manual gf30 property of american airlines · 2019-09-18 · (b)using a refrigeration recovery...
TRANSCRIPT
Maintenance
Manual GF30
V. April 2016
Confidential
S.A. LEBRUN - 13, rue Gerard - 7020 NIMY (Belgium), Phone : +32 65 403030, Fax : +32 65 3460 17, e-mail : [email protected] - Bank : account number : IBAN : BE54 3700 1714 0997 - BIC :
BBRUBEBB - TVA : BE421.297.922 - registration number : 421.297.922/08.27.12
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
57
CHAPTER 3
Maintenance
3.1 Servicing
3.1.1 Introduction
This section contains instructions for Servicing, Inspecting and Preventive Maintenance on the GF30air conditioning unit.
To ensure that the unit is kept in correct operation condition, it must be inspected and maintainedon a regular basis. Proper cleaning on the air filter at recommended intervals will help in preventingdamage or failure of the unit, and provide optimum performance.
Overhaul Intervals: Under normal operating conditions and with proper preventive maintenancepractices, the GF30 will provide years of excellent service. Typically 20.000 to 30.000 hours (dependingupon local conditions).
3.1.2 Refrigeration system
Refrigeration section access
Access doors and panels for the refrigeration section are located at right side of the unit.
WARNING!
WHEN WORKING WITH REFRIGERANTS, GOGGLES SHOULDALWAYS BE WORN. CONTACT WITH REFRIGERANT MAY CAUSE
INJURY.
S.A. LEBRUN - 13, rue Gerard - 7020 NIMY (Belgium), Phone : +32 65 403030, Fax : +32 65 3460 17, e-mail : [email protected] - Bank : account number : IBAN : BE54 3700 1714 0997 - BIC :
BBRUBEBB - TVA : BE421.297.922 - registration number : 421.297.922/08.27.12
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Refrigerant Leak Testing
A leak free system assures trouble system operation and performance. Loss of refrigerant willbe accompanied by reduced system efficiency and capacity. It will also cause repeated activation ofsystem safety monitors, shutting down the unit. Leak testing should be accomplished at scheduledintervals, and after any work has been accomplished on the unit.
Check the liquid line glass in order to control the flow of refrigerant and the humidity in the coolingcircuit.
If a leak has occurred, it may spread refrigerant throughout the interior of the unit, making locatingthe leak difficult. The interior of the unit should be aired prior to testing. When a leak is detectedbut you are unable to pinpoint the location, use compressed air to blow the area free of vapour, thenimmediately retest before the leaking vapour spreads.
Utilize a draft free area when leak testing to prevent the loss of vapour from small leaks. Insurethat the testing area is free of compressor oil, which may contain dissolved refrigerant, giving falsetest indications.
The testing method used here is the Electronic Leak Detector. This is the easiest method for leakdetection. Electronic leak detectors can be used in areas where an open flame is not permitted. Adetecting probe is passed over the area of a suspected leak. If a leak is present, the detector sounds ahigh frequency alarm or signals by a flashing light, depending on the model used.
Refrigerant leak repair
(a) Locate leak as described above.
(b) Using a refrigeration recovery system compatible with R134a, pump refrigerant from the systemand dispose.
(c) Replace drier if necessary, see sight glass for moisture indication.
(d) Correct leak as described below.
(e) If no leaks are present, pump out system and then evacuate system to at least 270 [Pa], holdfor 30 minutes. Break vacuum with nitrogen and raise system pressure to 0 to 0.34 bars. Re-evacuate system to 270 [Pa]. Repeat this for a total of three times, then charge the system withR134a.
WARNING!
ENSURE ADEQUATE VENTILATION DURING REPAIRS.PHOGENE GAS, A DEADLY POISON, IS GENERATED WHEN
REFRIGERANT IS EXPOSED TO FLAME.
– 58 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
(f) Leak repair procedure :
• Thoroughly clean paint, dirt and oil film from adjacent piping. Use a wire brush, sandclothor sandpaper.
• Wrap nearby parts with water-soaked cloths to protect them from heat damage duringrepairs.
• If a solder joint requires repair, disassemble the joint and clean away any refrigerant oilwhich may be present. Oil traces will not allow a leak-proof solder repair to be made.After cleaning, reassemble the parts and solder.
• Solder repairs the leak. For copper to copper piping, use Lastek 34 (30% silver) typeL-AG30CD.
• Reassemble and tighten any connections previously loosened.
• If the plumbing system has been opened for repair, evacuate the system previously open toa vacuum of 405 [Pa]. Add dry nitrogen to raise pressure to 10,3 [bar].
• Open all previously closed valves.
• Perform a pressure check for leaks with foam products.
• If all leaks are repaired, evacuate system to 270 [Pa] at least three times.
Refrigerant charging
Charge procedure method :
Prior to starting, weigh the bottle of refrigerant to be used for charging, and record its weight.
(a) Using a recovery/charging unit, add approximately 10 kg of R134a to the cooling section thatwas repaired.
