicating a short circuit overload condition exists with the Latch output.

Error on Unlatch Output An input indicating a short circuit overload condition exists with the Unlatch output.

Latch The output supplied to the ATI Master Ethernet node to couple the Tool Changer.

Locked A proximity sensor input indicating that the coupling mechanism is in the Locked position.

Input and Logic Power Good An input indicating the presence of Input Power (sourced from the Un-switched Power Supply) at the ATI Master.

RTL A proximity sensor input that senses when the ATI Tool is in close proximity.

Switched auxiliary power One circuit of the auxiliary power Supply that is tied into the E-stop circuit and will be switched off when the circuit is broken.

Tool-ID An input from the Master node reporting the values from the Tool-ID switches on the Tool module.

Tool Present A hard-wire input (sourced from the Tool) indicating the Master and Tool should be communicating with each other.

Unlatch The output supplied to the ATI Master Ethernet node to uncouple the Tool Changer.

Unlocked A proximity sensor input indicating that the coupling mechanism is in the Unlocked position.

Un-switched auxiliary power One circuit of the auxiliary power Supply that is continuous and is not broken during E-stop conditions.

Valve Power Available An input indicating the presence of Valve Power at the ATI Master.Unlatch The output supplied to the ATI Master node to uncouple the Tool Changer.

Unlocked A proximity sensor input indicating that the coupling mechanism is in the Unlocked position.

Un-switched auxiliary power One circuit of the auxiliary power Supply that is continuous and is not broken during E-stop conditions.

Valve Power Available An input indicating the presence of Valve Power at the ATI Master.

Page 4: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-4

C. Control and Signal Modules

DKD—Ethernet/IP Modules1. Product Overview

The DKD module enables the user to control and communicate with ATI’s Heavy Automation Robotic Tool Changers using EtherNet/IP while passing DeviceNet network and power to the Tool side. This allows utilizing EtherNet/IP on the robot up to the Tool Changer and establishing short connection times to the Tool side equipment by using DeviceNet Quick Connect equipment on the Tool.

Control of the Tool Changer is realized through the Master Node along with the reporting of Tool Changer I/O, such as Lock, Unlock, and Ready‑to‑Lock signals. The Tool‑side module supports Tool‑ID reported through the Master‑side and functions as a pass through for DeviceNet network and power to downstream equipment.

A single or double solenoid valve is provided with the Master valve adapter for Lock/Unlock control of the Tool Changer. The user is required to provide a pneumatic supply source to the Tool Changer.

When the modules are coupled, the V‑ring seal forms a water resistant but not waterproof seal around the pin block. Compliant spring pins are provided on the Master and fixed contact pins on the Tool. To avoid unintentional human contact, the Master spring pins are recessed below an insulated surface on both the power and signal circuits (See Figure 1.1).

General fault reporting is supported for the presence of power for Logic/Inputs and the Tool Changer valve. Advanced diagnostic and fault reporting is supported for output short circuit and overload conditions as well as for the presence of Tool‑ID. Refer to Section 2—Product Information and Section 4—Operation for more information on these attributes.

The DKD module incorporates ATI’s exclusive Arc Prevention Circuit which extends the life of all electrical power contacts.

1.1 DKD MasterThe Master module is designed with Tool Changer input signals (Locked, Unlocked, and Ready‑to‑Lock proximity sensors). Refer to Section 2—Product Information and Section 4—Operation for more information on these attributes.A standard 5‑pin Mini connector is provided on the Master module for DeviceNet communications interface to the Master and downstream nodes. A M12 4 pin D‑Coded connectors are provided on the Master module for EtherNet/IP communications interface with the Master. A M12 4 pin connector is provided to the customer for interfacing with auxiliary power. Refer to Section 9—Drawings for additional information.

1.2 DKD ToolA standard 5‑pin Mini connector is provided on the Tool module for DeviceNet communications interface to the Tool and downstream nodes. A M12 4 pin connector is provided to the customer for interfacing with auxiliary power. A M12 4‑pin connector is provided for interfacing with the TSI safety switch. The Tool module employs a series of push‑button switches for setting of the Tool‑ID input. This allows the customer to distinguish between the different Tools used in a robotic cell or on a production line. The Tool‑ID is reported through the Master module bitmap. Refer to Section 2.4—Software for bitmap and detailed I/O information.

Page 5: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-5

Figure 1.1—Modules

19-Pin Contacts

19-Pin Spring Contactsand Rubber V-ring Seal

DeviceNet Connector5-Pin Mini Female

DeviceNet Connector4-Pin Mini Male

TSI Connector4-Pin M12 Female

(4) Sensor ConnectorRTL, Lock, and Unlock3-Pin M8 Female

Auxilary Power Connector4-Pin Mini Male

Ethernet Connection4-Pin M12 Female

Auxilary Power Connector4-Pin Mini Female

0-9 Tool ID

Module Status LED (MS),Network Status LED (NS),

and DIP Switches

Valve Signal Pin Block(not visible)

9121-DKD-M

9121-DKD-T

Common Ledge Mounting FeatureCommon Ledge Mounting Feature

Page 6: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-6

2. Product InformationAn EtherNet/IP node is established on the Master module but not on the Tool module. Control of the Tool Changer is realized through the Master node along with the reporting of various Tool Changer I/O. The Tool module supports Tool‑ID reported through the Master and functions as a pass through for DeviceNet and auxiliary power signals to downstream equipment.

The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an M12 D‑Coded 4‑pin connector for EtherNet/IP communications. Please refer to Section 9—Drawings for specific module wiring and connector interface information.

Prior to using the Tool Changer and the EtherNet/IP modules, various hardware settings must be configured. Communicating with the EtherNet/IP modules requires knowledge of EtherNet/IP standards and operation.

2.1 Master Module NodeThe module operates as a Server on the EtherNet/IP network. It supports Class 3 Connected Explicit Messaging, UCMM Explicit Messaging, and Class 1 Connected Cyclic I/O Messaging. The Master Node does not support any Client functionality.

2.1.1 Class 1 Connection InformationTable 2.1 lists the Class 1 Connection Information for the Master module.

Table 2.1—Class 1 Connection InformationInstance Size in Bytes

Configuration 128 0Input 7 8Output 37 8

2.1.2 IP AddressThe IP address is factory set to a default value of 192.168.1.1. A new IP address can be configured through the integrated web server using the following procedure:

1. Click on the upper “Edit” button,2. Change the IP address and click on the “Apply” button,3. Cycle power to make the change effective.

Figure 2.1—Changing IP Address

Page 7: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-7

2.1.3 Module and Network Status LED’sThe module status LED is identified on the module as “MS”. It provides device status for power and operation. Refer to Figure 2.2 for location of LED’s. Refer to Table 2.2 for an outline of this LED’s operation. The network status LED is identified on the module as “NS”. It provides network status for power and communication. Refer to Table 2.3 for an outline of this LED’s operation.

Table 2.2—Master module Status LEDColor State IndicationNone OFF No Power

Red Solid Unrecoverable FaultFlashing Recoverable Fault

GreenSolid Normal Runtime Operation

Flashing No Tool module attached. Tool-ID in bitmap not available. Configuration missing, incomplete or incorrect.

Green-Red Flashing Device is performing a self-test.

Table 2.3—Master Network Status LEDColor State IndicationNone OFF No Power/ Off Line/No IP Address

Red Solid Device has detected that its IP address is already in use.Flashing One or more I/Os are timed out.

GreenSolid Device is on line with connections established.

Device is allocated to a Master.

Flashing Device is on line but connection is not established. Device not allocated to a Master.

Green-Red Flashing Device is performing a self-test.

