  • Corrigo E Heating manual, revision I Chapter 13 Energy / Cold water 51

    13.3 Electricity meter Energy total 1866.54 MWh

    The value can be reset.

    13.4 Leakage monitoring Leakage power 1.31 kW

  • Corrigo E Heating manual, revision I Chapter 14 Other functions 52

    Chapter 14 Other functions

    14.1 Alarm handling If an alarm condition occurs the red alarm LED on the front panel on units with display will start flashing. The LED will continue to flash as long as there are unacknowledged alarms.

    Alarms are logged in the alarm list. The list shows type of alarm, date and time for the alarm and the alarm class (A, B or C alarm).

    To access the alarm list, press the alarm button, the front panel button with the red button-top.

    Sensor error 24 Feb 10:43 Class:B

    Reset

    If there are multiple alarms, this is indicated by up / down arrow symbols at the right-hand edge of the display.

    Use the UP and DOWN buttons to access the other alarms.

    At the left end of the bottom display line the alarm status is shown. For active, unacknowledged alarms the space is blank. For alarms that have reset the text: Reset is shown, Acknowledged, still active or blocked alarms are indicated by Acknowledged or Blocked.

    Alarms are acknowledged by pressing the OK button. You are then given the choice of acknowledging the alarm or blocking the alarm.

    Acknowledged alarms will remain on the alarm list until the alarm input signal resets.

    Blocked alarms remain on the alarm list until the alarm has reset and the block has been removed. New alarms of the same type will not be activated as long as the block remains.

    Since blocking alarms can be potentially hazardous, you need a high log on authority to block alarms.

    Class A and B alarms will activate alarm output(s) if these have been configured.

    Class C alarms do not activate the alarm output(s).

    Class C alarms are removed from the alarm list when the alarm input resets even if the alarm has not been acknowledged.

    14.2 Free text If RIGHT is pressed once when the start-display is shown, see section 8.14.2, a menu showing text of your choice is displayed. The text can be used to show information concerning the commissioning company, name and phone number to service personnel etc. The easiest way to enter text is using E tool. Up to 4 lines of 20 characters can be entered.

    14.3 Revision numbers If RIGHT is pressed twice when the start-display is shown, see section 8.14.2, a menu showing the program revision number and id-number will be displayed.

  • Chapter 15 Index

    A Access rights, 27 Actual/Setpoint, 46 Address, 39 Alarm configuration, 35 Alarm list, 35 Alarm settings, 41 Alarms, 24

    Alarm handling, 52 Alarm list, 35

    Analogue inputs, 10 Analogue outputs, 10

    B Boost, 37 Building inertia, 37

    C Change language, 38 Change password, 27 Cold water meters, 50 Configuration, 29

    Inputs and outputs, 29 Running time, 3-pos. actuators, 34

    Control pressure Settings, 41

    D Dial-up modem, 40 Digital inputs, 10 Digital outputs, 10 Display, LEDs and buttons, 25 Domestic hot water, 21

    E Electricity meter, 51 Energy / Cold water, 50 Exercising, 34

    F Free text, 52 Frost protection, 38

    H Heating circuits, 20 Heating meter, 50 Holidays, 45 HS Heating System, supply, 31 HS_ Night Set-back, 44 HWC_ Night set-back, 45

    I Inputs and outputs, 10, 29

    Analogue inputs, 10 Analogue outputs, 10 Digital inputs, 10 Digital outputs, 10 Input and output lists, 12 Universal inputs, 10

    L Language, change, 38 Leakage monitoring, 34, 51 Log off, 27 Log on, 27

    M Manual / Auto, 48 Modbus communication, 40

    O Outputs. See Inputs and outputs

    P Password, 27 Power limitation, 37

  • Pulse inputs, 34 Pump stop, 32

    R Remote control, 39 Return temperature limitation, 32 Revision numbers, 52 Run indication / Motor protection, 33 Running time, 3-pos. actuators, 34

    S SMS, 40 Split of output signal, 38 Storage tank, 22

    Summer time adjustment, 39

    T Temperature control

    Settings, 41 Time/Date, 44 Timer channel outputs, 24 Timer outputs, 45

    U Universal inputs, 10