(b) Check all valves are open.
(c) Start the unit (compressor running).
(d) Charge the remainder of the refrigerant through the suction port until the liquid sight glassshows clear.
WARNING!
USE ONLY R134A REFRIGERANT. IF ANY OTHER TYPE OFREFRIGERANT IS USED, THE UNIT WILL NOT FUNCTION
PROPERLY.
– 59 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Moisture in a refrigerant system. Evacuation of moisture
Whenever the refrigeration system is opened, care must be taken to prevent the entry of moistureand/or air into the system.
The strainer/drier in the system is designed to remove particles and small amounts of moisturewhich may enter the system during minor servicing or fault conditions. Major moisture intrusionthrough fault or contamination may require complete system evacuation for moisture remova.
Moisture in a refrigerant system is directly or indirectly the real cause of more problems andcomplaints than all other causes combined. Moisture in a system can be classified as visible andinvisible. Rarely is liquid water found in a system, normally all intrusive moisture will be in the formof vapour. A single drop of moisture in a system can cause ”freeze-ups”’. Moisture can be picked upby the refrigerant and be transported through the lines as a fine mist, causing ice crystals to format the point of expansion (expansion valve). These ice crystals will retard or stop the flow of therefrigerant, causing a reduction or complete loss of cooling. As the expansion valve warms due to thelack of refrigerant, the ice melts and passes through the expansion valve. The moisture will then cyclethrough the system until it again returns to the expansion valve, and the cycle is repeated. The resultis intermittent cooling. Moisture can also cause corrosion, which can present serious problems, oftennot apparent until severe damage has occurred. Moisture, combined with refrigerants, can create acidswhich in turn greatly increase the corrosion of metals and copper plating.
Refrigerant oil has an attraction for moisture and will absorb it rapidly if left open to the atmo-sphere. Water formed acids mix with refrigerant oil, the two forming a closely bonded mixture offine globules. The effect is called ”sludging”’ and greatly reduces the lubricating ability of the oil.The corrosion caused by the presence of this moisture in the form of ”sludge”’ can plug fine strainers,expansion valves and capillary tubes. Because it usually contains acids, sludge will corrode whateverit clings to, accelerating system damage. It is imperative that only fresh oil from unopened containersbe used. Previously opened oil provides too great a danger of system moisture intrusion.
The most effective means in removing moisture from a system is to utilize a high (deep) vacuumpump. A high vacuum pump is capable of removing all moisture from a hermetic system by reducinginternal system pressures to the boiling point of water at normal temperatures. The vacuum pumpdoes not ”suck out”’ the liquid moisture, but rather causes it to boil into a vapour state at which timeit can be harmlessly removed from the system and exhausted through the vacuum pump.
The ideal vacuum pump should evacuate the system to at least 500 microns, and must also becapable of holding that vacuum throughout the dehydration process. It must pull that vacuum onthe entire system and not simply at the intake of the pump. This pump is able to remove moistureat an ambient temperature of 26oC or over. The adequate pump to be used for this cooling system ismentioned in the Support Test Equipement section.
– 60 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.1.3 Air handling system
Air Filter - Cleaning Instruction
If you have the warning ”Filter Clogged” on the PLC, you have to clean the filters according tothe instructions below.
(a) Opening the air inlet door
Figure 3.1: Door opened
Once the door is open you get access to the filters
Figure 3.2: PreFilter
– 61 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
(b) Taking out the prefilters
• Unlock and open the hooks at the four corners of each filter
Figure 3.3: Unlocking hook Figure 3.4: Opening hook
• Pull the prefilter out of the frame, you get access to the filter behind
Figure 3.5: Pulling out prefilter Figure 3.6: Filter
– 62 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
• Pull the filter out of the frame
Figure 3.7: Pulling out filter
• Repeat those operations for the other prefilters and filters
(c) Cleaning the filters.
• When the filters are dismounted, blow some compressed air through the filter in the oppositedirection of the air flow in operation
• Clean-up the remaining dusts on the air inlet face with a vacuum-cleaner.
– 63 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.2 Maintenance Schedule
3.2.1 Consumable Materials
The table below indicates the list of consumable materials requested to perform good servicing of theGF30 .
Filter drier
4 x 848CM. (ref: 2863950)
Air filter
4 x PreFilters (1750006)4 x Filters (1750005)
Table 3.1: Consumable material
– 64 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.2.2 Support Test Equipment Required
The equipments listed below are required to perform an adequate maintenance and inspection of theGF30 :
Connection - Regulator DANFOSS
Communication cable ADAP-COOL Adapter - cable AK2 to PC(080Z0262)Software Service Tools DANFOSS (080z0161)
Connection - PLC TELEMECANIQUE
(automate)Software SoMachine (Vers.3.1)Communication cable USB Type A to Mini USB
Connection - DISPLAY TELEMECANIQUE
Software Vijeo DesignerCommunication cable ETHERNET TCP/IP
Tools for cooling aggregate
Vacuum pump ITE MK 162DSManifold 4 V - ITE 2804 BC + connectionRatchet spanner TOTALINE 127 CVacuum meter REFCO DV-150Multimeter (current, voltage, frequency)Thermometer
Table 3.2: Support test equipments
– 65 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.2.3 Inspection
The following pages are provided as guidance to establish a proper service schedule. This periodicpreventive maintenance inspection schedule should be established and maintained. The followingschedule meets the minimum requirements necessary to ensure safe reliable service under normaloperating conditions. It may be modified as required to meet varying operating and environmentalconditions.