Page 8: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-8

Figure 2.2—Master Module DIP Switches and LED’s

Turn ON to set IP Address to Default

(Default Setting of 0)Add switch values

SHO

WN

IN F

AC

TOR

Y D

EFA

ULT

SET

TIN

G

1 ON

62

34

57

89

OFF: Reserved

OFF

10

M

N (NS) Network Status LED

(MS) Module Status LED

87 640

12801

62

34

5

Set Last Octet

of IPAddress

ON

Val

ueO

FF V

alue

1020

4080

160320

(SW 1) 0(SW 2) +0(SW 3) +0(SW 4) +0(SW 5) +0(SW 6) +0(SW 7) +0(SW 8) +0Total =0

Network Status LED

Module Status LED

Master ModuleDIP Switches

Shown with Window Removed

Page 9: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-9

2.2 Arc Prevention CircuitThe DKD module incorporates ATI’s exclusive Arc Prevention Circuit. The Arc Prevention Circuit extends the life of all electrical power contacts by eliminating arcing caused by inductive loads and high inrush current during coupling/uncoupling. The Arc Prevention Circuit makes it possible to couple/uncouple without switching power off and prevents damage to the contacts.In the DKD module, the Arc Prevention Circuit controls the ON/OFF status of the following three power signals:1. DeviceNet Power (CAN V+)2. Switched auxiliary power V+3. Unswitched auxiliary power V+The behavior of the Arc Prevention circuit is more fully described in the following sections.

2.2.1 Arc Prevention Circuit Behavior during CouplingThe behavior of the Arc Prevention circuit during coupling can be more clearly understood by referring to Figure 2.3, which shows the power on timing diagram for the Arc Prevention Circuit. Starting at the top of the diagram, the LATCH command is issued thus initiating locking of the Master and Tool.Soon after locking is initiated, electrical contact between Master and Tool pin contacts occurs (this time is designated t1 in the diagram). The magnitude of time t1 is a function of many factors including the weight of the EOAT, the distance between the Master and Tool when the LATCH command is issued, how well the Master and Tool are aligned during pick up, etc.As soon as electrical contact is made and the LATCH command is issued, the Arc Prevention Circuit will turn on Input and Output Power. The time delay between when the electrical contacts become fully engaged to when power is actually available to the EOAT (time t2 in the diagram) is less than 100 ms.Important: The Arc Prevention Circuit will only allow power to pass to the Tool after the LATCH command has been issued and the Master and Tool module’s electrical contacts are fully engaged.

Figure 2.3—Power On Timing

(diToolPresent)

(doLatchTool)

Page 10: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-10

2.2.2 Arc Prevention Circuit Behavior during UncouplingThe behavior of the Arc Prevention Circuit during uncoupling can be more clearly understood by referring to Figure 2.4, which shows the power off timing diagram for the Arc Prevention Circuit. Starting at the top of the diagram, the UNLATCH command is issued thus initiating uncoupling of the Master and Tool.Immediately after the UNLATCH command is issued, the Arc Prevention Circuit will turn off Input and Output Power. The power off time delay between the UNLATCH command and the switching off of power (designated t3 in the diagram) is less than 50 ms.Some time after power is turned off and the Master and Tool begin to separate, electrical contact between Master and Tool pin contacts will be lost. This occurs with a delay, designated t4 in the diagram, after the UNLATCH command is issued. The magnitude of time t4 is a function of many factors, including the weight of the EOAT, the friction between Master and Tool alignment pins, etc. but is usually not shorter than 100 ms.

Figure 2.4—Power Off Timing

(doUnlatchTool)

(diToolPresent)

Page 11: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-11

2.2.3 Tool Side TSIThe tool stand Interlock (TSI) circuit is provided to ONLY allow Tool release while in the stand or storage location as indicated by actuation of a customer‑integrated switch. It is suggested that the customer integrate a single throw, double pole (Normally Open, spring return) limit switch to work with this feature (reference Figure 2.5). The limit switch should be mounted to the end effector in such a way that the switch is “made” only when the Tool is in the stand or storage location. An interface to the TSI circuit is made available to the customer via a 4‑pin M12 connector on the master module. An off the shelf cord set can be utilized to connect this interface to the limit switch assembly. The 4‑pin connection is factory supplied with a teach plug to override the TSI circuit during setup and integration. Reference the drawings in Section 9—Drawings for additional details.

Figure 2.5—TSI Safety Switch

Tool Changer Master Side

TSI Limit Switch

Robot Arm

Control/Signal Module Master side

Control/Signal Module Tool Side

4-Pin M12 Connectorfor TSI Limit Switch

Tool Changer Tool SideTool Stand

Trip Dog Integalto the Tool Stand

TSI Switch Cable

Page 12: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-12

2.2.3.1 TSI OverviewThe DKD module relies on the status of the Ready‑to‑Lock (RTL) sensors and the TSIV input to determine when it is appropriate to unlatch the Tool. The RTL sensors indicate if the Master and Tool are coupled while the TSIV input indicates when the TSI mechanical switch on the Tool is actuated, thereby indicating that the Tool is in the stand.

For example, if the DKD module receives an UNLATCH command and the RTL sensor signals indicate that Master and Tool are coupled but the TSIV indicates that the Tool is not in the tool stand then the UNLATCH command is ignored. The logic employed to determine when to enable the UNLATCH command is detailed in Table 2.4.

Table 2.4—UNLATCH Enable Logic and Truth TableRTL1

& RTL2

TSIV UNLATCH Enabled Status of Master Body

0 0 1 No Tool, positioned in free air

0 1 1No Tool, positioned in tool stand (this is a transient state which is only true just prior to RTL being made)

1 0 0 Tool is present, positioned in free air1 1 1 Tool is present, positioned in tool stand

When UNLATCH is enabled it will be reported in the bitmap in the form of the “Unlatch Enabled” bit (refer to Section 2.4—Software).

As an additional safety measure, a “hard‑wired” interrupt of the UNLATCH signal is provided when the RTL sensors indicate that Master and Tool are coupled and the Tool is not in the tool stand.

The following TSI status signals are also reported in the bitmap (refer to Section 2.4—Software):

RTLV (Ready To Lock Verify): Ready To Lock Verify status of RTL bypass relay in the Master module.

TSIV (TSI Limit Switch Verify): Status of 2nd contact of the limit switch that is located on the Tool.

TSRV (TSI Relay Verify): Status of the TSI Relay in the Tool module.

The Sequence of Operations in Appendix A of this manual describes in detail the behavior of the RTLV, TSIV, and TSRV bits during the operation of the Tool Changer.

Page 13: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-13

2.3 Tool ModuleAn Ethernet node is not established on the Tool module. The Tool module utilizes a patented, rapid communication method to report the Tool‑ID information from the push‑button switches to the Master module as soon as the Tool Changer is coupled. Typically the Tool‑ID information is available to the Master within 250 ms from the time the changer is coupled. Diagnostic capability is provided for Tool‑ID via the Comm. Error input supported in the Master bitmap. If the Tool Present input is high, then a valid Tool‑ID should follow and if it does not then the Comm. Error is made high.In addition to providing Tool‑ID the Tool module also functions as a pass through for DeviceNet and auxiliary power signals to downstream equipment, reference drawings in Section 9.

2.3.1 Tool-ID SwitchesA push‑button switch is provided on the Tool module for setting of a Tool‑ID number. Figure 2.6 shows the location of the Tool‑ID push‑button switches. After adjustment is completed, ensure that the seal and window are re‑positioned correctly to prevent a leakage path to inside the module

Figure 2.6—Tool-ID Switch Settings

Tool-ID

(4) M3 CaptiveHead Screw

Window

Page 14: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-14

2.4 SoftwareA working EDS file for the Master node is available from our website: (www.ati‑ia.com/download/edsfiles) or by e‑mail, reference the following part number.DKD‑M Node EDS file 9030‑20‑1016An I/O bitmap for the Master node is provided in the Table 2.5 and Table 2.6.