WARNING!
EXTREME CAUTION MUST BE USED WHILE MAKING SERVICEINSPECTIONS WITHIN THE UNIT. NEVER SERVICE THE UNIT ALONE.
SWITCH OFF THE GROUND SWITCH BEFORE PERFORMING ANYMAINTENANCE OPERATION. FAILURE TO FOLLOW THIS PRECAUTION
COULD RESULT IN SERIOUS INJURY OR DEATH.
Figure 3.8: Engine
Daily
• Diesel engine
– Check and fill if necessary the lube oil (see 1 on figure 3.8)
– Check the coolant liquid level (see 2 on figure 3.8)
– Check for leaks
– Check the engine dry/suction air filter (see 3 on figure 3.8)
– 66 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
After every 200 operating hours
Cleaning of the unit outdoor prefilters with compressed air and with a vacuum cleaner (see figure3.1 in chapter 3.1.3).
• Check the temperatures and pressures against what reported on the machine history logbook.
• Check oil level of the compressor
• control bolts tightening
• Visual inspection if the status of cable insulation.
• The oil level in the compressors (while in operation) (see figure 3.9). If the level is low, checkingwill be made again 3 to 4 hours later.
After every 500 operating hours
• Cleaning or eventual replacement of unit outdoor filters (see figure 3.1 and chapter 3.1.3).
• Change the lube oil of the engine (see 1 on figure 3.8)
• Replace the oil filter cartridge of the engine (see 4 on figure 3.8)
• Inspection:
– The general aspect of the compressors (see figure 3.9) .
– The presence of refrigerant in the sightglass (after +/- 30 minutes of continuous operation).
– The lack of foam in the oil crankcase (see 1 on figure 3.9).
– The good state of the steelcasing, paint, hinges, door handles, wheels, etc...
– The presence of traces of unusual humidity under the unit.
– The cleanness of the condenser with eventual cleaning.
• Mesuring of:
– The working temperatures (ambience, outlet of supplied air, inside the unit).
– The air pressure.
• Check:
– The working state of control and visual devices
– Control panel:
∗ leds,
∗ Shut-off contactor,
∗ Refrigerating and ventilation test.
– The working of the crankcase resistance.
– 67 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Figure 3.9: Compressor elements
– The correct working of the water discharge.
– The battery charge level of the engine (see MRS 16)
– The V-belt of the engine (retighten or replace as necessary)
CAUTION!
THE DISCHARGE OF CONDENSATES IS ONLY ALLOWED IF THE INNERPRESSURE IS ABOVE +/- 10 [mBAR].
After every 1000 operating hours or twice a year
• Diesel engine
– Replacement of the fuel filter and pre-filter cartridge (see 5 & 6 on figure 3.8)
– Cleaning of the radiator (drain lube oil/condensate)
– Check the flexible fuel leakage lines
– Check the battery and cable connections
– Check the preheating plug
– Check the monitoring, warning system
– Check the fixings, hose connections(renew if damaged)
– Check the cooling system bearings (rubber and retaining elements)
After every 10000 operating hours
• Replacement of the oil and oil filter of the compressor
– 68 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Once a year
• Performance tests of the unit in ”cooling”’ working modes.
• Tests and adjustments of the different safety devices on the unit.
– Refrigeration part:
∗ HP pressostat (see PSH3.1 on figure 3.9),
– Aerodynamic part:
∗ Safety pressostat (see PSH1.1 on figure 3.9),
• Checking of the absorbed powers.
• Checking of the condenser’s fan.
• Checking of the capacity regulation valve working order.
• Checking of the cooling system of the engine
• Checking of the exhaust system of the engine
• Cleaning of the air filter of the engine
• Replacement of the battery
• Cleaning of the fuel filter and replacement if necessary
• Control the charge of refrigerant and adapt the complementary charge.
• Greasing of the steering axles at the front of the unit.
• Greasing of the brake system and checking of its good working order.
• General inspection of:
– The air handling unit (presence of humidity, air leakage, bad fixings, ...),
– The fixings of the refrigeration piping,
– The piping insulation,
– The correct fixings of temperature sensors,
– The fixings of side panels,
– The good state of the panels acoustic insulation,
– The detection of any trace of rust,
– The eventual presence of refrigerant leakage,
– The cleaning of the electrical brushes,
– The eventual tightening of terminals,
CAUTION!
PRESENCE OF ANY MAGNETIC DEVICE NEAR THE PLC MUST BE AVOIDED.
– 69 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.2.4 Maintenance Table of the cooling unit
We recommend you to maintain the unit according tothese guidelines and frequencies. The number of oper-ating hours refer to average market conditions. Otherfrequencies and hours may be applicable depending onenvironmental conditions and other market data. Inthis case, please contact Guinault-Lebrun. E
very
200
hou
rsor
wee
kly
Eve
ry50
0h
ours
ortw
ice
aye
ar
Eve
ry4000
hou
rsor
twic
ea
year
Eve
ry800
0h
ou
rsor
on
cea
yea
r
THE COMPRESSOR
Check the oil •Check the general aspect •Check the refrigerant charge •Check the operating data •Check the protection devices and all compressor moni-toring parts
•
Check electrical cable connections on tight fitting •Check the tightening torques •Perform a tightness test •Update date protocol •THE ELECTRICAL MOTORS
Initial Inspection (Only once) •Regreasing See lubricant plate
Permanent lubrication (with coupling output) •Cleaning Depending on degree of local fooling
Main inspection After the first 16000 h or after 2 years
GENERAL INSPECTION
Clean the outdoor prefilters •Clean the outdoor filters (replace if necessary) •The lack of foam in the oil crankcase •The air handling unit :- presence or trace of humidity •- air leakage, bad fixings, etc... •The cleanness of the condenser. Clean if necessary. •The good state (paint, trace of rust, fixing,...) of the sideand acoustic insulation panels, the steelcasing, the doorhandels, the hinges, the wheels, etc...
• •
The tightening of terminals if necessary •The replacement of the safeguard battery in the PLC •
continued next page
– 70 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
continued from previous page
Eve
ry20
0h
ou
rsor
wee
kly
Eve
ry500
hou
rsor
twic
ea
year
Eve
ry40
00
hou
rsor
twic
ea
yea
r
Eve
ry80
00h
ours
oron
cea
yea
r
The cleaning of the 3 electrical panels •Greasing of the steering axles at the front of the unit andof the brake system + checking of its good working order
•
Fixings and insulations of the piping •Presence of refrigerant leakage •The correct fixing of temperature sensors •TESTS
The working state of control and visual devices •Checking of the condenser’s 6 fans •Checking of the control panel :- Shut-off contactor •- Refrigerating and ventilation test •- Leds •Measuring of the working temperatures (ambiance, outletof supplied air, inside the unit)
•
Measuring of the number of operating hours •Measuring of the air pressure •Checking of the correct working of the water discharge •Checking of the good working of the crankcase resistance •Tests and adjustments of the different safety devices onthe unit- Refrigeration part: HP pressure switch •- Aerolic part: Safety pressure switch •Performance tests of the unit in ”cooling” working modes •Checking of the absorbed powers •
Table 3.3: Cooling unit maintenance planning
– 71 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.2.5 Maintenance Table of the internal generator
Please find here after the maintenance operationsto be carried out on the engine. It is necessaryto refer to the engine manufacturer maintenancemanual,supplied with the ACU. The followingpanels, issued by Guinault-Lebrun, can not re-place the engine manuals.
Eve
ry10
hou
rsor
dail
y
Eve
ry500
hou
rs
Eve
ry10
00
hou
rsor
yea
rly
Eve
ry20
00
hou
rsor
ever
ytw
oye
ars
Eve
ry45
00h
ours
Dep
end
son
nee
ds
THE ENGINE
Check engine oil level •Check coolant liquid level •Check fuel filter •Replace engine oil and oil filter •Replace fuel filter •Check crankcase vent filter •Check Radiator support & engine shock absorbers(to be replaced if deteriorated) •Check electrical wiring •Replace air filter •Check the belt tension (1) •Check the cooling circuit •Check the engine intake system •Replace crankcase vent filter •Check the crankshaft damper •Check the engine speed •Replace the coolant liquid •Check the valve clearance •Replace the crankshaft vibration damper •Clean or replace air filter cartridge (2) •Replace fan or alternator belt •Check the injectors •
Table 3.4: Internal generator maintenance planning
Note:
• (1): During the running in period (first 50 hours), check daily the tension of the belts.
• (2): Air filter replacement depends on surrounding conditions (dust, ...)
• After first 100 hours, replace engine oil and oil filter.
Meccalte alternator is equipped with sealed bearing. For this kind of bearing, no maintenance isrequired for the total operating time (estimated 30.000 hours). However, alternator needs maintenanceand it is necessary to refer to the Meccalte maintenance manual.
– 72 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.3 Troubleshooting
3.3.1 General
This section contains troubleshooting information to assist, to locate and to correct operating troubleswhich may develop in the unit. Each malfunction for an individual component, unit or system isfollowed by a list of tests or inspections which will help the technician to determine probable causesand corrective action to take.