Table 2.5—Robot Input From ATI MasterByte Bit# Name Description/Function

1

0 Locked Tool Changer Locked Proximity Sensor Input1 Unlocked Tool Changer Unlocked Proximity Sensor Input

2 Input and Logic Power Good Input and Logic Power Present Input

3 Valve Power Available Valve Power Present Input4 RTL1 Ready-to-Lock 1 Proximity Sensor Input5 RTL2 Ready-to-Lock 2 Proximity Sensor Input6 RTLV Ready-to-Lock Verify Input 7 - (Reserved)

2

0 Tool-ID 1 Tool-ID1 Tool-ID 2 Tool-ID2 Tool-ID 4 Tool-ID3 Tool-ID 8 Tool-ID4 TSIV TSI Limit Switch Verify5 TSRV TSI Relay Verify6 Unlatch Enabled Unlatched Enabled Status Information7 Tool Present Hard-Connect Tool Present Input

3

0 - (Reserved)1 - (Reserved)2 Error on Latch Output Latch output overloaded 3 Error on Unlatch Output Unlatch output overloaded 4 - (Reserved)5 - (Reserved)6 - (Reserved)7 - (Reserved)

4

0 - (Reserved)1 - (Reserved)2 - (Reserved)3 - (Reserved)4 - (Reserved)5 - (Reserved)6 COMM OK Indicates EtherNet/IP Connectivity is Established

7 Tool Power Is ON Indicates that Arc Prevention Circuit is turned ON and power is provided to the Tool

Page 15: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-15

Table 2.5—Robot Input From ATI MasterByte Bit# Name Description/Function

5

0 - (Reserved)1 - (Reserved)2 - (Reserved)3 - (Reserved)4 - (Reserved)5 - (Reserved)6 - (Reserved)7 - (Reserved)

6

0 - (Reserved)1 - (Reserved)2 - (Reserved)3 - (Reserved)4 - (Reserved)5 - (Reserved)6 - (Reserved)7 - (Reserved)

7

0 - (Reserved)1 - (Reserved)2 - (Reserved)3 - (Reserved)4 - (Reserved)5 - (Reserved)6 - (Reserved)7 - (Reserved)

8

0 - (Reserved)1 - (Reserved)2 - (Reserved)3 - (Reserved)4 - (Reserved)5 - (Reserved)6 - (Reserved)7 - (Reserved)

Table 2.6—Robot Outputs to ATI MasterByte Bit# Name Description/Function

1

0 Latch (Lock) Latch Solenoid Valve Output1 Unlatch (Unlock) Unlatch Solenoid Valve Output2 - (Reserved)3 Clear Errors Reset errors, allow affected I/O to be reactivated4 - (Reserved)5 - (Reserved)6 - (Reserved)7 - (Reserved)

2 - 8 - - (Reserved)

Page 16: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-16

3. InstallationThe control/signal modules are typically installed by ATI prior to shipment. The following steps outline the installation or removal. For wiring information refer to Section 9—Drawings.

WARNING: Do not perform maintenance or repair on Tool Changer or modules unless the Tool is safely supported or placed in the tool stand, all energized circuits (e.g. electrical, air, water, etc.) are turned off, pressurized connections purged and power discharged from circuits in accordance with the customer’s safety practices and policies. Injury or equipment damage can occur with Tool not placed and energized circuits on. Place the Tool safely in the tool stand, turn off and discharge all energized circuits, purge all pressurized connections, verify all energized circuits are de‑energized before performing maintenance or repair on Tool Changer or modules.

3.1 Master Module InstallationTools required: 5 mm Allen wrench (hex key), torque wrench

Supplies required: clean rag, Loctite® 242

1. Place the Tool in a secure location.2. Uncouple the Master and Tool plates.3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).4. Clean the mounting surfaces.5. Using the ledge feature, place the module on the valve adapter. Align the module with the valve adapter

using the dowels in the bottom of the ledge feature.6. Apply Loctite 242 to the supplied M6 socket head cap screws. Install the (2) M6 socket head cap screws

securing the module to the valve adapter and tighten to 70 in‑lbs (7.9 Nm) using a 5 mm Allen wrench.7. Set the DIP switches. Refer to Section 3.5—Setting the Master DIP Switches.8. Connect the (L) Lock, (U) Unlock, and (R1 and R2) RTL sensor cable connectors to the module.9. Customer interface, auxiliary power and Ethernet cables to the module. Ensure that the connectors are

cleaned prior to being secured.10. After the procedure is complete, resume normal operation.

Figure 3.1—Master Module Installation and Removal

Tool Changer

Valve Adapter

RTL, Lock, and UnlockSensor Connectors

DKD-M

(2) M6 Socket Head Cap Screw

L ConnectorU Connector

R2 Connector

R1 Connector

Ethernet Connector

DeviceNet Connector

Auxiliary Power Connector

Use Ledge Mounting Featureto Properly Align Module

Page 17: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-17

3.2 Master Module RemovalRefer to Figure 3.1

Tools required: 5 mm Allen wrench (hex key)

1. Place the Tool in a secure location.2. Uncouple the Master and Tool plates.3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).4. Disconnect the (L) Lock, (U) Unlock, and (R1 and R2) RTL sensor cable connectors from the module.5. Disconnect the auxiliary power and Ethernet cables from the module.6. Support the module and remove the (2) M6 socket head cap screws using a 5 mm Allen wrench. Lower

the module until it clears the guide pin.

Page 18: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-18

3.3 Tool Module InstallationTools required: 5 mm Allen wrench (hex key), torque wrenchSupplies required: clean rag, Loctite 242

1. Place the Tool in a secure location.2. Uncouple the Master and Tool plates.3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).4. Clean the mounting surfaces.5. Using the ledge feature, place the module on the valve adapter spacer. Align the module with the valve

adapter spacer using the dowels in the bottom of the ledge feature.6. Apply Loctite 242 to the supplied M6 socket head cap screws. Install the (2) M6 socket head cap screws

securing the module to the valve adapter spacer and tighten to 70 in‑lbs (7.9 Nm) using a 5 mm Allen wrench.

7. Connect the power cable and Ethernet/DeviceNet cable connectors to the module.8. Set the Tool‑ID. Refer to Section 3.6—Setting the Tool‑ID.9. After the procedure is complete, resume normal operation.

Figure 3.2—Tool Module Installation and Removal

Tool Changer

Tool Adapter Assembly

Use Ledge Mounting Featureto Properly Align Module

(2) M6 Socket Head Cap Screw

9121-DKD-T

Tool-ID

Auxiliary Power Connection

DeviceNet Connection

3.4 Tool Module RemovalTools required: 5 mm Allen wrench (hex key)

1. Place the Tool in a secure location.2. Uncouple the Master and Tool plates.3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).4. Disconnect the auxiliary power and Ethernet cables from the module.5. Support the module and remove the (2) M6 socket head cap screws using a 5 mm Allen wrench. Lift up

on the module until it clears the guide pin.

Page 19: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-19

3.5 Setting the Master DIP SwitchesTools required: Phillips screwdriver

1. Using a Phillips screwdriver, loosen the (2) M3 pan head captive screws and remove the window.2. Set the DIP switches as needed, refer to Figure 3.3 for details.

NOTICE: When replacing the window, ensure that the seal is positioned correctly to prevent fluid leakage into the module and damaging the electronics.

3. Re‑install the window and tighten the (2) M3 pan head captive screws.

Figure 3.3—Master module DIP Switches and LED’s

Turn ON to set IP Address to Default

(Default Setting of 0)Add switch values

SHO

WN

IN F

AC

TOR

Y D

EFA

ULT

SET

TIN

G

1 ON

62

34

57

89

OFF: Reserved

OFF

10

M

N (NS) Network Status LED

(MS) Module Status LED

87 640

12801

62

34

5

Set Last Octet

of IPAddress

ON

Val

ueO

FF V

alue

1020

4080

160320

(SW 1) 0(SW 2) +0(SW 3) +0(SW 4) +0(SW 5) +0(SW 6) +0(SW 7) +0(SW 8) +0Total =0

Network Status LED

Module Status LED

Master ModuleDIP Switches

Shown with Window Removed

Page 20: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-20

3.6 Setting the Tool-IDTools required: Phillips screwdriverA push button switch is provided on the Tool module for setting of a Tool‑ID number. Each Tool must have a unique single digit Tool‑ID number.