The test/inspections and corrective actions should be performed in the order listed. Troubleshoot-ing is a logical and systematic process of determining and correcting the cause of a malfunction. Theprocess begins with verification of the malfunction. This may often involve an operational check-outof the unit. After the trouble has been verified, identify all components in the circuit whose failurecould cause the symptoms observed during the operational check-out. The technician should start bychecking those items which are highest in probability of causing the problem. Inspect and test eachcomponent, until the exact cause of the problem is determined and corrected.
WARNING!
USE EXTREME CARE TO AVOID CONTACT WITH HIGH VOLTAGELEADS AT ALL TIMES. REMOVE ALL JEWELRY, SUCH AS RINGS,
WATCHES, CHAINS, ETC..., THAT COULD COME INTO CONTACT WITHEXPOSED LEADS AND WIRES. FAILURE TO COMPLY MAY RESULT IN
SEVIER ELECTRICAL SHOCK OR DEATH, AND/OR CAUSE DAMAGE TOEQUIPMENT.
WARNING!
EAR PROTECTION DEVICES MUST BE WORN WHEN IN THEIMMEDIATE VICINITY OF THIS UNIT DURING OPERATION. REPEATEDEXPOSURE TO HAZARDOUS NOISE CAN CAUSE PERMANENT HEARING
LOSS.
WARNING!
REFRIGERANTS, OILS AND OTHER PRODUCTS CAN READILY BEABSORBED THROUGH THE SKIN AND INTO THE BLOOD STREAM.
WASH IMMEDIATELY AFTER COMING INTO CONTACT WITH THESEPRODUCTS.
– 73 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
3.3.2 Troubleshooting chart
Default on the MRS16 display
When a default occurs with the engine, the ”ENGINE FAILURE” red lamp of the operating stationlights on. In order to identify the code corresponding to the current problem, the user must consultthe alarm menu of the MRS 16 display (figure 3.10). If a ”Wrn ECu Alarm” occurs on the alarm list,the user must consult the ECU Alarm list menu.
Figure 3.10: MRS 16 Engine Monitoring System
Based on the code, the user must go to the corresponding board in the troubleshooting chart. Onevery board, information is presented in three categories:
• Cause
• Type
• Solution
When it is appropriate, the solution is presented through a tree. When the problem is solved, resetthe MRS 16 (reset button on the electrical cabinetof the engine).
– 74 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Table 3.5: Troubleshooting chart for engine failure
Eng Cool Temp Wrn
CAUSE: High water temperature, engine too hot
TYPE: Engine default causing a stop
SOLUTION: - Turn off the general start button.- Wait for the refreshing of the engine.- Control the level of cooling liquid in the tank.- Retry to start.- Check if the fan of the radiator is working.
Oil Press Wrn
CAUSE: Oil pressure is smaller than Wrn Oil press setpoint.
TYPE: Warning
SOLUTION: - Control the oil level.- Control the pressostat.- If necessary, reload oil.
Oil Press Sd
CAUSE: Oil pressure is smaller than Sd Oil press setpoint.
TYPE: Engine default causing a stop
SOLUTION: See Oil Press Wrn.
Eng Cool Temp Sd
CAUSE: Water temperature is greater than Sd Water temp.
TYPE: Engine default causing a stop.
SOLUTION: - Turn off the general start button.- Wait for the refreshing of the engine.- Control the level of liquid cooling in the tank.- Retry to start.- Check if the fan of the radiator is working.
– 75 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Fuel level Wrn
CAUSE: Fuel level is smaller than Wrn fuel level setpoint (25%).
TYPE: Warning
SOLUTION: Refill the tank if necessary.
Fuel level Sd
CAUSE: Fuel level is smaller than Sd fuel level setpoint (10%).
TYPE: Shutdown
SOLUTION: Refill the tank if necessary.
Battery voltage <,>
CAUSE: Battery voltage is out of limits given by Batt overvolt and Batt un-dervolt setpoints.
TYPE: Warning
SOLUTION: - Check the alternator of the engine.- Check the main features of the battery.- Reload if necessary.- Retry to start.
Battery flat Sd
CAUSE: If the controller switches off during starting sequence due to badbattery condition, it doesn’t try to start again and activates thisprotection.
TYPE: Engine default causing a stop.
SOLUTION: See Battery voltage
Start failed
CAUSE: Gen-set start failed.
TYPE: Engine default causing a stop.
SOLUTION: Check the alternator.
– 76 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
EmergencyStop Sd
CAUSE: If the input Emergency stop is opened, shutdown is immediately ac-tivated.
TYPE: Engine default causing a stop.
SOLUTION: - Turn off the general start button.- Control all the securities before disengaging emergency button.- Retry yo start and check all the unit.
ChrgAlternFail Wrn
CAUSE: Failure of the alternator for charging the battery.
TYPE: Warning
SOLUTION: - Check the alternator.- Check the battery.- Check the wires.
Air Filter Sd
CAUSE: The air pressostat of the engine filter switched on.