1. Using a Phillips screwdriver, loosen the (4) M3 pan head captive screws and remove the Tool‑ID window.

2. Use a non‑conductive tool (e.g., plastic stylus) to press on the Tool‑ID push buttons to increase (+) or decrease (‑) the digit values.

NOTICE: When replacing the window, ensure that the seal is re‑positioned correctly to prevent fluid ingress.

3. Re‑install the Tool‑ID window and tighten the M3 pan head captive screws.

Figure 3.4—Tool-ID Switch Settings

Tool-ID

(4) M3 CaptiveHead Screw

Window

3.7 Utility SchematicRefer to Section 9—Drawings of this manual for customer interface and wiring details for the modules.

WARNING: All pneumatic fittings and tubing must be capable of withstanding the repetitive motions of the application without failing. The routing of electrical and pneumatic lines must minimize the possibility of over stressing, pullout, or kinking the lines. Failure to do so can cause some critical electrical and/or pneumatic lines not to function properly and may result in injury to personnel or damage to equipment. Follow the robot manufacturer’s guidelines and carefully route hoses and cables to avoid damage.

Page 21: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-21

4. OperationA procedure in Section 4.3—Recommended Sequence of Operations is to be used as a general guide when programming a robot or PLC for use with a Tool Changer and control/signal modules. This procedure is intended for “automatic” modes used during normal application processes. Recommendations for operation in “teach” or “manual” modes where the operator has the teach pendant in‑hand will be addressed in a separate Troubleshooting Guide. A thorough understanding of the advanced diagnostic and fault reporting capability is required to proficiently operate this product.

4.1 Lock, Unlock, and RTL Sensor Cable LED BehaviorThe Lock, Unlock, and RTL sensor cables are equipped with two LEDs. The Green LED indicates the sensor has power and the yellow LED indicates the switch has been made. The LED behavior is affected by the control/signal module.

Table 4.1—Sensor Cable LED Behavior for Common Tool Changer PositionsTool Changer Position Sensor cable LED Behavior

Unlocked (Tool Changer Master plate free of stand

with no Tool plate attached)

RTL (R1)Sensor

ON OFF

ON ON

Unlock (U)Sensor

RTL (R2)Sensor

ON OFF

ON OFF

Lock (L)Sensor

Ready to Lock(Tool Changer Master plate with Tool plate

parallel and at a distance of 1.22 mm or less from each other)

RTL (R1)Sensor

ON ON

ON ON

Unlock (U) Sensor

RTL (R2) Sensor

ON ON

ON OFF

Lock (L) Sensor

Locked(Tool Changer Master plate with Tool plate

attached in fully locked position)

RTL (R1) Sensor

ON ON

ON OFF

Unlock (U) Sensor

RTL (R2) Sensor

ON ON

ON ON

Lock (L) Sensor

Missed Tool(Tool Changer Master plate locked with no

Tool plate attached)

RTL (R1) Sensor

ON OFF

ON OFF

Unlock (U) Sensor

RTL (R2) Sensor

ON OFF

ON OFF

Lock (L) Sensor

Figure 4.1—Lock, Unlock, and RTL Sensor cable LED Behavior (Shown in Locked Position)

RTL (R1) Unlock (U)

RTL (R2) Lock (L)

Green LED (Power)

Yellow LED (Switch Made)

(Control module shown for reference only)

Page 22: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-22

4.2 Diagnostic Functions and Error HandlingThere are several diagnostic functions that can have an effect on the input bitmap and influence the Tool Changer control.

4.2.1 DeviceNet Power StatusThe DKD module continuously monitors the voltage of the DeviceNet power supply. If the voltage is between 11V and 25V the “Input and Logic Power Good” bit will be high. If the voltage falls outside of this range the “Input and Logic Power Good” bit will be low and will remain low until the voltage is between 11V and 25V and the Clear Errors output has been set from low to high. Note: The Tool Changer will not Unlatch while the “Input and Logic Power Good” bit is low.

4.2.2 Valve Power StatusThe DKD module continuously monitors the voltage of the switched AUX power which is used to supply the lock and unlock solenoid valves of the Tool Changer. If the voltage stays above 21V the “Valve Power Available” bit will be set high. If the voltage falls below the 21V threshold the bit will be set low. It will become high again as soon as the voltage rises above 21V.

4.2.3 Error on Latch or Unlatch OutputThe valve control outputs of the DKD module are protected against overload conditions such as those created by a short circuit. During an overload condition the LATCH and/or UNLATCH output is turned off and the corresponding error bit “Error on Latch Output” or “Error on Unlatch Output” is turned on. The output cannot be set high again until the overload condition is removed and the “Clear Errors” bit is set from low to high.

4.2.4 “COMM OK” bitThe “COMM OK” is set high as soon as Ethernet/IP communication is established.

4.2.5 “Tool Power is On” bitThe “Tool Power is ON” bit is set high when the Arc Prevention Circuit has activated power on the Tool‑side. If this bit is low there will be neither DeviceNet nor Switched or Unswitched Auxiliary power available on the Tool.

4.2.6 “Unlatch Enabled” bitThe “Unlatch Enabled” bit is set high when the DKD module determines that the necessary preconditions for unlatching the Tool have been met (i.e., Master and Tool are Coupled, Tool is in the tool stand, etc.). A Tool can only be released if the “Unlatch Enabled” bit is high. For additional details refer to Section 2.2.3—Tool Side TSI.

Page 23: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-23

4.3 Recommended Sequence of Operations1. The robot and Tool Changer Master are free of the stand or storage location, the Tool Changer

is uncoupled and the Tool Changer locking mechanism is fully retracted (unlocked condition). The Tool is by itself in the tool stand. No error or fault conditions exist.

a. The RTL inputs (RTL1 & RTL2) are OFF.b. The RTLV input is OFF.c. The ATI Tool and any downstream device are offline.d. The Input and Logic Power Good is ON. The Valve Power Available input is ON the

provided the Switched auxiliary power supply is on.e. The Tool Power Is ON input is OFF.f. The TSIV input is OFF.

2. Unlock the Master. (This must be done prior to the Master entering the Tool to prevent the ball bearings from impinging on the Tool bearing race.)

a. Turn the Latch output OFF and turn the Unlatch output ON. b. The Locked input turns OFF and a short time later the Unlocked input goes ON and

remains ON, indicating that the Tool Changer locking mechanism is fully retracted and the Unlatch operation is complete.

3. Robot and Master move into the tool, are parallel and within 0.15” of the tool (i.e., the module contact pins meet but the RTL sensors have not yet sensed the targets on the tool).

a. The Tool Present and TSIV inputs are ON, indicating that the Master and Tool are in the close proximity of each other and verifying the operation of the TSI limit switch.

b. When the Tool Present input is ON, Tool-ID is available within 50 ms.c. Power is not yet available on the Tool. The bit “Tool Power is On” is OFF.

4. Robot and Master move into the tool, are parallel and within 0.06” of the Tool

a. The RTL sensors are ON, indicating that its ok to couple Tool.b. The RTLV is true.

5. Couple the Tool Changer.

a. Turn the he Unlatch output OFF and turn the Latch output is made ON. (Note: Even for units with single solenoids the Latch output must be turned ON.)

b. With the Latch output ON, Power is available on the Tool and the “Tool Power is ON” input turns on.

c. The Unlocked input is OFF a short time later, indicating piston travel. Subsequently, the Locked input is on and remains ON, indicating that the coupling operation is complete.

d. Sometime thereafter, communications should be established with the downstream Ethernet device(s). (The time it takes to establish connection with a downstream EtherNet/IP node depends on the power up and reconnect time of the individual EtherNet/IP equipment that is installed on the tool.)

6. Robot moves away from the tool stand with the Tool Changer coupled.

a. The TSI Limit Switch is deactivated, and the TSIV input goes OFF.b. The Unlatch Enabled turns OFF.

Page 24: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-24

7. Normal operation

a. The following inputs are ON:i. Lockedii. Input and Logic Power Goodiii. Valve Power Availableiv. RTL (RTL1 & RTL2)v. Tool Presentvi. Tool Power is Onvii. RTLV

b. The following inputs are OFF:i. Unlockedii. TSIViii. Unlatch Enabled

c. The following output is ON:i. Latch

d. The following output is OFF:i. Unlatch

8. Robot moves into the tool stand with the Tool Changer coupled.

a. When the tool is returned to the stand, the TSI Limit Switch is activated and the TSIV input goes ON.

b. The Unlatch Enabled is ON, indicating that it is safe to uncouple the Tool Changer.

9. Uncouple the Tool Changer.

a. Turn the Latch output OFF and the Unlatch output ON.b. The Tool Power Is ON input turns OFF and power on the Tool turns off.c. Communication is lost with downstream device(s).d. The Locked input turns OFF a short time later the Unlocked input turns ON, indicating

that the uncoupling operation is complete.

10. Robot and Master move away from the tool, are parallel at a distance greater than 0.15” from the tool.

a. The Tool Present and TSIV inputs turn OFF.b. The Tool-ID is unavailable (all 1 → 0xF).

11. Robot and Master are in the free space

a. The following inputs are ON:i. Unlockedii. Input and Logic Power Goodiii. Valve Power Availableiv. Unlatch Enabled

b. The following inputs are OFF:i. Lockedii. RTL (RTL1 & RTL2)iii. RTLViv. TSIVv. Tool Present

c. The following output is ON:i. Unlatch

d. The following output is OFF:i. Latch

Page 25: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-25

5. MaintenanceThe modules are not designed to be field serviced as all point‑to‑point wiring connections are soldered. Component replacement is limited to the V‑ring seal on the Master.

WARNING: Do not perform maintenance or repair(s) on the Tool Changer or modules unless the Tool is safely supported or placed in the tool stand, all energized circuits (e.g. electrical, air, water, etc.) are turned off, pressurized connections are purged and power is discharged from circuits in accordance with the customer’s safety practices and policies. Injury or equipment damage can occur with the Tool not placed and energized circuits on. Place the Tool in the tool stand, turn off and discharge all energized circuits, purge all pressurized connections, and verify all circuits are de‑energized before performing maintenance or repair(s) on the Tool Changer or modules.

If the Tool Changer is used in dirty environments (e.g., welding or deburring applications), limit the exposure of the Tool Changer. Idle Tool assemblies should be covered to prevent debris from settling on the mating surface. Also, the Master assembly should be exposed for only a short period of time during Tool change and down time.

Under normal conditions, no special maintenance is necessary; however, perform periodic inspections to assess for unexpected damage and assure long‑lasting performance. Perform the following visual inspection monthly:

• Inspect mounting fasteners to verify they are tight and if loose, then tighten to the torque. Refer to Section 3—Installation.

• Cable connections should be inspected during maintenance periods to ensure they are secure. Loose connections should be cleaned and re‑tightened. Inspect cable sheathing for damage, repair or replace damaged cabling. Loose connections or damaged cabling are not expected and may indicate improper routing and/or strain relieving.

• Inspect the Master and Tool pin blocks for any pin damage, debris or darkened pins. Refer to Section 5.1—Pin Block Inspection and Cleaning.

• Inspect V‑ring seals for wear, abrasion, and cuts. If worn or damaged, replace. Refer to Section 6.2.1—V‑ring Seal Replacement.

Page 26: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-26

5.1 Pin Block Inspection and CleaningTools required: Nylon Brush (ATI Part Number 3690‑0000064‑60)

1. Place the Tool in a secure location.2. Uncouple the Master and Tool plates.3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).4. Inspect the Master and Tool pin blocks for any debris or darkened pins.

Figure 5.1—Inspect Master and Tool Pin Blocks

Tool Module Pin Block Master Module Pin Block

Note: Pin blocks shown are for illustration purposes only.

Weld Debris

Blackened Pins

5. If debris or darkened pins exist, remove debris using a vacuum and clean using a nylon brush (ATI Part Number 3690‑0000064‑60).

NOTICE: Do not use an abrasive media, cleaners, or solvents to clean the contact pins. Using abrasive media, cleaners, or solvents will cause damage to the contact surface or cause pins to stick. Clean contact surfaces with a vacuum or non-abrasive media such as a nylon brush (ATI Part Number 3690-0000064-60)

Figure 5.2—Clean Pin Blocks with a Nylon Brush

6. Inspect the Master and Tool pin blocks for stuck pins or pin block damage.

Figure 5.3—Stuck Pin and Pin Block Damage

Stuck Pins Pin Block Damage

Note: Pin blocks shown are for illustration purposes only.

7. If stuck pins or pin block damage exists, contact ATI for possible pin replacement procedures or module replacement.

8. After the procedure is complete, resume normal operation.

Page 27: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-27

6. Troubleshooting and Service ProceduresThe following section provides troubleshooting information to help diagnose conditions with the Tool Changer and service procedures to help resolve these conditions.

WARNING: Do not perform maintenance or repair on Tool Changer or modules unless the Tool is safely supported or placed in the tool stand, all energized circuits (e.g. electrical, air, water, etc.) are turned off, pressurized connections purged and power discharged from circuits in accordance with the customer’s safety practices and policies. Injury or equipment damage can occur with Tool not placed and energized circuits on. Place the Tool safely in the tool stand, turn off and discharge all energized circuits, purge all pressurized connections, verify all energized circuits are de‑energized before performing maintenance or repair on Tool Changer or modules.

6.1 TroubleshootingRefer to the following table for trouble shooting information.

Table 6.1—TroubleshootingPre-Troubleshooting Checklist:

• Check the product upstream and downstream of the Tool Changer for failure. This failure can “appear” to be caused by the Tool Changer or affect Tool Changer performance.

• Check for debris between the mating surfaces or contact pins. Refer to Section 5.1—Pin Block Inspection and Cleaning.

• Check for damaged cables or connectors.• Check the appropriate power being supplied to the modules. Refer to Section 8—Specifications.• Check the appropriate air pressure is supplied to the valve adapter. Refer to Valve Adapter

manual.• Check that the command was issued (Latch or Unlatch).

Symptom Possible Cause Correction

Unit will not lock or unlock.

Ball bearings are not moving freely.

Refer to the Maintenance section of the Tool Changer manual for instructions.

Valve adapter exhaust muffler is clogged.

Replace the valve adapter muffler. Refer to the valve adapter manual for more information.

TSI switch malfunctioning. Replace the TSI switch.Signals are mapped incorrectly. Refer to Section 9—Drawings for electrical schematic.

Master and Tool are not within the specified No‑Touch zone.

Adjust the Master and Tool within No‑Touch zone before locking. Refer to Tool Changer manual for more information.

Solenoid valve is not functioning. Replace the valve or valve adapter. Refer to the valve adapter manual.

Sensors are not operating but EtherNet/IP is operating.

Valve adapter exhaust muffler is clogged.

Replace the valve adapter muffler. Refer to the valve adapter manual for more information.

Sensors are not set correctly or malfunctioning.

Refer to the Troubleshooting Section of the Tool Changer manual.

Sensor cables damage or incorrectly connected.

Verify the cables are connected correctly and not damaged, replace if damaged. Refer to the Troubleshooting Section of the Tool Changer manual.

Page 28: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-28

Table 6.1—TroubleshootingPre-Troubleshooting Checklist:

• Check the product upstream and downstream of the Tool Changer for failure. This failure can “appear” to be caused by the Tool Changer or affect Tool Changer performance.