TYPE: Engine default causing a stop
SOLUTION: - Remove filter for cleaning or replacement.- Check the wires.
Water in Fuel
CAUSE: Water presence in fuel filter.
TYPE: Engine default causing a stop.
SOLUTION: - Drain the fuel filter.- Check the wires.
Coolant Level
CAUSE: The coolant level sensor switched on.
TYPE: Engine default causing a stop.
SOLUTION: - Control the level liquid in the radiator and reload.- Check the wires.
– 77 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Default on the PLC display
This section presents the required solutions when the ”AIR SUPPLY FAILURE” lamp lights on. Onevery board of the table 3.6, information is presented through three categories:
• Cause
• Type
• Solution
When it is appropriate, the solution is presented through a tree. When the problem is solved, resetthe PLC (Reset/Maintenance button).
– 78 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Table 3.6: Troubleshooting chart for unit failures
D001
CAUSE: Failure comes from the speed controller of the blower SC1
TYPE: Stop of the unit in all mode
SOLUTION: look at the alarme on the speed controller by the PLC display (SeeChapter 2)
.
D002
CAUSE: Failure comes from the PTC probe
TYPE: Stop of the unit in all mode
SOLUTION: - Wait until the temperature inside the unit goes down.- Restart the unit.- If the default occurs again, contact Guinault-Lebrun
– 79 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D003
CAUSE: The air pressure switch (PSH1.1) switched on
TYPE: Stop of the unit in all mode
SOLUTION:
Is the air pressureswitch activated onthe speed controllerscreen on the PLC ?
The default is fixed. Reset thePLC with the maintenancebutton and reboot the unitin the selected mode. Checkif the default occurs again
and in which condition.
YES
Is cable SC1-PSH1.1well connected accord-ing to the Guinault-Lebrundrawing andis it in a good state?
Check the wiring atthe terminal number
12 and 29 of the speedcontroller SC 1. If
the problem goes on,contact Guinault-Lebrun.
YE
S
Connect the ca-ble correctly and
replace it, if needed.
NO
NO
– 80 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D004
CAUSE: The circuit breaker Q1.0 switched off (blower protection device).
TYPE: Stop of the unit in all mode
SOLUTION:
Did the circuit breakerQ1.0 switched off?
Reset the circuit breaker.Reset thePLC. Restart the group measuring
the current value consumed bythe frequency driver (after thecircuit breaker).If the problem
goes on, contact Guinault-Lebrun.
YES
Is the auxiliary contact on the circuitbreaker Q1.0 working properly? (mea-
sure with a ohm-meter, off power)
Check the wiring ofthe PLC first card
TM3DI16G, terminal0. If the problemgoes on, contact
Guinault-Lebrun.
YE
S
Replace theauxiliary
contact of thecircuit breaker.
NO
NO
D005
CAUSE: The PLC did not receive the information that the speed controllerSC1 started even though it asked for it.
TYPE: Stop of the unit in all mode
SOLUTION:
Is speed controller under power?
Start the unit in ventilation mode.Check the proper working of
MODBUS TCP/IP communica-tion (contact Guinault-Lebrun)
YES
Check the circuit breakerQ1.0. If the problem goes
on, contact Guinault-Lebrun.
NO
– 81 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D009
CAUSE: The PLC detected a default on the Danfoss regulator (AKCC750).
TYPE: Stop of the unit in cooling mode
SOLUTION:
Is light n°0 of thefirst TM3DI8G card
of the PLC on?
The default disappeared.Reset the PLC with the
maintenance buttonand restart the unit
in the selection mode.Check if the default
comes back and underwhich circumstances.
YES
Check if the contacton the terminals 39
and 41 of the regulatorAKCC750 is opened.
Default of theAKCC750.
Check the pres-sure sensor PT2.2.
Check for over heating.Check the expansion
valves EV6A.1 /EV6B.1 / EV6C.1
(adjust if necessary).
YE
S
Check the wiringbetween the PLCand the AKCC750
regulator at theterminals 39 and 41of the regulator. Is
there a problem there?
Correctthe wiring.
YE
S
Check the wiringof the PLC
card TM3DI8G,terminal 0. Ifthe problem
goes on, contactGuinault-Lebrun.
NO
NO
NO
– 82 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D010
CAUSE: One of the circuit breaker Q2A.1 or Q2B.1 switched off (compressorprotection device).
TYPE: Stop of the unit in cooling mode
SOLUTION:
Did the circuitbreaker Q2A.1 or
Q2B.1 switched off?
Reset the circuit breaker.Reset the PLC.
Restart the group measur-ing the current value con-
sumed by the frequency driver(after the circuit breaker).
If the problem goes on,contact Guinault-Lebrun.
YES
Is the auxiliary contact on thecircuit breaker Q2A.1 or Q2B.1
working properly? (measurewith a ohm-meter, off power)
Check the wiring ofthe PLC first card
TM3DI16G, terminal7. If the problemgoes on, contact
Guinault-Lebrun.