• Check for debris between the mating surfaces or contact pins. Refer to Section 5.1—Pin Block Inspection and Cleaning.

• Check for damaged cables or connectors.• Check the appropriate power being supplied to the modules. Refer to Section 8—Specifications.• Check the appropriate air pressure is supplied to the valve adapter. Refer to Valve Adapter

manual.• Check that the command was issued (Latch or Unlatch).

Loss of communication with the modules.

No DCA power to the Master module.

Verify that DCA (input and logic) power is connected and available (Input and Logic Power Good bit is ON).

Worn or damaged contact pins. Contact ATI representative.

No power on the Tool module.

Latch output was not issued. Verify the Latch output is ON.

Tool Present bit is OFF.Verify the Tool Present bit is ON.TSI cables or switch needs replaced.

Tool Power is ON bit is OFF. Verify the Tool Power is ON bit is ON. Contact ATI representative.

Loss of DCA power on the Master will cause loss of auxiliary power to the Tool.

Restore DCA power to the Master.

Page 29: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-29

6.2 Service ProceduresThe following service procedures provide instructions for inspection, adjustment, test or replacement of components.

6.2.1 V-ring Seal ReplacementParts required: Refer to Section 9—Drawings.The seal protects the electrical connection between the Master and Tool module. If the seal becomes worn or damaged, it must be replaced.

1. Place the Tool in a secure location.2. Uncouple the Master and Tool plates.3. Turn off and de‑energize all energized circuits (e.g. electrical, air, water, etc.).4. To remove the existing seal, pinch the edge of the seal with your fingers and pull the seal away

from the pin block on the Master.5. To install a new seal, stretch the new seal over the shoulder of the pin block.6. Push the seal hub down against the pin block using your finger tip.

7. After the procedure is complete, resume normal operation.

Figure 6.1—V-ring Seal Replacement

V-ring Seal

Stretch seal over shoulder of pin block and push seal hub down against

the pin block with finger tipV-ring Seal

Pinch edge of seal with fingers and gently pull away from pin block

Page 30: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-30

7. Serviceable PartsSee Section 9—Drawings for serviceable parts directly associated with the modules.

Table 7.1—Master Module Mounting FastenersPart Number Description

3500-1066020-15 M6X20 Socket Head Cap Screw, 12.9, ISO4762/DIN912, ES-ATI-007

Table 7.2—Tool Module Mounting FastenersPart Number Description

3500-1066016-15 M6x16 Socket Head Cap Screw, 12.9, ISO4762/DIN912, ES-ATI-007

Table 7.3—AccessoriesPart Number Description

3690-0000064-60 Brush, Blue Nylon All Purpose (Contact Pin Cleaning)3690-0000049-00 Closure Cap for Female Mini Receptacles

Page 31: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-31

8. SpecificationsTable 8.1—DKD Master Module

9121-DKD-M

EtherNet/IP Master module supports DHCP functionality and DeviceNet pass through. M12 D‑coded Female Connector for Ethernet communication, Mini 5‑pin Male Connector for DeviceNet, Mini 4‑pin Male Connector for Switched and Un‑Switched Auxiliary Power circuits, an M12, 4‑pin Male Connector for Safety PLC control of the Tool Changer valve. Lock, Unlock and RTL sensing with LED cables on the Master and Tool ID from the Tool module are also supported. ARC Prevention Circuit applied to Auxiliary Switched, Auxiliary Unswitched, and DeviceNet Power

Factory Default Configuration

I/P Address: 192.168.1.1Subnet Mask: 255.255.255.0Gateway: 192.168.1.1Note: The DKD modules conform to the EtherNet/IP Adaptation of CIP Specification, Edition 1.1; © 2005, ODVAThe DHCP option is factory set to enabled.

Interface Connectors

Auxiliary Power: Mini, 4‑pin Male supporting Switched and Unswitched circuits.DeviceNet: Mini, 5‑pin Male.Ethernet: M12 D‑Coded, 4‑pin Female Integrated Tool Changer I/O: (4) @ 8 mm, 3‑pin Female supporting Tool Changer Locked, Unlocked and Ready‑to‑Lock proximity sensors, internal 3‑pin pin block to transmit latch and unlatch signal to the solenoid Valve.24 VDC for control signals, 5 A/24 VDC for pass through signals.

Electrical Rating

Power Pass through: Auxiliary Power: 100 mA, 24 VValve Power: 250 mA, 24 VSignal Pass through: 3 Amp, 30 V maximum.Tool Changer Control:Lock, Unlock, and Ready‑to‑Lock sensors: 10‑30 V operational voltageLatch/Unlatch integrated solenoid valve: -19 to -29 V operational voltage

Current Draw 180 mA @ 24 V (Locked and RTL sensors “on”)Weight 1.88 lbs (0.85 kg)

Page 32: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-32

Table 8.2—DKD Tool Module

9121-DKD-T

EtherNet/IP Tool module supports Tool-ID through the master module and pass through for DeviceNet and Auxiliary power. Mini 5-pin Female Connector for DeviceNet, Mini 4‑pin Female Connector for Switched and Un‑switched Auxiliary Power circuits

Factory Default Configuration Tool-ID set to 1

Interface Connectors

Auxiliary Power: Mini, 4‑pin, FemaleDeviceNet: Mini, 5‑pin, FemaleTSI connector: M12, 4‑pin, Female24 VDC for control signals, 5 A/24 VDC for pass through signalsTool-ID: (1) Thumbwheel switch reading 0–9 positions (i.e., ten unique ID values).

Electrical Rating

Power Pass through: Auxiliary Power: 100 mA, 24 VValve Power: 250 mA, 24 VSignal Pass through: 5 A, 24 V maximum.

Current Draw 180 mA @ 24 VWeight 1.3 lbs (0.59 kg)

Page 33: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-33

9. Drawings

3rd

AN

GLE

PRO

JEC

TION

102.

4(W

hen

Cou

pled

App

rox.

)56

.6

DK

D M

aste

r Mod

ule

(912

1-D

KD

-M)

DIP

Sw

itche

s

Mod

ule

Sta

tus

(MS

) LE

D

Net

wor

k S

tatu

s(N

S) L

ED

Vis

ible

Thro

ugh

Win

dow

4-Pi

n M

ale

Min

i(A

uxilia

ry P

ower

)Tu

rck

RSF

L 46

Mas

ter E

ther

Net

Con

nect

ion

4-P

in, M

12, D

-Cod

edFe

mal

e R

ecep

tacl

eTu

rck

FKD

D 4

4

5-P

in M

ale

Min

i(D

Net

Com

m.)

Turc

k R

SFL

56

149.

5

102.

2

12.9

45.6

Push

butto

nSw

itch

for

Tool

ID

4-Pi

n Fe

mal

e M

ini

(Aux

iliary

Pow

er)

Turc

k R

KFL

465-

Pin

Fem

ale

Min

i(D

Net

Com

m.)

Turc

k R

KFL

56

TSI C

onne

ctor

4-P

in, M

12, F

emal

eTu

rck

FK4.

4-0.

5/18

.25

70.4

133.

4

DK

D T

ool M

odul

e(9

121-

DK

D-T

)

1 2

3 4 Aux

iliar

y P

ower

Min

i4-

Pin

Fem

ale,

Tur

ck R

KFL

46

(See

Tab

le L

ower

Lef

t)

1

2

3 4A

uxili

ary

Pow

er M

ini

4-P

in M

ale,

Tur

ck R

SFL

46

1

2

3

4

Eth

erN

et M

aste

r4-

Pin

, D-C

oded

Fem

ale

Turc

k FK

DD

441

2D

evic

eNet

Min

i5-

Pin

Mal

e, T

urck

RS

FL 5

6

34

2 15

Dev

iceN

et M

ini

5-P

in F

emal

e, T

urck

RK

FL 5

6(S

ee T

able

Low

er L

eft)

543

2 1

Tool

Pin

Blo

ck

1

15

5

14413

3

122

11

6

79

8

10

19 18

17

16

19

10

92 11

123

65 4

1314

1516

17 818

71

Mas

ter P

in B

lock

Not

es: Ref

eren

ce th

e m

anua

l for

info

rmat

ion

rela

ted

to D

IP s

witc

h 1.

setti

ngs,

LE

D b

ehav

ior a

nd g

ener

al p

rodu

ct o

pera

tion.

Con

nect

ors

are

orie

nted

as

show

n un

less

oth

erw

ise

2.sp

ecifi

ed.

Unl

ess

othe

rwis

e no

ted,

con

nect

ors

at 1

:1 s

cale

, pin

blo

cks

3.at

2:1

sca

le.

Ser

vice

able

Par

ts a

re li

sted

on

She

et 2

. A

n el

ectri

cal

4.sc

hem

atic

is s

how

n on

She

et 3

.

Rev.

Des

crip

tion

Initi

ator

Dat

e

02A

dd

ed C

OM

M O

K an

d P

OW

ER O

N b

it re

fere

nce

to

sche

mat

ic o

n Sh

eet 3

. Del

eted

CO

MM

ERR

OR

bit.

WB

8/21

/200

903

Mod

ified

des

ign

to re

flect

ad

diti

on o

f TSI

.W

B10

/8/2

009

04Up

dat

ed sh

eet f

orm

at a

nd e

limin

ated

-UM

con

figur

atio

n.W

B4/

5/20

1005

Eco

7797

; Cha

nge

conn

ecto

r par

t num

ber.

ATM

06/0

7/20

10

06Ec

o 87

69; C

hang

ed 4

& 5

Pin

Min

i Con

nect

ors d

escr

iptio

n on

Mas

ter S

ide

from

Fem

ale

to M

ale.

CF

7/7/

2011

B1:

21

3RE

VISI

ON

NO

TES:

UN

LESS

OTH

ERW

ISE

SPEC

IFIE

D.

DO

NO

T SC

ALE

DRA

WIN

G.

ALL

DIM

ENSI

ON

S A

RE IN

M

ILLIM

ETER

S.

DRA

WN

BY:

CHE

CKE

D B

Y:

W. B

erro

cal,

7/27

/09

D. M

usho

w, 7

/28/

09

TITLE SC

ALE

SIZE

DRA

WIN

G N

UMBE

R

PRO

JEC

T #

SHEE

T

O

F 96

30-2

0-D

KD08

0715

-106

PRO

PERT

Y O

F A

TI IN

DUS

TRIA

L A

UTO

MA

TION

, IN

C. N

OT

TO B

E RE

PRO

DUC

ED IN

AN

Y M

AN

NER

EXC

EPT

ON

ORD

ER O

R W

ITH P

RIO

R W

RITT

EN A

UTHO

RIZA

TION

OF

ATI.

1031

Goo

dwor

th Dr

ive, A

pex,

NC 27

539,

USA

Tel: +

1.919

.772.0

115

Em

ail: in

fo@ati

-ia.co

mFa

x: +1

.919.7

72.82

59

www

.ati-ia

.com

ISO

9001

Reg

ister

ed C

ompa

ny

DKD

Eth

erne

t/Dev

icen

et M

odul

e C

usto

mer

Dra

win

g

Page 34: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-34

3rd

AN

GLE

PRO

JEC

TION

1

7

5

2

6

3

4

8

3

Mas

ter E

ther

Net

Con

nect

ion

Turc

k FK

DD

44

(Orie

ntat

ion

Not

Gua

rant

eed)

Tool

Cha

nger

Inte

grat

ed

Pro

xim

ity S

enso

r I/O

C

onne

ctio

ns4X

Tur

ck M

FKS

3(C

able

s P

rovi

ded

by A

TI,

Not

Sho

wn)

DK

D T

ool

Cle

at h

idde

n fo

r cla

rity.

Inte

grat

ed T

ool C

hang

er

Val

ve C

onne

ctio

n(In

terfa

ces

with

Val

ve

Ada

pter

Mod

ule,

Not

Sho

wn)

1 (V

+)3

(V-)

4 (In

put)

Turc

k M

FKS

3S

cale

2:1

Sen

sor I

nput

Con

nect

ion

Typi

cal

13

4V

alve

Sig

nal P

in B

lock

Sca

le 2

:1

TSI C

onne

ctor

Turc

k M

12 4

-Pin

Fem

ale

FK4.

4-0.

5/18

.25

Sca

le 2

:1

Cle

at h

idde

n fo

r cla

rity.

DK

D

Mas

terRe

v.D

escr

iptio

nIn

itiat

orD

ate

-Se

e Sh

eet1

--

B2:

32

3RE

VISI

ON

NO

TES:

UN

LESS

OTH

ERW

ISE

SPEC

IFIE

D.

DO

NO

T SC

ALE

DRA

WIN

G.

ALL

DIM

ENSI

ON

S A

RE IN

M

ILLIM

ETER

S.

DRA

WN

BY:

CHE

CKE

D B

Y:

W. B

erro

cal,

7/27

/09

D. M

usho

w, 7

/28/

09

TITLE SC

ALE

SIZE

DRA

WIN

G N

UMBE

R

PRO

JEC

T #

SHEE

T

O

F 96

30-2

0-D

KD08

0715

-106

PRO

PERT

Y O

F A

TI IN

DUS

TRIA

L A

UTO

MA

TION

, IN

C. N

OT

TO B

E RE

PRO

DUC

ED IN

AN

Y M

AN

NER

EXC

EPT

ON

ORD

ER O

R W

ITH P

RIO

R W

RITT

EN A

UTHO

RIZA

TION

OF

ATI.

1031

Goo

dwor

th Dr

ive, A

pex,

NC 27

539,

USA

Tel: +

1.919

.772.0

115

Em

ail: in

fo@ati

-ia.co

mFa

x: +1

.919.7

72.82

59

www

.ati-ia

.com

ISO

9001

Reg

ister

ed C

ompa

ny

DKD

Eth

erne

t/Dev

icen

et M

odul

e C

usto

mer

Dra

win

g

Page 35: Manual, Control/Signal Module, Ethernet/IP, DKD Document ... · The DKD modules provide a 4‑pin Mini connector for auxiliary power, 5‑pin Mini connector for DeviceNet, and an

Manual, Control/Signal Module, Ethernet/IP, DKDDocument #9620-20-C-DKD-12

Pinnacle Park • 1031 Goodworth Drive • Apex, NC 27539 • Tel: 919.772.0115 • Fax: 919.772.8259 • www.ati-ia.com • Email: [email protected] C-35

3rd

AN

GLE

PRO

JEC

TION

1

841 2

CA

N/A

UX

PO

WE

R

9 3 8

TOO

L ID

1 (N

OTE

5)

TOO

L ID

2

TOO

L ID

4

TOO

L ID

8

BY

TE 2

BIT

0

BY

TE 2

BIT

1

BY

TE 2

BIT

2

BY

TE 2

BIT

3

CA

N V

-

CA

N_L

DR

AIN

CA

N_H

CA

N V

+3

3

ER

RO

R L

ATC

H O

/PB

YTE

3 B

IT 2

E1

ETH

ER

NE

T C

ON

NE

CTO

RTU

RC

K F

KFD

D 4

4

Rx-

Tx-

Rx+Tx

+

AU

X V

-

AU

X V

+

AU

X V

-

AU

X V

+

CA

N V

-

CA

N_L

DR

AIN

CA

N_H

CA

N V

+D

EV

ICE

NE

T C

ON

NE

CTO

RTU

RC

K R

SFL

56

AU

X. P

OW

ER

C

ON

NE

CTO

RTU

RC

K R

SFL

46

AU

X V

-

AU

X V

+

AU

X V

-

AU

X V

+

VA

LVE

PO

WE

R A

VA

IL.