YE
S
Replace the aux-iliary contact of
the circuit breaker.
NO
NO
D011
CAUSE: The PLC detected a shortage of compressor oil.
TYPE: Stop of the unit in cooling mode
SOLUTION: - Reset the unit.- Check the auxiliary contacts of the contactors.- Control the oil level through the sightglass on the compressor.- Fill up if necessary.
– 83 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D012
CAUSE: The PLC did not receive the information that the compressor con-tactors started even though it commanded it.
TYPE: Stop of the unit in cooling mode
SOLUTION:
Check the K2A.1 and K2B.1 contactors.Check the auxiliary contacts of the con-tactors. Is there a problem with these?
Replace the defective part
YES
Reset the PLC and restart in coolingmode. Do the contactors turn on? Both?
Is light 4 of the firstcard TM3DI16G ”on”during the 5 secondsbefore the default?
Problemwith the
PLC.Contact
Guinault-Lebrun
YE
S
Problem ofinformationreturn of the
PLC. Check thewiring betweenthe auxiliarycontact and
the PLC. If theproblem goeson, contact
Guinault-Lebrun
NO
YE
S
Problem in thewiring of thecommand.
See next page
NO
NO
– 84 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D012 - Problem in the start command of the compressor
Is the light 4 on theTM3DQ16TG PLC card ”on”
Check the wiring beetween PLC card TM3DQ16TG,terminal 4 and K2.3 relay (wire 8405). Is it correct ?
Does relay K2.3operate properly
Check thewiring beetweenK2.3 relay and
contactor K2A.1(wire 2302).Is it correct?
Problemstill there,see next
page
YE
S
corretthe
wiring
NO
YE
S
Replace thedefective
part
NO
YE
S
Correctthe wiring.
NO
YES
Problem with the PLC.Contact Guinault-Lebrun
NO
– 85 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D012 - Problem in the start command of the compressor
Does K2A.1 contac-tor operate properly
Check the wiring beetween K2A.1 auxiliary contactand K2B.1 contactor (wire 2303). Is it correct ?
Replace K2B.1 contactor.Reset the unit and
restart in cooling mode
If problem is still therecontact Guinault-Lebrun.
YE
S
YE
S
Correctthe wiring.
NO
YES
Replace the defective part
NO
– 86 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D013
CAUSE: The PLC detected a default on the Danfoss economizer regulator(AKCC550)
TYPE: Stop of the unit in cooling mode
SOLUTION:
Is light 1 on the first cardTM3DI8G of the PLC on?
Check if the contact on theterminals 7 and 9 of the
regulator AKCC550 is open.
Check the wiringbetween the TM3DI8G
PLC card and theAKCC550 regulatorat terminals 7 and 9.
If problem goes on con-tact Guinault-Lebrun?
YE
S
Default of theAKCC550.
Send the code dis-played on the screenof the AKCC550 toGuinault-Lebrun.
NO
YES
The default disappeared. Reset thePLC with the maintenance button
and restart the unit with the selectionmode. Check if the default occurs
again and under which circumstances.
NO
D014
CAUSE: The PLC reduced the capacity of the compressor to limit the currentconsumption.
TYPE: Information
SOLUTION: This is no default. The PLC limits the use of the unit under thenormal working conditions.
– 87 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D015
CAUSE: Failure comes from the speed controller of the condenser SC3
TYPE: Stop of the unit in cooling mode
SOLUTION: look at the alarm on the speed controller by the PLC display (SeeChapter 2)
.
D016
CAUSE: The Q3.0 circuit breaker switched off.
TYPE: Stop of the unit in cooling mode
SOLUTION:
Did the Q3.0 circuitbreaker switch off?
Restart the Q3.0 circuit breaker.Reset the PLC.
Restart the group measuring thevalue of the current consumed by
the frequency driver SC3 (after thecircuit breaker). If the problemgoes, contact Guinault-Lebrun.
YES
Does the auxiliary contactQ3.0 work well? (measure
with a ohm-meter off power)
Check the wiring atthe PLC first card
TM3DI16G terminal1. If the problemgoes on, contact
Guinault-Lebrun.
YE
S
Replace the Q3.0auxiliary contact.
NO
NO
– 88 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D019
CAUSE: The number of successive start of the compressor is larger than 6 inan hour.
TYPE: Stop of the unit in cooling mode
SOLUTION: - Reset the unit.- Restart the unit.- Check the low pressure.- Check that there is no leak in the cooling circuit.- If the problem goes on, contact Guinault-Lebrun.
– 89 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
D020
CAUSE: The PLC detected a default with the internal protection of the com-pressor (Kriwan).
TYPE: Stop of the unit in cooling mode.
SOLUTION:
Is light 5 of the first card(TM3DI16G) of the PLC on?
The default is no morethere. Reset and check
the compressor working.If the problem goees on,contact Guinault-Lebrun
YES
Cut the current with theQ10.10 for 10 seconds. Reset
the Q10.10 and the PLC.Is the default still there
Check the wiringsbetween first card
TM3DI16G and con-nections x3-1 and x3-2Check cable U1-M2/3.If the problem goes on,
contact Guinault-Lebrun
YE
S
The default is no morethere. Reset and check
the compressor working.If the problem goes on,
contact Guinault-Lebrun
NO
NO
D021
CAUSE: The PLC detected a default with the high pressure pressure swtitch.
TYPE: Stop of the unit in cooling mode.
SOLUTION: - Reset the HP pressure switch (black button).- Reset the PLC.- Restart the unit → Check the operating pressure values.- Identify when the default occurs again.- Contact Guinault-Lebrun.
– 90 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
COOLING MODE
That section presents a non-exhaustive list of problems that can occur when the unit is in coolingmode and their solution.
Cooling compressor fails to start (red lamp is off).
Is the fan in operation
Check the circuitbreaker for the opera-tion of the PLC Q10.4
YES
Is there a partial or com-plete loss of refrigerant charge.
Check the pressure onthe manometers PI3.1
and PI2.1. This pressuremust be up to 2,5 Bar topermit the operation ofthe compressor.Repair
leak and recharge system.
YE
S
Is there a defaulton the pressuresensor PT2.1?
Check the valueof the PT2.1 on
the PLC andcompare withthe manome-
ter PI2.1.
YE
S
See nextPage.
NO
NO
NO
– 91 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Suction pressuretoo low (internalpressure switch).
Automatic restartof the compressorwhen the pressure
is up to 1 bar.
YES
Waiting for short delay?Automatic restartof the compressorafter 2 minutes.
NO
Noisy compressor.
Is one or more expansionvalve in ”open” position (in-
dicated by abnormallycold suction line)?).
Check superheat.Adjust or replacevalve. Control the
operation of the directexpansion regulator.
YES
If electrical repair has beenmade to unit, check compres-sor electrical power 3-phase
for proper phase connections.
NO
– 92 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
System cooling output poor.
Is there flash gas inliquid refrigerant line(indicated by a foamyor bubbly sight glass)?
Locate and repair leakin refrigerant system.Recharge refrigerant
to proper levels.
YES
Is the electronic expansionvalve not running correctly?
Control the opera-tion of the direct
expansion regulator.
YE
S
Is the drier/strainerclogged (feels cool
to the touch)?
Replacedrier/strainer
YE
S
See nextPage.
NO
NO
NO
– 93 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Is the evaporator coil dirty?
Clean coil.
YES
High ambient temperature(more than 50oC)
and/or air flow too high.
NO
Discharge pressure too high.
Is the condenserair flow too low?
Check speed controllerof the condenser.
chack fan operation.clean coil if required
YES
Is there air or any other non-condensable gas in system?
Evacuate system andrecharge. Install
new drier/strainer.
YE
S
If there is an over-charge of refrigerant,
purge or removeexcess from highside of system.
NO
NO
– 94 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Discharge pressure too low.
Is there a Lack of refrigerant (in-dicated by bubbles in sight glass)?
Repair leak and recharge system.
YE
S
Suction pressure too high.
Is the expansion valve not running correctly?
Repair or replace valve, if necessary.Controlthe operation of the direct expansion regulator.
YE
S
– 95 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Suction pressure too low.
Is there a lack of refrigerant(flash gas in liquid refrigerant
line indicated by a foamyor bubbly sight glass)?
Repair leakand recharge.
YES
Is the drier/strainer clogged(feels cool to the touch)?
Replacedrier/strainer.
YE
S
Is the expansionvalve not running
correctly?
Replace valveif necessary.Control theoperation ofthe directexpansionregulator.
YE
S
Is the Air sideof coil dirty?
Cleancoil.
YE
S
If the air flowis too low,
check the airflow at theunit outlet.
NO
NO
NO
NO
– 96 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Ventilation mode
The fan is running but the operation is not correct :- Air flow too low- Vibrations- Abnormal noise
– 97 –
Prope
rty o
f Am
erica
n Airli
nes
Operating manualGF30V. April 2016 Confidential
Maintenance
Operating modes starting
Engine is running and voltage is good but it is impossible to start the unit’s operatingmodes (cooling or ventilation).
Is the circuitbreaker of the
PLC off (Q10.4)?
Engage thecircuit breaker ofthe PLC. Check
the intensity.
YES
Is teh circuitbreaker ofthe currenttransformer
OFF (Q10.0)?
Engage the circuit breakerof the transformer.Check the intensity.
YE
S
Is the circuitbreaker 220 Voff (Q10.6)?
Engagethe circuit
breaker220 V.
Check theintensity.
YE
S
If the PLC isfaulty (red lamp inthe PLC), then :- Cut the circuit
breaker of the PLC.- Retry to engage
this circuit breaker.- If the PLC is
still in default, itmust be replaced.
NO
NO
NO
– 98 –
Prope
rty o
f Am
erica
n Airli
nes