ETH

ER

NE

T

7

Rx-

Tx-

43

Rx+

Tx+

21

DE

VIC

EN

ET

CO

NN

EC

TOR

TUR

CK

RK

FL 5

6

51 42

51

1512194

42

BY

TE 1

BIT

4R

TL1

17

Sch

emat

ic N

otes

:N

ote

that

the

sens

ors

are

pow

ered

by

Dev

iceN

et p

ower

. 1.

The

com

mon

V+

and

V- c

onne

ctio

ns a

re n

ot s

how

n he

re.

The

com

plet

e to

ol c

hang

er p

acka

ge c

omes

equ

ippe

d w

ith

2.ex

tern

al c

able

s th

at a

re c

onne

cted

to th

e se

nsor

s.

An

inte

rnal

pin

blo

ck is

use

d to

tran

smit

the

Latc

h/U

nlat

ch

3.si

gnal

to th

e V

alve

Ada

pter

. C

able

s fo

r Dev

iceN

et, E

ther

net,

and

Aux

iliar

y P

ower

to th

e 4.

DK

D M

odul

es a

re s

uppl

ied

by th

e us

er.

The

Tool

ID I/

O is

repo

rted

in th

e D

KD

Mas

ter B

itmap

. 5.

Ref

er to

the

prod

uct m

anua

l for

mor

e in

form

atio

n.Th

e A

rc P

reve

ntio

n C

ircui

ts tu

rn o

ff D

evic

eNet

, Sw

itche

d 6.

Aux

iliar

y, a

nd U

nsw

itche

d A

uxili

ary

Pow

er d

urin

g co

uplin

g an

d un

coup

ling

of th

e M

aste

r and

Too

l. Th

e sw

itchi

ng

func

tion

is c

ontro

lled

by th

e "P

OW

ER

ON

" sig

nal f

rom

the

mai

n P

C B

oard

. The

TO

OL

PR

ES

EN

T in

put i

s us

ed to

en

sure

that

the

sprin

g/co

ntac

t pin

s ar

e to

uchi

ng w

hen

pow

er is

turn

ed o

n. R

efer

to th

e pr

oduc

t man

ual f

or

addi

tiona

l inf

orm

atio

n.Th

e lim

it sw

itch

conn

ecte

d to

the

TSI c

onne

ctor

mus

t hav

e 7.

two

sets

of N

.O. c

onta

cts

(dou

ble

pole

sin

gle

thro

w).

A li

mit

switc

h is

ava

ilabl

e fro

m A

TI (p

/n 9

005-

20-1

165)

but

is n

ot

incl

uded

with

the

DK

D m

odul

es. C

onta

ct A

TI fo

r spe

cific

sw

itch

requ

irem

ents

.

AU

X V

- (U

NS

WIT

CH

ED

)

AU

X V

+ (U

NS

WIT

CH

ED

)

32

TOO

L C

HA

NG

ER

S

EN

SO

R IN

PU

TS

TUR

CK

MFK

S 3

, TY

PIC

AL

(SE

E N

OTE

S 1

& 2

)

"R1"

431V

-V

+

"R2"

431

V-

V+

"U"

431

V-

V+

"L"

431

V-

V+

LATC

H

UN

LATC

H

AUX V-

VA

LVE

CO

NN

EC

TIO

N

3-P

IN B

LOC

KN

OTE

3

14

3

24

LATCH

TOO

L P

RE

SE

NT

AU

X. P

OW

ER

C

ON

NE

CTO

RTU

RC

K R

KFL

46

9121-DKD-T

31

GN

D

216 1465

UNLATCH

BY

TE 1

BIT

1

BY

TE 1

BIT

0

OU

TPU

TS

INP

UT

PO

WE

R G

OO

DB

YTE

1 B

IT 2

BY

TE 1

BIT

3

ER

RO

R U

NLA

TCH

O/P

BY

TE 3

BIT

3

BY

TE 2

BIT

7

BY

TE 1

BIT

5

BY

TE 1

BIT

1B

YTE

1 B

IT 0

RTL

2

UN

LOC

KE

DLO

CK

ED

INP

UTS

Rx-

Tx-

Rx+

Tx+

LOG

IC P

OW

ER

AU

X V

- (S

WIT

CH

ED

)

AU

X V

+ (S

WIT

CH

ED

)

41

9121-DKD-M

ER

RO

R R

ES

ET

BY

TE 1

BIT

3

V+

(IN)

V+

(OU

T)

PO

WE

R O

N

10 13A

RC

SW

ITC

H

CIR

CU

IT 'B

'

AR

C S

WIT

CH

C

IRC

UIT

'C'

AR

C S

WIT

CH

C

IRC

UIT

'A'

V+

(IN)

V+

(OU

T)

V+

(OU

T)V

+ (IN

)

TOO

L P

RE

SE

NC

E IN

(CA

N V

+)

TOO

L P

RE

SE

NC

E O

UT

(CA

N V

+)11

V-

V-

V-

18

AU

X V

- (U

NS

WIT

CH

ED

)

AU

X V

+ (U

NS

WIT

CH

ED

)

AU

X V

- (S

WIT

CH

ED

)

AU

X V

+ (S

WIT

CH

ED

)

PO

WE

R O

N (N

OTE

6)

PO

WE

R O

N (N

OTE

6)

PO

WE

R O

N (N

OTE

6)

CO

MM

. OK

BY

TE 4

BIT

6B

YTE

4 B

IT 7

TOO

L P

OW

ER

IS O

N

Rel

ay C

ircui

t

1 2 3 4 5 6 7

1 2 3 4 5

J1

Pow

erR

eg.J2

42

TSI

CA

N V

+

CA

N V

+1 3

TSIV

TSIV

TSI O

UT

TSI I

NTS

RV

TSI CONNECTORFK4.4-0.5/18.25

TOO

L ID

SW

ITC

H

RTL

1 R

ELA

Y

CO

IL

RTL

1 R

ELA

Y

TSI S

WIT

CH

VE

RIF

YB

YTE

2 B

IT 4

TSI R

ELA

Y V

ER

IFY

BY

TE 2

BIT

5

BY

TE 2

BIT

6U

NLA

TCH

EN

AB

LED

LIM

IT S

WIT

CH

(NO

TE 7

)

Rev.

Des

crip

tion

Initi

ator

Dat

e-

See

Shee

t1-

-

B1:

103

3RE

VISI

ON

NO

TES:

UN

LESS

OTH

ERW

ISE

SPEC

IFIE

D.

DO

NO

T SC

ALE

DRA

WIN

G.

ALL

DIM

ENSI

ON

S A

RE IN

M

ILLIM

ETER

S.

DRA

WN

BY:

CHE

CKE

D B

Y:

W. B

erro

cal,

7/27

/09

D. M

usho

w, 7

/28/

09

TITLE SC

ALE

SIZE

DRA

WIN

G N

UMBE

R

PRO

JEC

T #

SHEE

T

O

F 96

30-2

0-D

KD08

0715

-106

PRO

PERT

Y O

F A

TI IN

DUS

TRIA

L A

UTO

MA

TION

, IN

C. N

OT

TO B

E RE

PRO

DUC

ED IN

AN

Y M

AN

NER

EXC

EPT

ON

ORD

ER O

R W

ITH P

RIO

R W

RITT

EN A

UTHO

RIZA

TION

OF

ATI.

1031

Goo

dwor

th Dr

ive, A

pex,

NC 27

539,

USA

Tel: +

1.919

.772.0

115

Em

ail: in

fo@ati

-ia.co

mFa

x: +1

.919.7

72.82

59

www

.ati-ia

.com

ISO

9001

Reg

ister

ed C

ompa

ny

DKD

Eth

erne

t/Dev

icen

et M

odul

e C

usto

mer

Dra

win

g